SlideShare a Scribd company logo
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 1 of 8
PART 1 GENERAL
1.1 SUMMARY
.1 TAB is used throughout this Section to describe the process, methods and requirements of
testing, adjusting and balancing for HVAC.
.2 TAB means to test, adjust and balance to perform in accordance with requirements of
Contract Documents and to do other work as specified in this Section.
1.2 QUALIFICATIONS OF TAB PERSONNEL
.1 Submit names of personnel certified to AABC, NBC, NEBB or SMACNA to perform
TAB to Owner’s Representative within 90 days of award of contract.
.2 Provide documentation confirming qualifications, successful experience. TAB contractor
shall have a minimum of 5 (five) years experience to AABC, NBC, NEBB or SMACNA.
.3 TAB: performed in accordance with the requirements of standard under which TAB
Firm’s qualifications are approved:
.1 Associated Air Balance Council, (AABC) National Standards for Total System
Balance, MN-1.
.2 National Balancing Council, (NBC) Certified Air Balancing Specifications and
Certified Hydronic Balancing Specifications.
.3 National Environmental Balancing Bureau (NEBB) TABES, Procedural
Standards for Testing, Adjusting, Balancing of Environmental Systems.
.4 Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA),
HVAC TAB HVAC Systems – Testing, Adjusting and Balancing.
.4 Recommendations and suggested practices contained in the TAB Standard: mandatory.
.5 Use TAB Standard provisions, including checklists, and report forms to satisfy Contract
requirements.
.6 Use TAB standard for TAB, including qualifications for TAB Firm and Specialist and
calibration of TAB instruments.
.7 Where instrument manufacturer calibration recommendations are more stringent than those
listed in the TAB standard, use manufacturer’s recommendations.
.8 TAB Standard quality assurance provisions such as performance guarantees form part of
this contract.
.1 For systems or system components not covered in TAB standard, use TAB
procedures developed by TAB Specialist.
.2 Where new procedures and requirements are applicable to Contract requirements
have been published or adopted by body responsible for TAB Standard used
(AABC, NBC, NEBB, or SMACNA), requirements and recommendations
contained in these procedures and requirements are mandatory.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 2 of 8
1.3 PURPOSE OF TAB
.1 Test to verify proper and safe operation, determine actual point of performance, evaluate
qualitative and quantitative performance of equipment, systems and controls at design,
average and low loads using actual or simulated loads.
.2 Adjust and regulate equipment and systems so as to meet specified performance
requirements and to achieve specified interaction with other related systems under normal
and emergency loads and operating conditions.
.3 Balance systems and equipment to regulate flow rates to match load requirements over full
operating ranges.
1.4 EXCEPTIONS
.1 TAB of systems and equipment regulated by codes, standards to be to satisfaction of
authority having jurisdiction.
1.5 CO-ORDINATION
.1 Schedule time required for TAB (including repairs, re-testing) into project construction
and completion schedule so as to ensure completion before acceptance of project.
.2 Do TAB of each system independently and subsequently, where interlocked with other
systems, in unison with those systems.
1.6 PRE-TAB REVIEW
.1 Review contract documents before project construction is started and confirm in writing to
Owner’s Representative adequacy of provisions for TAB and other aspects of design and
installation pertinent to success of TAB.
.2 Review specified standards and report to Owner’s Representative in writing all proposed
procedures which vary from standard.
.3 During construction, co-ordinate location and installation of TAB devices, equipment,
accessories, measurement ports and fittings.
1.7 START-UP
.1 Follow start-up procedures as recommended by equipment manufacturer unless specified
otherwise.
.2 Follow special start-up procedures specified elsewhere in other Divisions.
1.8 OPERATION OF SYSTEMS DURING TAB
.1 Operate systems for length of time required for TAB and as required by Owner’s
Representative for verification of TAB reports.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 3 of 8
1.9 START OF TAB
.1 Notify Owner’s Representative 7 (seven) days prior to start of TAB.
.2 Start TAB when building is essentially completed, including:
.1 Installation of ceilings, doors, windows, other construction affecting TAB.
.2 Application of weatherstripping, sealing, caulking.
.3 All pressure, leakage, other tests specified elsewhere in other Divisions.
.4 All provisions for TAB installed and operational.
.3 Start-up, verification for proper, normal and safe operation of mechanical and associated
electrical and control systems affecting TAB including but not limited to:
.1 Proper thermal overload protection in place for electrical equipment.
.2 Air systems:
.1 Filters in place, clean.
.2 Duct systems clean.
.3 Ducts, air shafts, ceiling plenums are airtight to within specified
tolerances.
.4 Correct fan rotation.
.5 Fire, smoke, volume control dampers installed and open.
.6 Coil fins combed, clean.
.7 Access doors, installed, closed.
.8 Outlets installed, volume control dampers open.
.3 Liquid systems:
.1 Flushed, filled, vented.
.2 Correct pump rotation.
.3 Strainers in place, baskets clean.
.4 Isolating and balancing valves installed, open.
.5 Calibrated balancing valves installed, at factory settings.
.6 Chemical treatment systems complete, operational.
1.10 APPLICATION TOLERANCES
.1 Do TAB to following tolerances of design values:
.1 Laboratory HVAC systems: plus 10%, minus 0%.
.2 Other HVAC systems: plus 5%, minus 5%.
.3 Hydronic systems: plus or minus 10 %.
.4 Refrigeration systems: plus or minus 10%.
1.11 ACCURACY TOLERANCES
.1 Measured values to be accurate to within plus or minus 2 % of actual values.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 4 of 8
1.12 INSTRUMENTS
.1 Prior to TAB, submit to Owner’s Representative list of instruments to be used together
with serial numbers.
.2 Calibrate in accordance with requirements of most stringent of referenced standard for
either applicable system or HVAC system.
.3 Calibrate within 3 (three) months of TAB. Provide certificate of calibration to Owner’s
Representative.
1.13 SUBMITTALS
.1 Submit, prior to commencement of TAB:
.2 Proposed methodology and procedures for performing TAB if different from referenced
standard.
1.14 PRELIMINARY TAB REPORT
.1 Submit for checking and approval of Owner’s Representative, prior to submission of
formal TAB report, sample of rough TAB sheets. Include:
.1 Details of instruments used.
.2 Details of TAB procedures employed.
.3 Calculations procedures.
.4 Summaries.
1.15 TAB REPORT
.1 Format to be in accordance with referenced standard.
.2 TAB report to show results in SI units and to include:
.1 Project record drawings.
.2 System schematics.
.3 Submit 3 (three) copies of TAB Report to Owner’s Representative for verification and
approval, in English in D-ring binders, complete with index tabs.
1.16 VERIFICATION
.1 Reported results subject to verification by Owner’s Representative.
.2 Provide manpower and instrumentation to verify up to 30% of reported results.
.3 Number and location of verified results to be at discretion of Owner’s Representative.
.4 Bear costs to repeat TAB as required to satisfaction of Owner’s Representative.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 5 of 8
1.17 SETTINGS
.1 After TAB is completed to satisfaction of Owner’s Representative, replace drive guards,
close access doors, lock devices in set positions, ensure sensors are at required settings.
.2 Permanently mark settings to allow restoration at any time during life of facility. Markings
not to be eradicated or covered in any way.
1.18 COMPLETION OF TAB
.1 TAB to be considered complete when final TAB Report received and approved by
Owner’s Representative.
1.19 AIR SYSTEMS
.1 Standard: TAB to be to most stringent of this section or TAB standards of AABC, NBC
or NEBB.
.2 Do TAB of systems, equipment, components, controls specified in other Divisions.
.3 Qualifications: personnel performing TAB to be qualified to standards of AABC, NBC or
NEBB.
.4 Quality assurance: Perform TAB under direction of supervisor qualified to standards of
AABC, NBC or NEBB.
.5 Measurements: to include, but not limited to, following as appropriate for systems,
equipment, components, controls: air velocity, static pressure, flow rate, pressure drop (or
loss), temperatures (dry bulb, wet bulb, dewpoint), duct cross-sectional area, RPM,
electrical power, voltage, noise, vibration, amperage and volts for each stage of electrical
heating coils.
.6 Locations of equipment measurements: To include, but not be limited to, following as
appropriate:
.1 Inlet and outlet of dampers, filter, coil, humidifier, fan, other equipment causing
changes in conditions.
.2 At controllers, controlled device.
.7 Locations of systems measurements to include, but not be limited to, following as
appropriate: Main ducts, main branch, sub-branch, run-out (or grille, register or diffuser).
1.20 HYDRONIC SYSTEMS
.1 Definitions: for purposes of this section, to include low pressure hot water heating, chilled
water, condenser water, glycol systems.
.2 Standard: TAB to be to most stringent of TAB standards of AABC, NBC or NEBB.
.3 Do TAB of systems, equipment, components, controls specified in other Divisions.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 6 of 8
.4 Qualifications: personnel performing TAB to be qualified to standards of AABC, NBC or
NEBB.
.5 Quality assurance: perform TAB under direction of supervisor qualified to standards of
AABC, NBC or NEBB.
.6 Measurements: to include, but not limited to, following as appropriate for systems,
equipment, components, controls: flow rate, static pressure, pressure drop (or loss),
temperature, specific gravity, density, RPM, electrical power, voltage, noise, vibration.
.7 Locations of equipment measurement: to include, but not be limited to, following as
appropriate:
.1 Inlet and outlet of heat exchangers (primary and secondary sides), boiler, chiller,
coil, humidifier, cooling tower, condenser, pump, PRV, control valve, other
equipment causing changes in conditions.
.2 At controllers, controlled device.
.8 Locations of systems measurements to include, but not be limited to, following as
appropriate: supply and return of primary and secondary loops (main, main branch,
branch, sub-branch) of all hydronic systems, inlet connection of make-up water.
1.21 DOMESTIC WATER SYSTEMS
.1 Meet requirements as specified for hydronic systems.
.2 Locations of equipment measurements: To include, but not be limited to, following as
appropriate: inlet and outlet of heaters, tank, pump, circulator, at controllers, controlled
device.
.3 Locations of systems measurements to include, but not be limited to, following as
appropriate: main, main branch, branch, sub-branch.
1.22 OTHER SYSTEMS
.1 Plumbing systems:
.1 Standard: National Plumbing Code.
.2 TAB procedures:
.1 Flush valves: adjust to suit project pressure conditions.
.2 Pressure booster systems: test for capacity and pressures under all
conditions and at all times.
.3 Controlled flow roof drain systems: adjust weirs to suit actual roof
conditions, slopes, areas drained.
.4 Pumped sanitary and storm water systems: test for proper operation at all
possible flow rates. Refer to Section 32 32 13.13 – Packaged Sewage
Lift, Wet Well Type.
.5 Pressure reducing station.
.2 Wet pipe sprinkler sprinkler systems:
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 7 of 8
.1 Standard: NFPA.
.2 TAB procedures: Refer to NFPA 13 Sprinkler System.
.3 Refrigeration systems forming part of HVAC systems:
.1 Standard: CSA B52 – Mechanical Refrigeration Code.
.2 TAB procedures: Refer to Standard as follows:
.1 Suction Pressure and Temperature.
.2 Discharge Pressure and Temperature.
.3 Suction Superheat
.4 Evaporation Pressure and Temperature.
.4 Chemical treatment systems:
.1 Standard: Section 23 25 00 – HVAC Water Treatment Systems.
.2 TAB procedures: refer to Section 23 25 00 – HVAC Water Treatment Systems.
1.23 OTHER TAB REQUIREMENTS
.1 General requirements applicable to work specified this paragraph:
.1 Qualifications of TAB personnel: as for air systems specified this section.
.2 Quality assurance: as for air systems specified this section.
.2 Laboratory fume hoods:
.1 Standard: ASHRAE 110 – Method of Testing Performance of Laboratory Fume
Hoods, applicable provincial standard.
.2 TAB procedures: as described in standard.
.3 Building pressure conditions:
.1 Adjust HVAC systems, equipment, controls to ensure specified pressure
conditions during winter and summer design conditions.
.4 Zone pressure differences:
.1 Adjust HVAC systems, equipment, controls to establish specified air pressure
differentials, with all systems in all possible combinations of normal operating
modes.
.5 Smoke management systems:
.1 Test for proper operation of all smoke and fire dampers, sensors, detectors,
installed as component parts of air systems specified in other Divisions.
.6 Measurement of noise and vibration from equipment specified in Mechanical Division.
.1 Standard: 23 05 48 - Vibration and Seismic Controls for HVAC Piping and
Equipment and 23 32 48 – Acoustical Air Plenums.
.2 Vibration measurements around each piece of rotating equipment.
.3 Sound measurements in each octave band around each piece of rotating
equipment.
.4 Induct sound measurements in each octave band at each fan inlet and discharge.
NL Master Specification Guide
for Public Funded Buildings
Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 8 of 8
.5 Induct sound measurements in each octave band at each air handling unit intake,
return and discharge.
.6 Sound measurements in each octave band for each normally occupied room with
air handling equipment running.
.7 Measurement of spatial noise:
.1 Standard: Section 23 32 48 – Acoustical Air Plenums.
1.24 POST- OCCUPANCY TAB
.1 Measure DBT, WBT (or %RH), air velocity, air flow patterns, NC levels, in occupied
zone of areas designated by Owner’s Representative.
.2 Participate in systems checks twice during Warranty Period - #1 approximately 3 months
after acceptance and #2 within 3 months of termination of Warranty Period.
PART 2 PRODUCTS (NOT APPLICABLE)
PART 3 EXECUTION (NOT APPLICABLE)
END OF SECTION

More Related Content

What's hot

HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance
AC Repair Local
 
SAFE HANDING OVER OF EQUIPMENTS.pptx
SAFE HANDING OVER OF EQUIPMENTS.pptxSAFE HANDING OVER OF EQUIPMENTS.pptx
SAFE HANDING OVER OF EQUIPMENTS.pptx
JOMON M.C
 
Energy Conservation Techniques For Industries
Energy Conservation Techniques For IndustriesEnergy Conservation Techniques For Industries
Energy Conservation Techniques For IndustriesShakti Prasad Ghadei
 
Some fact about Ammonia Production by Prem Baboo.pdf
Some fact about Ammonia Production by Prem Baboo.pdfSome fact about Ammonia Production by Prem Baboo.pdf
Some fact about Ammonia Production by Prem Baboo.pdf
PremBaboo4
 
Boiler ppt
Boiler pptBoiler ppt
Boiler ppt
HaleemullahMShafiq
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
Orange Slides
 
wasteheatrecovery.pptx
wasteheatrecovery.pptxwasteheatrecovery.pptx
wasteheatrecovery.pptx
rajarawat12
 
CLTD Tables ASHRAE in IP Units
CLTD Tables ASHRAE in IP UnitsCLTD Tables ASHRAE in IP Units
CLTD Tables ASHRAE in IP Units
HarisRiaz25
 
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...Mumin HACIMUSALAR
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plant
Dinesh Sannepally
 
Steam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvementSteam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvement
Summit Power International https://summitpowerinternational.com/
 
Boiler ppt
Boiler pptBoiler ppt
Boiler ppt
Er Ramgarhia
 
Cooling tower
Cooling towerCooling tower
Cooling tower
Ashif AR
 
Mebs6006 0910 04-load
Mebs6006 0910 04-loadMebs6006 0910 04-load
Mebs6006 0910 04-loadnarazmi
 
Duct sizing methods and filter types
Duct sizing methods and filter typesDuct sizing methods and filter types
Duct sizing methods and filter types
SANKA_SILVA
 
Steam Reforming - Tube Design
Steam Reforming - Tube DesignSteam Reforming - Tube Design
Steam Reforming - Tube Design
Gerard B. Hawkins
 
Energy Efficiency of Industrial Utilities
Energy Efficiency of Industrial UtilitiesEnergy Efficiency of Industrial Utilities
Energy Efficiency of Industrial Utilities
Pratap Jung Rai
 
Heat Exchangers by Hanif Dewan
Heat Exchangers by Hanif DewanHeat Exchangers by Hanif Dewan
Heat Exchangers by Hanif Dewan
Mohammud Hanif Dewan M.Phil.
 
Methanol Reformer Designs
Methanol Reformer DesignsMethanol Reformer Designs
Methanol Reformer Designs
Gerard B. Hawkins
 
Trouble Shooting of Chemical Process Industry
Trouble Shooting of Chemical Process IndustryTrouble Shooting of Chemical Process Industry
Trouble Shooting of Chemical Process Industry
Pankaj Khandelwal
 

What's hot (20)

HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance
 
SAFE HANDING OVER OF EQUIPMENTS.pptx
SAFE HANDING OVER OF EQUIPMENTS.pptxSAFE HANDING OVER OF EQUIPMENTS.pptx
SAFE HANDING OVER OF EQUIPMENTS.pptx
 
Energy Conservation Techniques For Industries
Energy Conservation Techniques For IndustriesEnergy Conservation Techniques For Industries
Energy Conservation Techniques For Industries
 
Some fact about Ammonia Production by Prem Baboo.pdf
Some fact about Ammonia Production by Prem Baboo.pdfSome fact about Ammonia Production by Prem Baboo.pdf
Some fact about Ammonia Production by Prem Baboo.pdf
 
Boiler ppt
Boiler pptBoiler ppt
Boiler ppt
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
wasteheatrecovery.pptx
wasteheatrecovery.pptxwasteheatrecovery.pptx
wasteheatrecovery.pptx
 
CLTD Tables ASHRAE in IP Units
CLTD Tables ASHRAE in IP UnitsCLTD Tables ASHRAE in IP Units
CLTD Tables ASHRAE in IP Units
 
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...
PRESENTATION-Commissioning Experiences on Ammonia and Urea projects- Independ...
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plant
 
Steam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvementSteam turbine deaerating condenser perforamace improvement
Steam turbine deaerating condenser perforamace improvement
 
Boiler ppt
Boiler pptBoiler ppt
Boiler ppt
 
Cooling tower
Cooling towerCooling tower
Cooling tower
 
Mebs6006 0910 04-load
Mebs6006 0910 04-loadMebs6006 0910 04-load
Mebs6006 0910 04-load
 
Duct sizing methods and filter types
Duct sizing methods and filter typesDuct sizing methods and filter types
Duct sizing methods and filter types
 
Steam Reforming - Tube Design
Steam Reforming - Tube DesignSteam Reforming - Tube Design
Steam Reforming - Tube Design
 
Energy Efficiency of Industrial Utilities
Energy Efficiency of Industrial UtilitiesEnergy Efficiency of Industrial Utilities
Energy Efficiency of Industrial Utilities
 
Heat Exchangers by Hanif Dewan
Heat Exchangers by Hanif DewanHeat Exchangers by Hanif Dewan
Heat Exchangers by Hanif Dewan
 
Methanol Reformer Designs
Methanol Reformer DesignsMethanol Reformer Designs
Methanol Reformer Designs
 
Trouble Shooting of Chemical Process Industry
Trouble Shooting of Chemical Process IndustryTrouble Shooting of Chemical Process Industry
Trouble Shooting of Chemical Process Industry
 

Viewers also liked

Sarcina nr 2 roma
Sarcina nr 2 romaSarcina nr 2 roma
Sarcina nr 2 roma
florinaarsenie
 
¿Qué es Slide Share?
¿Qué es Slide Share? ¿Qué es Slide Share?
¿Qué es Slide Share?
Family
 
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_ENKakim Goh
 
Magazine Genre Research
Magazine Genre ResearchMagazine Genre Research
Magazine Genre Research
daltonsenger
 
A Framework for Deadlock Detection in Java
A Framework for Deadlock Detection in JavaA Framework for Deadlock Detection in Java
A Framework for Deadlock Detection in Java
Vincenzo Lomonaco
 
Deep Learning for Computer Vision: A comparision between Convolutional Neural...
Deep Learning for Computer Vision: A comparision between Convolutional Neural...Deep Learning for Computer Vision: A comparision between Convolutional Neural...
Deep Learning for Computer Vision: A comparision between Convolutional Neural...
Vincenzo Lomonaco
 

Viewers also liked (8)

Sarcina nr 2 roma
Sarcina nr 2 romaSarcina nr 2 roma
Sarcina nr 2 roma
 
¿Qué es Slide Share?
¿Qué es Slide Share? ¿Qué es Slide Share?
¿Qué es Slide Share?
 
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN
2016-03-31 FAA Visual Arts at MDC Frontenac_May 2016_Press Kit_EN
 
Curriculum Vita1
Curriculum Vita1Curriculum Vita1
Curriculum Vita1
 
Magazine Genre Research
Magazine Genre ResearchMagazine Genre Research
Magazine Genre Research
 
A Framework for Deadlock Detection in Java
A Framework for Deadlock Detection in JavaA Framework for Deadlock Detection in Java
A Framework for Deadlock Detection in Java
 
SCHEMATIC REPORT
SCHEMATIC REPORTSCHEMATIC REPORT
SCHEMATIC REPORT
 
Deep Learning for Computer Vision: A comparision between Convolutional Neural...
Deep Learning for Computer Vision: A comparision between Convolutional Neural...Deep Learning for Computer Vision: A comparision between Convolutional Neural...
Deep Learning for Computer Vision: A comparision between Convolutional Neural...
 

Similar to Tab

TG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).docTG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).doc
jennbarroga7
 
Support utilities validation.pptx (asmita magare)
Support utilities validation.pptx (asmita magare)Support utilities validation.pptx (asmita magare)
Support utilities validation.pptx (asmita magare)
magareasmi
 
ANSI 2014 Update
ANSI 2014 UpdateANSI 2014 Update
Validation utility system
Validation utility systemValidation utility system
Validation utility system
ArpitSuralkar
 
Qualification of gc equipment
Qualification of gc equipmentQualification of gc equipment
Qualification of gc equipment
srikrupa institute of pharmaceutical analysis
 
Qualification of gc equipment by manoj kumar
Qualification of gc equipment by manoj kumarQualification of gc equipment by manoj kumar
Qualification of gc equipment by manoj kumar
himaja donthula
 
ANSI Standards & Updates
ANSI Standards & UpdatesANSI Standards & Updates
ANSI Standards & Updates
TESCO - The Eastern Specialty Company
 
Qualification of Analytical Equipments
Qualification of Analytical EquipmentsQualification of Analytical Equipments
Qualification of Analytical Equipments
Dhawal_Raghuvanshi
 
ANSI Testing
ANSI TestingANSI Testing
ANSI C12.20 and Proposed Field Testing Changes
ANSI C12.20 and Proposed Field Testing ChangesANSI C12.20 and Proposed Field Testing Changes
ANSI C12.20 and Proposed Field Testing Changes
TESCO - The Eastern Specialty Company
 
Anab Guidance Scopes Accreditation
Anab Guidance Scopes AccreditationAnab Guidance Scopes Accreditation
Anab Guidance Scopes Accreditation
ANSI-ASQ National Accreditation Board (ANAB)
 
Quality Installation Check list
Quality Installation Check listQuality Installation Check list
Quality Installation Check listGary Tate
 
Flare System Process Design Manual - Flour Daniel
Flare System Process Design Manual - Flour DanielFlare System Process Design Manual - Flour Daniel
Flare System Process Design Manual - Flour Daniel
crj2000
 
steam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdfsteam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdf
chintanraval24
 
Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2
Peter Sherwin
 
Validation utility system
Validation utility systemValidation utility system
Validation utility system
PRANJAY PATIL
 
Qualification of Dissolution Test Apparatus and Validation of Utility System
Qualification of Dissolution Test Apparatus and Validation of Utility SystemQualification of Dissolution Test Apparatus and Validation of Utility System
Qualification of Dissolution Test Apparatus and Validation of Utility System
Akshay Trivedi , Maliba Pharmacy College
 
Validation of equipments
Validation of equipmentsValidation of equipments
Validation of equipments
suhasini
 

Similar to Tab (20)

TG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).docTG-15595- report-and-analysis_powerpointviewer(1).doc
TG-15595- report-and-analysis_powerpointviewer(1).doc
 
Support utilities validation.pptx (asmita magare)
Support utilities validation.pptx (asmita magare)Support utilities validation.pptx (asmita magare)
Support utilities validation.pptx (asmita magare)
 
ANSI 2014 Update
ANSI 2014 UpdateANSI 2014 Update
ANSI 2014 Update
 
Validation utility system
Validation utility systemValidation utility system
Validation utility system
 
Qualification of gc equipment
Qualification of gc equipmentQualification of gc equipment
Qualification of gc equipment
 
Qualification of gc equipment by manoj kumar
Qualification of gc equipment by manoj kumarQualification of gc equipment by manoj kumar
Qualification of gc equipment by manoj kumar
 
ANSI Standards & Updates
ANSI Standards & UpdatesANSI Standards & Updates
ANSI Standards & Updates
 
Qualification of Analytical Equipments
Qualification of Analytical EquipmentsQualification of Analytical Equipments
Qualification of Analytical Equipments
 
ANSI Testing
ANSI TestingANSI Testing
ANSI Testing
 
019113
019113019113
019113
 
ANSI C12.20 and Proposed Field Testing Changes
ANSI C12.20 and Proposed Field Testing ChangesANSI C12.20 and Proposed Field Testing Changes
ANSI C12.20 and Proposed Field Testing Changes
 
Anab Guidance Scopes Accreditation
Anab Guidance Scopes AccreditationAnab Guidance Scopes Accreditation
Anab Guidance Scopes Accreditation
 
Air Conditioning Inspections For Buildings Talk
Air Conditioning Inspections For Buildings  TalkAir Conditioning Inspections For Buildings  Talk
Air Conditioning Inspections For Buildings Talk
 
Quality Installation Check list
Quality Installation Check listQuality Installation Check list
Quality Installation Check list
 
Flare System Process Design Manual - Flour Daniel
Flare System Process Design Manual - Flour DanielFlare System Process Design Manual - Flour Daniel
Flare System Process Design Manual - Flour Daniel
 
steam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdfsteam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdf
 
Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2Understanding AMS2750E (intermediate) v2
Understanding AMS2750E (intermediate) v2
 
Validation utility system
Validation utility systemValidation utility system
Validation utility system
 
Qualification of Dissolution Test Apparatus and Validation of Utility System
Qualification of Dissolution Test Apparatus and Validation of Utility SystemQualification of Dissolution Test Apparatus and Validation of Utility System
Qualification of Dissolution Test Apparatus and Validation of Utility System
 
Validation of equipments
Validation of equipmentsValidation of equipments
Validation of equipments
 

Recently uploaded

Online aptitude test management system project report.pdf
Online aptitude test management system project report.pdfOnline aptitude test management system project report.pdf
Online aptitude test management system project report.pdf
Kamal Acharya
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
fxintegritypublishin
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
ydteq
 
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesHarnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Christina Lin
 
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTSHeap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Soumen Santra
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
thanhdowork
 
Swimming pool mechanical components design.pptx
Swimming pool  mechanical components design.pptxSwimming pool  mechanical components design.pptx
Swimming pool mechanical components design.pptx
yokeleetan1
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
digital fundamental by Thomas L.floydl.pdf
digital fundamental by Thomas L.floydl.pdfdigital fundamental by Thomas L.floydl.pdf
digital fundamental by Thomas L.floydl.pdf
drwaing
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
zwunae
 
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
ssuser7dcef0
 
Building Electrical System Design & Installation
Building Electrical System Design & InstallationBuilding Electrical System Design & Installation
Building Electrical System Design & Installation
symbo111
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
AJAYKUMARPUND1
 
Fundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptxFundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptx
manasideore6
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
SyedAbiiAzazi1
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
SUTEJAS
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
ChristineTorrepenida1
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
Dr Ramhari Poudyal
 

Recently uploaded (20)

Online aptitude test management system project report.pdf
Online aptitude test management system project report.pdfOnline aptitude test management system project report.pdf
Online aptitude test management system project report.pdf
 
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdfHybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdf
 
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
一比一原版(UofT毕业证)多伦多大学毕业证成绩单如何办理
 
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesHarnessing WebAssembly for Real-time Stateless Streaming Pipelines
Harnessing WebAssembly for Real-time Stateless Streaming Pipelines
 
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTSHeap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
Heap Sort (SS).ppt FOR ENGINEERING GRADUATES, BCA, MCA, MTECH, BSC STUDENTS
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
 
Swimming pool mechanical components design.pptx
Swimming pool  mechanical components design.pptxSwimming pool  mechanical components design.pptx
Swimming pool mechanical components design.pptx
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
digital fundamental by Thomas L.floydl.pdf
digital fundamental by Thomas L.floydl.pdfdigital fundamental by Thomas L.floydl.pdf
digital fundamental by Thomas L.floydl.pdf
 
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
一比一原版(IIT毕业证)伊利诺伊理工大学毕业证成绩单专业办理
 
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
NUMERICAL SIMULATIONS OF HEAT AND MASS TRANSFER IN CONDENSING HEAT EXCHANGERS...
 
Building Electrical System Design & Installation
Building Electrical System Design & InstallationBuilding Electrical System Design & Installation
Building Electrical System Design & Installation
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
 
Fundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptxFundamentals of Induction Motor Drives.pptx
Fundamentals of Induction Motor Drives.pptx
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
 

Tab

  • 1. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 1 of 8 PART 1 GENERAL 1.1 SUMMARY .1 TAB is used throughout this Section to describe the process, methods and requirements of testing, adjusting and balancing for HVAC. .2 TAB means to test, adjust and balance to perform in accordance with requirements of Contract Documents and to do other work as specified in this Section. 1.2 QUALIFICATIONS OF TAB PERSONNEL .1 Submit names of personnel certified to AABC, NBC, NEBB or SMACNA to perform TAB to Owner’s Representative within 90 days of award of contract. .2 Provide documentation confirming qualifications, successful experience. TAB contractor shall have a minimum of 5 (five) years experience to AABC, NBC, NEBB or SMACNA. .3 TAB: performed in accordance with the requirements of standard under which TAB Firm’s qualifications are approved: .1 Associated Air Balance Council, (AABC) National Standards for Total System Balance, MN-1. .2 National Balancing Council, (NBC) Certified Air Balancing Specifications and Certified Hydronic Balancing Specifications. .3 National Environmental Balancing Bureau (NEBB) TABES, Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems. .4 Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA), HVAC TAB HVAC Systems – Testing, Adjusting and Balancing. .4 Recommendations and suggested practices contained in the TAB Standard: mandatory. .5 Use TAB Standard provisions, including checklists, and report forms to satisfy Contract requirements. .6 Use TAB standard for TAB, including qualifications for TAB Firm and Specialist and calibration of TAB instruments. .7 Where instrument manufacturer calibration recommendations are more stringent than those listed in the TAB standard, use manufacturer’s recommendations. .8 TAB Standard quality assurance provisions such as performance guarantees form part of this contract. .1 For systems or system components not covered in TAB standard, use TAB procedures developed by TAB Specialist. .2 Where new procedures and requirements are applicable to Contract requirements have been published or adopted by body responsible for TAB Standard used (AABC, NBC, NEBB, or SMACNA), requirements and recommendations contained in these procedures and requirements are mandatory.
  • 2. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 2 of 8 1.3 PURPOSE OF TAB .1 Test to verify proper and safe operation, determine actual point of performance, evaluate qualitative and quantitative performance of equipment, systems and controls at design, average and low loads using actual or simulated loads. .2 Adjust and regulate equipment and systems so as to meet specified performance requirements and to achieve specified interaction with other related systems under normal and emergency loads and operating conditions. .3 Balance systems and equipment to regulate flow rates to match load requirements over full operating ranges. 1.4 EXCEPTIONS .1 TAB of systems and equipment regulated by codes, standards to be to satisfaction of authority having jurisdiction. 1.5 CO-ORDINATION .1 Schedule time required for TAB (including repairs, re-testing) into project construction and completion schedule so as to ensure completion before acceptance of project. .2 Do TAB of each system independently and subsequently, where interlocked with other systems, in unison with those systems. 1.6 PRE-TAB REVIEW .1 Review contract documents before project construction is started and confirm in writing to Owner’s Representative adequacy of provisions for TAB and other aspects of design and installation pertinent to success of TAB. .2 Review specified standards and report to Owner’s Representative in writing all proposed procedures which vary from standard. .3 During construction, co-ordinate location and installation of TAB devices, equipment, accessories, measurement ports and fittings. 1.7 START-UP .1 Follow start-up procedures as recommended by equipment manufacturer unless specified otherwise. .2 Follow special start-up procedures specified elsewhere in other Divisions. 1.8 OPERATION OF SYSTEMS DURING TAB .1 Operate systems for length of time required for TAB and as required by Owner’s Representative for verification of TAB reports.
  • 3. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 3 of 8 1.9 START OF TAB .1 Notify Owner’s Representative 7 (seven) days prior to start of TAB. .2 Start TAB when building is essentially completed, including: .1 Installation of ceilings, doors, windows, other construction affecting TAB. .2 Application of weatherstripping, sealing, caulking. .3 All pressure, leakage, other tests specified elsewhere in other Divisions. .4 All provisions for TAB installed and operational. .3 Start-up, verification for proper, normal and safe operation of mechanical and associated electrical and control systems affecting TAB including but not limited to: .1 Proper thermal overload protection in place for electrical equipment. .2 Air systems: .1 Filters in place, clean. .2 Duct systems clean. .3 Ducts, air shafts, ceiling plenums are airtight to within specified tolerances. .4 Correct fan rotation. .5 Fire, smoke, volume control dampers installed and open. .6 Coil fins combed, clean. .7 Access doors, installed, closed. .8 Outlets installed, volume control dampers open. .3 Liquid systems: .1 Flushed, filled, vented. .2 Correct pump rotation. .3 Strainers in place, baskets clean. .4 Isolating and balancing valves installed, open. .5 Calibrated balancing valves installed, at factory settings. .6 Chemical treatment systems complete, operational. 1.10 APPLICATION TOLERANCES .1 Do TAB to following tolerances of design values: .1 Laboratory HVAC systems: plus 10%, minus 0%. .2 Other HVAC systems: plus 5%, minus 5%. .3 Hydronic systems: plus or minus 10 %. .4 Refrigeration systems: plus or minus 10%. 1.11 ACCURACY TOLERANCES .1 Measured values to be accurate to within plus or minus 2 % of actual values.
  • 4. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 4 of 8 1.12 INSTRUMENTS .1 Prior to TAB, submit to Owner’s Representative list of instruments to be used together with serial numbers. .2 Calibrate in accordance with requirements of most stringent of referenced standard for either applicable system or HVAC system. .3 Calibrate within 3 (three) months of TAB. Provide certificate of calibration to Owner’s Representative. 1.13 SUBMITTALS .1 Submit, prior to commencement of TAB: .2 Proposed methodology and procedures for performing TAB if different from referenced standard. 1.14 PRELIMINARY TAB REPORT .1 Submit for checking and approval of Owner’s Representative, prior to submission of formal TAB report, sample of rough TAB sheets. Include: .1 Details of instruments used. .2 Details of TAB procedures employed. .3 Calculations procedures. .4 Summaries. 1.15 TAB REPORT .1 Format to be in accordance with referenced standard. .2 TAB report to show results in SI units and to include: .1 Project record drawings. .2 System schematics. .3 Submit 3 (three) copies of TAB Report to Owner’s Representative for verification and approval, in English in D-ring binders, complete with index tabs. 1.16 VERIFICATION .1 Reported results subject to verification by Owner’s Representative. .2 Provide manpower and instrumentation to verify up to 30% of reported results. .3 Number and location of verified results to be at discretion of Owner’s Representative. .4 Bear costs to repeat TAB as required to satisfaction of Owner’s Representative.
  • 5. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 5 of 8 1.17 SETTINGS .1 After TAB is completed to satisfaction of Owner’s Representative, replace drive guards, close access doors, lock devices in set positions, ensure sensors are at required settings. .2 Permanently mark settings to allow restoration at any time during life of facility. Markings not to be eradicated or covered in any way. 1.18 COMPLETION OF TAB .1 TAB to be considered complete when final TAB Report received and approved by Owner’s Representative. 1.19 AIR SYSTEMS .1 Standard: TAB to be to most stringent of this section or TAB standards of AABC, NBC or NEBB. .2 Do TAB of systems, equipment, components, controls specified in other Divisions. .3 Qualifications: personnel performing TAB to be qualified to standards of AABC, NBC or NEBB. .4 Quality assurance: Perform TAB under direction of supervisor qualified to standards of AABC, NBC or NEBB. .5 Measurements: to include, but not limited to, following as appropriate for systems, equipment, components, controls: air velocity, static pressure, flow rate, pressure drop (or loss), temperatures (dry bulb, wet bulb, dewpoint), duct cross-sectional area, RPM, electrical power, voltage, noise, vibration, amperage and volts for each stage of electrical heating coils. .6 Locations of equipment measurements: To include, but not be limited to, following as appropriate: .1 Inlet and outlet of dampers, filter, coil, humidifier, fan, other equipment causing changes in conditions. .2 At controllers, controlled device. .7 Locations of systems measurements to include, but not be limited to, following as appropriate: Main ducts, main branch, sub-branch, run-out (or grille, register or diffuser). 1.20 HYDRONIC SYSTEMS .1 Definitions: for purposes of this section, to include low pressure hot water heating, chilled water, condenser water, glycol systems. .2 Standard: TAB to be to most stringent of TAB standards of AABC, NBC or NEBB. .3 Do TAB of systems, equipment, components, controls specified in other Divisions.
  • 6. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 6 of 8 .4 Qualifications: personnel performing TAB to be qualified to standards of AABC, NBC or NEBB. .5 Quality assurance: perform TAB under direction of supervisor qualified to standards of AABC, NBC or NEBB. .6 Measurements: to include, but not limited to, following as appropriate for systems, equipment, components, controls: flow rate, static pressure, pressure drop (or loss), temperature, specific gravity, density, RPM, electrical power, voltage, noise, vibration. .7 Locations of equipment measurement: to include, but not be limited to, following as appropriate: .1 Inlet and outlet of heat exchangers (primary and secondary sides), boiler, chiller, coil, humidifier, cooling tower, condenser, pump, PRV, control valve, other equipment causing changes in conditions. .2 At controllers, controlled device. .8 Locations of systems measurements to include, but not be limited to, following as appropriate: supply and return of primary and secondary loops (main, main branch, branch, sub-branch) of all hydronic systems, inlet connection of make-up water. 1.21 DOMESTIC WATER SYSTEMS .1 Meet requirements as specified for hydronic systems. .2 Locations of equipment measurements: To include, but not be limited to, following as appropriate: inlet and outlet of heaters, tank, pump, circulator, at controllers, controlled device. .3 Locations of systems measurements to include, but not be limited to, following as appropriate: main, main branch, branch, sub-branch. 1.22 OTHER SYSTEMS .1 Plumbing systems: .1 Standard: National Plumbing Code. .2 TAB procedures: .1 Flush valves: adjust to suit project pressure conditions. .2 Pressure booster systems: test for capacity and pressures under all conditions and at all times. .3 Controlled flow roof drain systems: adjust weirs to suit actual roof conditions, slopes, areas drained. .4 Pumped sanitary and storm water systems: test for proper operation at all possible flow rates. Refer to Section 32 32 13.13 – Packaged Sewage Lift, Wet Well Type. .5 Pressure reducing station. .2 Wet pipe sprinkler sprinkler systems:
  • 7. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 7 of 8 .1 Standard: NFPA. .2 TAB procedures: Refer to NFPA 13 Sprinkler System. .3 Refrigeration systems forming part of HVAC systems: .1 Standard: CSA B52 – Mechanical Refrigeration Code. .2 TAB procedures: Refer to Standard as follows: .1 Suction Pressure and Temperature. .2 Discharge Pressure and Temperature. .3 Suction Superheat .4 Evaporation Pressure and Temperature. .4 Chemical treatment systems: .1 Standard: Section 23 25 00 – HVAC Water Treatment Systems. .2 TAB procedures: refer to Section 23 25 00 – HVAC Water Treatment Systems. 1.23 OTHER TAB REQUIREMENTS .1 General requirements applicable to work specified this paragraph: .1 Qualifications of TAB personnel: as for air systems specified this section. .2 Quality assurance: as for air systems specified this section. .2 Laboratory fume hoods: .1 Standard: ASHRAE 110 – Method of Testing Performance of Laboratory Fume Hoods, applicable provincial standard. .2 TAB procedures: as described in standard. .3 Building pressure conditions: .1 Adjust HVAC systems, equipment, controls to ensure specified pressure conditions during winter and summer design conditions. .4 Zone pressure differences: .1 Adjust HVAC systems, equipment, controls to establish specified air pressure differentials, with all systems in all possible combinations of normal operating modes. .5 Smoke management systems: .1 Test for proper operation of all smoke and fire dampers, sensors, detectors, installed as component parts of air systems specified in other Divisions. .6 Measurement of noise and vibration from equipment specified in Mechanical Division. .1 Standard: 23 05 48 - Vibration and Seismic Controls for HVAC Piping and Equipment and 23 32 48 – Acoustical Air Plenums. .2 Vibration measurements around each piece of rotating equipment. .3 Sound measurements in each octave band around each piece of rotating equipment. .4 Induct sound measurements in each octave band at each fan inlet and discharge.
  • 8. NL Master Specification Guide for Public Funded Buildings Re-issued 2013/02/28 Section 23 05 93 – Testing, Adjusting and Balancing for HVAC Page 8 of 8 .5 Induct sound measurements in each octave band at each air handling unit intake, return and discharge. .6 Sound measurements in each octave band for each normally occupied room with air handling equipment running. .7 Measurement of spatial noise: .1 Standard: Section 23 32 48 – Acoustical Air Plenums. 1.24 POST- OCCUPANCY TAB .1 Measure DBT, WBT (or %RH), air velocity, air flow patterns, NC levels, in occupied zone of areas designated by Owner’s Representative. .2 Participate in systems checks twice during Warranty Period - #1 approximately 3 months after acceptance and #2 within 3 months of termination of Warranty Period. PART 2 PRODUCTS (NOT APPLICABLE) PART 3 EXECUTION (NOT APPLICABLE) END OF SECTION