SIL Suitable Final Elements
FUNCTIONAL SAFETY OF
FIRE & GAS SYSTEMS
SA FIRE PROTECTION
FUNCTIONAL SAFETY
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 2SIL Suitable Final Elements
DEFINITION OF FUNCTIONAL SAFETY
 Safety is the absence of an
unacceptable risk of physical injury to
people or damage to the properties
 Functional Safety is part of the overall
safety which depends on the correct
functioning of a safety-related system
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 3SIL Suitable Final Elements
SAFETY INSTRUMENTED SYSTEM (SIS)
 A Safety Instrumented System (SIS) or
Safety-related System is an appropriate
system required to reduce the risk
(shown by a hazard analysis) of the
Equipment Under Control (EUC)
 A SIS performs one or more Safety
Functions to reduce the risk
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 4SIL Suitable Final Elements
REQUIREMENTS TO FUNCTIONAL SAFETY
Two types of requirements are necessary
to achieve Functional Safety:
 Safety Function Requirements: the
scope of the Safety Function, derived
from the hazard analysis
 Safety Integrity Requirements: the
probability that the Safety Function will
be performed satisfactorily, derived
from the risk assessment
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 5SIL Suitable Final Elements
THE STANDARD IEC 61508
IEC 61508 “Functional Safety of electrical
/electronic / programmable electronic
(E/E/PE) safety-related systems”:
 Covers all the safety lifecycle activities
 Contains requirements for preventing
failures and controlling failures,
ensuring safety even when faults are
present
 Specifies the techniques and measures
to achieve the required Safety Integrity
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 6SIL Suitable Final Elements
SAFETY INTEGRITY LEVEL (SIL)
 Safety Integrity is the probability that
the SIS will perform the required Safety
Functions satisfactorily
 IEC 61508 specifies 4 levels of safety
performance for a Safety Function,
called Safety Integrity Level (SIL)
 The Standard details the requirements
necessary to achieve each Safety
Integrity Level. SIL1 is the lowest level
and SIL4 is the highest
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 7SIL Suitable Final Elements
SAFETY INTEGRITY LEVEL (SIL)
FUNCTIONAL SAFETY
• Definition
• SIS
• Requirements
• IEC 61508
• SIL
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 8SIL Suitable Final Elements
Low demand mode of operation:
frequency of demands for the SIS not
greater than once per year, and not
greater than twice the proof-test
frequency
Safety Integrity Level (SIL)
Average Probability of Failure
on Demand (PFDavg)
4 ≥ 10-5 to < 10-4
3 ≥ 10-4 to < 10-3
2 ≥ 10-3 to < 10-2
1 ≥ 10-2 to < 10-1
FIRE & GAS SYSTEM
FUNCTIONAL SAFETY
F&G SYSTEM
• Objectives
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 9SIL Suitable Final Elements
TASKS OF F&G SYSTEM
The main tasks of a F&G system are:
 Detect any hazardous fire or gas
condition
 Alert the personnel in the monitored
area
 Activate the control and mitigation
systems
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 10SIL Suitable Final Elements
F&G SYSTEM EFFECTIVENESS
The F&G system Effectiveness is the
product of three factors:
 Detection Coverage: the fraction of the
monitored area in which an eventual
hazard would be detected
 Mitigation Effectiveness: the
probability that the activation of the
Final Elements would reduce the
consequence of a defined hazard
 F&G Safety Availability (SA): 1-PFDavg
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 11SIL Suitable Final Elements
A F&G system consists of:
 Detectors
 Logic Solver
 Final Elements
A chain is only as strong as its weakest
element
COMPONENTS OF F&G SYSTEM
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 12SIL Suitable Final Elements
LOGIC
SOLVER
FINAL
ELEMENTS
DETECTORS
The F&G Effectiveness is related to the
Safety Availability of all its components
SA has developed
SIL suitable Final Elements
for the main fire-fighting systems
FINAL ELEMENTS
FUNCTIONAL SAFETY
F&G SYSTEM
• Tasks
• Effectiveness
• Components
• Final Elements
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 13SIL Suitable Final Elements
LOGIC
SOLVER
FINAL
ELEMENTS
DETECTORS
NIAGARA
ELECTRIC
MONITORS
ELECTRIC
ACTUATORS
VDD
DELUGE
VALVES
ELECTRIC MONITOR
NIAGARA SERIES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 14SIL Suitable Final Elements
DESCRIPTION
 The fire-fighting monitors
Niagara series are electric
type remote controlled
water cannons, intended to
deliver large amount of water
towards remote targets.
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 15SIL Suitable Final Elements
 The monitor architecture comprises
of a Logic Controller and one or more
monitor assemblies
MAIN FEATURES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 16SIL Suitable Final Elements
 Automatic self-diagnostic
analysis
 Remote controlled
 Designed for sea water and
water foam solution
 Suitability for SIL2 systems
validated by Bureau Veritas
ADVANTAGES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 17SIL Suitable Final Elements
Automatic self-diagnostic analysis: at
regular intervals the self-diagnostic
system in the Logic Controller checks the
correct operation on given commands
 Constant monitoring of any possible
failure of monitor and nozzle
 Reduction of the probability that
faults, taking place between regular
maintenance, will pass undetected
 Increased reliability on demand
APPLICATION
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
• Description
• Main features
• Advantages
• Application
ELECTRIC ACTUATOR
VDD DELUGE VALVE
28/02/2015 18SIL Suitable Final Elements
Designed for petrochemical
jetty and marine harbor and
structure cooling
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
 A large amount of water towards
remote targets
DOUBLE COIL
ELECTRIC ACTUATOR
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 19SIL Suitable Final Elements
DESCRIPTION
 The double coil electric actuator has
been developed to sharply reducing
the probability of failure of a pilot
cylinder of a gaseous based fire
protection system (carbon dioxide,
inert gases, halocarbons) or a water
mist system
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 20
MAIN FEATURES
 Redundancy: the actuator has two coils
which receive two independent signals
from the Logic Solver. If one coil should
fail, the other coil is able to open the
cylinder valve
 Suitability for SIL2
systems validated
by Bureau Veritas
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 21
APPLICATION
Designed for the protection of gas
turbines and their generators, electronic
rooms and general installations on FPSO
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
SIL Suitable Final Elements
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
• Description
• Main features
• Application
VDD DELUGE VALVE
28/02/2015 22
DOUBLE CHAMBER DELUGE VALVE
MODEL VDD
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 23SIL Suitable Final Elements
DESCRIPTION
 The VDD deluge valve combines all the
functions of a traditional deluge valve
with a fully redundant architecture,
designed to achieve a higher Safety
Availability
 The VDD deluge valve
has two priming
chambers, each one
provided with its own
diaphragm and trim
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 24SIL Suitable Final Elements
PRINCIPLE OF OPERATION
 In the set position (valve closed)
The pressure of the water trapped in
the priming chambers holds the
diaphragms on the valve seats, keeping
the valve closed
 In fire condition (valve open)
The pressure is released from the
priming chambers. The water supply
pressure forces the diaphragm off the
seats, opening the valve
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 25SIL Suitable Final Elements
MAIN FEATURES
 Fully redundant system
 Built-in emergency bypass line that
operates on both priming chambers in
“hot back-up”
 Continuous fire protection
 Designed to overcome a double failure
 Suitability for SIL3 systems validated by
Bureau Veritas
 Under UL testing for UL/cUL Listing
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 26SIL Suitable Final Elements
ADVANTAGES
Built-in emergency bypass line
 Each priming chamber provides the
nominal design waterway for the fire
protection system
 The system is fully redundant
 The time to respond to a failure is
reduced to zero
 No need of an external bypass line on
the skid: reduction of dimensions,
weight and cost of the skid
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 27SIL Suitable Final Elements
ADVANTAGES
Designed to overcome a double failure
 A hydraulic bridge between the trims
allows each trim to control both the
diaphragms
 In case of failure of one trim, the other
trim can open both the priming
chambers
 The VDD deluge valve can overcome a
double failure
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 28SIL Suitable Final Elements
ADVANTAGES
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 29SIL Suitable Final Elements
Designed to overcome a double failure
 Fault Tree of the VDD deluge valve
ADVANTAGES
Fire protection system always in service
 Two built-in isolation
valves allow alternate
in-line maintenance
to be performed
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 30SIL Suitable Final Elements
 An interlock system prevents
the accidental or incorrect
rotation of the isolation valves
APPLICATION
 Made of Ni-Al-Bronze, a
highly resistant material
 Specifically designed for
harsh environments, such
as oil & gas onshore and
offshore and chemical and
nuclear plants installations
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 31SIL Suitable Final Elements
 Sea water, foam
concentrate and
water foam solution
APPLICATION
Recommended for those systems which
require:
 A low probability of failure on demand
 A fire protection system with a high
Safety Integrity Level
 Continuity of fire protection during
maintenance or repair
 Reduction of weight, dimension and
cost of the skid
FUNCTIONAL SAFETY
F&G SYSTEM
NIAGARA MONITOR
ELECTRIC ACTUATOR
VDD DELUGE VALVE
• Description
• Principle of operation
• Main features
• Advantages
• Application
28/02/2015 32SIL Suitable Final Elements
REFERENCE CONTACT
SA Fire Protection
Viale Europa 121-123
Cascina ( PISA ) – Italy
Ph. +39.050.70.30.06
Fax. +39.050.70.35.80
export@sasrl.it

Sil presentation

  • 1.
    SIL Suitable FinalElements FUNCTIONAL SAFETY OF FIRE & GAS SYSTEMS SA FIRE PROTECTION
  • 2.
    FUNCTIONAL SAFETY FUNCTIONAL SAFETY •Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 2SIL Suitable Final Elements
  • 3.
    DEFINITION OF FUNCTIONALSAFETY  Safety is the absence of an unacceptable risk of physical injury to people or damage to the properties  Functional Safety is part of the overall safety which depends on the correct functioning of a safety-related system FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 3SIL Suitable Final Elements
  • 4.
    SAFETY INSTRUMENTED SYSTEM(SIS)  A Safety Instrumented System (SIS) or Safety-related System is an appropriate system required to reduce the risk (shown by a hazard analysis) of the Equipment Under Control (EUC)  A SIS performs one or more Safety Functions to reduce the risk FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 4SIL Suitable Final Elements
  • 5.
    REQUIREMENTS TO FUNCTIONALSAFETY Two types of requirements are necessary to achieve Functional Safety:  Safety Function Requirements: the scope of the Safety Function, derived from the hazard analysis  Safety Integrity Requirements: the probability that the Safety Function will be performed satisfactorily, derived from the risk assessment FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 5SIL Suitable Final Elements
  • 6.
    THE STANDARD IEC61508 IEC 61508 “Functional Safety of electrical /electronic / programmable electronic (E/E/PE) safety-related systems”:  Covers all the safety lifecycle activities  Contains requirements for preventing failures and controlling failures, ensuring safety even when faults are present  Specifies the techniques and measures to achieve the required Safety Integrity FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 6SIL Suitable Final Elements
  • 7.
    SAFETY INTEGRITY LEVEL(SIL)  Safety Integrity is the probability that the SIS will perform the required Safety Functions satisfactorily  IEC 61508 specifies 4 levels of safety performance for a Safety Function, called Safety Integrity Level (SIL)  The Standard details the requirements necessary to achieve each Safety Integrity Level. SIL1 is the lowest level and SIL4 is the highest FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 7SIL Suitable Final Elements
  • 8.
    SAFETY INTEGRITY LEVEL(SIL) FUNCTIONAL SAFETY • Definition • SIS • Requirements • IEC 61508 • SIL F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 8SIL Suitable Final Elements Low demand mode of operation: frequency of demands for the SIS not greater than once per year, and not greater than twice the proof-test frequency Safety Integrity Level (SIL) Average Probability of Failure on Demand (PFDavg) 4 ≥ 10-5 to < 10-4 3 ≥ 10-4 to < 10-3 2 ≥ 10-3 to < 10-2 1 ≥ 10-2 to < 10-1
  • 9.
    FIRE & GASSYSTEM FUNCTIONAL SAFETY F&G SYSTEM • Objectives • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 9SIL Suitable Final Elements
  • 10.
    TASKS OF F&GSYSTEM The main tasks of a F&G system are:  Detect any hazardous fire or gas condition  Alert the personnel in the monitored area  Activate the control and mitigation systems FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 10SIL Suitable Final Elements
  • 11.
    F&G SYSTEM EFFECTIVENESS TheF&G system Effectiveness is the product of three factors:  Detection Coverage: the fraction of the monitored area in which an eventual hazard would be detected  Mitigation Effectiveness: the probability that the activation of the Final Elements would reduce the consequence of a defined hazard  F&G Safety Availability (SA): 1-PFDavg FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 11SIL Suitable Final Elements
  • 12.
    A F&G systemconsists of:  Detectors  Logic Solver  Final Elements A chain is only as strong as its weakest element COMPONENTS OF F&G SYSTEM FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 12SIL Suitable Final Elements LOGIC SOLVER FINAL ELEMENTS DETECTORS
  • 13.
    The F&G Effectivenessis related to the Safety Availability of all its components SA has developed SIL suitable Final Elements for the main fire-fighting systems FINAL ELEMENTS FUNCTIONAL SAFETY F&G SYSTEM • Tasks • Effectiveness • Components • Final Elements NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 13SIL Suitable Final Elements LOGIC SOLVER FINAL ELEMENTS DETECTORS NIAGARA ELECTRIC MONITORS ELECTRIC ACTUATORS VDD DELUGE VALVES
  • 14.
    ELECTRIC MONITOR NIAGARA SERIES FUNCTIONALSAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 14SIL Suitable Final Elements
  • 15.
    DESCRIPTION  The fire-fightingmonitors Niagara series are electric type remote controlled water cannons, intended to deliver large amount of water towards remote targets. FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 15SIL Suitable Final Elements  The monitor architecture comprises of a Logic Controller and one or more monitor assemblies
  • 16.
    MAIN FEATURES FUNCTIONAL SAFETY F&GSYSTEM NIAGARA MONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 16SIL Suitable Final Elements  Automatic self-diagnostic analysis  Remote controlled  Designed for sea water and water foam solution  Suitability for SIL2 systems validated by Bureau Veritas
  • 17.
    ADVANTAGES FUNCTIONAL SAFETY F&G SYSTEM NIAGARAMONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 17SIL Suitable Final Elements Automatic self-diagnostic analysis: at regular intervals the self-diagnostic system in the Logic Controller checks the correct operation on given commands  Constant monitoring of any possible failure of monitor and nozzle  Reduction of the probability that faults, taking place between regular maintenance, will pass undetected  Increased reliability on demand
  • 18.
    APPLICATION FUNCTIONAL SAFETY F&G SYSTEM NIAGARAMONITOR • Description • Main features • Advantages • Application ELECTRIC ACTUATOR VDD DELUGE VALVE 28/02/2015 18SIL Suitable Final Elements Designed for petrochemical jetty and marine harbor and structure cooling Recommended for those systems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level  A large amount of water towards remote targets
  • 19.
    DOUBLE COIL ELECTRIC ACTUATOR FUNCTIONALSAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 19SIL Suitable Final Elements
  • 20.
    DESCRIPTION  The doublecoil electric actuator has been developed to sharply reducing the probability of failure of a pilot cylinder of a gaseous based fire protection system (carbon dioxide, inert gases, halocarbons) or a water mist system SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 20
  • 21.
    MAIN FEATURES  Redundancy:the actuator has two coils which receive two independent signals from the Logic Solver. If one coil should fail, the other coil is able to open the cylinder valve  Suitability for SIL2 systems validated by Bureau Veritas SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 21
  • 22.
    APPLICATION Designed for theprotection of gas turbines and their generators, electronic rooms and general installations on FPSO Recommended for those systems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level SIL Suitable Final Elements FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR • Description • Main features • Application VDD DELUGE VALVE 28/02/2015 22
  • 23.
    DOUBLE CHAMBER DELUGEVALVE MODEL VDD FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 23SIL Suitable Final Elements
  • 24.
    DESCRIPTION  The VDDdeluge valve combines all the functions of a traditional deluge valve with a fully redundant architecture, designed to achieve a higher Safety Availability  The VDD deluge valve has two priming chambers, each one provided with its own diaphragm and trim FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 24SIL Suitable Final Elements
  • 25.
    PRINCIPLE OF OPERATION In the set position (valve closed) The pressure of the water trapped in the priming chambers holds the diaphragms on the valve seats, keeping the valve closed  In fire condition (valve open) The pressure is released from the priming chambers. The water supply pressure forces the diaphragm off the seats, opening the valve FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 25SIL Suitable Final Elements
  • 26.
    MAIN FEATURES  Fullyredundant system  Built-in emergency bypass line that operates on both priming chambers in “hot back-up”  Continuous fire protection  Designed to overcome a double failure  Suitability for SIL3 systems validated by Bureau Veritas  Under UL testing for UL/cUL Listing FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 26SIL Suitable Final Elements
  • 27.
    ADVANTAGES Built-in emergency bypassline  Each priming chamber provides the nominal design waterway for the fire protection system  The system is fully redundant  The time to respond to a failure is reduced to zero  No need of an external bypass line on the skid: reduction of dimensions, weight and cost of the skid FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 27SIL Suitable Final Elements
  • 28.
    ADVANTAGES Designed to overcomea double failure  A hydraulic bridge between the trims allows each trim to control both the diaphragms  In case of failure of one trim, the other trim can open both the priming chambers  The VDD deluge valve can overcome a double failure FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 28SIL Suitable Final Elements
  • 29.
    ADVANTAGES FUNCTIONAL SAFETY F&G SYSTEM NIAGARAMONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 29SIL Suitable Final Elements Designed to overcome a double failure  Fault Tree of the VDD deluge valve
  • 30.
    ADVANTAGES Fire protection systemalways in service  Two built-in isolation valves allow alternate in-line maintenance to be performed FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 30SIL Suitable Final Elements  An interlock system prevents the accidental or incorrect rotation of the isolation valves
  • 31.
    APPLICATION  Made ofNi-Al-Bronze, a highly resistant material  Specifically designed for harsh environments, such as oil & gas onshore and offshore and chemical and nuclear plants installations FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 31SIL Suitable Final Elements  Sea water, foam concentrate and water foam solution
  • 32.
    APPLICATION Recommended for thosesystems which require:  A low probability of failure on demand  A fire protection system with a high Safety Integrity Level  Continuity of fire protection during maintenance or repair  Reduction of weight, dimension and cost of the skid FUNCTIONAL SAFETY F&G SYSTEM NIAGARA MONITOR ELECTRIC ACTUATOR VDD DELUGE VALVE • Description • Principle of operation • Main features • Advantages • Application 28/02/2015 32SIL Suitable Final Elements
  • 33.
    REFERENCE CONTACT SA FireProtection Viale Europa 121-123 Cascina ( PISA ) – Italy Ph. +39.050.70.30.06 Fax. +39.050.70.35.80 export@sasrl.it