A REVIEW ON SEISMIC ANALYSIS AND SUSTAINABILITY OF MULTI
STOREY STRUCTURE WITH AND WITHOUT FLOATING COLUMNS
Er. Shashank Kalla1, Er. Om Prakash Singh2, Dr. Shailesh Choudhary3
1M.E. Scholar, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur
2Ph.D. Scholar, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur
3Associate Professor, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur
---------------------------------------------------------------------***----------------------------------------------------------------------
Abstract - With escalating urbanization, demand for
greater spaces either in form of parking spaces, or in form of
aesthetic view point or for ambiance from architectural verse
sometimes let structural designer to plan andactaccordingto
it. Construction of multistorey structures with floating
columns have been never a choice of preference for any
structural engineer rather than being a demand or
requirement from either owner or architect. But such
structures are highly susceptible to be damaged during
earthquakes in highly seismic zone as compared to normal
structures. The paper turns out with static analysis done for
multistorey structures with and without floating columns
along with different cases of building structure are analyzed
by varying the location of floating columns floor wise. The
structural response of building models with respect to storey
drift, storey displacement, base shear and time periodforboth
building. The analysis is carried out using different structural
analysis and design software SAP2000v17, STAAD-PRO and
ETABS.
Key Words: Floating column, Earthquake analysis, Multi-
storey, Linear static method, Time history method,
SAP2000v17, STAAD-PRO, ETABS.
1. INTRODUCTION
Now a day’s, multistorey structures in urban cities are
required to have column free space due to shortageofspace,
increasing population and also for aesthetic and functional
requirements. To cope with such problems of parking
accommodations or reception lobbies most of multistorey
structures in India today prefers to have an open first storey
as an unavoidable feature or finds it aseasiestsolutionto the
problem. Thus, to meet-up with situation use of floating
columns starts, now talking about floating columns it’s a
vertical member without a foundation i.e. it rests on a beam.
Being without foundation this floating columncomesupasa
point load over the beam and further this beamtransfersthe
load to the columns below it. The floatingcolumnsometimes
also serves purpose of architectural view and sitesituations.
The Provision of floating columns can be stated as most of
the buildings in India are covering the maximum possible
area on a plot within the available by laws. Thus most times
for fulfilling the desires we neglect behaviour of a building
structures during earthquakes as it depends critically on
geometry, size and overall shape, in addition with how the
earthquake forces are carried to the ground. Hence,
ultimately not following basics of dynamic of structuresthat
earthquake forces developed at different floor levelsneed to
be brought down along the height to the ground by the
shortest path; any deviation or discontinuity here with load
transfer path results in poor performance of the building
structure. It had been found most of the energy developed
during earthquake is dissipated by columns of the soft
stories. Further transfer of this energy leads to formation of
plastic hinges at the ends of columns, which transform the
soft storey into a mechanism finally in such casethecollapse
is unavoidable. Building structures with vertical setbacks
(like the hotel buildings, malls, etc. with a few storey wider
than the rest) are most susceptibletocausea suddenjumpin
earthquake forces at the level of discontinuity. Structures
with fewer columns or walls in a particular storey or with
unusually tall storey tend to damage or collapse which is
initiated in that storey. These are highly undesirable in
building built in seismically active areas usually the civil
engineering infra structures are subjected to two classes of
loads, static and dynamic loads. The staticloadssuchasdead
load and live load are independent with respect to time in
case of dynamic loads, they are changing with respect to
time. Most of the cases the structures are designed with the
assumptions that all the loads applied are static. Generally
the dynamic loads i.e. earthquake loads are not taking
account in the design because the buildingsarenotregularly
subjected to earthquakes, and also it takes more time to
solve these parameters in the analysis and also its more
difficult to solve the solution.
It has been analyzed by using various designs and structural
analysis software that for an open ground storey frame,
retrofitting by introducing reinforced concrete wall in the
open ground storey, offers the maximum strength and
ductility. Building structures with columnsthathangorfloat
on beams at intermediate storey and not to go all the way to
the foundation, have discontinuitiesintheloadtransferpath.
These floating columns are highly disadvantageous in a
building built in seismically active areas, especially after the
desolating Nepal earthquake 25 April 2015 and tragic
example of Bhuj earthquake occurred on 26 January, 2001
there have been a mutual effort throughout India to provide
more awareness, especially in practice and education, with
respect to earthquake resistant design of structures.
Sustainability of such building structures could be achieved
up-to a certain extent by providing seismic retrofitting, as it
can be done in different ways and to various extents. The
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2898
purpose should be to certify that the building takes all the
damage, but does not collapse when severe earthquake
occurs.
2. REVIEW OF LITERATURE
(1) Sukumar Bahera* - Their literature comes up with
stiffness balance of first storey and above storey are studied
with the aim to minimize irregularity occurring with due
presence of a floating column. To make sure how structures
under different earthquake excitation having a different
frequency content responses keeping the time duration
factor and PGA constant they develop FEM codes for 2D
frames with and without floating column. This behaviour of
building structure frames with and withoutfloating columns
is studied for cases under static load, free vibration and
forced vibration condition. For developingthefinite element
codes MATLAB is used as primary platform. Various
computations including inter storey drift, overturning
moment, base shear, time history of floor displacement has
been done for both the frames with and without floating
column. Furthermore,studyfordynamic analysisofframeby
varying the column dimension had also been done. It
concludes that, with increment in ground floor column
values for the maximum displacement and inter storey drift
seems to be reduced. The change in column dimension also
leads to variation in base shear and overturning moment.
(2) A.P. Mundada*, S.G. Sawadakar - The paper covers up
the study for architectural and the framing drawing of the
building structure havingfloatingcolumns.Acomparison for
a G+7 existing residential building structure with and
without floating column are taken to carry out entireproject
work. The design creation of models and equivalent static
analysis of the models both have been done through the use
of STAAD ProV8i. Various parameters including moment
distribution, importance of line of action of force, axial load
and seismic factors are studied for designed models. Thus,
finally provides an edge to find various analytical properties
of the structure as well as provides criteria for very
systematic and economical design for the structure.
(3) Shrikanth M.K*, YogendraR.Holebu – Theliteratureis
about comparison of study for the behavior of a building
structure having only floating column and having floating
column with complexities. Highrisebuildingstructureshave
been analyzed for different intensity of earthquake force.
The study consist of creation of four models and analysis for
lower and higher seismic zones at medium soil condition.
Analysis being carried outwithhelpofextended3-Danalysis
of building system ETAB version 9.7.4software.Resultbeing
computed in regarding soft storey, storey drift and
displacement for designed four models and finallytabulated
on basis of linear seismic analysis.
(4) Hardik Bhensdadia*, Siddarth Shah – Theirstudyis an
attempt made to evaluate the effects of floating column &
soft story in different earthquake zones by seismic analysis.
As the analysis yieldsperformancelevel ofbuildingstructure
for design capacity (displacement) carried out up to failure
and to meet out this requirement methodology of push over
analysis is being adopted as it helps in determination of
collapse load and ductility capacity of the structure. For
fulfillment of this objective three RC bare frame structures
constituting of G+4, G+9, G+15 stories respectively have
been analysed and compared for base force and
displacement of RC bare frame structure with G+4, G+9,
G+15 stories. Providing different earthquakezonesintensity
like Bhuj, Jamnagar and Rajkot using SAP 2000 14 analyses
package.
(5) T. Raja Sekhar*, P.V. Prasad – The study provides up
with the behavior of building frame structure with and
without floating column and is studied for different cases of
dynamics under static load, free vibration and forced
vibration condition. The results for same is being plotted for
both the frames with and without floating column by
comparing each other for different parameteroftimehistory
of floor displacement, base shear. A 3D model using the
software STAAD Pro V8i is created and equivalent static
analysis is carried out for the entire project. Comparison of
these models are been presented. This will help to find
various analytical properties of the structure and we may
also have a very systematic and economical design for the
structure.
(6) S.S. Kadam*, D.D. Mohite*,Ms.S.V.Lale*, Ms.Waykule
S.B*, C.P. Pise, C.M. Deshmukh, Y.P. Pawar - The study
comes up with the effect of varying the location of floating
columns floor wise of multi storey RC building structure.
Attempt to mark out various structural response quantities
of the building structure using static analysis has been done.
It was being observed that with introduction of floating
column at 1st floor base shear of such building decreases as
compared to building without floating column. Along with
that it was also being found that base shear increases from
1st floor. The final observations lead to mark that
displacement of each storey of floating column building is
more than compared to without floating column building.
(7) Susanta Banerjee*, Sanjay Kumar Patra – The study
point out the effect of stiffness of infill wall to the damage
occurred in floating column building for ground shakes.Non
linear analysis programmeIDARC-2Dhasbeenusedtocarry
out modeling and analysis work. By formulating modified
Park & Ang model damages occurred in beams, columns,
storey are studied. Due to shaking of ground overall
structural damage indices in buildings are also obtained.
Various dynamic responseparametersincludingstoreydrift,
lateral floor displacement, base shear and time period of
buildings are obtained and results are compared with the
ordinary moment resisting frame buildings. Formation of
plastic hinge, cracks, yields are also being observed during
analysis. The final conclusion was being made that lateral
floor displacement, storey drift of floating column building
with infill wall are reduced in comparison to that floating
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2899
column building without infill wall. It was also being
concluded that values for fundamental time period, lateral
floor displacement of floating column building are higher
than ordinary moment resisting frame.
(8) Prerna Nautiyal*, Saleem Aktar, Geeta Batham – For
various soil conditions, since there is no provision or
magnification factor specified in I.S. Code, hence the
determination of such factors forsafeandeconomical design
of a building having floating column is difficult there paper
investigate about the effect of a floating column under
earthquake excitation for differentsoil conditions.Thestudy
is done on bases of Linear Dynamic Analysis for 2D multi
storey frame with and without floating column. To meet up
the requirements the model of G+4 and G+6 building
structures have been created, having changing the position
of floating column. Furthermore, the response spectrum
analysis is done for both building structures. Different
dynamic response parameters including base shear and
moment for hard and medium soil conditionareobtained for
both building models.
(9) Sreekanth Gandla Nanabala*, Pradeep kumar – The
literature deals with the fact to find to parameters firstly,
whether structure is safe or unsafe with floating column
when built in seismically active areas and secondly, are
floating column in buildingeconomical oruneconomical.The
whole analysis is carried by modeling of G+5 storey normal
building and one with floatingcolumnbuilding.Thisanalysis
was done by use of SAP2000 external lateral load were
calculated manually using equivalent static method for
analysis created 2D 3model, model1, model2, model3.
Model1 being a normal building with same dimension of
beam and column, model2 being with floating column
building without changing dimensions and model3 being a
floating column building with changing dimension of beam
and column. Finally, comparingthemondisplacementdueto
lateral load in terms of model1, model2, model3 and also
based on stiffness & time historyanalysis.Tocheck economy
of both building compares steel and concrete quantity in
terms of model, model2, model3 and wasconcludedthatone
with floating columns requireslarger quantity withcompare
to one that doesn’t have a floating columns.
(10) Er. Ashfi Rahman* - The study comes up with
response spectrum method for static analysis and dynamic
analysis. It’s done for multi-storeyed building structures
with and without floating columns.Byvaryingthelocationof
floating columns floor wise and within the floor different
cases of the building structure is studied. The structural
response of different parametersofthebuildingmodelswith
respect to Spectral acceleration, Base shear, Fundamental
time period, Storey drift and Storey displacements is
investigated. STAAD Pro V8i software was used to carry out
the analysis.
(11) S.B.Talavara* - It gives a comparative study of seismic
analysis of multi-storied building structures consisting of
both cases i.e. with and without floating columns. The entire
analysis is done by takingup ResponseSpectrumAnalysis,as
per IS: 1893-2002. Different features of lateral stiffness
strengthening system, including lateral bracing, shearwalls,
increasing the column size in the soft ground storey. Project
modeling is done with ETABS 3D model and the comparison
of these models are been presented withtheircombinations,
and are proposed to reduce the stiffness irregularity and
discontinuity in the load path incorporated by the soft
ground storey and the floating columns respectively. The
study consist of two models A & B and each furthermore
having five different models (namely 1A, 1B, 1C, 1D, 1E, 2A,
2B, 2C, 2D, 2E) with each one having different structural
compositions, comparison and study of these different
models have been taken up. Variousparameterssuchasbase
shear, storey drift and displacement are within the
permissible limit except the displacement provided by Time
history analysis fornormal multistoreybuilding.Provisionof
floating column could be advantageous in increasingFSItoa
certain extent of the building but is a risky factor and
increases the vulnerability of the building. Multistorey
building with shear walls comes out with the peak value of
base shear in time history analysis. It was found that shear
wall retrofit is the best method of retrofit the soft storeyasit
also reduces the displacement of the whole structure and
offers the maximum strength (frequency) and ductility. The
base shear value shows up increase for buildings with steel
braced soft story in comparison to without steel bracing
indicating increase in stiffness and ductility of building. As
per final outcomes out of all the three methods used to
evaluate base shear, Multistorey building with shear walls
were found to perform better from the points of view of
strength, stiffness, ductility and frequency profile compared
to normal multistorey building.
(12) D. Annapurna, Sriram Nadipelli* - The paper deals
with the comparison of a G+5 storey building with all
columns and a similar structure without edge columns or
with floating columns, i.e. from the first story to the top
storey all columns are present except for the ones atground.
Thus, mechanism for load transfer goes from edge columns
to the interior ones present in the ground storey. Up to the
extent applying the static loadsboththestructuresarefound
be safe but as the dynamic loads like earthquake loads in
lateral direction the structure without edge columns is
unsafe, that is displacement ofthisstructureismorethan the
structure with edge columns and stiffness of a structure is
also less than the structure with edge columns. For study
three models 1 (normal), 2 (with floating column) & 3(with
floating column and increased structural components) all
having different specifications have been prepared using
structural design and analysis software ETABS. Due to
application of lateral loads in X and Y directions the
displacements of Model 2 and Model 3 building found to be
more than displacements ofmodel 1building.SotheFloating
column buildings are unsafe for construction when
compared to a Normal building. On mitigating the problems
of model 2 in model 3 building, it was found that floating
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2900
column building can be made safe by increasing the size of
transfer girder beams and size of columns adjacent to
floating columns to which finally load is transferred.
Calculating lateral stiffness at each floor for the buildings, it
is observed that model 2 and model 3 buildings that are for
buildings with floating columns will suffer fromextremesoft
storey effect, where model 1 being a normal one is free from
soft storey effect. So the floating column building is unsafe.
Furthermore, after theanalysingandcomparingthequantity
of steel and concrete for model 1 & 3 building, from which it
is identified that model 3 building has more quantities of
rebar steel and more concrete quantities than model 1
building. So the Floating column building will be
uneconomical when compared to normal building.Fromthe
time history analysis it is noticed thatthemodel 2andmodel
3 building is having more displacements than model 1
building. Hence, floating column building seems out to be
unsafe than a normal building.
(13) Shiwli Roy*, Gargi Danda de – The paper presentsthe
floating column and RCC column analysis on multistoried
building and analyzed by STAADPROV8i.HereG+3,G+5and
G+10 structures are analyzed and compared with
parameters shear force and bendingmoment.Theanalysisis
carried out on a building structure with floating columns.
The building considered is a multistorey building having
G+3, G+5 and G+10 structures. All three models having
different heights from 12 m, 18 m & 36 m are designed and
analyzed by creating fixed support on ground storey, by
assigning dead load & live load for floating column as well as
for proper RCC column. The analysis on floating column for
G+3, G+5 and G+10 structures observes that if the height of
the structure increases, theshearforceandbendingmoment
also increases. Following are some conclusion as done on
above study: Along with that it was observed that as the
situation and orientation of columns varies the value for
column shear also varies. On comparison for shear force for
G+3 with normal column, floating column (column removed
from G.F.) and floating column 1 (column removed between
F.F. & S.F.) the variation shows that the shear force is
maximum in floating column (column removed from G.F.)
the shear force increases by a value about 57% for G+3
(normal column) to G+3 (floating column) structures and
6.67% for G+3 (floating column) to G+3 (floating
column1)structures in column1 (column for G.F.) and in
column2 (column for F.F.) it increases by 56% for G+ 3
(normal column) to G+3 (floating column)structures and
3.42% for G+3 (floating column) to G+3 (floating column1)
structures. While on comparison for bending moment for
G+3 structure in normal column, floating column (column
removed from G.F.) and floating column 1 (column removed
between F.F. & S.F.) it was found that the variation in
bending moment shows that the bending moment is
maximum in floating column 1 (column removed between
F.F. & S.F.) the bending moment increasesby10.25%for G+3
(normal column) to G+3 (floating column) structures and
12.82% for G+3 (floating column) to G+3 (floating column1)
structures in column1 (column for ground floor) and in
column2 (column for F.F.) it increases by 5.98% for G+3
(normal column) to G+3 (floating column) structures and
11.96% for G+3 (floating column) to G+3 (floating column1)
structures.
(14) Sampath KumarM.P.*,V.S.Jagadeesh – Theliterature
analyze tall structures with floating column basically
includes a preparatory outline, theoretical outline,
advancement and clear investigation to securely convey
gravity and lateral loads. The outline criteria include
serviceability, strength, stability and human comfort.
Floating column is a vertical component which closes at its
lower load level and lies on beam and exchange the load of
the structure through column to beam. The conclusions as
per there study were that lateral displacement increases
with the height of the building. The displacement parameter
is more for the floating column buildings compared with the
regular building. Similarly, it was found building structures
displacement increases with the height of column. Mass
irregularities of buildingseemtoposseshigherdisplacement
than that of regular building and soft story building. Inter
storey drift increases from top storey, later the storey drift
reduces due to stiffness near fixed end at base. As the
stiffness and mass parameter increases the base shear also
increases. Base shear is observed lesser in the floating
column building when compare to regular building due to
decrease in column weight. Finally,fromthestudyconcludes
that as for as possible, the floating columns should be
avoided, especially in the seismic prone areas.
(15) Niteen Malu*, Amaresh.S.Patil – As per scope of this
literature a G+10 storey building structure is taken for the
analysis. Building frame being prepared in ETABS by
defining beam, column and slab. Slab was modelled as thin
membrane. Frame elements being taken as rigid. Hinges
being also assigned to these frame elements. These hinges
are default hinges available in ETABS. For seismic analysis
structures in earthquake zone II and zone V with soil type II
(medium soil) were considered. Four different models were
created in ETABS constituting of Regular building (with &
without floating columns) and Irregular building (with &
without floating columns). Their analysis and outcomes
include, as the magnitude of intensitywill bemoreforhigher
zones, a sudden increase in displacement about 18-23%
could be seen from lower zones to higher zones. It was also
observed base shear performance of buildings was more for
case of structure without floating column in comparison to
those with floating columns. The parameters like bending
moment and shear force in column where the floating
column is provided at storey 5 is found to be more about
45% and 40% in compare to similar storey without floating
columns.
3. CONCLUSIONS
After going through all above literature reviews there were
certain conclusions to be marked out for longer
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2901
sustainability of structures some of these marked out points
have been discussed below:
1. It was observed that building structures with
floating column comes out with less base shear as
compared to ones without floating column.
2. Displacement factor for floating column building
observes out to be more than compared to without
floating column building.
3. Talking about storey drift it was found to be more
for building structures with floating column as
compared to building without floating column.
4. From dynamic analysis point of view it was
observed that floating column at different location
results into variation in dynamic response.
5. Buildings with floatingcolumnobservedouttohave
more time period as compared to building without
floating columns.
6. It was also found that as shift of floating column
starts towards top of the building it results out in
increasing time period which is majorly because of
decreased lateral stiffness of the building.
7. As we increase the number of storey’s the inter
storey drift also increases. The storey drift is more
for the floating column buildings because as the
columns are removed the mass gets increased.
8. On calculation analysis of lateral stiffness at each
floor for most of the buildings it is observed that
floating column building will suffer extreme soft
storey effect where normal buildingisfreefromsoft
storey effect. Making the floating column building
unsafe.
9. After overall analysis of buildings, it was found on
comparing for quantity of steel and concrete it was
found there was increase in both physical
parameters for building structures with floating
column building than a normal building. Ultimately
making floating column building uneconomical.
10. From the study of all above literature review it was
observed that there is still a lot of study required to
make sure that provision of floating column in
building to be safe from earthquake point ofview.It
have been observed from almost all literature
review the building structures without floating
columns seems to give better resultsascomparedto
floating column building so morestudyrequiredfor
this. Hence, finally from the study it can be
concluded that as far as possible, the floating
columns are to be avoided especially, in the seismic
prone areas.
REFERENCES
[1]. Sukumar Behera Seismic analysis of multistory
building with floating column, Department of Civil
Engineering, National InstituteofTechnologyRourkela (May
2012).
[2]. A.P.Mundada Comparative seismic analysis of multi
storey building with and without floating column,
International Journal of Current Engineering and
Technology, Vol.4, No.5 (Oct 2014)
[3]. Shrikanth M.K. Seismic response of complex building
with floating column and without floating column,
International journal ofEngineeringResearch-Online.APeer
Reviewed International Journal. Vol. 2, Issue 4, (2014).
[4]. Hardik.Bhensdadia Pushover analysis of RC structure
with floating column and soft storey in different earthquake
zones, frame International Journal of Research in
Engineering and Technology. Vol. 4, Issue 4 (Apr-2015).
[5]. T. Raja. Sekhar Study of behavior of seismic analysis of
multistory building with and without floating column,
SciTech, Vol 2, pp 697-710, (2014).
[6]. Ms. Waykule S.B et al Comparative Study of floating
column of multi storey building by using software, Int.
Journal of Engineering Research and Application, Vol. 7,
Issue 1, ( Part -3), pp.31-38 (January 2017).
[7]. Susanta Banerjee and Dr. Sanjaya K Patro Estimation
of park-Ang damage index for floating column building with
infill wall, 55th Annual Technical, Journal of Orissa State
Centre, Institute of Engineers (India), pp.211-217 (2014).
[8]. Prerna Nautiyal Seismic response evaluation of R.C.
frame building with floating column considering different
soil conditions , International Journal ofCurrentEngineering
and Technology, Vol.4, No.1 (2014).
[9]. Sreekanth Gandla Nanabala Seismic analysis of a
normal building and floating column building, International
Journal of Engineering Research & Technology (2014).
[10]. Er. Ashfi Rahma Effect of FloatingColumnsonSeismic
ResponseofMulti-StoredRCFramedBuildings,International
Journal of Engineering Research & Technology, Vol. 4 Issue
06, (June-2015).
[11]. Rahul Kapase, Mukund Pawar, M.M. Deshmukh,
S.B.Talavara Effect of Seismic Retrofitting on R.C. Building
with Soft Storey and Floating Column, International Journal
of Engineering Trends and Technology, Vol. 46, No. 7, (April
2017).
[12]. D. Annapurna, Sriram Nadipelli Comparative study
of seismic analysis of a normal building and building with
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2902
floating columns, IJRET, Vol. 04, Special Issue: 13, ICISE-
2015, (Dec-2015).
[13]. Shiwli Roy, Gargi Danda de Behavioural studies of
floating column on framed structure, IJRET, Vol. 09, Issue:
09, (Sept. -2015).
[14]. Sampath Kumar M.P, V.S. Jagadeesh Effectoffloating
columns on seismic response of multistory building,
International Research Journal of Engineering and
Technology, Vol. 03, Issue: 09, (Sep -2016).
[15]. Niteen Malu, Amaresh.S.Patil Performance of RC
frame structure with floating column and soft storey in
different earthquake zones using pushover analysis,
International Research Journal of Engineering and
Technology, Vol. 04, Issue 09, (Sep 2017).
[16]. Vijayanarayanan. R, Rupen Goswami and
C.V.R.Murty Special class of open ground storey RC
buildings built in india unsafe during earthquakes
67Department of Civil Engineering, IIT-Madras. pp. 0147.
[17]. Agarwal Pankaj, Shrikhande Manish Earthquake
resistant design of structures PHI learning private limited
(2009).
[18]. Criteria for Earthquake Resistant design of structures,
Part1: General provisions and buildings, IS 1893:2002,
Bureau of Indian Standards, New Delhi.
[19]. IS 875 (Part-I) Bureau ofIndianStandards(1987)Code
of Practice for Design Loads (Other than Earthquake) for
Buildings and Structures: Dead Loads-Unit Weights of
Building Materials and Stored Materials (Second Revision).
UDC 624.042: 006.76.
[20]. IS 875 (Part-II) Bureau of Indian Standards (1987)
Code of Practice for Design Loads For Buildings and
Structures: Imposed Loads (Second Revision).
UDC 624.042.3: 006.76.

More Related Content

What's hot

Significance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A ReviewSignificance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A ReviewIRJET Journal
 
Chronological construction sequence effects on reinforced concrete and steel ...
Chronological construction sequence effects on reinforced concrete and steel ...Chronological construction sequence effects on reinforced concrete and steel ...
Chronological construction sequence effects on reinforced concrete and steel ...Yousuf Dinar
 
P delta effect in reinforced concrete structures of rigid joint
P  delta effect in reinforced concrete structures of rigid jointP  delta effect in reinforced concrete structures of rigid joint
P delta effect in reinforced concrete structures of rigid jointYousuf Dinar
 
P- Delta Effect in Reinforced Concrete Structures of Rigid joint
P- Delta Effect in Reinforced Concrete Structures of Rigid joint P- Delta Effect in Reinforced Concrete Structures of Rigid joint
P- Delta Effect in Reinforced Concrete Structures of Rigid joint IOSR Journals
 
P-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear WallP-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear WallIRJET Journal
 
Performance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisPerformance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisIOSR Journals
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular StructureIRJET Journal
 
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...IRJET Journal
 
Seismic performance study on rc wall buildings from pushover analysis
Seismic performance study on rc wall buildings from pushover analysisSeismic performance study on rc wall buildings from pushover analysis
Seismic performance study on rc wall buildings from pushover analysiseSAT Publishing House
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET Journal
 
Seismic response of multi storey irregular building with floating column
Seismic response of multi storey irregular building with floating columnSeismic response of multi storey irregular building with floating column
Seismic response of multi storey irregular building with floating columneSAT Journals
 
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...IRJET Journal
 
IRJET- Non Linear Static Analysis of Frame with and without Infills
IRJET- Non Linear Static Analysis of Frame with and without InfillsIRJET- Non Linear Static Analysis of Frame with and without Infills
IRJET- Non Linear Static Analysis of Frame with and without InfillsIRJET Journal
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...IRJET Journal
 
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...IRJET Journal
 
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET Journal
 
Descriptive study of pushover analysis in rcc structures of rigid joint
Descriptive study of pushover analysis in rcc structures of rigid jointDescriptive study of pushover analysis in rcc structures of rigid joint
Descriptive study of pushover analysis in rcc structures of rigid jointYousuf Dinar
 
IRJET- Comparative Analysis of Seismic Performance of R.C Building Restin...
IRJET-  	  Comparative Analysis of Seismic Performance of R.C Building Restin...IRJET-  	  Comparative Analysis of Seismic Performance of R.C Building Restin...
IRJET- Comparative Analysis of Seismic Performance of R.C Building Restin...IRJET Journal
 
IRJET- Analysis and Design of Regular and Irregular Buildings
IRJET- Analysis and Design of Regular and Irregular BuildingsIRJET- Analysis and Design of Regular and Irregular Buildings
IRJET- Analysis and Design of Regular and Irregular BuildingsIRJET Journal
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisIJMER
 

What's hot (20)

Significance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A ReviewSignificance of shear wall in flat slab multi storied building - A Review
Significance of shear wall in flat slab multi storied building - A Review
 
Chronological construction sequence effects on reinforced concrete and steel ...
Chronological construction sequence effects on reinforced concrete and steel ...Chronological construction sequence effects on reinforced concrete and steel ...
Chronological construction sequence effects on reinforced concrete and steel ...
 
P delta effect in reinforced concrete structures of rigid joint
P  delta effect in reinforced concrete structures of rigid jointP  delta effect in reinforced concrete structures of rigid joint
P delta effect in reinforced concrete structures of rigid joint
 
P- Delta Effect in Reinforced Concrete Structures of Rigid joint
P- Delta Effect in Reinforced Concrete Structures of Rigid joint P- Delta Effect in Reinforced Concrete Structures of Rigid joint
P- Delta Effect in Reinforced Concrete Structures of Rigid joint
 
P-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear WallP-Delta Effects on Tall RC Buildings with and Without Shear Wall
P-Delta Effects on Tall RC Buildings with and Without Shear Wall
 
Performance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover AnalysisPerformance of Flat Slab Structure Using Pushover Analysis
Performance of Flat Slab Structure Using Pushover Analysis
 
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
IRJET-  	  Study of Literature on Seismic Response of RC Irregular StructureIRJET-  	  Study of Literature on Seismic Response of RC Irregular Structure
IRJET- Study of Literature on Seismic Response of RC Irregular Structure
 
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...
IRJET- Comparative Study of Seismic Analysis of Multi Storied Building with a...
 
Seismic performance study on rc wall buildings from pushover analysis
Seismic performance study on rc wall buildings from pushover analysisSeismic performance study on rc wall buildings from pushover analysis
Seismic performance study on rc wall buildings from pushover analysis
 
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...IRJET-  	  Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
IRJET- Seismic Analysis of Buildings with Shear Wall having Horizontal Ir...
 
Seismic response of multi storey irregular building with floating column
Seismic response of multi storey irregular building with floating columnSeismic response of multi storey irregular building with floating column
Seismic response of multi storey irregular building with floating column
 
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...
IRJET- Review Paper on Comparative Analysis of Flat Slabs & Conventional RC S...
 
IRJET- Non Linear Static Analysis of Frame with and without Infills
IRJET- Non Linear Static Analysis of Frame with and without InfillsIRJET- Non Linear Static Analysis of Frame with and without Infills
IRJET- Non Linear Static Analysis of Frame with and without Infills
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
 
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...
IRJET- Static and Dynamic Analysis of Multistorey Buildings having Floating C...
 
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
 
Descriptive study of pushover analysis in rcc structures of rigid joint
Descriptive study of pushover analysis in rcc structures of rigid jointDescriptive study of pushover analysis in rcc structures of rigid joint
Descriptive study of pushover analysis in rcc structures of rigid joint
 
IRJET- Comparative Analysis of Seismic Performance of R.C Building Restin...
IRJET-  	  Comparative Analysis of Seismic Performance of R.C Building Restin...IRJET-  	  Comparative Analysis of Seismic Performance of R.C Building Restin...
IRJET- Comparative Analysis of Seismic Performance of R.C Building Restin...
 
IRJET- Analysis and Design of Regular and Irregular Buildings
IRJET- Analysis and Design of Regular and Irregular BuildingsIRJET- Analysis and Design of Regular and Irregular Buildings
IRJET- Analysis and Design of Regular and Irregular Buildings
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
 

Similar to IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Structure with and without Floating Columns

IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...IRJET Journal
 
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...IRJET Journal
 
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET Journal
 
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...IRJET Journal
 
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...IRJET Journal
 
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear WallSeismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear WallIRJET Journal
 
Effect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumEffect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumIRJET Journal
 
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...IRJET Journal
 
Earthquake Analysis of Multi-Storied Buildings with Floating Columns
Earthquake Analysis of Multi-Storied Buildings with Floating ColumnsEarthquake Analysis of Multi-Storied Buildings with Floating Columns
Earthquake Analysis of Multi-Storied Buildings with Floating ColumnsIRJET Journal
 
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET Journal
 
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...ijtsrd
 
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating ColumnsA Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columnsijtsrd
 
IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...
IRJET-  	  Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...IRJET-  	  Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...
IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...IRJET Journal
 
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...IRJET Journal
 
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...IRJET Journal
 
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...IRJET Journal
 
IRJET- Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review PaperIRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET- Analytical Study of Punching Shear in Flat Slab - Review PaperIRJET Journal
 
A Literature Review On Seismic Response Of Floating Column Building
A Literature Review On Seismic Response Of Floating Column BuildingA Literature Review On Seismic Response Of Floating Column Building
A Literature Review On Seismic Response Of Floating Column BuildingRobin Beregovska
 
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...IRJET Journal
 
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...IRJET Journal
 

Similar to IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Structure with and without Floating Columns (20)

IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
 
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
 
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
 
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
 
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...
IRJET- Experimental Study of Floating Column for Seismic Analysis of Multisto...
 
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear WallSeismic Response of Multi storey Flat Slab Building with and without Shear Wall
Seismic Response of Multi storey Flat Slab Building with and without Shear Wall
 
Effect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with PodiumEffect of Backstay on Tall Structures with Podium
Effect of Backstay on Tall Structures with Podium
 
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...
IRJET- A Review on Analysis of Soft Story at Intermediate Levels in a Multi-S...
 
Earthquake Analysis of Multi-Storied Buildings with Floating Columns
Earthquake Analysis of Multi-Storied Buildings with Floating ColumnsEarthquake Analysis of Multi-Storied Buildings with Floating Columns
Earthquake Analysis of Multi-Storied Buildings with Floating Columns
 
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
 
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
 
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating ColumnsA Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
 
IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...
IRJET-  	  Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...IRJET-  	  Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...
IRJET- Seismic Behavior of RC Flat Slab with and without Shear Wall Techn...
 
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
STUDIES OF ANALYSIS AND DESIGN FOR MULTI-STORIES STRUCTURES WITH TRANSFER PLA...
 
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...
IRJET- Review Paper on Convincement based Seismic Design of Open Ground Store...
 
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
IRJET- Comparative Analysis of Seismic Behavior of Flat Slab and Conventional...
 
IRJET- Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review PaperIRJET-  	  Analytical Study of Punching Shear in Flat Slab - Review Paper
IRJET- Analytical Study of Punching Shear in Flat Slab - Review Paper
 
A Literature Review On Seismic Response Of Floating Column Building
A Literature Review On Seismic Response Of Floating Column BuildingA Literature Review On Seismic Response Of Floating Column Building
A Literature Review On Seismic Response Of Floating Column Building
 
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...Seismic Performance and Shear Wall Location  Assessment of a RC Building- Eva...
Seismic Performance and Shear Wall Location Assessment of a RC Building- Eva...
 
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...
IRJET- Comparative Study & Seismic Anyalysis of Regular and Irregular Geometr...
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTUREIRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsIRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASIRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProIRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemIRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesIRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web applicationIRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignIRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 

Recently uploaded (20)

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 

IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Structure with and without Floating Columns

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2897 A REVIEW ON SEISMIC ANALYSIS AND SUSTAINABILITY OF MULTI STOREY STRUCTURE WITH AND WITHOUT FLOATING COLUMNS Er. Shashank Kalla1, Er. Om Prakash Singh2, Dr. Shailesh Choudhary3 1M.E. Scholar, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur 2Ph.D. Scholar, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur 3Associate Professor, Department of Structural Engineering, M.B.M. College J.N.V.U Jodhpur ---------------------------------------------------------------------***---------------------------------------------------------------------- Abstract - With escalating urbanization, demand for greater spaces either in form of parking spaces, or in form of aesthetic view point or for ambiance from architectural verse sometimes let structural designer to plan andactaccordingto it. Construction of multistorey structures with floating columns have been never a choice of preference for any structural engineer rather than being a demand or requirement from either owner or architect. But such structures are highly susceptible to be damaged during earthquakes in highly seismic zone as compared to normal structures. The paper turns out with static analysis done for multistorey structures with and without floating columns along with different cases of building structure are analyzed by varying the location of floating columns floor wise. The structural response of building models with respect to storey drift, storey displacement, base shear and time periodforboth building. The analysis is carried out using different structural analysis and design software SAP2000v17, STAAD-PRO and ETABS. Key Words: Floating column, Earthquake analysis, Multi- storey, Linear static method, Time history method, SAP2000v17, STAAD-PRO, ETABS. 1. INTRODUCTION Now a day’s, multistorey structures in urban cities are required to have column free space due to shortageofspace, increasing population and also for aesthetic and functional requirements. To cope with such problems of parking accommodations or reception lobbies most of multistorey structures in India today prefers to have an open first storey as an unavoidable feature or finds it aseasiestsolutionto the problem. Thus, to meet-up with situation use of floating columns starts, now talking about floating columns it’s a vertical member without a foundation i.e. it rests on a beam. Being without foundation this floating columncomesupasa point load over the beam and further this beamtransfersthe load to the columns below it. The floatingcolumnsometimes also serves purpose of architectural view and sitesituations. The Provision of floating columns can be stated as most of the buildings in India are covering the maximum possible area on a plot within the available by laws. Thus most times for fulfilling the desires we neglect behaviour of a building structures during earthquakes as it depends critically on geometry, size and overall shape, in addition with how the earthquake forces are carried to the ground. Hence, ultimately not following basics of dynamic of structuresthat earthquake forces developed at different floor levelsneed to be brought down along the height to the ground by the shortest path; any deviation or discontinuity here with load transfer path results in poor performance of the building structure. It had been found most of the energy developed during earthquake is dissipated by columns of the soft stories. Further transfer of this energy leads to formation of plastic hinges at the ends of columns, which transform the soft storey into a mechanism finally in such casethecollapse is unavoidable. Building structures with vertical setbacks (like the hotel buildings, malls, etc. with a few storey wider than the rest) are most susceptibletocausea suddenjumpin earthquake forces at the level of discontinuity. Structures with fewer columns or walls in a particular storey or with unusually tall storey tend to damage or collapse which is initiated in that storey. These are highly undesirable in building built in seismically active areas usually the civil engineering infra structures are subjected to two classes of loads, static and dynamic loads. The staticloadssuchasdead load and live load are independent with respect to time in case of dynamic loads, they are changing with respect to time. Most of the cases the structures are designed with the assumptions that all the loads applied are static. Generally the dynamic loads i.e. earthquake loads are not taking account in the design because the buildingsarenotregularly subjected to earthquakes, and also it takes more time to solve these parameters in the analysis and also its more difficult to solve the solution. It has been analyzed by using various designs and structural analysis software that for an open ground storey frame, retrofitting by introducing reinforced concrete wall in the open ground storey, offers the maximum strength and ductility. Building structures with columnsthathangorfloat on beams at intermediate storey and not to go all the way to the foundation, have discontinuitiesintheloadtransferpath. These floating columns are highly disadvantageous in a building built in seismically active areas, especially after the desolating Nepal earthquake 25 April 2015 and tragic example of Bhuj earthquake occurred on 26 January, 2001 there have been a mutual effort throughout India to provide more awareness, especially in practice and education, with respect to earthquake resistant design of structures. Sustainability of such building structures could be achieved up-to a certain extent by providing seismic retrofitting, as it can be done in different ways and to various extents. The
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2898 purpose should be to certify that the building takes all the damage, but does not collapse when severe earthquake occurs. 2. REVIEW OF LITERATURE (1) Sukumar Bahera* - Their literature comes up with stiffness balance of first storey and above storey are studied with the aim to minimize irregularity occurring with due presence of a floating column. To make sure how structures under different earthquake excitation having a different frequency content responses keeping the time duration factor and PGA constant they develop FEM codes for 2D frames with and without floating column. This behaviour of building structure frames with and withoutfloating columns is studied for cases under static load, free vibration and forced vibration condition. For developingthefinite element codes MATLAB is used as primary platform. Various computations including inter storey drift, overturning moment, base shear, time history of floor displacement has been done for both the frames with and without floating column. Furthermore,studyfordynamic analysisofframeby varying the column dimension had also been done. It concludes that, with increment in ground floor column values for the maximum displacement and inter storey drift seems to be reduced. The change in column dimension also leads to variation in base shear and overturning moment. (2) A.P. Mundada*, S.G. Sawadakar - The paper covers up the study for architectural and the framing drawing of the building structure havingfloatingcolumns.Acomparison for a G+7 existing residential building structure with and without floating column are taken to carry out entireproject work. The design creation of models and equivalent static analysis of the models both have been done through the use of STAAD ProV8i. Various parameters including moment distribution, importance of line of action of force, axial load and seismic factors are studied for designed models. Thus, finally provides an edge to find various analytical properties of the structure as well as provides criteria for very systematic and economical design for the structure. (3) Shrikanth M.K*, YogendraR.Holebu – Theliteratureis about comparison of study for the behavior of a building structure having only floating column and having floating column with complexities. Highrisebuildingstructureshave been analyzed for different intensity of earthquake force. The study consist of creation of four models and analysis for lower and higher seismic zones at medium soil condition. Analysis being carried outwithhelpofextended3-Danalysis of building system ETAB version 9.7.4software.Resultbeing computed in regarding soft storey, storey drift and displacement for designed four models and finallytabulated on basis of linear seismic analysis. (4) Hardik Bhensdadia*, Siddarth Shah – Theirstudyis an attempt made to evaluate the effects of floating column & soft story in different earthquake zones by seismic analysis. As the analysis yieldsperformancelevel ofbuildingstructure for design capacity (displacement) carried out up to failure and to meet out this requirement methodology of push over analysis is being adopted as it helps in determination of collapse load and ductility capacity of the structure. For fulfillment of this objective three RC bare frame structures constituting of G+4, G+9, G+15 stories respectively have been analysed and compared for base force and displacement of RC bare frame structure with G+4, G+9, G+15 stories. Providing different earthquakezonesintensity like Bhuj, Jamnagar and Rajkot using SAP 2000 14 analyses package. (5) T. Raja Sekhar*, P.V. Prasad – The study provides up with the behavior of building frame structure with and without floating column and is studied for different cases of dynamics under static load, free vibration and forced vibration condition. The results for same is being plotted for both the frames with and without floating column by comparing each other for different parameteroftimehistory of floor displacement, base shear. A 3D model using the software STAAD Pro V8i is created and equivalent static analysis is carried out for the entire project. Comparison of these models are been presented. This will help to find various analytical properties of the structure and we may also have a very systematic and economical design for the structure. (6) S.S. Kadam*, D.D. Mohite*,Ms.S.V.Lale*, Ms.Waykule S.B*, C.P. Pise, C.M. Deshmukh, Y.P. Pawar - The study comes up with the effect of varying the location of floating columns floor wise of multi storey RC building structure. Attempt to mark out various structural response quantities of the building structure using static analysis has been done. It was being observed that with introduction of floating column at 1st floor base shear of such building decreases as compared to building without floating column. Along with that it was also being found that base shear increases from 1st floor. The final observations lead to mark that displacement of each storey of floating column building is more than compared to without floating column building. (7) Susanta Banerjee*, Sanjay Kumar Patra – The study point out the effect of stiffness of infill wall to the damage occurred in floating column building for ground shakes.Non linear analysis programmeIDARC-2Dhasbeenusedtocarry out modeling and analysis work. By formulating modified Park & Ang model damages occurred in beams, columns, storey are studied. Due to shaking of ground overall structural damage indices in buildings are also obtained. Various dynamic responseparametersincludingstoreydrift, lateral floor displacement, base shear and time period of buildings are obtained and results are compared with the ordinary moment resisting frame buildings. Formation of plastic hinge, cracks, yields are also being observed during analysis. The final conclusion was being made that lateral floor displacement, storey drift of floating column building with infill wall are reduced in comparison to that floating
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2899 column building without infill wall. It was also being concluded that values for fundamental time period, lateral floor displacement of floating column building are higher than ordinary moment resisting frame. (8) Prerna Nautiyal*, Saleem Aktar, Geeta Batham – For various soil conditions, since there is no provision or magnification factor specified in I.S. Code, hence the determination of such factors forsafeandeconomical design of a building having floating column is difficult there paper investigate about the effect of a floating column under earthquake excitation for differentsoil conditions.Thestudy is done on bases of Linear Dynamic Analysis for 2D multi storey frame with and without floating column. To meet up the requirements the model of G+4 and G+6 building structures have been created, having changing the position of floating column. Furthermore, the response spectrum analysis is done for both building structures. Different dynamic response parameters including base shear and moment for hard and medium soil conditionareobtained for both building models. (9) Sreekanth Gandla Nanabala*, Pradeep kumar – The literature deals with the fact to find to parameters firstly, whether structure is safe or unsafe with floating column when built in seismically active areas and secondly, are floating column in buildingeconomical oruneconomical.The whole analysis is carried by modeling of G+5 storey normal building and one with floatingcolumnbuilding.Thisanalysis was done by use of SAP2000 external lateral load were calculated manually using equivalent static method for analysis created 2D 3model, model1, model2, model3. Model1 being a normal building with same dimension of beam and column, model2 being with floating column building without changing dimensions and model3 being a floating column building with changing dimension of beam and column. Finally, comparingthemondisplacementdueto lateral load in terms of model1, model2, model3 and also based on stiffness & time historyanalysis.Tocheck economy of both building compares steel and concrete quantity in terms of model, model2, model3 and wasconcludedthatone with floating columns requireslarger quantity withcompare to one that doesn’t have a floating columns. (10) Er. Ashfi Rahman* - The study comes up with response spectrum method for static analysis and dynamic analysis. It’s done for multi-storeyed building structures with and without floating columns.Byvaryingthelocationof floating columns floor wise and within the floor different cases of the building structure is studied. The structural response of different parametersofthebuildingmodelswith respect to Spectral acceleration, Base shear, Fundamental time period, Storey drift and Storey displacements is investigated. STAAD Pro V8i software was used to carry out the analysis. (11) S.B.Talavara* - It gives a comparative study of seismic analysis of multi-storied building structures consisting of both cases i.e. with and without floating columns. The entire analysis is done by takingup ResponseSpectrumAnalysis,as per IS: 1893-2002. Different features of lateral stiffness strengthening system, including lateral bracing, shearwalls, increasing the column size in the soft ground storey. Project modeling is done with ETABS 3D model and the comparison of these models are been presented withtheircombinations, and are proposed to reduce the stiffness irregularity and discontinuity in the load path incorporated by the soft ground storey and the floating columns respectively. The study consist of two models A & B and each furthermore having five different models (namely 1A, 1B, 1C, 1D, 1E, 2A, 2B, 2C, 2D, 2E) with each one having different structural compositions, comparison and study of these different models have been taken up. Variousparameterssuchasbase shear, storey drift and displacement are within the permissible limit except the displacement provided by Time history analysis fornormal multistoreybuilding.Provisionof floating column could be advantageous in increasingFSItoa certain extent of the building but is a risky factor and increases the vulnerability of the building. Multistorey building with shear walls comes out with the peak value of base shear in time history analysis. It was found that shear wall retrofit is the best method of retrofit the soft storeyasit also reduces the displacement of the whole structure and offers the maximum strength (frequency) and ductility. The base shear value shows up increase for buildings with steel braced soft story in comparison to without steel bracing indicating increase in stiffness and ductility of building. As per final outcomes out of all the three methods used to evaluate base shear, Multistorey building with shear walls were found to perform better from the points of view of strength, stiffness, ductility and frequency profile compared to normal multistorey building. (12) D. Annapurna, Sriram Nadipelli* - The paper deals with the comparison of a G+5 storey building with all columns and a similar structure without edge columns or with floating columns, i.e. from the first story to the top storey all columns are present except for the ones atground. Thus, mechanism for load transfer goes from edge columns to the interior ones present in the ground storey. Up to the extent applying the static loadsboththestructuresarefound be safe but as the dynamic loads like earthquake loads in lateral direction the structure without edge columns is unsafe, that is displacement ofthisstructureismorethan the structure with edge columns and stiffness of a structure is also less than the structure with edge columns. For study three models 1 (normal), 2 (with floating column) & 3(with floating column and increased structural components) all having different specifications have been prepared using structural design and analysis software ETABS. Due to application of lateral loads in X and Y directions the displacements of Model 2 and Model 3 building found to be more than displacements ofmodel 1building.SotheFloating column buildings are unsafe for construction when compared to a Normal building. On mitigating the problems of model 2 in model 3 building, it was found that floating
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2900 column building can be made safe by increasing the size of transfer girder beams and size of columns adjacent to floating columns to which finally load is transferred. Calculating lateral stiffness at each floor for the buildings, it is observed that model 2 and model 3 buildings that are for buildings with floating columns will suffer fromextremesoft storey effect, where model 1 being a normal one is free from soft storey effect. So the floating column building is unsafe. Furthermore, after theanalysingandcomparingthequantity of steel and concrete for model 1 & 3 building, from which it is identified that model 3 building has more quantities of rebar steel and more concrete quantities than model 1 building. So the Floating column building will be uneconomical when compared to normal building.Fromthe time history analysis it is noticed thatthemodel 2andmodel 3 building is having more displacements than model 1 building. Hence, floating column building seems out to be unsafe than a normal building. (13) Shiwli Roy*, Gargi Danda de – The paper presentsthe floating column and RCC column analysis on multistoried building and analyzed by STAADPROV8i.HereG+3,G+5and G+10 structures are analyzed and compared with parameters shear force and bendingmoment.Theanalysisis carried out on a building structure with floating columns. The building considered is a multistorey building having G+3, G+5 and G+10 structures. All three models having different heights from 12 m, 18 m & 36 m are designed and analyzed by creating fixed support on ground storey, by assigning dead load & live load for floating column as well as for proper RCC column. The analysis on floating column for G+3, G+5 and G+10 structures observes that if the height of the structure increases, theshearforceandbendingmoment also increases. Following are some conclusion as done on above study: Along with that it was observed that as the situation and orientation of columns varies the value for column shear also varies. On comparison for shear force for G+3 with normal column, floating column (column removed from G.F.) and floating column 1 (column removed between F.F. & S.F.) the variation shows that the shear force is maximum in floating column (column removed from G.F.) the shear force increases by a value about 57% for G+3 (normal column) to G+3 (floating column) structures and 6.67% for G+3 (floating column) to G+3 (floating column1)structures in column1 (column for G.F.) and in column2 (column for F.F.) it increases by 56% for G+ 3 (normal column) to G+3 (floating column)structures and 3.42% for G+3 (floating column) to G+3 (floating column1) structures. While on comparison for bending moment for G+3 structure in normal column, floating column (column removed from G.F.) and floating column 1 (column removed between F.F. & S.F.) it was found that the variation in bending moment shows that the bending moment is maximum in floating column 1 (column removed between F.F. & S.F.) the bending moment increasesby10.25%for G+3 (normal column) to G+3 (floating column) structures and 12.82% for G+3 (floating column) to G+3 (floating column1) structures in column1 (column for ground floor) and in column2 (column for F.F.) it increases by 5.98% for G+3 (normal column) to G+3 (floating column) structures and 11.96% for G+3 (floating column) to G+3 (floating column1) structures. (14) Sampath KumarM.P.*,V.S.Jagadeesh – Theliterature analyze tall structures with floating column basically includes a preparatory outline, theoretical outline, advancement and clear investigation to securely convey gravity and lateral loads. The outline criteria include serviceability, strength, stability and human comfort. Floating column is a vertical component which closes at its lower load level and lies on beam and exchange the load of the structure through column to beam. The conclusions as per there study were that lateral displacement increases with the height of the building. The displacement parameter is more for the floating column buildings compared with the regular building. Similarly, it was found building structures displacement increases with the height of column. Mass irregularities of buildingseemtoposseshigherdisplacement than that of regular building and soft story building. Inter storey drift increases from top storey, later the storey drift reduces due to stiffness near fixed end at base. As the stiffness and mass parameter increases the base shear also increases. Base shear is observed lesser in the floating column building when compare to regular building due to decrease in column weight. Finally,fromthestudyconcludes that as for as possible, the floating columns should be avoided, especially in the seismic prone areas. (15) Niteen Malu*, Amaresh.S.Patil – As per scope of this literature a G+10 storey building structure is taken for the analysis. Building frame being prepared in ETABS by defining beam, column and slab. Slab was modelled as thin membrane. Frame elements being taken as rigid. Hinges being also assigned to these frame elements. These hinges are default hinges available in ETABS. For seismic analysis structures in earthquake zone II and zone V with soil type II (medium soil) were considered. Four different models were created in ETABS constituting of Regular building (with & without floating columns) and Irregular building (with & without floating columns). Their analysis and outcomes include, as the magnitude of intensitywill bemoreforhigher zones, a sudden increase in displacement about 18-23% could be seen from lower zones to higher zones. It was also observed base shear performance of buildings was more for case of structure without floating column in comparison to those with floating columns. The parameters like bending moment and shear force in column where the floating column is provided at storey 5 is found to be more about 45% and 40% in compare to similar storey without floating columns. 3. CONCLUSIONS After going through all above literature reviews there were certain conclusions to be marked out for longer
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2901 sustainability of structures some of these marked out points have been discussed below: 1. It was observed that building structures with floating column comes out with less base shear as compared to ones without floating column. 2. Displacement factor for floating column building observes out to be more than compared to without floating column building. 3. Talking about storey drift it was found to be more for building structures with floating column as compared to building without floating column. 4. From dynamic analysis point of view it was observed that floating column at different location results into variation in dynamic response. 5. Buildings with floatingcolumnobservedouttohave more time period as compared to building without floating columns. 6. It was also found that as shift of floating column starts towards top of the building it results out in increasing time period which is majorly because of decreased lateral stiffness of the building. 7. As we increase the number of storey’s the inter storey drift also increases. The storey drift is more for the floating column buildings because as the columns are removed the mass gets increased. 8. On calculation analysis of lateral stiffness at each floor for most of the buildings it is observed that floating column building will suffer extreme soft storey effect where normal buildingisfreefromsoft storey effect. Making the floating column building unsafe. 9. After overall analysis of buildings, it was found on comparing for quantity of steel and concrete it was found there was increase in both physical parameters for building structures with floating column building than a normal building. Ultimately making floating column building uneconomical. 10. From the study of all above literature review it was observed that there is still a lot of study required to make sure that provision of floating column in building to be safe from earthquake point ofview.It have been observed from almost all literature review the building structures without floating columns seems to give better resultsascomparedto floating column building so morestudyrequiredfor this. Hence, finally from the study it can be concluded that as far as possible, the floating columns are to be avoided especially, in the seismic prone areas. REFERENCES [1]. Sukumar Behera Seismic analysis of multistory building with floating column, Department of Civil Engineering, National InstituteofTechnologyRourkela (May 2012). [2]. A.P.Mundada Comparative seismic analysis of multi storey building with and without floating column, International Journal of Current Engineering and Technology, Vol.4, No.5 (Oct 2014) [3]. Shrikanth M.K. Seismic response of complex building with floating column and without floating column, International journal ofEngineeringResearch-Online.APeer Reviewed International Journal. Vol. 2, Issue 4, (2014). [4]. Hardik.Bhensdadia Pushover analysis of RC structure with floating column and soft storey in different earthquake zones, frame International Journal of Research in Engineering and Technology. Vol. 4, Issue 4 (Apr-2015). [5]. T. Raja. Sekhar Study of behavior of seismic analysis of multistory building with and without floating column, SciTech, Vol 2, pp 697-710, (2014). [6]. Ms. Waykule S.B et al Comparative Study of floating column of multi storey building by using software, Int. Journal of Engineering Research and Application, Vol. 7, Issue 1, ( Part -3), pp.31-38 (January 2017). [7]. Susanta Banerjee and Dr. Sanjaya K Patro Estimation of park-Ang damage index for floating column building with infill wall, 55th Annual Technical, Journal of Orissa State Centre, Institute of Engineers (India), pp.211-217 (2014). [8]. Prerna Nautiyal Seismic response evaluation of R.C. frame building with floating column considering different soil conditions , International Journal ofCurrentEngineering and Technology, Vol.4, No.1 (2014). [9]. Sreekanth Gandla Nanabala Seismic analysis of a normal building and floating column building, International Journal of Engineering Research & Technology (2014). [10]. Er. Ashfi Rahma Effect of FloatingColumnsonSeismic ResponseofMulti-StoredRCFramedBuildings,International Journal of Engineering Research & Technology, Vol. 4 Issue 06, (June-2015). [11]. Rahul Kapase, Mukund Pawar, M.M. Deshmukh, S.B.Talavara Effect of Seismic Retrofitting on R.C. Building with Soft Storey and Floating Column, International Journal of Engineering Trends and Technology, Vol. 46, No. 7, (April 2017). [12]. D. Annapurna, Sriram Nadipelli Comparative study of seismic analysis of a normal building and building with
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 2902 floating columns, IJRET, Vol. 04, Special Issue: 13, ICISE- 2015, (Dec-2015). [13]. Shiwli Roy, Gargi Danda de Behavioural studies of floating column on framed structure, IJRET, Vol. 09, Issue: 09, (Sept. -2015). [14]. Sampath Kumar M.P, V.S. Jagadeesh Effectoffloating columns on seismic response of multistory building, International Research Journal of Engineering and Technology, Vol. 03, Issue: 09, (Sep -2016). [15]. Niteen Malu, Amaresh.S.Patil Performance of RC frame structure with floating column and soft storey in different earthquake zones using pushover analysis, International Research Journal of Engineering and Technology, Vol. 04, Issue 09, (Sep 2017). [16]. Vijayanarayanan. R, Rupen Goswami and C.V.R.Murty Special class of open ground storey RC buildings built in india unsafe during earthquakes 67Department of Civil Engineering, IIT-Madras. pp. 0147. [17]. Agarwal Pankaj, Shrikhande Manish Earthquake resistant design of structures PHI learning private limited (2009). [18]. Criteria for Earthquake Resistant design of structures, Part1: General provisions and buildings, IS 1893:2002, Bureau of Indian Standards, New Delhi. [19]. IS 875 (Part-I) Bureau ofIndianStandards(1987)Code of Practice for Design Loads (Other than Earthquake) for Buildings and Structures: Dead Loads-Unit Weights of Building Materials and Stored Materials (Second Revision). UDC 624.042: 006.76. [20]. IS 875 (Part-II) Bureau of Indian Standards (1987) Code of Practice for Design Loads For Buildings and Structures: Imposed Loads (Second Revision). UDC 624.042.3: 006.76.