SlideShare a Scribd company logo
1 of 22
BHAGALPUR COLLEGE OF ENGINEERING, BHAGALPUR
(Department of Science & Technology, Government of Bihar)
Anshul Shekhar
Assistant Professor
Department of Electrical Engineering
Switchgear & Protection
Lecture-3 & 4 (07 August 2020)
UNIT-1: Circuit breakers
2
Arc voltage mechanism of arc interruption, Restriking
Voltage and Recovery Voltage, Classification of CBs
Oil CBs, Air CBs, Vacuum, SF6 CBs, HVDC CBs,
Rating and Resting of CBs.
3
A circuit breaker is an automatically operated electrical switch designed to protect an
electrical circuit from damage caused by overloading or short circuit.
It protects the circuit by interrupting the current flowing in the line, transformer etc when
fault occurs
A Circuit Breaker can make or break a circuit either manually or automatically under all
conditions i.e., no-load, full-load and short-circuit conditions.
An Introduction
4
Fig 1.1 Simplified Diagram of circuit breaker for opening operation
When the fault occurs in the protected circuit, the relay connected to the CT & VT detects
the fault, actuates and closes its contacts to complete the trip circuit. Current flows from the
battery to trip circuit. As the trip coil of CB energized, the CB operating mechanism is
actuated and it operates for the opening operation to disconnect the faulty elements.
Contd..
5
A circuit breaker is a switching and current interrupting device. It consists of fixed and
moving contacts called electrodes. Both contacts are placed in a closed chamber
containing a fluid insulating medium (either liquid or gas) which quenches the arc formed
between the contacts.
Working
Fig 1.2 Separation of contacts of the Circuit Breaker
6
Under normal operating conditions, these contacts remain closed (touching each other )
and will not open automatically until and unless the system becomes faulty. But the contacts
can be opened manually or remote control whenever desired)
Whenever fault occurs (i.e., under abnormal condition) at any part of the power system,
the relay coil gets energized which is sufficient enough to close the trip circuit. Thus trip coils
of the circuit breaker get energized and the moving contacts are pulled apart by some
mechanism, thus opening the circuit.
Working Contd..
7
When the contacts of a circuit breaker are separated under fault conditions, an arc is
struck between them. The current is thus able to continue until the discharge ceases. The
production of arc not only delays the current interruption process but it also generates
enormous heat which may cause damage to the system or to the circuit breaker itself.
The problem in a circuit breaker is to extinguish the arc within the shortest possible time
so that heat generated by it may not reach a dangerous value.
Working Contd..
8
When short-circuit occurs, a heavy current flows through the contacts of the circuit breaker
before they are opened by the protecting system. At the instant, when the contacts starts to
separate, the contact area decreases rapidly and large fault current will lead to increased
current density and hence rise in temperature.
The heat produced in the medium between contacts is sufficient enough to ionize the air or
vaporize and ionize the oil. The ionized air or vapour acts as conductor and an arc is struck
between the contacts.
The potential difference between the contacts is quite small and which is sufficient to
maintain the arc. The arc provides a low resistance path and consequently the current in the
circuit remains uninterrupted as long as the arc persists.
Arc Phenomenon
9
During the arcing period, the current flowing between the contacts depends upon the arc
resistance. Greater is the arc resistance, and then smaller will be the current that flows
in between the contacts. The arc resistance depends upon the following factors:
(i) Degree of ionization - the arc resistance increases with the decrease in the number of
ionized particles between the contacts.
(ii) Length of arc – the arc resistance increases with the length of the arc. i.e., separation
of contacts.
(iii) Cross-section of arc – the arc resistance increases with the decrease in area of cross-
section of the arc.
Arc Phenomenon Contd..
10
When current carrying contacts of circuit breaker are separated, an arc is formed, which
persists for a period after separation of contacts. The circuit breaker should be capable of
extinguishing the arc without causing any damage to the equipment or danger to personnel.
The factors responsible for the maintenance of arc between the contacts are:
1. Potential difference between the contacts
2. Ionized particles between the contacts
PRI NCIPLES OF ARC INTERRUPTION
11
Potential difference between the contacts: When the separation between the contacts is
small, the potential difference between them is sufficient enough to maintain the arc. One
way to extinguish the arc is to separate the contacts to a distance that the potential difference
becomes inadequate to maintain the arc. However, this method is impracticable in high
voltage system.
Ionized particles between the contacts: The ionized particles between the contacts tend
to maintain the arc. If the arc path is de-ionized then the arc extinction will be facilitated. This
may be achieved by cooling the arc or by removing ionized particles from the space between
the circuit breaker contacts.
PRI NCIPLES OF ARC INTERRUPTION Contd..
12
There are two methods of extinguishing the arc in the circuit breakers
1. High resistance method
2. Low resistance method or current zero method
1. High resistance method: In this method, arc resistance is made to increase with time so
that current is reduced to a value insufficient to maintain the arc. Consequently, the
current is interrupted or the arc is extinguished. The principal disadvantage of this
method is that enormous energy is dissipated in the arc. Therefore it is employed in D.C.
circuit breakers and low-capacity a.c. circuit breakers only.
METHODS OF ARC EXTINCTION
13
The resistance of the arc may be increased by
(i) Lengthening the arc: The resistance of the arc is directly proportional to its length. The
length of the arc can be increased by increasing the gap between the contacts.
(ii) Cooling the arc: Cooling helps in the deionization of the medium between the contacts.
This increases the arc resistance. Efficient cooling may be obtained by a gas blast
directed along the arc.
METHODS OF ARC EXTINCTION
(High resistance method)
Contd..
14
(iii) Reducing the Cross-section of the arc: If area of the cross-section of the arc is
reduced, the voltage necessary to maintain the arc is increased. In other words, the
resistance of the arc path is increased. The cross-section of the arc can be reduced by letting
the arc pass through a narrow opening or by having smaller area of contacts.
(iv) Splitting the arc: The resistance of the arc can be increased by splitting the arc into a
number of smaller arcs in series. Each one of these arcs experiences the effect of
lengthening and cooling. The arc may be split by introducing some conducting plates
between the contacts.
Contd..
METHODS OF ARC EXTINCTION
(High resistance method)
15
This method is applicable only in ac circuit interruption because there is natural zero of
current 100 times in a second for 50 Hz supply system. This property of ac circuit is exploited
for interruption purposes and current is not allowed to rise again after a current zero occurs.
The phenomenon of arc extinction is explained by two theories as follows.
(i) Energy balance or Cassie theory
(ii) Recovery Rate or Slepian’s Theory
METHODS OF ARC EXTINCTION
(Low Resistance or Current Zero Interruption)
16
(i) Energy Balance or Cassie Theory :
This theory states that “if the rate of heat dissipation between the contacts is
greater than the rate at which heat is generated, the arc will be extinguished,
otherwise it will restrike”.
 The heat generated varies from time to time depending upon the separation of breaker
contacts. Initially when the contacts are about to open, the restriking voltage is zero and
therefore, the heat generated is zero. Again when the contacts are fully open, the
resistance between the contacts is also infinite and hence the heat generated is zero.
METHODS OF ARC EXTINCTION
(Low Resistance or Current Zero Interruption)
Contd..
17
 Between these two limits the heat generation reaches a maximum. Now if the heat so
generated could be removed by cooling, lengthening and splitting the arc at a faster rate
than that of generation of heat, the arc is extinguished.
METHODS OF ARC EXTINCTION
(Energy Balance Theory)
Contd..
Fig 1.3 Energy Balance Theory
18
(ii) Recovery Rate or Slepian’s Theory:
This theory states that, the rate at which the gap recovers its dielectric strength is
faster than the rate at which voltage stress rises, the arc will be extinguished else
the arc may be interrupted for a brief period but it again restrikes.
METHODS OF ARC EXTINCTION
(Low Resistance or Current Zero Interruption)
Contd..
19
 In an a.c. system, current drops to zero after every half-cycle. At every current zero,
the arc extinguishes for a brief moment. Now the medium between the contacts
contains ions so that it has small dielectric strength and can be easily broken down by
the rising contact voltage known as restriking voltage.
 If such a breakdown occurs, the arc will persist for another half cycle. If immediately after
current zero, the dielectric strength of the medium between the contacts is built up more
rapidly than the voltage across the contacts, the arc fails to restrike and the current will
be interrupted.
METHODS OF ARC EXTINCTION
(Low Resistance or Current Zero Interruption)
Contd..
20
METHODS OF ARC EXTINCTION
(Low Resistance or Current Zero Interruption)
Contd..
Fig 1.4 Recovery Rate Theory
References:
21
Badari Ram, D. N. Vishwakarma “Power System Protection and Switchgear” 2nd
edition, TMH Publications, 2011.
22
Thank you

More Related Content

What's hot

EE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationEE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationKarthikeyanK816516
 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERNitish NIT
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdownvishalgohel12195
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PTChandan Singh
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Kamran Gillani
 
Power system protection
Power system protectionPower system protection
Power system protectionAnu Priya
 
Power system stability
Power system stabilityPower system stability
Power system stabilityBalaram Das
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Control of hvdc system
Control of hvdc systemControl of hvdc system
Control of hvdc systemAazim Rasool
 
Resonant Converter
Resonant ConverterResonant Converter
Resonant Converterpilurout
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruptionjawaharramaya
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at JassureShuvam Pathania
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Rohini Haridas
 
substation internship report
substation internship report substation internship report
substation internship report Arun Thapa
 

What's hot (20)

Power system protection
Power system protectionPower system protection
Power system protection
 
EE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordinationEE8701 - HVE - Insulation coordination
EE8701 - HVE - Insulation coordination
 
Protective relay
Protective relay Protective relay
Protective relay
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Streamer theory of breakdown
Streamer theory of breakdownStreamer theory of breakdown
Streamer theory of breakdown
 
Instrument transformer CT & PT
Instrument transformer CT & PTInstrument transformer CT & PT
Instrument transformer CT & PT
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)Power System Protection (Primary & Backup)
Power System Protection (Primary & Backup)
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Power system stability
Power system stabilityPower system stability
Power system stability
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Control of hvdc system
Control of hvdc systemControl of hvdc system
Control of hvdc system
 
Power factor
Power factorPower factor
Power factor
 
Resonant Converter
Resonant ConverterResonant Converter
Resonant Converter
 
Circuit interruption
Circuit interruptionCircuit interruption
Circuit interruption
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
 
substation internship report
substation internship report substation internship report
substation internship report
 
Static relay
Static relayStatic relay
Static relay
 

Similar to Circuit Breakers Explained

Circuit breakers
Circuit breakersCircuit breakers
Circuit breakersAdnan Sayed
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
PSG_unit3_motor protection.ppt
PSG_unit3_motor protection.pptPSG_unit3_motor protection.ppt
PSG_unit3_motor protection.pptRajaDesingu2
 
arc phenomena and c.b.
arc phenomena and c.b.arc phenomena and c.b.
arc phenomena and c.b.Kinjalshah93
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomenaBhavin Pradhan
 
Circuit Breaker : Types
Circuit Breaker : TypesCircuit Breaker : Types
Circuit Breaker : TypesRidwanul Hoque
 
High voltage circuit breakers
High voltage circuit breakersHigh voltage circuit breakers
High voltage circuit breakersKabilesh K
 
highvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfhighvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfNagsSuresh
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakersali raza
 
ARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxBadhonBiswas3
 
SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................MANOJ KHARADE
 
SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................MANOJ KHARADE
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit BreakerRAHUL-GOPU
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breakerdipak doud
 
Basic Terms of Circuit Breaker
Basic Terms of Circuit BreakerBasic Terms of Circuit Breaker
Basic Terms of Circuit BreakerAnshulShekhar3
 

Similar to Circuit Breakers Explained (20)

Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
PSG_unit3_motor protection.ppt
PSG_unit3_motor protection.pptPSG_unit3_motor protection.ppt
PSG_unit3_motor protection.ppt
 
arc phenomena and c.b.
arc phenomena and c.b.arc phenomena and c.b.
arc phenomena and c.b.
 
Circuit breaker arc phenomena
Circuit breaker arc phenomenaCircuit breaker arc phenomena
Circuit breaker arc phenomena
 
Circuit Breaker : Types
Circuit Breaker : TypesCircuit Breaker : Types
Circuit Breaker : Types
 
High voltage circuit breakers
High voltage circuit breakersHigh voltage circuit breakers
High voltage circuit breakers
 
highvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdfhighvoltagecircuitbreakers-180415102549.pdf
highvoltagecircuitbreakers-180415102549.pdf
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
ARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptxARC PHENOMENON (Power Protection System).pptx
ARC PHENOMENON (Power Protection System).pptx
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................SGPD(MOD-4).pdf...................................................
SGPD(MOD-4).pdf...................................................
 
SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................SGPD(MOD-4).pdfsgp .....................
SGPD(MOD-4).pdfsgp .....................
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit Breaker
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Shruthi
ShruthiShruthi
Shruthi
 
Basic Terms of Circuit Breaker
Basic Terms of Circuit BreakerBasic Terms of Circuit Breaker
Basic Terms of Circuit Breaker
 
Lightening Arrester.pptx
Lightening Arrester.pptxLightening Arrester.pptx
Lightening Arrester.pptx
 

Recently uploaded

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 

Recently uploaded (20)

APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 

Circuit Breakers Explained

  • 1. BHAGALPUR COLLEGE OF ENGINEERING, BHAGALPUR (Department of Science & Technology, Government of Bihar) Anshul Shekhar Assistant Professor Department of Electrical Engineering Switchgear & Protection Lecture-3 & 4 (07 August 2020)
  • 2. UNIT-1: Circuit breakers 2 Arc voltage mechanism of arc interruption, Restriking Voltage and Recovery Voltage, Classification of CBs Oil CBs, Air CBs, Vacuum, SF6 CBs, HVDC CBs, Rating and Resting of CBs.
  • 3. 3 A circuit breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overloading or short circuit. It protects the circuit by interrupting the current flowing in the line, transformer etc when fault occurs A Circuit Breaker can make or break a circuit either manually or automatically under all conditions i.e., no-load, full-load and short-circuit conditions. An Introduction
  • 4. 4 Fig 1.1 Simplified Diagram of circuit breaker for opening operation When the fault occurs in the protected circuit, the relay connected to the CT & VT detects the fault, actuates and closes its contacts to complete the trip circuit. Current flows from the battery to trip circuit. As the trip coil of CB energized, the CB operating mechanism is actuated and it operates for the opening operation to disconnect the faulty elements. Contd..
  • 5. 5 A circuit breaker is a switching and current interrupting device. It consists of fixed and moving contacts called electrodes. Both contacts are placed in a closed chamber containing a fluid insulating medium (either liquid or gas) which quenches the arc formed between the contacts. Working Fig 1.2 Separation of contacts of the Circuit Breaker
  • 6. 6 Under normal operating conditions, these contacts remain closed (touching each other ) and will not open automatically until and unless the system becomes faulty. But the contacts can be opened manually or remote control whenever desired) Whenever fault occurs (i.e., under abnormal condition) at any part of the power system, the relay coil gets energized which is sufficient enough to close the trip circuit. Thus trip coils of the circuit breaker get energized and the moving contacts are pulled apart by some mechanism, thus opening the circuit. Working Contd..
  • 7. 7 When the contacts of a circuit breaker are separated under fault conditions, an arc is struck between them. The current is thus able to continue until the discharge ceases. The production of arc not only delays the current interruption process but it also generates enormous heat which may cause damage to the system or to the circuit breaker itself. The problem in a circuit breaker is to extinguish the arc within the shortest possible time so that heat generated by it may not reach a dangerous value. Working Contd..
  • 8. 8 When short-circuit occurs, a heavy current flows through the contacts of the circuit breaker before they are opened by the protecting system. At the instant, when the contacts starts to separate, the contact area decreases rapidly and large fault current will lead to increased current density and hence rise in temperature. The heat produced in the medium between contacts is sufficient enough to ionize the air or vaporize and ionize the oil. The ionized air or vapour acts as conductor and an arc is struck between the contacts. The potential difference between the contacts is quite small and which is sufficient to maintain the arc. The arc provides a low resistance path and consequently the current in the circuit remains uninterrupted as long as the arc persists. Arc Phenomenon
  • 9. 9 During the arcing period, the current flowing between the contacts depends upon the arc resistance. Greater is the arc resistance, and then smaller will be the current that flows in between the contacts. The arc resistance depends upon the following factors: (i) Degree of ionization - the arc resistance increases with the decrease in the number of ionized particles between the contacts. (ii) Length of arc – the arc resistance increases with the length of the arc. i.e., separation of contacts. (iii) Cross-section of arc – the arc resistance increases with the decrease in area of cross- section of the arc. Arc Phenomenon Contd..
  • 10. 10 When current carrying contacts of circuit breaker are separated, an arc is formed, which persists for a period after separation of contacts. The circuit breaker should be capable of extinguishing the arc without causing any damage to the equipment or danger to personnel. The factors responsible for the maintenance of arc between the contacts are: 1. Potential difference between the contacts 2. Ionized particles between the contacts PRI NCIPLES OF ARC INTERRUPTION
  • 11. 11 Potential difference between the contacts: When the separation between the contacts is small, the potential difference between them is sufficient enough to maintain the arc. One way to extinguish the arc is to separate the contacts to a distance that the potential difference becomes inadequate to maintain the arc. However, this method is impracticable in high voltage system. Ionized particles between the contacts: The ionized particles between the contacts tend to maintain the arc. If the arc path is de-ionized then the arc extinction will be facilitated. This may be achieved by cooling the arc or by removing ionized particles from the space between the circuit breaker contacts. PRI NCIPLES OF ARC INTERRUPTION Contd..
  • 12. 12 There are two methods of extinguishing the arc in the circuit breakers 1. High resistance method 2. Low resistance method or current zero method 1. High resistance method: In this method, arc resistance is made to increase with time so that current is reduced to a value insufficient to maintain the arc. Consequently, the current is interrupted or the arc is extinguished. The principal disadvantage of this method is that enormous energy is dissipated in the arc. Therefore it is employed in D.C. circuit breakers and low-capacity a.c. circuit breakers only. METHODS OF ARC EXTINCTION
  • 13. 13 The resistance of the arc may be increased by (i) Lengthening the arc: The resistance of the arc is directly proportional to its length. The length of the arc can be increased by increasing the gap between the contacts. (ii) Cooling the arc: Cooling helps in the deionization of the medium between the contacts. This increases the arc resistance. Efficient cooling may be obtained by a gas blast directed along the arc. METHODS OF ARC EXTINCTION (High resistance method) Contd..
  • 14. 14 (iii) Reducing the Cross-section of the arc: If area of the cross-section of the arc is reduced, the voltage necessary to maintain the arc is increased. In other words, the resistance of the arc path is increased. The cross-section of the arc can be reduced by letting the arc pass through a narrow opening or by having smaller area of contacts. (iv) Splitting the arc: The resistance of the arc can be increased by splitting the arc into a number of smaller arcs in series. Each one of these arcs experiences the effect of lengthening and cooling. The arc may be split by introducing some conducting plates between the contacts. Contd.. METHODS OF ARC EXTINCTION (High resistance method)
  • 15. 15 This method is applicable only in ac circuit interruption because there is natural zero of current 100 times in a second for 50 Hz supply system. This property of ac circuit is exploited for interruption purposes and current is not allowed to rise again after a current zero occurs. The phenomenon of arc extinction is explained by two theories as follows. (i) Energy balance or Cassie theory (ii) Recovery Rate or Slepian’s Theory METHODS OF ARC EXTINCTION (Low Resistance or Current Zero Interruption)
  • 16. 16 (i) Energy Balance or Cassie Theory : This theory states that “if the rate of heat dissipation between the contacts is greater than the rate at which heat is generated, the arc will be extinguished, otherwise it will restrike”.  The heat generated varies from time to time depending upon the separation of breaker contacts. Initially when the contacts are about to open, the restriking voltage is zero and therefore, the heat generated is zero. Again when the contacts are fully open, the resistance between the contacts is also infinite and hence the heat generated is zero. METHODS OF ARC EXTINCTION (Low Resistance or Current Zero Interruption) Contd..
  • 17. 17  Between these two limits the heat generation reaches a maximum. Now if the heat so generated could be removed by cooling, lengthening and splitting the arc at a faster rate than that of generation of heat, the arc is extinguished. METHODS OF ARC EXTINCTION (Energy Balance Theory) Contd.. Fig 1.3 Energy Balance Theory
  • 18. 18 (ii) Recovery Rate or Slepian’s Theory: This theory states that, the rate at which the gap recovers its dielectric strength is faster than the rate at which voltage stress rises, the arc will be extinguished else the arc may be interrupted for a brief period but it again restrikes. METHODS OF ARC EXTINCTION (Low Resistance or Current Zero Interruption) Contd..
  • 19. 19  In an a.c. system, current drops to zero after every half-cycle. At every current zero, the arc extinguishes for a brief moment. Now the medium between the contacts contains ions so that it has small dielectric strength and can be easily broken down by the rising contact voltage known as restriking voltage.  If such a breakdown occurs, the arc will persist for another half cycle. If immediately after current zero, the dielectric strength of the medium between the contacts is built up more rapidly than the voltage across the contacts, the arc fails to restrike and the current will be interrupted. METHODS OF ARC EXTINCTION (Low Resistance or Current Zero Interruption) Contd..
  • 20. 20 METHODS OF ARC EXTINCTION (Low Resistance or Current Zero Interruption) Contd.. Fig 1.4 Recovery Rate Theory
  • 21. References: 21 Badari Ram, D. N. Vishwakarma “Power System Protection and Switchgear” 2nd edition, TMH Publications, 2011.