Building Construction
Related to the Fire Service

 Chapter 2 — Structural Fire
   Resistance and Building
       Classifications
Learning Objective 1




  Define fire resistance.




             Building Construction
                      2–2
Fire Resistance

• Function of the properties of all
  materials used; includes combustibility,
  thermal conductivity, chemical
  composition, density, and dimensions
• Ability of a structural assembly to
  maintain load-bearing and structural
  integrity under fire conditions
                                       (Continued)

               Building Construction
                        2–3
Fire Resistance

• Ability of walls, partitions, and ceilings
  to act as a fire barrier
• Fire resistance rating
  – Expressed in hours and fractions of hours
  – Incorporated into construction
    classifications and building codes



                Building Construction
                         2–4
Learning Objective 2




 Discuss methods of determining fire
 resistance and the limitations of each
 method.




              Building Construction
                       2–5
Determination of Fire
Resistance

• Conducting standard fire resistance
  testing in a laboratory
• Performing analytical calculations to
  determine the resistance to a standard
  fire test exposure
• Employing analytical structural fire
  engineering design methods based on
  real fire exposure characteristics
              Building Construction
                       2–6
Fire Resistance Test Method

• Laboratory test is most commonly used
  method
• Component subject to heat of a
  standard fire in test furnace
• Primary points of failure for test
• Fire resistance ratings expressed in
  standard intervals
                                         (Continued)

              Building Construction
                       2–7
Fire Resistance Test Method

• Factors impacting fire resistance ratings
  from standard test
• Standard fire test evaluates ability of
  structural assemblies to carry a
  structural load and act as a fire barrier
• Information NOT provided by test
• Assemblies may be penetrated
                                        (Continued)

               Building Construction
                        2–8
Fire Resistance Test Method




          Building Construction
                   2–9
Learning Objective 3




 Identify fire testing organizations and
 discuss the significance of fire test
 results.




              Building Construction
                      2–10
Fire Testing Organizations

• Testing for fire resistance ratings is
  beyond capability of local fire and
  building departments
• Several laboratories are equipped to
  conduct testing
• Some organizations use furnaces
  primarily for research and product
  development
               Building Construction
                       2–11
Fire Test Results

• Published by testing
  laboratories
• Deviation from
  materials or
  dimensions specified
  alters test results



              Building Construction
                      2–12
Learning Objective 4




 Recognize the role of analysis in
 determining fire resistance.




              Building Construction
                      2–13
Analytical Calculation of
Fire Resistance

• Mathematical equations have been
  developed to predict behavior of
  materials under test conditions
• ASCE/SFPE 29 provides methods for
  calculating fire resistance ratings
• Limited to use with certain materials


              Building Construction
                      2–14
Analytical Design Using
Real Fire Exposures

• NFPA® 251 test
  – Most commonly used
  – May be too severe or not severe enough
• Ratings determined analytically using a
 different time-temperature curve must
 be interpreted cautiously


               Building Construction
                       2–15
Noncombustible Materials

• Building codes contain explicit criteria
  for determining combustible material
• Incapable of supporting combustion
  under normal circumstances
• Most common test for determining
  combustibility – ASTM E 136


               Building Construction
                       2–16
Learning Objective 5




 Discuss the basic building
 classifications as they relate to fire
 resistance.




               Building Construction
                       2–17
Classifications

• Type I, Fire-Resistive
• Type II, Noncombustible or protected
  noncombustible
• Type III, Exterior protected
• Type IV, Heavy timber
• Type V, Wood frame
                                       (Continued)

               Building Construction
                       2–18
Classifications

• In building codes, based on materials
 used in construction and hourly fire
 resistance ratings required for structural
 components




              Building Construction
                      2–19
NFPA ® 220

• Details requirements for each classification
  and subclassification
• Designated by three-digit number code
  – 1st – Fire resistance rating in hours of exterior
    bearing walls
  – 2nd – Fire resistance rating of structural frames
    or columns and girders supporting loads
    greater than one floor
  – 3rd – Fire resistance rating of floor construction
                  Building Construction
                          2–20
International Building Code ®
(IBC ® )

• Similar to NFPA® 220
• Requirements for individual structural
  members differ
• Building codes use construction types
  and occupancy in conjunction with
  sprinkler systems and separations to
  establish limits on heights and areas of
  buildings
               Building Construction
                       2–21
Type I Construction

• Structural members
  are noncombustible
  construction with a
  specified fire
  resistance                   Courtesy of McKinney (TX) Fire Department



• Combustible material typically permitted
  in certain components
• Most common methods of construction
              Building Construction
                      2–22
Type II Construction

• Noncombustible – Can be either
  protected or unprotected
• IBC® divides into two subclassifications
• Material other than steel can be used
• Building codes allow combustible
  material similar to that in Type I

                                       (Continued)

               Building Construction
                       2–23
Type II Construction

• Unprotected, noncombustible building
  cannot be expected to provide
  structural stability under fire conditions
• Point at which unprotected members
  will fail depends on several factors
• Protected, noncombustible structural
  fire protection is similar to Type I

                Building Construction
                        2–24
Type III Construction

• “Ordinary construction”
• Exterior walls frequently masonry, but
  can be any noncombustible material
  with required fire resistance
• Interior members
  – Partially or wholly combustible
  – Protected or unprotected
                                        (Continued)

                Building Construction
                        2–25
Type III Construction

• IBC® divides into two subclassifications
• When fire resistance is required, most
  common is plaster (older) or gypsum
  board (newer)
• Wood dimensions permitted to be
  smaller than Type IV
• Fundamental fire concern – Concealed
  spaces
               Building Construction
                       2–26
Type IV Construction

• “Mill construction”
• Difference from Type III
• Used in older factories,
  mills, and warehouses
• Primary fire hazard –
  Massive amount of fuel               Courtesy of McKinney (TX) Fire Department



  from large structural
  members
               Building Construction
                       2–27
Type V Construction

• All structural components
  may be combustible
• Two subclassifications
• Differences from Type III
• Threat to adjacent
  structures if heavily
  involved in fire

              Building Construction
                      2–28
Mixed Construction

• Some buildings are allowed a mixed
  construction type
• May result in special challenges for
  emergency responders




               Building Construction
                       2–29
Learning Objective 6




 Discuss the concept of fire load and its
 impact on building construction types.




              Building Construction
                      2–30
Fire Load

• Maximum heat released if all available
  fuel in a building was consumed
• Product of weight of combustibles
  multiplied by their heat of combustion
• Expressed in lb/sq ft (kg/sq m)
• Varies depending on heat of
  combustion of fuel

               Building Construction
                       2–31
Fire Load and Construction
Type

• Buildings with combustible structural
  components have greater fire load than
  Type I and II
• Fire load does not translate into
  equivalent structural load




               Building Construction
                       2–32
Learning Objective 7




 Explain occupancy classifications as
 they relate to fire risks.




             Building Construction
                     2–33
Occupancy Classifications



• Assign building occupancies into
 groups with broadly similar fire risks




              Building Construction
                      2–34
IBC ® Classifications

•   Group A – Assembly       •   Group I – Institutional
•   Group B – Business       •   Group M – Mercantile
•   Group E – Education      •   Group R – Residential
•   Group F – Factories      •   Group S – Storage
•   Group H – High           •   Group U – Utility and
    Hazard                       Misc.




                 Building Construction
                         2–35
International Building Code ®

• Considerable variation of hazards within
  groups, so further divided to describe
  occupancy groups with more similar
  characteristics
• Total of 26 subgroups
• Separate provision for one- and two-
  family dwellings not more than three
  stories high
               Building Construction
                       2–36
NFPA ® Classifications

• Assembly                 • Residential
• Educational              • Residential board
• Day care                     and care
• Health care              •   Mercantile
• Ambulatory health        •   Business
  care                     •   Industrial
• Detention and            •   Storage
  correctional

               Building Construction
                       2–37
Mixed Occupancies

• Buildings may contain more than one
  occupancy classification
• Codes require fire-resistive separations
  between various occupancies
• Requirements depend on local code
• Reduction in occupancy separation may
  be permitted if building is sprinklered

              Building Construction
                      2–38
Change of Occupancy

• Frequently occurs
• Can create problems
• May require expensive renovations that
 owner not willing to pay




              Building Construction
                      2–39
Summary

• Fire behavior in buildings is determined
  largely by construction materials and
  structural fire resistance.
• Structural fire resistance is determined
  most often through laboratory testing.


                                       (Continued)

               Building Construction
                       2–40
Summary

• Building codes classify construction into
  types based on construction material,
  structural fire resistance, and
  occupancy.
• Occupancies within individual
  occupancy groups present roughly
  similar fire risk factors.

               Building Construction
                       2–41
Review Questions

  1.      What is fire resistance?
  2.      What is the value of standard
  fire tests?
  3.      What is a noncombustible
  material?
  4.      What considerations do
  firefighters need to take into account
  when they encounter dropped        (Continued)

  ceilings? Building Construction
                   2–42
Review Questions

  5.     What are the major occupancy
  classifications contained in the
  International Building Code® (IBC®)?




            Building Construction
                    2–43

Bldg Construction Chapter 02

  • 1.
    Building Construction Related tothe Fire Service Chapter 2 — Structural Fire Resistance and Building Classifications
  • 2.
    Learning Objective 1 Define fire resistance. Building Construction 2–2
  • 3.
    Fire Resistance • Functionof the properties of all materials used; includes combustibility, thermal conductivity, chemical composition, density, and dimensions • Ability of a structural assembly to maintain load-bearing and structural integrity under fire conditions (Continued) Building Construction 2–3
  • 4.
    Fire Resistance • Abilityof walls, partitions, and ceilings to act as a fire barrier • Fire resistance rating – Expressed in hours and fractions of hours – Incorporated into construction classifications and building codes Building Construction 2–4
  • 5.
    Learning Objective 2 Discuss methods of determining fire resistance and the limitations of each method. Building Construction 2–5
  • 6.
    Determination of Fire Resistance •Conducting standard fire resistance testing in a laboratory • Performing analytical calculations to determine the resistance to a standard fire test exposure • Employing analytical structural fire engineering design methods based on real fire exposure characteristics Building Construction 2–6
  • 7.
    Fire Resistance TestMethod • Laboratory test is most commonly used method • Component subject to heat of a standard fire in test furnace • Primary points of failure for test • Fire resistance ratings expressed in standard intervals (Continued) Building Construction 2–7
  • 8.
    Fire Resistance TestMethod • Factors impacting fire resistance ratings from standard test • Standard fire test evaluates ability of structural assemblies to carry a structural load and act as a fire barrier • Information NOT provided by test • Assemblies may be penetrated (Continued) Building Construction 2–8
  • 9.
    Fire Resistance TestMethod Building Construction 2–9
  • 10.
    Learning Objective 3 Identify fire testing organizations and discuss the significance of fire test results. Building Construction 2–10
  • 11.
    Fire Testing Organizations •Testing for fire resistance ratings is beyond capability of local fire and building departments • Several laboratories are equipped to conduct testing • Some organizations use furnaces primarily for research and product development Building Construction 2–11
  • 12.
    Fire Test Results •Published by testing laboratories • Deviation from materials or dimensions specified alters test results Building Construction 2–12
  • 13.
    Learning Objective 4 Recognize the role of analysis in determining fire resistance. Building Construction 2–13
  • 14.
    Analytical Calculation of FireResistance • Mathematical equations have been developed to predict behavior of materials under test conditions • ASCE/SFPE 29 provides methods for calculating fire resistance ratings • Limited to use with certain materials Building Construction 2–14
  • 15.
    Analytical Design Using RealFire Exposures • NFPA® 251 test – Most commonly used – May be too severe or not severe enough • Ratings determined analytically using a different time-temperature curve must be interpreted cautiously Building Construction 2–15
  • 16.
    Noncombustible Materials • Buildingcodes contain explicit criteria for determining combustible material • Incapable of supporting combustion under normal circumstances • Most common test for determining combustibility – ASTM E 136 Building Construction 2–16
  • 17.
    Learning Objective 5 Discuss the basic building classifications as they relate to fire resistance. Building Construction 2–17
  • 18.
    Classifications • Type I,Fire-Resistive • Type II, Noncombustible or protected noncombustible • Type III, Exterior protected • Type IV, Heavy timber • Type V, Wood frame (Continued) Building Construction 2–18
  • 19.
    Classifications • In buildingcodes, based on materials used in construction and hourly fire resistance ratings required for structural components Building Construction 2–19
  • 20.
    NFPA ® 220 •Details requirements for each classification and subclassification • Designated by three-digit number code – 1st – Fire resistance rating in hours of exterior bearing walls – 2nd – Fire resistance rating of structural frames or columns and girders supporting loads greater than one floor – 3rd – Fire resistance rating of floor construction Building Construction 2–20
  • 21.
    International Building Code® (IBC ® ) • Similar to NFPA® 220 • Requirements for individual structural members differ • Building codes use construction types and occupancy in conjunction with sprinkler systems and separations to establish limits on heights and areas of buildings Building Construction 2–21
  • 22.
    Type I Construction •Structural members are noncombustible construction with a specified fire resistance Courtesy of McKinney (TX) Fire Department • Combustible material typically permitted in certain components • Most common methods of construction Building Construction 2–22
  • 23.
    Type II Construction •Noncombustible – Can be either protected or unprotected • IBC® divides into two subclassifications • Material other than steel can be used • Building codes allow combustible material similar to that in Type I (Continued) Building Construction 2–23
  • 24.
    Type II Construction •Unprotected, noncombustible building cannot be expected to provide structural stability under fire conditions • Point at which unprotected members will fail depends on several factors • Protected, noncombustible structural fire protection is similar to Type I Building Construction 2–24
  • 25.
    Type III Construction •“Ordinary construction” • Exterior walls frequently masonry, but can be any noncombustible material with required fire resistance • Interior members – Partially or wholly combustible – Protected or unprotected (Continued) Building Construction 2–25
  • 26.
    Type III Construction •IBC® divides into two subclassifications • When fire resistance is required, most common is plaster (older) or gypsum board (newer) • Wood dimensions permitted to be smaller than Type IV • Fundamental fire concern – Concealed spaces Building Construction 2–26
  • 27.
    Type IV Construction •“Mill construction” • Difference from Type III • Used in older factories, mills, and warehouses • Primary fire hazard – Massive amount of fuel Courtesy of McKinney (TX) Fire Department from large structural members Building Construction 2–27
  • 28.
    Type V Construction •All structural components may be combustible • Two subclassifications • Differences from Type III • Threat to adjacent structures if heavily involved in fire Building Construction 2–28
  • 29.
    Mixed Construction • Somebuildings are allowed a mixed construction type • May result in special challenges for emergency responders Building Construction 2–29
  • 30.
    Learning Objective 6 Discuss the concept of fire load and its impact on building construction types. Building Construction 2–30
  • 31.
    Fire Load • Maximumheat released if all available fuel in a building was consumed • Product of weight of combustibles multiplied by their heat of combustion • Expressed in lb/sq ft (kg/sq m) • Varies depending on heat of combustion of fuel Building Construction 2–31
  • 32.
    Fire Load andConstruction Type • Buildings with combustible structural components have greater fire load than Type I and II • Fire load does not translate into equivalent structural load Building Construction 2–32
  • 33.
    Learning Objective 7 Explain occupancy classifications as they relate to fire risks. Building Construction 2–33
  • 34.
    Occupancy Classifications • Assignbuilding occupancies into groups with broadly similar fire risks Building Construction 2–34
  • 35.
    IBC ® Classifications • Group A – Assembly • Group I – Institutional • Group B – Business • Group M – Mercantile • Group E – Education • Group R – Residential • Group F – Factories • Group S – Storage • Group H – High • Group U – Utility and Hazard Misc. Building Construction 2–35
  • 36.
    International Building Code® • Considerable variation of hazards within groups, so further divided to describe occupancy groups with more similar characteristics • Total of 26 subgroups • Separate provision for one- and two- family dwellings not more than three stories high Building Construction 2–36
  • 37.
    NFPA ® Classifications •Assembly • Residential • Educational • Residential board • Day care and care • Health care • Mercantile • Ambulatory health • Business care • Industrial • Detention and • Storage correctional Building Construction 2–37
  • 38.
    Mixed Occupancies • Buildingsmay contain more than one occupancy classification • Codes require fire-resistive separations between various occupancies • Requirements depend on local code • Reduction in occupancy separation may be permitted if building is sprinklered Building Construction 2–38
  • 39.
    Change of Occupancy •Frequently occurs • Can create problems • May require expensive renovations that owner not willing to pay Building Construction 2–39
  • 40.
    Summary • Fire behaviorin buildings is determined largely by construction materials and structural fire resistance. • Structural fire resistance is determined most often through laboratory testing. (Continued) Building Construction 2–40
  • 41.
    Summary • Building codesclassify construction into types based on construction material, structural fire resistance, and occupancy. • Occupancies within individual occupancy groups present roughly similar fire risk factors. Building Construction 2–41
  • 42.
    Review Questions 1. What is fire resistance? 2. What is the value of standard fire tests? 3. What is a noncombustible material? 4. What considerations do firefighters need to take into account when they encounter dropped (Continued) ceilings? Building Construction 2–42
  • 43.
    Review Questions 5. What are the major occupancy classifications contained in the International Building Code® (IBC®)? Building Construction 2–43