1) The document discusses various fire safety design principles including fire avoidance, detection, growth restriction, containment, control and smoke control.
2) Key elements of fire avoidance include fire zoning, limiting combustible materials and fire load. Fire detection focuses on manual and automatic detection methods. Growth restriction methods center around manual firefighting equipment like extinguishers and sprinklers.
3) Fire containment principles involve compartmentalizing buildings using fire-rated walls and doors to confine fires. Fire control ensures firefighter access to buildings and hydrants.
This presentation includes definition, causes, types of fire extinguishers, types of fire component system, NBC regulations, types of sprinklers, fire escapes , Building Planning Consideration for fire prevention, how to escape the fire, capacity of exits, occupants per unit exit width, travel distance, and calculations.
Fire fighting, types of fires, types of fire extinguishers, building management systems, sprinkler systems, heat and smoke sensors.
http://www.greenarchworld.com/
This presentation deals with the capacity of Fire Escapes, no. of fire escapes required in a building and the different Fire Escape system along with their functionality...
This presentation includes definition, causes, types of fire extinguishers, types of fire component system, NBC regulations, types of sprinklers, fire escapes , Building Planning Consideration for fire prevention, how to escape the fire, capacity of exits, occupants per unit exit width, travel distance, and calculations.
Fire fighting, types of fires, types of fire extinguishers, building management systems, sprinkler systems, heat and smoke sensors.
http://www.greenarchworld.com/
This presentation deals with the capacity of Fire Escapes, no. of fire escapes required in a building and the different Fire Escape system along with their functionality...
It has become more apparent over the years how important it is to have adequate fire protection in every building. For most people (Non-technical), what comes to mind when they think of fire protection are Sprinkler system, smoke detectors and fire extinguishers. However, these two elements only cover a small portion of the protection services you should have at all times. There are in fact two types of fire protection: Active Fire Protection (AFP) and Passive Fire Protection (PFP). One type of protection must not be chosen over the other. On the contrary, both AFP and PFP must be used together for full fire protection. It is important to understand the difference between AFP and PFP so that you are confident that your building is protected by both types.
,
fire protection signalling suppression detection
,
fire extingusher types
,
smoke detectors
,
thermal detectors
,
classification of building
,
classification of fire
,
classification of hazards
,
stand pipe and hose
,
sprinklers
,
automatic sprinkling system
,
planning for fire protection
,
fire suppression equipment's & systems
,
fire alarm systems
,
fire safety design
,
fire load
,
use or occupancy
,
type of construction
,
fire saftey requirments for building
,
fire resistant construction
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
Fire safety in Office building Literature, net and live case studyIrene Devakirubai
Construction project management in architecture. Fire safety in Office building net and live case study. NBC norms for fire safety. Net case studies -KLK and Pam center malaysia. Live case study - Global infocity.
Chennai the fourth largest metropolis in India. Chennai Metropolitan Area (CMA) extends over 1189 sq.km.and comprises of
Chennai Corporation,
16 Municipalities,
20 Town Panchayats and
214 villages covered in 10 Panchayats Unions
It encompasses the Chennai District (176 sq.km.), part of Thiruvallur District (637 sq.km.) and a part of Kancheepuram District (376 sq.km.).
It has become more apparent over the years how important it is to have adequate fire protection in every building. For most people (Non-technical), what comes to mind when they think of fire protection are Sprinkler system, smoke detectors and fire extinguishers. However, these two elements only cover a small portion of the protection services you should have at all times. There are in fact two types of fire protection: Active Fire Protection (AFP) and Passive Fire Protection (PFP). One type of protection must not be chosen over the other. On the contrary, both AFP and PFP must be used together for full fire protection. It is important to understand the difference between AFP and PFP so that you are confident that your building is protected by both types.
,
fire protection signalling suppression detection
,
fire extingusher types
,
smoke detectors
,
thermal detectors
,
classification of building
,
classification of fire
,
classification of hazards
,
stand pipe and hose
,
sprinklers
,
automatic sprinkling system
,
planning for fire protection
,
fire suppression equipment's & systems
,
fire alarm systems
,
fire safety design
,
fire load
,
use or occupancy
,
type of construction
,
fire saftey requirments for building
,
fire resistant construction
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
Fire safety in Office building Literature, net and live case studyIrene Devakirubai
Construction project management in architecture. Fire safety in Office building net and live case study. NBC norms for fire safety. Net case studies -KLK and Pam center malaysia. Live case study - Global infocity.
Chennai the fourth largest metropolis in India. Chennai Metropolitan Area (CMA) extends over 1189 sq.km.and comprises of
Chennai Corporation,
16 Municipalities,
20 Town Panchayats and
214 villages covered in 10 Panchayats Unions
It encompasses the Chennai District (176 sq.km.), part of Thiruvallur District (637 sq.km.) and a part of Kancheepuram District (376 sq.km.).
The Kolumba (previously "Diocesan Museum") is an art museum in Cologne, Germany.
The site was originally occupied by the romanesque Church of St. Columba, which was destroyed in World War II and replaced in 1950 by a Gottfried Böhm chapel nicknamed the "Madonna of the Ruins".
The new structure Zumthor built for the museum now shares its site with Gothic church and the 1950s chapel, wrapping a perforated grey brick façade.
Construction of the Kolumba began in 2003 and was completed in 2007.
The 21 1/4 inches long and 19/16 inches high bricks were handmade in the
region, a process which took over two years to complete.
Burj Khalifa, known as Burj Dubai prior to its inauguration, is a skyscraper in Dubai, United Arab Emirates. It is the tallest artificial structure in the world, standing at 829.8 m.
Architect: Charles Correa
Location : Bombay, India
Date: 1970 – 1983
Building Type: Skyscraper multifamily housing
Construction System: Concrete
Climate: Hot
Style: Modern
The attached Fire Safety Manual gives details about details about the fire safety in workplace. It spells out the types of fire, types of fire extinguishers and measures to take for avoiding fire accidents. Further to that, it also explains in detail about steps to take in case of fire.
The objective is that at the end of the Fire Warden / Marshal course you will:
Have a greater understanding of the fire precautions that are built into your workplace
Recognize the hazards and the threat posed by fire to people, property and jobs
Be equipped to carry out your fire safety management responsibilities effectively
Understand why it is essential that fire emergency procedures are implemented and monitored on a daily basis
Distinguish between the different types of extinguishers and their limitations and the fires for which they are suited.
Demonstrate an understanding of the nature and behavior of fire
Be aware of the measures that can be taken to minimize the chances and effect of an arson attack
Fire protection System.This is analysis of fire Hazard, its soure and causes.Also The Detection and Prevention Methods of Fire Hazards.Types Of Fire Extinguisher.
meaning of fire hazards, types of fire,fire triangle,classification of fire,precaution devices,fire extinguisher,types of fire extinguisher, reason of fire hazards,precaution taken in case of fire hazards......important points related to fire hazards..this is very helpful presentation.
Architectural Planning An office building must have flexible and technologically-advanced working environments that are safe, healthy, comfortable, durable, aesthetically-pleasing, and accessible. It must be able to accommodate the specific space and equipment needs of the tenant.
In land use planning, urban open space is open space areas for "parks", "green spaces", and other open areas. The landscape of urban open spaces can range from playing fields to highly maintained environments to relatively natural landscapes. They are commonly open to public access, however, urban open spaces may be privately owned. Areas outside city boundaries, such as state and national parks as well as open space in the countryside, are not considered urban open space. Streets, piazzas, plazas and urban squares are not always defined as urban open space in land use planning.
A design museum is a museum with a focus on product, industrial, graphic, fashion and architectural design. Many design museums were founded as museums for applied arts or decorative arts and started only in the late 20th century to collect design.
The first museum of this kind was the Victoria and Albert Museum in London. In Germany the first museum of decorative arts was the Deutsches-Gewerbe-Museum zu Berlin (now Kunstgewerbemuseum), founded in 1868 in Berlin.[1]
Also some museums of contemporary or modern art have important design collections, like the MoMA in New York, the Centre Pompidou in Paris. A special concept has been realised in the Pinakothek der Moderne in Munich, in which four independent museums cooperate, one of them being Die Neue Sammlung – the largest design museum in the world.
Today corporate museums like the Vitra Design Museum, Museo Alessi or Museo Kartell play an important role.
TDR - CASE STUDIES OF MUMBAI CHENNAI BANGALORE
TRANSFERABLE DEVELOPMENT RIGHTS
Transferable Development Rights or TDR can be considered as an important raw material in the real estate industry as it allows the developer to build over and above the permissible Floor Space Index (FSI) under the prevalent rules of the respective locations.
Burj Khalifa, known as Burj Dubai prior to its inauguration, is a skyscraper in Dubai, United Arab Emirates. It is the tallest artificial structure in the world, standing at 829.8 m.
Urban morphology approaches human settlements as generally unconscious products that
emerge over long periods, through the accrual of successive generations of building activity.
This leaves traces that serve to structure subsequent building activity and provide
opportunities and constraints for city-building processes, such as land subdivision,
infrastructure development, or building construction. Articulating and analysing the logic of
these traces is the central question of urban morphology. Urban morphology is not generally
object-centered, in that it emphasizes the relationships between components of the city. We
will be discussing in detail about the urban morphology of the Chennai metropolitan.
Architecture is the art of spaces. The human feelings were influenced by architectural
space from time to time. Relating to the design of a history museum, it could evoke a
certain feeling or memory of a historical event. This dissertation focuses on the
influence of architectural space over period of times.
A theoretical as well as practical key issue in the design of museum and galleries is how
the layout of space interacts with displays to create a specific effect, express the intended
message to visitors. This dissertation aims to capture and represent the history of
mankind’s understanding of space in the design of an architectural building.
Museum Case Studies
http://en.wikipedia.org/wiki/Museum
A museum is an institution that cares for (conserves) a collection of artifacts and other objects of scientific, artistic, cultural, or historical importance and makes them available for public viewing through exhibits that may be permanent or temporary.[1] Most large museums are located in major cities throughout the world and more local ones exist in smaller cities, towns and even the countryside. Museums have varying aims, ranging from serving researchers and specialists to serving the general public. The continuing acceleration in the digitization of information, combined with the increasing capacity of digital information storage, is causing the traditional model of museums (i.e. as static "collections of collections" of three-dimensional specimens and artifacts) to expand to include virtual exhibits and high-resolution images of their collections for perusal, study, and exploration from any place with Internet.[citation needed] The city with the largest number of museums is Mexico City with over 128 museums. According to The World Museum Community, there are more than 55,000 museums in 202 countries.[2]
Model Attribute Check Company Auto PropertyCeline George
In Odoo, the multi-company feature allows you to manage multiple companies within a single Odoo database instance. Each company can have its own configurations while still sharing common resources such as products, customers, and suppliers.
Ethnobotany and Ethnopharmacology:
Ethnobotany in herbal drug evaluation,
Impact of Ethnobotany in traditional medicine,
New development in herbals,
Bio-prospecting tools for drug discovery,
Role of Ethnopharmacology in drug evaluation,
Reverse Pharmacology.
Operation “Blue Star” is the only event in the history of Independent India where the state went into war with its own people. Even after about 40 years it is not clear if it was culmination of states anger over people of the region, a political game of power or start of dictatorial chapter in the democratic setup.
The people of Punjab felt alienated from main stream due to denial of their just demands during a long democratic struggle since independence. As it happen all over the word, it led to militant struggle with great loss of lives of military, police and civilian personnel. Killing of Indira Gandhi and massacre of innocent Sikhs in Delhi and other India cities was also associated with this movement.
Instructions for Submissions thorugh G- Classroom.pptxJheel Barad
This presentation provides a briefing on how to upload submissions and documents in Google Classroom. It was prepared as part of an orientation for new Sainik School in-service teacher trainees. As a training officer, my goal is to ensure that you are comfortable and proficient with this essential tool for managing assignments and fostering student engagement.
The Roman Empire A Historical Colossus.pdfkaushalkr1407
The Roman Empire, a vast and enduring power, stands as one of history's most remarkable civilizations, leaving an indelible imprint on the world. It emerged from the Roman Republic, transitioning into an imperial powerhouse under the leadership of Augustus Caesar in 27 BCE. This transformation marked the beginning of an era defined by unprecedented territorial expansion, architectural marvels, and profound cultural influence.
The empire's roots lie in the city of Rome, founded, according to legend, by Romulus in 753 BCE. Over centuries, Rome evolved from a small settlement to a formidable republic, characterized by a complex political system with elected officials and checks on power. However, internal strife, class conflicts, and military ambitions paved the way for the end of the Republic. Julius Caesar’s dictatorship and subsequent assassination in 44 BCE created a power vacuum, leading to a civil war. Octavian, later Augustus, emerged victorious, heralding the Roman Empire’s birth.
Under Augustus, the empire experienced the Pax Romana, a 200-year period of relative peace and stability. Augustus reformed the military, established efficient administrative systems, and initiated grand construction projects. The empire's borders expanded, encompassing territories from Britain to Egypt and from Spain to the Euphrates. Roman legions, renowned for their discipline and engineering prowess, secured and maintained these vast territories, building roads, fortifications, and cities that facilitated control and integration.
The Roman Empire’s society was hierarchical, with a rigid class system. At the top were the patricians, wealthy elites who held significant political power. Below them were the plebeians, free citizens with limited political influence, and the vast numbers of slaves who formed the backbone of the economy. The family unit was central, governed by the paterfamilias, the male head who held absolute authority.
Culturally, the Romans were eclectic, absorbing and adapting elements from the civilizations they encountered, particularly the Greeks. Roman art, literature, and philosophy reflected this synthesis, creating a rich cultural tapestry. Latin, the Roman language, became the lingua franca of the Western world, influencing numerous modern languages.
Roman architecture and engineering achievements were monumental. They perfected the arch, vault, and dome, constructing enduring structures like the Colosseum, Pantheon, and aqueducts. These engineering marvels not only showcased Roman ingenuity but also served practical purposes, from public entertainment to water supply.
Welcome to TechSoup New Member Orientation and Q&A (May 2024).pdfTechSoup
In this webinar you will learn how your organization can access TechSoup's wide variety of product discount and donation programs. From hardware to software, we'll give you a tour of the tools available to help your nonprofit with productivity, collaboration, financial management, donor tracking, security, and more.
2. The Fire Triangle:
Three elements - fuel,
oxygen and heat - are
required to start a fire.
The oxidation process
will not be possible
without any one of these
elements.
Fuel (Fire Load)
Oxygen (Ventilation) Heat (Ignition)
Fire is a rapid oxidation process
accompanied by the evolution
of heat, light, flame and the
emission of sound.
Definition and Causes of Fire
2Intro
3. Ordinary combustible
materials such as wood,
cloth, paper, rubber and
plastics, etc.
Class A:
Flammable or combustible
liquids, flammable gases.
Class B:
Energized electrical
equipment
Class C:
Fire involving:
Combustible metals such
as potassium, sodium,
magnesium and other
reactive metals
Class D:
How to
Suppress:
Use Water
Exclude air from
burning materials
No Water; Use electrically
non-conductive
extinguishing agents such
as gaseous systems
Heat-absorbing
medium which is not
reactive with burning
metals
Intro Classes of Fire
3
4. Intro Fire Growth
2
Pre-flashover or
growth phase
Stage 1:
FlashoverStage 2:
Fully developed
fire (Stable phase)
Stage 3:
Decay (Cooling
Period)
Stage 4:
Involves flaming combustion of an
item and may lead to a spread of
fire; or a smoldering, poorly-
ventilated fire with substantial
smoke.
Rapid change from a local fire to
one involving all combustible
materials in a room.
All materials in compartment are
alight; maximum rate of heat
release is dependent on either
available ventilation or quantity of
fuel.
Gradual consumption of fuel in the
compartment.
Stages
5. Behavior of Fire and Smoke
1
Vertical Shaft or Duct
(Stack Effect)
Suspended Ceiling
Ceiling Void
Smoke and Flame
likely to re-enter Enclosed Area
Vertical Shaft or Duct
Outlet to
adjoining space
Enclosed
Area
Outlet to
open air
1.00 m
Intro
6. Internal Fire Spread due to:
Internal Fire Spread
between Rooms and Floors
Through
Vertical
Shafts
Through Air Ducts
Through Ceiling and
Collapsed Partitions
Through Non-Fire
Rated Doors
Origin of Fire
Fire Spread
2Intro
8. Fire Spread
2
Ignition of Materials
Ignition of Materials
Ignition of Materials
Ignition of Materials
Convection
Currents
Origin of Fire
Proximity of Buildings
Intro
External Fire Spread due to:
9. Aims in
Fire Safety Design
A To prevent fire
B To safeguard the lives of
occupants and firefighters
C To reduce damage on the
building, its contents, and on
surrounding buildings
11. Definition & Implication
PrinciplesFire Avoidance1
1
Reducing the possibility of accidental ignition of
construction materials, as well as fittings and
fixtures.
This implies:
a. keeping separate heat
sources and materials which
might ignite readily through
proper planning and zoning
b. need to specify materials to
reduce the risk of fire starting
c. reducing fire load
Basic
12. PrinciplesFire Avoidance1
1
ForHospitals
(eg. Hospitals)Fire Zoning
Basic
ForMostBuildings
1. Life Risk Areas – areas in which all occupants are ambulant and
able to move unaided away from a fire
- eg. Outpatient department; Service Zone
2. High Fire Risk Areas – areas which, due to their function, are
more usually susceptible to an outbreak of fire, or to a rapid spread of
fire or smoke.
- eg. Kitchen or Boiler Room
3. High Fire Load Areas – areas which, because of their
construction or contents, contain large amounts of combustible
materials, thereby constituting a fire load in excess of that normally
found
- eg. Gas Storage, Linen Closets
4. High Life Risk Areas – areas in which persons may reside and
are not able to move unaided away from a fire.
- eg. Intensive Care Unit, Operating Department
13. Choice of Materials and Knowledge
on Material Performance
1
Steel
- does not burn
- may buckle in fire
- high conductivity spreads
heat
- loses half its strength in
550°C
Timber
- combustible
- little loss of strength
as charcoal formed
insulates wood core
- spreads flames
Masonry
- high fire resistance
- cracks at 575°C
- are subject to high
temperatures during
manufacture
Calcium Silicate
- excellent thermal shock
resistance
- up to 1000°C
- suitable for cladding
structural members
Glass
- standard float, toughened
and laminated glass panes do
not provide any fire resistance
- monolithic fire-rated glass is
available
Basic
PrinciplesFire Avoidance2
1
Concrete
-high fire resistance
- disintegrates at 400-500°C
- holes in concrete will
expose steel structural
members
14. “the amount of material which is able to burn
and release heat and smoke”
In a compartment, limiting fuel will
help reduce the dangers of heat and
smoke.
Building contents make up the
majority of the fire load, since most
fires start from the ignition of these
contents.
The total amount of fuel in a building, its accessibility to fire
engines, the availability of water, etc. will determine the level
of fire resistance and the maximum size of a building
compartment.
Basic
PrinciplesFire Avoidance2
1
Knowledge on Fire Load
1
15. Visual Fire Detection
To visually expose FIRE RISK and FIRE LOAD
areas to building occupants.
Basic
Principles
Patient Room
Nurse Station
Patient Room
Sto
2Fire Detection
Lounge
16. fire-prone areas
should be visually
accessible
provide peepholes
on doors
Basic
Principles
Visual Fire Detection
2Fire Detection
17. Makes use of manual and automatic (electric/
electronic) methods of informing the occupants in
charge that a fire has occurred in a given location.
Heat and smoke alarm systems
inside Fire Risk and Fire Load
areas.
Basic
Principles
Mechanical Fire Detection
2Fire Detection
Fire alarm systems must be
accessible in all zones especially in
fire-prone areas.
18. Aimed at ensuring that the growing fire is extinguished
immediately and at providing adequate time for firemen to
arrive, control the fire and evacuate the occupants.
Basic
Principles
Actively extinguishing or slowing down
the development of a fire before the full
involvement of the room. This is done
by the room’s local occupants.
Means:
1. Fire Extinguisher
2. Water Supply
3. Fire Blanket
4. Bucket of Sand
3Fire Growth Restriction
Manual Means of Restricting
Fire Growth
5
19. Basic
Principles 3Fire Growth Restriction
Rating of Fire Extinguishers
4
:
Class A Extinguishers will put out fires in ordinary
combustibles, such as wood and paper. The numerical rating
for this class of fire extinguisher refers to the amount of water
the fire extinguisher holds and the amount of fire it will
extinguish
Class B Extinguishers should be used on fires involving
flammable liquids, such as grease, gasoline, oil, etc. The
numerical rating for this class of fire extinguisher states the
approximate number of square feet of a flammable liquid fire
that a non-expert person can expect to extinguish
Class C Extinguishers are suitable for use on electrically
energized fires. This class of fire extinguishers does not have
a numerical rating. The presence of the letter “C” indicates
that the extinguishing agent is non-conductive
Class D Extinguishers are designed for use on flammable
metals and are often specific for the type of metal in
question. There is no picture designator for Class D
extinguishers. These extinguishers generally have no rating
nor are they given a multi-purpose rating for use on other
types of fires
20. Basic
Principles 3Fire Growth Restriction
Types of Fire Extinguishers
4
:
Dry Chemical extinguishers are usually rated for multiple purpose use. They
contain an extinguishing agent and use a compressed, non-flammable gas as a
propellant
Halon extinguishers contain a gas that interrupts the chemical reaction that takes
place when fuels burn. These types of extinguishers are often used to protect
valuable electrical equipment since them leave no residue to clean up. Halon
extinguishers have a limited range, usually 1.2 to 1.8 meters. The initial application
of Halon should be made at the base of the fire, even after the flames have been
extinguished
Carbon Dioxide (CO2) extinguishers are most effective on Class B and C (liquids
and electrical) fires. Since the gas disperses quickly, these extinguishers are only
effective from 1.0 to 2.4 feet. The carbon dioxide is stored as a compressed liquid
in the extinguisher; as it expands, it cools the surrounding air. The cooling will often
cause ice to form around the “horn” where the gas is expelled from the
extinguisher. Since the fire could re-ignite, continue to apply the agent even after
the fire appears to be out
21. Basic
Principles
-Categories: General Use, Institutional,
Residential, Attics, Special Hazards,
Storage
-3 heads: upright, pendent and sidewall
-Rated to 175 psi
3Fire Growth Restriction
Mechanical Means of
Restricting Fire Growth
6
Sprinkler Specifications:
Sprinklers can be spaced
from 3.6 to 6.0 meters apart.
22. Assumes that measures to control a growing fire
may not be successful, hence its maximum size
needs to be restricted both to reduce the risk
and to allow effective firefighting.
Extend CHB
walls up to
slab
Provide 1 m.
ledge to prevent
spread of fire
- providing a 1-meter ledge to prevent fire from creeping up
exterior walls into the floor above through windows.
This implies:
1. Fire cladding of structural components to ensure stability
of structural frames.
2. The use of fire-rated walls and slabs to contain fire in
rooms, sub-compartments and compartments so as to
segregate areas where fire may occur.
3. Others:
- plugging all holes; extending CHB walls up to the slab;
Basic
Principles 4Fire Containment
Definition and Implication
23. Fire-Rated
Surface
Compartment
Compartment
Sizes
The more combustible the contents of a building, the
smaller the compartment should be.
Joints must be filled with non-combustible materials
to prevent the spread of smoke or flame.
Objectives
-To limit fire and smoke spread
-To allow longer escape time
-To reduce the maximum potential size of the fire
Containing fire-
prone areas by
means of fire-
resistive
enclosures
Definition
Basic
Principles 4Fire Containment
Sub-Compartment
Concepts of Fire Compartmentation
2
Room
24. Basic
Principles 4Fire Containment
Fire Rating of Construction Systems
3
Gypsum Walls
-Two layers 16mm type X gypsum
wallboard or veneer base applied
to each side of 62mm metal studs
400mm O.C.
-Two layers 16mm type X gypsum
wallboard or veneer base applied
to each side of 50mmx100mm
wood studs 600mm O.C.
-One layer 16mm type X
gypsum wallboard or veneer
base applied to each side of
40mm metal studs 600mm
O.C.
-One layer 12mm type X
veneer base nailed to each
side of 50mmX100mm wood
studs 400mm O.C.
SteelWoodSteelWood
2 Hour1 Hour
Concrete Masonry Wall Units
4 Hour2 Hour
4” 6”
25. Basic
Principles 4Fire Containment
Fire Rating of Construction Systems
3
-Flush Metal Door
-No Glass Permitted
-3mm clearance at jambs
-10mm clearance at non-combustinle floor
-For openings in fire walls or walls that
divide a single building into fire areas
-Maximum glass area 0.063 sq.m
-6mm thk Wire glass in a steel frame
-For openings in enclosures of vertical
communications through buildings and in
2-hour rated partitions providing horizontal
fire separations
-Maximum glass area: 0.83 sq.m
-For openings in walls or partitions
between rooms and corridors having a fire
resistance rating of 1 hour or less
3 Hour2 Hour1 Hour
Door Openings For 1.2m X 3.0m single hollow metal doors (ga.20 steel face), with
labeled single-point or 3-point latching hardware, steel hinges or pivots
1.370m
max
0.83m
max
125mm
min
125mm
min
26. Covers those devices and systems which aid
firefighters in actively extinguishing the fire and
bringing it to an end earlier than a free-burning fire.
ensure that all areas inside
and outside the building
are covered by reach of the
firehose
Basic
Principles 5Fire Control
Definition and Implication
access road for firetrucks
Access Road
27. Basic
Principles 5Fire Control
Fire apparatus should have
unobstructed access to
buildings.
R
L
W
Bollards and fences used for
traffic control must allow for
sufficient open road width for fire
truck
Site Access for Fire Control8:
30m> DEAD END
CUL-DE-SAC
T-TURN
Prevent time-consuming, hazardous
back-ups at dead-ends by using T-
turns and cul-de-sacs
MAX. 90 METERS
FIRE HYDRANT
Place hydrants at max. 3 meters
from curb. Siamese connection
to standpipes must be visible
and within 60m from hydrant
SIAMESE
CONNECTION
Utility poles, kiosks, sculpture,
fountains, plant boxes can impede
fire rescue operations
0.3m
Hydrant must be
unobstructed; Fire hose
connection should be at
least 0.3m above grade
28. Basic
Principles 5Fire Control
Firetrucks
75 ° (safe
angle)
30m.
33m.
Approx. 10 storeys
8.5 m.
26m.
75 °
25m.
Approx. 8-9 storeys
6.7 m.
22m.
75 °
20m.
Approx. 6-7 storeys
5.6 m.
Aerial Apparatus
Specifications:
29. Provides access to a building, especially in high
rise buildings, for fire brigades.
Is fully-equipped with firefighting equipment,
service elevator, stair and lobby.
Provides a sufficiently secure operating base
and a rest area in between firefighting
operations.
Wet and Dry
Risers
Elevator
shaft
Fire-rated
doors
Basic
Principles 5Fire Control
Concept of the Firefighting Shaft
30. Measures which can assist to some extent
occupants in the fire zone but are particularly
needed for others in adjacent areas or
compartments.
Techniques of Smoke
Control
a. SMOKE CONTAINMENT/
BARRIER – technique of
restricting the movement of
smoke by the provision of fire
resisting elements.
b. SMOKE DISPERSAL –
technique of clearing smoke
locally by provision of natural
cross-ventilation or mechanical
venting.
Make Up Air
Smoke Barrier
Smoke Plume
Shop
Mall
Basic
Principles 6Smoke Control
Definition and Techniques
2
Venting
Extraction of Smoke
Ceiling Reservoir
31. Low
Pressure
High
PressureUses barriers including
walls, floors and
doors, to contain
pressurized air
generated by
mechanical means to
keep smoke away
from protected areas
such as escape
staircases and
corridors.
c. PRESSURIZATION – technique whereby air is blown into
spaces which are designed to be kept clear of smoke.
Basic
Principles 6Smoke Control
Definition and Techniques
2
32. Cover a range of passive or active systems which
permit the occupants to move or be moved to a
place of safety within or to the outside of a building.
FIRE ESCAPE:
fire escape stairs designed to be used daily for familiarity
of escape route
well-maintained (not used as storage of junk)
CORRIDOR SYSTEM:
direct, not tortuous
simple lay-out
no barriers, cul-de-sacs, bottlenecks
doors open out, not in
easily detectible, not hidden from view
Basic
Principles 7Escape Provisions
Definition
33. Escape Route Leading to:
Place of Safety
Place of Safety
Stairway
Enclosure
c. Protected Stairway Enclosure
Place of Safety Place of Safety
Protected Escape
Route
a. Protected Escape Route
Place of Safety
Place of Safety
Protected Lobby
b. Protected Lobby
To provide safety,
the routes must
be properly
protected from
the effects of fire
and smoke for an
acceptable time
period, usually a
minimum of 60
minutes.
This can be
achieved by:
- Compartmentation
- Fire resistance of
escape route
structure
- Use of smoke
control systems to
keep smoke out of
escape routes
Protected escape routes are designed in such a
way that they lead to a place of safety, and once
inside the occupants are safe from the immediate
danger from fire and smoke.
Basic
Principles 7Escape Provisions
Protected Escape Routes
1
34. Access through
Courtyards
exit courtyard
Alternative
Means of Escape
-Doors should be as far
as possible from each
other; preferably on
opposite walls
-Both doors should not
open into the same
compartment
compart-
ment
courtyard
subcomp-
artment subcomp-
artment
subcomp-
artmentsubcomp-
artment
Place of
Safety
Place of
Safety
Basic
Principles 7Escape Provisions
Alternative Means of Escape
1
36. Means of EgressMeans of Egress
Components of an Egress System
1. Exit Access – a corridor, an aisle, a path across a room, or a short stair or
ramp that conducts the occupants of a building to an exit.
2. Exit – a protected means of evacuation (door opening, an enclosed and
protected exit passageway leading to a door, or an enclosed exit stair or
ramp) from an exit access to a safe discharge point, must be of 2 hour
construction with self closing doors rated at 1 1/2 hrs.
3. Exit Discharge – a means (door, protected exit corridor, path across a
ground floor vestibule or lobby) of moving from an exit to a safe discharge
point (public way or other large open area.)
37. Distance Between ExitsDistance Between Exits
The minimum distance between exits is one-half the diagonal measurement of the building or the space served by the exits. On an open floor, this is measured as a straight-line
distance between exits. Where the exits are joined by an exit access corridor that is protected from fire as specified by the building code, this distance is measured along
the path through the corridor.
Most buildings require at least two separate exits. These must be as remote from each other as possible and arranged to minimize the possibility that a single fire or other
emergency condition could simultaneously render both exits unsafe or inaccessible. With only minor exceptions, the access path to an exit may not pass through kitchens,
restrooms, storerooms, workrooms, bedrooms, hazardous areas, or rooms subject to being locked.
Two Remote ExitsTwo Remote Exits
39. Maximum Travel DistanceMaximum Travel Distance
Maximum travel distance to the nearest exit is specified by the code. Travel distance is
always measured along the actual path occupants must take to reach an exit. There are two
way to measure as shown on the diagram. The code will dictate which way you must
measure it.
40. DoorsDoors
Doors should always swing in the direction of egress travel in all buildings except
single family dwellings and in all rooms except those with fewer than 50
occupants.
Exit access corridors must be enclosed in fire-resistant walls and accessed via fire-
resistant doors. One-hour walls with 20-minute doors are required in most
buildings.
41. Exit StairwayExit Stairway
The most common type of exit is an enclosed stairway. The enclosure must be of 2-hour
construction with 1 ½ hour self-closing doors that swing in the direction of egress travel.
Stairway and landing widths are determined in accordance with the occupant load they serve
and are calculated according guidelines in the prevailing codes.
44. "Travel Distance" means the actual distance to be travelled by a
person from any point within a floor area to the nearest protected route
or final exit having regard to layout of walls, partitions and fittings.
Safety from fire is normally considered to be attained in the open, at
ground
level at a point clear of the building. In larger, fire-compartmented
buildings,
safety from fire may be considered in terms of partial evacuation, or
evacuation to a place of relative safety. Generally, however, three
stages of evacuation accommodation can be identified:
Stages of Evacuation
(i) evacuation from room
(ii) horizontal evacuation
(iii) vertical evacuation
45. REFUGE AREAS
For buildings more than 24m in height, refuge area of 15 sq.m or an area
equivalent to 0.3 sq.m per person to accommodate the occupants of two
consecutive floors,which ever is higher, shall be provided as under.
For floors above 24 mt and up to 39 m - One refuge area on the floor
immediately above 24 m.
For floors above 39 m- One refuge area on the floor immediately above 39 m and
so on after every 15 m. Refuge area provided in excess of the requirements shall
be counted towards FAR.
The refuge area shall be provided on the periphery of the floor and open to air,
at-least on one side, protected with suitable railings.
46. RAMPS
Ramps shall comply with all the applicable requirements of stairways
regarding enclosure capacity and limiting dimensions.
The slope of a ramp shall not exceed 1 in 10. Ramps with slopes greater
than those recommended render them difficult to be used, particularly by
physically handicapped elderly people and children, and hence this
requirement.
Ramps in means of egress are required to be enclosed or protected.
Further, they must have landings located at the top, at the bottom
and at doors opening into the ramp
47. Automatic Fire Detection and Alarm
System:
Fire Alarm system comprising components for
automati cally detecting a fire, initiating an alarm
of fire and initiating other actions as appropriate.
Automatic Sprinkler System:
A system of water pipes fitted with sprinkler
heads at suitable intervals and heights and
designed to actuate automatically, control and
extinguish a fire by discharge of water.
Combustible Material:
The material which either burns itself or adds
heat to a fire.
48. Down comer:
An arrangement of fire fighting within the building
by means of down comer pipe connected to
terrace tank through terrace pump, gate valve
and non return valve and having mains not less
than 100mm internal diameter with landing
valves on each floor landing. It is also fitted with
inlet connections at ground level for charging
with water by pumping from fire services
appliances and air release valve at roof level to
release trapped air inside.
Dry Riser:
An arrangement of fire fighting within the building
by means of vertical rising mains not less than
100mm internal diameter with landing valves on
each floor/landing, which is normally dry but is
capable of being charged with water usually by
pumping from fire service appliances.
49. Emergency Lighting:
Lighting provided for use when the supply to the
normal lighting fails.
Requirements for installation, operation and
maintenance of emergency systems circuits and
equipments are given in National Electric Code(NEC).
Escape Lighting:
That part of emergency lighting which is provided
to ensure that the escape route is illuminated at
all material times (for example, at all times when
persons are on the premises), or at times the
main lighting is not available, either for the whole
building or the escape routes.
50. Escape lighting luminaries should be sited to
cover the following locations:
(a) Near each intersection of corridors,
(b) At each exit door,
(c) Near each change of direction in escape route,
(d) Near each staircase so that each flight of stairs
receives direct light,
(e) Near any other change of floor level,
(f) Outside each final exit and close to it,
(g) Near each fire alarm call point,
(h) Near fire fighting equipment, and
(j) To illuminate exit and safety signs as required
by the enforcing authority.
51. Fire Door:
A fire-resistive door approved for openings in
fire separation walls.
Fire Lift:
The lift installed to enable fire services personnel
to reach different floors with minimum deley,
having such features as required in accordance
with this Part.
Fire Resistance Rating:
The time that a material or construction will
withstand the standard fire exposure as
determined by fire test done in accordance with
the standard methods of fire tests of materials/
structures.
52.
53. Fire Lift:
The lift installed to enable fire services personnel
to reach different floors with minimum deley,
having such features as required in accordance
with this Part.
4.15. Fire Lifts
4.15.1. Where applicable, fire lifts shall be provided with
a minimum capacity for 8 passengers and fully
automated with emergency switch on ground
level. In general, buildings 15m in height or above
shall be provided with fire lifts.
4.15.2. In case of fire, only firemen or any member of
fire service shall operate the fire lift. In normal
course, lifts may be used by other persons.
54. 4.15.3. Each fire lift shall be equipped with suitable
intercommunication equipment for communicating
with the control room on the ground
floor of the building.
4.15.4. The number and location of fire lifts in a building
shall be decided after taking into consideration
various factors like building population, floor area,
compartmentation etc.
55. Fire Tower:
An enclosed staircase which can only be
approached from the various floors through
landings or lobbies separated from both the floor
areas and the staircase by fire-resisting doors,
and open to the outer air.
Means of Egress:
A continuous and unobstructed way of travel
from any point in a building or structure to a place
of comparative safety.
Wet Riser
An arrangement for fire fighting within the
building by means of vertical rising mains of not
less than 100 mm diameter with landing valves
on each floor/landing for fire fighting purposes and
permanently charged with water from a pressurised
56. Wet Riser
Difference between this and a dry riser, is that wet
risers are permanently charged with water by a fire
pump from a permanent water supply (which can
either be an underground water tank or an elevated
water tank at the terrace), whereas, the dry riser has
to be fed with water by fire brigade after their arrival.
Landing valves are nothing but internal hydrants
fitted with standard instantaneous female couplings
and may be of single or double outlet types.
57. Pressurisation is a method adopted for protected
escape routes against ingress of smoke,
especially in high-rise buildings.In pressurisation
air injected into the staircases, lobbies or
corridors, to raise their pressure in adjacent parts
of the building .As a result, ingress of smoke or
toxic gases into the escape routes will be
prevented.
Pressurisation system may be of two types:
(a) Single-stage, designed for operation only in the
event of emergency, and
(b) Two-stage, where normally a level of
pressurisation is maintained in the protected
escape routes, and an increased level of
pressurisation can be brought into operation in
an emergency.
58. Fire Extinguishing Equipment:
Portable fire
extinguishingManualFireExtinguishingEquipme
-These devices are used for extinguishing fire as soon-
as it starts.
-They are not so useful when once the fire has spread.
The discharge from a portable fire extinguisher lasts only
for a short duration of 20 to 120 seconds.
Fire sand bucket
- A fire sand bucket or fire bucket is a steel
bucket filled withstand which is used to put out
fires.
-They are placed in prominent positions in rooms
or corridors. They are a low-technology method
of fighting small fires.
-The main advantages of fire buckets are that
they are cheap, reliable and easy to use.
59. Fire Hydrants
These are provided on a ring main of 150 mm dia. in the
ground around the building periphery. The ring main gets
water from under ground water tank with pressure, so that
available pressure at each hydrant is of the order of about
3.5 to 4 kg/cm. The fire hydrants are placed at 300ft.c/c with
easy access in case of emergency.
Automatic Sprinkler System
- This arrangement is adopted for Commercial & industrial
buildings.
-The system consists of a net work of 20 mm dia. Fixed to
the ceiling of the room spaced at 3 m center to center.
-Heat actuated sprinkler heads are fixed to these pipes. The
pipes get supply from a header. Each sprinkler head is
provided with a fusible plug.
-In the event of fire, the fusible plug in the sprinkler nearest
to the wire melts due to rise of temperature, and water
gushes out of the sprinkler head. The fire is thus brought
under control in a short period.
60. Wet Riser system
These system is adopted in high rise Buildings as wellas Public
buildings such as Cinemas,malls,Multiplexes etc. The system consist
of providing 100 to 150 mm dia. vertical G.I.Pipes (Risers) at suitable
locations in the buildings. A fire pump is used to feed water from
under ground fire fighting water tank to these pipes, to ensure a
pressure of 3 kg/cm2. at upper most outlet.
The fire fighting tank of 75,000 litres to 1 lakh litres are provided.
61.
62. • 1 fire station or sub fire station within 1
to 3 km to be provided for 2 lakh
population
• Area for fire station with essential
residential accommodation
• Area for sub- fire-station with essential
residential accommodation
1 ha
0.60
ha
Norms as per UDPFI Guidelines: