N999 – Basic Drive Programming 
PowerFlex N999 – 753 
Your lab title goes here 
Presenter: <<Your name>> 
<<Your business group>> 
Presenter: <<Your name>> 
Rockwell Automation Drives Business 
For Classroom Use Only! 
Publication Number -- Date Copyright © 2009 Rockw ell Automation, Inc.
PowerFlex 753 Basic Start Up for Speed Controlled 
3 of 68 
Applications 
Contents 
Before you begin .............................................................................................................................. 5 
Tools ................................................................................................................................................. 5 
About this lab ..................................................................................................................................... 5 
About the Demo ................................................................................................................................ 6 
Lab Setup.......................................................................................................................................... 7 
Lab Objective .................................................................................................................................... 8 
Using the Human Interface Module (H.I.M)........................................................................................ 9 
Disabling DeviceLogix Program – IF LOADED & RUNNING ............................................................ 10 
Preparing the PowerFlex 753 Demo To Run In Simulation Mode .................................................... 14 
Assisted Startup using the Human Interface Module (H.I.M)........................................................... 16 
Resetting factory defaults .................................................................................................................. 17 
Setting the Motor Control Mode ......................................................................................................... 20 
Entering Motor Nameplate Data......................................................................................................... 21 
Setting the Speed Feedback Device .................................................................................................. 24 
Setting the Speed Limits ................................................................................................................... 24 
Direction Auto Tune and Inertia Tests ................................................................................................ 25 
Configuring the Speed Reference and Ramp rates ............................................................................. 28 
Configuring the Inputs and Outputs .................................................................................................... 30
Drive Programming via Software Tool (Optional) ........................................................................... 32 
About This Section............................................................................................................................ 32 
Using Drive Explorer with PF753 ....................................................................................................... 32 
Starting Drive Explore and Connect To Drive ...................................................................................... 33 
Reset Drive to Defaults ..................................................................................................................... 36 
Displaying The Status View ............................................................................................................... 39 
Displaying Parameters with the Linear List View ................................................................................. 43 
Displaying Parameters with the File / Group View ............................................................................... 44 
Using the Startup Wizard................................................................................................................... 45 
Using the Control Bar Tool ................................................................................................................ 62 
Using Off-line Files ........................................................................................................................... 64 
4 of 68
5 of 68 
Before you begin 
Tools 
 PowerFlex 753 Training Demo 
 Windows XP PC with DriveExplorer (full version 6.02 or greater); for optional section 
About this lab 
This session provides you with an opportunity to explore the PowerFlex 753 AC drive. In this session you 
will learn to: 
 Use the Assisted Startup for simple Speed Controlled Applications 
 Control the Drive and simulate spinning a motor 
This lab takes approximately 45 minutes to complete.
6 of 68 
About the Demo 
The DHQ packaged PowerFlex 753 Demo is a reduced size, packaged demo kit for demonstrating 
programming of PowerFlex 753, as well as Premier Integration, and DeviceLogix. On board I/O facilitates 
user input as well as feedback. 
This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives 
internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production 
drive the demo itself was not designed to run an actual motor. There are no user connections to apply an 
external motor nor was the internal step up transformer or fusing sized to run anything greater then the 
drive rated current w/o any loading. 
The image below labels the switches, push buttons and the potentiometer required in this lab session. 
Di 0 – Normally Open Pushbutton 
Di 1 – Normally Closed Pushbutton 
Di 2 – Selector Switch 
0- 10 V Analog Input 
DRIVE POWER Circuit Breaker
7 of 68 
Lab Setup 
1. On the PowerFlex 753 demo case, verify position switch Di 2 is selected to the left (OFF) 
2. Energize the drive demo; switch the single-pole breaker labeled ‘POWER’, located on the front of 
the demo, to the on position.
8 of 68 
Lab Objective 
At the end of this lab, you should have successfully completed the Assisted Startup routine of the PF753 
drive and 
1. Programmed the Drive to start the drive/motor using the green pushbutton labeled ‘Di 1’. 
2. Programmed the Drive to stop the drive/motor using the red pushbutton labeled ‘Di 0’. 
3. Programmed the Drive to forward or reverse the drive/motor using t he selector switch labeled ‘Di 
2’. 
4. Programmed the Drive to get Speed Reference from an Analog Source, the potentiometer 
labeled ‘0-10 INPUT’.
Using the Human Interface Module (H.I.M) 
The image below shows some of the essential keys which you will be using in this session. Please 
familiarize yourself with these keys (buttons) 
9 of 68 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
00 
Soft Keys 
Navigation Keys 
Enter Key 
Stop Key 
Start Key Folders Key
Disabling DeviceLogix Program – IF LOADED & RUNNING 
If a DeviceLogix Program is loaded and running in the PowerFlex 753 demo, the logic needs to be 
disabled and the drive reset prior to conducting the lab. If the DeviceLogix program has not been 
properly disabled, the drive will not operate according to the lab procedure. 
Consult with your instructor before performing the following procedure: 
1. From the Status screen which is displayed on HIM PowerUp. Use the left or right 
arrow keys to navigate to the DeviceLogix option. 
10 of 68 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
 
DeviceLogix 
Embedded 
LogicEnabled 
14 
2. The HIM screenshot above shows the display if the DeviceLogix is enabled ‘LogicEnabled’. If the 
logic is disabled ‘LogicDisabld’ then disabling of the DeviceLogix is not required, skip to the next 
section. 
3. Press the ‘PAR#’ soft key and enter the number 53 followed by the ‘ENTER’ soft key to goto 
parameter 53 
Devi ceLogi x 
Jump t o Par am # 
53 
14 
 
Por t 14 Host Par am 53 
DLX Operation 
LogicEnabled 6
4. Use the ‘EDIT’ soft key followed by the scroll down or scroll up arrow soft keys to change 
parameter #53 to DisableLogic then the ‘ENTER’ soft key to confirm. 
11 of 68 
Edi t DLX Oper at i on 
DisableLogic 1 
0 << 6 
 
Por t 14 Host Par am 53 
DLX Operation 
LogicDisabld 5 
Parameter 53 [DLX Operation] is of the parameter type that contains both operation 
commands as well as status information. Setting it to disable logic is option 1, however 
once the ‘ENTER’ key is pressed to confirm the display is option 5 “LogicDisabled”. 
5. Press the ‘ESC’ soft key to return the display to the top level DeviceLogix screen 
DeviceLogix 
Embedded 
LogicDisabld 
14 
6. Use the left or right arrow keys to navigate to the drives initial screen (Main 
Control Board Slot 0) 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2
7. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of 
the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the 
HIM screen display to the Folders screen ( see right image below) 
12 of 68 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
00 
PORTS 
00 Power Fl ex 753 
01 20- HI M- x6 
06 20- COMM- E 
14 Devi ceLogi x 
8. Use the left or right arrow keys to scroll through the different folders, to locate the 
folder called ‘DIAGNOSTIC’. 
DI AGNOSTI C 
Faul t s 
Al ar ms 
Di agnost i c I t ems 
Reset Devi ce
9. Use the down arrow key to highlight ‘ Reset Device’ then press the Enter key 
located in the center of the HIM keypad to make this your selection. 
13 of 68 
DI AGNOSTI C 
Faul t s 
Al ar ms 
Di agnost i c I t ems 
Reset Devi ce 
10. A confirmation screen follows press the ‘ENTER’ soft key to confirm your selection. 
C O N F I R M 
Ar e you sur e you want t o 
r eset t he devi ce 
11. The drive will then reset, upon completion the drive maybe faulted; press the ‘CLR’ soft key to 
clear acknowledge and clear fault.
Preparing the PowerFlex 753 Demo To Run In Simulation Mode 
This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives 
internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production 
drive the demo itself was NOT designed to run an actual motor. In order to complete the lab the feedback 
mode needs to changed to simulate. 
1. From the Status screen which is displayed on HIM PowerUp. Press the ‘PAR#’ soft key and 
enter the number 301 using the numeric keypad followed by the ‘ENTER’ soft key to goto 
parameter 301 [Access Level] 
14 of 68 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
 
Por t 00 Dev Par am 301 
Expert 2 
Access Level 
2. Verify that P301 [Access Level] is set to ‘Expert’ if not press the ‘EDIT’ soft key followed by the 
scroll down or scroll up arrow soft keys to change the parameter to Expert then the 
‘ENTER’ soft key to confirm. 
Edi t Access Level 
0 << 2 
Basic 0 
 
Por t 00 Dev Par am 301 
Expert 2 
Access Level
3. Press the ‘PAR#’ soft key and enter the number 125 followed by the ‘ENTER’ soft key to goto 
15 of 68 
parameter 125 [Pri Vel Fdbk Sel] 
Power Fl ex 753 
Jump t o Par am # 
125 
00 
 
Por t 00 Dev Par am 125 
Pri Vel Fdbk Sel 
P00 P0137 
Por t Power Fl ex 753 
EDI T 
4. Press the ‘EDIT’ soft key, the default (and only choice) for ‘Edit Spd Ref A Sel’ is PowerFlex 753. 
Make this selection using the ‘Enter’ soft key 
Edi t Spd Ref A Sel 
Sel ect Par m To Use 
Port 00 Power Fl ex 753 
5. For ‘Pri Vel Fdbk Sel’ selection use the down arrow key to select ‘Simulator Fdbk’. Then 
make this selection using the ‘Enter’ soft key. 
Edi t Pr i Vel Fdbk Sel 
Sel ect Par m To Use 
Si mul at or Fdbk 
Par 0137 
Par 0138 
Open Loop Fdbk 
6. Press the ‘ESC’ soft key to return the display to the top level Status Screen.
Assisted Startup using the Human Interface Module (H.I.M) 
One of the ways to perform an Assisted Startup on the PowerFlex 753 is using the Startup routine in the 
H.I.M. The following steps will lead you through that: 
1. Access the Status screen which is displayed on HIM PowerUp. 
16 of 68 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
2. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of 
the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the 
HIM screen display to the Folders screen ( see right image below) 
PowerFlex 753 
240V 4.2A 
20F . . . B4P2 
00 
PORTS 
00 Power Fl ex 753 
01 20- HI M- x6 
06 20- COMM- E 
14 Devi ceLogi x
17 of 68 
Resetting factory defaults 
3. Use the left or right arrow keys to scroll through the different folders, to locate the 
folder called ‘MEMORY’. 
MEMORY 
HI M CopyCat 
Set Def aul t s 
4. Use the down arrow key to highlight ‘ Set Defaults’ if necessary and press the Enter key 
located in the center of the HIM keypad to make this your selection. 
5. The screen which follows after completion of the previous step is shown. Use the down arrow key 
to highlight ‘This Port only’. Press the Enter key located in the center of the HIM 
keypad to make this your selection. 
Por t 00 Set Def aul t s 
Host and Por t s ( Pr ef er r ed) 
Thi s Por t Onl y 
ESC INFO
6. Use the soft key labeled ‘ALL’ to reset default all parameter settings in the Drive. 
18 of 68 
W A R N I N G 
Use MOST t o r eset t ypi cal 
set t i ngs on t hi s por t 
( pr ef er r ed) . Use ALL t o 
r eset al l set t i ngs 
ALL MOST 
7. Use the ‘CLR’ soft key to acknowledge and clear the ‘Module Defaulted’ fault. 
8. If you receive a screen that confirms that setting factor defaults is complete press the ‘ENTER’ 
soft key to confirm. 
9. Press the ‘Folders’ button on the HIM keypad again to access the Folders Menu. 
10. Now use the left or right arrow keys to scroll through the different folders, to 
locate the folder called ‘START UP’. 
START UP 
Begi n St ar t Up 
11. The first item listed in the ‘START UP’ folder is ‘Begin Start Up’ and this is highlighted by default. 
Press the Enter key located in the center of the HIM keypad to make this your selection.
12. The startup routine starts with an Introduction screen. Press the ‘ENTER’ soft key to continue. 
The ‘ENTER’ soft key is located on the top row of the HIM keypad. 
19 of 68 
Power Fl ex 753 St ar t up 
St ar t - Up consi st s of sever al 
st eps t o conf i gur e t he dr i ve. 
Pr ess ENTER 
ABORT ENTER 
Note: You can always use the ESC soft key to return to a previous step. 
13. Pressing the ‘ENTER’ soft key in the previous step has led you to a new screen, which allows you 
to select the type of startup you wish to perform. For this lab session, we will choose ‘General 
Startup’. This is highlighted by default. Press the ‘ENTER’ soft key located on the top row of the 
HIM keypad to make this your selection. 
Power Fl ex 753 St ar t up 
Gener al St ar t up 
Appl Speci f i c 
Exi t St ar t up 
ABORT ENTER
Compl et e t hese st eps i n or der : 
20 of 68 
Setting the Motor Control Mode 
14. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘General Startup Main 
Menu’. You will go through steps listed in this menu to configure your drive. Press ‘ENTER’ soft 
key to enter the first section ‘Motor Control’. 
Gener al St ar t up 
Mai n Menu 
Mot or Cont r ol 
Mot or Dat a 
Feedback 
ABORT ENTER 
Li mi t s 
15. The introduction screen provides information about the ‘Motor Control section. Press the ‘ENTER’ 
soft key to continue. 
St ar t up 
Mot or Cont r ol 
Thi s sect i on sel ect s t he t ype 
of Mot or Cont r ol t he dr i ve wi l l 
use. 
Pr ess ENTER 
ABORT ENTER
16. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available 
motor control modes in the PowerFlex 753. For this lab session, we will choose the Flux Vector 
mode. Use the down arrow key to navigate and select ‘Flux Vector’. Press the ‘ENTER’ 
soft key to make this your selection. 
St ar t up 
Mot or Cont r ol 
Pl ease Sel ect : 
ABORT ENTER 
Compl et e t hese st eps i n or der : 
21 of 68 
Sensor l ess Vect 
V/ Hz 
Fl ux Vect or 
17. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available 
Control Modes in the PowerFlex 753. For this lab session, we will choose the default selection of 
‘Speed’. Press the ‘ENTER’ soft key to make this your selection 
Entering Motor Nameplate Data 
18. After selecting the motor control mode in the previous step, you are directed back to the General 
Startup Main Menu. ‘Motor Data’ should be highlighted now. Press the ‘ENTER’ soft key to 
make this your selection. The next few steps will require you to input the nameplate information 
of the motor you are doing a Startup on. 
Gener al St ar t up 
Mai n Menu 
Mot or Cont r ol 
Mot or Dat a 
Feedback 
ABORT ENTER 
Li mi t s
19. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘Startup Motor Data Entry’ 
screen. The first information you will provide is the Motor Nameplate (NP) Volts. The Motor in the 
demo is rated for 230 V. This should be the default value for this parameter. Press the ‘ENTER’ 
soft key to confirm your input and move to the next screen. 
230.00 VAC 
22 of 68 
St ar t up 
Mot or Dat a Ent r y 
Edi t Mot or NP Vol t s 
0.10 << 264.50 
20. The next information you need to provide is the Power Units. By default the value of the 
parameter should be set to ‘HP’. Press the ‘ENTER’ soft key to confirm your selection and move 
to the next screen. 
Mot or Dat a Ent r y 
Sel ect t ype of power uni t s 
Shown on mot or namepl at e: 
ABORT ENTER 
St ar t up 
HP 
kW
21. You will now be required to input the Motor Nameplate (NP) Power. Since there actually is no 
motor connected use the default of 1.00 HP Press the ‘ENTER’ soft key to confirm your input and 
move to the next screen. 
23 of 68 
Edi t Mot or NP Power 
0.01 << 2000.00 
1.00 HP 
St ar t up 
Mot or Dat a Ent r y 
22. You will now be required to input the Motor Nameplate (NP) Amperes. Again accept the default 
value here. Press the ‘ENTER’ soft key to confirm your input and move to the next screen. 
St ar t up 
Mot or Dat a Ent r y 
Edi t Mot or NP Amps 
2.90 Amps 
0.01 << 42.00 
23. Continue through the Startup / Motor Data Entry section choosing the default values. Once all 
the Motor Data Entry steps are complete you will be brought back to the General Startup Main 
Menu with “Feedback” being highlighted.
Setting the Speed Feedback Device 
24. Setting the Speed Feedback Device will be skipped in this lab – going back to “About The Demo” 
section there is physically no actually motor and the demo unit was selected to a simulated 
feedback. Selecting this option now would force a feedback selection that is NOT valid for 
simulation mode. 
Compl et e t hese st eps i n or der : 
24 of 68 
Setting the Speed Limits 
25. In the previous step configuring your feedback device was skipped; configuring the limits is the 
next step in the Startup routine. Use the down arrow key to navigate to the ‘Limits’ step. 
. Press the ‘ENTER’ soft key to access ‘Limits’ section. 
Gener al St ar t up 
Mai n Menu 
Mot or Cont r ol 
Mot or Dat a 
Feedback 
ABORT ENTER 
Li mi t s 
26. For this lab session, we will not be changing the limits but verify the following selections in the 
‘Limits’ section. Use the number keys to input the values listed for each item and press the 
‘ENTER’ soft key to move forward to the next screen. After the four values have been entered, 
you will be exited out of this section. 
Max Fwd Speed = 60 Hz 
Max Rev Speed = -60 Hz (you can directly enter a value of ‘60’; the negative s ign is defaulted) 
Min Fwd Speed = 0.00 Hz 
Min Rev Speed = 0.00 Hz
Direction Auto Tune and Inertia Tests 
27. You should now have been directed back to the General Startup Main Menu. The ’Tests’ section 
is next and should be highlighted by default at this stage. Press the ‘ENTER’ soft key to access 
‘Tests’ section. 
Mai n Menu 
Compl et e t hese st eps i n or der : 
Mot or Dat a 
Feedback 
ABORT ENTER 
25 of 68 
Gener al St ar t up 
Li mi t s 
Test s 
28. There are two tests which are part of the Startup Routine. You will perform these tests in the next 
few steps. You will run the Direction test first. The ‘Direction Test’ list item should be highlighted 
by default. Press the ‘ENTER’ soft key to make this your selection. Press the Start key to 
start the motor. 
29. The next screen asks the question ‘Is the direction of rotation forward?’ To demonstrate the 
ability of the PowerFlex 753 to electronically swap motor leads to change motor direction, let us 
choose ‘No’ as the answer to this question. Use the down arrow key to select and 
highlight ‘No’ and press the Press the ‘ENTER’ soft key. 
St ar t up 
Di r ect i on Test 
I s t he di r ect i on of r ot at i on 
f or war d? 
Yes 
No
30. The next screen asks the question ‘How would you like to fix motor polarity? ’. Select the default 
highlighted option ‘Automatic change’ by using the ‘ENTER’ soft key. 
How woul d you l i ke t o f i x t he 
mot or pol ar i t y? 
Aut omat i c Change 
26 of 68 
St ar t up 
Di r ect i on Test 
Change mt r wi r es 
31. The screen that follows asks you to stop the drive so this change in direction, initiated in the 
previous step, can take place. Press the ‘STOP’ key to stop the drive. 
St ar t up 
Di r ect i on Test 
Pr ess STOP 
St ar t up wi l l t hen aut omat i cal l y 
change r ot at i on as i f mot or 
l eads wer e r ever sed 
32. Follow the direction on the next screen which asks you t o ‘START’ the drive. You can start the 
drive and by using the START key. 
33. The next screen asks the question ‘Is the direction of rotation forward?’ and requires confirmation 
that the changes to direction are acceptable. Select ‘Yes’ by pressing the ‘ENTER’ soft key. 
34. Press the Stop key .This should successfully complete the Direction test. 
35. You should now be back in the ‘Motor Test Menu’ screen. Now use the ‘ENTER’ soft key to select 
the ‘Auto tune’ Test. Read the important information on the screen and press the ‘ENTER’ soft 
key.
36. Pressing the ‘ENTER’ soft key in the previous step has directed you to the ‘Select the tuning 
mode’ screen. For this lab session, we will perform a rotate tune on the demo motor. Select the 
default highlighted option ‘Rotate Tune’ by pressing the ‘ENTER’ soft key. 
37. As directed by the HIM screen information, press the START key to start the ‘Auto tune’ 
Test. Notice the changing information on the HIM (as the different parts of the Auto tune tests are 
completed).Wait till the test is completed. 
27 of 68 
St ar t up 
Aut o Tune 
Test i n pr ogr ess: 
St at or Resi st ance 
Pl ease Wai t 
Pr ess STOP t o abor t t est 
St ar t up 
Aut o Tune 
Test i n pr ogr ess: 
Fl ux Cur r ent 
Pl ease Wai t 
Pr ess STOP t o abor t t est 
38. The completion of the test is indicated by the ‘Test Completed Successfully’ screen. Press the 
‘ENTER’ soft key. 
39. Select the ‘Inertia Test’ using the ‘ENTER’ soft key and use the ‘ENTER’ soft key again to confirm 
that the load is connected to the motor. 
40. As directed by the HIM screen information, press the START key to start the ‘Inertia’ Test.
41. The completion of the test is indicated by the ‘Test Completed Successfully’ screen . Press the 
‘ENTER’ soft key. This will bring up the ‘Edit Speed Reg BW’ entry screen. Select the ‘ENTER’ 
soft key to accept the default value of 10.00 R/S. 
28 of 68 
Edi t Speed Reg BW 
0.00 << 100.00 
10.00 R/S 
St ar t up 
I ner t i a Test 
42. Pressing the ‘ENTER’ key in the previous step has directed you bac k to the ‘Motor Test Menu’. 
Use the ‘ENTER’ soft key to select ‘Done’ in the ‘Motor Test Menu’ screen. 
Configuring the Speed Reference and Ramp rates 
43. At this time you should be in the ‘General Startup Main Menu’. The next item on the Startup 
menu list’ Ref Ramp Stop’ should be highlighted by default. Press the ‘ENTER’ soft key to make 
this your selection. 
44. The ‘Edit Direction Mode’ box should be on the screen now. We will use the default parameter 
value of ‘Unipolar’ for this lab session. Press the ‘ENTER’ soft key to confirm and save your 
selection. 
45. You should be on the ‘speed reference source’ selection screen. Use the down arrow or 
up arrow keys to highlight ‘Analog Input’ as your Speed Reference source. Use the 
‘ENTER’ soft key to make this your selection.
46. In the window ‘Select Port to Use’ that appears following the previous step, use the down arrow 
or up arrow keys to highlight ‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key 
29 of 68 
to confirm and save your selection. 
St ar t up 
Ref er ence Sel ect i on 
Edi t Spd Ref A Sel 
Sel ect Por t To Use 
Zer o Speed 
Port 00 Power Fl ex 753 
47. Use the down arrow and up arrow keys, to highlight ‘Par 0260 Anlg In0 Value’. The 
selected choice is the last in the list and pressing the once will get you there faster. Press 
the ‘ENTER’ soft key to confirm and save your selection. 
St ar t up 
Ref er ence Sel ect i on 
Edi t Spd Ref A Sel 
Sel ect Par m To Use 
Par 0878 
Por t 14 Ref er ence 
Anl g I n0 Val ue 
Par 0876 
Par 0260 
Por t 6 Ref er ence 
48. The next few steps will configure the Analog Input you chose as Speed Reference. For this lab 
session we will use the 0-10V potentiometer (labeled 0-10 Input) on the demo as our Analog 
Input speed reference. Pressing the ‘ENTER’ soft key in the previous step has led you to the first 
item required to configure the Analog Input. You should be in ‘Edit Anlg In0 Hi’ screen. Press the 
‘ENTER’ soft key to accept the default value of ‘10.000’ Volt. 
49. In the ’Edit Anlg In0 Lo’ screen that follows, press the ‘ENTER’ soft key to accept the default 
value of ‘0.000’ Volt. 
50. In the next few screens input these values 
‘Speed Ref A Anlg Hi’ = 60Hz and 
‘Speed Ref A Anlg Lo’ = 0Hz. Press the ‘ENTER’ soft key. 
51. You should be in the ‘Startup / Stop Config’ screen now, press the ‘ENTER’ soft key to accept the 
default selection of ‘Ramp’ to be used as ‘Stop Stop Mode A’.
52. Pressing the ‘ENTER’ key in the previous step has directed you to the screen to configure the 
‘Bus Reg Mode A’. Select the default of ‘Adjust Freq’ using the ‘ENTER’ soft key 
53. Following the step to set bus regulation you will now set Ramp (Accel and Decel) times. In the 
‘Edit Accel Time 1’ screen, use the appropriate number key to enter a value of ‘3’ seconds. Press 
the ‘ENTER’ soft key. 
54. Similarly enter a value of 3 seconds for the deceleration time in the ‘Edit Decel Time 1’ screen. 
30 of 68 
Press the ‘ENTER’ soft key. 
55. The next screen continues the ramp speed configuration and asks the question ‘Do you want to 
perform S-curve for Accel/Decel? ‘. We will select ‘No’ as the answer for this lab session. You can 
select ‘No’ by highlighting it using the down and up arrow keys and then using the 
‘ENTER’ soft key to confirm and save your selection. 
Configuring the Inputs and Outputs 
56. Completing the previous step successfully has led you to the ‘General Startup Main Menu’ with 
the item ‘I/O’ highlighted. Press the ‘ENTER’ soft key to enter the ‘I/O’ section. 
57. You should be in the ‘Start Stop I/O’ screen now. The first item to configure on this lis t is ‘Start 
Stop & Dir’. Press the ‘ENTER’ soft key to enter this section. Read the Introductory screen to this 
section and press the ‘ENTER’ soft key to continue. 
58. The next screen requires you to answer the question ‘Will a Digital Input be used as a START 
Source? Select ‘Yes’ using the down and up arrow keys and then using ‘ENTER’ 
soft key to confirm and save your selection. We will use the green push button labeled ’Di 1’ in 
the demo as our Start Source in a later step. 
59. The next screen will ask the question ‘Is Reverse required from a digital input?’? Select ‘Yes’ 
using the down and up arrow keys and then using ‘ENTER’ soft key to confirm and 
save your selection. We will use the switch labeled ’Di 2’ in the demo as forward/reverse in a 
later step. 
60. Select ‘3 wire’ as your choice for the question ‘Enter Choice for the control method’. 
61. In the ‘Edit DI Start / Select Port To Use’ window use the up and down arrow keys to highlight 
‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key to make this your selection. 
62. In the ‘Edit DI Start / Select Parm To Use’ window. Press the Enter soft key to select and confirm 
‘Par 0220 Digital In Sts’ selection. 
63. The ‘Edit DI Start’ window will be displayed first; select the bit/Digital Input you want to use as 
your START. We are going to use the green push button labeled ‘Di 1’ as our start input. To do 
this scroll to ‘Digital Input 1’ and press the Enter soft key.
64. Follow procedures similar to the previous steps to select the red push button labeled ‘Di 0’ as 
your stop switch and the selector switch labeled ‘Di 2’ as your Forward/Revers e switch in that 
order. 
65. You should now be back in the ‘Start Stop I/O’ menu screen. This is all we will configure in this 
section so use the down arrow keys to scroll down to the last item on the list ‘Done’. After 
‘Done’ is highlighted, use the ‘ENTER’ soft key to make this your selection. 
66. You should now be back in the General Startup Main Menu screen .you have finished with the 
Startup routine steps required for this lab session. Select ‘Done’ using the ‘ENTER’ soft key to 
exit out this screen. 
67. Select ‘Exit Startup’ using the ‘ENTER’ soft key to exit out of the Startup routine. 
68. You can now test your drive to perform the functions you configured during the startup routine 
namely, Start using the green push button Di 1, Stop using the red push button Di 0, change 
direction using Di 2 and provide speed reference using the ‘0-10V Input’ pot. 
Again, remember that there is no physical motor connected to this demo unit however the speed 
and status are being simulated on the top lines of the HIM display. 
31 of 68
Drive Programming via Software Tool (Optional) 
Besides the HIM the drive parameters and programming can be accessed via software tool. These tools 
include DriveTools SP, Drive Explorer, or RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater). 
32 of 68 
About This Section 
In this lab, we will introduce you to DriveExplorer software and some of the features that are common 
across all the software tools. In this lab you will: 
 Connect to a PowerFlex drive using DriveExplorer software 
 Display the Status View 
 Display and edit parameters with the Linear List View 
 Display and edit parameters with the File / Group View 
 Use the Control Bar to control a drive 
 Use a Wizard 
 Upload configuration from drive to PC 
 Download configuration to drive from PC 
Using Drive Explorer with PF753 
1. Verify that the PowerFlex 753 drive is connected to the computer. 
2. When using DriveExplorer, it may be necessary to shutdown RSLinx if it has the serial or USB 
driver configured. If RSLinx is running, it will display an icon in the Systray on the PC’s desktop.
3. Right click on the RSLinx Icon in the Systray. 
4. Select Shutdown RSLinx Classic on the Pop-up menu. 
Starting Drive Explore and Connect To Drive 
1. Double-click the DriveExplorer icon to start the software. 
2. If the Danger dialog appears, read it and click OK. 
3. Maximize the DriveExplorer window, so it fills the entire screen 
4. Click on the “Connect Ethernet” icon in the taskbar. 
33 of 68
a. If the ‘Connect Serial” icon has focus instead; DriveExplorer is configured to 
communicate serially; configuration path needs to be changed to Ethernet. Go to Explore 
 Configure communication  Select Ethernet  ok. 
b. The following screen will appear. Select yes to accept the communication interface 
34 of 68 
change 
c. At this point the “Connect Ethernet” icon will now have focus, select it by clicking on it
5. When the node selection window opens, highlight the node with IP address 192.168.1.21 and 
click the ‘Connect’ button to connect to the drive. 
a. If the IP Address of the drive is not in the window then select Add Node, type in the IP 
35 of 68 
address then click OK. 
b. Click Yes to the following message windows. 
6. Wait for the parameters to be read and populated.
7. Once the parameters are read and populated, by default Port 0 PowerFlex 753 240V 4.2 A 
should be highlighted, as shown in the following graphic. 
36 of 68 
Reset Drive to Defaults 
8. Navigate to Actions  Non Volatile Memory and click on Non Volatile Memory.
9. This will open a new window. Use the default selection of ‘Host and Ports to Defaults (Preferred) 
37 of 68 
and click on the button ‘Load Defaults’ 
10. Observe the prompted warning then click ‘Yes’ to the question “Do you wish to continue?” in the 
next window.
11. A pop window confirms that loading of parameter defaults was successful. Click ‘OK’. 
12. You will be returned to the Non-Volatile Memory window, Click ‘Close’ 
38 of 68
39 of 68 
Displaying The Status View 
13. If you have not already expanded the Drive Explorer application do so now by clicking on 
the lower right corner of the window and drag it so the entire Status View area can be 
seen (you can also maximize the window using the Maximize icon if desired) 
The Status View displays the drive’s User Text (“PowerFlex 753” in the image above) as 
well as important drive information, such as voltage and amp ratings, series, revision, 
and operational status. The Status View is automatically displayed the first time you 
connect to a drive. You can also display it at any time by clicking on the drive name in 
the device tree (PowerFlex 753 in the above image).
14. You can display the status view for any peripheral (e.g. the DeviceLogix adapter or other 
communication adapter) by selecting the peripheral in the device tree. 
15. Return to the drives status view; Click on the drive’s User Text (in the image, it is “PowerFlex 
753”) to edit it. Enter new text such as “PowerFlex Rocks!” and click Apply 
 
40 of 68 
16. The new User Text is now displayed.
17. Click on the Pencil icon for the middle display item. 
18. This is where you select, scale and assign text to Display Item 1. 
19. Change Process Display Item 1 to the following values and click Apply 
41 of 68
20. Close the Process Display Item 1 window. 
21. Note the change you made to Process Display Item 1. Adjust the 0-10V Input potentiometer on 
the drive demo to change the value on the screen. 
The PowerFlex 753 has six Process Display items displayed. Other products may have 
more or less and each will be display on theirs in the Status View. 
42 of 68
Displaying Parameters with the Linear List View 
22. Click on Parameter List in the device tree to display a linear list of the drive parameters. 
23. Scroll down to view Parameter 260 [Anlg In0 Value] and then double-click on this parameter to 
43 of 68 
view it. 
This is a read-only parameter that displays the value of Analog In0, which is connected to the 
potentiometer (0-10V INPUT) on the demo unit. Adjust the potentiometer to see the value 
change. Click Close.
24. Scroll down even further to Parameter 535 [Accel Time 1]. and then double-click on this 
44 of 68 
parameter to view and edit it 
This is a writeable parameter that determines the acceleration rate it takes to go from 0 Hz to 
P27[Motor NP Hertz] or P28[Motor NP RPM), according to the setting in P300[Speed Units]. To 
edit this parameter, a new value would be entered followed by clicking either ‘OK’ or ‘Apply’. 
Click ‘Cancel’. 
Displaying Parameters with the File / Group View 
25. In the device tree, click on the ‘Speed Control’ file and then the ‘Speed Ramp Rates’ group to 
display those parameters. 
See how getting to the same parameter as what was previously scrolled to using the Linear List 
function can be accessed by its grouping. If you do not know a parameter’s number, it maybe 
easier to find it with the File / Group view.
45 of 68 
Using the Startup Wizard 
The Startup Wizards eliminate the need to search for setup parameters because commonly used 
parameters are contained in a single wizard. Configuration becomes a guided, step-by-step process 
using graphics and parameter names (not numbers!), which simplifies drive setup. 
1. Click on the Wizard Browser icon to launch the Wizard Browser and display the available 
wizards. 
The PowerFlex 753 Startup Wizard is similar to performing the HIM Assisted Startup. 
Configuration parameters that are common to most applications are displayed in text / graphic 
forms and presented in a sequential step-by-step process. 
The DPI/DSI Tech Support Wizard is used to collect information for a remote support person to 
help troubleshoot a problem. Drive and peripheral information such as series and revision is 
collected along with changed parameters, fault & event queues, diagnostic items, etc. This 
information is saved to a text file which can be emailed to RA Tech Support, the OEM that 
supplied the machine, or the Corporate Engineer responsible for the remote plant, etc. 
Additional wizards will be available in the future and can be added to DriveExplorer v6.02 (and 
higher) at any time. New wizards will be posted on the AB Drives Web Updates page for free 
download: 
http://www.ab.com/support/abdrives/webupdate/index.html 
Note: The same wizards also work with DriveTools SP v6.02 and higher and 
RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater).
26. Select the PowerFlex 753 Startup Wizard and click ‘Select’. 
The wizard will first upload the parameters for each of the wizard pages. 
27. The first step in the wizard is the Welcome page. It explains the wizard and gives hints and tips 
46 of 68 
for using the wizard. Click ‘Next’.
28. The Reset Parameters step is next. It allows you to reset the drive’s parameters back to factory 
defaults. Verify ‘High Voltage’ and ‘Normal Duty’ is selected from the pull down menus. Then 
click ‘Reset Parameters’. 
47 of 68 
In the confirmation window, click ‘Yes’. 
Observe the on screen confirmation of the parameters being reset. 
Click Next> to continue; viewing the sequential process and continuing to click Next> until you 
reach the Motor Control Step of the Wizard
29. Perform the Motor Control Step of the PowerFlex 753 Startup Wizard. Make the selections 
48 of 68 
shown: 
Motor Control Mode = Select ‘Induction Flux Vector’ 
Primary Speed Feedback = Slot 0 (PowerFlex 753); Parameter 138 (Simulator Fdbk) 
Click Next> to the Motor Data Step of the Wizard.
30. The Motor Data is next. This step assists in entering the data from your motor’s nameplate into 
the drive. No selections need to be changed on this step, keep the default selections. 
Click Next> to the Stop Mode Step of the Wizard. 
49 of 68
31. The Stop Mode step is next. This step assists in selecting the drive’s stop mode and Dynamic 
Brake (DB) resistor type. No selections need to be changed on this step, keep the default 
selections. 
Click Next> to the Direction Test Step of the Wizard. 
50 of 68
32. The Direction Test step is next. It helps you determine if the motor is rotating in the proper 
direction for your application. No selections need to be changed on this screen. 
Direction Tests are not needed for this example; however they can be ran if you desire. If you do 
perform the autotune note the following: 
Click the button and hold it for a few seconds to run the drive. As long as you hold the jog 
button, the drive will run. Once you let go of the button, the drive will stop. After the motor stops, 
click the Yes radio button. Observe how clicking the Yes radio button updated the screen with a 
“Test Passed” status as well as adding ‘Change Direction’ option. 
Click Next> to the AutoTune Step of the Wizard. 
51 of 68
33. The AutoTune step is next. This step is where you can use automatic tuning algorithms 
(AutoTune). When running these algorithms the drive energizes the motor and makes 
measurements, which are used to make parameter settings. 
AutoTune tests are not needed for this example; however they can be ran if you desire. If you do 
perform the autotune note the test status: 
leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not 
leave AutoTune test page until test completes: 
Click Next> to the Inertia AutoTune Step of the Wizard. 
Note: Clicking <Back, Next>, or leaving step by any means will about the test. 
52 of 68
34. The Inertia AutoTune is next. This step is where you can use an automatic tuning algorithm to 
determine the load’s inertia. When running this algorithm the drive spins the motor and makes 
measurements, which are used to make parameter settings 
AutoTune tests are not needed for this example; however they can be ran if you desire. 
If you do perform the autotune note the test status: 
leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not 
leave AutoTune test page until test completes: 
Click Next> to the Ramp Rates / Speed Limits Step of the Wizard. 
Note: Clicking <Back, Next>, or leaving step by any means will about the test. 
53 of 68
24. Perform the Ramp Rates/Speed Limits Step of the PowerFlex 755 Startup Wizard. 
Enter: Max Forward / Reverse Speed 60 Hz 
Min Forward / Reverse Speed 0 Hz 
Enter a non-zero value for the S Curve to see what happens with the graphic. 
Then reset it back to 0. 
Click Next> to the Speed Reference Step of the Wizard. 
54 of 68
35. The Speed Reference step is next. It helps you select where the drive gets its speed reference. 
Observe the screen with the default value for speed reference selected to Port 0. 
Now select the reference to be from P260 [Anlg In0], observe how the wizard shows the pertinent 
parameters and for this analog input. 
Click Next> to continue; viewing the sequential process, continue to click Next> until you reach 
the Start / Stop step of the Wizard. 
55 of 68
36. Perform the Start / Stop step of the PowerFlex 753 Startup Wizard. Make the selections shown. 
DI Start = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 1) 
DI Stop = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 0) 
DI Forward / Reverse = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 2) 
Click Next> to the Other Digital Inputs Step of the Wizard. 
56 of 68
37. The Other Digital Inputs step is next. This step helps you configure the drive’s most commonly 
used digital inputs. No selections need to be changed on this step, keep the default selections 
Click Next> to the Digital Output Port 0 Step of the Wizard. 
There are other digital inputs available to user; however the Wizard shows 
the most commonly programmed inputs. All the available digital inputs can 
be accessed via the HIM or software tool (parameters 150 – 201). 
57 of 68
38. Perform the Digital Relay Out 0 step of the PowerFlex 753 Startup Wizard. This step helps you 
configure the drive’s digital outputs. Make the selections shown 
Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 16 (Running) 
Click Next> to the Digital Output Port 0 Step of the Wizard. 
There are no I/O options installed in this demo; however if there were an 
additional digital option card installed more Digital Output and Analog 
Output steps would become available to user and would be designated by 
their associated port. 
58 of 68
39. Perform the Digital Transistor Out 0 Step of the PowerFlex 753 Startup Wizard. This step helps 
you configure the drive’s digital outputs. Make the selections shown 
Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 7 (Faulted) 
Click Next> to the Analog Output Port 0 Step of the Wizard. 
59 of 68
40. The Analog Out 0 step is next. It helps you configure the drive’s analog outputs. No selections 
need to be changed on this step, keep the default selections. 
Click Next> to the Pending Changes Step of the Wizard. 
60 of 68
41. The Applied and Pending Changes page will appear. The purpose of this step is to verify all of 
the changes you made in the wizard, and then apply the changes to the drive. The below screen 
is for reference (your changes may differ from what is shown below). 
Click Finish >>. The wizard will write your changes to the drive. 
The Pending Changes step can be used as a reference tool. You can print 
the summary with the print button at the bottom of the window. You can 
refer to the printed summary when commissioning duplicate drives or 
replacing a faulted drive. 
61 of 68
62 of 68 
Using the Control Bar Tool 
42. Click on the button in the tool bar at the top of the window 
43. Read Caution advisory and click OK
44. Use the buttons on the left-hand side of the control bar to start, stop, jog and control the direction 
63 of 68 
of the drive 
The speed reference was selected to the Analog In0 in the previous step. To allow the control 
bar to have control of the speed reference; Parameter 545[Spd Ref A Sel] will need to be 
changed (while the drive is not running). Stop the drive and change Parameter 545 setting to 
Port ‘PowerFlex 753’, Parameter ‘876 - Port 6 Reference’. 
Start the Drive again and use the slider on the right-hand side to control the speed reference. 
45. Stop the Drive and turn off the control bar by clicking the button again. Observe the Caution 
pop up window and click Yes.
64 of 68 
Using Off-line Files 
This feature allows you to save your drive configuration to a computer. It is useful for several reasons: 
 You can use the configuration if you replace the drive or install an identical one. 
 You can use the configuration to troubleshoot the drive if it begins to malfunction because the 
settings have been changed. 
Uploading and Saving the Drive’s Configuration to a PC 
46. Select the drive in the device tree. 
47. From the Actions menu, select Upload/Download All. 
48. On the Upload/Download All window choose Upload.
49. By selecting the Upload/Download All you now are prompted to select with ports to upload. 
Deselect port 1 (20-HIM-x6) and Port 6 (20-COMM-E) and then click Upload. 
50. Each of the ports parameters will be uploaded. As indicated by the below screen, each port will 
be displayed as its parameters are uploaded. 
51. In the Save As window define the filename and location of the file. Take note of the name and 
remember where you save this file, it will be needed later. 
52. After choosing the name and location to save file the Uploading… screen will regain focus; click 
65 of 68 
Close.
53. Again the Upload/Download All window will appear, click Close. 
This section had described how to upload all the ports in the drive into one file. Also 
available on the Actions menu is the option to select Upload and Save. Doing this will 
upload and save the parameters for the selected port in the device tree. 
Downloading Configuration to Drive from a PC 
54. Change the value of a parameter that you can easily verify (e.g. P535 [Accel Time 1]). 
55. From the Actions menu, select Upload/Download All. 
56. On the Upload/Download All window choose Download. 
57. Select Yes. To the resulting dialog window. 
58. Select the same file you created in the section above and click the Open button. 
66 of 68
59. Notice on the Select Sets To Download window that only the chosen option ports that were 
selected to upload in the previous steps are available. Click Download. 
60. The saved parameter file values will be downloaded. Close the Download Complete! 
67 of 68 
Acknowledgement. 
61. Again the Upload/Download All window will appear, click Close. 
62. Verify that the value of the parameter you changed a few steps back has returned to its original 
value.
68 of 68 
Notes:

More Related Content

What's hot

03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.pptHaTa33
 
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAI
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAIABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAI
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAIDEEPAK GORAI
 
Fieldbus Tutorial Part 9 - Fieldbus Diagnostics
Fieldbus Tutorial Part 9 - Fieldbus DiagnosticsFieldbus Tutorial Part 9 - Fieldbus Diagnostics
Fieldbus Tutorial Part 9 - Fieldbus DiagnosticsEmerson Exchange
 
Honeywell Building Solutions
Honeywell Building SolutionsHoneywell Building Solutions
Honeywell Building Solutionsguest9b6532e
 
PLC ARCHITECTURE AND HARDWARE COMPONENTS
PLC ARCHITECTURE AND HARDWARE COMPONENTSPLC ARCHITECTURE AND HARDWARE COMPONENTS
PLC ARCHITECTURE AND HARDWARE COMPONENTSAkshay Dhole
 
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...Emerson Exchange
 
12cR2 Single-Tenant: Multitenant Features for All Editions
12cR2 Single-Tenant: Multitenant Features for All Editions12cR2 Single-Tenant: Multitenant Features for All Editions
12cR2 Single-Tenant: Multitenant Features for All EditionsFranck Pachot
 
Fieldbus Tutorial Part 2 - Justifying Fieldbus
Fieldbus Tutorial Part 2 - Justifying FieldbusFieldbus Tutorial Part 2 - Justifying Fieldbus
Fieldbus Tutorial Part 2 - Justifying FieldbusEmerson Exchange
 
DeltaV Safety Instrumented System Overview
DeltaV Safety Instrumented System OverviewDeltaV Safety Instrumented System Overview
DeltaV Safety Instrumented System OverviewSumeet Goel
 
TIA Portal STEP 7 Basic
TIA Portal STEP 7 BasicTIA Portal STEP 7 Basic
TIA Portal STEP 7 BasicBinh Vo
 
2006 Toyota Hiace OEm Electrical Wiring Diagrams
2006 Toyota Hiace OEm Electrical Wiring Diagrams2006 Toyota Hiace OEm Electrical Wiring Diagrams
2006 Toyota Hiace OEm Electrical Wiring DiagramsDardoorASM
 
Gaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementGaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementUpsite Technologies
 
Philippine Economic Zone Authority (PEZA) Expat Handbook
Philippine Economic Zone Authority (PEZA)  Expat HandbookPhilippine Economic Zone Authority (PEZA)  Expat Handbook
Philippine Economic Zone Authority (PEZA) Expat HandbookKirk Go
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_enDeepak kumar
 

What's hot (20)

03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt03_20R300_1_C300 Controller Architecture.ppt
03_20R300_1_C300 Controller Architecture.ppt
 
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAI
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAIABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAI
ABB ACS 800 SERIES VFD TRAINNING GUIDE BY DEEPAK GORAI
 
Fieldbus Tutorial Part 9 - Fieldbus Diagnostics
Fieldbus Tutorial Part 9 - Fieldbus DiagnosticsFieldbus Tutorial Part 9 - Fieldbus Diagnostics
Fieldbus Tutorial Part 9 - Fieldbus Diagnostics
 
Honeywell Building Solutions
Honeywell Building SolutionsHoneywell Building Solutions
Honeywell Building Solutions
 
PLC ARCHITECTURE AND HARDWARE COMPONENTS
PLC ARCHITECTURE AND HARDWARE COMPONENTSPLC ARCHITECTURE AND HARDWARE COMPONENTS
PLC ARCHITECTURE AND HARDWARE COMPONENTS
 
Allen bradley
Allen bradleyAllen bradley
Allen bradley
 
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...
New DeltaV Module Templates to Easily Configure, View, and Trend Advanced Pre...
 
SIEMENS S7-300c.ppt
SIEMENS S7-300c.pptSIEMENS S7-300c.ppt
SIEMENS S7-300c.ppt
 
12cR2 Single-Tenant: Multitenant Features for All Editions
12cR2 Single-Tenant: Multitenant Features for All Editions12cR2 Single-Tenant: Multitenant Features for All Editions
12cR2 Single-Tenant: Multitenant Features for All Editions
 
Fieldbus Tutorial Part 2 - Justifying Fieldbus
Fieldbus Tutorial Part 2 - Justifying FieldbusFieldbus Tutorial Part 2 - Justifying Fieldbus
Fieldbus Tutorial Part 2 - Justifying Fieldbus
 
DeltaV Safety Instrumented System Overview
DeltaV Safety Instrumented System OverviewDeltaV Safety Instrumented System Overview
DeltaV Safety Instrumented System Overview
 
TIA Portal STEP 7 Basic
TIA Portal STEP 7 BasicTIA Portal STEP 7 Basic
TIA Portal STEP 7 Basic
 
NFS2-640
NFS2-640NFS2-640
NFS2-640
 
2006 Toyota Hiace OEm Electrical Wiring Diagrams
2006 Toyota Hiace OEm Electrical Wiring Diagrams2006 Toyota Hiace OEm Electrical Wiring Diagrams
2006 Toyota Hiace OEm Electrical Wiring Diagrams
 
Gaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow ManagementGaining Data Center Cooling Efficiency Through Airflow Management
Gaining Data Center Cooling Efficiency Through Airflow Management
 
Data Centre Design Guideline and Standards
Data Centre Design Guideline and StandardsData Centre Design Guideline and Standards
Data Centre Design Guideline and Standards
 
2017 07-04 ms300 cmm-eip01
2017 07-04 ms300 cmm-eip012017 07-04 ms300 cmm-eip01
2017 07-04 ms300 cmm-eip01
 
Private foundations
Private foundationsPrivate foundations
Private foundations
 
Philippine Economic Zone Authority (PEZA) Expat Handbook
Philippine Economic Zone Authority (PEZA)  Expat HandbookPhilippine Economic Zone Authority (PEZA)  Expat Handbook
Philippine Economic Zone Authority (PEZA) Expat Handbook
 
Technical slides tia_portal_v15_en
Technical slides tia_portal_v15_enTechnical slides tia_portal_v15_en
Technical slides tia_portal_v15_en
 

Viewers also liked

Laboratorio programacao pf 755 com ihm
Laboratorio programacao pf 755 com ihmLaboratorio programacao pf 755 com ihm
Laboratorio programacao pf 755 com ihmconfidencial
 
1.2 power flex update
1.2 power flex update1.2 power flex update
1.2 power flex updateconfidencial
 
1.2a power flex750 r2
1.2a power flex750 r21.2a power flex750 r2
1.2a power flex750 r2confidencial
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeconfidencial
 
Drv13 power flex 755 programming with devicelogix
Drv13   power flex 755 programming with devicelogixDrv13   power flex 755 programming with devicelogix
Drv13 power flex 755 programming with devicelogixconfidencial
 
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlex
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlexBiến tần Rockwell - tài liệu tổng quan biến tần PowerFlex
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlexLong Trump
 
Power flex series 750 installation instruction
Power flex series 750 installation instructionPower flex series 750 installation instruction
Power flex series 750 installation instructionKhoi Nguyen
 
1.8 recursos de aplicação
1.8 recursos de aplicação1.8 recursos de aplicação
1.8 recursos de aplicaçãoconfidencial
 
Ladder logic tutorial
Ladder logic tutorialLadder logic tutorial
Ladder logic tutorialdas1964
 
Hype vs. Reality: The AI Explainer
Hype vs. Reality: The AI ExplainerHype vs. Reality: The AI Explainer
Hype vs. Reality: The AI ExplainerLuminary Labs
 

Viewers also liked (11)

Laboratorio programacao pf 755 com ihm
Laboratorio programacao pf 755 com ihmLaboratorio programacao pf 755 com ihm
Laboratorio programacao pf 755 com ihm
 
Power flex400
Power flex400Power flex400
Power flex400
 
1.2 power flex update
1.2 power flex update1.2 power flex update
1.2 power flex update
 
1.2a power flex750 r2
1.2a power flex750 r21.2a power flex750 r2
1.2a power flex750 r2
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verde
 
Drv13 power flex 755 programming with devicelogix
Drv13   power flex 755 programming with devicelogixDrv13   power flex 755 programming with devicelogix
Drv13 power flex 755 programming with devicelogix
 
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlex
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlexBiến tần Rockwell - tài liệu tổng quan biến tần PowerFlex
Biến tần Rockwell - tài liệu tổng quan biến tần PowerFlex
 
Power flex series 750 installation instruction
Power flex series 750 installation instructionPower flex series 750 installation instruction
Power flex series 750 installation instruction
 
1.8 recursos de aplicação
1.8 recursos de aplicação1.8 recursos de aplicação
1.8 recursos de aplicação
 
Ladder logic tutorial
Ladder logic tutorialLadder logic tutorial
Ladder logic tutorial
 
Hype vs. Reality: The AI Explainer
Hype vs. Reality: The AI ExplainerHype vs. Reality: The AI Explainer
Hype vs. Reality: The AI Explainer
 

Similar to Basic drive programing pf753

Drv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamDrv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamconfidencial
 
Dhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bDhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bconfidencial
 
Pf400 process pid_for_fans_lab
Pf400 process pid_for_fans_labPf400 process pid_for_fans_lab
Pf400 process pid_for_fans_labconfidencial
 
Micro c lab2(led patterns)
Micro c lab2(led patterns)Micro c lab2(led patterns)
Micro c lab2(led patterns)Mashood
 
Digital Watchdog DW-VF960H161T User Manual
Digital Watchdog DW-VF960H161T User ManualDigital Watchdog DW-VF960H161T User Manual
Digital Watchdog DW-VF960H161T User ManualJMAC Supply
 
AutoCount Accounting User Manual
AutoCount Accounting User ManualAutoCount Accounting User Manual
AutoCount Accounting User ManualAngela Shin
 
Pf700 energy savings_lab
Pf700 energy savings_labPf700 energy savings_lab
Pf700 energy savings_labconfidencial
 
FlashPAK-III_Operator_Guide
FlashPAK-III_Operator_GuideFlashPAK-III_Operator_Guide
FlashPAK-III_Operator_GuideRoger A Sharp
 
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...Ted Jurca
 
Mvi56 e mcmr quickstart
Mvi56 e mcmr quickstartMvi56 e mcmr quickstart
Mvi56 e mcmr quickstartSEICO
 
Dell Inspiron 15 3000 - Laptops Trần Phát
Dell Inspiron 15 3000 - Laptops Trần PhátDell Inspiron 15 3000 - Laptops Trần Phát
Dell Inspiron 15 3000 - Laptops Trần PhátLAPTOP TRẦN PHÁT
 
Security commans User's guide.pdf
Security commans User's guide.pdfSecurity commans User's guide.pdf
Security commans User's guide.pdfFarahHaseenah1
 
Pcu230 pi pump_controlwithpf400drives_rev_a
Pcu230 pi pump_controlwithpf400drives_rev_aPcu230 pi pump_controlwithpf400drives_rev_a
Pcu230 pi pump_controlwithpf400drives_rev_aconfidencial
 
Fanuc educational cell manual
Fanuc educational cell manualFanuc educational cell manual
Fanuc educational cell manualCalin Neamtu
 
Dell Inspiron 15 7000 - Laptops Trần Phát
Dell Inspiron 15 7000 - Laptops Trần PhátDell Inspiron 15 7000 - Laptops Trần Phát
Dell Inspiron 15 7000 - Laptops Trần PhátLAPTOP TRẦN PHÁT
 
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter board
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter boardLab: Installation of Xilkernel on Xilinx Spartan 3E Starter board
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter boardVincent Claes
 
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...Ted Jurca
 
SATYAM_VERMA_PLC_REPORT.docx.pptx
SATYAM_VERMA_PLC_REPORT.docx.pptxSATYAM_VERMA_PLC_REPORT.docx.pptx
SATYAM_VERMA_PLC_REPORT.docx.pptxsatyamVerma186725
 

Similar to Basic drive programing pf753 (20)

Cpcu08 drv14
Cpcu08 drv14Cpcu08 drv14
Cpcu08 drv14
 
Drv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamDrv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcam
 
Dhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bDhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_b
 
Pf400 process pid_for_fans_lab
Pf400 process pid_for_fans_labPf400 process pid_for_fans_lab
Pf400 process pid_for_fans_lab
 
Micro c lab2(led patterns)
Micro c lab2(led patterns)Micro c lab2(led patterns)
Micro c lab2(led patterns)
 
Digital Watchdog DW-VF960H161T User Manual
Digital Watchdog DW-VF960H161T User ManualDigital Watchdog DW-VF960H161T User Manual
Digital Watchdog DW-VF960H161T User Manual
 
AutoCount Accounting User Manual
AutoCount Accounting User ManualAutoCount Accounting User Manual
AutoCount Accounting User Manual
 
Pf700 energy savings_lab
Pf700 energy savings_labPf700 energy savings_lab
Pf700 energy savings_lab
 
FlashPAK-III_Operator_Guide
FlashPAK-III_Operator_GuideFlashPAK-III_Operator_Guide
FlashPAK-III_Operator_Guide
 
Hm 5750 manual-0817
Hm 5750 manual-0817Hm 5750 manual-0817
Hm 5750 manual-0817
 
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc4 ltm Automatic lift truck onboard OSHA compliances recorders with impact ...
 
Mvi56 e mcmr quickstart
Mvi56 e mcmr quickstartMvi56 e mcmr quickstart
Mvi56 e mcmr quickstart
 
Dell Inspiron 15 3000 - Laptops Trần Phát
Dell Inspiron 15 3000 - Laptops Trần PhátDell Inspiron 15 3000 - Laptops Trần Phát
Dell Inspiron 15 3000 - Laptops Trần Phát
 
Security commans User's guide.pdf
Security commans User's guide.pdfSecurity commans User's guide.pdf
Security commans User's guide.pdf
 
Pcu230 pi pump_controlwithpf400drives_rev_a
Pcu230 pi pump_controlwithpf400drives_rev_aPcu230 pi pump_controlwithpf400drives_rev_a
Pcu230 pi pump_controlwithpf400drives_rev_a
 
Fanuc educational cell manual
Fanuc educational cell manualFanuc educational cell manual
Fanuc educational cell manual
 
Dell Inspiron 15 7000 - Laptops Trần Phát
Dell Inspiron 15 7000 - Laptops Trần PhátDell Inspiron 15 7000 - Laptops Trần Phát
Dell Inspiron 15 7000 - Laptops Trần Phát
 
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter board
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter boardLab: Installation of Xilkernel on Xilinx Spartan 3E Starter board
Lab: Installation of Xilkernel on Xilinx Spartan 3E Starter board
 
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...
Osc1 epm Automatic lift truck onboard OSHA compliances recorders with impact ...
 
SATYAM_VERMA_PLC_REPORT.docx.pptx
SATYAM_VERMA_PLC_REPORT.docx.pptxSATYAM_VERMA_PLC_REPORT.docx.pptx
SATYAM_VERMA_PLC_REPORT.docx.pptx
 

More from confidencial

19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_enconfidencial
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0confidencial
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_enconfidencial
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_enconfidencial
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_enconfidencial
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_enconfidencial
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_enconfidencial
 
11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_enconfidencial
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_enconfidencial
 
09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_enconfidencial
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_enconfidencial
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_enconfidencial
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_enconfidencial
 
05 project setup v1.00_en
05 project setup v1.00_en05 project setup v1.00_en
05 project setup v1.00_enconfidencial
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_enconfidencial
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 enconfidencial
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_enconfidencial
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 enconfidencial
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01confidencial
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01confidencial
 

More from confidencial (20)

19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_en
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_en
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_en
 
11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_en
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en
 
09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_en
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_en
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_en
 
05 project setup v1.00_en
05 project setup v1.00_en05 project setup v1.00_en
05 project setup v1.00_en
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_en
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01
 

Recently uploaded

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 

Recently uploaded (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 

Basic drive programing pf753

  • 1. N999 – Basic Drive Programming PowerFlex N999 – 753 Your lab title goes here Presenter: <<Your name>> <<Your business group>> Presenter: <<Your name>> Rockwell Automation Drives Business For Classroom Use Only! Publication Number -- Date Copyright © 2009 Rockw ell Automation, Inc.
  • 2.
  • 3. PowerFlex 753 Basic Start Up for Speed Controlled 3 of 68 Applications Contents Before you begin .............................................................................................................................. 5 Tools ................................................................................................................................................. 5 About this lab ..................................................................................................................................... 5 About the Demo ................................................................................................................................ 6 Lab Setup.......................................................................................................................................... 7 Lab Objective .................................................................................................................................... 8 Using the Human Interface Module (H.I.M)........................................................................................ 9 Disabling DeviceLogix Program – IF LOADED & RUNNING ............................................................ 10 Preparing the PowerFlex 753 Demo To Run In Simulation Mode .................................................... 14 Assisted Startup using the Human Interface Module (H.I.M)........................................................... 16 Resetting factory defaults .................................................................................................................. 17 Setting the Motor Control Mode ......................................................................................................... 20 Entering Motor Nameplate Data......................................................................................................... 21 Setting the Speed Feedback Device .................................................................................................. 24 Setting the Speed Limits ................................................................................................................... 24 Direction Auto Tune and Inertia Tests ................................................................................................ 25 Configuring the Speed Reference and Ramp rates ............................................................................. 28 Configuring the Inputs and Outputs .................................................................................................... 30
  • 4. Drive Programming via Software Tool (Optional) ........................................................................... 32 About This Section............................................................................................................................ 32 Using Drive Explorer with PF753 ....................................................................................................... 32 Starting Drive Explore and Connect To Drive ...................................................................................... 33 Reset Drive to Defaults ..................................................................................................................... 36 Displaying The Status View ............................................................................................................... 39 Displaying Parameters with the Linear List View ................................................................................. 43 Displaying Parameters with the File / Group View ............................................................................... 44 Using the Startup Wizard................................................................................................................... 45 Using the Control Bar Tool ................................................................................................................ 62 Using Off-line Files ........................................................................................................................... 64 4 of 68
  • 5. 5 of 68 Before you begin Tools  PowerFlex 753 Training Demo  Windows XP PC with DriveExplorer (full version 6.02 or greater); for optional section About this lab This session provides you with an opportunity to explore the PowerFlex 753 AC drive. In this session you will learn to:  Use the Assisted Startup for simple Speed Controlled Applications  Control the Drive and simulate spinning a motor This lab takes approximately 45 minutes to complete.
  • 6. 6 of 68 About the Demo The DHQ packaged PowerFlex 753 Demo is a reduced size, packaged demo kit for demonstrating programming of PowerFlex 753, as well as Premier Integration, and DeviceLogix. On board I/O facilitates user input as well as feedback. This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production drive the demo itself was not designed to run an actual motor. There are no user connections to apply an external motor nor was the internal step up transformer or fusing sized to run anything greater then the drive rated current w/o any loading. The image below labels the switches, push buttons and the potentiometer required in this lab session. Di 0 – Normally Open Pushbutton Di 1 – Normally Closed Pushbutton Di 2 – Selector Switch 0- 10 V Analog Input DRIVE POWER Circuit Breaker
  • 7. 7 of 68 Lab Setup 1. On the PowerFlex 753 demo case, verify position switch Di 2 is selected to the left (OFF) 2. Energize the drive demo; switch the single-pole breaker labeled ‘POWER’, located on the front of the demo, to the on position.
  • 8. 8 of 68 Lab Objective At the end of this lab, you should have successfully completed the Assisted Startup routine of the PF753 drive and 1. Programmed the Drive to start the drive/motor using the green pushbutton labeled ‘Di 1’. 2. Programmed the Drive to stop the drive/motor using the red pushbutton labeled ‘Di 0’. 3. Programmed the Drive to forward or reverse the drive/motor using t he selector switch labeled ‘Di 2’. 4. Programmed the Drive to get Speed Reference from an Analog Source, the potentiometer labeled ‘0-10 INPUT’.
  • 9. Using the Human Interface Module (H.I.M) The image below shows some of the essential keys which you will be using in this session. Please familiarize yourself with these keys (buttons) 9 of 68 PowerFlex 753 240V 4.2A 20F . . . B4P2 00 Soft Keys Navigation Keys Enter Key Stop Key Start Key Folders Key
  • 10. Disabling DeviceLogix Program – IF LOADED & RUNNING If a DeviceLogix Program is loaded and running in the PowerFlex 753 demo, the logic needs to be disabled and the drive reset prior to conducting the lab. If the DeviceLogix program has not been properly disabled, the drive will not operate according to the lab procedure. Consult with your instructor before performing the following procedure: 1. From the Status screen which is displayed on HIM PowerUp. Use the left or right arrow keys to navigate to the DeviceLogix option. 10 of 68 PowerFlex 753 240V 4.2A 20F . . . B4P2  DeviceLogix Embedded LogicEnabled 14 2. The HIM screenshot above shows the display if the DeviceLogix is enabled ‘LogicEnabled’. If the logic is disabled ‘LogicDisabld’ then disabling of the DeviceLogix is not required, skip to the next section. 3. Press the ‘PAR#’ soft key and enter the number 53 followed by the ‘ENTER’ soft key to goto parameter 53 Devi ceLogi x Jump t o Par am # 53 14  Por t 14 Host Par am 53 DLX Operation LogicEnabled 6
  • 11. 4. Use the ‘EDIT’ soft key followed by the scroll down or scroll up arrow soft keys to change parameter #53 to DisableLogic then the ‘ENTER’ soft key to confirm. 11 of 68 Edi t DLX Oper at i on DisableLogic 1 0 << 6  Por t 14 Host Par am 53 DLX Operation LogicDisabld 5 Parameter 53 [DLX Operation] is of the parameter type that contains both operation commands as well as status information. Setting it to disable logic is option 1, however once the ‘ENTER’ key is pressed to confirm the display is option 5 “LogicDisabled”. 5. Press the ‘ESC’ soft key to return the display to the top level DeviceLogix screen DeviceLogix Embedded LogicDisabld 14 6. Use the left or right arrow keys to navigate to the drives initial screen (Main Control Board Slot 0) PowerFlex 753 240V 4.2A 20F . . . B4P2
  • 12. 7. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the HIM screen display to the Folders screen ( see right image below) 12 of 68 PowerFlex 753 240V 4.2A 20F . . . B4P2 00 PORTS 00 Power Fl ex 753 01 20- HI M- x6 06 20- COMM- E 14 Devi ceLogi x 8. Use the left or right arrow keys to scroll through the different folders, to locate the folder called ‘DIAGNOSTIC’. DI AGNOSTI C Faul t s Al ar ms Di agnost i c I t ems Reset Devi ce
  • 13. 9. Use the down arrow key to highlight ‘ Reset Device’ then press the Enter key located in the center of the HIM keypad to make this your selection. 13 of 68 DI AGNOSTI C Faul t s Al ar ms Di agnost i c I t ems Reset Devi ce 10. A confirmation screen follows press the ‘ENTER’ soft key to confirm your selection. C O N F I R M Ar e you sur e you want t o r eset t he devi ce 11. The drive will then reset, upon completion the drive maybe faulted; press the ‘CLR’ soft key to clear acknowledge and clear fault.
  • 14. Preparing the PowerFlex 753 Demo To Run In Simulation Mode This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production drive the demo itself was NOT designed to run an actual motor. In order to complete the lab the feedback mode needs to changed to simulate. 1. From the Status screen which is displayed on HIM PowerUp. Press the ‘PAR#’ soft key and enter the number 301 using the numeric keypad followed by the ‘ENTER’ soft key to goto parameter 301 [Access Level] 14 of 68 PowerFlex 753 240V 4.2A 20F . . . B4P2  Por t 00 Dev Par am 301 Expert 2 Access Level 2. Verify that P301 [Access Level] is set to ‘Expert’ if not press the ‘EDIT’ soft key followed by the scroll down or scroll up arrow soft keys to change the parameter to Expert then the ‘ENTER’ soft key to confirm. Edi t Access Level 0 << 2 Basic 0  Por t 00 Dev Par am 301 Expert 2 Access Level
  • 15. 3. Press the ‘PAR#’ soft key and enter the number 125 followed by the ‘ENTER’ soft key to goto 15 of 68 parameter 125 [Pri Vel Fdbk Sel] Power Fl ex 753 Jump t o Par am # 125 00  Por t 00 Dev Par am 125 Pri Vel Fdbk Sel P00 P0137 Por t Power Fl ex 753 EDI T 4. Press the ‘EDIT’ soft key, the default (and only choice) for ‘Edit Spd Ref A Sel’ is PowerFlex 753. Make this selection using the ‘Enter’ soft key Edi t Spd Ref A Sel Sel ect Par m To Use Port 00 Power Fl ex 753 5. For ‘Pri Vel Fdbk Sel’ selection use the down arrow key to select ‘Simulator Fdbk’. Then make this selection using the ‘Enter’ soft key. Edi t Pr i Vel Fdbk Sel Sel ect Par m To Use Si mul at or Fdbk Par 0137 Par 0138 Open Loop Fdbk 6. Press the ‘ESC’ soft key to return the display to the top level Status Screen.
  • 16. Assisted Startup using the Human Interface Module (H.I.M) One of the ways to perform an Assisted Startup on the PowerFlex 753 is using the Startup routine in the H.I.M. The following steps will lead you through that: 1. Access the Status screen which is displayed on HIM PowerUp. 16 of 68 PowerFlex 753 240V 4.2A 20F . . . B4P2 2. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the HIM screen display to the Folders screen ( see right image below) PowerFlex 753 240V 4.2A 20F . . . B4P2 00 PORTS 00 Power Fl ex 753 01 20- HI M- x6 06 20- COMM- E 14 Devi ceLogi x
  • 17. 17 of 68 Resetting factory defaults 3. Use the left or right arrow keys to scroll through the different folders, to locate the folder called ‘MEMORY’. MEMORY HI M CopyCat Set Def aul t s 4. Use the down arrow key to highlight ‘ Set Defaults’ if necessary and press the Enter key located in the center of the HIM keypad to make this your selection. 5. The screen which follows after completion of the previous step is shown. Use the down arrow key to highlight ‘This Port only’. Press the Enter key located in the center of the HIM keypad to make this your selection. Por t 00 Set Def aul t s Host and Por t s ( Pr ef er r ed) Thi s Por t Onl y ESC INFO
  • 18. 6. Use the soft key labeled ‘ALL’ to reset default all parameter settings in the Drive. 18 of 68 W A R N I N G Use MOST t o r eset t ypi cal set t i ngs on t hi s por t ( pr ef er r ed) . Use ALL t o r eset al l set t i ngs ALL MOST 7. Use the ‘CLR’ soft key to acknowledge and clear the ‘Module Defaulted’ fault. 8. If you receive a screen that confirms that setting factor defaults is complete press the ‘ENTER’ soft key to confirm. 9. Press the ‘Folders’ button on the HIM keypad again to access the Folders Menu. 10. Now use the left or right arrow keys to scroll through the different folders, to locate the folder called ‘START UP’. START UP Begi n St ar t Up 11. The first item listed in the ‘START UP’ folder is ‘Begin Start Up’ and this is highlighted by default. Press the Enter key located in the center of the HIM keypad to make this your selection.
  • 19. 12. The startup routine starts with an Introduction screen. Press the ‘ENTER’ soft key to continue. The ‘ENTER’ soft key is located on the top row of the HIM keypad. 19 of 68 Power Fl ex 753 St ar t up St ar t - Up consi st s of sever al st eps t o conf i gur e t he dr i ve. Pr ess ENTER ABORT ENTER Note: You can always use the ESC soft key to return to a previous step. 13. Pressing the ‘ENTER’ soft key in the previous step has led you to a new screen, which allows you to select the type of startup you wish to perform. For this lab session, we will choose ‘General Startup’. This is highlighted by default. Press the ‘ENTER’ soft key located on the top row of the HIM keypad to make this your selection. Power Fl ex 753 St ar t up Gener al St ar t up Appl Speci f i c Exi t St ar t up ABORT ENTER
  • 20. Compl et e t hese st eps i n or der : 20 of 68 Setting the Motor Control Mode 14. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘General Startup Main Menu’. You will go through steps listed in this menu to configure your drive. Press ‘ENTER’ soft key to enter the first section ‘Motor Control’. Gener al St ar t up Mai n Menu Mot or Cont r ol Mot or Dat a Feedback ABORT ENTER Li mi t s 15. The introduction screen provides information about the ‘Motor Control section. Press the ‘ENTER’ soft key to continue. St ar t up Mot or Cont r ol Thi s sect i on sel ect s t he t ype of Mot or Cont r ol t he dr i ve wi l l use. Pr ess ENTER ABORT ENTER
  • 21. 16. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available motor control modes in the PowerFlex 753. For this lab session, we will choose the Flux Vector mode. Use the down arrow key to navigate and select ‘Flux Vector’. Press the ‘ENTER’ soft key to make this your selection. St ar t up Mot or Cont r ol Pl ease Sel ect : ABORT ENTER Compl et e t hese st eps i n or der : 21 of 68 Sensor l ess Vect V/ Hz Fl ux Vect or 17. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available Control Modes in the PowerFlex 753. For this lab session, we will choose the default selection of ‘Speed’. Press the ‘ENTER’ soft key to make this your selection Entering Motor Nameplate Data 18. After selecting the motor control mode in the previous step, you are directed back to the General Startup Main Menu. ‘Motor Data’ should be highlighted now. Press the ‘ENTER’ soft key to make this your selection. The next few steps will require you to input the nameplate information of the motor you are doing a Startup on. Gener al St ar t up Mai n Menu Mot or Cont r ol Mot or Dat a Feedback ABORT ENTER Li mi t s
  • 22. 19. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘Startup Motor Data Entry’ screen. The first information you will provide is the Motor Nameplate (NP) Volts. The Motor in the demo is rated for 230 V. This should be the default value for this parameter. Press the ‘ENTER’ soft key to confirm your input and move to the next screen. 230.00 VAC 22 of 68 St ar t up Mot or Dat a Ent r y Edi t Mot or NP Vol t s 0.10 << 264.50 20. The next information you need to provide is the Power Units. By default the value of the parameter should be set to ‘HP’. Press the ‘ENTER’ soft key to confirm your selection and move to the next screen. Mot or Dat a Ent r y Sel ect t ype of power uni t s Shown on mot or namepl at e: ABORT ENTER St ar t up HP kW
  • 23. 21. You will now be required to input the Motor Nameplate (NP) Power. Since there actually is no motor connected use the default of 1.00 HP Press the ‘ENTER’ soft key to confirm your input and move to the next screen. 23 of 68 Edi t Mot or NP Power 0.01 << 2000.00 1.00 HP St ar t up Mot or Dat a Ent r y 22. You will now be required to input the Motor Nameplate (NP) Amperes. Again accept the default value here. Press the ‘ENTER’ soft key to confirm your input and move to the next screen. St ar t up Mot or Dat a Ent r y Edi t Mot or NP Amps 2.90 Amps 0.01 << 42.00 23. Continue through the Startup / Motor Data Entry section choosing the default values. Once all the Motor Data Entry steps are complete you will be brought back to the General Startup Main Menu with “Feedback” being highlighted.
  • 24. Setting the Speed Feedback Device 24. Setting the Speed Feedback Device will be skipped in this lab – going back to “About The Demo” section there is physically no actually motor and the demo unit was selected to a simulated feedback. Selecting this option now would force a feedback selection that is NOT valid for simulation mode. Compl et e t hese st eps i n or der : 24 of 68 Setting the Speed Limits 25. In the previous step configuring your feedback device was skipped; configuring the limits is the next step in the Startup routine. Use the down arrow key to navigate to the ‘Limits’ step. . Press the ‘ENTER’ soft key to access ‘Limits’ section. Gener al St ar t up Mai n Menu Mot or Cont r ol Mot or Dat a Feedback ABORT ENTER Li mi t s 26. For this lab session, we will not be changing the limits but verify the following selections in the ‘Limits’ section. Use the number keys to input the values listed for each item and press the ‘ENTER’ soft key to move forward to the next screen. After the four values have been entered, you will be exited out of this section. Max Fwd Speed = 60 Hz Max Rev Speed = -60 Hz (you can directly enter a value of ‘60’; the negative s ign is defaulted) Min Fwd Speed = 0.00 Hz Min Rev Speed = 0.00 Hz
  • 25. Direction Auto Tune and Inertia Tests 27. You should now have been directed back to the General Startup Main Menu. The ’Tests’ section is next and should be highlighted by default at this stage. Press the ‘ENTER’ soft key to access ‘Tests’ section. Mai n Menu Compl et e t hese st eps i n or der : Mot or Dat a Feedback ABORT ENTER 25 of 68 Gener al St ar t up Li mi t s Test s 28. There are two tests which are part of the Startup Routine. You will perform these tests in the next few steps. You will run the Direction test first. The ‘Direction Test’ list item should be highlighted by default. Press the ‘ENTER’ soft key to make this your selection. Press the Start key to start the motor. 29. The next screen asks the question ‘Is the direction of rotation forward?’ To demonstrate the ability of the PowerFlex 753 to electronically swap motor leads to change motor direction, let us choose ‘No’ as the answer to this question. Use the down arrow key to select and highlight ‘No’ and press the Press the ‘ENTER’ soft key. St ar t up Di r ect i on Test I s t he di r ect i on of r ot at i on f or war d? Yes No
  • 26. 30. The next screen asks the question ‘How would you like to fix motor polarity? ’. Select the default highlighted option ‘Automatic change’ by using the ‘ENTER’ soft key. How woul d you l i ke t o f i x t he mot or pol ar i t y? Aut omat i c Change 26 of 68 St ar t up Di r ect i on Test Change mt r wi r es 31. The screen that follows asks you to stop the drive so this change in direction, initiated in the previous step, can take place. Press the ‘STOP’ key to stop the drive. St ar t up Di r ect i on Test Pr ess STOP St ar t up wi l l t hen aut omat i cal l y change r ot at i on as i f mot or l eads wer e r ever sed 32. Follow the direction on the next screen which asks you t o ‘START’ the drive. You can start the drive and by using the START key. 33. The next screen asks the question ‘Is the direction of rotation forward?’ and requires confirmation that the changes to direction are acceptable. Select ‘Yes’ by pressing the ‘ENTER’ soft key. 34. Press the Stop key .This should successfully complete the Direction test. 35. You should now be back in the ‘Motor Test Menu’ screen. Now use the ‘ENTER’ soft key to select the ‘Auto tune’ Test. Read the important information on the screen and press the ‘ENTER’ soft key.
  • 27. 36. Pressing the ‘ENTER’ soft key in the previous step has directed you to the ‘Select the tuning mode’ screen. For this lab session, we will perform a rotate tune on the demo motor. Select the default highlighted option ‘Rotate Tune’ by pressing the ‘ENTER’ soft key. 37. As directed by the HIM screen information, press the START key to start the ‘Auto tune’ Test. Notice the changing information on the HIM (as the different parts of the Auto tune tests are completed).Wait till the test is completed. 27 of 68 St ar t up Aut o Tune Test i n pr ogr ess: St at or Resi st ance Pl ease Wai t Pr ess STOP t o abor t t est St ar t up Aut o Tune Test i n pr ogr ess: Fl ux Cur r ent Pl ease Wai t Pr ess STOP t o abor t t est 38. The completion of the test is indicated by the ‘Test Completed Successfully’ screen. Press the ‘ENTER’ soft key. 39. Select the ‘Inertia Test’ using the ‘ENTER’ soft key and use the ‘ENTER’ soft key again to confirm that the load is connected to the motor. 40. As directed by the HIM screen information, press the START key to start the ‘Inertia’ Test.
  • 28. 41. The completion of the test is indicated by the ‘Test Completed Successfully’ screen . Press the ‘ENTER’ soft key. This will bring up the ‘Edit Speed Reg BW’ entry screen. Select the ‘ENTER’ soft key to accept the default value of 10.00 R/S. 28 of 68 Edi t Speed Reg BW 0.00 << 100.00 10.00 R/S St ar t up I ner t i a Test 42. Pressing the ‘ENTER’ key in the previous step has directed you bac k to the ‘Motor Test Menu’. Use the ‘ENTER’ soft key to select ‘Done’ in the ‘Motor Test Menu’ screen. Configuring the Speed Reference and Ramp rates 43. At this time you should be in the ‘General Startup Main Menu’. The next item on the Startup menu list’ Ref Ramp Stop’ should be highlighted by default. Press the ‘ENTER’ soft key to make this your selection. 44. The ‘Edit Direction Mode’ box should be on the screen now. We will use the default parameter value of ‘Unipolar’ for this lab session. Press the ‘ENTER’ soft key to confirm and save your selection. 45. You should be on the ‘speed reference source’ selection screen. Use the down arrow or up arrow keys to highlight ‘Analog Input’ as your Speed Reference source. Use the ‘ENTER’ soft key to make this your selection.
  • 29. 46. In the window ‘Select Port to Use’ that appears following the previous step, use the down arrow or up arrow keys to highlight ‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key 29 of 68 to confirm and save your selection. St ar t up Ref er ence Sel ect i on Edi t Spd Ref A Sel Sel ect Por t To Use Zer o Speed Port 00 Power Fl ex 753 47. Use the down arrow and up arrow keys, to highlight ‘Par 0260 Anlg In0 Value’. The selected choice is the last in the list and pressing the once will get you there faster. Press the ‘ENTER’ soft key to confirm and save your selection. St ar t up Ref er ence Sel ect i on Edi t Spd Ref A Sel Sel ect Par m To Use Par 0878 Por t 14 Ref er ence Anl g I n0 Val ue Par 0876 Par 0260 Por t 6 Ref er ence 48. The next few steps will configure the Analog Input you chose as Speed Reference. For this lab session we will use the 0-10V potentiometer (labeled 0-10 Input) on the demo as our Analog Input speed reference. Pressing the ‘ENTER’ soft key in the previous step has led you to the first item required to configure the Analog Input. You should be in ‘Edit Anlg In0 Hi’ screen. Press the ‘ENTER’ soft key to accept the default value of ‘10.000’ Volt. 49. In the ’Edit Anlg In0 Lo’ screen that follows, press the ‘ENTER’ soft key to accept the default value of ‘0.000’ Volt. 50. In the next few screens input these values ‘Speed Ref A Anlg Hi’ = 60Hz and ‘Speed Ref A Anlg Lo’ = 0Hz. Press the ‘ENTER’ soft key. 51. You should be in the ‘Startup / Stop Config’ screen now, press the ‘ENTER’ soft key to accept the default selection of ‘Ramp’ to be used as ‘Stop Stop Mode A’.
  • 30. 52. Pressing the ‘ENTER’ key in the previous step has directed you to the screen to configure the ‘Bus Reg Mode A’. Select the default of ‘Adjust Freq’ using the ‘ENTER’ soft key 53. Following the step to set bus regulation you will now set Ramp (Accel and Decel) times. In the ‘Edit Accel Time 1’ screen, use the appropriate number key to enter a value of ‘3’ seconds. Press the ‘ENTER’ soft key. 54. Similarly enter a value of 3 seconds for the deceleration time in the ‘Edit Decel Time 1’ screen. 30 of 68 Press the ‘ENTER’ soft key. 55. The next screen continues the ramp speed configuration and asks the question ‘Do you want to perform S-curve for Accel/Decel? ‘. We will select ‘No’ as the answer for this lab session. You can select ‘No’ by highlighting it using the down and up arrow keys and then using the ‘ENTER’ soft key to confirm and save your selection. Configuring the Inputs and Outputs 56. Completing the previous step successfully has led you to the ‘General Startup Main Menu’ with the item ‘I/O’ highlighted. Press the ‘ENTER’ soft key to enter the ‘I/O’ section. 57. You should be in the ‘Start Stop I/O’ screen now. The first item to configure on this lis t is ‘Start Stop & Dir’. Press the ‘ENTER’ soft key to enter this section. Read the Introductory screen to this section and press the ‘ENTER’ soft key to continue. 58. The next screen requires you to answer the question ‘Will a Digital Input be used as a START Source? Select ‘Yes’ using the down and up arrow keys and then using ‘ENTER’ soft key to confirm and save your selection. We will use the green push button labeled ’Di 1’ in the demo as our Start Source in a later step. 59. The next screen will ask the question ‘Is Reverse required from a digital input?’? Select ‘Yes’ using the down and up arrow keys and then using ‘ENTER’ soft key to confirm and save your selection. We will use the switch labeled ’Di 2’ in the demo as forward/reverse in a later step. 60. Select ‘3 wire’ as your choice for the question ‘Enter Choice for the control method’. 61. In the ‘Edit DI Start / Select Port To Use’ window use the up and down arrow keys to highlight ‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key to make this your selection. 62. In the ‘Edit DI Start / Select Parm To Use’ window. Press the Enter soft key to select and confirm ‘Par 0220 Digital In Sts’ selection. 63. The ‘Edit DI Start’ window will be displayed first; select the bit/Digital Input you want to use as your START. We are going to use the green push button labeled ‘Di 1’ as our start input. To do this scroll to ‘Digital Input 1’ and press the Enter soft key.
  • 31. 64. Follow procedures similar to the previous steps to select the red push button labeled ‘Di 0’ as your stop switch and the selector switch labeled ‘Di 2’ as your Forward/Revers e switch in that order. 65. You should now be back in the ‘Start Stop I/O’ menu screen. This is all we will configure in this section so use the down arrow keys to scroll down to the last item on the list ‘Done’. After ‘Done’ is highlighted, use the ‘ENTER’ soft key to make this your selection. 66. You should now be back in the General Startup Main Menu screen .you have finished with the Startup routine steps required for this lab session. Select ‘Done’ using the ‘ENTER’ soft key to exit out this screen. 67. Select ‘Exit Startup’ using the ‘ENTER’ soft key to exit out of the Startup routine. 68. You can now test your drive to perform the functions you configured during the startup routine namely, Start using the green push button Di 1, Stop using the red push button Di 0, change direction using Di 2 and provide speed reference using the ‘0-10V Input’ pot. Again, remember that there is no physical motor connected to this demo unit however the speed and status are being simulated on the top lines of the HIM display. 31 of 68
  • 32. Drive Programming via Software Tool (Optional) Besides the HIM the drive parameters and programming can be accessed via software tool. These tools include DriveTools SP, Drive Explorer, or RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater). 32 of 68 About This Section In this lab, we will introduce you to DriveExplorer software and some of the features that are common across all the software tools. In this lab you will:  Connect to a PowerFlex drive using DriveExplorer software  Display the Status View  Display and edit parameters with the Linear List View  Display and edit parameters with the File / Group View  Use the Control Bar to control a drive  Use a Wizard  Upload configuration from drive to PC  Download configuration to drive from PC Using Drive Explorer with PF753 1. Verify that the PowerFlex 753 drive is connected to the computer. 2. When using DriveExplorer, it may be necessary to shutdown RSLinx if it has the serial or USB driver configured. If RSLinx is running, it will display an icon in the Systray on the PC’s desktop.
  • 33. 3. Right click on the RSLinx Icon in the Systray. 4. Select Shutdown RSLinx Classic on the Pop-up menu. Starting Drive Explore and Connect To Drive 1. Double-click the DriveExplorer icon to start the software. 2. If the Danger dialog appears, read it and click OK. 3. Maximize the DriveExplorer window, so it fills the entire screen 4. Click on the “Connect Ethernet” icon in the taskbar. 33 of 68
  • 34. a. If the ‘Connect Serial” icon has focus instead; DriveExplorer is configured to communicate serially; configuration path needs to be changed to Ethernet. Go to Explore  Configure communication  Select Ethernet  ok. b. The following screen will appear. Select yes to accept the communication interface 34 of 68 change c. At this point the “Connect Ethernet” icon will now have focus, select it by clicking on it
  • 35. 5. When the node selection window opens, highlight the node with IP address 192.168.1.21 and click the ‘Connect’ button to connect to the drive. a. If the IP Address of the drive is not in the window then select Add Node, type in the IP 35 of 68 address then click OK. b. Click Yes to the following message windows. 6. Wait for the parameters to be read and populated.
  • 36. 7. Once the parameters are read and populated, by default Port 0 PowerFlex 753 240V 4.2 A should be highlighted, as shown in the following graphic. 36 of 68 Reset Drive to Defaults 8. Navigate to Actions  Non Volatile Memory and click on Non Volatile Memory.
  • 37. 9. This will open a new window. Use the default selection of ‘Host and Ports to Defaults (Preferred) 37 of 68 and click on the button ‘Load Defaults’ 10. Observe the prompted warning then click ‘Yes’ to the question “Do you wish to continue?” in the next window.
  • 38. 11. A pop window confirms that loading of parameter defaults was successful. Click ‘OK’. 12. You will be returned to the Non-Volatile Memory window, Click ‘Close’ 38 of 68
  • 39. 39 of 68 Displaying The Status View 13. If you have not already expanded the Drive Explorer application do so now by clicking on the lower right corner of the window and drag it so the entire Status View area can be seen (you can also maximize the window using the Maximize icon if desired) The Status View displays the drive’s User Text (“PowerFlex 753” in the image above) as well as important drive information, such as voltage and amp ratings, series, revision, and operational status. The Status View is automatically displayed the first time you connect to a drive. You can also display it at any time by clicking on the drive name in the device tree (PowerFlex 753 in the above image).
  • 40. 14. You can display the status view for any peripheral (e.g. the DeviceLogix adapter or other communication adapter) by selecting the peripheral in the device tree. 15. Return to the drives status view; Click on the drive’s User Text (in the image, it is “PowerFlex 753”) to edit it. Enter new text such as “PowerFlex Rocks!” and click Apply  40 of 68 16. The new User Text is now displayed.
  • 41. 17. Click on the Pencil icon for the middle display item. 18. This is where you select, scale and assign text to Display Item 1. 19. Change Process Display Item 1 to the following values and click Apply 41 of 68
  • 42. 20. Close the Process Display Item 1 window. 21. Note the change you made to Process Display Item 1. Adjust the 0-10V Input potentiometer on the drive demo to change the value on the screen. The PowerFlex 753 has six Process Display items displayed. Other products may have more or less and each will be display on theirs in the Status View. 42 of 68
  • 43. Displaying Parameters with the Linear List View 22. Click on Parameter List in the device tree to display a linear list of the drive parameters. 23. Scroll down to view Parameter 260 [Anlg In0 Value] and then double-click on this parameter to 43 of 68 view it. This is a read-only parameter that displays the value of Analog In0, which is connected to the potentiometer (0-10V INPUT) on the demo unit. Adjust the potentiometer to see the value change. Click Close.
  • 44. 24. Scroll down even further to Parameter 535 [Accel Time 1]. and then double-click on this 44 of 68 parameter to view and edit it This is a writeable parameter that determines the acceleration rate it takes to go from 0 Hz to P27[Motor NP Hertz] or P28[Motor NP RPM), according to the setting in P300[Speed Units]. To edit this parameter, a new value would be entered followed by clicking either ‘OK’ or ‘Apply’. Click ‘Cancel’. Displaying Parameters with the File / Group View 25. In the device tree, click on the ‘Speed Control’ file and then the ‘Speed Ramp Rates’ group to display those parameters. See how getting to the same parameter as what was previously scrolled to using the Linear List function can be accessed by its grouping. If you do not know a parameter’s number, it maybe easier to find it with the File / Group view.
  • 45. 45 of 68 Using the Startup Wizard The Startup Wizards eliminate the need to search for setup parameters because commonly used parameters are contained in a single wizard. Configuration becomes a guided, step-by-step process using graphics and parameter names (not numbers!), which simplifies drive setup. 1. Click on the Wizard Browser icon to launch the Wizard Browser and display the available wizards. The PowerFlex 753 Startup Wizard is similar to performing the HIM Assisted Startup. Configuration parameters that are common to most applications are displayed in text / graphic forms and presented in a sequential step-by-step process. The DPI/DSI Tech Support Wizard is used to collect information for a remote support person to help troubleshoot a problem. Drive and peripheral information such as series and revision is collected along with changed parameters, fault & event queues, diagnostic items, etc. This information is saved to a text file which can be emailed to RA Tech Support, the OEM that supplied the machine, or the Corporate Engineer responsible for the remote plant, etc. Additional wizards will be available in the future and can be added to DriveExplorer v6.02 (and higher) at any time. New wizards will be posted on the AB Drives Web Updates page for free download: http://www.ab.com/support/abdrives/webupdate/index.html Note: The same wizards also work with DriveTools SP v6.02 and higher and RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater).
  • 46. 26. Select the PowerFlex 753 Startup Wizard and click ‘Select’. The wizard will first upload the parameters for each of the wizard pages. 27. The first step in the wizard is the Welcome page. It explains the wizard and gives hints and tips 46 of 68 for using the wizard. Click ‘Next’.
  • 47. 28. The Reset Parameters step is next. It allows you to reset the drive’s parameters back to factory defaults. Verify ‘High Voltage’ and ‘Normal Duty’ is selected from the pull down menus. Then click ‘Reset Parameters’. 47 of 68 In the confirmation window, click ‘Yes’. Observe the on screen confirmation of the parameters being reset. Click Next> to continue; viewing the sequential process and continuing to click Next> until you reach the Motor Control Step of the Wizard
  • 48. 29. Perform the Motor Control Step of the PowerFlex 753 Startup Wizard. Make the selections 48 of 68 shown: Motor Control Mode = Select ‘Induction Flux Vector’ Primary Speed Feedback = Slot 0 (PowerFlex 753); Parameter 138 (Simulator Fdbk) Click Next> to the Motor Data Step of the Wizard.
  • 49. 30. The Motor Data is next. This step assists in entering the data from your motor’s nameplate into the drive. No selections need to be changed on this step, keep the default selections. Click Next> to the Stop Mode Step of the Wizard. 49 of 68
  • 50. 31. The Stop Mode step is next. This step assists in selecting the drive’s stop mode and Dynamic Brake (DB) resistor type. No selections need to be changed on this step, keep the default selections. Click Next> to the Direction Test Step of the Wizard. 50 of 68
  • 51. 32. The Direction Test step is next. It helps you determine if the motor is rotating in the proper direction for your application. No selections need to be changed on this screen. Direction Tests are not needed for this example; however they can be ran if you desire. If you do perform the autotune note the following: Click the button and hold it for a few seconds to run the drive. As long as you hold the jog button, the drive will run. Once you let go of the button, the drive will stop. After the motor stops, click the Yes radio button. Observe how clicking the Yes radio button updated the screen with a “Test Passed” status as well as adding ‘Change Direction’ option. Click Next> to the AutoTune Step of the Wizard. 51 of 68
  • 52. 33. The AutoTune step is next. This step is where you can use automatic tuning algorithms (AutoTune). When running these algorithms the drive energizes the motor and makes measurements, which are used to make parameter settings. AutoTune tests are not needed for this example; however they can be ran if you desire. If you do perform the autotune note the test status: leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not leave AutoTune test page until test completes: Click Next> to the Inertia AutoTune Step of the Wizard. Note: Clicking <Back, Next>, or leaving step by any means will about the test. 52 of 68
  • 53. 34. The Inertia AutoTune is next. This step is where you can use an automatic tuning algorithm to determine the load’s inertia. When running this algorithm the drive spins the motor and makes measurements, which are used to make parameter settings AutoTune tests are not needed for this example; however they can be ran if you desire. If you do perform the autotune note the test status: leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not leave AutoTune test page until test completes: Click Next> to the Ramp Rates / Speed Limits Step of the Wizard. Note: Clicking <Back, Next>, or leaving step by any means will about the test. 53 of 68
  • 54. 24. Perform the Ramp Rates/Speed Limits Step of the PowerFlex 755 Startup Wizard. Enter: Max Forward / Reverse Speed 60 Hz Min Forward / Reverse Speed 0 Hz Enter a non-zero value for the S Curve to see what happens with the graphic. Then reset it back to 0. Click Next> to the Speed Reference Step of the Wizard. 54 of 68
  • 55. 35. The Speed Reference step is next. It helps you select where the drive gets its speed reference. Observe the screen with the default value for speed reference selected to Port 0. Now select the reference to be from P260 [Anlg In0], observe how the wizard shows the pertinent parameters and for this analog input. Click Next> to continue; viewing the sequential process, continue to click Next> until you reach the Start / Stop step of the Wizard. 55 of 68
  • 56. 36. Perform the Start / Stop step of the PowerFlex 753 Startup Wizard. Make the selections shown. DI Start = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 1) DI Stop = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 0) DI Forward / Reverse = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 2) Click Next> to the Other Digital Inputs Step of the Wizard. 56 of 68
  • 57. 37. The Other Digital Inputs step is next. This step helps you configure the drive’s most commonly used digital inputs. No selections need to be changed on this step, keep the default selections Click Next> to the Digital Output Port 0 Step of the Wizard. There are other digital inputs available to user; however the Wizard shows the most commonly programmed inputs. All the available digital inputs can be accessed via the HIM or software tool (parameters 150 – 201). 57 of 68
  • 58. 38. Perform the Digital Relay Out 0 step of the PowerFlex 753 Startup Wizard. This step helps you configure the drive’s digital outputs. Make the selections shown Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 16 (Running) Click Next> to the Digital Output Port 0 Step of the Wizard. There are no I/O options installed in this demo; however if there were an additional digital option card installed more Digital Output and Analog Output steps would become available to user and would be designated by their associated port. 58 of 68
  • 59. 39. Perform the Digital Transistor Out 0 Step of the PowerFlex 753 Startup Wizard. This step helps you configure the drive’s digital outputs. Make the selections shown Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 7 (Faulted) Click Next> to the Analog Output Port 0 Step of the Wizard. 59 of 68
  • 60. 40. The Analog Out 0 step is next. It helps you configure the drive’s analog outputs. No selections need to be changed on this step, keep the default selections. Click Next> to the Pending Changes Step of the Wizard. 60 of 68
  • 61. 41. The Applied and Pending Changes page will appear. The purpose of this step is to verify all of the changes you made in the wizard, and then apply the changes to the drive. The below screen is for reference (your changes may differ from what is shown below). Click Finish >>. The wizard will write your changes to the drive. The Pending Changes step can be used as a reference tool. You can print the summary with the print button at the bottom of the window. You can refer to the printed summary when commissioning duplicate drives or replacing a faulted drive. 61 of 68
  • 62. 62 of 68 Using the Control Bar Tool 42. Click on the button in the tool bar at the top of the window 43. Read Caution advisory and click OK
  • 63. 44. Use the buttons on the left-hand side of the control bar to start, stop, jog and control the direction 63 of 68 of the drive The speed reference was selected to the Analog In0 in the previous step. To allow the control bar to have control of the speed reference; Parameter 545[Spd Ref A Sel] will need to be changed (while the drive is not running). Stop the drive and change Parameter 545 setting to Port ‘PowerFlex 753’, Parameter ‘876 - Port 6 Reference’. Start the Drive again and use the slider on the right-hand side to control the speed reference. 45. Stop the Drive and turn off the control bar by clicking the button again. Observe the Caution pop up window and click Yes.
  • 64. 64 of 68 Using Off-line Files This feature allows you to save your drive configuration to a computer. It is useful for several reasons:  You can use the configuration if you replace the drive or install an identical one.  You can use the configuration to troubleshoot the drive if it begins to malfunction because the settings have been changed. Uploading and Saving the Drive’s Configuration to a PC 46. Select the drive in the device tree. 47. From the Actions menu, select Upload/Download All. 48. On the Upload/Download All window choose Upload.
  • 65. 49. By selecting the Upload/Download All you now are prompted to select with ports to upload. Deselect port 1 (20-HIM-x6) and Port 6 (20-COMM-E) and then click Upload. 50. Each of the ports parameters will be uploaded. As indicated by the below screen, each port will be displayed as its parameters are uploaded. 51. In the Save As window define the filename and location of the file. Take note of the name and remember where you save this file, it will be needed later. 52. After choosing the name and location to save file the Uploading… screen will regain focus; click 65 of 68 Close.
  • 66. 53. Again the Upload/Download All window will appear, click Close. This section had described how to upload all the ports in the drive into one file. Also available on the Actions menu is the option to select Upload and Save. Doing this will upload and save the parameters for the selected port in the device tree. Downloading Configuration to Drive from a PC 54. Change the value of a parameter that you can easily verify (e.g. P535 [Accel Time 1]). 55. From the Actions menu, select Upload/Download All. 56. On the Upload/Download All window choose Download. 57. Select Yes. To the resulting dialog window. 58. Select the same file you created in the section above and click the Open button. 66 of 68
  • 67. 59. Notice on the Select Sets To Download window that only the chosen option ports that were selected to upload in the previous steps are available. Click Download. 60. The saved parameter file values will be downloaded. Close the Download Complete! 67 of 68 Acknowledgement. 61. Again the Upload/Download All window will appear, click Close. 62. Verify that the value of the parameter you changed a few steps back has returned to its original value.
  • 68. 68 of 68 Notes: