SlideShare a Scribd company logo
1 of 7
PowerFlex™ 400 Process PID for Fans 
Equipment List 
PowerFlex 400 Demo 
With Red Fan Demo 
Windows 2000 PC with DriveExecutive™ 
and DriveObserver™ software 
Background 
The PowerFlex 400 drive will be used to operate the fan motor and control air-flow with the built-in 
PID loop. Our application scenario is an intake fan that must maintain a constant pressure regardless 
of the demand. The damper in the plenum will be used to simulate different demand settings. 
Lab Objectives 
This lab is designed to familiarize the student with process PI. At the conclusion of this lab, the 
student will be able to: 
 Configure process PID for fan control 
 Verify drive setup 
 Configure DriveObserver to monitor data 
 View PID variables 
 Tune the PID regulator 
Conventions Used in This Lab 
 ATTENTION: Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage or economic loss. Attention statements help you 
identify a hazard, avoid a hazard, and recognize the consequences. 
 TIP: Identifies information that is helpful, but not necessary, in completing a task. 
 FYI: Provides additional information regarding the lab equipment, but is not needed to 
complete the lab. 
Drive Demo Setup 
1. Position all switches to the OFF position. (Left for IN1, IN2, RUN FWD, RUN REV) 
 Attention: High Voltage Shock Hazard Exists. Do Not Remove Cover Unless ALL 
Power is Removed. Verify this by checking if the Emergency Stop pushbutton is pushed 
in and is not lit. The front cover must be in place prior to applying power to the 
PowerFlex 400 demo. During this lab, do not remove the cover.
• 1. Verify that the PC is connected to the PowerFlex 400 drive as follows: 
 Connect the PC to the PowerFlex drive as follows: 
 Connect 9 Pin D-shell connector to Com1 of the computer. 
 Connect cable to the 22-SCM-232 module. 
 Connect RJ45 Cable to the drive and the 22-SCM-232 module 
• 2. Verify that the fan is connected to the PowerFlex 400 drive as follows: 
 Connect motor cable of the fan to the external motor connector on the drive 
2 pf400processpidforfanslab-140914194054-phpapp02 
demo 
 Connect the fan I/O connector to the external I/O connector on the drive 
demo 
 Connect the fan to 120 Vac (for the meter supply) 
 FYI: The “Aux” must have the connector with the chain, plugged in. 
• 3. Pull the Power Switch (Red mushroom button) to power the demo. 
(NOTE: If your demo does not power up, please ask an instructor for help). 
Set the Drive to Defaults 
• 1. Set parameter P041 [Reset To Defaults] to 1 “Factory Rset” to reset all 
parameter values to factory default settings. 
• 2. Press “Stop” to clear the active fault (F048). 
Programming the Process PID Design 
Connecting to the Drive Using DriveExecutive 
• 1. Double-click the DriveExecutive icon on the Windows desktop (or in the 
Windows Start menu select Programs > DriveTools 2000 > DriveExecutive) 
to start the software. (If RSLinx is not configured, refer to last page for setup 
instructions) 
• 2. If a Danger dialog appears, read it and click OK. 
• 3. In the menus select Drive > Connect to Drive… 
• 4. When the Connect to Drive dialog opens, navigate the tree to the serial driver 
(in this case, “Unrecognized Device”). 
• 5. Select the drive device (Unrecognized Device) and click OK. The drive window 
opens. At this time, DriveExecutive may create a Device Database File.
3 pf400processpidforfanslab-140914194054-phpapp02 
PID Regulator 
Process Control uses the output of PID regulator as the speed reference. No master 
speed reference exists and the PID Output directly controls the drive output. This 
configuration does not require a master reference, only a desired setpoint, such as a 
desired pressure or flow rate. The PID loop compares the setpoint to the process 
feedback. The PID loop controls the drive output to maintain the process steady state 
to match the setpoint. 
Our application will use the Process Control configuration to control pressure in the fan 
plenum. 
Configuring Reference and Feedback Signals 
• 1. Set parameter A152 [PID Ref Sel] to 1 “PID Setpoint” to enable the setpoint. 
• 2. Set parameter A153 [PID Feedback Sel] to 1 “Analog Input 2” 
• 3. Set parameter T073 [Analog In 2 Sel] to 1 “Current Mode 4-20 mA” 
• 4. Set A12 DIP Switch to 20 mA 
• 5. Set parameter A157 [PID Setpoint] to a value of 25% (the desired Setpoint). 
 TIP: The parameter setting changes can be made on-line from the “Linear List” 
window that is open in DriveExecutive or using the integral keypad on the drive. 
Drive Executive will not show the letter before the parameter number. 
Defining Control of the PID Regulator 
The PID regulator was enabled when you set parameter A152 [PID Ref Sel] to 1 “PID 
Setpoint” and parameter A157 [PID Setpoint] to 25.0% 
Setting Limits for the PI Regulator 
• 1. Set parameter P035 [Maximum Frequency] to a value of 100 Hz. This will allow 
the PI Regulator to control the airflow even when the damper is completely 
closed. If the frequency is limited to 60Hz, the airflow would not reach the 
desired level when the damper is closed.
4 pf400processpidforfanslab-140914194054-phpapp02 
Verifying Drive Setup 
Checking Switch Settings and Verifying Reference and Feedback Signals 
• 1. Start the drive by switching the RUN FWD switch on the demo to ON. Verify 
that P036 is set to 2 “2-Wire”; P037 is set to 4 “Ramp to Stop”; and A166 is set 
to 0 “Reverse Enable” 
• 2. Run the drive in Forward. The fan in the bottom of the demo should be turning 
counter-clockwise when looking at it top perspective. (Run the drive in Reverse 
if the fan is turning in the wrong direction.) 
• 3. View the drive in DriveExecutive. 
• 4. Locate parameter d306 [Analog In 2] 
• 5. View parameter d306[Analog In 2] and verify that there is approximately 25% 
flow rate. 
• 6. Stop the drive. 
Viewing the PID Variables 
Starting DriveObserver 
To perform this portion of the lab, you will be using DriveObserver software. 
• 1. Double-click the DriveObserver icon on the Windows desktop (or in the 
Windows Start menu select Programs > DriveTools 2000 > DriveObserver) 
to start the software. 
• 2. In the menus, select File > New. The sampling dialogue will open. 
• 3. Select a sampling period of 300 milliseconds, and then click OK. 
Adding Traces 
• 1. If the Add Trace dialog is not already open, select Chart >Add traces… 
• 2. DriveObserver will display the node that is currently being used by 
DriveExecutive. (Otherwise, you will need to use the Add Node button to select 
a drive.) 
• 3. From the drive Linear List, select the following parameters from the linear list of 
the node by clicking the checkbox in front of each desired parameter: d001 
[Output Freq] and d306[Analog In 2], A157 [PID Setpoint]. 
• 4. Click OK. 
Recording Data 
• 1. Start the drive by switching the RUN FWD (or RUN REV) switch on the demo to 
the ON position. 
• 2. In the DriveObserver toolbar, click the Record button . DriveObserver now 
displays new data. 
• 3. If you want to stop recording data, click the Stop button .
 TIP: Double clicking the parameter in the table beneath the chart will open a dialog so that 
you can change the color, minimum & maximum values, line format, etc. For this exercise, 
you may wish to set the Analog in 4-20ma and the PID Setpoint to a scale of 0-100%.This 
will allow you to verify that they are equal 
5 pf400processpidforfanslab-140914194054-phpapp02 
Tuning the PID Regulator 
The PID regulator in the drive must be adjusted for the specific fan that you are 
connected to. These adjustments need to be made to optimize how the drive reacts to 
changes in the connected load. 
Understanding Gain Settings 
This section will help you get a feeling for how to adjust the drive gain values. Use 
DriveExecutive to make changes while you watch the [Output Freq] and [Analog In 4- 
20mA] signal in DriveObserver. Do not forget to change the damper position after 
each parameter setting change. 
The Proportional component affects how the regulator reacts to the magnitude of the 
error. To increase the responsiveness program parameter A154 [PID Proportional 
Gain] to a larger value. The default value is 0.01. 
The Integral component affects how the regulator reacts to error over time. To increase 
the integration rate, program parameter A155 [PID Integral Time] to a smaller value. 
The default value is 2.0. 
The Differential component affects the rate of change of the PID output. To increase 
the responsiveness, program parameter A156[PID Differential Rate] to a larger value. 
The default value is 0.00. 
Using DriveObserver, you should be able to adjust the gain settings in the PowerFlex 
400 drive until you have a graph that looks like the one below. A properly tuned PI 
regulator will minimize overshoot (and ringing) while avoiding excessive undershoot. 
When properly tuned, your chart should look something like this when the damper is 
changed from fully-open to fully-closed. 
1. Change the accel and decel to 0.1 sec. This will ensure that they do not affect the PID 
loop. 
2. Parameter A154 [PID Prop Gain] is set to a default of 0.01. This equates to 1% output 
change for 100% feed back change. Adjust A154 [PID Prop Gain] to a larger value (like 
0.5) and verify the operation of the PID regulator by varying the position of the damper 
from fully open to fully closed on the fan. Continue to adjust this value until an optimum 
value is reached. (If the system becomes unstable, back off the value). Record your 
value for PID Prop Gain ______________________________. 
3. Parameter A155 [PID Integral Time] is set to a default of 2.0 seconds. This parameter is 
scaled so that when it is set to 2.0, the process will integrate from 0-100% of [Maximum 
Frequency] in 2.0 seconds when the process error is 100%. Adjust A155 [PID Integral 
Time] to a lower value (like 1.0) and verify the operation of the PID regulator by varying 
the position of the damper from fully-open to fully-closed on the fan. Continue to adjust 
this value until an optimum value is reached. (If the system becomes unstable, the value 
is too small). Record your value for PID Integral Time _____________________. 
4. Parameter A156 [PID Differential Rate] is set to 0 default. This parameter is scaled so 
that when it is set to 1.0, the process response is 0.1% of [Maximum Frequency] when
the process error is changing at 1% / second. Adjust this and observe the effect on the 
process response when making changes to the damper from fully-open to fully-closed 
on the fan. Record your value for PID Differential Rate ____________________. 
5. Parameter A158 [PID Deadband]. This parameter setting allows a deadband that is +/- 
of the Setpoint, that is, if A138 [PID Deadband] is set to 5.0 and Setpoint is set to 25.0. 
This allows the feedback to change from 20 to 30 without the PID regulator acting on 
the error. Set to a value (less than 5) and observe affect. 
6. Parameter A159 [PID Preload]. This parameter will be pre-loaded into the integral 
component of the PID at any start or enable. Stop the drive, wait a couple of seconds, 
then start the drive. Note the time it takes to null the error. 
7. Note the steady state output frequency of the drive. Stop the drive. Set A159 to the 
output frequency observed before stopping the drive. Start the drive. Note how preload 
affects the reaction time at start. Adjust the value of preload to an optimum setting. 
8. Change the damper position. Does the preload value work for this new plenum system? 
9. Select a value for PID Preload that works under various damper positions and record 
your value _________________________. 
6 pf400processpidforfanslab-140914194054-phpapp02 
70 
60 
50 
40 
30 
20 
10 
0 
Set Up an RSLinx Serial Driver 
• 1. Connect the PC to the PowerFlex drive as follows: 
60 
50 
40 
30 
20 
10 
0 
Commanded Frequency 
Feedback 
Start 
Stop
• 2. Double-click on RSLinx icon on your desktop (or in the Windows Start menu select 
Programs > Rockwell Software > RSLinx > RSLinx) to start RSLinx. We need to start 
RSLinx the first time so that we can configure a serial driver. 
• 3. In the menus, select Communications > Configure Drivers. The Configure Drivers 
7 pf400processpidforfanslab-140914194054-phpapp02 
dialog box will open. 
• 4. Look in the list of Configured Drivers. If you see a driver whose name begins with 
“AB_DF1”, select it and click Delete. 
• 5. In the Available Drivers selection box, select “RS-232 DF1 devices” and click Add New. 
• 6. When prompted for a name, click OK. The Configure RS-232 DF1 Devices dialog box 
will open. Make sure that: 
 The “Comm Port” is set to the communications port on your PC (COM1 for this 
lab). 
 The “Device” is set to 1770-KF2/1785-KE/SCANport. 
• 7. The baud rate is set to the baud rate of your adapter (38400 for this lab). 
• 8. Click OK to close the dialog box. 
• 9. Verify that the driver that you just configured is listed in the Configured Drivers list 
with a status of “Running”. 
 TIP: If the Status is “Conflict”, other software may be using the serial comm port or you 
may have two RSLinx serial drivers programmed for the same serial port: 
 Delete duplicate drivers 
 If another serial software package, such as DriveExplorer, is running, close it. Then 
stop and re-start the RSLinx serial driver. 
• 10. Click Close to close the Configure Drivers dialog. 
• 11. In the menus, select Communications > RSWho…. The RSWho dialog will open. 
• 12. You should see both a computer (Workstation) and the connected drive device 
(AB_DF1-1, Data Highway Plus). ** NOTE: At this time, the drive device will be 
depicted by a question mark icon labeled “Unrecognized Device”. The serial driver 
will work. **. If this is not the case, verify that you have properly connected the PC to 
the drive using the 22-SCM-232 adapter and that power to the drive is on. If you check 
all these things and the connected drive device still does not appear, verify your device 
driver settings and try other baud rates (9600, 19200 38400) and computer comm ports 
(COM1, COM2). 
• 13. Close RSLinx.

More Related Content

What's hot

Design and tuning of PID override control system based on signal filtering
Design and tuning of PID override control system based on signal filteringDesign and tuning of PID override control system based on signal filtering
Design and tuning of PID override control system based on signal filteringMinh Chien Tran
 
Tuning presentation v1
Tuning presentation v1Tuning presentation v1
Tuning presentation v1tony arman
 
Instraction on Smart Home Software
Instraction on Smart Home SoftwareInstraction on Smart Home Software
Instraction on Smart Home SoftwareDaniel Chen
 
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...ufjjdjkkskemmd
 
Pid controllers
Pid controllersPid controllers
Pid controllersHussain K
 
Operation of hydro power plants
Operation of hydro power plants Operation of hydro power plants
Operation of hydro power plants DINESHPRASAD39
 
Kast md 902 explorer case study
Kast   md 902 explorer case studyKast   md 902 explorer case study
Kast md 902 explorer case studyStephen Kast
 
Inst maint practices
Inst maint practicesInst maint practices
Inst maint practicesPrem Baboo
 
Machine monitoring system
Machine monitoring systemMachine monitoring system
Machine monitoring systemPrem Baboo
 
Screenshot 2021-02-23 at 2.46.02 PM.pdf
Screenshot 2021-02-23 at 2.46.02 PM.pdfScreenshot 2021-02-23 at 2.46.02 PM.pdf
Screenshot 2021-02-23 at 2.46.02 PM.pdfmuhammadsubhan626458
 

What's hot (13)

Stc
StcStc
Stc
 
Design and tuning of PID override control system based on signal filtering
Design and tuning of PID override control system based on signal filteringDesign and tuning of PID override control system based on signal filtering
Design and tuning of PID override control system based on signal filtering
 
Tuning presentation v1
Tuning presentation v1Tuning presentation v1
Tuning presentation v1
 
Instraction on Smart Home Software
Instraction on Smart Home SoftwareInstraction on Smart Home Software
Instraction on Smart Home Software
 
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...
Daewoo doosan dx300 lc excavator service repair manual (serial number 5001 an...
 
Pid controllers
Pid controllersPid controllers
Pid controllers
 
Operation of hydro power plants
Operation of hydro power plants Operation of hydro power plants
Operation of hydro power plants
 
Kast md 902 explorer case study
Kast   md 902 explorer case studyKast   md 902 explorer case study
Kast md 902 explorer case study
 
Pi controller ieee format
Pi controller ieee formatPi controller ieee format
Pi controller ieee format
 
Inst maint practices
Inst maint practicesInst maint practices
Inst maint practices
 
Machine monitoring system
Machine monitoring systemMachine monitoring system
Machine monitoring system
 
Screenshot 2021-02-23 at 2.46.02 PM.pdf
Screenshot 2021-02-23 at 2.46.02 PM.pdfScreenshot 2021-02-23 at 2.46.02 PM.pdf
Screenshot 2021-02-23 at 2.46.02 PM.pdf
 
PID Tuning
PID TuningPID Tuning
PID Tuning
 

Similar to Pf400 process pid_for_fans_lab

Pf700 energy savings_lab
Pf700 energy savings_labPf700 energy savings_lab
Pf700 energy savings_labconfidencial
 
Drv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamDrv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamconfidencial
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01confidencial
 
Sitrain s7 1200 pwm pid
Sitrain s7 1200 pwm pidSitrain s7 1200 pwm pid
Sitrain s7 1200 pwm pidconfidencial
 
Manual e plano Zexel Covec F VRZ
Manual e plano Zexel Covec F VRZ Manual e plano Zexel Covec F VRZ
Manual e plano Zexel Covec F VRZ Junior Iung
 
Ls catalog thiet bi tu dong i e5_e_1105
Ls catalog thiet bi tu dong i e5_e_1105Ls catalog thiet bi tu dong i e5_e_1105
Ls catalog thiet bi tu dong i e5_e_1105Dien Ha The
 
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vnLs catalog thiet bi tu dong i e5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vnDien Ha The
 
Dhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bDhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bconfidencial
 
PID Control Basics
PID Control BasicsPID Control Basics
PID Control BasicsYokogawa1
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vnBien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vnDien Ha The
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vnBien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vnDien Ha The
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1
Bien tan ls   gioi thieu bien tan i e5 series (new)-1Bien tan ls   gioi thieu bien tan i e5 series (new)-1
Bien tan ls gioi thieu bien tan i e5 series (new)-1Dien Ha The
 
Premier integration with logix, pf drives and ft view (pf755)
Premier integration with logix, pf drives and ft view (pf755)Premier integration with logix, pf drives and ft view (pf755)
Premier integration with logix, pf drives and ft view (pf755)confidencial
 
vm1118-vertiv-geist-watchdog-100-manual.pdf
vm1118-vertiv-geist-watchdog-100-manual.pdfvm1118-vertiv-geist-watchdog-100-manual.pdf
vm1118-vertiv-geist-watchdog-100-manual.pdfJorge Gonzales
 
Guia HAP para LG MultiV
Guia HAP para LG MultiVGuia HAP para LG MultiV
Guia HAP para LG MultiVfranco5190
 

Similar to Pf400 process pid_for_fans_lab (20)

Pf70 700 process_pi
Pf70 700 process_piPf70 700 process_pi
Pf70 700 process_pi
 
Pf700 energy savings_lab
Pf700 energy savings_labPf700 energy savings_lab
Pf700 energy savings_lab
 
User Guide - PID
User Guide - PIDUser Guide - PID
User Guide - PID
 
Drv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcamDrv10 lab3 pf755_pcam
Drv10 lab3 pf755_pcam
 
Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01Sitrains7 1200pwmpid-150301123045-conversion-gate01
Sitrains7 1200pwmpid-150301123045-conversion-gate01
 
Sitrain s7 1200 pwm pid
Sitrain s7 1200 pwm pidSitrain s7 1200 pwm pid
Sitrain s7 1200 pwm pid
 
Manual e plano Zexel Covec F VRZ
Manual e plano Zexel Covec F VRZ Manual e plano Zexel Covec F VRZ
Manual e plano Zexel Covec F VRZ
 
Ls catalog thiet bi tu dong i e5_e_1105
Ls catalog thiet bi tu dong i e5_e_1105Ls catalog thiet bi tu dong i e5_e_1105
Ls catalog thiet bi tu dong i e5_e_1105
 
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vnLs catalog thiet bi tu dong i e5_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i e5_e_1105_dienhathe.vn
 
Dhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_bDhq pf700 pump_energy_savings_rev_b
Dhq pf700 pump_energy_savings_rev_b
 
Cpcu08 drv14
Cpcu08 drv14Cpcu08 drv14
Cpcu08 drv14
 
PID Control Basics
PID Control BasicsPID Control Basics
PID Control Basics
 
PID Controllers from Precision Digital
PID Controllers from Precision DigitalPID Controllers from Precision Digital
PID Controllers from Precision Digital
 
SPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
SPP-01 Super Parameter Programmer User Manual Ultisolar New EnergySPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
SPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vnBien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vnBien tan ls   gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
Bien tan ls gioi thieu bien tan i e5 series (new)-1-dienhathe.vn
 
Bien tan ls gioi thieu bien tan i e5 series (new)-1
Bien tan ls   gioi thieu bien tan i e5 series (new)-1Bien tan ls   gioi thieu bien tan i e5 series (new)-1
Bien tan ls gioi thieu bien tan i e5 series (new)-1
 
Premier integration with logix, pf drives and ft view (pf755)
Premier integration with logix, pf drives and ft view (pf755)Premier integration with logix, pf drives and ft view (pf755)
Premier integration with logix, pf drives and ft view (pf755)
 
vm1118-vertiv-geist-watchdog-100-manual.pdf
vm1118-vertiv-geist-watchdog-100-manual.pdfvm1118-vertiv-geist-watchdog-100-manual.pdf
vm1118-vertiv-geist-watchdog-100-manual.pdf
 
Guia HAP para LG MultiV
Guia HAP para LG MultiVGuia HAP para LG MultiV
Guia HAP para LG MultiV
 

More from confidencial

19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_enconfidencial
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0confidencial
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_enconfidencial
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_enconfidencial
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_enconfidencial
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_enconfidencial
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_enconfidencial
 
11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_enconfidencial
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_enconfidencial
 
09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_enconfidencial
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_enconfidencial
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_enconfidencial
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_enconfidencial
 
05 project setup v1.00_en
05 project setup v1.00_en05 project setup v1.00_en
05 project setup v1.00_enconfidencial
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_enconfidencial
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 enconfidencial
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_enconfidencial
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 enconfidencial
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeconfidencial
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01confidencial
 

More from confidencial (20)

19 exercises v1.00_en
19 exercises v1.00_en19 exercises v1.00_en
19 exercises v1.00_en
 
18 syntax rules v1.0
18 syntax rules v1.018 syntax rules v1.0
18 syntax rules v1.0
 
17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en17 demonstration server client system-v1.00_en
17 demonstration server client system-v1.00_en
 
15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en15 final steps of configuration v1.00_en
15 final steps of configuration v1.00_en
 
14 mass data engineering v1.00_en
14 mass data engineering v1.00_en14 mass data engineering v1.00_en
14 mass data engineering v1.00_en
 
13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en13 locking functions and operating modes v1.00_en
13 locking functions and operating modes v1.00_en
 
12 archiving system v1.00_en
12 archiving system v1.00_en12 archiving system v1.00_en
12 archiving system v1.00_en
 
11 customizing the os v1.00_en
11 customizing the os v1.00_en11 customizing the os v1.00_en
11 customizing the os v1.00_en
 
10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en10 basics automatic mode control v1.00_en
10 basics automatic mode control v1.00_en
 
09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en09 basics operating and monitoring v1.00_en
09 basics operating and monitoring v1.00_en
 
08 basics control functions v1.00_en
08 basics control functions v1.00_en08 basics control functions v1.00_en
08 basics control functions v1.00_en
 
07 connection to the process v1.00_en
07 connection to the process v1.00_en07 connection to the process v1.00_en
07 connection to the process v1.00_en
 
06 station and network configuration v1.00_en
06 station and network configuration v1.00_en06 station and network configuration v1.00_en
06 station and network configuration v1.00_en
 
05 project setup v1.00_en
05 project setup v1.00_en05 project setup v1.00_en
05 project setup v1.00_en
 
03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en03 requirements and functional process description v1.00_en
03 requirements and functional process description v1.00_en
 
02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en02 pcs 7 documentation and support v1.00 en
02 pcs 7 documentation and support v1.00 en
 
01 introduction v1.00_en
01 introduction v1.00_en01 introduction v1.00_en
01 introduction v1.00_en
 
00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en00 st pcs7-sys_v8.0_register 20 en
00 st pcs7-sys_v8.0_register 20 en
 
Fluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verdeFluxograma processo acucar_alcool_etanol_verde
Fluxograma processo acucar_alcool_etanol_verde
 
01tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp0101tiaportal handson-basicov11v2-140421084257-phpapp01
01tiaportal handson-basicov11v2-140421084257-phpapp01
 

Recently uploaded

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 

Recently uploaded (20)

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 

Pf400 process pid_for_fans_lab

  • 1. PowerFlex™ 400 Process PID for Fans Equipment List PowerFlex 400 Demo With Red Fan Demo Windows 2000 PC with DriveExecutive™ and DriveObserver™ software Background The PowerFlex 400 drive will be used to operate the fan motor and control air-flow with the built-in PID loop. Our application scenario is an intake fan that must maintain a constant pressure regardless of the demand. The damper in the plenum will be used to simulate different demand settings. Lab Objectives This lab is designed to familiarize the student with process PI. At the conclusion of this lab, the student will be able to:  Configure process PID for fan control  Verify drive setup  Configure DriveObserver to monitor data  View PID variables  Tune the PID regulator Conventions Used in This Lab  ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss. Attention statements help you identify a hazard, avoid a hazard, and recognize the consequences.  TIP: Identifies information that is helpful, but not necessary, in completing a task.  FYI: Provides additional information regarding the lab equipment, but is not needed to complete the lab. Drive Demo Setup 1. Position all switches to the OFF position. (Left for IN1, IN2, RUN FWD, RUN REV)  Attention: High Voltage Shock Hazard Exists. Do Not Remove Cover Unless ALL Power is Removed. Verify this by checking if the Emergency Stop pushbutton is pushed in and is not lit. The front cover must be in place prior to applying power to the PowerFlex 400 demo. During this lab, do not remove the cover.
  • 2. • 1. Verify that the PC is connected to the PowerFlex 400 drive as follows:  Connect the PC to the PowerFlex drive as follows:  Connect 9 Pin D-shell connector to Com1 of the computer.  Connect cable to the 22-SCM-232 module.  Connect RJ45 Cable to the drive and the 22-SCM-232 module • 2. Verify that the fan is connected to the PowerFlex 400 drive as follows:  Connect motor cable of the fan to the external motor connector on the drive 2 pf400processpidforfanslab-140914194054-phpapp02 demo  Connect the fan I/O connector to the external I/O connector on the drive demo  Connect the fan to 120 Vac (for the meter supply)  FYI: The “Aux” must have the connector with the chain, plugged in. • 3. Pull the Power Switch (Red mushroom button) to power the demo. (NOTE: If your demo does not power up, please ask an instructor for help). Set the Drive to Defaults • 1. Set parameter P041 [Reset To Defaults] to 1 “Factory Rset” to reset all parameter values to factory default settings. • 2. Press “Stop” to clear the active fault (F048). Programming the Process PID Design Connecting to the Drive Using DriveExecutive • 1. Double-click the DriveExecutive icon on the Windows desktop (or in the Windows Start menu select Programs > DriveTools 2000 > DriveExecutive) to start the software. (If RSLinx is not configured, refer to last page for setup instructions) • 2. If a Danger dialog appears, read it and click OK. • 3. In the menus select Drive > Connect to Drive… • 4. When the Connect to Drive dialog opens, navigate the tree to the serial driver (in this case, “Unrecognized Device”). • 5. Select the drive device (Unrecognized Device) and click OK. The drive window opens. At this time, DriveExecutive may create a Device Database File.
  • 3. 3 pf400processpidforfanslab-140914194054-phpapp02 PID Regulator Process Control uses the output of PID regulator as the speed reference. No master speed reference exists and the PID Output directly controls the drive output. This configuration does not require a master reference, only a desired setpoint, such as a desired pressure or flow rate. The PID loop compares the setpoint to the process feedback. The PID loop controls the drive output to maintain the process steady state to match the setpoint. Our application will use the Process Control configuration to control pressure in the fan plenum. Configuring Reference and Feedback Signals • 1. Set parameter A152 [PID Ref Sel] to 1 “PID Setpoint” to enable the setpoint. • 2. Set parameter A153 [PID Feedback Sel] to 1 “Analog Input 2” • 3. Set parameter T073 [Analog In 2 Sel] to 1 “Current Mode 4-20 mA” • 4. Set A12 DIP Switch to 20 mA • 5. Set parameter A157 [PID Setpoint] to a value of 25% (the desired Setpoint).  TIP: The parameter setting changes can be made on-line from the “Linear List” window that is open in DriveExecutive or using the integral keypad on the drive. Drive Executive will not show the letter before the parameter number. Defining Control of the PID Regulator The PID regulator was enabled when you set parameter A152 [PID Ref Sel] to 1 “PID Setpoint” and parameter A157 [PID Setpoint] to 25.0% Setting Limits for the PI Regulator • 1. Set parameter P035 [Maximum Frequency] to a value of 100 Hz. This will allow the PI Regulator to control the airflow even when the damper is completely closed. If the frequency is limited to 60Hz, the airflow would not reach the desired level when the damper is closed.
  • 4. 4 pf400processpidforfanslab-140914194054-phpapp02 Verifying Drive Setup Checking Switch Settings and Verifying Reference and Feedback Signals • 1. Start the drive by switching the RUN FWD switch on the demo to ON. Verify that P036 is set to 2 “2-Wire”; P037 is set to 4 “Ramp to Stop”; and A166 is set to 0 “Reverse Enable” • 2. Run the drive in Forward. The fan in the bottom of the demo should be turning counter-clockwise when looking at it top perspective. (Run the drive in Reverse if the fan is turning in the wrong direction.) • 3. View the drive in DriveExecutive. • 4. Locate parameter d306 [Analog In 2] • 5. View parameter d306[Analog In 2] and verify that there is approximately 25% flow rate. • 6. Stop the drive. Viewing the PID Variables Starting DriveObserver To perform this portion of the lab, you will be using DriveObserver software. • 1. Double-click the DriveObserver icon on the Windows desktop (or in the Windows Start menu select Programs > DriveTools 2000 > DriveObserver) to start the software. • 2. In the menus, select File > New. The sampling dialogue will open. • 3. Select a sampling period of 300 milliseconds, and then click OK. Adding Traces • 1. If the Add Trace dialog is not already open, select Chart >Add traces… • 2. DriveObserver will display the node that is currently being used by DriveExecutive. (Otherwise, you will need to use the Add Node button to select a drive.) • 3. From the drive Linear List, select the following parameters from the linear list of the node by clicking the checkbox in front of each desired parameter: d001 [Output Freq] and d306[Analog In 2], A157 [PID Setpoint]. • 4. Click OK. Recording Data • 1. Start the drive by switching the RUN FWD (or RUN REV) switch on the demo to the ON position. • 2. In the DriveObserver toolbar, click the Record button . DriveObserver now displays new data. • 3. If you want to stop recording data, click the Stop button .
  • 5.  TIP: Double clicking the parameter in the table beneath the chart will open a dialog so that you can change the color, minimum & maximum values, line format, etc. For this exercise, you may wish to set the Analog in 4-20ma and the PID Setpoint to a scale of 0-100%.This will allow you to verify that they are equal 5 pf400processpidforfanslab-140914194054-phpapp02 Tuning the PID Regulator The PID regulator in the drive must be adjusted for the specific fan that you are connected to. These adjustments need to be made to optimize how the drive reacts to changes in the connected load. Understanding Gain Settings This section will help you get a feeling for how to adjust the drive gain values. Use DriveExecutive to make changes while you watch the [Output Freq] and [Analog In 4- 20mA] signal in DriveObserver. Do not forget to change the damper position after each parameter setting change. The Proportional component affects how the regulator reacts to the magnitude of the error. To increase the responsiveness program parameter A154 [PID Proportional Gain] to a larger value. The default value is 0.01. The Integral component affects how the regulator reacts to error over time. To increase the integration rate, program parameter A155 [PID Integral Time] to a smaller value. The default value is 2.0. The Differential component affects the rate of change of the PID output. To increase the responsiveness, program parameter A156[PID Differential Rate] to a larger value. The default value is 0.00. Using DriveObserver, you should be able to adjust the gain settings in the PowerFlex 400 drive until you have a graph that looks like the one below. A properly tuned PI regulator will minimize overshoot (and ringing) while avoiding excessive undershoot. When properly tuned, your chart should look something like this when the damper is changed from fully-open to fully-closed. 1. Change the accel and decel to 0.1 sec. This will ensure that they do not affect the PID loop. 2. Parameter A154 [PID Prop Gain] is set to a default of 0.01. This equates to 1% output change for 100% feed back change. Adjust A154 [PID Prop Gain] to a larger value (like 0.5) and verify the operation of the PID regulator by varying the position of the damper from fully open to fully closed on the fan. Continue to adjust this value until an optimum value is reached. (If the system becomes unstable, back off the value). Record your value for PID Prop Gain ______________________________. 3. Parameter A155 [PID Integral Time] is set to a default of 2.0 seconds. This parameter is scaled so that when it is set to 2.0, the process will integrate from 0-100% of [Maximum Frequency] in 2.0 seconds when the process error is 100%. Adjust A155 [PID Integral Time] to a lower value (like 1.0) and verify the operation of the PID regulator by varying the position of the damper from fully-open to fully-closed on the fan. Continue to adjust this value until an optimum value is reached. (If the system becomes unstable, the value is too small). Record your value for PID Integral Time _____________________. 4. Parameter A156 [PID Differential Rate] is set to 0 default. This parameter is scaled so that when it is set to 1.0, the process response is 0.1% of [Maximum Frequency] when
  • 6. the process error is changing at 1% / second. Adjust this and observe the effect on the process response when making changes to the damper from fully-open to fully-closed on the fan. Record your value for PID Differential Rate ____________________. 5. Parameter A158 [PID Deadband]. This parameter setting allows a deadband that is +/- of the Setpoint, that is, if A138 [PID Deadband] is set to 5.0 and Setpoint is set to 25.0. This allows the feedback to change from 20 to 30 without the PID regulator acting on the error. Set to a value (less than 5) and observe affect. 6. Parameter A159 [PID Preload]. This parameter will be pre-loaded into the integral component of the PID at any start or enable. Stop the drive, wait a couple of seconds, then start the drive. Note the time it takes to null the error. 7. Note the steady state output frequency of the drive. Stop the drive. Set A159 to the output frequency observed before stopping the drive. Start the drive. Note how preload affects the reaction time at start. Adjust the value of preload to an optimum setting. 8. Change the damper position. Does the preload value work for this new plenum system? 9. Select a value for PID Preload that works under various damper positions and record your value _________________________. 6 pf400processpidforfanslab-140914194054-phpapp02 70 60 50 40 30 20 10 0 Set Up an RSLinx Serial Driver • 1. Connect the PC to the PowerFlex drive as follows: 60 50 40 30 20 10 0 Commanded Frequency Feedback Start Stop
  • 7. • 2. Double-click on RSLinx icon on your desktop (or in the Windows Start menu select Programs > Rockwell Software > RSLinx > RSLinx) to start RSLinx. We need to start RSLinx the first time so that we can configure a serial driver. • 3. In the menus, select Communications > Configure Drivers. The Configure Drivers 7 pf400processpidforfanslab-140914194054-phpapp02 dialog box will open. • 4. Look in the list of Configured Drivers. If you see a driver whose name begins with “AB_DF1”, select it and click Delete. • 5. In the Available Drivers selection box, select “RS-232 DF1 devices” and click Add New. • 6. When prompted for a name, click OK. The Configure RS-232 DF1 Devices dialog box will open. Make sure that:  The “Comm Port” is set to the communications port on your PC (COM1 for this lab).  The “Device” is set to 1770-KF2/1785-KE/SCANport. • 7. The baud rate is set to the baud rate of your adapter (38400 for this lab). • 8. Click OK to close the dialog box. • 9. Verify that the driver that you just configured is listed in the Configured Drivers list with a status of “Running”.  TIP: If the Status is “Conflict”, other software may be using the serial comm port or you may have two RSLinx serial drivers programmed for the same serial port:  Delete duplicate drivers  If another serial software package, such as DriveExplorer, is running, close it. Then stop and re-start the RSLinx serial driver. • 10. Click Close to close the Configure Drivers dialog. • 11. In the menus, select Communications > RSWho…. The RSWho dialog will open. • 12. You should see both a computer (Workstation) and the connected drive device (AB_DF1-1, Data Highway Plus). ** NOTE: At this time, the drive device will be depicted by a question mark icon labeled “Unrecognized Device”. The serial driver will work. **. If this is not the case, verify that you have properly connected the PC to the drive using the 22-SCM-232 adapter and that power to the drive is on. If you check all these things and the connected drive device still does not appear, verify your device driver settings and try other baud rates (9600, 19200 38400) and computer comm ports (COM1, COM2). • 13. Close RSLinx.