COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINKIJARIIT
This paper presents a comparison between the Direct-On-Line (D.O.L.), and Soft Starter by using MATLAB Simulink .The purpose of this project is to find out the theoretical and actual characteristics of Induction motor. These three basic starting methods which different the irrespective wiring connection are the most applicable and widely-used starting method in the industrial area due to its economic reasons. This project is done by analyzing the characteristics during the motor starting by using the MATLAB Simulation to capture the waveforms of these events. After the Simulation, the three different starting method are being compared to conclude the most suitable and applicable starting method.
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
Most induction motors are started directly on line, but when very large motors are started that way, they cause a disturbance of voltage on the supply lines due to large starting current surges. To limit the starting current surge, large induction motors are started at reduced voltage and then have full supply voltage reconnected when they run up to near rotated speed.
COMPARATIVE STUDY OF INDUCTION MOTOR STARTERS USING MATLAB SIMULINKIJARIIT
This paper presents a comparison between the Direct-On-Line (D.O.L.), and Soft Starter by using MATLAB Simulink .The purpose of this project is to find out the theoretical and actual characteristics of Induction motor. These three basic starting methods which different the irrespective wiring connection are the most applicable and widely-used starting method in the industrial area due to its economic reasons. This project is done by analyzing the characteristics during the motor starting by using the MATLAB Simulation to capture the waveforms of these events. After the Simulation, the three different starting method are being compared to conclude the most suitable and applicable starting method.
Motor StarterTypes and Technology of Motor Starter And Its Applicationselprocus
Most induction motors are started directly on line, but when very large motors are started that way, they cause a disturbance of voltage on the supply lines due to large starting current surges. To limit the starting current surge, large induction motors are started at reduced voltage and then have full supply voltage reconnected when they run up to near rotated speed.
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...ijtsrd
Induction motors are considered nowadays the most commonly used electrical machines, which are mainly used as electrical induction motors and sometimes as generators. This is mainly due to the simplicity of composition, low price, light weight, high reliability, easy to command and control performance and not containing parts that could easily breakdown compared with DC machines and synchronous machines. Starting the IM is the most important and dangerous step, where the motor properties play a major role in the evaluation of all electrical motors, and these properties are defined by the following factors Starting torque. starting current. transient state. smoothness of the starting, simplicity and economics of starting. In this paper, three different methods of starting three phase Induction Motor are discussed and compared through curves of currents, torque, speed. These methods are Direct On Line, Auto Transformer, Star Delta, for a constant power load condition. Simulation is made in MATLAB SIMULINK and comparatively results are estimated to evaluate the best starting method for different range of induction motor rating. Suraj Grover | Mr. Mahesh Mankar ""Minimization of Starting Torque and Inrush Current of Induction Motor by Different Starting Methods using MATLAB/SIMULINK"" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-3 , April 2019, URL: https://www.ijtsrd.com/papers/ijtsrd22935.pdf
Paper URL: https://www.ijtsrd.com/engineering/electrical-engineering/22935/minimization-of-starting-torque-and-inrush-current-of-induction-motor-by-different-starting-methods-using-matlabsimulink/suraj-grover
Starting Time Calculation for Induction Motor.IJERA Editor
This Paper Presents The Starting Time Calculation For A Squirrel Cage Induction Motor. The Importance Of
Starting Time Lies In Determining The Duration Of Large Current, Which Flows During The Starting Of An
Induction Motor. Normally, The Starting Current Of An Induction Motor Is Six To Eight Time Of Full Load
Current. Plenty Of Methods Have Been Discovered To Start Motor In A Quick Time, But Due To Un-Economic
Nature, Use Are Limited. Hence, For Large Motors Direct Online Starting Is Most Popular Amongst All Due To
Its Economic And Feasible Nature. But Large Current With Dol Starting Results In A Heavy Potential Drop In
The Power System. Thus, Special Care And Attention Is Required In Order To Design A Healthy System.
A Very Simple Method To Calculate The Starting Time Of Motor Is Proposed In This Paper. Respective
Simulation Study Has Been Carried Out Using Matlab 7.8.0 Environment, Which Demonstrates The
Effectiveness Of The Starting Time Calculation.
Energy Efficient Operation of Three Phase Induction Motor using Delstar Conve...IJECEIAES
DELSTAR converter is an electronic system to be interfaced with the existing STAR – DELTA starter for machine tools. Induction motor consumes more power while it is operated at DELTA mode for a long time under no load condition. The proposed system gives the solution for the above stated problem. When the load on the motor is less than 40% of full load, it switches the motor to operate in STAR mode to save energy. When the load increases beyond 40%, it automatically switches the motor to operate in DELTA mode. The starting regimen is not disturbed. The proposed converter is recommended for applications where load changes are not more than 120 times/hour. This can be used with any capacity motor by choosing appropriate current transformers and setting the current level using the potentiometer built in. The proposed converter is designed for 5HP induction motor and experimentally tested.
International Journal of Computational Engineering Research(IJCER)ijceronline
International Journal of Computational Engineering Research(IJCER) is an intentional online Journal in English monthly publishing journal. This Journal publish original research work that contributes significantly to further the scientific knowledge in engineering and Technology.
This ppt is for your education purpose.
I can explain the electrical starters in very best ways ,
you can understande the all electrical starters in very easy methods.
For your any inquiry,
CONTECT NO : - 9082557285
CREATED BY : - AYUSH .A. PITHAL
Industrial Star Delta Starter for a 3-Phase Induction Motorelprocus
The most basic feature of an Induction motor is its self starting mechanism. Due to the rotating magnetic field, an emf is induced in the rotor, because of which current starts flowing in the rotor.
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
It is a project on pure electrical engineering. Here three phase motor is starting from star to delta automatically by using some components.In other hand it also provide protection to the motor.
CONTENT
Starting Of Induction Motor
Starters
Types Of Starter For 3-ph Induction Motors
Starting Of Slip Ring Induction Motor
D.O.L.(Direct On Line) starter
Star-delta Starter
Auto Transformer Starter
Difference Between DOL/Star Delta/ Autotransformer
Minimization of Starting Torque and Inrush Current of Induction Motor by Diff...ijtsrd
Induction motors are considered nowadays the most commonly used electrical machines, which are mainly used as electrical induction motors and sometimes as generators. This is mainly due to the simplicity of composition, low price, light weight, high reliability, easy to command and control performance and not containing parts that could easily breakdown compared with DC machines and synchronous machines. Starting the IM is the most important and dangerous step, where the motor properties play a major role in the evaluation of all electrical motors, and these properties are defined by the following factors Starting torque. starting current. transient state. smoothness of the starting, simplicity and economics of starting. In this paper, three different methods of starting three phase Induction Motor are discussed and compared through curves of currents, torque, speed. These methods are Direct On Line, Auto Transformer, Star Delta, for a constant power load condition. Simulation is made in MATLAB SIMULINK and comparatively results are estimated to evaluate the best starting method for different range of induction motor rating. Suraj Grover | Mr. Mahesh Mankar ""Minimization of Starting Torque and Inrush Current of Induction Motor by Different Starting Methods using MATLAB/SIMULINK"" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-3 , April 2019, URL: https://www.ijtsrd.com/papers/ijtsrd22935.pdf
Paper URL: https://www.ijtsrd.com/engineering/electrical-engineering/22935/minimization-of-starting-torque-and-inrush-current-of-induction-motor-by-different-starting-methods-using-matlabsimulink/suraj-grover
Starting Time Calculation for Induction Motor.IJERA Editor
This Paper Presents The Starting Time Calculation For A Squirrel Cage Induction Motor. The Importance Of
Starting Time Lies In Determining The Duration Of Large Current, Which Flows During The Starting Of An
Induction Motor. Normally, The Starting Current Of An Induction Motor Is Six To Eight Time Of Full Load
Current. Plenty Of Methods Have Been Discovered To Start Motor In A Quick Time, But Due To Un-Economic
Nature, Use Are Limited. Hence, For Large Motors Direct Online Starting Is Most Popular Amongst All Due To
Its Economic And Feasible Nature. But Large Current With Dol Starting Results In A Heavy Potential Drop In
The Power System. Thus, Special Care And Attention Is Required In Order To Design A Healthy System.
A Very Simple Method To Calculate The Starting Time Of Motor Is Proposed In This Paper. Respective
Simulation Study Has Been Carried Out Using Matlab 7.8.0 Environment, Which Demonstrates The
Effectiveness Of The Starting Time Calculation.
Energy Efficient Operation of Three Phase Induction Motor using Delstar Conve...IJECEIAES
DELSTAR converter is an electronic system to be interfaced with the existing STAR – DELTA starter for machine tools. Induction motor consumes more power while it is operated at DELTA mode for a long time under no load condition. The proposed system gives the solution for the above stated problem. When the load on the motor is less than 40% of full load, it switches the motor to operate in STAR mode to save energy. When the load increases beyond 40%, it automatically switches the motor to operate in DELTA mode. The starting regimen is not disturbed. The proposed converter is recommended for applications where load changes are not more than 120 times/hour. This can be used with any capacity motor by choosing appropriate current transformers and setting the current level using the potentiometer built in. The proposed converter is designed for 5HP induction motor and experimentally tested.
International Journal of Computational Engineering Research(IJCER)ijceronline
International Journal of Computational Engineering Research(IJCER) is an intentional online Journal in English monthly publishing journal. This Journal publish original research work that contributes significantly to further the scientific knowledge in engineering and Technology.
This ppt is for your education purpose.
I can explain the electrical starters in very best ways ,
you can understande the all electrical starters in very easy methods.
For your any inquiry,
CONTECT NO : - 9082557285
CREATED BY : - AYUSH .A. PITHAL
Industrial Star Delta Starter for a 3-Phase Induction Motorelprocus
The most basic feature of an Induction motor is its self starting mechanism. Due to the rotating magnetic field, an emf is induced in the rotor, because of which current starts flowing in the rotor.
star delta auto starter with forward reverse and motor protectionBHUPATI PRADHAN
It is a project on pure electrical engineering. Here three phase motor is starting from star to delta automatically by using some components.In other hand it also provide protection to the motor.
CONTENT
Starting Of Induction Motor
Starters
Types Of Starter For 3-ph Induction Motors
Starting Of Slip Ring Induction Motor
D.O.L.(Direct On Line) starter
Star-delta Starter
Auto Transformer Starter
Difference Between DOL/Star Delta/ Autotransformer
Students, digital devices and success - Andreas Schleicher - 27 May 2024..pptxEduSkills OECD
Andreas Schleicher presents at the OECD webinar ‘Digital devices in schools: detrimental distraction or secret to success?’ on 27 May 2024. The presentation was based on findings from PISA 2022 results and the webinar helped launch the PISA in Focus ‘Managing screen time: How to protect and equip students against distraction’ https://www.oecd-ilibrary.org/education/managing-screen-time_7c225af4-en and the OECD Education Policy Perspective ‘Students, digital devices and success’ can be found here - https://oe.cd/il/5yV
We all have good and bad thoughts from time to time and situation to situation. We are bombarded daily with spiraling thoughts(both negative and positive) creating all-consuming feel , making us difficult to manage with associated suffering. Good thoughts are like our Mob Signal (Positive thought) amidst noise(negative thought) in the atmosphere. Negative thoughts like noise outweigh positive thoughts. These thoughts often create unwanted confusion, trouble, stress and frustration in our mind as well as chaos in our physical world. Negative thoughts are also known as “distorted thinking”.
Power-sharing Class 10 is a vital aspect of democratic governance. It refers to the distribution of power among different organs of government, levels of government, and social groups. This ensures that no single entity can control all aspects of governance, promoting stability and unity in a diverse society.
For more information, visit-www.vavaclasses.com
Unit 8 - Information and Communication Technology (Paper I).pdfThiyagu K
This slides describes the basic concepts of ICT, basics of Email, Emerging Technology and Digital Initiatives in Education. This presentations aligns with the UGC Paper I syllabus.
The Art Pastor's Guide to Sabbath | Steve ThomasonSteve Thomason
What is the purpose of the Sabbath Law in the Torah. It is interesting to compare how the context of the law shifts from Exodus to Deuteronomy. Who gets to rest, and why?
Instructions for Submissions thorugh G- Classroom.pptxJheel Barad
This presentation provides a briefing on how to upload submissions and documents in Google Classroom. It was prepared as part of an orientation for new Sainik School in-service teacher trainees. As a training officer, my goal is to ensure that you are comfortable and proficient with this essential tool for managing assignments and fostering student engagement.
2024.06.01 Introducing a competency framework for languag learning materials ...Sandy Millin
http://sandymillin.wordpress.com/iateflwebinar2024
Published classroom materials form the basis of syllabuses, drive teacher professional development, and have a potentially huge influence on learners, teachers and education systems. All teachers also create their own materials, whether a few sentences on a blackboard, a highly-structured fully-realised online course, or anything in between. Despite this, the knowledge and skills needed to create effective language learning materials are rarely part of teacher training, and are mostly learnt by trial and error.
Knowledge and skills frameworks, generally called competency frameworks, for ELT teachers, trainers and managers have existed for a few years now. However, until I created one for my MA dissertation, there wasn’t one drawing together what we need to know and do to be able to effectively produce language learning materials.
This webinar will introduce you to my framework, highlighting the key competencies I identified from my research. It will also show how anybody involved in language teaching (any language, not just English!), teacher training, managing schools or developing language learning materials can benefit from using the framework.
Extraction Of Natural Dye From Beetroot (Beta Vulgaris) And Preparation Of He...SachinKumar945617
If you want to make , ppt, dissertation/research, project or any document edit service
DM me on what's app 8434381558
E-mail sachingone220@gmail.com
I will take charge depend upon how much pages u want
Extraction Of Natural Dye From Beetroot (Beta Vulgaris) And Preparation Of He...
AUTOMATIC STAR DELTA STARTER.
1. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1160
Journal Homepage: -www.journalijar.com
Article DOI:10.21474/IJAR01/6965
DOI URL: http://dx.doi.org/10.21474/IJAR01/6965
RESEARCH ARTICLE
AUTOMATIC STAR DELTA STARTER.
Krunal Jayswal and Jay Modi.
Department of Electrical Engineering, Indus Institute of Technology and Engineering, Indus University.
……………………………………………………………………………………………………....
Manuscript Info Abstract
……………………. ………………………………………………………………
Manuscript History
Received: 16 February 2018
Final Accepted: 18 March 2018
Published: April 2018
This equipment/appliance reduces starting current and starting torque.
Automatic Star Delta Starter design normally consists of three
contactors, an overload relay or circuit breaker, and a timer for setting
the time in the Star position (starting position). For the Star Delta
Starter, a motor must be in delta connected position during a normal
run and the main purpose is to be able to use the starter.
When the motor is at idle, it just is like the short-circuited transformer
at secondary side because all the rotor bars are connected together to
form a closed path. This will draw a large current flow through the
rotor bars. So, when the motor is started, stator draws high current
which is 8-10 times that of the rated current. Therefore, before starting
the motor, it is necessary to reduce the voltage applied to the motor.
In Star connection current is in different phases but line voltage is root
three times that of the phase voltage. So, the voltage is reduced which
results in reduction of current if motor is started in star connection. In
Delta connection the voltage is same as that of phase voltage so full
voltage is applied if we run the motor in delta connection. The
Star/Delta Starter is generally obtained from three contactors,
pneumatic timer, and a thermal overload relay or circuit breaker, for 3
phase motor at 440 volt AC main supply 50 Hz.
Copy Right, IJAR, 2018,. All rights reserved.
………………………………………………………………………………………………......
Introduction:-
Function of Starters:-
The device which is used to limit the starting current and reduce the starting torque is called Starter. It reduces the
starting current to a safe value.
Need of Starters:-
Rotor current at standstill, I = E/Z = E/√ )
The magnitude of E depends on the flux linking with the rotor conductors and its relative speed. The strength of the
rotor flux depends upon the applied voltage. At the instant of applying rated voltage to the stator winding, rotor is
stationary and as such the slip is unity. So, if full rated voltage is given to stator winding, then magnitude of the emf
induced in rotor conductors will be high, because the relative speed between the rotor conductors and stator
revolving flux is very high i.e. equal to the synchronous speed of the stator flux. Further the rotor conductors are
short circuited and thus have low impedance.
Corresponding Author:- Krunal Jayswal, Jay Modi.
Address:- Department of Electrical Engineering, Indus Institute of Technology and Engineering
Indus University.
2. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1161
Hence the current drawn by the stator winding or motor is very large, approximately 5 to 7 times the full load
current.
The ill effects of high starting current are as follows:-
The copper losses occurring in the stator and rotor windings due high starting current are extremely large, which
would produce a lot of heat inside the machine and may damage the insulation of the windings. Moreover, there will
be a dip in supply voltage.
The starting current drawn by the motor can be reduced to a permissible value by:
1. Applying reduced voltage to the stator winding
2. Inserting resistance in the stator circuit
3. Inserting resistance in the rotor circuit
In case of slip ring induction motors, it is possible to add external resistance in rotor phases as wound rotor has 3
phase star connected winding to limit the starting high current. However, in case of squirrel cage induction motors it
is not possible to add any kind external resistance as it consists of copper bars, which is short circuited by end rings
on both sides. So, in case of squirrel cage induction motors, initial high current is controlled by applying reduced
voltage to stator winding during starting period and the full normal voltage is applied when rotor has picked up
speed to about 70 to 80% of its normal speed.
Different types of Starting methods:-
There mainly two types of starters available:-
DC Starters:-
1. Two-point Starter
2. Three-point Starter
3. Four-point Starter
AC Starters:-
1. D.O.L Starter (Direct Online)
2. Automatic/Manual Primary Resistance Starter
3. Automatic/Manual Autotransformer Starter
4. Automatic/Manual Star Delta Starter
Two Point Starter:-
As its name suggests this starter has two points for connections and is majorly used for DC Series motors to limit
starting currents and torque. It works on principle of adding resistance between supply and armature due to which
current is decreased for starting. As the resistance is decreased motor picks speed and runs a full supply voltage.
Three Point Starter:-
The working principle of this starter is similar to two-point starter unlike it has three points and is majorly used for
DC Shunt Motors.
Four Point Starter:-
It has same working principles as that of two point and three points but here and extra resistance pair is added in
field point connection which reduces current more efficiently for DC Compound Motors.
Direct Online Starter (D.O.L):-
It consists of contactors which a charged when supply is given to them and allows flowing same voltage to stator
windings. This starter is very simple inexpensive and easy to install and maintain. Under faulty conditions overload
relays are present which deenergize contactor and stops the flow of current. But in this starting the rate of
temperature rise is very high and motor may get damaged if the starting period is large, which may be due to
excessive voltage drop in supply lines. Thus, this type of starter is generally used for motor ratings up to 5KW.
Automatic/Manual Primary Resistance Starter:-
3. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1162
In this type of starting of 3 phase induction motor primary resistance are connected in all the three phases of the
stator winding as a result of which the applied voltage across stator winding at the instant of starting is reduced to a
fraction of rated voltage of motor. In manual starter resistance is increased or decreased manually while in automatic
particular fixed value of resistance is there for fixed time with the help of pneumatic timer connected across
contactors. This starting method heats up starting resistors and a large amount of power loss results. So, they are
used for small motors or less rated value motors.
Automatic/Manual Autotransformer Starter:-
In this method 3 phase auto transformer with fixed tappings is used to obtain reduced voltage for starting of 3 phase
induction motors. Normally 50 to 60% tappings can used to obtain a safe value of starting currents. Thuds 50 to 60%
of the rated voltage is applied at starting and the autotransformer is cut out of the motor circuit, when motor has
picked up the speed about 70 to 80% of the normal speed by changeover lever. Same thing is achieved in automatic
starter by interlocking mechanism of contactor with pneumatic timer. This starter can be efficiently used instead or
primary resistance starter where heating of resistors was a major problem. This starter provides same amount of
voltage reduction and does not lead to heating effect.
Automatic/Manual Star Delta Starter:-
This is the most commonly used starter, compared to different types of starters. Star Delta starter works on the
principle of voltage reduction during starting period. In star connection current is same as that of to line and phases
but line voltage is times phase voltage which leads to reduction in voltages in starting period. When the motor has
picked up speed we can say up to 70 to 80% of its rated speed the phases changeover to delta connection position. In
delta connection voltage across lines is same as that of phase voltage. A star delta starter is cheaper compared to
auto transformer starter. Thus, it is commonly used for both medium and small size motors. Since torque is
proportional to square of applied voltage, star delta starting reduces starting torque to 1/3 of that obtained from
Direct online. The automatic star to delta changeover is obtained by using interlocking connection in contactors with
that of pneumatic timer which changes over to delta after a fixed period of time.
Star Delta Starter
This is a starting method that reduces the starting current and starting torque. Star delta starter design normally
consists of three contactors, an overload relay or circuit breaker and a timer for setting the time in the star-position
(starting position). For the star delta starter, a motor must be in delta connected during a normal run and the main
purpose is to be able to use star delta starter.
In Star delta starter the received starting current is about 30 percent of the starting current during direct on line start
and the starting torque is reduced to about 25 percent of the torque available at a D.O.L starter. Star delta starter
only works when the application is light loaded during the start.
If the motor is too heavily loaded, there will not be enough torque to accelerate the motor up to speed before
switching over to the delta position.
Figure 2.1 shows manual star delta starter where star to delta changeover of done by changeover switch mechanism.
As the motor picks up speed and reaches up to desirable speed, switch is changeover of delta for running condition
leading to full voltage supply.
Unlike manual star delta starter in automatic star delta starter as shown in figure 2.2 an external circuit namely
control circuit is present which consists of timer contacts. With these timer contacts we can change star connection
to delta connection automatically within time of 0-30 seconds as desired. This time duration can be varied as per
starting and running characteristics as per our requirement. Contactors are used for changeover mechanism. These
contactors are connected according to controlling circuit with timer box to work accordingly.
4. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1163
Figure 2.1:- Manual Star Delta Starter
Figure 2.2:-Power Supply Diagram of Automatic Star Delta Starter
5. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1164
Working of Automatic Star Delta Starter
When the 'Start' push button PB1 is pressed the operating coil CM is energized. Hence, all the M contacts and
auxiliary contact MA will be closed and therefore connects the supply lines to motor terminals U1, V1, W1. At the
same time, the operating contacts CS for star contacts is also energized and closes its a contacts S and connects
motor terminals U2, V2, W2, which forms star point causing the motor to start as star connected motor. Therefore,
at starting the applied voltage to each phase of the winding will be 1/ of the rated voltage of the motor.
Now after a predetermined time, TR, operates which opens TO and closes TC, hence coil CD is energized and
closes its contacts D and coil CS will be deenergized and hence opens the contacts S, causing the motor to run in
delta at full supply voltage. The operating coil is energized by path 'L1-PB2-PB1-CM-OL-OL-OL-L2'. At the same
time the operating coil CS get energized by path 'L1-PB2-PB1-TO-D-CS-OL-OL-OL-L2'. The operating coil CD is
energized by path 'L1-PB2-MA-TC-OL-OL-OL-L2'. Pressing the OFF-push button, deenergizes all contactors and
disconnects the motor from line.
Figure 3.1:-Wiring and control circuit diagram of Automatic Star Delta Starter
L1, L2, L3 - Lines
S – Star Contacts
Cs – Operating coil for star contacts
D – Delta contacts
Cd – Operating coil for delta contacts
M – Line contacts
Cm – Operating coil for main contacts
TR – Pneumatic Timer
TO – Time Opening Contact
TC – Time Closing Contact
6. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1165
OLC – Overload relay coil
OL – Overload relay contact
PB1 – START push button
PB2 – OFF push button
Motor Starting Characteristics: The available starting current is 33% of full load current. The peak starting
characteristics is about 1.3 to 2.6 full load current. Peak starting torque is about 33% of full load torque.
Figure 3.2:-Starting condition (star position)
Figure 3.3:-Running condition (delta position).
7. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1166
Figure 3.4:-Readings of line voltage and phase voltage for 3 phase star (starting condition)
Figure 3.5:-Readings for line voltage and phase voltage for 3 phase Delta position (running condition)
Hardware Model
Our project consists of following hardware parts:
1. Contactors
2. Timer Box
3. Cable
4. START and STOP push button
Contactors:-
There are three assembled contactors used for star delta starter. The ratings of contactors are about 18A 230 VAC
which can work for a motor of 3Hp which is approximately 2,237.1 watts. The star and delta contactors are
interlocked with a particular fixed time after which star to delta changeover in connection occurs. Below is the
figure of Contactor.
8. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1167
Figure 4.1:-Contactor: 18A 230 VAC ratings
Timer Box:-
The timer box is of ELLICO Company. Its rated current is 5A with 230V single phase AC supply 50Hz. The time
within which star to delta changeover is done can be varied from 0 - 30 seconds. Below is the figure of Timer Box.
9. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1168
Figure 4.2 Timer Box 230V 5A
Cables:-
The cables used here are of 2.5m. They can allow passing up to 15-16A of current. The resistance of 2.5 m
according to resistance table provided by standard units is 8.21Ω/Km, provided is the figure of cables used in the
starter.
Figure 4.3:-Cables 2.5
START and STOP push buttons:-
These push buttons are based on the working principle of NO - normally open and NC - normally close type
buttons. The START button here used is connected in NO type connection while for STOP button NC type
connection is used. Below is the figure provided of START and STOP push buttons.
10. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1169
Figure 4.4:-STOP push buttons and START push buttons
Figure 4.5:-Final Outcome After Assembling
Conclusion and Future Scope:-
This type of starting is used for low to medium voltage and light starting torque motors. It is the cheapest way to
reduce the starting current and it is in the order of 3-4 times that in case of direct online starting of induction motor.
It can be easily implemented by the relays and the timer circuit.
The way of connecting the relays also prevents the motor from the single phasing. The project is designed to
provide low voltage start to induction motors. This is achieved by using star to delta conversion. Star/Delta starters
are probably the most common reduced voltage starters in the 50Hz industrial motor world.
Star delta is used in an attempt to reduce the start current applied to the motor then after sometime full load current
is applied to the motor. Since in star connection current is same in different phases while line voltage is the root
three times the phase voltage. So, the voltage is reduced (results to reduce current) if motor is started as star.
The interlocking arrangement of all the contactor coils is traditionally wired in 440-volt AC. The project is designed
to provide low voltage start to induction motors. The Star/Delta starter is generally manufactured from three
contactors; and pneumatic timer for operating a 3-phase motor at 440 volts at ac mains supply 50 Hz.
11. ISSN: 2320-5407 Int. J. Adv. Res. 6(4), 1160-1170
1170
Future Scope:-
Compared to the reduced voltage methods it is the simple and cheapest way of starting the motor. But it takes large
in rush currents during switching operation. Further the project can be enhanced by using a thyristor in firing angle
control principle for soft start of the induction motor that would overcome all the drawbacks of star delta starter.
References:-
1. Jamnani J.G, “Elements of Electrical Design”, Mahajan Publications, 2015, chap-3, pp. 3.1-3.20.
2. Gupta J.B, Theory and performance of Electrical machines, Katson books publications, 15th
edition: 2015
Section V, pp. - 5.1 – 5.30.
3. Jignesh Parmar, wordpress.com Star delta Starter,
https://electricalnotes.wordpress.com/2012/03/16/star-delta-starter/
4. PLC training - Star Delta Starter, wiring animated video, Real Pars
https://youtu.be./qA3Yg5CS-F8/
5. Star Delta 3-phase Motor automatic starter with timer,
http://www.electricaltechnology.org/2012/02/star-delta-3-phase-motor-starting.html
6. Star delta starter motor control with circuit diagram – practical video, Motor circuits,
https://www.youtube.com/watch?v=doBPliY-cik
7. Semi-automatic star delta starter, RJ electrical,
https://www.youtube.com/watch?v=7pY7Koh-Gi8
8. 3 phase induction motor starting with industrial star delta starter, EL-PRO-CUS,
https://www.elprocus.com/industrial-star-delta-starter-3-phase-induction-motor/
9. Circuit globe, Star delta starter, http://circuitglobe.com/star-delta-
starter.html
10. Academia education, automatic star delta starter with adjustable timer,
http://www.academia.edu/23086369/AUTOMATIC_STAR_DELTA_STARTER_USING_RELAYS_AND_A
DJUSTABLE_ELECTRONIC_TIMER_FOR_INDU CTION_MOTOR_Project_Synopsis