BUILDING SERVICES TECHNOLOGY
Course No: Arch 3151
Lecture: 03
Protection against Hazards
Hazard : A hazard poses the threat that an unwanted event,
possibly a catastrophe, may occur.
Risk: Risk is the probability that the event will occur.
All buildings are subject to hazards such as hurricanes, earthquakes,
flood, fire, and lightning strikes, both during and after construction.
Assessment of risk of a hazard and selection of cost-effective way of
avoiding the hazard and protection against it required to be done.
▪ Wind Protection
▪ Protection against Earthquakes
▪ Protection against Water
▪ Protection against Fire
▪ Lightning Protection
▪ Protection against Intruders
2
Protection against Fire
There are two distinct aspects of fire protection: life safety and
property protection.
A program that provides for prompt notification and evacuation of
occupants meets the objectives for life safety, but provides
no protection for property.
Conversely, it is possible that adequate property protection might
not be sufficient for protection of life.
Absolute safety from fire is not attainable. It is not possible to
eliminate all combustible materials or all potential ignition sources.
Thus, in most cases, an adequate fire protection plan must assume
that unwanted fires will occur despite the best efforts to prevent
them.
3
Fire Protection Concepts:
Some of the reasons for causing Fire in the Buildings- are human
error, arson, faulty electrical equipment, poor maintenance
of heating equipment, and natural causes, such as lightning.
Consequently, buildings should be designed to minimize the
probability of a fire and to protect life and limit property damage if a
fire should occur.
Following steps should be taken for Fire Prevention:
Fire prevention steps.pdf
4
Extinguishment of Fires:
▪ Design of all buildings should include provisions for prompt
extinguishment of fires.
▪ Such apparatus may range from small, hand-held extinguishers
for small fires to hoses attached to a large, pressurized water
supply and automatic fire sprinklers.
▪ Also desirable are fire and smoke detectors and a protective
signaling system that sounds an alarm to alert building occupants
and calls fire fighters.
5
6
7
8
Classes of Fires:
▪ Classes of Fires-a classification that separates combustible
materials into four types:
1. Class A fires involve ordinary combustibles and are readily
extinguishable by water or cooling, or by coating with a suitable
chemical powder.
2. Class B fires involve flammable liquids where smothering is
effective and where a cooling agent must be applied with care.
3. Class C fires are those in live electrical equipment where the
extinguishing agent must be nonconductive. Since a continuing
electrical malfunction will keep the fire source active, circuit
protection must operate to cut off current flow.
4. Class D fires involve metals that burn, such as magnesium,
sodium, and powdered aluminum. Special powders are necessary for
such fires, as well as special training for operators.
9
10
11
12
13
14
Apparatus for Extinguishment of Fires:
▪ Automatic Sprinklers: The most widely used apparatus for fire
protection in buildings is the automatic sprinkler system.
Sprinkler system consists of a network of piping installed at the
ceiling or roof and supplied with water from a suitable source.
▪ Standpipes: Hoses supplied with water from standpipes are the
usual means of manual application of water to interior building
fires.
▪ Chemical Extinguishment: Fires involving some materials may
not be readily extinguished with water alone. When such
materials may be present in a building, provision should be made
for application of appropriate chemicals-
o Chemical foam
o Air foam (mechanical foam)
o High-expansion foam
o Carbon dioxide
o Halon 1301
o Dry chemical extinguishing agents
o Dry powder extinguishing agents
15
16
17
18
There are two types of fire control
A. Active control
B. Passive control
Types of fire control
A. Active control
1.Fire Detection / Fire alarm System :
Fire alarm System can be either manual or automatic.
2.Fire extinguishing systems
It is obligatory to make provision of fire detection and/or fire
extinguishing systems. These systems are described below –
Types of fire control
These are simplest and most reliable fire
detection and are commonly used in building.
They are also known as temperature detectors.
This consists of a hand bell or similar sounding
devise emitting distinctive sound when struck.
Such devices are installed near all the main exit
and passages.
This type of system on detection of fire starts
sounding alarms or information to the nearest
control point.
1. Fire Detection System :
The commonly adopted fire extinguishing systems are described below:
a) Manual Fire alarm System :
b) Automatic alarm System :
c) Heat detector :
Active control
When a fire starts before the flame actually surface smoke is generated. These devices are
best suited for areas within a building when an anticipated fire would produce a large
column of smoke before the temperature of a fire is sufficient to operate heat detectors.
d) Smoke detector :
Active control
2. Fire Extinguishing System :
The commonly adopted fire extinguishing systems are described below:
a) Manual Fire Extinguishing System :
Portable fire extinguisher can be of carbon dioxide type, large foam generation
type and so on. Depending upon the capacity, the discharge from a fire
extinguisher may last 20 to 120 seconds. Sometimes buckets full of water and dry
sand are also installed.
Active control
b) Fire Hydrants:
This consists in providing a l50mm diameter ring main outside in the ground
around the periphery of the building.
The ring main is fed from an underground water tank and it is ensured that the
water pressure Available at each fire hydrant is of the order of 3.5kg/cm 2
.
Active control
c) Wet riser System:
1. 100 to 150 mm dia vertical G.I. Pipes at suitable locations within the building.
2. The risers are fed from underground water storage lank through a fire pump
which supplies water at 2.3kg/cm2
at the topmost outlet.
3. The wet risers have suitable connections at each floor from where constant
supply of water can be drawn in the event of fire.
wet riser system
Active control
sprinkler system Bashundhara City
d) Sprinkler system:
Pipes are normally 20mm dia
The pipes receive supply of water normally 40mm dia.
Active control
Fire Pump:
A fire pump is a part of a fire sprinkler system's water supply.
Active control
e) Stand pipe system:
In multi- storied building the hose from fire fighting equipment cannot reach
the upper floors, therefore a stand pipe system must be designed for such a
Structure.
stand pipe system
Active control
Active control
National building code
Corridor:
User should find exits at every end of the corridor. Closed corridor
should not more than 10 m.
Passive Control
Height of the corridor is minimum 2.4 m.
The size of Corridor according to number of users:
Maximum walking distance should not more than 23 m.
User Width
50 or less than 50 0.9 m
More than 50 1.1 m
More than 150 1.8 m
Passive Control
Types of Exits
Building codes generally indicate what types of facilities may
qualify as exits. These usually include:
Exit Passageway
Exit Doors
Stairs
Ramps
Refuge floors
Passive Control
Exit Passageways
Horizontal extensions of vertical exits, or a passage leading from
a yard or court to an outdoor space. Minimum floor ­
to-ceiling
height is the same as for corridors. Width should be at least that
of the vertical exit. Building codes may require the passageway
en­
closures to have a 2-hr fire rating.
Passive Control
Exit Doors
doors providing access to streets
doors to stairs and exit passageways
There should be one exit door for every 50 persons.
Minimum width of the door is 1 m & height is 2 m.
The exit door should be side swinging.
The door should be of outer direction if the user number is more than 50.
Passive Control
Detection of Fires:
Every fire-extinguishing activity must start with detection. To assist
in this, many types of automatic detectors are available, with a wide
range of sensitivity.
There are five general types of detectors, each employing a different
physical means of operation. The types are designated –
• fixed-temperature detectors,
• rate-of-rise detectors,
• Photoelectric detectors,
• combustion-products detectors, and
• ultraviolet or infrared detectors.
• Detectors.pdf
35
36
In addition to providing means for early detection of fire, preventing its
spread, and extinguishing it speedily, building designers should also provide
the appropriate number, sizes, and arrangements of exits to permit quick
evacuation of occupants if fire or other conditions dangerous to life occur.
Building codes generally contain requirements for safe, emergency egress
from buildings.
Egress Components
‘‘Life Safety Code’’ defines a means of egress composed of three
Parts-
Exit access—that portion that leads to an entrance to an exit
Exit—the portion that is separated from all other building spaces by
construction or equipment required to provide a protected path to the exit
discharge
Exit discharge—the portion that connects the termination of an exit to a
public way
37
Emergency Egress:
Means of egress may be provided by exterior and interior doors and
enclosed horizontal and vertical passageways, including stairs and
escalators.
Types of Exits:
Building codes generally recognize the following as acceptable
exits when they meet the codes’ safety requirements:
• Corridors
• Exit passageways
• Exit doors
• Horizontal exit
• Interior stairs
• Exterior stairs
• Smokeproof tower
• Escalators
• Moving walks
38
Emergency Egress:
Refuge Areas:
A refuge area is a space protected against fire and smoke. When
located within a building, the refuge should be at about the same level as the
areas served and separated from them by construction with at least a 2-hr fire
rating.
Access to the refuge areas should be protected by fire doors with a fire rating
of 1.5 hr or more.
Location of Exits:
Building codes usually require a building to have at least two
means of egress from every floor. Exits should be remote from each other, to
reduce the chance that both will be blocked in an emergency.
All exit access facilities and exits should be located so as to be clearly visible to
building occupants or signs should be installed to indicate the direction of
travel to the exits.
Signs marking the locations of exits should be illuminated with at least 5 ft-c of
light. Floors of means of egress should be illuminated with at least 1 ft-c of
artificial light whenever the building is occupied.
39
Emergency Egress:
Required Exit Capacity:
Minimum width of a passageway for normal use is 36 in. This is large
enough to accommodate one-way travel for persons on crutches or in
wheelchairs.
For two way travel, a 60-in width is necessary. Building codes,
however, may require greater widths to permit rapid passage of the
anticipated number of evacuees in emergencies.
This number depends on a factor called the occupant load, but the
minimum width should be ample for safe, easy passage of
handicapped persons. (Occupant load of a building space is the
maximum number of persons that may be in the space at any time)
Emergency Egress.pdf
40
Emergency Egress:
Thank You
41

building services /... .pptx

  • 1.
    BUILDING SERVICES TECHNOLOGY CourseNo: Arch 3151 Lecture: 03
  • 2.
    Protection against Hazards Hazard: A hazard poses the threat that an unwanted event, possibly a catastrophe, may occur. Risk: Risk is the probability that the event will occur. All buildings are subject to hazards such as hurricanes, earthquakes, flood, fire, and lightning strikes, both during and after construction. Assessment of risk of a hazard and selection of cost-effective way of avoiding the hazard and protection against it required to be done. ▪ Wind Protection ▪ Protection against Earthquakes ▪ Protection against Water ▪ Protection against Fire ▪ Lightning Protection ▪ Protection against Intruders 2
  • 3.
    Protection against Fire Thereare two distinct aspects of fire protection: life safety and property protection. A program that provides for prompt notification and evacuation of occupants meets the objectives for life safety, but provides no protection for property. Conversely, it is possible that adequate property protection might not be sufficient for protection of life. Absolute safety from fire is not attainable. It is not possible to eliminate all combustible materials or all potential ignition sources. Thus, in most cases, an adequate fire protection plan must assume that unwanted fires will occur despite the best efforts to prevent them. 3
  • 4.
    Fire Protection Concepts: Someof the reasons for causing Fire in the Buildings- are human error, arson, faulty electrical equipment, poor maintenance of heating equipment, and natural causes, such as lightning. Consequently, buildings should be designed to minimize the probability of a fire and to protect life and limit property damage if a fire should occur. Following steps should be taken for Fire Prevention: Fire prevention steps.pdf 4
  • 5.
    Extinguishment of Fires: ▪Design of all buildings should include provisions for prompt extinguishment of fires. ▪ Such apparatus may range from small, hand-held extinguishers for small fires to hoses attached to a large, pressurized water supply and automatic fire sprinklers. ▪ Also desirable are fire and smoke detectors and a protective signaling system that sounds an alarm to alert building occupants and calls fire fighters. 5
  • 6.
  • 7.
  • 8.
  • 9.
    Classes of Fires: ▪Classes of Fires-a classification that separates combustible materials into four types: 1. Class A fires involve ordinary combustibles and are readily extinguishable by water or cooling, or by coating with a suitable chemical powder. 2. Class B fires involve flammable liquids where smothering is effective and where a cooling agent must be applied with care. 3. Class C fires are those in live electrical equipment where the extinguishing agent must be nonconductive. Since a continuing electrical malfunction will keep the fire source active, circuit protection must operate to cut off current flow. 4. Class D fires involve metals that burn, such as magnesium, sodium, and powdered aluminum. Special powders are necessary for such fires, as well as special training for operators. 9
  • 10.
  • 11.
  • 12.
  • 13.
  • 14.
  • 15.
    Apparatus for Extinguishmentof Fires: ▪ Automatic Sprinklers: The most widely used apparatus for fire protection in buildings is the automatic sprinkler system. Sprinkler system consists of a network of piping installed at the ceiling or roof and supplied with water from a suitable source. ▪ Standpipes: Hoses supplied with water from standpipes are the usual means of manual application of water to interior building fires. ▪ Chemical Extinguishment: Fires involving some materials may not be readily extinguished with water alone. When such materials may be present in a building, provision should be made for application of appropriate chemicals- o Chemical foam o Air foam (mechanical foam) o High-expansion foam o Carbon dioxide o Halon 1301 o Dry chemical extinguishing agents o Dry powder extinguishing agents 15
  • 16.
  • 17.
  • 18.
  • 19.
    There are twotypes of fire control A. Active control B. Passive control Types of fire control
  • 20.
    A. Active control 1.FireDetection / Fire alarm System : Fire alarm System can be either manual or automatic. 2.Fire extinguishing systems It is obligatory to make provision of fire detection and/or fire extinguishing systems. These systems are described below – Types of fire control
  • 21.
    These are simplestand most reliable fire detection and are commonly used in building. They are also known as temperature detectors. This consists of a hand bell or similar sounding devise emitting distinctive sound when struck. Such devices are installed near all the main exit and passages. This type of system on detection of fire starts sounding alarms or information to the nearest control point. 1. Fire Detection System : The commonly adopted fire extinguishing systems are described below: a) Manual Fire alarm System : b) Automatic alarm System : c) Heat detector : Active control
  • 22.
    When a firestarts before the flame actually surface smoke is generated. These devices are best suited for areas within a building when an anticipated fire would produce a large column of smoke before the temperature of a fire is sufficient to operate heat detectors. d) Smoke detector : Active control
  • 23.
    2. Fire ExtinguishingSystem : The commonly adopted fire extinguishing systems are described below: a) Manual Fire Extinguishing System : Portable fire extinguisher can be of carbon dioxide type, large foam generation type and so on. Depending upon the capacity, the discharge from a fire extinguisher may last 20 to 120 seconds. Sometimes buckets full of water and dry sand are also installed. Active control
  • 24.
    b) Fire Hydrants: Thisconsists in providing a l50mm diameter ring main outside in the ground around the periphery of the building. The ring main is fed from an underground water tank and it is ensured that the water pressure Available at each fire hydrant is of the order of 3.5kg/cm 2 . Active control
  • 25.
    c) Wet riserSystem: 1. 100 to 150 mm dia vertical G.I. Pipes at suitable locations within the building. 2. The risers are fed from underground water storage lank through a fire pump which supplies water at 2.3kg/cm2 at the topmost outlet. 3. The wet risers have suitable connections at each floor from where constant supply of water can be drawn in the event of fire. wet riser system Active control
  • 26.
    sprinkler system BashundharaCity d) Sprinkler system: Pipes are normally 20mm dia The pipes receive supply of water normally 40mm dia. Active control
  • 27.
    Fire Pump: A firepump is a part of a fire sprinkler system's water supply. Active control
  • 28.
    e) Stand pipesystem: In multi- storied building the hose from fire fighting equipment cannot reach the upper floors, therefore a stand pipe system must be designed for such a Structure. stand pipe system Active control
  • 29.
  • 30.
    National building code Corridor: Usershould find exits at every end of the corridor. Closed corridor should not more than 10 m. Passive Control
  • 31.
    Height of thecorridor is minimum 2.4 m. The size of Corridor according to number of users: Maximum walking distance should not more than 23 m. User Width 50 or less than 50 0.9 m More than 50 1.1 m More than 150 1.8 m Passive Control
  • 32.
    Types of Exits Buildingcodes generally indicate what types of facilities may qualify as exits. These usually include: Exit Passageway Exit Doors Stairs Ramps Refuge floors Passive Control
  • 33.
    Exit Passageways Horizontal extensionsof vertical exits, or a passage leading from a yard or court to an outdoor space. Minimum floor ­ to-ceiling height is the same as for corridors. Width should be at least that of the vertical exit. Building codes may require the passageway en­ closures to have a 2-hr fire rating. Passive Control
  • 34.
    Exit Doors doors providingaccess to streets doors to stairs and exit passageways There should be one exit door for every 50 persons. Minimum width of the door is 1 m & height is 2 m. The exit door should be side swinging. The door should be of outer direction if the user number is more than 50. Passive Control
  • 35.
    Detection of Fires: Everyfire-extinguishing activity must start with detection. To assist in this, many types of automatic detectors are available, with a wide range of sensitivity. There are five general types of detectors, each employing a different physical means of operation. The types are designated – • fixed-temperature detectors, • rate-of-rise detectors, • Photoelectric detectors, • combustion-products detectors, and • ultraviolet or infrared detectors. • Detectors.pdf 35
  • 36.
  • 37.
    In addition toproviding means for early detection of fire, preventing its spread, and extinguishing it speedily, building designers should also provide the appropriate number, sizes, and arrangements of exits to permit quick evacuation of occupants if fire or other conditions dangerous to life occur. Building codes generally contain requirements for safe, emergency egress from buildings. Egress Components ‘‘Life Safety Code’’ defines a means of egress composed of three Parts- Exit access—that portion that leads to an entrance to an exit Exit—the portion that is separated from all other building spaces by construction or equipment required to provide a protected path to the exit discharge Exit discharge—the portion that connects the termination of an exit to a public way 37 Emergency Egress:
  • 38.
    Means of egressmay be provided by exterior and interior doors and enclosed horizontal and vertical passageways, including stairs and escalators. Types of Exits: Building codes generally recognize the following as acceptable exits when they meet the codes’ safety requirements: • Corridors • Exit passageways • Exit doors • Horizontal exit • Interior stairs • Exterior stairs • Smokeproof tower • Escalators • Moving walks 38 Emergency Egress:
  • 39.
    Refuge Areas: A refugearea is a space protected against fire and smoke. When located within a building, the refuge should be at about the same level as the areas served and separated from them by construction with at least a 2-hr fire rating. Access to the refuge areas should be protected by fire doors with a fire rating of 1.5 hr or more. Location of Exits: Building codes usually require a building to have at least two means of egress from every floor. Exits should be remote from each other, to reduce the chance that both will be blocked in an emergency. All exit access facilities and exits should be located so as to be clearly visible to building occupants or signs should be installed to indicate the direction of travel to the exits. Signs marking the locations of exits should be illuminated with at least 5 ft-c of light. Floors of means of egress should be illuminated with at least 1 ft-c of artificial light whenever the building is occupied. 39 Emergency Egress:
  • 40.
    Required Exit Capacity: Minimumwidth of a passageway for normal use is 36 in. This is large enough to accommodate one-way travel for persons on crutches or in wheelchairs. For two way travel, a 60-in width is necessary. Building codes, however, may require greater widths to permit rapid passage of the anticipated number of evacuees in emergencies. This number depends on a factor called the occupant load, but the minimum width should be ample for safe, easy passage of handicapped persons. (Occupant load of a building space is the maximum number of persons that may be in the space at any time) Emergency Egress.pdf 40 Emergency Egress:
  • 41.