Automatic Fire Extinguisher system
Saurabh Sarang1, Sanket Kahane2, Manoj Matsagar3,Vaibhav Kokane4,Amol varade5
1234Student,Dept. of Electrical Engineering ,AVCOE Sangamner, Maharastra, India.
5Assistant professor, AVCOE Sangamner, Maharastra, India.
---------------------------------------------------------------------***---------------------------------------------------------------------
1.Abstract –Protecting and preserving an institution's
buildings, collections, operations and occupants. Items
destroyed by fire, however, are gone forever. An uncontrolled
fire can obliterate an entire room's contents within a few
minutes and completely burn out a building in a couple hours.
The first step toward halting a fire is to properly identify the
incident, raise the occupant alarm, andthen notifyemergency
response professionals. This is often the function of the
Automatic fire extinguisher system. Several system types
and options are available, depending on the specific
characteristics of the protected space. Fire protection experts
generally agree that automatic sprinklersrepresentoneofthe
single, most significantaspectsofafiremanagementprogram.
Properly designed, installed, and maintained, these systems
can overcome deficiencies in risk management, building
construction, and emergency response. They may alsoprovide
enhanced flexibility of building designand increasetheoverall
level of fire safety. The following text presents an overview of
fire detection, alarm and sprinkler systems working.
2.INTRODUCTION:
Recent and earlier fire incidents have clearly
demonstrated some of the major Short comings in our
firefighting capabilities along thelengthandbreadthof
the country. The recent fire incident in a hospital in
India has added another dangerous possibility and
dimensions to fire accident. We need to have a serious
look at the capabilities of our fire services in this
context. If the teletherapy machine in the hospital had
been damaged, the incident would have assumed a
completely different tone and escalated into an even
worse tragedy. The Mayapuriincidentinourcountryis
a very recent example of what can happen if a
radiological device gets damaged. We need to examine
whether our fire services have the capability to
respond in a fire incident whenradiologicalequipment
has got damaged. Are the fire services trained and
equipped to respond or even capable to contain and
restrict the dangers till other experts arrive? There is
more than an urgent need to ensure that the fire
services are wellequippedandtrainedtorespondtoall
possible vulnerabilities resulting out of fire accidents.
Fire extinguishers, in one form or another, have
probably postdated fire by only a short time. The more
practical and unitized extinguisher now commonplace
began as a pressurized vessel that spewed forth water,
and later, a combination of liquid elements. The older
extinguishers comprised cylinders containing a
solution of baking soda (sodium bicarbonate) and
water. Inside, a vessel of sulfuricacidwaspositionedat
the top of the body. Thisdesignhadtobeturnedupside
down to be activated, so that the acid spilled into the
sodium bicarbonate solution andreactedchemicallyto
form enough carbon dioxide to pressurize the body
cylinder and drive out the water through a delivery
pipe. This volatile device was improved by placing the
acid in a glass bottle, designed to be broken by
a plunger set on the top of the cylinder body or by a
hammer striking a ring contraption on the side to
release the acid. Cumbersome and sometimes
ineffective, this design also required improvement.[1]
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5074
advantages of fire system mist has been received
considerable attention for fire suppression in recent
years due to many advantages, such as high fire
extinguishingeffectiveness,lesswaterconsumption,no
pollution to environment, safety to protected objects
etc. Considerable numbers of studies and applications
of water mist system in normal altitude areas have
been carried out widely.[2]
Fire protection of historical buildings in high altitude
areas with water mist had also been performed
recently. We studied the applicability and design
optimization of water mist system aiming many
application .Comparisonfiresuppressioneffectiveness
of water mist with conventional fire suppression
technologies, known as carbon dioxide extinguisher
and sprinkler system. Studieshadalsobeenperformed
on spray characterization with the consideration of
ambient pressure effects. We studied the effects of
ambient pressure on spray of an atomization nozzle,
where the ambient pressure was changed.[3]
The effects of working pressure and ambient density
on spray characteristics.[4]
Fire brings great harm to the country's economic and
social stability, the current fire detection and alarm
system use the two bus for connecting Smoke
temperature composite fire detector and central
console. It has anti-interference, high reliability, etc., It
has been widely used in society and played an
important role in Socio-economic, national security.
But it is high cost, design, construction and
maintenance is complex. So people invented the
wireless fire detection and alarm system.[5]
Recently, wireless fire detection and alarm system has
been rapid development. Has Emerge in the wireless
temperature, smoke, smoke temperature composite
fire detection and alarm system.[6]
Sprinkler systemisakindoffixedextinguishingsystem
and has been widely used all over the world. Many
references have carried on deep discussions and
propose their own views on the water distribution
characteristics of sprinkler in sprinkler systems.
According to reference, sprinkling densityisuniformly
distributed in the sprinkling effective coverage area.
[7]
Sprinkling density is a major parameter for fire
controlling capability of the sprinkler system.
Sprinkling distribution characteristics of sprinkler are
studied and analyzed from an experimental
viewpoint.[8]
The NFPA established theTechnicalCommitteeonFire
Pumps in 1899 to create a uniform set of guidelines to
govern the proper installation of fire pumps. The 1993
edition of NFPA 20 included “…significant revisions to
the arrangementofpowersupplytoelectric-drivenfire
pumps. These clarifications were intended to provide
the necessary requirements to make the system as
reliable as possible…”.[9]
effectiveness of a fire-pump system designed and
installed per NFPA 20 to provide protection for a
building or facility. A basic premise governing the
requirements found in NFPA 20 is that single-fault
failures that could result intotalsystemfailuremustbe
minimized. The preface to Pumps for Fire Protection
Systems.[10]
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5075
3.Need:
The need of this project is to increase the safety of
emergency responders and building occupants by
providing information about how firefighters typically
interact with building features and fire protection
systemsduringfiresandsimilaremergencies.Bybetter
understanding the needs of the fire service, designers
and code officials can work together to streamline fire
service emergency operations within the built
environment.
The faster the fire servicecanrespond,enter,locatethe
emergency incident, and safely operate in or near a
building, the sooner they can usually resolve the
incident in a safe manner. This, in turn, will likely
increase the safety of building occupants (workers,
residents, and visitors), reduce property damage, and
limit related indirect losses. Therefore, both building
occupants as well as fire service employees willrealize
the benefits of this document in terms of reasonably
safe working conditions as intended by the
Occupational Safety and Health Act of 1970.
4.Block Diagram:
3. Working
The working of project is mainly depend on
temperature sense by the thermostat. Firstly we have
to set temperature on thermostat according to our
requirement. For The temperature below the set point
system remain in off condition. At the moment when
temperature is goes beyond the set temperature the
system is turn on and sprinklers star spraying the
water or extinguisher medium.
The temperature is sense by the temperature
sensing device (thermostat).then this signal is go
through relay unit.Relayisactasthecontrollingswitch
to turn on and off the centrifugal pump and alarm unit
,then by using centrifugal pump extinguisher medium
is passes through pipewithpressureandthenitspread
or through on fire source.
5.Actul Circuit Diagram:
6.Comparision with existing system:
Sr/no. Automatic fire
extinguisher
Traditional
extinguisher
1. More effective Less effective
2. Automatic system Manual system
3. Less operation time More time for
operation
4. Automatic systemsono
need of man power
Required man
power
5. Required less fire
extinguisher medium
for same intensity of
fire
Required more
fire extinguisher
medium for
same intensity
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5076
7. CONCLUSIONS
Automatic fire extinguishing system with nozzle has
better reliability, portability, cost-effectiveness, a very
simple design, good serviceability and operable at
almost all places. Soon most of the manual fire control
will be replaced by automatic for their swift action in
case of fire and there location at unconventional
positions difficult for human interference. The
government should persuade construction and
manufacturing industries to install such automatic
system, which will save both life and property.
8.REFERENCES
[1]David Wagman,powerplant run on Co2,June-2018.
[2] Torgrim Log, Peter Cannon-Brookes, Water mist
for fire protection of historic buildings and museums,
Museum Management andCuratorship,14(3),pp.283-
298 (1995)
[3] Liao Guangxuan, Huang Xin, Cong Beihua, Qin Jun,
Liu Jianghong, Wang Xishi, Progress in water mist fire
suppression technology, Journal of University of
Science and Technology of China; 36(1), pp. 9-
19.(2006)
[4] Wang Xishi, Liao Guangxuan, Qin Jun and Fan
Weicheng, Experimental study on effectiveness of
extinction of a pool fire with water mist, Journal of Fire
Sciences. 20(4), pp. 279-295. (2002)
[5] Wu Longbiao,Fang Jun,Xie Qiyuan. Fire detection
and information processing[M]. Beijing: Chemical
Industry Press, 2006, 264-265(in Chinese)
[6] Chen nan. Design of Fire Detection and Control
Systems for Intelligent Buildings[M]. Beijing:Tsinghua
University Press, 2001, 7: 19-60(in Chinese)
[7] Deng Ke-yang: The numerical simulation of the
spatial distribution of water spray intensityforZST-15
sprinklers, journal of China water & wastewater,
supplement of Vol.33 (2007) (In Chinese)
[8] XU Xiao-ling, YAO Bin, WANG Han-jie and LI Juan:
Water density
probability distribution and fire control capability of
sprinkler system,
journal of FIRE SAFETY SCIENCE,Vol.18, No.3(2009)
(In Chinese)
[9] Standard for the Installation of Stationary Pumps
for Fire Protection, NFPA
Standard 20, 2007.
[10] K. E. Isman and M. T. Puchovsky, Pumps for Fire
Protection Systems.
Quincy, MA: NFPA, 2002.
BIOGRAPHIES
Mr.Sanket Dnyaneshwar
Kahane.
Appearig in BE Electrical from
AVCOE, Sangamner ,
Maharastra, India.
Mr.Saurabh Suresh Sarang.
Appearig in BE Electrical from
AVCOE, Sangamner ,
Maharastra, India.
Mr.Manoj Shivaji Matsagar.
Appearig in BE Electrical from
AVCOE, Sangamner ,
Maharastra, India.
Mr.Vaibhav Dinkar Kokane.
Appearig in BE Electrical from
AVCOE, Sangamner ,
Maharastra, India.
uthor
Photo
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5077
Mr.Amol Sopan Varade.
Currently working as assistant
professor in AVCOE,
Sangamner , Affiliated to Pune
university, Completed PG in
Electrical Machine And Drives.
And Research Area is electrical
Drives, Solar Design, Safety
Measures from electrical.

More Related Content

What's hot

Building services report
Building services report Building services report
Building services report
Soh Shing
 
Gas Turbine Fire Suppression Introduction
Gas Turbine Fire Suppression IntroductionGas Turbine Fire Suppression Introduction
Gas Turbine Fire Suppression Introduction
kevta
 

What's hot (15)

Guards manual
Guards manualGuards manual
Guards manual
 
Building Services
Building ServicesBuilding Services
Building Services
 
Building services report
Building services report Building services report
Building services report
 
Building services final report
Building services final reportBuilding services final report
Building services final report
 
Building Service, Taylor's University Lakeside Campus //
Building Service, Taylor's University Lakeside Campus // Building Service, Taylor's University Lakeside Campus //
Building Service, Taylor's University Lakeside Campus //
 
BUILDING SERVICES final
BUILDING SERVICES finalBUILDING SERVICES final
BUILDING SERVICES final
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systems
 
Building Services in Public Buildings Report
Building Services in Public Buildings ReportBuilding Services in Public Buildings Report
Building Services in Public Buildings Report
 
Gas Turbine Fire Suppression Introduction
Gas Turbine Fire Suppression IntroductionGas Turbine Fire Suppression Introduction
Gas Turbine Fire Suppression Introduction
 
Fired heater simulation
Fired heater simulationFired heater simulation
Fired heater simulation
 
Building service-final-report
Building service-final-reportBuilding service-final-report
Building service-final-report
 
Bservice report
Bservice reportBservice report
Bservice report
 
36 9143 it smart gas outflow detection and safety edit septian
36 9143 it  smart gas outflow detection and safety edit septian36 9143 it  smart gas outflow detection and safety edit septian
36 9143 it smart gas outflow detection and safety edit septian
 
Bserve report (final)
Bserve report (final)Bserve report (final)
Bserve report (final)
 
Data collection
Data collectionData collection
Data collection
 

Similar to IRJET- Automatic Fire Extinguisher System

Final Year Project on Fire Fighting systems
Final Year Project on Fire Fighting systemsFinal Year Project on Fire Fighting systems
Final Year Project on Fire Fighting systems
Naqash Kazmi
 

Similar to IRJET- Automatic Fire Extinguisher System (20)

REVIEW OF FIRE EXTINGUISH TECHINQUE
REVIEW OF FIRE EXTINGUISH TECHINQUEREVIEW OF FIRE EXTINGUISH TECHINQUE
REVIEW OF FIRE EXTINGUISH TECHINQUE
 
IRJET- Facility Management in Residential Township
IRJET- Facility Management in Residential TownshipIRJET- Facility Management in Residential Township
IRJET- Facility Management in Residential Township
 
Optimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics SimulatorOptimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics Simulator
 
IRJET- Simulation of Sand Bath Heater
IRJET-  	  Simulation of Sand Bath HeaterIRJET-  	  Simulation of Sand Bath Heater
IRJET- Simulation of Sand Bath Heater
 
A Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants SafetyA Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants Safety
 
434 15
434 15434 15
434 15
 
IRJET- Design and Fabrication of “Cavitation Water Heater”
IRJET-  	  Design and Fabrication of “Cavitation Water Heater”IRJET-  	  Design and Fabrication of “Cavitation Water Heater”
IRJET- Design and Fabrication of “Cavitation Water Heater”
 
Nuclear Power Plant Safety
Nuclear Power Plant SafetyNuclear Power Plant Safety
Nuclear Power Plant Safety
 
Case Study of Building Service in Public buildings
Case Study of Building Service in Public buildingsCase Study of Building Service in Public buildings
Case Study of Building Service in Public buildings
 
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
Building Service Case Study Report - Pantai Hospital, Kuala Lumpur (Bangsar)
 
IRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum IndustryIRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum Industry
 
IRJET- A Review on Applications of Shock Wave
IRJET-  	  A Review on Applications of Shock WaveIRJET-  	  A Review on Applications of Shock Wave
IRJET- A Review on Applications of Shock Wave
 
Building Services Case Study
Building Services Case StudyBuilding Services Case Study
Building Services Case Study
 
IRJET- Implementation and Automation of Air Blaster
IRJET- Implementation and Automation of Air BlasterIRJET- Implementation and Automation of Air Blaster
IRJET- Implementation and Automation of Air Blaster
 
Calculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data CenterCalculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data Center
 
IRJET- Design and Analysis of Absorber Tube of Solar Parabolic trough Collector
IRJET- Design and Analysis of Absorber Tube of Solar Parabolic trough CollectorIRJET- Design and Analysis of Absorber Tube of Solar Parabolic trough Collector
IRJET- Design and Analysis of Absorber Tube of Solar Parabolic trough Collector
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
Fire Fighting System project
Fire Fighting System projectFire Fighting System project
Fire Fighting System project
 
Final Year Project on Fire Fighting systems
Final Year Project on Fire Fighting systemsFinal Year Project on Fire Fighting systems
Final Year Project on Fire Fighting systems
 
IRJET- Design &Analysis of Parabolic Trough Collector on Effect on Nano-F...
IRJET-  	  Design &Analysis of Parabolic Trough Collector on Effect on Nano-F...IRJET-  	  Design &Analysis of Parabolic Trough Collector on Effect on Nano-F...
IRJET- Design &Analysis of Parabolic Trough Collector on Effect on Nano-F...
 

More from IRJET Journal

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 

Recently uploaded (20)

Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 

IRJET- Automatic Fire Extinguisher System

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5073 Automatic Fire Extinguisher system Saurabh Sarang1, Sanket Kahane2, Manoj Matsagar3,Vaibhav Kokane4,Amol varade5 1234Student,Dept. of Electrical Engineering ,AVCOE Sangamner, Maharastra, India. 5Assistant professor, AVCOE Sangamner, Maharastra, India. ---------------------------------------------------------------------***--------------------------------------------------------------------- 1.Abstract –Protecting and preserving an institution's buildings, collections, operations and occupants. Items destroyed by fire, however, are gone forever. An uncontrolled fire can obliterate an entire room's contents within a few minutes and completely burn out a building in a couple hours. The first step toward halting a fire is to properly identify the incident, raise the occupant alarm, andthen notifyemergency response professionals. This is often the function of the Automatic fire extinguisher system. Several system types and options are available, depending on the specific characteristics of the protected space. Fire protection experts generally agree that automatic sprinklersrepresentoneofthe single, most significantaspectsofafiremanagementprogram. Properly designed, installed, and maintained, these systems can overcome deficiencies in risk management, building construction, and emergency response. They may alsoprovide enhanced flexibility of building designand increasetheoverall level of fire safety. The following text presents an overview of fire detection, alarm and sprinkler systems working. 2.INTRODUCTION: Recent and earlier fire incidents have clearly demonstrated some of the major Short comings in our firefighting capabilities along thelengthandbreadthof the country. The recent fire incident in a hospital in India has added another dangerous possibility and dimensions to fire accident. We need to have a serious look at the capabilities of our fire services in this context. If the teletherapy machine in the hospital had been damaged, the incident would have assumed a completely different tone and escalated into an even worse tragedy. The Mayapuriincidentinourcountryis a very recent example of what can happen if a radiological device gets damaged. We need to examine whether our fire services have the capability to respond in a fire incident whenradiologicalequipment has got damaged. Are the fire services trained and equipped to respond or even capable to contain and restrict the dangers till other experts arrive? There is more than an urgent need to ensure that the fire services are wellequippedandtrainedtorespondtoall possible vulnerabilities resulting out of fire accidents. Fire extinguishers, in one form or another, have probably postdated fire by only a short time. The more practical and unitized extinguisher now commonplace began as a pressurized vessel that spewed forth water, and later, a combination of liquid elements. The older extinguishers comprised cylinders containing a solution of baking soda (sodium bicarbonate) and water. Inside, a vessel of sulfuricacidwaspositionedat the top of the body. Thisdesignhadtobeturnedupside down to be activated, so that the acid spilled into the sodium bicarbonate solution andreactedchemicallyto form enough carbon dioxide to pressurize the body cylinder and drive out the water through a delivery pipe. This volatile device was improved by placing the acid in a glass bottle, designed to be broken by a plunger set on the top of the cylinder body or by a hammer striking a ring contraption on the side to release the acid. Cumbersome and sometimes ineffective, this design also required improvement.[1]
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5074 advantages of fire system mist has been received considerable attention for fire suppression in recent years due to many advantages, such as high fire extinguishingeffectiveness,lesswaterconsumption,no pollution to environment, safety to protected objects etc. Considerable numbers of studies and applications of water mist system in normal altitude areas have been carried out widely.[2] Fire protection of historical buildings in high altitude areas with water mist had also been performed recently. We studied the applicability and design optimization of water mist system aiming many application .Comparisonfiresuppressioneffectiveness of water mist with conventional fire suppression technologies, known as carbon dioxide extinguisher and sprinkler system. Studieshadalsobeenperformed on spray characterization with the consideration of ambient pressure effects. We studied the effects of ambient pressure on spray of an atomization nozzle, where the ambient pressure was changed.[3] The effects of working pressure and ambient density on spray characteristics.[4] Fire brings great harm to the country's economic and social stability, the current fire detection and alarm system use the two bus for connecting Smoke temperature composite fire detector and central console. It has anti-interference, high reliability, etc., It has been widely used in society and played an important role in Socio-economic, national security. But it is high cost, design, construction and maintenance is complex. So people invented the wireless fire detection and alarm system.[5] Recently, wireless fire detection and alarm system has been rapid development. Has Emerge in the wireless temperature, smoke, smoke temperature composite fire detection and alarm system.[6] Sprinkler systemisakindoffixedextinguishingsystem and has been widely used all over the world. Many references have carried on deep discussions and propose their own views on the water distribution characteristics of sprinkler in sprinkler systems. According to reference, sprinkling densityisuniformly distributed in the sprinkling effective coverage area. [7] Sprinkling density is a major parameter for fire controlling capability of the sprinkler system. Sprinkling distribution characteristics of sprinkler are studied and analyzed from an experimental viewpoint.[8] The NFPA established theTechnicalCommitteeonFire Pumps in 1899 to create a uniform set of guidelines to govern the proper installation of fire pumps. The 1993 edition of NFPA 20 included “…significant revisions to the arrangementofpowersupplytoelectric-drivenfire pumps. These clarifications were intended to provide the necessary requirements to make the system as reliable as possible…”.[9] effectiveness of a fire-pump system designed and installed per NFPA 20 to provide protection for a building or facility. A basic premise governing the requirements found in NFPA 20 is that single-fault failures that could result intotalsystemfailuremustbe minimized. The preface to Pumps for Fire Protection Systems.[10]
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5075 3.Need: The need of this project is to increase the safety of emergency responders and building occupants by providing information about how firefighters typically interact with building features and fire protection systemsduringfiresandsimilaremergencies.Bybetter understanding the needs of the fire service, designers and code officials can work together to streamline fire service emergency operations within the built environment. The faster the fire servicecanrespond,enter,locatethe emergency incident, and safely operate in or near a building, the sooner they can usually resolve the incident in a safe manner. This, in turn, will likely increase the safety of building occupants (workers, residents, and visitors), reduce property damage, and limit related indirect losses. Therefore, both building occupants as well as fire service employees willrealize the benefits of this document in terms of reasonably safe working conditions as intended by the Occupational Safety and Health Act of 1970. 4.Block Diagram: 3. Working The working of project is mainly depend on temperature sense by the thermostat. Firstly we have to set temperature on thermostat according to our requirement. For The temperature below the set point system remain in off condition. At the moment when temperature is goes beyond the set temperature the system is turn on and sprinklers star spraying the water or extinguisher medium. The temperature is sense by the temperature sensing device (thermostat).then this signal is go through relay unit.Relayisactasthecontrollingswitch to turn on and off the centrifugal pump and alarm unit ,then by using centrifugal pump extinguisher medium is passes through pipewithpressureandthenitspread or through on fire source. 5.Actul Circuit Diagram: 6.Comparision with existing system: Sr/no. Automatic fire extinguisher Traditional extinguisher 1. More effective Less effective 2. Automatic system Manual system 3. Less operation time More time for operation 4. Automatic systemsono need of man power Required man power 5. Required less fire extinguisher medium for same intensity of fire Required more fire extinguisher medium for same intensity
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5076 7. CONCLUSIONS Automatic fire extinguishing system with nozzle has better reliability, portability, cost-effectiveness, a very simple design, good serviceability and operable at almost all places. Soon most of the manual fire control will be replaced by automatic for their swift action in case of fire and there location at unconventional positions difficult for human interference. The government should persuade construction and manufacturing industries to install such automatic system, which will save both life and property. 8.REFERENCES [1]David Wagman,powerplant run on Co2,June-2018. [2] Torgrim Log, Peter Cannon-Brookes, Water mist for fire protection of historic buildings and museums, Museum Management andCuratorship,14(3),pp.283- 298 (1995) [3] Liao Guangxuan, Huang Xin, Cong Beihua, Qin Jun, Liu Jianghong, Wang Xishi, Progress in water mist fire suppression technology, Journal of University of Science and Technology of China; 36(1), pp. 9- 19.(2006) [4] Wang Xishi, Liao Guangxuan, Qin Jun and Fan Weicheng, Experimental study on effectiveness of extinction of a pool fire with water mist, Journal of Fire Sciences. 20(4), pp. 279-295. (2002) [5] Wu Longbiao,Fang Jun,Xie Qiyuan. Fire detection and information processing[M]. Beijing: Chemical Industry Press, 2006, 264-265(in Chinese) [6] Chen nan. Design of Fire Detection and Control Systems for Intelligent Buildings[M]. Beijing:Tsinghua University Press, 2001, 7: 19-60(in Chinese) [7] Deng Ke-yang: The numerical simulation of the spatial distribution of water spray intensityforZST-15 sprinklers, journal of China water & wastewater, supplement of Vol.33 (2007) (In Chinese) [8] XU Xiao-ling, YAO Bin, WANG Han-jie and LI Juan: Water density probability distribution and fire control capability of sprinkler system, journal of FIRE SAFETY SCIENCE,Vol.18, No.3(2009) (In Chinese) [9] Standard for the Installation of Stationary Pumps for Fire Protection, NFPA Standard 20, 2007. [10] K. E. Isman and M. T. Puchovsky, Pumps for Fire Protection Systems. Quincy, MA: NFPA, 2002. BIOGRAPHIES Mr.Sanket Dnyaneshwar Kahane. Appearig in BE Electrical from AVCOE, Sangamner , Maharastra, India. Mr.Saurabh Suresh Sarang. Appearig in BE Electrical from AVCOE, Sangamner , Maharastra, India. Mr.Manoj Shivaji Matsagar. Appearig in BE Electrical from AVCOE, Sangamner , Maharastra, India. Mr.Vaibhav Dinkar Kokane. Appearig in BE Electrical from AVCOE, Sangamner , Maharastra, India. uthor Photo
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5077 Mr.Amol Sopan Varade. Currently working as assistant professor in AVCOE, Sangamner , Affiliated to Pune university, Completed PG in Electrical Machine And Drives. And Research Area is electrical Drives, Solar Design, Safety Measures from electrical.