ANALYSIS AND DESIGN OF RESIDENTIAL BUILDING WITH FLOATING
COLUMN
Abdul Azeed1, Beebijahira H Talageri1, Nidith Kumar Shetty1, Sankarshan M.2
1B.E, Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal
2Assistant Professor, Department of Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal,
Karnataka, India.
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract –In the modern era of Construction multi-storied
building with floating column plays a major role in urban
cities of India. These floating columns are used mainly for
satisfying the space requirement in the structure and to get
good architectural view of the building. A residential multi-
storied building consisting of G+6hasbeen chosenforcarrying
out project work. The work was carried out considering
different cases of removal of columnsindifferentpositionsand
in different floors of the building. The above building models
are generated using the software E-TABs 2015 and are
analyzed and designed by using IS 456-2000 guidelines.
Key Words: Floating columns, E-TABs, RCC frames,
Building Analysis, Bending moment, Shear force
1. INTRODUCTION
In the present day, constructions of buildings in urban cities
in India, the main problem arises in the accommodation of
parking areas, reception lobbies etc. To overcome this
problem floating columns cameintoexistenceand nowithas
become an unavoidable feature in most of the multi-storied
buildings from foundation level and transferring the load to
the ground. The term floating column is also a vertical
element which (due to architectural design/sitesituation)at
its lower level (termination level) rests on a beam which is a
horizontal member. The beams transfer theloadtotheother
columns below it. There are many projects in which floating
columns are adopted, especially above the ground floor,
where transfer girders are employed, so that more open
space is available in the groundfloor. Theseopenspaces may
be required for assembly hall or parking purpose. The
transfer girders have to be designed and detailed properly.
The floating column act as a point load on the beam and this
beam transfers the load to the columns below it as far as
analysis is concerned, the column isoftenassumedpinnedat
the base and is therefore taken as a point load on the
transfer beam. The floating column is a vertical member
which rest on a beam and doesn’t have a foundation. But
such column cannot be implemented easily to construct
practically since the true columns below the termination
level are not constructed with careandhencefinallycauseto
failure.
Buildings with floating columns that hang or float on beams
at an intermediate storey and do not go all the way to the
foundation, have discontinuities in the load transfer path.
The floating column is used for the purpose of architectural
view and site situations. It can be analysed by using E-TABs.
The provisions of floating columns can be stated as most of
the buildings in India are covering the maximum possible
area on a plot within the available bylaws.
1.1 Floating Column
The floating column is a vertical member which rest on a
beam but doesn’t transfer theload directly to thefoundation.
The floating column acts asappointloadonthebeamandthis
beam transfers the load to the column below it. The column
may start off on the first or second or any other intermediate
floor while resting on a beam. Usually columns rest on the
foundation to transfer load from slabs and beams. But the
floating column rest on beam. The floating column in a
building as shown in Fig.1
Fig.1. Floating column in Building
In modern times the buildings are becoming complex
particularly the mix use ones. There are different uses on
different floors and hence tofollowitstructuralgridbecomes
difficult as columns on any floor would become a hindrance.
Even in residential buildings when there is a parking on
ground floor or lower stories or huge cantileversaretakento
exploit ambiguities in local bylaws for gaining more free
spaces, the lower floors need column-free spaces for easy
movement of vehicles; while on upper floors which are more
in number of the columns have been designedbasedonroom
layout. They are also frequently used when there are shops
on ground floor and residence on upper floors. Rather than
finding an architectural solution one easily take recourse to
floating columns and remove columns on lower stories,
which is a dangerous proposal.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5250
1.2 TRANSFER BEAM
Transfer beams are required at places where column
locations are changing, and to transfer the forces from
column above to column below.
To design the transfer beams, consider the point loadsatthe
locations where the columns are stopping. This point load
will actually to be equal to the magnitude of the column
reactions. Add the other loads which might act on the beam
(self-weight, live load acting on the beam). Then check for
shear and flexure, similar to a normal beam.
Fig.2. Transfer beam which support Floating Column
2. OBJECTIVES AND SCOPE OF WORK
The objective of the present work is to study the behavior of
multistory buildings with floating columns. The base of the
building frame is assumed to be fixed. Usually all
multistoried buildings are of 3 types they are
 Load bearing construction
 Framed construction
 Composite construction
But among the above 3 types, in the present stage all the
multistoried structure are framed construction which are
durable. An engineering structure is an assemblyofmember
of elements transferringtheloadsandprovidinga firmspace
to serve the desired foundation. The structural design is a
science and art of designing, with economy and elegance, a
durable structure is that which can safely carry the forces
and can serve the desired function satisfactorily during its
expected service life span. The entire process of structural
planning and designing requires not only imagination and
conceptual thinking but of practical aspects,suchasrelevant
design codes and bylaws, backed up by ample experience,
institutions and judgment. Theprocessofdesigncommences
with planning of a structure, primarilytomeetthefunctional
equipment of the user or client. The functional requirements
and the aspects of the aesthetics looked in to normally by an
architect while the aspect of safety, serviceability, durability
and economy of the structure for its intended use over the
life span.
3. METHODOLOGY
With reference to the national building code, plan for the
building is made, and models are made. Analysis and design
is done by using structural software E-TABs 2015. The
design of RCC structural elements are carried out by
considering the minimum dimensions of column, beam and
slab. The dimensions of RCCstructureelementsaredesigned
using MS EXCEL (spread sheet) by considering the various
loads such as Live load, Dead load and Wind load.Thedesign
is carried as per the code i.e., IS 456-2000.
3.1 MODEL FORMULATION
The study is carried out on a building withfloatingcolumns.
The plan layout of the building is shown in the figure. The
building is considered as residential building having G+6.
Height of each storey is kept same as other prevalent data.
3.2 REASERACH SIGNIFICANCE
In urban areas, multi storey buildings are constructed by
providing floating column for the various purposes which
are stated above. These floating column buildings are not
designated for earthquake loads. So these buildings are not
designed for earthquake loads. So these buildingsareunsafe
in seismic prone areas. The project aimstocreateawareness
about these issues in earthquake resistant design of multi-
storey buildings.
3.3 LIMIT STATE METHOD
In the limit state design method, non-deterministic
parameters are determined based on observations taken
over a period of time. The objective of design based on the
limit state concept is to achieve an acceptable probability
that a structure will not become unserviceable initslifetime
for the use for which it is intended, that is, it will not reach a
limit state. A structurewithappropriatedegreesofreliability
should be able to withstand safely all loads that are liable to
act on it throughout its life and it should also satisfy the
serviceability requirements such aslimitationsondeflection
and cracking. It should also be able to maintain the required
structural integrity during and after accidents such as fires,
explosions and local failure. Due to its realistic approach,
limit state method is used in design of structures. The most
important limit states which must be examinedindesign are
as follows:
3.3.1 LIMIT STATE OF COLLAPSE
This state corresponds to the maximum load carrying
capacity; violation of collapse limit state implies failure in
the sense that a clearly defined limit state of structural
usefulness has been exceeded. However, it does not mean a
complete collapse. Thus limit state may correspond to:
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5251
 Flexure
 Compression
 Shear
 Torsion
3.3.2 LIMIT STATE OF SERVICEABILITY
This state corresponds to development of excessive
deformation and is used for checking members in which
magnitude of deformations maylimittheuseofthestructure
or it is components. This limit state may correspond to:
 Deflection
 Cracking
 Vibration
3.4 MODELING OF BUILDING
The residential building (G+6) with floating columns were
selected for the study. The building is considered to be
located in Zone III (Bhatkal) as per IS 1893-2002.
The building is modeled using the structural software E-
TABs 2015. The analytical models of the building include all
the component that influence the mass, strength, stiffness
and durability of structure. The building structural system
consists of beam, column, floating column, slab, grid slab,
foundation, shear wall and staircase.
Fig.3. Typical floor plan
Fig.4. 3D Model of the Building
3.4.1 DESCRIPTION OF THE BUILDING
 Floor area = 521 m2
 Number of floor = G+6
 Number of flat in each floor = 4
 Number of rooms in each flat = 3
 Floor to floor height = 3.6m
 Number of staircase = 1
 Number of lifts = 1
 Types of footing = Isolated footing
 Party hall & Gym at top floor
Table – 1: Structural element with Properties
RCC Member Properties
Grade of
Concrete
Size in mm
Columns
M30 230X600
230X750
230X900
Beams
M30 230X450
230X600
230X750
Slab M30 125
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5252
3.5 TYPES OF LOADS
Various types of loads on a structures and requiring in
consideration in design are,
 Dead load
 Live load
 Wind load
3.6 LIST OF ISCODEUSEDINANALYSISANDDESIGN
 IS 456-2000 Plain and Reinforced concrete
 IS-SP-16:1980 for R.C Column Design
 IS 875-1987 Part-I for Dead Load
 IS 875-1987 Part-II for Live Load
 IS 875-1987 Part-III for Wind Load
3.7 LOAD COMBINATION
A load combination results when more than one load type
acts on the structure. Building codesusuallyspecifya variety
of load combinations together with load factors(weightings)
for each load type in order to ensure the safety of the
structure under different maximum expected loading
scenarios.
Load combinations used in the design are,
 1.5(DL+LL)
 1.2(DL+LL+WL)
4. ANALYSIS & DESIGN
The project requires the analysis of the building in order to
find out the magnitude of loadsandtheirdistribution.Hence,
the software has been used for the analysis was E-TABs
2015. The building was modeled with all the structural
element and floating column. The various loads that would
act on the structure were defined along with the properties
of the structural elements. The analysis was carried out and
the loads and the moments were determined. After which
the structural elements are designed manually and have
been checked for safety.
5. RESULTS & DISCUSSION
5.1 BENDING MOMENT
The BMD of beams for the G+6 storied frame structure is as
shown in the Fig.6. It is observed that the bendingmomentis
greater at mid span of each beam and reduces linearly as it
proceeds towards the support of the beam span.
Fig.5. Bending Moment
5.2 SHEAR FORCE
The SFD for the desired multi storied structure is as
shown in Fig.6. It is observed that the shear force is
greater towards the end portions of the beams that is
towards the joint pertaining a beam andcolumn.Shear
force may also occur in a beam to beam junction.
Fig.6. Shear Force
5.3 FOOTING REACTIONS
The below fig.7.shows the vertical load along the
column of the structure to the base of the footing.
These footing loads are used to determine the type of
footings corresponding to the soil condition and
seismology. These column loads are grouped and used
to design a combined footing.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5253
Fig.7. Reactions & Moment for Footing
5.4 ESTIMATION OF THE PROJECT
Table – 2: Plinth Area Rate
Total cost of the
project(INR)
Area of the
building
In Sq.ft.
Plinth area
rate per Sq.ft
7,15,50,000 5608 1823
6. CONCLUSIONS
Based on the test result, the following conclusions were
made:
 Building provided with the floating column shows
more storey drift & storeydisplacementascompare
to building without floating column.
 The optimum position to provide floating columnis
at 1st floor alternatively so that moment, shear &
steel requirement of the whole building can be
minimized.
 Hence provide the floating column is advantageous
in providing good floor space index but risky &
vulnerability of the building increases.
 The use of floating column in modern building are
increasing vastly
REFERENCES
[1] Badgire Udhav S and Shaikh A.N, “Analysis of
Multistorey Building with Floating Column”,Volumeno.
4, Issue No. 9, 01 Sept. 2015, pp: 475-478.
[2] Sasidhar T and P. Sai Avinash, “Analysis of Multistoried
Building with and without Floating Column Using E-
TABs”, Volume 8, Issue 6, June 2017, pp:91-98.
[3] Shivam Tyagi and B.S. Tyagi, “Seismic Analysis of
Multistorey Building with Floating Column”, Volume 5,
Issue No. 5, May 2018.
[4] MD Najeeb Ur Rahman and B Rajkumar Singh, “Analysis
of Multi-storey Building with Floating Column”, Volume
6, Issue No. 01, January-June 2018.
[5] P. Pavan Kumar and D. Thrimurthi Naik, “Design and
Analysis of Residential Building with Floating Columns
By Considering Footing Design”, Volume 2, Issue No. 6,
June 2017.
[6] Bureau of Indian Standards: IS-875, Part I (1987), Dead
Loads on Buildings and Structures, New Delhi, India.
[7] Bureau of Indian Standards: IS-875, Part II (1987), Live
Loads on Buildings and Structures, New Delhi, India.
[8] Bureau of Indian Standards: IS-875, Part III (1987),
Wind Loads on Buildings and Structures, New Delhi,
India.
[9] IS 456-2000 Plain and Reinforced Concrete code
BIOGRAPHIES
ABDUL AZEED
Student, B.E, Department of Civil
Engineering,
Anjuman Institute of Technology
and Management, Bhatkal
BEEBIJAHIRA H TALAGERI
Student, B.E, Department of Civil
Engineering,
Anjuman Institute of Technology
and Management, Bhatkal
NIDITH KUMAR SHETTY
Student, B.E, Department of Civil
Engineering,
Anjuman Institute of Technology
and Management, Bhatkal

More Related Content

What's hot

analysis of high rise building
analysis of high rise buildinganalysis of high rise building
analysis of high rise buildingishant_kukreja
 
Use of flat slabs in multi storey commercial building situated in high seismi...
Use of flat slabs in multi storey commercial building situated in high seismi...Use of flat slabs in multi storey commercial building situated in high seismi...
Use of flat slabs in multi storey commercial building situated in high seismi...eSAT Publishing House
 
IRJET- Performance of Multi-Story RCC Structure with Floating Column
IRJET-  	  Performance of Multi-Story RCC Structure with Floating ColumnIRJET-  	  Performance of Multi-Story RCC Structure with Floating Column
IRJET- Performance of Multi-Story RCC Structure with Floating ColumnIRJET Journal
 
Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...
 Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب... Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...
Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...Dr.Youssef Hammida
 
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADS
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADSRESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADS
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADSIjripublishers Ijri
 
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...IJSRD
 
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...IRJET Journal
 
Drift analysis and Comparison due to rigid frame structure
Drift analysis and Comparison due to rigid frame structureDrift analysis and Comparison due to rigid frame structure
Drift analysis and Comparison due to rigid frame structureFarok Ahmed
 
Behavioural studies of floating column on framed structure
Behavioural studies of floating column on framed structureBehavioural studies of floating column on framed structure
Behavioural studies of floating column on framed structureeSAT Journals
 
Design of Multi-storey car parking
Design of Multi-storey car parkingDesign of Multi-storey car parking
Design of Multi-storey car parkingManoj Navneeth
 
IRJET-Lateral Stability of High Rise Steel Buildings using E TABS
IRJET-Lateral Stability of High Rise Steel Buildings using E TABSIRJET-Lateral Stability of High Rise Steel Buildings using E TABS
IRJET-Lateral Stability of High Rise Steel Buildings using E TABSIRJET Journal
 
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...Malavika Chakravarthy
 
Analysis and design of multi-storey building using staad.Pro
Analysis and design of multi-storey building using staad.ProAnalysis and design of multi-storey building using staad.Pro
Analysis and design of multi-storey building using staad.Progsharda123
 
IRJET- Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...
IRJET-  	  Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...IRJET-  	  Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...
IRJET- Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...IRJET Journal
 
2012 ctbuh outrigger_guide_preview
2012 ctbuh outrigger_guide_preview2012 ctbuh outrigger_guide_preview
2012 ctbuh outrigger_guide_previewSyed Raziuddin
 
IRJET- Study on Cable Stayed Bridge using Csibridge Software
IRJET- Study on Cable Stayed Bridge using Csibridge SoftwareIRJET- Study on Cable Stayed Bridge using Csibridge Software
IRJET- Study on Cable Stayed Bridge using Csibridge SoftwareIRJET Journal
 
Virtual Outriggers in Tall Buildings
Virtual Outriggers in Tall BuildingsVirtual Outriggers in Tall Buildings
Virtual Outriggers in Tall BuildingsAndrew J Horton
 

What's hot (20)

Basic design criteria for high rise buildings
Basic design criteria for high rise buildings Basic design criteria for high rise buildings
Basic design criteria for high rise buildings
 
analysis of high rise building
analysis of high rise buildinganalysis of high rise building
analysis of high rise building
 
Use of flat slabs in multi storey commercial building situated in high seismi...
Use of flat slabs in multi storey commercial building situated in high seismi...Use of flat slabs in multi storey commercial building situated in high seismi...
Use of flat slabs in multi storey commercial building situated in high seismi...
 
IRJET- Performance of Multi-Story RCC Structure with Floating Column
IRJET-  	  Performance of Multi-Story RCC Structure with Floating ColumnIRJET-  	  Performance of Multi-Story RCC Structure with Floating Column
IRJET- Performance of Multi-Story RCC Structure with Floating Column
 
Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...
 Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب... Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...
Transfer Slabs Beams Design Tall Building- تصميم بلا طات وجوائز التحويل الأب...
 
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADS
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADSRESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADS
RESPONSE OF LATERAL SYSTEM IN HIGH RISE BUILDING UNDER SEISMIC LOADS
 
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...
Study on Effect of Wind Load and Earthquake Load on Multi-storey RC Framed Bu...
 
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...
IRJET - A Review of Seismic Analysis of Circular Shape RC Building by using S...
 
Ijciet 08 02_040
Ijciet 08 02_040Ijciet 08 02_040
Ijciet 08 02_040
 
Drift analysis and Comparison due to rigid frame structure
Drift analysis and Comparison due to rigid frame structureDrift analysis and Comparison due to rigid frame structure
Drift analysis and Comparison due to rigid frame structure
 
Behavioural studies of floating column on framed structure
Behavioural studies of floating column on framed structureBehavioural studies of floating column on framed structure
Behavioural studies of floating column on framed structure
 
Design of Multi-storey car parking
Design of Multi-storey car parkingDesign of Multi-storey car parking
Design of Multi-storey car parking
 
IRJET-Lateral Stability of High Rise Steel Buildings using E TABS
IRJET-Lateral Stability of High Rise Steel Buildings using E TABSIRJET-Lateral Stability of High Rise Steel Buildings using E TABS
IRJET-Lateral Stability of High Rise Steel Buildings using E TABS
 
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...
Seismic Design for Floating Column multi- storeyed Building by P.G.Malavika C...
 
Analysis and design of multi-storey building using staad.Pro
Analysis and design of multi-storey building using staad.ProAnalysis and design of multi-storey building using staad.Pro
Analysis and design of multi-storey building using staad.Pro
 
IRJET- Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...
IRJET-  	  Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...IRJET-  	  Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...
IRJET- Dynamic Wind Analysis of RC Bundled Tube in Tube Structure using E...
 
2012 ctbuh outrigger_guide_preview
2012 ctbuh outrigger_guide_preview2012 ctbuh outrigger_guide_preview
2012 ctbuh outrigger_guide_preview
 
Abhijit kumar
Abhijit kumarAbhijit kumar
Abhijit kumar
 
IRJET- Study on Cable Stayed Bridge using Csibridge Software
IRJET- Study on Cable Stayed Bridge using Csibridge SoftwareIRJET- Study on Cable Stayed Bridge using Csibridge Software
IRJET- Study on Cable Stayed Bridge using Csibridge Software
 
Virtual Outriggers in Tall Buildings
Virtual Outriggers in Tall BuildingsVirtual Outriggers in Tall Buildings
Virtual Outriggers in Tall Buildings
 

Similar to IRJET- Analysis and Design of Residential Building with Floating Column

IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET Journal
 
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...IRJET Journal
 
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...IRJET Journal
 
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer Beam
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer BeamIRJET - A Review on Seismic Behaviour of Floating Column and Transfer Beam
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer BeamIRJET Journal
 
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET Journal
 
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...IRJET Journal
 
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating ColumnsA Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columnsijtsrd
 
IRJET- A Performance Study of High Raise Building with Flat Slab System u...
IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...
IRJET- A Performance Study of High Raise Building with Flat Slab System u...IRJET Journal
 
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET Journal
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET Journal
 
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONS
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONSBEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONS
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONSIRJET Journal
 
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...IRJET Journal
 
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...IRJET Journal
 
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...ijtsrd
 
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...IRJET Journal
 
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET Journal
 
IRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET Journal
 
IRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET Journal
 
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using EtabsIRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using EtabsIRJET Journal
 

Similar to IRJET- Analysis and Design of Residential Building with Floating Column (20)

IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
IRJET- Seismic Analysis of Multistorey Buildings with Vertical Irregularities...
 
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
IRJET- A Review on Seismic Analysis and Sustainability of Multi Storey Struct...
 
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
Optimization of Circular RC Frame Structure by Using Shear Wall at a Differen...
 
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer Beam
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer BeamIRJET - A Review on Seismic Behaviour of Floating Column and Transfer Beam
IRJET - A Review on Seismic Behaviour of Floating Column and Transfer Beam
 
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
IRJET- Seismic Analysis of a RC Multi Storey Building with and without Floati...
 
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...IRJET-  	  Seismic Analysis of Multistory Building with Floating Column : A R...
IRJET- Seismic Analysis of Multistory Building with Floating Column : A R...
 
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating ColumnsA Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
A Review on Analysis of a Tall Structure with Shear Panel and Floating Columns
 
floating coloumn.pptx
floating coloumn.pptxfloating coloumn.pptx
floating coloumn.pptx
 
IRJET- A Performance Study of High Raise Building with Flat Slab System u...
IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...IRJET-  	  A Performance Study of High Raise Building with Flat Slab System u...
IRJET- A Performance Study of High Raise Building with Flat Slab System u...
 
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
IRJET- Seismic Analysis of Multi-Storey Building with and without Floating Co...
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
 
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONS
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONSBEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONS
BEHAVIOUR OF G+10 BUILDING WITH SHEAR-WALLS AT DIFFERENT POSITIONS
 
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
COMPARATIVE SEISMIC ANALYSIS OF A MULTI-STOREY RCC STRUCTURE WITH & WITHOUT F...
 
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...
IRJET- Result Analysis of Multistorey Building by using Response Spectrum Met...
 
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
An Analysis of a Tall Structure with Shear Panel and floating Columns in Seis...
 
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...
PARAMETRIC OPTIMIZATION OF MOBILE TOWER BY VARYING LOADING CONDITIONS WITH DI...
 
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET-  	  Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
 
IRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different LevelsIRJET- Performance of Framed Building with Soft Storey at Different Levels
IRJET- Performance of Framed Building with Soft Storey at Different Levels
 
IRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise BuildingIRJET - Review on Behavior of Outrigger System in High Rise Building
IRJET - Review on Behavior of Outrigger System in High Rise Building
 
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using EtabsIRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTUREIRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsIRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASIRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProIRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemIRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesIRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web applicationIRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignIRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 

Recently uploaded (20)

chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 

IRJET- Analysis and Design of Residential Building with Floating Column

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5249 ANALYSIS AND DESIGN OF RESIDENTIAL BUILDING WITH FLOATING COLUMN Abdul Azeed1, Beebijahira H Talageri1, Nidith Kumar Shetty1, Sankarshan M.2 1B.E, Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal 2Assistant Professor, Department of Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal, Karnataka, India. ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract –In the modern era of Construction multi-storied building with floating column plays a major role in urban cities of India. These floating columns are used mainly for satisfying the space requirement in the structure and to get good architectural view of the building. A residential multi- storied building consisting of G+6hasbeen chosenforcarrying out project work. The work was carried out considering different cases of removal of columnsindifferentpositionsand in different floors of the building. The above building models are generated using the software E-TABs 2015 and are analyzed and designed by using IS 456-2000 guidelines. Key Words: Floating columns, E-TABs, RCC frames, Building Analysis, Bending moment, Shear force 1. INTRODUCTION In the present day, constructions of buildings in urban cities in India, the main problem arises in the accommodation of parking areas, reception lobbies etc. To overcome this problem floating columns cameintoexistenceand nowithas become an unavoidable feature in most of the multi-storied buildings from foundation level and transferring the load to the ground. The term floating column is also a vertical element which (due to architectural design/sitesituation)at its lower level (termination level) rests on a beam which is a horizontal member. The beams transfer theloadtotheother columns below it. There are many projects in which floating columns are adopted, especially above the ground floor, where transfer girders are employed, so that more open space is available in the groundfloor. Theseopenspaces may be required for assembly hall or parking purpose. The transfer girders have to be designed and detailed properly. The floating column act as a point load on the beam and this beam transfers the load to the columns below it as far as analysis is concerned, the column isoftenassumedpinnedat the base and is therefore taken as a point load on the transfer beam. The floating column is a vertical member which rest on a beam and doesn’t have a foundation. But such column cannot be implemented easily to construct practically since the true columns below the termination level are not constructed with careandhencefinallycauseto failure. Buildings with floating columns that hang or float on beams at an intermediate storey and do not go all the way to the foundation, have discontinuities in the load transfer path. The floating column is used for the purpose of architectural view and site situations. It can be analysed by using E-TABs. The provisions of floating columns can be stated as most of the buildings in India are covering the maximum possible area on a plot within the available bylaws. 1.1 Floating Column The floating column is a vertical member which rest on a beam but doesn’t transfer theload directly to thefoundation. The floating column acts asappointloadonthebeamandthis beam transfers the load to the column below it. The column may start off on the first or second or any other intermediate floor while resting on a beam. Usually columns rest on the foundation to transfer load from slabs and beams. But the floating column rest on beam. The floating column in a building as shown in Fig.1 Fig.1. Floating column in Building In modern times the buildings are becoming complex particularly the mix use ones. There are different uses on different floors and hence tofollowitstructuralgridbecomes difficult as columns on any floor would become a hindrance. Even in residential buildings when there is a parking on ground floor or lower stories or huge cantileversaretakento exploit ambiguities in local bylaws for gaining more free spaces, the lower floors need column-free spaces for easy movement of vehicles; while on upper floors which are more in number of the columns have been designedbasedonroom layout. They are also frequently used when there are shops on ground floor and residence on upper floors. Rather than finding an architectural solution one easily take recourse to floating columns and remove columns on lower stories, which is a dangerous proposal.
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5250 1.2 TRANSFER BEAM Transfer beams are required at places where column locations are changing, and to transfer the forces from column above to column below. To design the transfer beams, consider the point loadsatthe locations where the columns are stopping. This point load will actually to be equal to the magnitude of the column reactions. Add the other loads which might act on the beam (self-weight, live load acting on the beam). Then check for shear and flexure, similar to a normal beam. Fig.2. Transfer beam which support Floating Column 2. OBJECTIVES AND SCOPE OF WORK The objective of the present work is to study the behavior of multistory buildings with floating columns. The base of the building frame is assumed to be fixed. Usually all multistoried buildings are of 3 types they are  Load bearing construction  Framed construction  Composite construction But among the above 3 types, in the present stage all the multistoried structure are framed construction which are durable. An engineering structure is an assemblyofmember of elements transferringtheloadsandprovidinga firmspace to serve the desired foundation. The structural design is a science and art of designing, with economy and elegance, a durable structure is that which can safely carry the forces and can serve the desired function satisfactorily during its expected service life span. The entire process of structural planning and designing requires not only imagination and conceptual thinking but of practical aspects,suchasrelevant design codes and bylaws, backed up by ample experience, institutions and judgment. Theprocessofdesigncommences with planning of a structure, primarilytomeetthefunctional equipment of the user or client. The functional requirements and the aspects of the aesthetics looked in to normally by an architect while the aspect of safety, serviceability, durability and economy of the structure for its intended use over the life span. 3. METHODOLOGY With reference to the national building code, plan for the building is made, and models are made. Analysis and design is done by using structural software E-TABs 2015. The design of RCC structural elements are carried out by considering the minimum dimensions of column, beam and slab. The dimensions of RCCstructureelementsaredesigned using MS EXCEL (spread sheet) by considering the various loads such as Live load, Dead load and Wind load.Thedesign is carried as per the code i.e., IS 456-2000. 3.1 MODEL FORMULATION The study is carried out on a building withfloatingcolumns. The plan layout of the building is shown in the figure. The building is considered as residential building having G+6. Height of each storey is kept same as other prevalent data. 3.2 REASERACH SIGNIFICANCE In urban areas, multi storey buildings are constructed by providing floating column for the various purposes which are stated above. These floating column buildings are not designated for earthquake loads. So these buildings are not designed for earthquake loads. So these buildingsareunsafe in seismic prone areas. The project aimstocreateawareness about these issues in earthquake resistant design of multi- storey buildings. 3.3 LIMIT STATE METHOD In the limit state design method, non-deterministic parameters are determined based on observations taken over a period of time. The objective of design based on the limit state concept is to achieve an acceptable probability that a structure will not become unserviceable initslifetime for the use for which it is intended, that is, it will not reach a limit state. A structurewithappropriatedegreesofreliability should be able to withstand safely all loads that are liable to act on it throughout its life and it should also satisfy the serviceability requirements such aslimitationsondeflection and cracking. It should also be able to maintain the required structural integrity during and after accidents such as fires, explosions and local failure. Due to its realistic approach, limit state method is used in design of structures. The most important limit states which must be examinedindesign are as follows: 3.3.1 LIMIT STATE OF COLLAPSE This state corresponds to the maximum load carrying capacity; violation of collapse limit state implies failure in the sense that a clearly defined limit state of structural usefulness has been exceeded. However, it does not mean a complete collapse. Thus limit state may correspond to:
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5251  Flexure  Compression  Shear  Torsion 3.3.2 LIMIT STATE OF SERVICEABILITY This state corresponds to development of excessive deformation and is used for checking members in which magnitude of deformations maylimittheuseofthestructure or it is components. This limit state may correspond to:  Deflection  Cracking  Vibration 3.4 MODELING OF BUILDING The residential building (G+6) with floating columns were selected for the study. The building is considered to be located in Zone III (Bhatkal) as per IS 1893-2002. The building is modeled using the structural software E- TABs 2015. The analytical models of the building include all the component that influence the mass, strength, stiffness and durability of structure. The building structural system consists of beam, column, floating column, slab, grid slab, foundation, shear wall and staircase. Fig.3. Typical floor plan Fig.4. 3D Model of the Building 3.4.1 DESCRIPTION OF THE BUILDING  Floor area = 521 m2  Number of floor = G+6  Number of flat in each floor = 4  Number of rooms in each flat = 3  Floor to floor height = 3.6m  Number of staircase = 1  Number of lifts = 1  Types of footing = Isolated footing  Party hall & Gym at top floor Table – 1: Structural element with Properties RCC Member Properties Grade of Concrete Size in mm Columns M30 230X600 230X750 230X900 Beams M30 230X450 230X600 230X750 Slab M30 125
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5252 3.5 TYPES OF LOADS Various types of loads on a structures and requiring in consideration in design are,  Dead load  Live load  Wind load 3.6 LIST OF ISCODEUSEDINANALYSISANDDESIGN  IS 456-2000 Plain and Reinforced concrete  IS-SP-16:1980 for R.C Column Design  IS 875-1987 Part-I for Dead Load  IS 875-1987 Part-II for Live Load  IS 875-1987 Part-III for Wind Load 3.7 LOAD COMBINATION A load combination results when more than one load type acts on the structure. Building codesusuallyspecifya variety of load combinations together with load factors(weightings) for each load type in order to ensure the safety of the structure under different maximum expected loading scenarios. Load combinations used in the design are,  1.5(DL+LL)  1.2(DL+LL+WL) 4. ANALYSIS & DESIGN The project requires the analysis of the building in order to find out the magnitude of loadsandtheirdistribution.Hence, the software has been used for the analysis was E-TABs 2015. The building was modeled with all the structural element and floating column. The various loads that would act on the structure were defined along with the properties of the structural elements. The analysis was carried out and the loads and the moments were determined. After which the structural elements are designed manually and have been checked for safety. 5. RESULTS & DISCUSSION 5.1 BENDING MOMENT The BMD of beams for the G+6 storied frame structure is as shown in the Fig.6. It is observed that the bendingmomentis greater at mid span of each beam and reduces linearly as it proceeds towards the support of the beam span. Fig.5. Bending Moment 5.2 SHEAR FORCE The SFD for the desired multi storied structure is as shown in Fig.6. It is observed that the shear force is greater towards the end portions of the beams that is towards the joint pertaining a beam andcolumn.Shear force may also occur in a beam to beam junction. Fig.6. Shear Force 5.3 FOOTING REACTIONS The below fig.7.shows the vertical load along the column of the structure to the base of the footing. These footing loads are used to determine the type of footings corresponding to the soil condition and seismology. These column loads are grouped and used to design a combined footing.
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 05 | May 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 5253 Fig.7. Reactions & Moment for Footing 5.4 ESTIMATION OF THE PROJECT Table – 2: Plinth Area Rate Total cost of the project(INR) Area of the building In Sq.ft. Plinth area rate per Sq.ft 7,15,50,000 5608 1823 6. CONCLUSIONS Based on the test result, the following conclusions were made:  Building provided with the floating column shows more storey drift & storeydisplacementascompare to building without floating column.  The optimum position to provide floating columnis at 1st floor alternatively so that moment, shear & steel requirement of the whole building can be minimized.  Hence provide the floating column is advantageous in providing good floor space index but risky & vulnerability of the building increases.  The use of floating column in modern building are increasing vastly REFERENCES [1] Badgire Udhav S and Shaikh A.N, “Analysis of Multistorey Building with Floating Column”,Volumeno. 4, Issue No. 9, 01 Sept. 2015, pp: 475-478. [2] Sasidhar T and P. Sai Avinash, “Analysis of Multistoried Building with and without Floating Column Using E- TABs”, Volume 8, Issue 6, June 2017, pp:91-98. [3] Shivam Tyagi and B.S. Tyagi, “Seismic Analysis of Multistorey Building with Floating Column”, Volume 5, Issue No. 5, May 2018. [4] MD Najeeb Ur Rahman and B Rajkumar Singh, “Analysis of Multi-storey Building with Floating Column”, Volume 6, Issue No. 01, January-June 2018. [5] P. Pavan Kumar and D. Thrimurthi Naik, “Design and Analysis of Residential Building with Floating Columns By Considering Footing Design”, Volume 2, Issue No. 6, June 2017. [6] Bureau of Indian Standards: IS-875, Part I (1987), Dead Loads on Buildings and Structures, New Delhi, India. [7] Bureau of Indian Standards: IS-875, Part II (1987), Live Loads on Buildings and Structures, New Delhi, India. [8] Bureau of Indian Standards: IS-875, Part III (1987), Wind Loads on Buildings and Structures, New Delhi, India. [9] IS 456-2000 Plain and Reinforced Concrete code BIOGRAPHIES ABDUL AZEED Student, B.E, Department of Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal BEEBIJAHIRA H TALAGERI Student, B.E, Department of Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal NIDITH KUMAR SHETTY Student, B.E, Department of Civil Engineering, Anjuman Institute of Technology and Management, Bhatkal