EE 369
POWER SYSTEM ANALYSIS
Lecture 12
Power Flow
Tom Overbye and Ross Baldick
1
Announcements
• Homework 9 is: 3.47, 3.49, 3.53, 3.57, 3.61, 6.2, 6.9,
6.13, 6.14, 6.18, 6.19, 6.20; due November 7. (Use
infinity norm and epsilon = 0.01 for any problems
where norm or stopping criterion not specified.)
• Read Chapter 12, concentrating on sections 12.4
and 12.5.
• Homework 10 is 6.23, 6,25, 6.26, 6.28, 6.29, 6.30
(see figure 6.18 and table 6.9 for system), 6.31,
6.38, 6.42, 6.46, 6.52, 6.54; due November 14.
• Homework 11 is 6.43, 6.48, 6.59, 6.61, 12.19, 12.22,
12.20, 12.24, 12.26, 12.28, 12.29; due Nov. 21. 2
Power System Planning
Source: Midwest ISO MTEP08 Report 3
MISO Generation Queue
Source: Midwest ISO MTEP08 Report 4
MISO Conceptual EHV Overlay
Black lines are DC, blue lines are 765kV, red are 500 kV
Source: Midwest ISO MTEP08 Report 5
ERCOT
Also has considerable wind and
expecting considerable more!
“Competitive Renewable Energy
Zones” study identified most
promising wind sites,
Building around $5 billion (original
estimate, now closer to $7 billion) of
transmission to support an additional
11 GW of wind.
Will be completed in 2014. 6
CREZ Transmission Lines
7
NR Application to Power Flow
*
* * *
1 1
We first need to rewrite complex power equations
as equations with real coefficients (we've seen this earlier):
These can be derived by defining
n n
i i i i ik k i ik k
k k
ik ik ik
i
S V I V Y V V Y V
Y G jB
V
 
 
   
 

 
Recall e cos sin
ij
i i i
ik i k
j
V e V
j



  
 
 

 
8
Real Power Balance Equations
* *
1 1
1
1
1
( )
(cos sin )( )
Resolving into the real and imaginary parts:
( cos sin )
( sin cos
ik
n n
j
i i i i ik k i k ik ik
k k
n
i k ik ik ik ik
k
n
i i k ik ik ik ik Gi Di
k
n
i i k ik ik ik
k
S P jQ V Y V V V e G jB
V V j G jB
P V V G B P P
Q V V G B

 
 
 
 



    
  
   
 
 


 )ik Gi DiQ Q 
9
Newton-Raphson Power Flow
In the Newton-Raphson power flow we use Newton's
method to determine the voltage magnitude and angle at
each bus in the power system that satisfies power balance.
We need to solve the power balance equ
1
1
ations:
( cos sin ) 0
( sin cos ) 0
n
i k ik ik ik ik Gi Di
k
n
i k ik ik ik ik Gi Di
k
V V G B P P
V V G B Q Q
 
 


   
   


10
Power Flow Variables
1
1
For convenience, write:
( ) ( cos sin )
( ) ( sin cos )
The power balance equations are then:
( ) 0
( ) 0
n
i i k ik ik ik ik
k
n
i i k ik ik ik ik
k
i Gi Di
i Gi Di
P V V G B
Q V V G B
P P P
Q Q Q
 
 


 
 
  
  


x
x
x
x
11
Power Flow Variables
2
n
2
Assume the slack bus is the first bus (with a fixed
voltage angle/magnitude). We then need to determine
the voltage angle/magnitude at the other buses.
We must solve ( ) , where:
n
V
V









f x 0
x
2 2 2
2 2 2
( )
( )
( )
( )
( )
G D
n Gn Dn
G D
n Gn Dn
P P P
P P P
Q Q Q
Q Q Q
   
  
  
   
    
   
   
     
x
x
f x
x
x
12
N-R Power Flow Solution
(0)
( )
( 1) ( ) ( ) 1 ( )
The power flow is solved using the same procedure
discussed previously for general equations:
For 0; make an initial guess of ,
While ( ) Do
[ ( )] ( )
1
End
v
v v v v
v
v v

 


 
 
x x
f x
x x J x f x
13
Power Flow Jacobian Matrix
1 1 1
1 2 2 2
2 2 2
1 2 2 2
2 2 2 2 2 2
1 2
The most difficult part of the algorithm is determining
and factorizing the Jacobian matrix, ( )
( ) ( ) ( )
( ) ( ) ( )
( )
( ) ( )
n
n
n n n
f f f
x x x
f f f
x x x
f f f
x x x


  
  
  
  
  
  
  
J x
x x x
x x x
J x
x x
2 2
( )
n
 
 
 
 
 
 
 
 
 
 
x
14
Power Flow Jacobian Matrix, cont’d
1
Jacobian elements are calculated by differentiating
each function, ( ), with respect to each variable.
For example, if ( ) is the bus real power equation
( ) ( cos sin )
i
i
n
i i k ik ik ik ik Gi
k
f x
f x i
f x V V G B P P 

   
1
( ) ( sin cos )
( ) ( sin cos ) ( )
Di
n
i
i k ik ik ik ik
i k
k i
i
i j ij ij ij ij
j
f
x V V G B
f
x V V G B j i
 

 




  


  


15
Two Bus Newton-Raphson Example
Line Z = 0.1j
One Two1.000 pu 1.000 pu
200 MW
100 MVR
0 MW
0 MVR
For the two bus power system shown below, use the
Newton-Raphson power flow to determine the
voltage magnitude and angle at bus two. Assume
that bus one is the slack and SBase = 100 MVA.
2
2
10 10
Unkown: , Also,
10 10
bus
j j
V j j
    
      
x Y
16
Two Bus Example, cont’d
1
1
General power balance equations:
( cos sin ) 0
( sin cos ) 0
For bus two, the power balance equations are
(load real power is 2.0 per unit,
while react
n
i k ik ik ik ik Gi Di
k
n
i k ik ik ik ik Gi Di
k
V V G B P P
V V G B Q Q
 
 


   
   


2 1 2
2
2 1 2 2
ive power is 1.0 per unit):
(10sin ) 2.0 0
( 10cos ) (10) 1.0 0
V V
V V V


 
    17
Two Bus Example, cont’d
2 2 2
2
2 2 2 2
2 2
2 2
2 2
2 2
2 2 2
2 2 2 2
( ) 2.0 (10sin ) 2.0
( ) 1.0 ( 10cos ) (10) 1.0
Now calculate the power flow Jacobian
( ) ( )
( )
( ) ( )
10 cos 10sin
10 sin 10cos 20
P V
Q V V
P P
x x
V
Q Q
x x
V
V
V V




 
 
  
    
  
  
 
  
   
 
    
x
x
J x
18
Two Bus Example, First Iteration
(0)
2(0)
(0)
2
(0) (0)
2 2
(0)
2(0) (0) (0)
2 2 2
(0) (0) (0)
2 2 2(0)
(0) (0)
2 2
0
For 0, guess . Calculate:
1
(10sin ) 2.0 2.0
( )
1.0( 10cos ) (10) 1.0
10 cos 10sin
( )
10 sin 10cos
v
V
V
V V
V
V



 

   
     
   
 
           


x
f x
J x
(0) (0)
2 2
1
(1)
10 0
0 1020
0 10 0 2.0 0.2
Solve
1 0 10 1.0 0.9
V

 
         
       
         
       
x
19
Two Bus Example, Next Iterations
(1)
2
(1)
1
(2)
0.9(10sin( 0.2)) 2.0 0.212
( )
0.2790.9( 10cos( 0.2)) 0.9 10 1.0
8.82 1.986
( )
1.788 8.199
0.2 8.82 1.986 0.212 0.233
0.9 1.788 8.199 0.279 0.8586
(

    
           
 
   
         
                
f x
J x
x
f (2) (3)
(3)
2
0.0145 0.236
)
0.0190 0.8554
0.0000906
( ) Close enough! 0.8554 13.52
0.0001175
V
   
    
   
 
     
 
x x
f x
20
Two Bus Solved Values
Line Z = 0.1j
One Two1.000 pu 0.855 pu
200 MW
100 MVR
200.0 MW
168.3 MVR
-13.522 Deg
200.0 MW
168.3 MVR
-200.0 MW
-100.0 MVR
Once the voltage angle and magnitude at bus 2 are
known we can calculate all the other system values,
such as the line flows and the generator reactive
power output
21
Two Bus Case Low Voltage Solution
(0)
(0) (0)
2 2
(0)
(0) (0) (0
2 2 2
This case actually has two solutions! The second
"low voltage" is found by using a low initial guess.
0
Set 0, guess . Calculate:
0.25
(10sin ) 2.0
( )
( 10cos )
v
V
V V


 
   
 


 
x
f x 2)
(0) (0) (0)
2 2 2(0)
(0) (0) (0) (0)
2 2 2 2
2
0.875(10) 1.0
10 cos 10sin 2.5 0
( )
0 510 sin 10cos 20
V
V V
 
 
 
         
 
          
J x
22
Low Voltage Solution, cont'd
1
(1)
(2) (2) (3)
0 2.5 0 2 0.8
Solve
0.25 0 5 0.875 0.075
1.462 1.42 0.921
( )
0.534 0.2336 0.220

       
                 
      
       
     
x
f x x x
Line Z = 0.1j
One Two1.000 pu 0.261 pu
200 MW
100 MVR
200.0 MW
831.7 MVR
-49.914 Deg
200.0 MW
831.7 MVR
-200.0 MW
-100.0 MVR
Low voltage solution
23
Two Bus Region of Convergence
Graph shows the region of convergence for different initial
guesses of bus 2 angle (horizontal axis) and magnitude
(vertical axis).
Red region
converges
to the high
voltage
solution,
while the
yellow region
converges
to the low
voltage
solution
Maximum
of 15
iterations24
PV Buses
Since the voltage magnitude at PV buses is
fixed there is no need to explicitly include
these voltages in x nor write the reactive
power balance equations:
– the reactive power output of the generator
varies to maintain the fixed terminal voltage
(within limits), so we can just set the reactive
power product to whatever is needed.
– An alternative is these variations/equations can
be included by just writing the explicit voltage
constraint for the generator bus:
|Vi | – Vi setpoint = 0 25
Three Bus PV Case Example
Line Z = 0.1j
Line Z = 0.1j Line Z = 0.1j
One Two1.000 pu
0.941 pu
200 MW
100 MVR
170.0 MW
68.2 MVR
-7.469 Deg
Three 1.000 pu
30 MW
63 MVR
2 2 2 2
3 3 3 3
2 2 2
For this three bus case we have
( )
( ) ( ) 0
( )
G D
G D
D
P P P
P P P
V Q Q


    
       
   
     
x
x f x x
x
26
PV Buses
• With Newton-Raphson, PV buses means that
there are less unknown variables we need to
calculate explicitly and less equations we need
to satisfy explicitly.
• Reactive power balance is satisfied implicitly
by choosing reactive power production to be
whatever is needed, once we have a solved
case (like real power at the slack bus).
• Contrast to Gauss iterations where PV buses
complicated the algorithm. 27
Modeling Voltage Dependent Load
So far we've assumed that the load is independent of
the bus voltage (i.e., constant power). However, the
power flow can be easily extended to include voltage
dependence with both the real and reactive
1
1
load. This
is done by making and a function of :
( cos sin ) ( ) 0
( sin cos ) ( ) 0
Di Di i
n
i k ik ik ik ik Gi Di i
k
n
i k ik ik ik ik Gi Di i
k
P Q V
V V G B P P V
V V G B Q Q V
 
 


   
   


28
Voltage Dependent Load Example
2 2
2 2 2 2 2
2 2 2
2 2 2 2 2 2
In previous two bus example now assume the load is
constant impedance, with corresponding per unit
admittance of 2.0 1.0:
( ) 2.0 (10sin ) 2.0 0
( ) 1.0 ( 10cos ) (10) 1.0 0
Now
j
P V V V
Q V V V V



   
     
x
x
2 2 2 2
2 2 2 2 2
calculate the power flow Jacobian
10 cos 10sin 4.0
( )
10 sin 10cos 20 2.0
V V
V V V
 
 
 
     
J x
29
Voltage Dependent Load, cont'd
(0)
2(0)
(0)
2
2(0) (0) (0)
2 2 2(0)
2 2(0) (0) (0) (0)
2 2 2 2
(0)
(1)
0
Again for 0, guess . Calculate:
1
(10sin ) 2.0 2.0
( )
1.0
( 10cos ) (10) 1.0
10 4
( )
0 12
0
Solve
1
v
V
V V
V V V



   
     
   
              
 
  
 

 

x
f x
J x
x
1
10 4 2.0 0.1667
0 12 1.0 0.9167

      
       
      
30
Voltage Dependent Load, cont'd
Line Z = 0.1j
One Two1.000 pu
0.894 pu
160 MW
80 MVR
160.0 MW
120.0 MVR
-10.304 Deg
160.0 MW
120.0 MVR
-160.0 MW
-80.0 MVR
With constant impedance load the MW/MVAr load at
bus 2 varies with the square of the bus 2 voltage
magnitude. This if the voltage level is less than 1.0,
the load is lower than 200/100 MW/MVAr.
31
In practice, load is the sum of constant power,
constant impedance, and, in some cases,
constant current load terms: “ZIP” load.
Solving Large Power Systems
Most difficult computational task is inverting the
Jacobian matrix (or solving the update equation):
– factorizing a full matrix is an order n3 operation, meaning
the amount of computation increases with the cube of
the size of the problem.
– this amount of computation can be decreased
substantially by recognizing that since Ybus is a sparse
matrix, the Jacobian is also a sparse matrix.
– using sparse matrix methods results in a computational
order of about n1.5.
– this is a substantial savings when solving systems with
tens of thousands of buses. 32
Newton-Raphson Power Flow
 Advantages
– fast convergence as long as initial guess is close to
solution
– large region of convergence
 Disadvantages
– each iteration takes much longer than a Gauss-Seidel
iteration
– more complicated to code, particularly when
implementing sparse matrix algorithms
 Newton-Raphson algorithm is very common in
power flow analysis.
33

Newton raphson method

  • 1.
    EE 369 POWER SYSTEMANALYSIS Lecture 12 Power Flow Tom Overbye and Ross Baldick 1
  • 2.
    Announcements • Homework 9is: 3.47, 3.49, 3.53, 3.57, 3.61, 6.2, 6.9, 6.13, 6.14, 6.18, 6.19, 6.20; due November 7. (Use infinity norm and epsilon = 0.01 for any problems where norm or stopping criterion not specified.) • Read Chapter 12, concentrating on sections 12.4 and 12.5. • Homework 10 is 6.23, 6,25, 6.26, 6.28, 6.29, 6.30 (see figure 6.18 and table 6.9 for system), 6.31, 6.38, 6.42, 6.46, 6.52, 6.54; due November 14. • Homework 11 is 6.43, 6.48, 6.59, 6.61, 12.19, 12.22, 12.20, 12.24, 12.26, 12.28, 12.29; due Nov. 21. 2
  • 3.
    Power System Planning Source:Midwest ISO MTEP08 Report 3
  • 4.
    MISO Generation Queue Source:Midwest ISO MTEP08 Report 4
  • 5.
    MISO Conceptual EHVOverlay Black lines are DC, blue lines are 765kV, red are 500 kV Source: Midwest ISO MTEP08 Report 5
  • 6.
    ERCOT Also has considerablewind and expecting considerable more! “Competitive Renewable Energy Zones” study identified most promising wind sites, Building around $5 billion (original estimate, now closer to $7 billion) of transmission to support an additional 11 GW of wind. Will be completed in 2014. 6
  • 7.
  • 8.
    NR Application toPower Flow * * * * 1 1 We first need to rewrite complex power equations as equations with real coefficients (we've seen this earlier): These can be derived by defining n n i i i i ik k i ik k k k ik ik ik i S V I V Y V V Y V Y G jB V              Recall e cos sin ij i i i ik i k j V e V j              8
  • 9.
    Real Power BalanceEquations * * 1 1 1 1 1 ( ) (cos sin )( ) Resolving into the real and imaginary parts: ( cos sin ) ( sin cos ik n n j i i i i ik k i k ik ik k k n i k ik ik ik ik k n i i k ik ik ik ik Gi Di k n i i k ik ik ik k S P jQ V Y V V V e G jB V V j G jB P V V G B P P Q V V G B                                )ik Gi DiQ Q  9
  • 10.
    Newton-Raphson Power Flow Inthe Newton-Raphson power flow we use Newton's method to determine the voltage magnitude and angle at each bus in the power system that satisfies power balance. We need to solve the power balance equ 1 1 ations: ( cos sin ) 0 ( sin cos ) 0 n i k ik ik ik ik Gi Di k n i k ik ik ik ik Gi Di k V V G B P P V V G B Q Q                 10
  • 11.
    Power Flow Variables 1 1 Forconvenience, write: ( ) ( cos sin ) ( ) ( sin cos ) The power balance equations are then: ( ) 0 ( ) 0 n i i k ik ik ik ik k n i i k ik ik ik ik k i Gi Di i Gi Di P V V G B Q V V G B P P P Q Q Q                   x x x x 11
  • 12.
    Power Flow Variables 2 n 2 Assumethe slack bus is the first bus (with a fixed voltage angle/magnitude). We then need to determine the voltage angle/magnitude at the other buses. We must solve ( ) , where: n V V          f x 0 x 2 2 2 2 2 2 ( ) ( ) ( ) ( ) ( ) G D n Gn Dn G D n Gn Dn P P P P P P Q Q Q Q Q Q                                  x x f x x x 12
  • 13.
    N-R Power FlowSolution (0) ( ) ( 1) ( ) ( ) 1 ( ) The power flow is solved using the same procedure discussed previously for general equations: For 0; make an initial guess of , While ( ) Do [ ( )] ( ) 1 End v v v v v v v v          x x f x x x J x f x 13
  • 14.
    Power Flow JacobianMatrix 1 1 1 1 2 2 2 2 2 2 1 2 2 2 2 2 2 2 2 2 1 2 The most difficult part of the algorithm is determining and factorizing the Jacobian matrix, ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) n n n n n f f f x x x f f f x x x f f f x x x                        J x x x x x x x J x x x 2 2 ( ) n                     x 14
  • 15.
    Power Flow JacobianMatrix, cont’d 1 Jacobian elements are calculated by differentiating each function, ( ), with respect to each variable. For example, if ( ) is the bus real power equation ( ) ( cos sin ) i i n i i k ik ik ik ik Gi k f x f x i f x V V G B P P       1 ( ) ( sin cos ) ( ) ( sin cos ) ( ) Di n i i k ik ik ik ik i k k i i i j ij ij ij ij j f x V V G B f x V V G B j i                    15
  • 16.
    Two Bus Newton-RaphsonExample Line Z = 0.1j One Two1.000 pu 1.000 pu 200 MW 100 MVR 0 MW 0 MVR For the two bus power system shown below, use the Newton-Raphson power flow to determine the voltage magnitude and angle at bus two. Assume that bus one is the slack and SBase = 100 MVA. 2 2 10 10 Unkown: , Also, 10 10 bus j j V j j             x Y 16
  • 17.
    Two Bus Example,cont’d 1 1 General power balance equations: ( cos sin ) 0 ( sin cos ) 0 For bus two, the power balance equations are (load real power is 2.0 per unit, while react n i k ik ik ik ik Gi Di k n i k ik ik ik ik Gi Di k V V G B P P V V G B Q Q                 2 1 2 2 2 1 2 2 ive power is 1.0 per unit): (10sin ) 2.0 0 ( 10cos ) (10) 1.0 0 V V V V V         17
  • 18.
    Two Bus Example,cont’d 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 ( ) 2.0 (10sin ) 2.0 ( ) 1.0 ( 10cos ) (10) 1.0 Now calculate the power flow Jacobian ( ) ( ) ( ) ( ) ( ) 10 cos 10sin 10 sin 10cos 20 P V Q V V P P x x V Q Q x x V V V V                                       x x J x 18
  • 19.
    Two Bus Example,First Iteration (0) 2(0) (0) 2 (0) (0) 2 2 (0) 2(0) (0) (0) 2 2 2 (0) (0) (0) 2 2 2(0) (0) (0) 2 2 0 For 0, guess . Calculate: 1 (10sin ) 2.0 2.0 ( ) 1.0( 10cos ) (10) 1.0 10 cos 10sin ( ) 10 sin 10cos v V V V V V V                                     x f x J x (0) (0) 2 2 1 (1) 10 0 0 1020 0 10 0 2.0 0.2 Solve 1 0 10 1.0 0.9 V                                        x 19
  • 20.
    Two Bus Example,Next Iterations (1) 2 (1) 1 (2) 0.9(10sin( 0.2)) 2.0 0.212 ( ) 0.2790.9( 10cos( 0.2)) 0.9 10 1.0 8.82 1.986 ( ) 1.788 8.199 0.2 8.82 1.986 0.212 0.233 0.9 1.788 8.199 0.279 0.8586 (                                                    f x J x x f (2) (3) (3) 2 0.0145 0.236 ) 0.0190 0.8554 0.0000906 ( ) Close enough! 0.8554 13.52 0.0001175 V                        x x f x 20
  • 21.
    Two Bus SolvedValues Line Z = 0.1j One Two1.000 pu 0.855 pu 200 MW 100 MVR 200.0 MW 168.3 MVR -13.522 Deg 200.0 MW 168.3 MVR -200.0 MW -100.0 MVR Once the voltage angle and magnitude at bus 2 are known we can calculate all the other system values, such as the line flows and the generator reactive power output 21
  • 22.
    Two Bus CaseLow Voltage Solution (0) (0) (0) 2 2 (0) (0) (0) (0 2 2 2 This case actually has two solutions! The second "low voltage" is found by using a low initial guess. 0 Set 0, guess . Calculate: 0.25 (10sin ) 2.0 ( ) ( 10cos ) v V V V               x f x 2) (0) (0) (0) 2 2 2(0) (0) (0) (0) (0) 2 2 2 2 2 0.875(10) 1.0 10 cos 10sin 2.5 0 ( ) 0 510 sin 10cos 20 V V V                              J x 22
  • 23.
    Low Voltage Solution,cont'd 1 (1) (2) (2) (3) 0 2.5 0 2 0.8 Solve 0.25 0 5 0.875 0.075 1.462 1.42 0.921 ( ) 0.534 0.2336 0.220                                                 x f x x x Line Z = 0.1j One Two1.000 pu 0.261 pu 200 MW 100 MVR 200.0 MW 831.7 MVR -49.914 Deg 200.0 MW 831.7 MVR -200.0 MW -100.0 MVR Low voltage solution 23
  • 24.
    Two Bus Regionof Convergence Graph shows the region of convergence for different initial guesses of bus 2 angle (horizontal axis) and magnitude (vertical axis). Red region converges to the high voltage solution, while the yellow region converges to the low voltage solution Maximum of 15 iterations24
  • 25.
    PV Buses Since thevoltage magnitude at PV buses is fixed there is no need to explicitly include these voltages in x nor write the reactive power balance equations: – the reactive power output of the generator varies to maintain the fixed terminal voltage (within limits), so we can just set the reactive power product to whatever is needed. – An alternative is these variations/equations can be included by just writing the explicit voltage constraint for the generator bus: |Vi | – Vi setpoint = 0 25
  • 26.
    Three Bus PVCase Example Line Z = 0.1j Line Z = 0.1j Line Z = 0.1j One Two1.000 pu 0.941 pu 200 MW 100 MVR 170.0 MW 68.2 MVR -7.469 Deg Three 1.000 pu 30 MW 63 MVR 2 2 2 2 3 3 3 3 2 2 2 For this three bus case we have ( ) ( ) ( ) 0 ( ) G D G D D P P P P P P V Q Q                          x x f x x x 26
  • 27.
    PV Buses • WithNewton-Raphson, PV buses means that there are less unknown variables we need to calculate explicitly and less equations we need to satisfy explicitly. • Reactive power balance is satisfied implicitly by choosing reactive power production to be whatever is needed, once we have a solved case (like real power at the slack bus). • Contrast to Gauss iterations where PV buses complicated the algorithm. 27
  • 28.
    Modeling Voltage DependentLoad So far we've assumed that the load is independent of the bus voltage (i.e., constant power). However, the power flow can be easily extended to include voltage dependence with both the real and reactive 1 1 load. This is done by making and a function of : ( cos sin ) ( ) 0 ( sin cos ) ( ) 0 Di Di i n i k ik ik ik ik Gi Di i k n i k ik ik ik ik Gi Di i k P Q V V V G B P P V V V G B Q Q V                 28
  • 29.
    Voltage Dependent LoadExample 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 In previous two bus example now assume the load is constant impedance, with corresponding per unit admittance of 2.0 1.0: ( ) 2.0 (10sin ) 2.0 0 ( ) 1.0 ( 10cos ) (10) 1.0 0 Now j P V V V Q V V V V              x x 2 2 2 2 2 2 2 2 2 calculate the power flow Jacobian 10 cos 10sin 4.0 ( ) 10 sin 10cos 20 2.0 V V V V V             J x 29
  • 30.
    Voltage Dependent Load,cont'd (0) 2(0) (0) 2 2(0) (0) (0) 2 2 2(0) 2 2(0) (0) (0) (0) 2 2 2 2 (0) (1) 0 Again for 0, guess . Calculate: 1 (10sin ) 2.0 2.0 ( ) 1.0 ( 10cos ) (10) 1.0 10 4 ( ) 0 12 0 Solve 1 v V V V V V V                                            x f x J x x 1 10 4 2.0 0.1667 0 12 1.0 0.9167                        30
  • 31.
    Voltage Dependent Load,cont'd Line Z = 0.1j One Two1.000 pu 0.894 pu 160 MW 80 MVR 160.0 MW 120.0 MVR -10.304 Deg 160.0 MW 120.0 MVR -160.0 MW -80.0 MVR With constant impedance load the MW/MVAr load at bus 2 varies with the square of the bus 2 voltage magnitude. This if the voltage level is less than 1.0, the load is lower than 200/100 MW/MVAr. 31 In practice, load is the sum of constant power, constant impedance, and, in some cases, constant current load terms: “ZIP” load.
  • 32.
    Solving Large PowerSystems Most difficult computational task is inverting the Jacobian matrix (or solving the update equation): – factorizing a full matrix is an order n3 operation, meaning the amount of computation increases with the cube of the size of the problem. – this amount of computation can be decreased substantially by recognizing that since Ybus is a sparse matrix, the Jacobian is also a sparse matrix. – using sparse matrix methods results in a computational order of about n1.5. – this is a substantial savings when solving systems with tens of thousands of buses. 32
  • 33.
    Newton-Raphson Power Flow Advantages – fast convergence as long as initial guess is close to solution – large region of convergence  Disadvantages – each iteration takes much longer than a Gauss-Seidel iteration – more complicated to code, particularly when implementing sparse matrix algorithms  Newton-Raphson algorithm is very common in power flow analysis. 33