IJIRST –International Journal for Innovative Research in Science & Technology| Volume 3 | Issue 07 | December 2016
ISSN (online): 2349-6010
All rights reserved by www.ijirst.org 1
A Novel Method to Analyse the Effects of
Geomagnetic Induced Current on Transformer
Roshni. R. Jethani Dr. Harikumar Naidu
Student Professor & Head of the Department
Department of Electrical Engineering Department of Electrical Engineering
Tulsiramji Gaikwad-Patil College of Engineering &
Technology
Tulsiramji Gaikwad-Patil College of Engineering &
Technology
Abstract
Geomagnetic induced currents are generated on the power system by solar storms and solar flare, which causes damages to power
transformer. GIC (DC) current when enter the power grid through the neutral point of transformer causes saturation of the
transformer and the transformer gets damaged hence a novel hardware model was fabricated and the effects were analyzed. A
software simulation was done using MATLAB and the effects on power transformer were observed to be increase in reactive power
consumption and fluctuating harmonics in neutral current and the excitations current. Were analyzed which has got significance
in the practical field to give warnings before the occurrence of the damage to the transformer and the subsequent interruption of
power supply.
Keywords: Geomagnetially Induced Current (GIC), Transformer, power system, harmonics
_______________________________________________________________________________________________________
I. INTRODUCTION
Normally power transformers are designed to operate with a sinusoidal voltage. Due to solar activity on Earth Surface and ESP
Earth surface potential is induced which distorts the input voltage of the power grid and cause superimposition of DC current on
transformer and causes various damages to the system.
In power system, neutral points of transformer are generally grounded for providing protection to the system. Therefore, due to
variation in geomagnetic field it will produce potential difference and induce current between neutral point of transformer. This
current is known as Geomagnetically induced current.
Flow of current between neutral is known as geomagnetically induced current (GIC) and causes instability issues and equipment
damage in power systems during geomagnetic storms. The transformer are designed to operate close to the knee of the
magnetization characteristics and when DC enters it causes the transformer to enter into the saturation region in the half cycle of
input supply. This is known as half cycle saturation of transformer.
Due to half cycle saturation transformer draws large exciting current and result in increased reactive power consumption heating
of the transformer and distortion of the alternating current waveform and harmonic generation in currents.
During GMD, the saturation of transformer depends on the magnitude of DC current and on the core. The level of half cycle
saturation determines the nature of waveform of magnetizing current and reactive power consumption of transformer. The
simulation is carried out to analyze the effect of GIC (DC) on transformer. This paper presents the simulation results to show the
effects of GIC on the waveform of neutral current of transformer. The simulation model and results of transformer are presented
in section
II. HARDWARE IMPLEMENTATION TO ANALYZE THE EFFECT OF DC ON TRANSFORMER
Fig. 1: Hardware Implementation of Transformer with injection of DC Current
A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer
(IJIRST/ Volume 3 / Issue 07/ 001)
All rights reserved by www.ijirst.org 2
In real high voltage power transformer, it is difficult to conduct test due to high magnitude of the currents and power. This problem
was resolved by using reduced scale transformer. Thus, effect and investigation of it is done in a laboratory setup by injecting DC
currents into a three-phase transformer.
Three phase AC voltage in the range of (0-440V) is applied to three phase transformers with the help of autotransformer and
digital multimeter. A three-phase transformer of 440V/12V, 12VA, with primary winding delta and secondary winding star
connected and neutral grounded so as to measure the effect of GIC on transformer and power system. For injection of DC current
into the secondary winding of the transformer a half wave rectifier is used in series with three phases of the secondary winding.
The DC source injects a current which depends upon the three-phase resistive load. As the maximum secondary voltage is 12V
a maximum DC current of 1 A can be injected into the star point, hence 0.333 A per phase. As the secondary side magnetization
current of the transformer is about 1A the DC source is able to deliver a current that is half of the magnetization current.
This leads to saturation effects within the transformer core material. For monitoring of the primary and secondary side voltage
to ground a digital storage oscilloscope (DSO) is used. The primary side and secondary side current are metered with the help of
clamp meter. The waveform of voltage before and after DC current injected is shown in figure 2 and figure 3
Fig. 2: Waveform on Primary Side of Transformer before DC Current is injected
Fig. 3: Waveform on Secondary Side of Transformer after DC is injected into Transformer
III. SIMULATION AND RESULT TO ANALYZE THE EFFECT OF GIC (DC) CURRENT ON THREE PHASE TRANSFORMERS
The simulink model consist of a transformer with three phase saturable transformer, resistive load, Bus bar B1and B2, current and
voltage measurement meter to measure current and voltage in respective phase, DC voltage source to produce DC current in order
to simulate GIC effect.
A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer
(IJIRST/ Volume 3 / Issue 07/ 001)
All rights reserved by www.ijirst.org 3
Figure 4 shows simulation model to analyze the effect of GIC (DC) on transformer using simulation on MATLAB. Three phase
saturable transformer is designed with a voltage of 440V in the primary and the secondary voltage of 12V, and a resistive load.
The aim of this is to evaluate the effect of GIC with the transformer operating with DC. The rating of three phase transformers
is a 12VA, 50 Hz. The line voltage of primary winding is 400 V & line voltage of secondary winding is 12V.
Fig. 4: Simulink Model of Transformer with effect of GIC (DC)
Fig. 5: Flux-Current Characteristics of Transformer
A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer
(IJIRST/ Volume 3 / Issue 07/ 001)
All rights reserved by www.ijirst.org 4
Fig. 6: Hysteresis Curve of Transformer When DC current is induced in Transformer by Power GUI Tool
Fig. 7: Iexc Saturation Current of Transformer
Fig. 8: Neutral Current When DC is induced at Secondary Side of Transformer
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-3.5
-3
-2.5
-2
-1.5
-1
-0.5
0
0.5
1
1.5
x 10
-3
Time
NeutralCurrent
A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer
(IJIRST/ Volume 3 / Issue 07/ 001)
All rights reserved by www.ijirst.org 5
Fig. 9: Active and Reactive Power Compensation of Transformer
Fig. 11: FFT Analysis in Current when DC is Induced in Secondary Star connected Transformer
IV. CONCLUSION
The simulations of GIC using a three phase saturable transformer model shows
1) Reactive power consumption is increasing from 0 to 0.02 m sec and after 0.02 m sec it becomes constant while the active
power of transformer decreases from 0 to 0.02 m sec and thereafter it becomes constant.
2) The neutral current fluctuations are observed predominantly as the DC is injected into the neutral of the saturable transformer.
3) The fluctuating harmonics in neutral current using power GUI FFT tool is found to be 0.03%.
4) The fluctuating harmonics is also found in the excitation current of transformer.
5) The B-H curve is also plotted and the area of the curve increases which shows the hysteresis losses are proportionally
increasing as DC current is being increased.
The hardware and simulation model has given the results which will be of immense importances to the practical field engineers.
Further studies could observe effects which happen in a bigger scaled power transformer leading to damages of the insulation or
even to failures occurring after GIC events. Further investigations about these phenomena on large scaled setups shall be followed
and the scalability of the setup needs to be investigated.
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2
-5
0
5
10
15
20
25
30
35
40
45
Time
ActiveandReactivePowerConsumption
ActiveandReactivePowerConsumption
ReactivePower
ActivePower
A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer
(IJIRST/ Volume 3 / Issue 07/ 001)
All rights reserved by www.ijirst.org 6
REFERENCES
[1] Jon Berge, Luis Marti, Rajiv K. Varma,” Modeling and Mitigation of Geomagnetically Induced Currents on a Realistic Power System Network”, IEEE
Electrical Power and Energy Conference (2011)
[2] Baris Kovan, Francisco de León,” Mitigation of Geomagnetically Induced Currents by Neutral Switching”, IEEE TRANSACTIONS ON POWER
DELIVERY, VOL. 30, NO. 4, AUGUST 2015
[3] F. R. Faxvog, W. Jensen, G. Fuchs, G. Nordling, D. B. Jackson, B. Groh, N. Ruehl, A.P. Vitols, T. L. Volkmann, M.R. Rooney, Russell Neal,” Power Grid
Protection against Geomagnetic Disturbances (GMD)”, 2013 IEEE Electrical Power & Energy Conferenc (EPEC) 978-1-4799-0106-7/13/$31.00 ©2013
IEEE.
[4] Philip R. Price,” Geomagnetically Induced Current Effects on Transformers” IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4,
OCTOBER 2002
[5] A.D. Rajapakse, N. Perera, F. R. Faxvog, W. Jensen, G. Nordling, G. Fuchs, D. B. Jackson, T. L. Volkmann, N. Ruehl, B. Groh,” Power Grid Stability
Protection against GIC Using a Capacitive Grounding Circuit.
[6] José Ramírez-Ni˜no, Carlos Haro-Hernández, Joaquín Héctor Rodriguez-Rodriguez, Rito Mijarez,” Core saturation effects of geomagnetic induced currents
in power transformers“Journal of Applied Research and Technology

More Related Content

What's hot

Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...
IAEME Publication
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Tao Yang
 

What's hot (19)

Ijertv2 is2554
Ijertv2 is2554Ijertv2 is2554
Ijertv2 is2554
 
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
Comparison of solar based closed loop DC-DC converter using PID and ANN contr...
 
Ct4201633637
Ct4201633637Ct4201633637
Ct4201633637
 
Stability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faultsStability analysis of photovoltaic system under grid faults
Stability analysis of photovoltaic system under grid faults
 
Modelling of three phase SVPWM AC-AC converter using unity power factor control
Modelling of three phase SVPWM AC-AC converter using unity power factor controlModelling of three phase SVPWM AC-AC converter using unity power factor control
Modelling of three phase SVPWM AC-AC converter using unity power factor control
 
Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...Battery energy storage and power electronics based voltage and frequency cont...
Battery energy storage and power electronics based voltage and frequency cont...
 
254 ishwri
254 ishwri254 ishwri
254 ishwri
 
Dynamic Voltage Stability Comparison of Thermal and Wind Power Generation wit...
Dynamic Voltage Stability Comparison of Thermal and Wind Power Generation wit...Dynamic Voltage Stability Comparison of Thermal and Wind Power Generation wit...
Dynamic Voltage Stability Comparison of Thermal and Wind Power Generation wit...
 
Kw2519001905
Kw2519001905Kw2519001905
Kw2519001905
 
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
The new approach minimizes harmonics in a single-phase three-level NPC 400 Hz...
 
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EINext Generation Researchers in Power Systems_Tao Yang_UCD EI
Next Generation Researchers in Power Systems_Tao Yang_UCD EI
 
Ak4101210215
Ak4101210215Ak4101210215
Ak4101210215
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...
 
Voltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOMVoltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOM
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable load
 
40220140505011
4022014050501140220140505011
40220140505011
 
Close Loop Control of Induction Motor Using Z-Source Inverter
Close Loop Control of Induction Motor Using Z-Source InverterClose Loop Control of Induction Motor Using Z-Source Inverter
Close Loop Control of Induction Motor Using Z-Source Inverter
 
SRF THEORY BASED STATCOM FOR COMPENSATION OF REACTIVE POWER AND HARMONICS
SRF THEORY BASED STATCOM FOR COMPENSATION OF REACTIVE POWER AND HARMONICSSRF THEORY BASED STATCOM FOR COMPENSATION OF REACTIVE POWER AND HARMONICS
SRF THEORY BASED STATCOM FOR COMPENSATION OF REACTIVE POWER AND HARMONICS
 

Similar to Ijirstv3i7002 170302112524

Similar to Ijirstv3i7002 170302112524 (20)

Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
 
Fr3610401047
Fr3610401047Fr3610401047
Fr3610401047
 
Cost effective solar Inverter
Cost effective solar InverterCost effective solar Inverter
Cost effective solar Inverter
 
Ijertv2 is2554
Ijertv2 is2554Ijertv2 is2554
Ijertv2 is2554
 
Ijertv2 is2554
Ijertv2 is2554Ijertv2 is2554
Ijertv2 is2554
 
J010236770
J010236770J010236770
J010236770
 
Solar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid systemSolar energy based impedance-source inverter for grid system
Solar energy based impedance-source inverter for grid system
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
 
Design and Simulation of Induction Heating Equipment using MATLAB / SIMULINK ...
Design and Simulation of Induction Heating Equipment using MATLAB / SIMULINK ...Design and Simulation of Induction Heating Equipment using MATLAB / SIMULINK ...
Design and Simulation of Induction Heating Equipment using MATLAB / SIMULINK ...
 
C43030914
C43030914C43030914
C43030914
 
Enhancement of power quality using microprocessor based shunt active power fi...
Enhancement of power quality using microprocessor based shunt active power fi...Enhancement of power quality using microprocessor based shunt active power fi...
Enhancement of power quality using microprocessor based shunt active power fi...
 
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
 
05636775
0563677505636775
05636775
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system
 
Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...Analysis of direct power control AC-DC converter under unbalance voltage supp...
Analysis of direct power control AC-DC converter under unbalance voltage supp...
 
Gz3412811286
Gz3412811286Gz3412811286
Gz3412811286
 
Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution system
 
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
ZVZCS Based High Frequency Link Grid Connected SVM Applied Three Phase Three ...
 
Dh34667671
Dh34667671Dh34667671
Dh34667671
 

More from university of johannesburg (7)

novel
novel novel
novel
 
Shortstories 120709090438-phpapp02
Shortstories 120709090438-phpapp02Shortstories 120709090438-phpapp02
Shortstories 120709090438-phpapp02
 
Personalletter 140126074601-phpapp02
Personalletter 140126074601-phpapp02Personalletter 140126074601-phpapp02
Personalletter 140126074601-phpapp02
 
Parts of-speech-1222899793596097-8
Parts of-speech-1222899793596097-8Parts of-speech-1222899793596097-8
Parts of-speech-1222899793596097-8
 
Inmrstilchersclass 111121061550-phpapp01
Inmrstilchersclass 111121061550-phpapp01Inmrstilchersclass 111121061550-phpapp01
Inmrstilchersclass 111121061550-phpapp01
 
Comprehension 100821124805-phpapp01
Comprehension 100821124805-phpapp01Comprehension 100821124805-phpapp01
Comprehension 100821124805-phpapp01
 
Advicepowerpoint1 111019200215-phpapp02
Advicepowerpoint1 111019200215-phpapp02Advicepowerpoint1 111019200215-phpapp02
Advicepowerpoint1 111019200215-phpapp02
 

Recently uploaded

Orientation Canvas Course Presentation.pdf
Orientation Canvas Course Presentation.pdfOrientation Canvas Course Presentation.pdf
Orientation Canvas Course Presentation.pdf
Elizabeth Walsh
 
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
MysoreMuleSoftMeetup
 

Recently uploaded (20)

How to Manage Call for Tendor in Odoo 17
How to Manage Call for Tendor in Odoo 17How to Manage Call for Tendor in Odoo 17
How to Manage Call for Tendor in Odoo 17
 
What is 3 Way Matching Process in Odoo 17.pptx
What is 3 Way Matching Process in Odoo 17.pptxWhat is 3 Way Matching Process in Odoo 17.pptx
What is 3 Way Matching Process in Odoo 17.pptx
 
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
NO1 Top Black Magic Specialist In Lahore Black magic In Pakistan Kala Ilam Ex...
 
Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)Jamworks pilot and AI at Jisc (20/03/2024)
Jamworks pilot and AI at Jisc (20/03/2024)
 
Orientation Canvas Course Presentation.pdf
Orientation Canvas Course Presentation.pdfOrientation Canvas Course Presentation.pdf
Orientation Canvas Course Presentation.pdf
 
When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...When Quality Assurance Meets Innovation in Higher Education - Report launch w...
When Quality Assurance Meets Innovation in Higher Education - Report launch w...
 
UGC NET Paper 1 Unit 7 DATA INTERPRETATION.pdf
UGC NET Paper 1 Unit 7 DATA INTERPRETATION.pdfUGC NET Paper 1 Unit 7 DATA INTERPRETATION.pdf
UGC NET Paper 1 Unit 7 DATA INTERPRETATION.pdf
 
OSCM Unit 2_Operations Processes & Systems
OSCM Unit 2_Operations Processes & SystemsOSCM Unit 2_Operations Processes & Systems
OSCM Unit 2_Operations Processes & Systems
 
FICTIONAL SALESMAN/SALESMAN SNSW 2024.pdf
FICTIONAL SALESMAN/SALESMAN SNSW 2024.pdfFICTIONAL SALESMAN/SALESMAN SNSW 2024.pdf
FICTIONAL SALESMAN/SALESMAN SNSW 2024.pdf
 
21st_Century_Skills_Framework_Final_Presentation_2.pptx
21st_Century_Skills_Framework_Final_Presentation_2.pptx21st_Century_Skills_Framework_Final_Presentation_2.pptx
21st_Century_Skills_Framework_Final_Presentation_2.pptx
 
Including Mental Health Support in Project Delivery, 14 May.pdf
Including Mental Health Support in Project Delivery, 14 May.pdfIncluding Mental Health Support in Project Delivery, 14 May.pdf
Including Mental Health Support in Project Delivery, 14 May.pdf
 
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
MuleSoft Integration with AWS Textract | Calling AWS Textract API |AWS - Clou...
 
dusjagr & nano talk on open tools for agriculture research and learning
dusjagr & nano talk on open tools for agriculture research and learningdusjagr & nano talk on open tools for agriculture research and learning
dusjagr & nano talk on open tools for agriculture research and learning
 
HMCS Vancouver Pre-Deployment Brief - May 2024 (Web Version).pptx
HMCS Vancouver Pre-Deployment Brief - May 2024 (Web Version).pptxHMCS Vancouver Pre-Deployment Brief - May 2024 (Web Version).pptx
HMCS Vancouver Pre-Deployment Brief - May 2024 (Web Version).pptx
 
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
80 ĐỀ THI THỬ TUYỂN SINH TIẾNG ANH VÀO 10 SỞ GD – ĐT THÀNH PHỐ HỒ CHÍ MINH NĂ...
 
REMIFENTANIL: An Ultra short acting opioid.pptx
REMIFENTANIL: An Ultra short acting opioid.pptxREMIFENTANIL: An Ultra short acting opioid.pptx
REMIFENTANIL: An Ultra short acting opioid.pptx
 
Play hard learn harder: The Serious Business of Play
Play hard learn harder:  The Serious Business of PlayPlay hard learn harder:  The Serious Business of Play
Play hard learn harder: The Serious Business of Play
 
Ernest Hemingway's For Whom the Bell Tolls
Ernest Hemingway's For Whom the Bell TollsErnest Hemingway's For Whom the Bell Tolls
Ernest Hemingway's For Whom the Bell Tolls
 
Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...Andreas Schleicher presents at the launch of What does child empowerment mean...
Andreas Schleicher presents at the launch of What does child empowerment mean...
 
Towards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptxTowards a code of practice for AI in AT.pptx
Towards a code of practice for AI in AT.pptx
 

Ijirstv3i7002 170302112524

  • 1. IJIRST –International Journal for Innovative Research in Science & Technology| Volume 3 | Issue 07 | December 2016 ISSN (online): 2349-6010 All rights reserved by www.ijirst.org 1 A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer Roshni. R. Jethani Dr. Harikumar Naidu Student Professor & Head of the Department Department of Electrical Engineering Department of Electrical Engineering Tulsiramji Gaikwad-Patil College of Engineering & Technology Tulsiramji Gaikwad-Patil College of Engineering & Technology Abstract Geomagnetic induced currents are generated on the power system by solar storms and solar flare, which causes damages to power transformer. GIC (DC) current when enter the power grid through the neutral point of transformer causes saturation of the transformer and the transformer gets damaged hence a novel hardware model was fabricated and the effects were analyzed. A software simulation was done using MATLAB and the effects on power transformer were observed to be increase in reactive power consumption and fluctuating harmonics in neutral current and the excitations current. Were analyzed which has got significance in the practical field to give warnings before the occurrence of the damage to the transformer and the subsequent interruption of power supply. Keywords: Geomagnetially Induced Current (GIC), Transformer, power system, harmonics _______________________________________________________________________________________________________ I. INTRODUCTION Normally power transformers are designed to operate with a sinusoidal voltage. Due to solar activity on Earth Surface and ESP Earth surface potential is induced which distorts the input voltage of the power grid and cause superimposition of DC current on transformer and causes various damages to the system. In power system, neutral points of transformer are generally grounded for providing protection to the system. Therefore, due to variation in geomagnetic field it will produce potential difference and induce current between neutral point of transformer. This current is known as Geomagnetically induced current. Flow of current between neutral is known as geomagnetically induced current (GIC) and causes instability issues and equipment damage in power systems during geomagnetic storms. The transformer are designed to operate close to the knee of the magnetization characteristics and when DC enters it causes the transformer to enter into the saturation region in the half cycle of input supply. This is known as half cycle saturation of transformer. Due to half cycle saturation transformer draws large exciting current and result in increased reactive power consumption heating of the transformer and distortion of the alternating current waveform and harmonic generation in currents. During GMD, the saturation of transformer depends on the magnitude of DC current and on the core. The level of half cycle saturation determines the nature of waveform of magnetizing current and reactive power consumption of transformer. The simulation is carried out to analyze the effect of GIC (DC) on transformer. This paper presents the simulation results to show the effects of GIC on the waveform of neutral current of transformer. The simulation model and results of transformer are presented in section II. HARDWARE IMPLEMENTATION TO ANALYZE THE EFFECT OF DC ON TRANSFORMER Fig. 1: Hardware Implementation of Transformer with injection of DC Current
  • 2. A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer (IJIRST/ Volume 3 / Issue 07/ 001) All rights reserved by www.ijirst.org 2 In real high voltage power transformer, it is difficult to conduct test due to high magnitude of the currents and power. This problem was resolved by using reduced scale transformer. Thus, effect and investigation of it is done in a laboratory setup by injecting DC currents into a three-phase transformer. Three phase AC voltage in the range of (0-440V) is applied to three phase transformers with the help of autotransformer and digital multimeter. A three-phase transformer of 440V/12V, 12VA, with primary winding delta and secondary winding star connected and neutral grounded so as to measure the effect of GIC on transformer and power system. For injection of DC current into the secondary winding of the transformer a half wave rectifier is used in series with three phases of the secondary winding. The DC source injects a current which depends upon the three-phase resistive load. As the maximum secondary voltage is 12V a maximum DC current of 1 A can be injected into the star point, hence 0.333 A per phase. As the secondary side magnetization current of the transformer is about 1A the DC source is able to deliver a current that is half of the magnetization current. This leads to saturation effects within the transformer core material. For monitoring of the primary and secondary side voltage to ground a digital storage oscilloscope (DSO) is used. The primary side and secondary side current are metered with the help of clamp meter. The waveform of voltage before and after DC current injected is shown in figure 2 and figure 3 Fig. 2: Waveform on Primary Side of Transformer before DC Current is injected Fig. 3: Waveform on Secondary Side of Transformer after DC is injected into Transformer III. SIMULATION AND RESULT TO ANALYZE THE EFFECT OF GIC (DC) CURRENT ON THREE PHASE TRANSFORMERS The simulink model consist of a transformer with three phase saturable transformer, resistive load, Bus bar B1and B2, current and voltage measurement meter to measure current and voltage in respective phase, DC voltage source to produce DC current in order to simulate GIC effect.
  • 3. A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer (IJIRST/ Volume 3 / Issue 07/ 001) All rights reserved by www.ijirst.org 3 Figure 4 shows simulation model to analyze the effect of GIC (DC) on transformer using simulation on MATLAB. Three phase saturable transformer is designed with a voltage of 440V in the primary and the secondary voltage of 12V, and a resistive load. The aim of this is to evaluate the effect of GIC with the transformer operating with DC. The rating of three phase transformers is a 12VA, 50 Hz. The line voltage of primary winding is 400 V & line voltage of secondary winding is 12V. Fig. 4: Simulink Model of Transformer with effect of GIC (DC) Fig. 5: Flux-Current Characteristics of Transformer
  • 4. A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer (IJIRST/ Volume 3 / Issue 07/ 001) All rights reserved by www.ijirst.org 4 Fig. 6: Hysteresis Curve of Transformer When DC current is induced in Transformer by Power GUI Tool Fig. 7: Iexc Saturation Current of Transformer Fig. 8: Neutral Current When DC is induced at Secondary Side of Transformer 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 -3.5 -3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1 1.5 x 10 -3 Time NeutralCurrent
  • 5. A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer (IJIRST/ Volume 3 / Issue 07/ 001) All rights reserved by www.ijirst.org 5 Fig. 9: Active and Reactive Power Compensation of Transformer Fig. 11: FFT Analysis in Current when DC is Induced in Secondary Star connected Transformer IV. CONCLUSION The simulations of GIC using a three phase saturable transformer model shows 1) Reactive power consumption is increasing from 0 to 0.02 m sec and after 0.02 m sec it becomes constant while the active power of transformer decreases from 0 to 0.02 m sec and thereafter it becomes constant. 2) The neutral current fluctuations are observed predominantly as the DC is injected into the neutral of the saturable transformer. 3) The fluctuating harmonics in neutral current using power GUI FFT tool is found to be 0.03%. 4) The fluctuating harmonics is also found in the excitation current of transformer. 5) The B-H curve is also plotted and the area of the curve increases which shows the hysteresis losses are proportionally increasing as DC current is being increased. The hardware and simulation model has given the results which will be of immense importances to the practical field engineers. Further studies could observe effects which happen in a bigger scaled power transformer leading to damages of the insulation or even to failures occurring after GIC events. Further investigations about these phenomena on large scaled setups shall be followed and the scalability of the setup needs to be investigated. 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18 0.2 -5 0 5 10 15 20 25 30 35 40 45 Time ActiveandReactivePowerConsumption ActiveandReactivePowerConsumption ReactivePower ActivePower
  • 6. A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer (IJIRST/ Volume 3 / Issue 07/ 001) All rights reserved by www.ijirst.org 6 REFERENCES [1] Jon Berge, Luis Marti, Rajiv K. Varma,” Modeling and Mitigation of Geomagnetically Induced Currents on a Realistic Power System Network”, IEEE Electrical Power and Energy Conference (2011) [2] Baris Kovan, Francisco de León,” Mitigation of Geomagnetically Induced Currents by Neutral Switching”, IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 4, AUGUST 2015 [3] F. R. Faxvog, W. Jensen, G. Fuchs, G. Nordling, D. B. Jackson, B. Groh, N. Ruehl, A.P. Vitols, T. L. Volkmann, M.R. Rooney, Russell Neal,” Power Grid Protection against Geomagnetic Disturbances (GMD)”, 2013 IEEE Electrical Power & Energy Conferenc (EPEC) 978-1-4799-0106-7/13/$31.00 ©2013 IEEE. [4] Philip R. Price,” Geomagnetically Induced Current Effects on Transformers” IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 [5] A.D. Rajapakse, N. Perera, F. R. Faxvog, W. Jensen, G. Nordling, G. Fuchs, D. B. Jackson, T. L. Volkmann, N. Ruehl, B. Groh,” Power Grid Stability Protection against GIC Using a Capacitive Grounding Circuit. [6] José Ramírez-Ni˜no, Carlos Haro-Hernández, Joaquín Héctor Rodriguez-Rodriguez, Rito Mijarez,” Core saturation effects of geomagnetic induced currents in power transformers“Journal of Applied Research and Technology