SlideShare a Scribd company logo
1 of 155
BUILDING ENERGY CODES UNIVERSITY




ANSI/ASHRAE/IES
Standard 90.1-2010 HVAC
                                   Erik chiang
                                                                        1
April 2011 – PNNL-SA-80143
                                                 www.energycodes.gov/BECU
HVAC Compliance

 Building System         Compliance Options


                                    Prescriptive
   Envelope
                                      Option

                   Mandatory
    HVAC
                   Provisions        Trade Off
                                                   Energy Code
               (required for most     Option       Compliance
     SWH      compliance options)


                                    Energy Cost
    Power
                                      Budget

   Lighting
                                     Simplified
    Other

                                                                           2

                                                    www.energycodes.gov/BECU
Section 6 – 6.1.1
HVAC Scope


 9 New Buildings
 9 Additions to Existing Buildings
 9 Alterations in Existing Buildings




                                                              3

                                       www.energycodes.gov/BECU
Section 6 – 6.1.1.3
HVAC Alterations Scope

  9 Equipment
      – New equipment shall meet the minimum efficiency requirements
      –
  9 Cooling systems
      – New cooling systems installed to serve previously uncooled spaces
        shall comply with this section

      – Alterations to existing cooling systems shall not decrease economizer
        capacity (unless economizer tradeoff is used)
                                                (                      )
  9 Ductwork
      – New and replacement ductwork shall comply with applicable
        requirements
      –
  9 Piping
      – New and replacement piping shall comply with applicable requirements




                                                                                          4

                                                                   www.energycodes.gov/BECU
Section 6 – 6.1.1.3
HVAC Alterations

  Alterations to the building HVAC system shall comply with
  the requirements of Section 6
                               6
      9 Exceptions that are allowed:               ,
         – Equipment being modified or repaired (not replaced)
                            (         )
             • provided such modifications will not result in an increase in the
               annual energy consumption

         – Equipment being replaced or altered which requires extensive
           revisions to other systems and such replaced or altered equipment
           is a like-for-like replacement
                                                       ,

         – Refrigerant change of existing equipment
         – Relocation of existing equipment
         – Ducts and pipes where there is insufficient space or access to meet
           these requirements                                                              5

                                                                    www.energycodes.gov/BECU
Section 6 – 6.2
HVAC Compliance Paths


  9 You have to follow Sections
     – 6.1 General,
     – 6.7 Submittals, and
     – 6.8 Minimum Equipment Efficiency
  9 And then you can follow either
     – Section 6.3 Simplified Approach OR
         6.3           ,
     – Sections 6.4 Mandatory Provisions and 6.5 Prescriptive Path
         6.4                 6.5
  9 Alternatively, you can follow Section 11 (ECB), in which
    case Section 6.4 is mandatory
              ,           11 (                ),    6.4

                                                                                 6

                                                          www.energycodes.gov/BECU
Section 6 – 6.3
Simplified Approach Option


  The simplified approach is an optional path for compliance
  when the following are met:
                    ,
      9 Buildings with 1 or 2 stories 1 2
      9 Buildings with gross floor area < 25,000 ft2
                         < 25,000 ft2
      9 System serving single HVAC zone

      9 Unitary packaged or split air
        conditioners (air-cooled or
        evaporatily cooled)
                                (
                    )

                                                                              7

                                                       www.energycodes.gov/BECU
Section 6 – 6.3
Simplified Approach Criteria

  a.   Single HVAC zone
  b.   Single zone VAV controls (6.4.3.10)         VAV
  c.   Cooling equipment efficiency (6.8.1)
  d.   Air economizers (6.5.1)
  e.   Heating equipment efficiency (6.8.1)
  f.   Exhaust air energy recovery (6.5.6.1)
  g.   Dual set point thermostat or manual changeover
  h.   Heat pump auxiliary heat control
  i.   No reheat or simultaneous cooling and heating for humidity control
  j.   Off-hour shutoff and temperature setback/setup
       setback/setup
  k.   Piping insulation (Tables 6.8.3A and 6.8.3B)
  l.   Ductwork insulation and sealing (6.4.4.2.1)
  m.   Air balancing of ducted system
  n.   Outdoor air intake and exhaust systems (6.4.3.4)
  o.   Zone thermostatic controls to prevent simultaneous heating and cooling
  p.   Optimum start controls
  q.   Demand control ventilation (6.4.3.9)


                                                                                               8

                                                                        www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls

9 Supply fans controlled by two-speed motors or variable-speed drives

    –   Air-handling and fan coil units with chilled-water cooling coils

    –   Supply fans with motors • 5 hp
                 >=5hp
9 At cooling demands ” 50%, supply fan controls able to reduce airflow to
  no greater than the LARGER of
              <=50%,
    – ½ of the full fan speed OR
                   1/2       ,
    – volume of outdoor air required to meet Standard 62.1 On and after
        January 1, 2012
             62.1                     2012.1.1       ,



                                                                                                  9

                                                                           www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls

9 Supply fans controlled by two-speed motors or variable speed drives

    – all AC equipment and air-handling units with direct expansion cooling and
      cooling capacity at AHRI conditions • 110,000 Btu/h serving single zones
                                                             AHRI
           >=110,000Btu/h
9 At control demands

    – 2/3 of the full fan speed OR
                   2/3
    – volume of outdoor air required to meet Standard 62.1
           62.1




                                                                                        10

                                                                  www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls (cont’d)




                                                          11

                                    www.energycodes.gov/BECU
Section 6 – 6.8.1A (6.3.2c)
Equipment Efficiency




           Reference Tables 6.8.1A, 6.81B and 6.8.1.D in 90.1-2010
                90.1-2010 , 6.8.1A, 6.8.1B, 6.8.1D




                                                                                       12

                                                                 www.energycodes.gov/BECU
Section 6 – 6.3.2
Economizers


 The system shall have an economizer, unless the economizer
 Trade-off Option is used
                  ,
    9 Limited to unitary systems
    9 Requires higher minimum cooling efficiency (EER)
                             (EER)
    9 Trade-off EER by EER
        – System size
        – Climate zone




                                                                               13

                                                         www.energycodes.gov/BECU
Section 6 – 6.3.2
Economizers




          Reference Table 6.3.2 on page 40 in 90.1-2010




                                                                                14

                                                          www.energycodes.gov/BECU
Section 6 – 6.5.1 (6.3.2d)
Economizers (cont’d)


  9 Climate and size dependent (Tables 6.5.1A and B)
                       (   6.5.1A   B)
  9 There are LOTS of exception

  9 Can use air economizers

      – 100% of design supply air 100%
      – Sequenced with mechanical cooling equipment

      – High limit shutoff
      – Dampers



                                                                             15

                                                       www.energycodes.gov/BECU
Section 6 – 6.5.1 (6.3.2d)
Economizer Exceptions

 Exceptions
     9 Systems with gas phase air cleaning per Standard 62.1
         62.1
     9 Where >75% of the air must be humidified >35 Fdp
            75%        >35 Fdp
     9 Systems with condenser heat recovery per 6.5.6.2.2a or
       6.5.6.2.2b 6.5.6.2.2a 6.5.6.2.2b
     9 Residential systems <5X limits in Table 6.5.1A         <
       6.5.1A 5
     9 Systems with a balance point <=60 F            <= 60 F
     9 Systems expected to operate < 20hrs/wk                   20hr
     9 Systems serving zones with refrigerated casework



                                                                               16

                                                         www.energycodes.gov/BECU
Section 6 – 6.5.1 (6.3.2d)
Economizer Exceptions (cont’d)

  Exceptions
      9 Where comfort cooling efficiency meets or exceeds Table 6.3.2
                                   6.3.2
      9 Systems serving computer rooms under certain conditions
                    ,




                                                                                 17

                                                           www.energycodes.gov/BECU
Section 6 – 6.3
Simplified Approach Option (cont’d)


  9 Manual changeover or dual set-point thermostat

  9 Heat pump supplementary control

  9 No reheat or simultaneous heating and cooling for
    humidity control

  9 Time clocks (except hotel/motel guest rooms and
    systems requiring continuous operation)
           (    /                                            )


                                                                        18

                                                  www.energycodes.gov/BECU
Section 6 – 6.3
Simplified Approach Option (cont’d)


  9 Balancing of ducted systems

  9 Outdoor air intake and exhaust systems

  9 Interlocked thermostats for separate heating and cooling

  9 System > 10,000 cfm:
         > 10,000 cfm
      – optimum start controls
      –
  9 Demand control ventilation


                                                                         19

                                                   www.energycodes.gov/BECU
Section 6 – 6.3
Simplified Approach Option (cont’d)



   Piping and ductwork/plenum insulated
              /




                                                                20

                                          www.energycodes.gov/BECU
Section 6 – 6.8.2B
Duct Insulation




           Reference Tables 6.8.2A and B on page 68 in 90.1-2010




                                                                                         21

                                                                   www.energycodes.gov/BECU
Section 6 – 6.4.4.1.3 (6.3.2k)
Piping Insulation

    Tables 6.8.3A and 6.8.3B

    Exceptions
       9 Factory-installed
       9 Piping conveying fluids
           – design operating temperature range between 60 F-105 F, inclusive
                                   60 F-105 F      ,
           – that haven’t been heated or cooled through the use of fossil fuels or
             electricity or where heat gain or heat loss will not increase energy
             usage
                                                 ,
       9 Hot water piping between shut off valve and coil, not > 4 ft in length,
         when located in conditioned spaces
                           ,                                         4ft
       9 Piping ” 1 in.      <= 1 in.
           – No insulation required for strainers, control values, and balancing
             values
                    ,       ,

                                                                                           22

                                                                     www.energycodes.gov/BECU
Section 6 – 6.8.3
Piping Insulation




              Reference Tables 6.8.3A and B on page 69 in 90.1-2010




                                                                                            23

                                                                      www.energycodes.gov/BECU
Section 6 – 6.5.6.1 (6.3.2f)
Exhaust Air Energy Recovery


 Required if:
     9 Supply air capacity • value listed in Table 6.5.6.1
              >= 6.5.6.1
         – Values are based on climate zone and % of outdoor air flow rate at
           design conditions




 Recovery system effectiveness • 50%
              >= 50%




                                                                                       24

                                                                 www.energycodes.gov/BECU
Section 6 – 6.5.6.1 (6.3.2f)
Exhaust Air Energy Recovery Exceptions


 9 Lab systems meeting 6.5.7.2
        6.5.7.2
 9 Systems serving uncooled spaces that are heated to < 60 F
                                 < 60 F
 9 Systems exhausting toxic, flammable, paint or corrosive fumes
   or dust
                ,     ,
 9 Commercial kitchen hoods used for collecting grease or smoke

 9 Where > 60% of outdoor heating energy is provided from site-
   recovered or site solar energy
                   > 60%,
 9 Heating energy recovery in climate zones 1 and 2
          1 2
 9 Cooling energy recovery in climate zones 3c, 4c, 5b, 5c, 6b, 7,
   and 8
          3c, 4c, 5b, 5c, 6b, 7 8
                                                                             25

                                                       www.energycodes.gov/BECU
Section 6 – 6.5.6.1 (6.3.2f)
Exhaust Air Energy Recovery Exceptions


 9 Where largest exhaust source is < 75% of the design outdoor
   airflow
                  < 75%
 9 Systems requiring dehumidification that employ energy
   recovery in series with the cooling coil
                 ,
 9 Systems operating < 20 hrs/week at outdoor air % in Table
   6.5.6.1
         6.5.6.1                ,                20hr,




                                                                          26

                                                    www.energycodes.gov/BECU
Section 6 – 6.8.2B (6.3.2l)
Duct & Plenum Insulation




            Reference Table 6.8.2B on page 68 in 90.1-2010




                                                                                   27

                                                             www.energycodes.gov/BECU
Section 6 – 6.4.3.9 (6.3.2q)
Demand Control Ventilation


DCV must be provided for each zone with a area > 500 ft² and
the design occupancy > 40 people/1000 ft² where the HVAC
system has:
     >500 ft²               >40 /1000 ft² ,
      ,
    9 An air-side economizer,
    9 Automatic modulating control of the OSA dampers, or
                    ,
    9 A design outdoor airflow
      > 3,000 cfm
                     > 3000 cfm

      Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction
      of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less
                                                than design occupancy.
                                                                                                                         28

                                                                                                   www.energycodes.gov/BECU
HVAC Compliance

 Building System         Compliance Options


                                    Prescriptive
   Envelope
                                      Option

                   Mandatory
    HVAC
                   Provisions        Trade Off
                                                   Energy Code
               (required for most     Option       Compliance
     SWH      compliance options)


                                    Energy Cost
    Power
                                      Budget

   Lighting
                                     Simplified
    Other

                                                                          29

                                                    www.energycodes.gov/BECU
Section 6 – 6.4
HVAC Mandatory Provisions


  9 Minimum Equipment Efficiency (Section 6.4.1)

  9 Calculations (Section 6.4.2)

  9 Controls (Section 6.4.3)

  9 HVAC System Construction and Insulation (Section 6.4.4)




                                                                         30

                                                   www.energycodes.gov/BECU
Section 6 – 6.4.1.1
Minimum Equipment Efficiency


  HVAC Equipment Covered

     9 Air conditioners and condensing units

     9 Heat pumps (air, water, and ground source)
           ( ,               )
     9 Water-chilling packages (chillers)

     9 Packaged terminal and room air conditioners and heat pumps

     9 Furnaces, duct furnaces and unit heaters
               ,
     9 Boilers

     9 Heat rejection equipment (cooling towers)
                 (         )
                                                                                 31

                                                           www.energycodes.gov/BECU
Section 6 – 6.4.1.1
Minimum Equipment Efficiency (cont’d)


  HVAC Equipment Covered

      9 Heat transfer equipment (heat exchangers)
                      (         )
      9 Variable refrigerant flow (VRF) air conditioners

      9 VRF air-to-air and applied heat pumps

      9 Air conditioners serving computer rooms




                                                                                 32

                                                           www.energycodes.gov/BECU
Section 6 – 6.4.1.4
Verification of Equipment Efficiencies


  Equipment efficiency information from manufacturers verified as
  follows
                                            ,
    9 EPACT equipment – to comply with DOE certification requirements
              (EPACT)               –                   (DOE)
    9 If certification program exists for covered product and includes provisions
      for verification and challenge of equipment efficiency ratings, product listed
      in program OR
                                        ,
              ,                                 ,
    9 If product not listed in program, ratings verified by an independent
      laboratory test report OR
                                                    ,
              ,


                                                                                               33

                                                                         www.energycodes.gov/BECU
Section 6 – 6.4.1.4
Verification of Equipment Efficiencies (cont’d)


     9 If no certification program exists, equipment efficiency ratings
       supported by data furnished by manufacturer OR
                                               ,
                           ,
     9 Where components from different manufacturers are used, system
       designer specifies components whose combined efficiency meets
       Section 6.4.1
                                       ,
                               6.4.1
     9 Requirements for plate type liquid-to-liquid heat exchangers listed
       in Table 6.8.1H
              -                            ,       6.8.1H



                                                                                         34

                                                                   www.energycodes.gov/BECU
Section 6 – 6.4.1.5
Labeling


  Mechanical equipment (6.4.1.5.1) – equipment not
  covered by NAECA to have a permanent label stating
  equipment complies with 90.1
            (6.4.1.5.1) –           NAECA
                             90.1
  ( NAECA                            )




                                                                   35

                                             www.energycodes.gov/BECU
Section 6 – 6.4.1.5
Labeling


  Packaged terminal air conditioners (6.4.1.5.2) –
  packaged terminal air conditioners and heat pumps
  with sleeve sizes < 16 in. high and 42 in. wide with a
  cross-sectional area < 670 in2 to be factory labeled as
  follows:
                       (6.4.1.5.2) –
            16           42                      670             ,
                         :
      9 Manufactured for nonstandard size applications only: not to be
        installed in new construction projects
                                :


                                                                                  36

                                                            www.energycodes.gov/BECU
Section 6 – 6.4.2.1
Load Calculations




  Must calculate heating and
  cooling system design loads



  Must determine calculations with
  ANSI/ASHRAE/ACCA Standard
  183-2007
          ASHRAE Std. 183



                                                           37

                                     www.energycodes.gov/BECU
Section 6 – 6.4.2.2
Pump Head



  • When sizing pumps, head to be determined in
    accordance with generally accepted engineering
    standards/handbooks
  • Method must be approved by the authority having
    jurisdiction

  • Must calculate the pressure drop through each device
    and pipe segment in the critical circuit at design
    conditions
  •              ,


                                                                       38

                                                 www.energycodes.gov/BECU
Section 6 – 6.4.3.1
Controls – Zone Thermostatic & Dead Band



  Required for each zone
     9 Perimeter can be treated differently


  Dead band controls
     9 Thermostats must have at least a 5 F dead band
                        5F
     9 Exceptions
         – Thermostats that require manual changeover between heating and
           cooling modes

         – Special occupancy or applications where wide temperature ranges
           aren’t acceptable (e.g., retirement homes) and approved by
           adopting authority
                              ,                             ( ;       )

                                                                                     39

                                                               www.energycodes.gov/BECU
Section 6 – 6.4.3.2
Controls – Setpoint Overlap Restriction


  If limit switches, mechanical stops, or software
  programming for DDC systems are used
                  ,        , DDC
      9 means will be provided to prevent the heating setpoint from
        exceeding the cooling setpoint minus any applicable proportional
        band




                                                                                  40

                                                            www.energycodes.gov/BECU
Section 6 – 6.4.3.3
Controls – Off-Hour



  Temperature Control off-hour requirements

     9   Automatic shutdown
     9   Setback controls
     9   Optimum start
     9   Zone isolation
     9   Exceptions, HVAC systems
             ,
         – with heating/cooling capacity < 15,000 Btu/h
         –      /        < 15,000 Btu/h
         – intended to operate continuously
         –




                                                                                41

                                                          www.energycodes.gov/BECU
Section 6 – 6.4.3.3.1
Controls - Automatic Shutdown


  Automatic 7-day/week time clock with 10-hour battery backup
      10
      9 Exception: 2-day/week thermostat for residential applications
           :           ,
  Each control to have

      9 Occupant sensor, OR             ,
      9 Manually-operated timer with maximum two hour duration, OR
                     ,                      ,
      9 Security system interlock

  Exception
      9 Residential occupancies allowed to operate with only 2 different
        time schedules/wk



                                                                                      42

                                                                www.energycodes.gov/BECU
Section 6 – 6.4.3.3.2
Controls - Setback


  Climate Zones 2-8
      9 Lower heating setpoint to 55ºF or less
                            55ºF


  Climate Zones 1b, 2b, 3b (hot/dry)
      9 Automatically restart, temporarily operate
                     ,
         – Raise cooling setpoint to 90ºF or higher OR
                             90ºF
         – Prevent high space humidity levels




                                                                               43

                                                         www.energycodes.gov/BECU
Section 6 – 6.4.3.3.3
Controls - Optimum Start


  Individual heating and cooling air distribution
  systems with
                                  ,
      9 Total design supply air capacity > 10,000 cfm
                      > 10,000 cfm
      9 Served by one or more supply fans


  Control algorithm to at least be a function of

      9 Difference between space temperature and
        occupied setpoint and amount of time prior to
        scheduled occupancy
                 ,
                                                                              44

                                                        www.energycodes.gov/BECU
Section 6 – 6.4.3.3.4
Controls - Zone Isolation

  Applies to
      9 Each floor in a multistory building
      9 Maximum 25,000 ft2 zone on one floor
        25,000ft2
  Requirements
      9 Isolation devices to shut off outdoor and exhaust airflow when >
        5,000 cfm                      >5,000cfm ,
      9 Central systems shall be capable of stable operation with one
        isolation zone
      9 Capable of separate time schedules for each isolation zone



        Figure 6-E
        Isolation Methods for a Central VAV System
        (User’s Manual – 90.1.-2007)


                                                                                   45

                                                             www.energycodes.gov/BECU
Section 6 – 6.4.3.4
Controls – Ventilation System


  Stair and Shaft Vent dampers (6.4.3.4.1)
  9Automatically closed during normal building operation

  9Interlocked to open as required by fire and smoke detection systems


  Shutoff Damper Controls (6.4.3.4.2)
      9 All outdoor air intake and exhaust systems require motorized damper

      9 Ventilation outdoor air and exhaust/relief dampers capable of automatically
        shutting off during
                         /                    ,
          – Preoccupancy building warm-up, cool down, and setback
                                     ,
            (Except when ventilation reduces energy costs or when ventilation must be
            supplied due to code requirements)
             (                                            ,    .)



                                                                                                   46

                                                                             www.energycodes.gov/BECU
Section 6 – 6.4.3.4
Controls – Ventilation System (cont’d)


  9Exceptions:
        9 Backdraft gravity dampers okay
                                   (BDD)
              – For exhaust and relief in buildings < 3 stories in height above grade
                 3
              – Of any height in climate zones 1 – 3
                          1, 2, 3
        9 Ventilation systems serving unconditioned spaces

          –   300 CFM




                                                                                             47

                                                                       www.energycodes.gov/BECU
Section 6 – 6.4.3.4.3
Controls - Damper Leakage


 Table 6.4.3.4.3 provides maximum leakage rates for
 outdoor air supply and exhaust dampers
 Table 6.4.3.4.3
 Where OA supply and exhaust air dampers are required by
 Section 6.4.3.4
                              6.4.3.4
     9 They shall have a maximum leakage rate when tested in
       accordance with AMCA Standard 500 as indicated in Table
       6.4.3.4.3
                             AMCA
       Standard 500,
            Table 6.4.3.4.3.

                                                                               48

                                                         www.energycodes.gov/BECU
Section 6 – 6.4.3.4.3
Controls - Damper Leakage


      Table 6.4.3.4.3. Maximum Damper Leakage, cfm per ft2 at 1.0 in. w.g.
                            Ventilation Air Intake                  Exhaust / Reflief
     Climate Zones   Non-motorized1           Motorized   Non-motorized1           Motorized



          1, 2             -                     -              -                       -
       any heigh          20                     4             20                       4

           3               -                      -             -                        -
       any heigh          20                     10            20                       10

        4,5b,5c             -                     -              -                       -
      < 3 stories     not allowed                10             20                      10
      >=3 stories     not allowed                10        not allowed                  10


       5a,6,7,8             -                    -               -                      -
      < 3 stories     not allowed                4              20                      4
      >=3 stories     not allowed                4         not allowed                  4




                                                                                                      49

                                                                                www.energycodes.gov/BECU
Section 6 – 6.4.3.4.4
Ventilation Fan Controls


  Fans with motors > 0.75 hp shall have automatic controls
  complying with Section 6.4.3.3.1 that are capable of
  shutting off fans when not required
                 0.75 hp ,            6.4.3.3.1          ,
                   ,

  Exception
      9 HVAC systems intended to operate continuously




                                                                              50

                                                        www.energycodes.gov/BECU
Section 6 – 6.4.3.4.5
Enclosed Parking Garage Ventilation


  Ventilation systems in enclosed parking garages

  9automatically detect contaminant levels and stage fans or

  9modulate fan airflow rates to ” 50%, provided acceptable
   contaminant levels are maintained
                     50%
  Exception
     9 Garages < 30,000 ft2 with ventilation systems that don’t use
       mechanical cooling or heating
                            30,000 ft2
      9 Garages with a garage area to ventilation system motor nameplate
        hp ratio > 1500 ft2/hp and don’t use mechanical cooling or heating
                                         1500 ft2/hp,

      9 Where permitted by AHJ


                                                                                     51

                                                               www.energycodes.gov/BECU
Section 6 – 6.4.3.5
Heat Pump Auxiliary Heat Control



  Controls to prevent supplementary heat when heat pump
  can handle the load
                                ,

  Exception
  9Heat pumps
         – With minimum efficiency regulated by NAECA
                                             (NAECA)
         – With HSPF rating meeting Table 6.8.1B (Includes all usage of
           internal electric resistance heating)
                     Table 6.8.1B         (                          )



                                                                                       52

                                                                 www.energycodes.gov/BECU
Section 6 – 6.4.3.6
Controls - Humidifier Preheat



    Automatic valve to shut off preheat when humidification isn’t required
                                   ,




                                                                                    53

                                                              www.energycodes.gov/BECU
Section 6 – 6.4.3.7
Controls - Humidification and Dehumidification


 Provide means to prevent simultaneous
 operation of humidification and
 dehumidification equipment

      9 Limit switches, mechanical stops, or
        software programming (DDC systems)


 Exceptions
      9 Zones served by desiccant systems, used
        with direct evaporative cooling in series

      9 Systems serving zones where specific
        humidity levels are required and approved
        by jurisdiction

          – Museums and hospitals
                 ,

                                                                          54

                                                    www.energycodes.gov/BECU
Section 6 – 6.4.3.8
Controls - Freeze Protection and Snow/Ice


  Automatic controls for
          ,
      9 Freeze protection systems

          – outside air temperatures > 40 F or when conditions of protected
            fluid will prevent freezing
                                 40oF
      9 Snow- and ice-melting systems

          – pavement temperature > 50 F and no precipitation is falling and
            outdoor temperature > 40 F
                        50oF                                              40oF



                                                                                         55

                                                                   www.energycodes.gov/BECU
Section 6 – 6.4.3.9 (6.3.2q)
Demand Control Ventilation


DCV must be provided for each zone with a area > 500 ft² and
the design occupancy > 40 people/1000 ft² where the HVAC
system has:
     >500 ft²               >40 /1000 ft² ,
      ,
    9 An air-side economizer,
    9 Automatic modulating control of the OSA dampers, or
                    ,
    9 A design outdoor airflow
      > 3,000 cfm
                     > 3000 cfm

      Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction
      of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less
                                                than design occupancy.
                                                                                                                         56

                                                                                                   www.energycodes.gov/BECU
Section 6 – 6.4.3.9
Demand Control Ventilation (cont’d)


  Exceptions :
      9 System with energy recovery complying with 6.5.6.1
                                6.5.6.1
      9 Multiple-zone systems without DDC of individual zones
        communicating with a central control panel
                                      DDC
      9 Systems with a design outdoor airflow less than 1200 cfm
                             1200cfm
      9 Spaces where the supply airflow rate minus any makeup or
        outgoing transfer air requirement is less than 1200 cfm
                                                              1200cfm




                                                                                  57

                                                            www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls

9 Supply fans controlled by two-speed motors or variable-speed drives

    –   Air-handling and fan coil units with chilled-water cooling coils

    –   Supply fans with motors • 5 hp
                 >=5hp
9 At cooling demands ” 50%, supply fan controls able to reduce airflow to
  no greater than the LARGER of
              <=50%,
    – ½ of the full fan speed OR
                   1/2       ,
    – volume of outdoor air required to meet Standard 62.1 On and after
        January 1, 2012
             62.1                     2012.1.1       ,



                                                                                                 58

                                                                           www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls

9 Supply fans controlled by two-speed motors or variable speed drives

    – all AC equipment and air-handling units with direct expansion cooling and
      cooling capacity at AHRI conditions • 110,000 Btu/h serving single zones
                                                             AHRI
           >=110,000Btu/h
9 At control demands

    – 2/3 of the full fan speed OR
                   2/3
    – volume of outdoor air required to meet Standard 62.1
           62.1




                                                                                        59

                                                                  www.energycodes.gov/BECU
Section 6 – 6.4.3.10 (6.3.2b)
Single Zone VAV Controls (cont’d)




                                                          60

                                    www.energycodes.gov/BECU
Section 6 – 6.4.4
HVAC System Construction and Insulation

  9 Insulation installed in accordance with industry-accepted standards

  9 Insulation protection

  9 Duct and plenum insulation

  9 Piping insulation

  9 Sensible heating panel insulation

  9 Radiant floor heating

  9 Duct sealing

  9 Duct leakage tests


                                                                                            61

                                                                      www.energycodes.gov/BECU
Section 6 – 6.4.4.1.1
General


 Insulation installed in accordance with industry-accepted standards

 Insulation

     9 Protected from damage due to sunlight, moisture, equipment
       maintenance, and wind
             ,      ,
     9 Exposed to weather to be suitable for outdoor service
                  ,
     9 Covering chilled water piping, refrigerant suction piping, or cooling ducts
       located outside the conditioned space to include a vapor retardant
       located outside the insulation, all penetrations and joints of which to be
       sealed
                                   ,                                         ,
                       ,
                                                                                          62

                                                                    www.energycodes.gov/BECU
Section 6 – 6.4.4.1.2
Duct and Plenum Insulation

  All supply and return ducts and plenums to be insulated per Tables 6.8.2A
  and 6.8.2B
              ,                         6.8.2A 6.8.2B
  Exceptions
      9 Factory-installed plenums, casings, or ductwork furnished as part of HVAC
        equipment
                        ,            ,
      9 Ducts located in heated, semiheated, or cooled spaces
                           ,
      9 For runouts < 10 ft in length to air terminals or air outlets, the R-value need
        not exceed R-3.5
                                          10 ft,                       R-3.5
      9 Backs of air outlets and outlet plenums exposed to unconditioned or indirectly
        conditioned spaces with face areas > 5 ft2 need not exceed R-2; those ” 5 ft2
        need not be insulated
                                                                   5 ft2
             R-2;      ( ) 5 ft2




                                                                                                 63

                                                                           www.energycodes.gov/BECU
Section 6 – 6.4.4.1.3 (6.3.2k)
Piping Insulation

    Tables 6.8.3A and 6.8.3B

    Exceptions
       9 Factory-installed
       9 Piping conveying fluids
           – design operating temperature range between 60 F-105 F, inclusive
                                   60 F-105 F      ,
           – that haven’t been heated or cooled through the use of fossil fuels or
             electricity or where heat gain or heat loss will not increase energy
             usage
                                                 ,
       9 Hot water piping between shut off valve and coil, not > 4 ft in length,
         when located in conditioned spaces
                           ,                                         4ft
       9 Piping ” 1 in.      <= 1 in.
           – No insulation required for strainers, control values, and balancing
             values
                    ,       ,

                                                                                           64

                                                                     www.energycodes.gov/BECU
Section 6 – 6.4.4.2.1
Duct Sealing


  Ductwork and all plenums with
  pressure class ratings shall be
  constructed to

    ,
        9 seal class A, as required to
          meet the requirements of
          6.4.4.2.2
            class A               ,
          6.4.4.2.2
        9 standard industry practice




                                                               65

                                         www.energycodes.gov/BECU
Section 6 – 6.4.4.2.2
Duct Leakage Tests

  Designed > 3 in. w.c. and all ductwork
  located outdoors
               3 in.
      9 Leak tested

      9 Representative sections • 25% of
        the total installed duct area shall
        be tested
          25%( )
      9 Ratings > 3 in. w.c. to be
        identified on drawings
                            3 in.,

      9 Maximum permitted duct leakage

          – Lmax = CLP0.65
              • Where Lmax = maximum
                 permitted leakage in
                 cfm/100 ft2 duct surface
                 area
              • CL = 6 cfm/100ft2 duct
                 surface area at 1 in. wc
              • P = test pressure in. wc.                           66

                                              www.energycodes.gov/BECU
HVAC Compliance - Prescriptive

  Building System         Compliance Options


                                     Prescriptive
    Envelope
                                       Option

                    Mandatory
     HVAC
                    Provisions        Trade Off
                                                    Energy Code
                (required for most     Option       Compliance
      SWH      compliance options)


                                     Energy Cost
     Power
                                       Budget

    Lighting
                                      Simplified
     Other

                                                                           67

                                                     www.energycodes.gov/BECU
Section 6 – 6.5
HVAC Prescriptive Path


 9 Economizers (Section 6.5.1)

 9 Simultaneous Heating and Cooling Limitation (Section 6.5.2)

 9 Air System Design and Control (Section 6.5.3)

 9 Hydronic System Design and Control (Section 6.5.4)

 9 Heat Rejection Equipment (Section 6.5.5)

 9 Energy Recovery (Section 6.5.6)

 9 Exhaust Systems (Section 6.5.7)

 9 Radiant Heating Systems (Section 6.5.8)

 9 Hot Gas Bypass Limitation (Section 6.5.9)

                                                                                       68

                                                                 www.energycodes.gov/BECU
Section 6 – 6.5.1.1.2
Control Signal


  Dampers capable of being sequenced with the mechanical
  cooling equipment and shall not be controlled by only
  mixed air temperature
                                       ,



  Exception
      9 Systems controlled from space temperature (such as single-
        zone systems)
                              (             )




                                                                                 69

                                                           www.energycodes.gov/BECU
Section 6 – 6.5.1.1.3
High Limit Shutoff


  9 Automatically reduce outdoor air intake to minimum
    outdoor air quantity when outdoor air intake will no
    longer reduce cooling energy usage
                                                ,

  9 Control types for specific climates from Table 6.5.1.1.3A
         6.5.1.1.3A.               ,
  9 Settings from Table 6.5.1.1.3B




                                                                          70

                                                    www.energycodes.gov/BECU
Section 6 – 6.5.1.1.3A
High-limit Shutoff Control Options



   Table 6.5.1.1.3A. High-Limit Shutoff Controls Options for Air Economizers
                  Climate                      Allowed Control        Prohibited Control Types
                   Zones                             Types
    1b, 2b, 3b, 3c, 4b, 4c, 5b, 5c, 6b, 7,       Fixed Dry Bulb            Fixed Enthalpy
                      8                       Differential Dry Bulb
                                              Electronic Enthalpya
                                              Differential Enthalpy
                                             DP & DB Temperature
               1a, 2a, 3a, 4a                    Fixed Dry Bulb             Fixed Dry Bulb
                                                 Fixed Enthalpy          Differential Dry Bulb
                                              Differential Enthalpy
                                             DP & DB Temperature
                   5a, 6a                        Fixed Dry Bulb
                                              Differential Dry Bulb
                                                 Fixed Enthalpy
                                              Electronic Enthalpya
                                              Differential Enthalpy
                                             DP & DB Temperature




                                                                                                         71

                                                                                   www.energycodes.gov/BECU
Section 6 – 6.5.1.1.3B
High-limit Shutoff Control Settings



              Table 6.5.1.1.3B. High Limit Shutoff Control Setting for Air Economizers
                                              Required High Limit (Economizer Off When)
    Device Type            Climate
                                              Equation                        Description

                      1b, 2b, 3b, 3c, 4b,
                                              TOA>75oF               OA temperature exceeds 75oF
   Fixed Dry Bulb     4c, 5a, 5b, 5c, 6a,
                                              TOA>70oF               OA temperature exceeds 70oF
                           6b, 7, 8

                      1b, 2b, 3b, 3c, 4b,
   Differential Dry                                                OA temperature exceeds return air
                      4c, 5a, 5b, 5c, 6a,      TOA>TRA
         Bulb                                                               temperature
                           6b, 7, 8

                                                                    OA enthalpy exceeds 28 Btu/lb of
   Fixed Enthalpy     2a, 3a, 4a, 5a, 6a    hOA>28 Btu/lba
                                                                                dry aira
     Electronic                                                     OA temperature/RH exceeds the
                              All           (TOA,xRHOA)>A
     Enthalpy                                                             “A” setpoint curveb
     Differential                                                    OA enthalpy exceeds return air
                              All              hOA>hRA
      Enthalpy                                                                 enthalpy

                                                                     OA Dry Bulb exceeds 75oF or
      DP & DB                               DPOA>55oF or
                              All                                   Outside dew point exceeds 55oF
    Temperature                              TOA>75oF
                                                                               (65gr/lb)

                                                                                                           72

                                                                                     www.energycodes.gov/BECU
Section 6 – 6.5.1.1.4
Dampers


 Return, exhaust/relief and outdoor air dampers to meet the
 requirements in 6.4.3
     ,    /    ,                         6.4.3




                                                                        73

                                                  www.energycodes.gov/BECU
Section 6 – 6.5.1.1.5
Relief of Excess Outdoor Air


  Means to relieve excess outdoor air during economizer
  operation to prevent overpressurizing the building



  Outlet located to avoid recirculation into the building




                                                                             74

                                                       www.energycodes.gov/BECU
Section 6 – 6.5.1.2.1
Design Capacity – Water Economizers

 System capable of cooling supply air by indirect evaporation and
 providing up to 100% of expected system cooling load at outside air
 temperatures of 50 F dry bulb/45 F wet bulb and below
                                                   50oF/        45oF
            ,        100%

 Exception
     9 Systems primarily serving computer rooms

         – Where 100% of expected system cooling load at 40 F dry bulb/35 F wet
           bulb is met with evaporative water economizers
                             ,        40oF DB/35oF WB       100%
         – With dry cooler water economizers that satisfy 100% of expected system
           cooling load at 35 F dry bulb
                             ,        35oF DB      100%
     9 Dehumidification requirements that your design can meet 100% of
       expected cooling load at 45 F dry bulb/40 F wet bulb with evaporative
       water economizers
                         ,              45oF DB/40oF WB          100%
               .
                                                                                            75

                                                                      www.energycodes.gov/BECU
Section 6 – 6.5.1.2.2
Maximum Pressure Drop - Water Economizers



  Precooling coils and water-to-                                                                              Valve
                                                                                                              Closes
                                                                                                              In
                                                          Head                                                Economizer
  water heat exchangers to                                Pressure
                                                          Control
                                                          Valve                 In
                                                                                                              Mode

                                                                       Evaporator
  have either                                Cooling
                                             Tower
                                                                     Out
                                                                              Out            Primary
                                                                                             CHWP Secondary
                                                                                                         CHWP
                                                                       Condenser                           With
                                                                     In                   Heat          Variable
                                                                                          ExchangerSpeed Drive
                                                                        Chiller
                                               CWP


                                           Economizer CWP


     9 Water-side pressure drop of                                                                 2-Way
                                                                                                   Valve


       < 15 ft of water OR                                                           Typical
                                                                                     Cooling
                                                                                     Coil



                                                                                     Cooling

     9 Bypassed when not in use
                                                                                     Coil
                                                                                     With
                                                                                     Tertiary
                                                                                     Pump

                ,
                                                                                                           CHWS CHWR

                                     Figure 6-O from
                                     90.1 User’s Manual




                                                                                                                           76

                                                                                                www.energycodes.gov/BECU
Section 6 – 6.5.1.3
Integrated Economizer Control


  Economizers must be integrated with mechanical cooling
  systems and be capable of providing partial cooling even
  when additional mechanical cooling is required
                                                        ,




                                                                         77

                                                   www.energycodes.gov/BECU
Section 6 – 6.5.1.4
Economizer Heating System Impact


  Designed so economizer
  operation doesn’t increase the
  building heating energy use during
  normal operation
                  ,

  Exception
     9 Economizers on VAV systems that
       cause zone level heating to
       increase due to a reduction in
       supply air temperature
                (VAV)               ,
                           ,
                                                               78

                                         www.energycodes.gov/BECU
Section 6 – 6.5.2.1
Zone Thermostatic Controls


  Capable of operating in sequence the supply of heating and
  cooling energy to the zone

  Controls prevent
     9 Reheating

     9 Recooling

     9 Mixing or simultaneously supplying air previously heated or
       cooled

     9 Other simultaneous operation of heating and cooling systems to
       the same zone
                                                                                  79

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.2.1
Zone Thermostatic Controls – Exceptions


  Zones for which volume of air that is reheated, recooled, or
  mixed is less than the larger of the following
              ,
     9 30% of zone design peak supply
                                30%
     9 Outside air flow rate to meet 6.2 of Standard 62.1 for the zone
                         ASHRAE Std. 62.1 6.2
     9 Any higher rate that can be demonstrated to jurisdiction to reduce
       overall system annual energy usage

     9 Air flow rate required to meet applicable codes or accreditation
       standards (pressure relationships or minimum air change rates)
                                                 (                             )


                                                                                   80

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.2.1
Zone Thermostatic Controls – Exceptions (cont’d)


  Zones that comply with all of these

      9 Air flow rate in dead band that doesn’t exceed larger of these
                     ,
          •   20% of zone design peak supply
                                      20%
          •   Outdoor air flow rate to meet 6.2 of Standard 62.1 for the zone
                               ASHRAE Std. 62.1        6.2
          •   Any higher rate that can be demonstrated to jurisdiction to reduce overall system annual energy
              usage

      9 Air flow rate that’s reheated, recooled, or mixed in peak heating demand < 50% of zone design
        peak supply
              ,                                                                   50%
      9 Air flow between dead band and full heating or full cooling to be modulated

      9 Lab exhaust systems complying with 6.5.7.2
                                6.5.7.2
      9 Zones where • 75% of energy for reheating or providing warm air in mixing systems is from
        site-recovered or site-solar source
                                  75%

                                                                                                                 81

                                                                                           www.energycodes.gov/BECU
Section 6 – 6.5.2.1.1
Supply Air Temperature Reheat Limit


  Zones with both supply and return/exhaust air openings > 6
  ft above floor to not supply heating air > 20 F above space
  temperature
                 /                        6ft,
                      20oF
     9Applies in other parts of the Standard where reheating is allowed


  Exceptions
     9Laboratory exhaust systems complying with 6.5.7.2
                           6.5.7.2
     9During preoccupancy building warm-up and setback



                                                                                   82

                                                             www.energycodes.gov/BECU
Section 6 – 6.5.2.2
Hydronic System Controls



  To prevent the simultaneous heating and cooling in
  hydronic systems




                                                                        83

                                                  www.energycodes.gov/BECU
Section 6 – 6.5.2.2.1
Three-Pipe System


   No common return system for both hot and chilled water




                                                                       84

                                                 www.energycodes.gov/BECU
Section 6 – 6.5.2.2.2
Two-Pipe Changeover System




                                                                                   85
                             Diagram Courtesy of Ken Baker
                                                             www.energycodes.gov/BECU
Section 6 – 6.5.2.2.2
Two-Pipe Changeover System (cont’d)

  Two-pipe changeover system is allowed if it meets the following
  requirements:
               ,
      9 Dead band from one mode to another is • 15 F outdoor air
         temperature
                           15oF
      9 Controls to allow operation of • 4 hours in one mode before
         changing to another mode
                                           4
      9 Reset controls so heating and cooling supply temperatures at
         changeover point no more than 30 F apart
                 ,                                       30oF




                                                                                             86
                                       Diagram Courtesy of Ken Baker
                                                                       www.energycodes.gov/BECU
Section 6 – 6.5.2.2.3
Hydronic (Water Loop) Heat Pump Systems


                                          Diagram Courtesy of Ken Baker




                                                                                      87

                                                                www.energycodes.gov/BECU
Section 6 – 6.5.2.2.3
Hydronic (Water Loop) Heat Pump Systems (cont’d)

Controls to provide heat pump water supply temperature deadband of at
least 20 F between initiation of heat rejection and heat addition by central
devices
                                                                       20oF


Cooling tower bypass or cooling tower isolation dampers


A two-position valve at each hydronic heat pump for hydronic systems
having a total pump system power > 10 hp
                        10hp           ,

Exception
    9 If system loop temperature optimization controller is used, deadband < 20 F is
      allowed




                                                                                                88

                                                                          www.energycodes.gov/BECU
Section 6 – 6.5.2.3
Dehumidification


  Humidistatic controls to prevent

     9 Reheating

     9 Mixing of hot and cold air streams

     9 Heating and cooling of same air stream




                                                                      89

                                                www.energycodes.gov/BECU
Section 6 – 6.5.2.3
Dehumidification Exceptions


 9 Systems capable of reducing supply air flow to 50%, or to
   minimum ventilation
                          50%,
 9 Systems under 80,000 BTU/h that can unload at least 50%
           80,000 Btu/h,                  50%
 9 Systems smaller than 40,000 BTU/h
           40,000 Btu/h
 9 Process applications (exception does NOT apply to
   computer rooms)
            (              )
 9 75% of reheat or re-cool energy is recovered or solar
   75%
                                                                       90

                                                 www.energycodes.gov/BECU
Section 6 – 6.5.2.4
Humidification


Systems with hydronic cooling
                                                                                                 Valve

  and humidification systems                 Head
                                                                                                 Closes
                                                                                                 In
                                                                                                 Economizer
                                             Pressure                                            Mode
 designed to maintain inside                 Control
                                             Valve                 In
                                                          Evaporator
                                                                 Out
 humidity at > 35 F dewpoint       Cooling
                                   Tower
                                                        Out
                                                          Condenser
                                                                                Primary
                                                                                CHWP Secondary
                                                                                            CHWP
                                                                                              With
                                                        In                   Heat          Variable
temperature shall use a water        CWP
                                                           Chiller
                                                                             ExchangerSpeed Drive



economizer if required by 6.5.1   Economizer CWP


      6.5.1 ,                                                                         2-Way
                                                                                      Valve


        ,       35oF          ,                                         Typical
                                                                        Cooling
                                                                        Coil

                        ,                                               Cooling
                                                                        Coil
                                                                        With
                                                                        Tertiary
                                                                        Pump



                                                                                              CHWS CHWR




                                                                                                              91

                                                                                   www.energycodes.gov/BECU
Section 6 – 6.5.3
Air System Design and Control


 Each HVAC system with total fan system power > 5 hp to
 meet 6.5.3.1 through 6.5.3.2
                              5 hp       6.5.3.1 6.5.3.4.
     9 Fan Power Limitation

     9 VAV Fan Control

         – Part Load Fan Power Limitation

         – Static Pressure Sensor location

         – Set Point Reset



                                                                      92

                                                www.energycodes.gov/BECU
Section 6 – 6.5.3.1
Fan Power Limitation


 Table 6.5.3.1.1A
    Two options:
        nameplate hp (Option 1)
         fan system bhp (Option 2)

 Exceptions
 9Hospital, vivarium, and laboratory systems that utilize
  flow control devices on exhaust and/or return to maintain
  space pressure relationships necessary for occupant health
  and safety or environmental control may use variable-volume
  fan power limitation
       ,                    ,                             ,
     ( )     ,
  .
 9Individual exhaust fans with motor nameplate hp ” 1 hp
                1 hp
                                                                          93

                                                    www.energycodes.gov/BECU
Section 6 – 6.5.3.1
Fan Power Limitation



                         6.5.3.1.1A Fan Power Limitation
         Option               Limit           Constant Volume      Variable Volume




                       Allowable Nameplate
           1                                   hp CFMs*0.0011      hp    CFMs*0.0015
                             Motor hp




                            Allowable
           2               Fan System        bhp CFMs*0.00094+A   bhp CFMs*0.0013+A
                               bhp




                                                                                              94

                                                                        www.energycodes.gov/BECU
Section 6 – 6.5.3.1
Fan Power Limitation



       6.5.3.1.1B Fan Power Limitation Pressure Drop Adjustment

        Device                               Adjustment

        Credits

        Fully ducted return and/or exhaust   0.5 in. w.c. (2.15 in. w.c. for laboratory and vivarium
        air system                           systems)

        Return and/or exhaust airflow        0.5 in. w.c.
        control devices

        Exhaust filters, scrubbers, or       The pressure drop of device calculated at fan system
        other exhaust treatment              design condition

        Particulate Filter Credit :          0.5 in. w.c.
        MERV 9-12

        Particulate Filter Credit :          0.9 in. w.c.
        MERV 13-15




                                                                                                                 95

                                                                                           www.energycodes.gov/BECU
Section 6 – 6.5.3.1
Fan Power Limitation



        6.5.3.1.1B Fan Power Limitation Pressure Drop Adjustment
       Particulate Filter Credit :                    The pressure drop of device calculated at 2*
       MERV 16 and greater                            clean filter pressure drop at fan system
       and electronically enhanced filters            design condition

       Carbon and other gas-phase air cleaners        Clean filter pressure drop at fan system design
                                                      condition

       Biosafety cabinet                              Pressure drop of device at fan system design
                                                      condition

       Energy Recovery Device, other than Coil        (2.2 Energy Recovery Effectiveness)-0.5 in.
       Runaround Loop                                 w.c. for each airstream

       Coil Runaround Loop                            0.6 in. w.c. for each airstream
       Evaporative humidifier/cooler in series with   Pressure drop of device at fan system design
       another cooling coil                           condition

       Sound Attenuation Section                      0.15 in. w.c.
       Exhaust system serving fume hoods              0.35 in. w.c.
       laboratory and vivarium exhaust systems in     0.25 in. w.c. / 100ft of vertical duct exceeding
       high-rise building                             75ft


                                                                                                                 96

                                                                                           www.energycodes.gov/BECU
Section 6 – 6.5.3.1.2
Motor Nameplate Horsepower


 Selected fan motor to be no larger than first available motor size
 greater than bhp
               ,                                 (BHP)
 Fan bhp on design documents
            (BHP)
 Exceptions
     9 Fans < 6 bhp, where first available motor larger than bhp has
       nameplate rating within 50% of bhp, next larger nameplate motor
       size may be selected
                 6 bhp         ,                          (bhp) 50%
          ,
     9 Fans • 6 bhp, where first available motor larger than bhp has
       nameplate rating within 30% of bhp, next larger nameplate motor
       size may be selected
                 6 bhp( )          ,                          (bhp)
       30%     ,                                                                97

                                                          www.energycodes.gov/BECU
Section 6 – 6.5.3.2.1
Part-Load Fan Power Limitation


 Individual VAV fans with motors • 10 hp
 10 hp( )                   (VAV)
     9 Must have either:

         – Variable Speed Drive

         – Vane axial fan with variable-pitch fan blades

         – Other controls and devices to result in fan motor demand ” 30% of
           design wattage at 50% of design air volume when static pressure
           set point = 1/3 of total design static pressure, based on
           manufacturer’s certified fan data
         –                            ,                              1/3 ,
                                                   50% ,
                       30%
                                                                                       98

                                                                 www.energycodes.gov/BECU
Section 6 – 6.5.3.2.2
Static Pressure Sensor Location


 Placed so controller set point is ” 1/3 the total design fan
 static pressure
           ,                                         1/3
     9 Except for digital control systems with zone reset capabilities
       where it may be at the fan discharge
                                                 ,


 Install multiple sensors in each major branch if sensor
 would be located downstream of a major duct split
                                         ,



                                                                                    99

                                                              www.energycodes.gov/BECU
Section 6 – 6.5.3.2.3
Setpoint Reset


  For systems with direct digital control of individual zone
  boxes reporting to the central control panel


     9 Static pressure set point reset based on zone requiring the
       most pressure




                                                                                 100

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.3.3
Multiple-zone VAV System Ventilation Optimization
Control


  In multiple-zone VAV systems with DDC of individual zone boxes
  reporting to central control panel
                                           DDC
      9 Include means to automatically reduce outdoor air intake flow below
        design rates in response to changes in system ventilation efficiency
        as per Standard 62.1, Appendix A
                                      (   Std. 62.1   A     ),




                                                                                      101

                                                                 www.energycodes.gov/BECU
Section 6 – 6.5.3.3
Multiple-zone VAV System Ventilation Optimization
Control Exceptions


  Exceptions
      9 VAV systems with zonal transfer fans that recirculate air from other
        zones without directly mixing it with outdoor air, dual-duct dual-fan
        VAV systems, and VAV systems with fan-powered terminal units
                                       ,
               ,                           ,
           .
      9 Systems required to have exhaust air energy recovery complying
        with 6.5.6.1
                    6.5.6.1
      9 Systems where total design exhaust airflow is > 70% of total
        outdoor air intake flow requirements
                                                           70%




                                                                                       102

                                                                  www.energycodes.gov/BECU
Section 6 – 6.5.3.4
Supply-air Temperature Reset Controls


  Multiple zone HVAC systems to have controls to automatically reset
  supply-air temperature in response to building loads or outdoor air
  temperature
                                  ,                                   ,


  Controls to be capable of resetting supply air temperature at least 25%
  of difference between design supply-air temperature and design room
  air temperature

  25%

  Controls that adjust the reset based on zone humidity are okay


  Zones expected to experience relatively constant loads to be designed
  for fully reset supply temperature
                              ¸
                                                                                        103

                                                                   www.energycodes.gov/BECU
Section 6 – 6.5.3.4
Supply-air Temperature Reset Controls Exceptions



  Exceptions
     9 Climate zones 1a, 2a, and 3a
              1a, 2a, 3a
     9 Systems that prevent reheating, recooling or mixing of heated and cooled
       supply air
                       ,      ,
     9 75% of energy for reheating is from site-recovered or site solar energy
       sources
           75%




                                                                                             104

                                                                        www.energycodes.gov/BECU
Section 6 – 6.5.4
Hydronic System Design and Control


 HVAC hydronic systems with total pump system power
 > 10 hp to meet 6.5.4.1 – 6.5.4.4
                                 10 hp ,    6.5.4.1-6.5.4.4
     9 Hydronic Variable Flow Systems

     9 Pump Isolation

     9 Chilled and Hot Water Temperature Reset

     9 Hydronic (water-loop) Heat Pumps and Water-Cooled Unitary
       Air-Conditioners
            (      )
     9 Pipe Sizing

                                                                             105

                                                        www.energycodes.gov/BECU
Section 6 – 6.5.4.1
Hydronic Variable Flow


 HVAC pumping systems to include control valves

     9 Designed to modulate or step open and close as a function of load
                                      ,
     9 Designed for variable fluid flow

     9 Capable of reducing flow rates to ” 50% of design flow rate
                     50%(    )

 Individual pumps serving variable flow systems with a motor > 5
 hp
                              ,                5 hp
     9 Have controls and/or devices resulting in pump motor demand
       ” 30% of design wattage at 50% of design water flow
                /        ,            50%   ,                  30%


                                                                                    106

                                                               www.energycodes.gov/BECU
Section 6 – 6.5.4.1
Hydronic Variable Flow (cont’d)


  Differential pressure setpoint to be ” 110% of that required to
  achieve design flow through the heat exchanger
                                                    110%

  If differential pressure control and DDC controls are used
                  DDC
      9 Reset setpoint downward based on valve positions until one valve
        is nearly wide open




                                                                                   107

                                                              www.energycodes.gov/BECU
Section 6 – 6.5.4.1
Hydronic Variable Flow


 Exceptions
 9 Systems where
       – Minimum flow is < minimum flow required by equipment
         manufacturer for proper operation of equipment served
         by the system



       – Total pump system power ” 75 hp
                            75 hp( )
 9 Systems that include ” 3 control valves
             3



                                                                              108

                                                         www.energycodes.gov/BECU
Section 6 – 6.5.4.2
Pump Isolation


 If chilled water plant has more than one chiller or boiler
 plant has more than one boiler

     9 Provide for flow reduction when chiller or boiler is shut down
                                   ,




                                                                                   109

                                                              www.energycodes.gov/BECU
Section 6 – 6.5.4.3
Chilled and Hot Water Temperature Reset Controls



 Affects systems with design capacity > 300,000 Btu/h
              300,000 Btu/h ,
      9 To include controls to automatically reset supply water
        temperatures by representative building loads (including return
        water temperature) or by outside air temperature
                                  (           )


 Exceptions
      9 If controls would result in improper operation

      9 Hydronic systems with variable flow



                                                                                  110

                                                             www.energycodes.gov/BECU
Section 6 – 6.5.4.4
Hydronic Heat Pumps and Water-Cooled Unitary
Air-Conditioners


 9 Two-position valves at each hydronic heat pump must be provided
   and interlocked to shut off water flow to the heat pump when the
   compressor is off
                                                            ,

 Exceptions
     9 Units using water economizers

 For hydronic heat pumps and water-cooled unitary ACs with total pump
    power > 5 hp
                                                5hp
     9 Controls or devices must be provided to have pump motor demand ”
       30% of design wattage at 50% of design water flow
                       /      ,             50%    ,                     30%
         9 This basically converts the system into a variable flow system. As
           such, these systems must also comply with 6.5.4.1
                                                 6.4.4.1
                                                                                       111

                                                                  www.energycodes.gov/BECU
Section 6 – 6.5.4.5
Pipe Sizing


 Chilled-water and condenser-water piping so design flow rate in
 each segment doesn’t exceed values in Table 6.5.4.5.
                   ,                 ,                  6.5.4.5

 This table presents the maximum allowed flow rates per section of
 pipe as a function of the following three criteria:
                                   ,
     – Pipe size

     – Annual hours of operation

     – System flow and control



                                                                           112

                                                      www.energycodes.gov/BECU
Section 6 – 6.5.4.5
Pipe Sizing Exceptions


 Exceptions
 9Rates exceeding the Table are allowed if the specific section of
  pipe in question isn’t in the critical circuit > 30% of operating
  hours
                                  ,
          30%,                6.5.4.5
 9Piping systems with equivalent or lower total pressure drop than
  the same system with standard weight steel pipe with piping and
  fittings sized per the Table
                    6.5.4.5                                               ,




                                                                              113

                                                        www.energycodes.gov/BECU
Section 6 – 6.5.5
Heat Rejection Equipment


  Applies to heat rejection equipment used in comfort cooling systems
  such as

      9 Air-cooled condensers

      9 Open cooling towers

      9 Closed-circuit cooling towers

      9 Evaporative condensers


  Exceptions
      9 Heat rejection devices included as an integral part of equipment listed
        devices whose energy usage is included in Tables 6.8.1A-6.8.1D
                                  ,           Tables 6.8.1A 6.8.1D
                                                                                         114

                                                                    www.energycodes.gov/BECU
Section 6 – 6.5.5.2
Fan Speed Control


 Fan Speed Control

 9 Each fan powered by a motor • 7.5 hp
                 7.5 hp( )
       – Have capability to operate fan at ” 2/3 full speed
                            2/3
       – Have controls to automatically change the fan speed to control the
         leaving fluid temperature or condensing temperature/pressure of the
         heat rejection device




                                                                                     115

                                                                www.energycodes.gov/BECU
Section 6 – 6.5.5.2
Fan Speed Control Exceptions


 Exceptions
       – Condenser fans serving multiple refrigerant circuits or flooded
         condensers

       – Installations in climates zones 1 and 2
                        1 2
       – Up to 1/3 of the fans on a multiple fan application speed
         controlled
                     1/3( )             ,




                                                                                  116

                                                             www.energycodes.gov/BECU
Section 6 – 6.5.5.3
Limitation on Centrifugal Fan Open-Circuit
Cooling Towers



 • If towers have a combined rated capacity • 1100 gpm at 95 F
   condenser water return, 85 F condenser water supply, and
   75 F outdoor air wet-bulb temperature
                 ,         1100gpm( )      , 95oF
    85oF     ,             75oF
     – Must meet requirement for axial fan open-circuit cooling towers
       in Table 6.8.1G
                6.8.1G
 Exceptions
     – Ducted (inlet or discharge)
                (                 )
     – Require external sound attenuation

                                                                                 117

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.6.2
Heat Recovery for Service Water Heating


 Condenser recovery required if
                      ,
     9 24 hrs per day and
           24          ,
     9 Heat rejection > 6,000,000 Btu/h and
                     6,000,000 Btu/h,
     9 SWH load > 1,000,000 Btu/h
                              1,000,000 Btu/h

 The required heat recovery system shall have the
 capacity to provide the smaller of

     9 60% of the peak heat rejection load at design conditions or
                                  60%,
     9 preheat of the peak service hot water draw to 85 F.
                             85 oF

                                                                                 118

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.6.2
Heat Recovery for Service Water Heating Exceptions


 Exceptions
 9If condenser heat recovery is used for space heating with a heat
  recover design > 30% of peak water-cooled condenser load at
  design conditions
                                        ,
                                    30%
 9If 60% of service water heating is provided from site-solar or
  site-recovered energy or other sources
                         60%




                                                                                 119

                                                            www.energycodes.gov/BECU
Section 6 – 6.5.7.1
Kitchen Exhaust Systems


 • Replacement air introduced directly into hood cavity to be ”
   10% of hood exhaust airflow rate

      10%
 • Conditioned supply air to not exceed the greater of
                                                                           :
     – Supply flow required to meet space heating or cooling load

     – Hood exhaust flow minus available transfer air from adjacent
       spaces




                                                                                   120

                                                              www.energycodes.gov/BECU
Section 6 – 6.5.7.1
Kitchen Exhaust Systems


 • If kitchen/dining facility has total kitchen hood exhaust airflow
   rate > 5,000 cfm, each hood’s exhaust rate must comply with
   Table 6.5.7.1.3
             /                                    5000cfm ,
                              6.5.7.1.3
     – If a single hood or hood section is over appliances with different
       duty ratings, then the max. airflow rate for that can’t exceed the
       Table values for highest appliance duty rating under that hood or
       hood section
                                 ,                              ,

 Exception
 • If at least 75% of all replacement air is transfer air that would
   otherwise be exhausted
                         75%              ,                             .


                                                                                     121

                                                                www.energycodes.gov/BECU
Section 6 – 6.5.7.1
Kitchen Exhaust Systems, con’t


 9 Kitchens/dining facilities with total kitchen hood exhaust airflow rate
   > 5,000 cfm must have one of these:
       /                                      5000cfm ,                  :
     – At least 50% of all replacement air is transfer air that would otherwise
       be exhausted
                            50%             ,                           .
     – Demand ventilation systems on at least 75% of exhaust air (capable of
       at least 50% reduction in exhaust and replacement air system airflow
       rates)
                     ,       75%      .
            50%
     – Listed energy recovery devices with sensible heat recover effectiveness
       of not less than 40% on at least 50% of the total exhaust airflow
              50%              ,                                 40%


                                                                                       122

                                                                  www.energycodes.gov/BECU
Section 6 – 6.5.7.1
Kitchen Exhaust Systems, con’t


 9 Performance testing must be done using an approved
   field test method

     9 If demand control ventilation systems are used, additional testing
       is required
                                   ,




                                                                                  123

                                                             www.energycodes.gov/BECU
Section 6 – 6.5.7.2
Laboratory Exhaust Systems


 9 Laboratory exhaust systems with total exhaust rate > 5,000
   cfm to have one of the following
                                 5,000 cfm ,                    :
     9 VAV lab exhaust and room supply system capable of reducing
       exhaust and makeup air flow rates and/or incorporate a heat
       recovery system
                                        ,                                 /


     9 VAV lab exhaust and room supply systems required to have
       minimum circulation rates to comply with code to be capable of
       reducing zone exhaust and makeup air flow rates to the regulated
       minimum circulation values or minimum required to maintain
       pressurization relationship requirements
                                        ,
                      ,                                                          ,

         9 Non-regulated zones capable of reducing exhaust and makeup air flow
           rates to 50% of zone design values or minimum required to maintain
           pressurization relationship requirements
                          ,                           50%       ,

                                                                                         124

                                                                    www.energycodes.gov/BECU
Section 6 – 6.5.7.2
Laboratory Exhaust Systems (Cont’d)


     9 Direct makeup air supply to equal at least 75% of exhaust air flow
       rate, heated no warmer than 2 F below room setpoint, cooled to no
       cooler than 3 F above room setpoint, no humidification added, and
       no simultaneous heating and cooling used for dehumidification
       control
            75%             (    )    ,                                   2oF,
                                          3oF,   ,                  ,




                                                                                   125

                                                              www.energycodes.gov/BECU
Section 6 – 6.5.8
Radiant Heating Systems


  Required for unenclosed spaces
  exception: loading docks with air
  curtains

       :




                                                           126

                                      www.energycodes.gov/BECU
Section 6 – 6.5.8
Radiant Heating Systems


  “Radiant heating systems that are
  used as primary or supplemental
  enclosed space heating must be in
  conformance with the governing
  provisions of the standard”
  •
                   ,
         9 Radiant hydronic ceiling or floor
           panels

         9 Combination or hybrid systems with
           radiant heating (or cooling) panels
                                       (           )
         9 Radiant heating (or cooling) panels
           used in conjunction with other
           systems such as VAV or thermal
           storage systems
                       (   )                   ,




                                                                            127

                                                       www.energycodes.gov/BECU
Section 6 – 6.5.9
Hot Gas Bypass Limitation



    Rated capacity                 Maximum HGBP capacity,
    of system                      % of total capacity

    ” 240,000 Btu/h                50%

    > 240,000 Btu/h                25%

        9 Applied in systems with stepped or continuous unloading


        9 Limitation also pertains to chillers


        9 Exception: Packaged unitary systems
          ” 90,000 Btu/h (7.5 tons)
               :                 90,000 Btu/h
                                                                                 128

                                                            www.energycodes.gov/BECU
Section 6 – 6.7
Submittals


 9 Record drawings

 9 Operating and maintenance manuals

 9 System balancing

 9 System commissioning




                                                            129

                                       www.energycodes.gov/BECU
Section 6 – 6.7.2.1
Drawings


 Record drawings of actual installation to building owner
 within 90 days of system acceptance and include, as a
 minimum
            90
   .
    9 Location and performance data on each piece of equipment

    9 General configuration of duct and pipe distribution system
      including sizes
                               ,
    9 Terminal air or water design flow rates



                                                                                130

                                                           www.energycodes.gov/BECU
Section 6 – 6.7.2.2
Manuals


 Operating and maintenance manuals to building owner within 90 days of
 system acceptance and include several items
            90




                                                                               131

                                                          www.energycodes.gov/BECU
Section 6 - 6.7.2.3
System Balancing


 9 Systems shall be balanced in accordance with accepted
   engineering standards

 9 Written report for conditioned spaces > 5000 ft2
                     5,000 ft2              ,
 9 Minimize throttling losses

 9 For fans with system power > 1 hp
                 1 hp
     – Adjust fan speed to meet design flow conditions



                                                                              132

                                                         www.energycodes.gov/BECU
Section 6 – 6.7.2.3.3
Hydronic System Balancing


 Proportionately balanced to minimize throttling losses

 Pump impeller trimmed or pump speed adjusted to meet design flow
 conditions

 Each system to have either the ability to measure differential pressure
 increase across the pump or have test ports at each side of the pump


 Exceptions
     9 Pumps with pump motors ” 10 hp
                     10 hp( )
     9 When throttling results in < 5% of the nameplate hp draw, or 3 hp, whichever is
       greater, above that required if the impeller was trimmed
                                           5%, 3hp,                  ,



                                                                                               133

                                                                          www.energycodes.gov/BECU
Section 6 – 6.7.2.4
System Commissioning


 Control elements are calibrated, adjusted, and in proper
 working condition
                   ,

 ¾ 50,000 ft2 conditioned area
             50,000 ft2
    9 Except warehouses and semiheated spaces

    9 Requires commissioning instructions




                                                                        134

                                                   www.energycodes.gov/BECU
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH
BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH

More Related Content

What's hot

Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...
Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...
Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...IJAPEJOURNAL
 
ace088_subramanian_2013_o
ace088_subramanian_2013_oace088_subramanian_2013_o
ace088_subramanian_2013_oSwami Nathan
 
Powergen off grid power supply
Powergen off grid power supplyPowergen off grid power supply
Powergen off grid power supplyHoward Wright
 
The westinghouse pressurized water reactor nuclear power plant
The westinghouse pressurized water reactor nuclear power plant The westinghouse pressurized water reactor nuclear power plant
The westinghouse pressurized water reactor nuclear power plant Arturo David Yelmo Márquez
 
Nucleir power plant and characterization
Nucleir power plant and characterizationNucleir power plant and characterization
Nucleir power plant and characterizationHaris Setiawan
 
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...Heather Martin, P.E.
 
Report on Madras Atomic Power Station Emass Coolant Channel Replacement
Report on Madras Atomic Power Station Emass Coolant Channel ReplacementReport on Madras Atomic Power Station Emass Coolant Channel Replacement
Report on Madras Atomic Power Station Emass Coolant Channel ReplacementSujit Tharakan
 
VVER Nuclear Reactors
VVER Nuclear ReactorsVVER Nuclear Reactors
VVER Nuclear ReactorsSabinoMiani
 
IAEA, Small and Medium Size Reactors 2009, Kuznetsov
IAEA, Small and Medium Size Reactors 2009, KuznetsovIAEA, Small and Medium Size Reactors 2009, Kuznetsov
IAEA, Small and Medium Size Reactors 2009, Kuznetsovmyatom
 
Doubling a VFD driven test-stand’s throughput and capacity
Doubling a VFD driven test-stand’s throughput and capacityDoubling a VFD driven test-stand’s throughput and capacity
Doubling a VFD driven test-stand’s throughput and capacityVacon Plc
 
Bangladesh Power Stations & Power Plants Overview
Bangladesh Power Stations & Power Plants OverviewBangladesh Power Stations & Power Plants Overview
Bangladesh Power Stations & Power Plants OverviewRidwanul Hoque
 
Design and Modelling of 5 Phase DFIM for Wind Energy System
Design and Modelling of 5 Phase DFIM for Wind Energy SystemDesign and Modelling of 5 Phase DFIM for Wind Energy System
Design and Modelling of 5 Phase DFIM for Wind Energy SystemShachin Shibi
 
2014.05.06 Granada Green Energy Inc
2014.05.06  Granada Green Energy Inc2014.05.06  Granada Green Energy Inc
2014.05.06 Granada Green Energy IncMohsin M. Siddiqui
 
GMCP Site Presentation_August 2013
GMCP Site Presentation_August 2013GMCP Site Presentation_August 2013
GMCP Site Presentation_August 2013Sean Chen, PMP, MBA
 
Flex Leasing Power and Service Introduction Presentation 2016-02-15
Flex Leasing Power and Service Introduction Presentation 2016-02-15Flex Leasing Power and Service Introduction Presentation 2016-02-15
Flex Leasing Power and Service Introduction Presentation 2016-02-15Mark MacLean
 
Refrigeration Design
Refrigeration DesignRefrigeration Design
Refrigeration Designgary wysocki
 

What's hot (19)

Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...
Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...
Load Flow Analysis for Process – Tank Loading Power Generation Networks Inter...
 
ace088_subramanian_2013_o
ace088_subramanian_2013_oace088_subramanian_2013_o
ace088_subramanian_2013_o
 
Powergen off grid power supply
Powergen off grid power supplyPowergen off grid power supply
Powergen off grid power supply
 
The westinghouse pressurized water reactor nuclear power plant
The westinghouse pressurized water reactor nuclear power plant The westinghouse pressurized water reactor nuclear power plant
The westinghouse pressurized water reactor nuclear power plant
 
APR 1400 Presentation
APR 1400 PresentationAPR 1400 Presentation
APR 1400 Presentation
 
Nucleir power plant and characterization
Nucleir power plant and characterizationNucleir power plant and characterization
Nucleir power plant and characterization
 
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...
01 Redevelopment of the Proctor Hydroelectric Powerstation - Hydrovision Pape...
 
Report on Madras Atomic Power Station Emass Coolant Channel Replacement
Report on Madras Atomic Power Station Emass Coolant Channel ReplacementReport on Madras Atomic Power Station Emass Coolant Channel Replacement
Report on Madras Atomic Power Station Emass Coolant Channel Replacement
 
VVER Nuclear Reactors
VVER Nuclear ReactorsVVER Nuclear Reactors
VVER Nuclear Reactors
 
IAEA, Small and Medium Size Reactors 2009, Kuznetsov
IAEA, Small and Medium Size Reactors 2009, KuznetsovIAEA, Small and Medium Size Reactors 2009, Kuznetsov
IAEA, Small and Medium Size Reactors 2009, Kuznetsov
 
1
11
1
 
Doubling a VFD driven test-stand’s throughput and capacity
Doubling a VFD driven test-stand’s throughput and capacityDoubling a VFD driven test-stand’s throughput and capacity
Doubling a VFD driven test-stand’s throughput and capacity
 
Advanced Power Reactor 1400 MWe
Advanced Power Reactor 1400 MWe  Advanced Power Reactor 1400 MWe
Advanced Power Reactor 1400 MWe
 
Bangladesh Power Stations & Power Plants Overview
Bangladesh Power Stations & Power Plants OverviewBangladesh Power Stations & Power Plants Overview
Bangladesh Power Stations & Power Plants Overview
 
Design and Modelling of 5 Phase DFIM for Wind Energy System
Design and Modelling of 5 Phase DFIM for Wind Energy SystemDesign and Modelling of 5 Phase DFIM for Wind Energy System
Design and Modelling of 5 Phase DFIM for Wind Energy System
 
2014.05.06 Granada Green Energy Inc
2014.05.06  Granada Green Energy Inc2014.05.06  Granada Green Energy Inc
2014.05.06 Granada Green Energy Inc
 
GMCP Site Presentation_August 2013
GMCP Site Presentation_August 2013GMCP Site Presentation_August 2013
GMCP Site Presentation_August 2013
 
Flex Leasing Power and Service Introduction Presentation 2016-02-15
Flex Leasing Power and Service Introduction Presentation 2016-02-15Flex Leasing Power and Service Introduction Presentation 2016-02-15
Flex Leasing Power and Service Introduction Presentation 2016-02-15
 
Refrigeration Design
Refrigeration DesignRefrigeration Design
Refrigeration Design
 

Viewers also liked

5156 p1-p psp-pengawasan mutu
5156 p1-p psp-pengawasan mutu5156 p1-p psp-pengawasan mutu
5156 p1-p psp-pengawasan mutuWinarto Winartoap
 
Ashrae 62.1 2010 最小外氣量需求計算
Ashrae 62.1 2010 最小外氣量需求計算Ashrae 62.1 2010 最小外氣量需求計算
Ashrae 62.1 2010 最小外氣量需求計算erik chiang
 
Permenkes 9 2015 perubahan penggolongan psikotropika
Permenkes 9 2015 perubahan penggolongan psikotropikaPermenkes 9 2015 perubahan penggolongan psikotropika
Permenkes 9 2015 perubahan penggolongan psikotropikaUlfah Hanum
 
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...bccomfort
 
ASHRAE Standard 62.1 2010 Table 6.1
ASHRAE Standard 62.1 2010 Table 6.1ASHRAE Standard 62.1 2010 Table 6.1
ASHRAE Standard 62.1 2010 Table 6.1erik chiang
 
Rancangan Formularium 2
Rancangan Formularium 2Rancangan Formularium 2
Rancangan Formularium 2Sisca Yoliza
 
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015weni chris
 
Rancangan Formularium 1
Rancangan Formularium 1Rancangan Formularium 1
Rancangan Formularium 1Sisca Yoliza
 
Contoh form pengusulan obat formularium
Contoh form pengusulan obat formulariumContoh form pengusulan obat formularium
Contoh form pengusulan obat formulariumKaraengRewaMatt
 
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotika
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotikaPermenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotika
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotikaUlfah Hanum
 
Contoh surat permohonan obat
Contoh surat permohonan obatContoh surat permohonan obat
Contoh surat permohonan obatEdi Purwanto
 
Spo penyimp narkotika
Spo penyimp narkotikaSpo penyimp narkotika
Spo penyimp narkotikaWawan Wan
 

Viewers also liked (15)

5156 p1-p psp-pengawasan mutu
5156 p1-p psp-pengawasan mutu5156 p1-p psp-pengawasan mutu
5156 p1-p psp-pengawasan mutu
 
Ashrae 62.1 2010 最小外氣量需求計算
Ashrae 62.1 2010 最小外氣量需求計算Ashrae 62.1 2010 最小外氣量需求計算
Ashrae 62.1 2010 最小外氣量需求計算
 
Table 6.3.2
Table 6.3.2Table 6.3.2
Table 6.3.2
 
Permenkes 9 2015 perubahan penggolongan psikotropika
Permenkes 9 2015 perubahan penggolongan psikotropikaPermenkes 9 2015 perubahan penggolongan psikotropika
Permenkes 9 2015 perubahan penggolongan psikotropika
 
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
BC Comfort ASHRAE 90.1 2010 Envelope Highlights (Christopher Boyzk Architects...
 
Borang kosong
Borang kosongBorang kosong
Borang kosong
 
ASHRAE Standard 62.1 2010 Table 6.1
ASHRAE Standard 62.1 2010 Table 6.1ASHRAE Standard 62.1 2010 Table 6.1
ASHRAE Standard 62.1 2010 Table 6.1
 
Rancangan Formularium 2
Rancangan Formularium 2Rancangan Formularium 2
Rancangan Formularium 2
 
Patient safety (apoteker wajib baca)
Patient safety (apoteker wajib baca)Patient safety (apoteker wajib baca)
Patient safety (apoteker wajib baca)
 
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015
Kepmenkes no. 137 th 2016 ttg perubahan formularium nasional 2015
 
Rancangan Formularium 1
Rancangan Formularium 1Rancangan Formularium 1
Rancangan Formularium 1
 
Contoh form pengusulan obat formularium
Contoh form pengusulan obat formulariumContoh form pengusulan obat formularium
Contoh form pengusulan obat formularium
 
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotika
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotikaPermenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotika
Permenkes 3 2015 peredaran, penyimpanan, pemusnahan, dan pelaporan narkotika
 
Contoh surat permohonan obat
Contoh surat permohonan obatContoh surat permohonan obat
Contoh surat permohonan obat
 
Spo penyimp narkotika
Spo penyimp narkotikaSpo penyimp narkotika
Spo penyimp narkotika
 

Similar to BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH

Options for Retrofit Regulations at Time of Renovation
Options for Retrofit Regulations at Time of RenovationOptions for Retrofit Regulations at Time of Renovation
Options for Retrofit Regulations at Time of RenovationRDH Building Science
 
Energy optimization &amp; building ventilation systems 10.02.2020
Energy optimization &amp; building ventilation systems   10.02.2020Energy optimization &amp; building ventilation systems   10.02.2020
Energy optimization &amp; building ventilation systems 10.02.2020Consistent Engineering Consultants
 
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...lizzabel
 
PSO Optimized PID Controller for Interconnected multi-area Power system with ...
PSO Optimized PID Controller for Interconnected multi-area Power system with ...PSO Optimized PID Controller for Interconnected multi-area Power system with ...
PSO Optimized PID Controller for Interconnected multi-area Power system with ...IRJET Journal
 
KK Wind Solutions presentation on Control System Retrofit
KK Wind Solutions presentation on Control System RetrofitKK Wind Solutions presentation on Control System Retrofit
KK Wind Solutions presentation on Control System RetrofitRené Balle
 
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...Ingeteam Wind Energy
 
SESG Seminar Presentation
SESG Seminar PresentationSESG Seminar Presentation
SESG Seminar PresentationIES VE
 
Bob Bach: Energy Efficiency in the Ontario Building Code
Bob Bach: Energy Efficiency in the Ontario Building CodeBob Bach: Energy Efficiency in the Ontario Building Code
Bob Bach: Energy Efficiency in the Ontario Building CodeToronto 2030 District
 
personal Introduction
personal Introductionpersonal Introduction
personal Introduction劲松 楼
 
Flex stat brochure_sb-049c
Flex stat brochure_sb-049cFlex stat brochure_sb-049c
Flex stat brochure_sb-049calfmich
 
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...Ingeteam Wind Energy
 
Hybrid Controller | Design 150KW PV with DG1:700KW
Hybrid  Controller | Design 150KW PV with DG1:700KWHybrid  Controller | Design 150KW PV with DG1:700KW
Hybrid Controller | Design 150KW PV with DG1:700KWEyad Adnan
 
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxUtility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxMoturiVinodKumar
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...IJERA Editor
 
04 7988 9055-1-pb
04 7988 9055-1-pb04 7988 9055-1-pb
04 7988 9055-1-pbIAESIJEECS
 

Similar to BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH (20)

Options for Retrofit Regulations at Time of Renovation
Options for Retrofit Regulations at Time of RenovationOptions for Retrofit Regulations at Time of Renovation
Options for Retrofit Regulations at Time of Renovation
 
Ppt.ppt
Ppt.pptPpt.ppt
Ppt.ppt
 
Energy optimization &amp; building ventilation systems 10.02.2020
Energy optimization &amp; building ventilation systems   10.02.2020Energy optimization &amp; building ventilation systems   10.02.2020
Energy optimization &amp; building ventilation systems 10.02.2020
 
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...
Oct. 24 Webinar/Seminar: Is ASHRAE 90.1 2012 or iecc-2012 the right energy co...
 
PSO Optimized PID Controller for Interconnected multi-area Power system with ...
PSO Optimized PID Controller for Interconnected multi-area Power system with ...PSO Optimized PID Controller for Interconnected multi-area Power system with ...
PSO Optimized PID Controller for Interconnected multi-area Power system with ...
 
KK Wind Solutions presentation on Control System Retrofit
KK Wind Solutions presentation on Control System RetrofitKK Wind Solutions presentation on Control System Retrofit
KK Wind Solutions presentation on Control System Retrofit
 
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
 
P1111143901
P1111143901P1111143901
P1111143901
 
SESG Seminar Presentation
SESG Seminar PresentationSESG Seminar Presentation
SESG Seminar Presentation
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 
Bob Bach: Energy Efficiency in the Ontario Building Code
Bob Bach: Energy Efficiency in the Ontario Building CodeBob Bach: Energy Efficiency in the Ontario Building Code
Bob Bach: Energy Efficiency in the Ontario Building Code
 
personal Introduction
personal Introductionpersonal Introduction
personal Introduction
 
Flex stat brochure_sb-049c
Flex stat brochure_sb-049cFlex stat brochure_sb-049c
Flex stat brochure_sb-049c
 
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...
Indian Wind Power - New-generation DFIG Power Converters for 6-8 MW Wind Turb...
 
final design
final designfinal design
final design
 
Hybrid Controller | Design 150KW PV with DG1:700KW
Hybrid  Controller | Design 150KW PV with DG1:700KWHybrid  Controller | Design 150KW PV with DG1:700KW
Hybrid Controller | Design 150KW PV with DG1:700KW
 
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxUtility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...
Massive Energy Saving Systems and Strategies at Equipment Level in the Highes...
 
04 7988 9055-1-pb
04 7988 9055-1-pb04 7988 9055-1-pb
04 7988 9055-1-pb
 

More from erik chiang

Ashrae standard 90.1 2010 (中文版) p1 5
Ashrae standard 90.1 2010 (中文版) p1 5Ashrae standard 90.1 2010 (中文版) p1 5
Ashrae standard 90.1 2010 (中文版) p1 5erik chiang
 
資料中心PUE量測 (Measuring PUE for Data Centers)
資料中心PUE量測 (Measuring PUE for Data Centers)資料中心PUE量測 (Measuring PUE for Data Centers)
資料中心PUE量測 (Measuring PUE for Data Centers)erik chiang
 
Ashrae 90.1 生活用水加熱-上課資料
Ashrae 90.1 生活用水加熱-上課資料Ashrae 90.1 生活用水加熱-上課資料
Ashrae 90.1 生活用水加熱-上課資料erik chiang
 
伸展操動作圖示與說明
伸展操動作圖示與說明伸展操動作圖示與說明
伸展操動作圖示與說明erik chiang
 
Filter Efficiency Selection
Filter Efficiency SelectionFilter Efficiency Selection
Filter Efficiency Selectionerik chiang
 

More from erik chiang (6)

Ashrae standard 90.1 2010 (中文版) p1 5
Ashrae standard 90.1 2010 (中文版) p1 5Ashrae standard 90.1 2010 (中文版) p1 5
Ashrae standard 90.1 2010 (中文版) p1 5
 
資料中心PUE量測 (Measuring PUE for Data Centers)
資料中心PUE量測 (Measuring PUE for Data Centers)資料中心PUE量測 (Measuring PUE for Data Centers)
資料中心PUE量測 (Measuring PUE for Data Centers)
 
Ashrae 90.1 生活用水加熱-上課資料
Ashrae 90.1 生活用水加熱-上課資料Ashrae 90.1 生活用水加熱-上課資料
Ashrae 90.1 生活用水加熱-上課資料
 
TIA 942-2005
TIA 942-2005TIA 942-2005
TIA 942-2005
 
伸展操動作圖示與說明
伸展操動作圖示與說明伸展操動作圖示與說明
伸展操動作圖示與說明
 
Filter Efficiency Selection
Filter Efficiency SelectionFilter Efficiency Selection
Filter Efficiency Selection
 

Recently uploaded

PSYCHIATRIC History collection FORMAT.pptx
PSYCHIATRIC   History collection FORMAT.pptxPSYCHIATRIC   History collection FORMAT.pptx
PSYCHIATRIC History collection FORMAT.pptxPoojaSen20
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting DataJhengPantaleon
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docxPoojaSen20
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxSayali Powar
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsanshu789521
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdfSoniaTolstoy
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application ) Sakshi Ghasle
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
Micromeritics - Fundamental and Derived Properties of Powders
Micromeritics - Fundamental and Derived Properties of PowdersMicromeritics - Fundamental and Derived Properties of Powders
Micromeritics - Fundamental and Derived Properties of PowdersChitralekhaTherkar
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfUmakantAnnand
 
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991RKavithamani
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityGeoBlogs
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Celine George
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxGaneshChakor2
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 

Recently uploaded (20)

PSYCHIATRIC History collection FORMAT.pptx
PSYCHIATRIC   History collection FORMAT.pptxPSYCHIATRIC   History collection FORMAT.pptx
PSYCHIATRIC History collection FORMAT.pptx
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docx
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha elections
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application )
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Micromeritics - Fundamental and Derived Properties of Powders
Micromeritics - Fundamental and Derived Properties of PowdersMicromeritics - Fundamental and Derived Properties of Powders
Micromeritics - Fundamental and Derived Properties of Powders
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.Compdf
 
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
 
Paris 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activityParis 2024 Olympic Geographies - an activity
Paris 2024 Olympic Geographies - an activity
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptx
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 

BUILDING ENERGY CODES UNIVERSITY SIMPLIFIED HVAC PATH

  • 1. BUILDING ENERGY CODES UNIVERSITY ANSI/ASHRAE/IES Standard 90.1-2010 HVAC Erik chiang 1 April 2011 – PNNL-SA-80143 www.energycodes.gov/BECU
  • 2. HVAC Compliance Building System Compliance Options Prescriptive Envelope Option Mandatory HVAC Provisions Trade Off Energy Code (required for most Option Compliance SWH compliance options) Energy Cost Power Budget Lighting Simplified Other 2 www.energycodes.gov/BECU
  • 3. Section 6 – 6.1.1 HVAC Scope 9 New Buildings 9 Additions to Existing Buildings 9 Alterations in Existing Buildings 3 www.energycodes.gov/BECU
  • 4. Section 6 – 6.1.1.3 HVAC Alterations Scope 9 Equipment – New equipment shall meet the minimum efficiency requirements – 9 Cooling systems – New cooling systems installed to serve previously uncooled spaces shall comply with this section – Alterations to existing cooling systems shall not decrease economizer capacity (unless economizer tradeoff is used) ( ) 9 Ductwork – New and replacement ductwork shall comply with applicable requirements – 9 Piping – New and replacement piping shall comply with applicable requirements 4 www.energycodes.gov/BECU
  • 5. Section 6 – 6.1.1.3 HVAC Alterations Alterations to the building HVAC system shall comply with the requirements of Section 6 6 9 Exceptions that are allowed: , – Equipment being modified or repaired (not replaced) ( ) • provided such modifications will not result in an increase in the annual energy consumption – Equipment being replaced or altered which requires extensive revisions to other systems and such replaced or altered equipment is a like-for-like replacement , – Refrigerant change of existing equipment – Relocation of existing equipment – Ducts and pipes where there is insufficient space or access to meet these requirements 5 www.energycodes.gov/BECU
  • 6. Section 6 – 6.2 HVAC Compliance Paths 9 You have to follow Sections – 6.1 General, – 6.7 Submittals, and – 6.8 Minimum Equipment Efficiency 9 And then you can follow either – Section 6.3 Simplified Approach OR 6.3 , – Sections 6.4 Mandatory Provisions and 6.5 Prescriptive Path 6.4 6.5 9 Alternatively, you can follow Section 11 (ECB), in which case Section 6.4 is mandatory , 11 ( ), 6.4 6 www.energycodes.gov/BECU
  • 7. Section 6 – 6.3 Simplified Approach Option The simplified approach is an optional path for compliance when the following are met: , 9 Buildings with 1 or 2 stories 1 2 9 Buildings with gross floor area < 25,000 ft2 < 25,000 ft2 9 System serving single HVAC zone 9 Unitary packaged or split air conditioners (air-cooled or evaporatily cooled) ( ) 7 www.energycodes.gov/BECU
  • 8. Section 6 – 6.3 Simplified Approach Criteria a. Single HVAC zone b. Single zone VAV controls (6.4.3.10) VAV c. Cooling equipment efficiency (6.8.1) d. Air economizers (6.5.1) e. Heating equipment efficiency (6.8.1) f. Exhaust air energy recovery (6.5.6.1) g. Dual set point thermostat or manual changeover h. Heat pump auxiliary heat control i. No reheat or simultaneous cooling and heating for humidity control j. Off-hour shutoff and temperature setback/setup setback/setup k. Piping insulation (Tables 6.8.3A and 6.8.3B) l. Ductwork insulation and sealing (6.4.4.2.1) m. Air balancing of ducted system n. Outdoor air intake and exhaust systems (6.4.3.4) o. Zone thermostatic controls to prevent simultaneous heating and cooling p. Optimum start controls q. Demand control ventilation (6.4.3.9) 8 www.energycodes.gov/BECU
  • 9. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls 9 Supply fans controlled by two-speed motors or variable-speed drives – Air-handling and fan coil units with chilled-water cooling coils – Supply fans with motors • 5 hp >=5hp 9 At cooling demands ” 50%, supply fan controls able to reduce airflow to no greater than the LARGER of <=50%, – ½ of the full fan speed OR 1/2 , – volume of outdoor air required to meet Standard 62.1 On and after January 1, 2012 62.1 2012.1.1 , 9 www.energycodes.gov/BECU
  • 10. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls 9 Supply fans controlled by two-speed motors or variable speed drives – all AC equipment and air-handling units with direct expansion cooling and cooling capacity at AHRI conditions • 110,000 Btu/h serving single zones AHRI >=110,000Btu/h 9 At control demands – 2/3 of the full fan speed OR 2/3 – volume of outdoor air required to meet Standard 62.1 62.1 10 www.energycodes.gov/BECU
  • 11. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls (cont’d) 11 www.energycodes.gov/BECU
  • 12. Section 6 – 6.8.1A (6.3.2c) Equipment Efficiency Reference Tables 6.8.1A, 6.81B and 6.8.1.D in 90.1-2010 90.1-2010 , 6.8.1A, 6.8.1B, 6.8.1D 12 www.energycodes.gov/BECU
  • 13. Section 6 – 6.3.2 Economizers The system shall have an economizer, unless the economizer Trade-off Option is used , 9 Limited to unitary systems 9 Requires higher minimum cooling efficiency (EER) (EER) 9 Trade-off EER by EER – System size – Climate zone 13 www.energycodes.gov/BECU
  • 14. Section 6 – 6.3.2 Economizers Reference Table 6.3.2 on page 40 in 90.1-2010 14 www.energycodes.gov/BECU
  • 15. Section 6 – 6.5.1 (6.3.2d) Economizers (cont’d) 9 Climate and size dependent (Tables 6.5.1A and B) ( 6.5.1A B) 9 There are LOTS of exception 9 Can use air economizers – 100% of design supply air 100% – Sequenced with mechanical cooling equipment – High limit shutoff – Dampers 15 www.energycodes.gov/BECU
  • 16. Section 6 – 6.5.1 (6.3.2d) Economizer Exceptions Exceptions 9 Systems with gas phase air cleaning per Standard 62.1 62.1 9 Where >75% of the air must be humidified >35 Fdp 75% >35 Fdp 9 Systems with condenser heat recovery per 6.5.6.2.2a or 6.5.6.2.2b 6.5.6.2.2a 6.5.6.2.2b 9 Residential systems <5X limits in Table 6.5.1A < 6.5.1A 5 9 Systems with a balance point <=60 F <= 60 F 9 Systems expected to operate < 20hrs/wk 20hr 9 Systems serving zones with refrigerated casework 16 www.energycodes.gov/BECU
  • 17. Section 6 – 6.5.1 (6.3.2d) Economizer Exceptions (cont’d) Exceptions 9 Where comfort cooling efficiency meets or exceeds Table 6.3.2 6.3.2 9 Systems serving computer rooms under certain conditions , 17 www.energycodes.gov/BECU
  • 18. Section 6 – 6.3 Simplified Approach Option (cont’d) 9 Manual changeover or dual set-point thermostat 9 Heat pump supplementary control 9 No reheat or simultaneous heating and cooling for humidity control 9 Time clocks (except hotel/motel guest rooms and systems requiring continuous operation) ( / ) 18 www.energycodes.gov/BECU
  • 19. Section 6 – 6.3 Simplified Approach Option (cont’d) 9 Balancing of ducted systems 9 Outdoor air intake and exhaust systems 9 Interlocked thermostats for separate heating and cooling 9 System > 10,000 cfm: > 10,000 cfm – optimum start controls – 9 Demand control ventilation 19 www.energycodes.gov/BECU
  • 20. Section 6 – 6.3 Simplified Approach Option (cont’d) Piping and ductwork/plenum insulated / 20 www.energycodes.gov/BECU
  • 21. Section 6 – 6.8.2B Duct Insulation Reference Tables 6.8.2A and B on page 68 in 90.1-2010 21 www.energycodes.gov/BECU
  • 22. Section 6 – 6.4.4.1.3 (6.3.2k) Piping Insulation Tables 6.8.3A and 6.8.3B Exceptions 9 Factory-installed 9 Piping conveying fluids – design operating temperature range between 60 F-105 F, inclusive 60 F-105 F , – that haven’t been heated or cooled through the use of fossil fuels or electricity or where heat gain or heat loss will not increase energy usage , 9 Hot water piping between shut off valve and coil, not > 4 ft in length, when located in conditioned spaces , 4ft 9 Piping ” 1 in. <= 1 in. – No insulation required for strainers, control values, and balancing values , , 22 www.energycodes.gov/BECU
  • 23. Section 6 – 6.8.3 Piping Insulation Reference Tables 6.8.3A and B on page 69 in 90.1-2010 23 www.energycodes.gov/BECU
  • 24. Section 6 – 6.5.6.1 (6.3.2f) Exhaust Air Energy Recovery Required if: 9 Supply air capacity • value listed in Table 6.5.6.1 >= 6.5.6.1 – Values are based on climate zone and % of outdoor air flow rate at design conditions Recovery system effectiveness • 50% >= 50% 24 www.energycodes.gov/BECU
  • 25. Section 6 – 6.5.6.1 (6.3.2f) Exhaust Air Energy Recovery Exceptions 9 Lab systems meeting 6.5.7.2 6.5.7.2 9 Systems serving uncooled spaces that are heated to < 60 F < 60 F 9 Systems exhausting toxic, flammable, paint or corrosive fumes or dust , , 9 Commercial kitchen hoods used for collecting grease or smoke 9 Where > 60% of outdoor heating energy is provided from site- recovered or site solar energy > 60%, 9 Heating energy recovery in climate zones 1 and 2 1 2 9 Cooling energy recovery in climate zones 3c, 4c, 5b, 5c, 6b, 7, and 8 3c, 4c, 5b, 5c, 6b, 7 8 25 www.energycodes.gov/BECU
  • 26. Section 6 – 6.5.6.1 (6.3.2f) Exhaust Air Energy Recovery Exceptions 9 Where largest exhaust source is < 75% of the design outdoor airflow < 75% 9 Systems requiring dehumidification that employ energy recovery in series with the cooling coil , 9 Systems operating < 20 hrs/week at outdoor air % in Table 6.5.6.1 6.5.6.1 , 20hr, 26 www.energycodes.gov/BECU
  • 27. Section 6 – 6.8.2B (6.3.2l) Duct & Plenum Insulation Reference Table 6.8.2B on page 68 in 90.1-2010 27 www.energycodes.gov/BECU
  • 28. Section 6 – 6.4.3.9 (6.3.2q) Demand Control Ventilation DCV must be provided for each zone with a area > 500 ft² and the design occupancy > 40 people/1000 ft² where the HVAC system has: >500 ft² >40 /1000 ft² , , 9 An air-side economizer, 9 Automatic modulating control of the OSA dampers, or , 9 A design outdoor airflow > 3,000 cfm > 3000 cfm Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy. 28 www.energycodes.gov/BECU
  • 29. HVAC Compliance Building System Compliance Options Prescriptive Envelope Option Mandatory HVAC Provisions Trade Off Energy Code (required for most Option Compliance SWH compliance options) Energy Cost Power Budget Lighting Simplified Other 29 www.energycodes.gov/BECU
  • 30. Section 6 – 6.4 HVAC Mandatory Provisions 9 Minimum Equipment Efficiency (Section 6.4.1) 9 Calculations (Section 6.4.2) 9 Controls (Section 6.4.3) 9 HVAC System Construction and Insulation (Section 6.4.4) 30 www.energycodes.gov/BECU
  • 31. Section 6 – 6.4.1.1 Minimum Equipment Efficiency HVAC Equipment Covered 9 Air conditioners and condensing units 9 Heat pumps (air, water, and ground source) ( , ) 9 Water-chilling packages (chillers) 9 Packaged terminal and room air conditioners and heat pumps 9 Furnaces, duct furnaces and unit heaters , 9 Boilers 9 Heat rejection equipment (cooling towers) ( ) 31 www.energycodes.gov/BECU
  • 32. Section 6 – 6.4.1.1 Minimum Equipment Efficiency (cont’d) HVAC Equipment Covered 9 Heat transfer equipment (heat exchangers) ( ) 9 Variable refrigerant flow (VRF) air conditioners 9 VRF air-to-air and applied heat pumps 9 Air conditioners serving computer rooms 32 www.energycodes.gov/BECU
  • 33. Section 6 – 6.4.1.4 Verification of Equipment Efficiencies Equipment efficiency information from manufacturers verified as follows , 9 EPACT equipment – to comply with DOE certification requirements (EPACT) – (DOE) 9 If certification program exists for covered product and includes provisions for verification and challenge of equipment efficiency ratings, product listed in program OR , , , 9 If product not listed in program, ratings verified by an independent laboratory test report OR , , 33 www.energycodes.gov/BECU
  • 34. Section 6 – 6.4.1.4 Verification of Equipment Efficiencies (cont’d) 9 If no certification program exists, equipment efficiency ratings supported by data furnished by manufacturer OR , , 9 Where components from different manufacturers are used, system designer specifies components whose combined efficiency meets Section 6.4.1 , 6.4.1 9 Requirements for plate type liquid-to-liquid heat exchangers listed in Table 6.8.1H - , 6.8.1H 34 www.energycodes.gov/BECU
  • 35. Section 6 – 6.4.1.5 Labeling Mechanical equipment (6.4.1.5.1) – equipment not covered by NAECA to have a permanent label stating equipment complies with 90.1 (6.4.1.5.1) – NAECA 90.1 ( NAECA ) 35 www.energycodes.gov/BECU
  • 36. Section 6 – 6.4.1.5 Labeling Packaged terminal air conditioners (6.4.1.5.2) – packaged terminal air conditioners and heat pumps with sleeve sizes < 16 in. high and 42 in. wide with a cross-sectional area < 670 in2 to be factory labeled as follows: (6.4.1.5.2) – 16 42 670 , : 9 Manufactured for nonstandard size applications only: not to be installed in new construction projects : 36 www.energycodes.gov/BECU
  • 37. Section 6 – 6.4.2.1 Load Calculations Must calculate heating and cooling system design loads Must determine calculations with ANSI/ASHRAE/ACCA Standard 183-2007 ASHRAE Std. 183 37 www.energycodes.gov/BECU
  • 38. Section 6 – 6.4.2.2 Pump Head • When sizing pumps, head to be determined in accordance with generally accepted engineering standards/handbooks • Method must be approved by the authority having jurisdiction • Must calculate the pressure drop through each device and pipe segment in the critical circuit at design conditions • , 38 www.energycodes.gov/BECU
  • 39. Section 6 – 6.4.3.1 Controls – Zone Thermostatic & Dead Band Required for each zone 9 Perimeter can be treated differently Dead band controls 9 Thermostats must have at least a 5 F dead band 5F 9 Exceptions – Thermostats that require manual changeover between heating and cooling modes – Special occupancy or applications where wide temperature ranges aren’t acceptable (e.g., retirement homes) and approved by adopting authority , ( ; ) 39 www.energycodes.gov/BECU
  • 40. Section 6 – 6.4.3.2 Controls – Setpoint Overlap Restriction If limit switches, mechanical stops, or software programming for DDC systems are used , , DDC 9 means will be provided to prevent the heating setpoint from exceeding the cooling setpoint minus any applicable proportional band 40 www.energycodes.gov/BECU
  • 41. Section 6 – 6.4.3.3 Controls – Off-Hour Temperature Control off-hour requirements 9 Automatic shutdown 9 Setback controls 9 Optimum start 9 Zone isolation 9 Exceptions, HVAC systems , – with heating/cooling capacity < 15,000 Btu/h – / < 15,000 Btu/h – intended to operate continuously – 41 www.energycodes.gov/BECU
  • 42. Section 6 – 6.4.3.3.1 Controls - Automatic Shutdown Automatic 7-day/week time clock with 10-hour battery backup 10 9 Exception: 2-day/week thermostat for residential applications : , Each control to have 9 Occupant sensor, OR , 9 Manually-operated timer with maximum two hour duration, OR , , 9 Security system interlock Exception 9 Residential occupancies allowed to operate with only 2 different time schedules/wk 42 www.energycodes.gov/BECU
  • 43. Section 6 – 6.4.3.3.2 Controls - Setback Climate Zones 2-8 9 Lower heating setpoint to 55ºF or less 55ºF Climate Zones 1b, 2b, 3b (hot/dry) 9 Automatically restart, temporarily operate , – Raise cooling setpoint to 90ºF or higher OR 90ºF – Prevent high space humidity levels 43 www.energycodes.gov/BECU
  • 44. Section 6 – 6.4.3.3.3 Controls - Optimum Start Individual heating and cooling air distribution systems with , 9 Total design supply air capacity > 10,000 cfm > 10,000 cfm 9 Served by one or more supply fans Control algorithm to at least be a function of 9 Difference between space temperature and occupied setpoint and amount of time prior to scheduled occupancy , 44 www.energycodes.gov/BECU
  • 45. Section 6 – 6.4.3.3.4 Controls - Zone Isolation Applies to 9 Each floor in a multistory building 9 Maximum 25,000 ft2 zone on one floor 25,000ft2 Requirements 9 Isolation devices to shut off outdoor and exhaust airflow when > 5,000 cfm >5,000cfm , 9 Central systems shall be capable of stable operation with one isolation zone 9 Capable of separate time schedules for each isolation zone Figure 6-E Isolation Methods for a Central VAV System (User’s Manual – 90.1.-2007) 45 www.energycodes.gov/BECU
  • 46. Section 6 – 6.4.3.4 Controls – Ventilation System Stair and Shaft Vent dampers (6.4.3.4.1) 9Automatically closed during normal building operation 9Interlocked to open as required by fire and smoke detection systems Shutoff Damper Controls (6.4.3.4.2) 9 All outdoor air intake and exhaust systems require motorized damper 9 Ventilation outdoor air and exhaust/relief dampers capable of automatically shutting off during / , – Preoccupancy building warm-up, cool down, and setback , (Except when ventilation reduces energy costs or when ventilation must be supplied due to code requirements) ( , .) 46 www.energycodes.gov/BECU
  • 47. Section 6 – 6.4.3.4 Controls – Ventilation System (cont’d) 9Exceptions: 9 Backdraft gravity dampers okay (BDD) – For exhaust and relief in buildings < 3 stories in height above grade 3 – Of any height in climate zones 1 – 3 1, 2, 3 9 Ventilation systems serving unconditioned spaces – 300 CFM 47 www.energycodes.gov/BECU
  • 48. Section 6 – 6.4.3.4.3 Controls - Damper Leakage Table 6.4.3.4.3 provides maximum leakage rates for outdoor air supply and exhaust dampers Table 6.4.3.4.3 Where OA supply and exhaust air dampers are required by Section 6.4.3.4 6.4.3.4 9 They shall have a maximum leakage rate when tested in accordance with AMCA Standard 500 as indicated in Table 6.4.3.4.3 AMCA Standard 500, Table 6.4.3.4.3. 48 www.energycodes.gov/BECU
  • 49. Section 6 – 6.4.3.4.3 Controls - Damper Leakage Table 6.4.3.4.3. Maximum Damper Leakage, cfm per ft2 at 1.0 in. w.g. Ventilation Air Intake Exhaust / Reflief Climate Zones Non-motorized1 Motorized Non-motorized1 Motorized 1, 2 - - - - any heigh 20 4 20 4 3 - - - - any heigh 20 10 20 10 4,5b,5c - - - - < 3 stories not allowed 10 20 10 >=3 stories not allowed 10 not allowed 10 5a,6,7,8 - - - - < 3 stories not allowed 4 20 4 >=3 stories not allowed 4 not allowed 4 49 www.energycodes.gov/BECU
  • 50. Section 6 – 6.4.3.4.4 Ventilation Fan Controls Fans with motors > 0.75 hp shall have automatic controls complying with Section 6.4.3.3.1 that are capable of shutting off fans when not required 0.75 hp , 6.4.3.3.1 , , Exception 9 HVAC systems intended to operate continuously 50 www.energycodes.gov/BECU
  • 51. Section 6 – 6.4.3.4.5 Enclosed Parking Garage Ventilation Ventilation systems in enclosed parking garages 9automatically detect contaminant levels and stage fans or 9modulate fan airflow rates to ” 50%, provided acceptable contaminant levels are maintained 50% Exception 9 Garages < 30,000 ft2 with ventilation systems that don’t use mechanical cooling or heating 30,000 ft2 9 Garages with a garage area to ventilation system motor nameplate hp ratio > 1500 ft2/hp and don’t use mechanical cooling or heating 1500 ft2/hp, 9 Where permitted by AHJ 51 www.energycodes.gov/BECU
  • 52. Section 6 – 6.4.3.5 Heat Pump Auxiliary Heat Control Controls to prevent supplementary heat when heat pump can handle the load , Exception 9Heat pumps – With minimum efficiency regulated by NAECA (NAECA) – With HSPF rating meeting Table 6.8.1B (Includes all usage of internal electric resistance heating) Table 6.8.1B ( ) 52 www.energycodes.gov/BECU
  • 53. Section 6 – 6.4.3.6 Controls - Humidifier Preheat Automatic valve to shut off preheat when humidification isn’t required , 53 www.energycodes.gov/BECU
  • 54. Section 6 – 6.4.3.7 Controls - Humidification and Dehumidification Provide means to prevent simultaneous operation of humidification and dehumidification equipment 9 Limit switches, mechanical stops, or software programming (DDC systems) Exceptions 9 Zones served by desiccant systems, used with direct evaporative cooling in series 9 Systems serving zones where specific humidity levels are required and approved by jurisdiction – Museums and hospitals , 54 www.energycodes.gov/BECU
  • 55. Section 6 – 6.4.3.8 Controls - Freeze Protection and Snow/Ice Automatic controls for , 9 Freeze protection systems – outside air temperatures > 40 F or when conditions of protected fluid will prevent freezing 40oF 9 Snow- and ice-melting systems – pavement temperature > 50 F and no precipitation is falling and outdoor temperature > 40 F 50oF 40oF 55 www.energycodes.gov/BECU
  • 56. Section 6 – 6.4.3.9 (6.3.2q) Demand Control Ventilation DCV must be provided for each zone with a area > 500 ft² and the design occupancy > 40 people/1000 ft² where the HVAC system has: >500 ft² >40 /1000 ft² , , 9 An air-side economizer, 9 Automatic modulating control of the OSA dampers, or , 9 A design outdoor airflow > 3,000 cfm > 3000 cfm Demand control ventilation (DCV): a ventilation system capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy. 56 www.energycodes.gov/BECU
  • 57. Section 6 – 6.4.3.9 Demand Control Ventilation (cont’d) Exceptions : 9 System with energy recovery complying with 6.5.6.1 6.5.6.1 9 Multiple-zone systems without DDC of individual zones communicating with a central control panel DDC 9 Systems with a design outdoor airflow less than 1200 cfm 1200cfm 9 Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm 1200cfm 57 www.energycodes.gov/BECU
  • 58. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls 9 Supply fans controlled by two-speed motors or variable-speed drives – Air-handling and fan coil units with chilled-water cooling coils – Supply fans with motors • 5 hp >=5hp 9 At cooling demands ” 50%, supply fan controls able to reduce airflow to no greater than the LARGER of <=50%, – ½ of the full fan speed OR 1/2 , – volume of outdoor air required to meet Standard 62.1 On and after January 1, 2012 62.1 2012.1.1 , 58 www.energycodes.gov/BECU
  • 59. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls 9 Supply fans controlled by two-speed motors or variable speed drives – all AC equipment and air-handling units with direct expansion cooling and cooling capacity at AHRI conditions • 110,000 Btu/h serving single zones AHRI >=110,000Btu/h 9 At control demands – 2/3 of the full fan speed OR 2/3 – volume of outdoor air required to meet Standard 62.1 62.1 59 www.energycodes.gov/BECU
  • 60. Section 6 – 6.4.3.10 (6.3.2b) Single Zone VAV Controls (cont’d) 60 www.energycodes.gov/BECU
  • 61. Section 6 – 6.4.4 HVAC System Construction and Insulation 9 Insulation installed in accordance with industry-accepted standards 9 Insulation protection 9 Duct and plenum insulation 9 Piping insulation 9 Sensible heating panel insulation 9 Radiant floor heating 9 Duct sealing 9 Duct leakage tests 61 www.energycodes.gov/BECU
  • 62. Section 6 – 6.4.4.1.1 General Insulation installed in accordance with industry-accepted standards Insulation 9 Protected from damage due to sunlight, moisture, equipment maintenance, and wind , , 9 Exposed to weather to be suitable for outdoor service , 9 Covering chilled water piping, refrigerant suction piping, or cooling ducts located outside the conditioned space to include a vapor retardant located outside the insulation, all penetrations and joints of which to be sealed , , , 62 www.energycodes.gov/BECU
  • 63. Section 6 – 6.4.4.1.2 Duct and Plenum Insulation All supply and return ducts and plenums to be insulated per Tables 6.8.2A and 6.8.2B , 6.8.2A 6.8.2B Exceptions 9 Factory-installed plenums, casings, or ductwork furnished as part of HVAC equipment , , 9 Ducts located in heated, semiheated, or cooled spaces , 9 For runouts < 10 ft in length to air terminals or air outlets, the R-value need not exceed R-3.5 10 ft, R-3.5 9 Backs of air outlets and outlet plenums exposed to unconditioned or indirectly conditioned spaces with face areas > 5 ft2 need not exceed R-2; those ” 5 ft2 need not be insulated 5 ft2 R-2; ( ) 5 ft2 63 www.energycodes.gov/BECU
  • 64. Section 6 – 6.4.4.1.3 (6.3.2k) Piping Insulation Tables 6.8.3A and 6.8.3B Exceptions 9 Factory-installed 9 Piping conveying fluids – design operating temperature range between 60 F-105 F, inclusive 60 F-105 F , – that haven’t been heated or cooled through the use of fossil fuels or electricity or where heat gain or heat loss will not increase energy usage , 9 Hot water piping between shut off valve and coil, not > 4 ft in length, when located in conditioned spaces , 4ft 9 Piping ” 1 in. <= 1 in. – No insulation required for strainers, control values, and balancing values , , 64 www.energycodes.gov/BECU
  • 65. Section 6 – 6.4.4.2.1 Duct Sealing Ductwork and all plenums with pressure class ratings shall be constructed to , 9 seal class A, as required to meet the requirements of 6.4.4.2.2 class A , 6.4.4.2.2 9 standard industry practice 65 www.energycodes.gov/BECU
  • 66. Section 6 – 6.4.4.2.2 Duct Leakage Tests Designed > 3 in. w.c. and all ductwork located outdoors 3 in. 9 Leak tested 9 Representative sections • 25% of the total installed duct area shall be tested 25%( ) 9 Ratings > 3 in. w.c. to be identified on drawings 3 in., 9 Maximum permitted duct leakage – Lmax = CLP0.65 • Where Lmax = maximum permitted leakage in cfm/100 ft2 duct surface area • CL = 6 cfm/100ft2 duct surface area at 1 in. wc • P = test pressure in. wc. 66 www.energycodes.gov/BECU
  • 67. HVAC Compliance - Prescriptive Building System Compliance Options Prescriptive Envelope Option Mandatory HVAC Provisions Trade Off Energy Code (required for most Option Compliance SWH compliance options) Energy Cost Power Budget Lighting Simplified Other 67 www.energycodes.gov/BECU
  • 68. Section 6 – 6.5 HVAC Prescriptive Path 9 Economizers (Section 6.5.1) 9 Simultaneous Heating and Cooling Limitation (Section 6.5.2) 9 Air System Design and Control (Section 6.5.3) 9 Hydronic System Design and Control (Section 6.5.4) 9 Heat Rejection Equipment (Section 6.5.5) 9 Energy Recovery (Section 6.5.6) 9 Exhaust Systems (Section 6.5.7) 9 Radiant Heating Systems (Section 6.5.8) 9 Hot Gas Bypass Limitation (Section 6.5.9) 68 www.energycodes.gov/BECU
  • 69. Section 6 – 6.5.1.1.2 Control Signal Dampers capable of being sequenced with the mechanical cooling equipment and shall not be controlled by only mixed air temperature , Exception 9 Systems controlled from space temperature (such as single- zone systems) ( ) 69 www.energycodes.gov/BECU
  • 70. Section 6 – 6.5.1.1.3 High Limit Shutoff 9 Automatically reduce outdoor air intake to minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy usage , 9 Control types for specific climates from Table 6.5.1.1.3A 6.5.1.1.3A. , 9 Settings from Table 6.5.1.1.3B 70 www.energycodes.gov/BECU
  • 71. Section 6 – 6.5.1.1.3A High-limit Shutoff Control Options Table 6.5.1.1.3A. High-Limit Shutoff Controls Options for Air Economizers Climate Allowed Control Prohibited Control Types Zones Types 1b, 2b, 3b, 3c, 4b, 4c, 5b, 5c, 6b, 7, Fixed Dry Bulb Fixed Enthalpy 8 Differential Dry Bulb Electronic Enthalpya Differential Enthalpy DP & DB Temperature 1a, 2a, 3a, 4a Fixed Dry Bulb Fixed Dry Bulb Fixed Enthalpy Differential Dry Bulb Differential Enthalpy DP & DB Temperature 5a, 6a Fixed Dry Bulb Differential Dry Bulb Fixed Enthalpy Electronic Enthalpya Differential Enthalpy DP & DB Temperature 71 www.energycodes.gov/BECU
  • 72. Section 6 – 6.5.1.1.3B High-limit Shutoff Control Settings Table 6.5.1.1.3B. High Limit Shutoff Control Setting for Air Economizers Required High Limit (Economizer Off When) Device Type Climate Equation Description 1b, 2b, 3b, 3c, 4b, TOA>75oF OA temperature exceeds 75oF Fixed Dry Bulb 4c, 5a, 5b, 5c, 6a, TOA>70oF OA temperature exceeds 70oF 6b, 7, 8 1b, 2b, 3b, 3c, 4b, Differential Dry OA temperature exceeds return air 4c, 5a, 5b, 5c, 6a, TOA>TRA Bulb temperature 6b, 7, 8 OA enthalpy exceeds 28 Btu/lb of Fixed Enthalpy 2a, 3a, 4a, 5a, 6a hOA>28 Btu/lba dry aira Electronic OA temperature/RH exceeds the All (TOA,xRHOA)>A Enthalpy “A” setpoint curveb Differential OA enthalpy exceeds return air All hOA>hRA Enthalpy enthalpy OA Dry Bulb exceeds 75oF or DP & DB DPOA>55oF or All Outside dew point exceeds 55oF Temperature TOA>75oF (65gr/lb) 72 www.energycodes.gov/BECU
  • 73. Section 6 – 6.5.1.1.4 Dampers Return, exhaust/relief and outdoor air dampers to meet the requirements in 6.4.3 , / , 6.4.3 73 www.energycodes.gov/BECU
  • 74. Section 6 – 6.5.1.1.5 Relief of Excess Outdoor Air Means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building Outlet located to avoid recirculation into the building 74 www.energycodes.gov/BECU
  • 75. Section 6 – 6.5.1.2.1 Design Capacity – Water Economizers System capable of cooling supply air by indirect evaporation and providing up to 100% of expected system cooling load at outside air temperatures of 50 F dry bulb/45 F wet bulb and below 50oF/ 45oF , 100% Exception 9 Systems primarily serving computer rooms – Where 100% of expected system cooling load at 40 F dry bulb/35 F wet bulb is met with evaporative water economizers , 40oF DB/35oF WB 100% – With dry cooler water economizers that satisfy 100% of expected system cooling load at 35 F dry bulb , 35oF DB 100% 9 Dehumidification requirements that your design can meet 100% of expected cooling load at 45 F dry bulb/40 F wet bulb with evaporative water economizers , 45oF DB/40oF WB 100% . 75 www.energycodes.gov/BECU
  • 76. Section 6 – 6.5.1.2.2 Maximum Pressure Drop - Water Economizers Precooling coils and water-to- Valve Closes In Head Economizer water heat exchangers to Pressure Control Valve In Mode Evaporator have either Cooling Tower Out Out Primary CHWP Secondary CHWP Condenser With In Heat Variable ExchangerSpeed Drive Chiller CWP Economizer CWP 9 Water-side pressure drop of 2-Way Valve < 15 ft of water OR Typical Cooling Coil Cooling 9 Bypassed when not in use Coil With Tertiary Pump , CHWS CHWR Figure 6-O from 90.1 User’s Manual 76 www.energycodes.gov/BECU
  • 77. Section 6 – 6.5.1.3 Integrated Economizer Control Economizers must be integrated with mechanical cooling systems and be capable of providing partial cooling even when additional mechanical cooling is required , 77 www.energycodes.gov/BECU
  • 78. Section 6 – 6.5.1.4 Economizer Heating System Impact Designed so economizer operation doesn’t increase the building heating energy use during normal operation , Exception 9 Economizers on VAV systems that cause zone level heating to increase due to a reduction in supply air temperature (VAV) , , 78 www.energycodes.gov/BECU
  • 79. Section 6 – 6.5.2.1 Zone Thermostatic Controls Capable of operating in sequence the supply of heating and cooling energy to the zone Controls prevent 9 Reheating 9 Recooling 9 Mixing or simultaneously supplying air previously heated or cooled 9 Other simultaneous operation of heating and cooling systems to the same zone 79 www.energycodes.gov/BECU
  • 80. Section 6 – 6.5.2.1 Zone Thermostatic Controls – Exceptions Zones for which volume of air that is reheated, recooled, or mixed is less than the larger of the following , 9 30% of zone design peak supply 30% 9 Outside air flow rate to meet 6.2 of Standard 62.1 for the zone ASHRAE Std. 62.1 6.2 9 Any higher rate that can be demonstrated to jurisdiction to reduce overall system annual energy usage 9 Air flow rate required to meet applicable codes or accreditation standards (pressure relationships or minimum air change rates) ( ) 80 www.energycodes.gov/BECU
  • 81. Section 6 – 6.5.2.1 Zone Thermostatic Controls – Exceptions (cont’d) Zones that comply with all of these 9 Air flow rate in dead band that doesn’t exceed larger of these , • 20% of zone design peak supply 20% • Outdoor air flow rate to meet 6.2 of Standard 62.1 for the zone ASHRAE Std. 62.1 6.2 • Any higher rate that can be demonstrated to jurisdiction to reduce overall system annual energy usage 9 Air flow rate that’s reheated, recooled, or mixed in peak heating demand < 50% of zone design peak supply , 50% 9 Air flow between dead band and full heating or full cooling to be modulated 9 Lab exhaust systems complying with 6.5.7.2 6.5.7.2 9 Zones where • 75% of energy for reheating or providing warm air in mixing systems is from site-recovered or site-solar source 75% 81 www.energycodes.gov/BECU
  • 82. Section 6 – 6.5.2.1.1 Supply Air Temperature Reheat Limit Zones with both supply and return/exhaust air openings > 6 ft above floor to not supply heating air > 20 F above space temperature / 6ft, 20oF 9Applies in other parts of the Standard where reheating is allowed Exceptions 9Laboratory exhaust systems complying with 6.5.7.2 6.5.7.2 9During preoccupancy building warm-up and setback 82 www.energycodes.gov/BECU
  • 83. Section 6 – 6.5.2.2 Hydronic System Controls To prevent the simultaneous heating and cooling in hydronic systems 83 www.energycodes.gov/BECU
  • 84. Section 6 – 6.5.2.2.1 Three-Pipe System No common return system for both hot and chilled water 84 www.energycodes.gov/BECU
  • 85. Section 6 – 6.5.2.2.2 Two-Pipe Changeover System 85 Diagram Courtesy of Ken Baker www.energycodes.gov/BECU
  • 86. Section 6 – 6.5.2.2.2 Two-Pipe Changeover System (cont’d) Two-pipe changeover system is allowed if it meets the following requirements: , 9 Dead band from one mode to another is • 15 F outdoor air temperature 15oF 9 Controls to allow operation of • 4 hours in one mode before changing to another mode 4 9 Reset controls so heating and cooling supply temperatures at changeover point no more than 30 F apart , 30oF 86 Diagram Courtesy of Ken Baker www.energycodes.gov/BECU
  • 87. Section 6 – 6.5.2.2.3 Hydronic (Water Loop) Heat Pump Systems Diagram Courtesy of Ken Baker 87 www.energycodes.gov/BECU
  • 88. Section 6 – 6.5.2.2.3 Hydronic (Water Loop) Heat Pump Systems (cont’d) Controls to provide heat pump water supply temperature deadband of at least 20 F between initiation of heat rejection and heat addition by central devices 20oF Cooling tower bypass or cooling tower isolation dampers A two-position valve at each hydronic heat pump for hydronic systems having a total pump system power > 10 hp 10hp , Exception 9 If system loop temperature optimization controller is used, deadband < 20 F is allowed 88 www.energycodes.gov/BECU
  • 89. Section 6 – 6.5.2.3 Dehumidification Humidistatic controls to prevent 9 Reheating 9 Mixing of hot and cold air streams 9 Heating and cooling of same air stream 89 www.energycodes.gov/BECU
  • 90. Section 6 – 6.5.2.3 Dehumidification Exceptions 9 Systems capable of reducing supply air flow to 50%, or to minimum ventilation 50%, 9 Systems under 80,000 BTU/h that can unload at least 50% 80,000 Btu/h, 50% 9 Systems smaller than 40,000 BTU/h 40,000 Btu/h 9 Process applications (exception does NOT apply to computer rooms) ( ) 9 75% of reheat or re-cool energy is recovered or solar 75% 90 www.energycodes.gov/BECU
  • 91. Section 6 – 6.5.2.4 Humidification Systems with hydronic cooling Valve and humidification systems Head Closes In Economizer Pressure Mode designed to maintain inside Control Valve In Evaporator Out humidity at > 35 F dewpoint Cooling Tower Out Condenser Primary CHWP Secondary CHWP With In Heat Variable temperature shall use a water CWP Chiller ExchangerSpeed Drive economizer if required by 6.5.1 Economizer CWP 6.5.1 , 2-Way Valve , 35oF , Typical Cooling Coil , Cooling Coil With Tertiary Pump CHWS CHWR 91 www.energycodes.gov/BECU
  • 92. Section 6 – 6.5.3 Air System Design and Control Each HVAC system with total fan system power > 5 hp to meet 6.5.3.1 through 6.5.3.2 5 hp 6.5.3.1 6.5.3.4. 9 Fan Power Limitation 9 VAV Fan Control – Part Load Fan Power Limitation – Static Pressure Sensor location – Set Point Reset 92 www.energycodes.gov/BECU
  • 93. Section 6 – 6.5.3.1 Fan Power Limitation Table 6.5.3.1.1A Two options: nameplate hp (Option 1) fan system bhp (Option 2) Exceptions 9Hospital, vivarium, and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control may use variable-volume fan power limitation , , , ( ) , . 9Individual exhaust fans with motor nameplate hp ” 1 hp 1 hp 93 www.energycodes.gov/BECU
  • 94. Section 6 – 6.5.3.1 Fan Power Limitation 6.5.3.1.1A Fan Power Limitation Option Limit Constant Volume Variable Volume Allowable Nameplate 1 hp CFMs*0.0011 hp CFMs*0.0015 Motor hp Allowable 2 Fan System bhp CFMs*0.00094+A bhp CFMs*0.0013+A bhp 94 www.energycodes.gov/BECU
  • 95. Section 6 – 6.5.3.1 Fan Power Limitation 6.5.3.1.1B Fan Power Limitation Pressure Drop Adjustment Device Adjustment Credits Fully ducted return and/or exhaust 0.5 in. w.c. (2.15 in. w.c. for laboratory and vivarium air system systems) Return and/or exhaust airflow 0.5 in. w.c. control devices Exhaust filters, scrubbers, or The pressure drop of device calculated at fan system other exhaust treatment design condition Particulate Filter Credit : 0.5 in. w.c. MERV 9-12 Particulate Filter Credit : 0.9 in. w.c. MERV 13-15 95 www.energycodes.gov/BECU
  • 96. Section 6 – 6.5.3.1 Fan Power Limitation 6.5.3.1.1B Fan Power Limitation Pressure Drop Adjustment Particulate Filter Credit : The pressure drop of device calculated at 2* MERV 16 and greater clean filter pressure drop at fan system and electronically enhanced filters design condition Carbon and other gas-phase air cleaners Clean filter pressure drop at fan system design condition Biosafety cabinet Pressure drop of device at fan system design condition Energy Recovery Device, other than Coil (2.2 Energy Recovery Effectiveness)-0.5 in. Runaround Loop w.c. for each airstream Coil Runaround Loop 0.6 in. w.c. for each airstream Evaporative humidifier/cooler in series with Pressure drop of device at fan system design another cooling coil condition Sound Attenuation Section 0.15 in. w.c. Exhaust system serving fume hoods 0.35 in. w.c. laboratory and vivarium exhaust systems in 0.25 in. w.c. / 100ft of vertical duct exceeding high-rise building 75ft 96 www.energycodes.gov/BECU
  • 97. Section 6 – 6.5.3.1.2 Motor Nameplate Horsepower Selected fan motor to be no larger than first available motor size greater than bhp , (BHP) Fan bhp on design documents (BHP) Exceptions 9 Fans < 6 bhp, where first available motor larger than bhp has nameplate rating within 50% of bhp, next larger nameplate motor size may be selected 6 bhp , (bhp) 50% , 9 Fans • 6 bhp, where first available motor larger than bhp has nameplate rating within 30% of bhp, next larger nameplate motor size may be selected 6 bhp( ) , (bhp) 30% , 97 www.energycodes.gov/BECU
  • 98. Section 6 – 6.5.3.2.1 Part-Load Fan Power Limitation Individual VAV fans with motors • 10 hp 10 hp( ) (VAV) 9 Must have either: – Variable Speed Drive – Vane axial fan with variable-pitch fan blades – Other controls and devices to result in fan motor demand ” 30% of design wattage at 50% of design air volume when static pressure set point = 1/3 of total design static pressure, based on manufacturer’s certified fan data – , 1/3 , 50% , 30% 98 www.energycodes.gov/BECU
  • 99. Section 6 – 6.5.3.2.2 Static Pressure Sensor Location Placed so controller set point is ” 1/3 the total design fan static pressure , 1/3 9 Except for digital control systems with zone reset capabilities where it may be at the fan discharge , Install multiple sensors in each major branch if sensor would be located downstream of a major duct split , 99 www.energycodes.gov/BECU
  • 100. Section 6 – 6.5.3.2.3 Setpoint Reset For systems with direct digital control of individual zone boxes reporting to the central control panel 9 Static pressure set point reset based on zone requiring the most pressure 100 www.energycodes.gov/BECU
  • 101. Section 6 – 6.5.3.3 Multiple-zone VAV System Ventilation Optimization Control In multiple-zone VAV systems with DDC of individual zone boxes reporting to central control panel DDC 9 Include means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency as per Standard 62.1, Appendix A ( Std. 62.1 A ), 101 www.energycodes.gov/BECU
  • 102. Section 6 – 6.5.3.3 Multiple-zone VAV System Ventilation Optimization Control Exceptions Exceptions 9 VAV systems with zonal transfer fans that recirculate air from other zones without directly mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fan-powered terminal units , , , . 9 Systems required to have exhaust air energy recovery complying with 6.5.6.1 6.5.6.1 9 Systems where total design exhaust airflow is > 70% of total outdoor air intake flow requirements 70% 102 www.energycodes.gov/BECU
  • 103. Section 6 – 6.5.3.4 Supply-air Temperature Reset Controls Multiple zone HVAC systems to have controls to automatically reset supply-air temperature in response to building loads or outdoor air temperature , , Controls to be capable of resetting supply air temperature at least 25% of difference between design supply-air temperature and design room air temperature 25% Controls that adjust the reset based on zone humidity are okay Zones expected to experience relatively constant loads to be designed for fully reset supply temperature ¸ 103 www.energycodes.gov/BECU
  • 104. Section 6 – 6.5.3.4 Supply-air Temperature Reset Controls Exceptions Exceptions 9 Climate zones 1a, 2a, and 3a 1a, 2a, 3a 9 Systems that prevent reheating, recooling or mixing of heated and cooled supply air , , 9 75% of energy for reheating is from site-recovered or site solar energy sources 75% 104 www.energycodes.gov/BECU
  • 105. Section 6 – 6.5.4 Hydronic System Design and Control HVAC hydronic systems with total pump system power > 10 hp to meet 6.5.4.1 – 6.5.4.4 10 hp , 6.5.4.1-6.5.4.4 9 Hydronic Variable Flow Systems 9 Pump Isolation 9 Chilled and Hot Water Temperature Reset 9 Hydronic (water-loop) Heat Pumps and Water-Cooled Unitary Air-Conditioners ( ) 9 Pipe Sizing 105 www.energycodes.gov/BECU
  • 106. Section 6 – 6.5.4.1 Hydronic Variable Flow HVAC pumping systems to include control valves 9 Designed to modulate or step open and close as a function of load , 9 Designed for variable fluid flow 9 Capable of reducing flow rates to ” 50% of design flow rate 50%( ) Individual pumps serving variable flow systems with a motor > 5 hp , 5 hp 9 Have controls and/or devices resulting in pump motor demand ” 30% of design wattage at 50% of design water flow / , 50% , 30% 106 www.energycodes.gov/BECU
  • 107. Section 6 – 6.5.4.1 Hydronic Variable Flow (cont’d) Differential pressure setpoint to be ” 110% of that required to achieve design flow through the heat exchanger 110% If differential pressure control and DDC controls are used DDC 9 Reset setpoint downward based on valve positions until one valve is nearly wide open 107 www.energycodes.gov/BECU
  • 108. Section 6 – 6.5.4.1 Hydronic Variable Flow Exceptions 9 Systems where – Minimum flow is < minimum flow required by equipment manufacturer for proper operation of equipment served by the system – Total pump system power ” 75 hp 75 hp( ) 9 Systems that include ” 3 control valves 3 108 www.energycodes.gov/BECU
  • 109. Section 6 – 6.5.4.2 Pump Isolation If chilled water plant has more than one chiller or boiler plant has more than one boiler 9 Provide for flow reduction when chiller or boiler is shut down , 109 www.energycodes.gov/BECU
  • 110. Section 6 – 6.5.4.3 Chilled and Hot Water Temperature Reset Controls Affects systems with design capacity > 300,000 Btu/h 300,000 Btu/h , 9 To include controls to automatically reset supply water temperatures by representative building loads (including return water temperature) or by outside air temperature ( ) Exceptions 9 If controls would result in improper operation 9 Hydronic systems with variable flow 110 www.energycodes.gov/BECU
  • 111. Section 6 – 6.5.4.4 Hydronic Heat Pumps and Water-Cooled Unitary Air-Conditioners 9 Two-position valves at each hydronic heat pump must be provided and interlocked to shut off water flow to the heat pump when the compressor is off , Exceptions 9 Units using water economizers For hydronic heat pumps and water-cooled unitary ACs with total pump power > 5 hp 5hp 9 Controls or devices must be provided to have pump motor demand ” 30% of design wattage at 50% of design water flow / , 50% , 30% 9 This basically converts the system into a variable flow system. As such, these systems must also comply with 6.5.4.1 6.4.4.1 111 www.energycodes.gov/BECU
  • 112. Section 6 – 6.5.4.5 Pipe Sizing Chilled-water and condenser-water piping so design flow rate in each segment doesn’t exceed values in Table 6.5.4.5. , , 6.5.4.5 This table presents the maximum allowed flow rates per section of pipe as a function of the following three criteria: , – Pipe size – Annual hours of operation – System flow and control 112 www.energycodes.gov/BECU
  • 113. Section 6 – 6.5.4.5 Pipe Sizing Exceptions Exceptions 9Rates exceeding the Table are allowed if the specific section of pipe in question isn’t in the critical circuit > 30% of operating hours , 30%, 6.5.4.5 9Piping systems with equivalent or lower total pressure drop than the same system with standard weight steel pipe with piping and fittings sized per the Table 6.5.4.5 , 113 www.energycodes.gov/BECU
  • 114. Section 6 – 6.5.5 Heat Rejection Equipment Applies to heat rejection equipment used in comfort cooling systems such as 9 Air-cooled condensers 9 Open cooling towers 9 Closed-circuit cooling towers 9 Evaporative condensers Exceptions 9 Heat rejection devices included as an integral part of equipment listed devices whose energy usage is included in Tables 6.8.1A-6.8.1D , Tables 6.8.1A 6.8.1D 114 www.energycodes.gov/BECU
  • 115. Section 6 – 6.5.5.2 Fan Speed Control Fan Speed Control 9 Each fan powered by a motor • 7.5 hp 7.5 hp( ) – Have capability to operate fan at ” 2/3 full speed 2/3 – Have controls to automatically change the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat rejection device 115 www.energycodes.gov/BECU
  • 116. Section 6 – 6.5.5.2 Fan Speed Control Exceptions Exceptions – Condenser fans serving multiple refrigerant circuits or flooded condensers – Installations in climates zones 1 and 2 1 2 – Up to 1/3 of the fans on a multiple fan application speed controlled 1/3( ) , 116 www.energycodes.gov/BECU
  • 117. Section 6 – 6.5.5.3 Limitation on Centrifugal Fan Open-Circuit Cooling Towers • If towers have a combined rated capacity • 1100 gpm at 95 F condenser water return, 85 F condenser water supply, and 75 F outdoor air wet-bulb temperature , 1100gpm( ) , 95oF 85oF , 75oF – Must meet requirement for axial fan open-circuit cooling towers in Table 6.8.1G 6.8.1G Exceptions – Ducted (inlet or discharge) ( ) – Require external sound attenuation 117 www.energycodes.gov/BECU
  • 118. Section 6 – 6.5.6.2 Heat Recovery for Service Water Heating Condenser recovery required if , 9 24 hrs per day and 24 , 9 Heat rejection > 6,000,000 Btu/h and 6,000,000 Btu/h, 9 SWH load > 1,000,000 Btu/h 1,000,000 Btu/h The required heat recovery system shall have the capacity to provide the smaller of 9 60% of the peak heat rejection load at design conditions or 60%, 9 preheat of the peak service hot water draw to 85 F. 85 oF 118 www.energycodes.gov/BECU
  • 119. Section 6 – 6.5.6.2 Heat Recovery for Service Water Heating Exceptions Exceptions 9If condenser heat recovery is used for space heating with a heat recover design > 30% of peak water-cooled condenser load at design conditions , 30% 9If 60% of service water heating is provided from site-solar or site-recovered energy or other sources 60% 119 www.energycodes.gov/BECU
  • 120. Section 6 – 6.5.7.1 Kitchen Exhaust Systems • Replacement air introduced directly into hood cavity to be ” 10% of hood exhaust airflow rate 10% • Conditioned supply air to not exceed the greater of : – Supply flow required to meet space heating or cooling load – Hood exhaust flow minus available transfer air from adjacent spaces 120 www.energycodes.gov/BECU
  • 121. Section 6 – 6.5.7.1 Kitchen Exhaust Systems • If kitchen/dining facility has total kitchen hood exhaust airflow rate > 5,000 cfm, each hood’s exhaust rate must comply with Table 6.5.7.1.3 / 5000cfm , 6.5.7.1.3 – If a single hood or hood section is over appliances with different duty ratings, then the max. airflow rate for that can’t exceed the Table values for highest appliance duty rating under that hood or hood section , , Exception • If at least 75% of all replacement air is transfer air that would otherwise be exhausted 75% , . 121 www.energycodes.gov/BECU
  • 122. Section 6 – 6.5.7.1 Kitchen Exhaust Systems, con’t 9 Kitchens/dining facilities with total kitchen hood exhaust airflow rate > 5,000 cfm must have one of these: / 5000cfm , : – At least 50% of all replacement air is transfer air that would otherwise be exhausted 50% , . – Demand ventilation systems on at least 75% of exhaust air (capable of at least 50% reduction in exhaust and replacement air system airflow rates) , 75% . 50% – Listed energy recovery devices with sensible heat recover effectiveness of not less than 40% on at least 50% of the total exhaust airflow 50% , 40% 122 www.energycodes.gov/BECU
  • 123. Section 6 – 6.5.7.1 Kitchen Exhaust Systems, con’t 9 Performance testing must be done using an approved field test method 9 If demand control ventilation systems are used, additional testing is required , 123 www.energycodes.gov/BECU
  • 124. Section 6 – 6.5.7.2 Laboratory Exhaust Systems 9 Laboratory exhaust systems with total exhaust rate > 5,000 cfm to have one of the following 5,000 cfm , : 9 VAV lab exhaust and room supply system capable of reducing exhaust and makeup air flow rates and/or incorporate a heat recovery system , / 9 VAV lab exhaust and room supply systems required to have minimum circulation rates to comply with code to be capable of reducing zone exhaust and makeup air flow rates to the regulated minimum circulation values or minimum required to maintain pressurization relationship requirements , , , 9 Non-regulated zones capable of reducing exhaust and makeup air flow rates to 50% of zone design values or minimum required to maintain pressurization relationship requirements , 50% , 124 www.energycodes.gov/BECU
  • 125. Section 6 – 6.5.7.2 Laboratory Exhaust Systems (Cont’d) 9 Direct makeup air supply to equal at least 75% of exhaust air flow rate, heated no warmer than 2 F below room setpoint, cooled to no cooler than 3 F above room setpoint, no humidification added, and no simultaneous heating and cooling used for dehumidification control 75% ( ) , 2oF, 3oF, , , 125 www.energycodes.gov/BECU
  • 126. Section 6 – 6.5.8 Radiant Heating Systems Required for unenclosed spaces exception: loading docks with air curtains : 126 www.energycodes.gov/BECU
  • 127. Section 6 – 6.5.8 Radiant Heating Systems “Radiant heating systems that are used as primary or supplemental enclosed space heating must be in conformance with the governing provisions of the standard” • , 9 Radiant hydronic ceiling or floor panels 9 Combination or hybrid systems with radiant heating (or cooling) panels ( ) 9 Radiant heating (or cooling) panels used in conjunction with other systems such as VAV or thermal storage systems ( ) , 127 www.energycodes.gov/BECU
  • 128. Section 6 – 6.5.9 Hot Gas Bypass Limitation Rated capacity Maximum HGBP capacity, of system % of total capacity ” 240,000 Btu/h 50% > 240,000 Btu/h 25% 9 Applied in systems with stepped or continuous unloading 9 Limitation also pertains to chillers 9 Exception: Packaged unitary systems ” 90,000 Btu/h (7.5 tons) : 90,000 Btu/h 128 www.energycodes.gov/BECU
  • 129. Section 6 – 6.7 Submittals 9 Record drawings 9 Operating and maintenance manuals 9 System balancing 9 System commissioning 129 www.energycodes.gov/BECU
  • 130. Section 6 – 6.7.2.1 Drawings Record drawings of actual installation to building owner within 90 days of system acceptance and include, as a minimum 90 . 9 Location and performance data on each piece of equipment 9 General configuration of duct and pipe distribution system including sizes , 9 Terminal air or water design flow rates 130 www.energycodes.gov/BECU
  • 131. Section 6 – 6.7.2.2 Manuals Operating and maintenance manuals to building owner within 90 days of system acceptance and include several items 90 131 www.energycodes.gov/BECU
  • 132. Section 6 - 6.7.2.3 System Balancing 9 Systems shall be balanced in accordance with accepted engineering standards 9 Written report for conditioned spaces > 5000 ft2 5,000 ft2 , 9 Minimize throttling losses 9 For fans with system power > 1 hp 1 hp – Adjust fan speed to meet design flow conditions 132 www.energycodes.gov/BECU
  • 133. Section 6 – 6.7.2.3.3 Hydronic System Balancing Proportionately balanced to minimize throttling losses Pump impeller trimmed or pump speed adjusted to meet design flow conditions Each system to have either the ability to measure differential pressure increase across the pump or have test ports at each side of the pump Exceptions 9 Pumps with pump motors ” 10 hp 10 hp( ) 9 When throttling results in < 5% of the nameplate hp draw, or 3 hp, whichever is greater, above that required if the impeller was trimmed 5%, 3hp, , 133 www.energycodes.gov/BECU
  • 134. Section 6 – 6.7.2.4 System Commissioning Control elements are calibrated, adjusted, and in proper working condition , ¾ 50,000 ft2 conditioned area 50,000 ft2 9 Except warehouses and semiheated spaces 9 Requires commissioning instructions 134 www.energycodes.gov/BECU