6. metrics in practice
V.S. CO2
Energy Green House
Consumption Gas Emissions
In Ontario,
electricity emits 281 g eCO2/kWh
natural gas emits 190 g eCO2/kWh
19. Where does ASHRAE 62.1 apply?
• Any building intended for human
occupancy
• Except residential (< 3 storeys)
• Regularly occupied and
unoccupied spaces
• Single- and multi-zone systems
20. ASHRAE 62.1
ASHRAE specifies two different ways to
calculate minimum ventilation rates:
Ventilation Rate Procedure
• Required by most codes
• LEED EQp1 requirement
• Minimum OA ventilation rate
OR
Indoor Air Quality Procedure
• Rarely used (not credited by LEED)
22. Breathing zone OA flow (Vbz)
Vbz = (Rp*Occupancy) + (Ra*Area)
Table 6-1: ASHRAE 62.1
23. Zone Air Distribution Effectiveness
Ceiling supply of cold Ceiling supply of warm
air (typical VAV) air (VAV with reheat coils)
effectiveness = 1 effectiveness = 0.8
24. Zone Air Distribution Effectiveness
Displacement ventilation Under floor air distribution
(floor supply of cool air) (mixing of air at 1.4m AFF)
effectiveness = 1.2 effectiveness = 1
25. Modes of Ventilation
Mixed Air Systems
• VAV, CV, Induction Unit
• Return air is mixed with
outdoor air
• Air handler provides
ventilation and conditioning
air
• Fans and dampers are
sized for cooling load
typically
Mixing Dampers
• Outdoor air provided is
based on the outdoor air
fraction required at the
“critical zone”
ASHRAE Fundamentals – Chapter 27
26. Modes of Ventilation
Decoupled Systems
• DOAS or 100% OA
• No mixing of return air with
outdoor air
• Stale air is exhaust from the
space
• Heating/cooling provided in
the zone by radiant panels,
heat pumps, or fancoils.
• Outdoor air provided is sum
of outdoor air required in all
zones
Modified from ASHRAE Fundamentals – Chapter 27
27. Modes of Ventilation
Natural Ventilation
• Ventilation is provided
without the use of fans
through operable windows
or dampers
• Process is driven by wind
pressure or stack effect
• Challenges with
implementing in our climate
• May see mixed mode
systems that use natural
ventilation when the OA
temp is acceptable
http://www.architecture.uwaterloo.ca/faculty_projects/terri/carbon-aia/case/global/global10.html
29. Ventilation Energy
General Exhaust
Sanitary Exhaust
• Outdoor air required for
BAS – Time of Day Schedule ventilation.
• Outdoor air must usually
be heated or cooled.
• That requires energy.
Outdoor
Air
Supply
Air
Return
Air
30. Ventilation Energy Recovery
• Exhaust air has energy in it (warmth in
winter, “coolth” in summer)
• Concept: Use that energy to temper the
incoming outdoor air
31. Heat vs. Energy
Recovery
Common Terms:
• “Heat Recovery Wheel”
• “Heat Recovery Ventilator”
• “Energy Recovery Wheel”
• “Enthalpy Wheel”
• “Energy Recovery
Ventilator”
• “Total Energy Wheel”
• Change in DB is sensible
heat (dry)
• Change in WB is latent
heat (wet)
32. Wheels
• Pros:
• Efficient
• Both heat and
humidity
• Cons:
• Big
• Bulky (square)
41. focus
What’s
important?
Source: Halsall building
performance database
42. focus
What’s
important?
Ventilation
Source: Halsall building
performance database
43. focus
On Ventilation
1. Window-to-wall ratio
2. Lighting power (fixtures and controls)
3. Window performance (highest U-value affordable)
4. Separate ventilation from heating and cooling
(and low-energy hydronic heating and cooling)
5. Ventilation heat-recovery
6. Demand-controlled ventilation
7. Condensing heating boilers
8. Chiller efficiency (including chiller heat-recovery)
9. Wall and roof insulation (MNECB + R20 max)
10. Domestic hot water flow
Adapted from Stephen Pope, NRCan
(List prioritized for BC Lower Mainland)
47. HVAC Systems
Heating Ventilation Air Conditioning
The purpose of an HVAC system is to control:
• Temperature
• Moisture (humidity)
• Supply of outside air for ventilation
• Filtration
• Air movement in occupied spaces
48. HVAC Components
t
sst
auu
hha
PLANT
PLANT x
EEx
DISTRIBUTION
S
NE
ZO
Ventilation
Ventilation
59. System Types –Single Zone Air
Systems (Single Duct)
Air is supplied to a single
zone:
• May or may not heat
• Constant or variable volume
• Constant or Variable temperature
• Supply fan only, or return fan too
• Cooling by DX or chilled water.
• Heating by natural gas, or hot water
• Provides ventilation
• Simple controls
60. System Types –Multi Zone Air
Systems (Single Duct)
Air is supplied to multiple zones:
• Generally cooling only
• Constant (CV) or variable volume (VAV)
• Constant or Variable temperature
• Supply fan only, or return fan too
• Cooling by DX or chilled water.
• Heating by natural gas, or hot water
• Provides Ventilation
• Complicated Controls
61. System Types –Multi Zone Air
Systems (Dual Duct)
Air is supplied to multiple zones:
• Heating and cooling by air
• CV or VAV
• Single fan or Dual fan (2 Supply Fans)
• Used to avoid piping water
• Cooling by DX or chilled water.
• Heating by natural gas or hot water
• Provides ventilation
• Very Complicated Controls
62. System Types – Mixed
Fan Coils / Heat Pumps / Induction Units
Heating and Cooling is distributed
to/from zone by water
• Heating and cooling in zone by air
• CV
• Single fan
• Needs ventilation ducted to space
• Simple Controls
63. System Types – Water
Heating and Cooling is distributed
to/from zone by water
• Heating / Cooling is done by water
• Used typically with displacement
ventilation but can be used with airside
cooling
• Radiant cooling requires tight controls
on humidity
• Controls can be fairly simple or very
complex
66. Making Decisions
What & When
Concept Design
•Zone Terminal
•Distribution Method
•Systems and Plants
Schematic Design Detailed Design
•Building Loads •Equipment Type,
•Plant Location Location, and Size
•Distribution Size and •Control Strategy
Path •Coordination
Tender
•Contractors
•Equipment
67. Making Decisions
Challenges
Concept Design
•Mechanical / Energy
Modeling not involved
this early
Schematic Design Detailed Design
•Space Limitations •Service Space
•Incomplete information •Coordination
•Changes
Tender
•Controls
73. The Operational Reality
How does it run?
How is it used?
Building Occupant
operations space use Users account for 25% to
50% of all energy in a
commercial office building.
Building
systems
74. Off is better than Efficient
Provide Controllability
– Lighting controls
– Separate ventilation from
heat/cool
– Decentralized conditioning
– Tenant engagement
– Simple to Operate
Manual override to turn ON
76. Biomass
Plant derived organic material
Used as fuel source
Direct or indirect combustion
Continuous (unlike wind / solar)
Fuel is cheap
Delivery and storage can be an
issue
77. Combined Heat and Power
Electricity and Heat
Fossil or biomass fuels
Needs a heating base load year
round for full efficiency
Economics depend on utilities
78. Fuel Cells
Direct energy conversion (no
combustion)
No moving parts
Quiet
Fuel flexibility
Expensive
Very early building applications
79. Ground Source Systems
Heating and cooling system
Usually combined with a electric
heat pump system
Effectiveness depends on
ground conditions
Requires a balanced heating /
cooling load to be most
efficient
82. Solar Cooling
Solar thermal energy
Combined with absorption chiller
Often combined with CHP
Solution to “what to do with solar
thermal in summer”
83. The Game
Real-World Application of Low-Energy Design
William Ding’s Novelty Bat Factory Head Office
40,000 sf two-story office building
Cheap, inefficient design
You’re hired as the Sustainability Consultant
84. Energy Modelling Wizard Game
The Rules:
Six Teams
– Company A (3 teams)
– Company B (3 teams)
Each Team starts at different point:
– Conceptual
– Design Documents
– Construction Documents
88. Energy Modelling Wizard Game
Long east-west axis gives greater
access to daylight with ease of glare
control and reduced heat gain
Long north-south axis creates greater
exposure to low angle sun with more
glare and heat gain
N
Building BUILDING