LU-VE has experience producing heat exchangers for refrigeration and HVAC, especially with natural refrigerants like CO2. They presented on CO2 heat exchangers and their work on the NXTHPG project. Their CO2 test facility in Europe allows them to test heat exchangers under stationary conditions. Software predictions of capacity and pressure drop generally match test results well within 10%. Testing of CO2 evaporators showed capacity increases with Reynolds number as expected. Their 5mm tube CO2 coil for the NXTHPG project was smaller and lighter than the standard design while maintaining performance. CFD analysis helped optimize the fan configuration to increase COP by 2%.