This document discusses faults in power systems, including types (open circuit and short circuit), causes, and effects. Open circuit faults are caused by failures of conductors and can cause unbalanced voltages and currents. Short circuit faults are caused by insulation failures and result in abnormally high currents, potentially damaging equipment. Faults are classified as symmetrical (all phases shorted simultaneously) or unsymmetrical. Unsymmetrical faults like single line-to-ground are most common. When faults occur, protection devices like circuit breakers and relays quickly isolate the faulty section to prevent damage.
This document discusses out-of-step (OOS) protection fundamentals. It explains that power swings can cause undesired relay operation and lead to cascading outages. It discusses relay elements prone to operate during power swings like distance and overcurrent relays. It describes stable and unstable power swings and the need for OOS protection to separate asynchronous areas. The document outlines various OOS protection functions like power swing blocking and out-of-step tripping and discusses their benefits. It analyzes relay and generator performance during OOS conditions using system examples. Finally, it recommends protection system and other grid improvements to preserve stability.
System protection is used to detect problems in power system components and isolate faulty equipment to maintain reliable power. The key elements of a protection system include differential relays to protect generators and transformers from internal faults, overcurrent and distance relays to protect transmission lines from external faults, and bus differential relays to protect distribution buses. Protective devices are needed to maintain acceptable operation, isolate damaged equipment, and minimize harm to personnel and property.
This document discusses restricted earth fault (REF) protection schemes for transformers and generators. It explains that a REF scheme is needed to detect internal earth faults since they may not cause current to flow through the external overcurrent protection. A REF scheme works by summing the currents entering and exiting a protected zone using two sets of current transformers, and tripping if the sums are unequal, indicating an internal fault. Key elements of a REF scheme include the REF relay, stabilizing resistor to avoid spurious trips from CT mismatches, and specifying a high knee point voltage for the CTs. Examples of REF schemes for generators and transformer configurations are also provided.
The document discusses transformer protection. It describes various failures that can occur in transformers such as winding failures, bushing failures, and tap changer failures. It provides statistics on historical transformer failures. It also discusses different types of protection for transformers including electrical protection methods like differential protection, overcurrent protection, overexcitation protection and thermal protection. Internal short circuits, system short circuits, and abnormal conditions are some of the issues addressed by transformer protection schemes.
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
Part 1. Generator Protection
Protection of generators against stator faults
Rotor faults and abnormal conditions
Restricted earth fault and inter-turn fault protection
Numerical examples
The following topics are covered: components of power distribution systems, fuses, padmounted transformers, pole mounted transformers, vault installed transformers, transformer stations protection, transformer connections, thermometers, pressure relief devices, restricted ground faults, differential protection current transformers connections, overexcitation, inrush current, percentage differential relays, gas relays, characteristics of CTs.
The document discusses over current protection in electrical systems. It describes over current as a situation where excess current flows through a conductor, risking heat generation and equipment damage. Possible causes of over current include short circuits, excessive load, incorrect design, or ground faults. Over current relays protect systems by detecting excess current from current transformers and tripping circuit breakers. Relays are classified based on their time of operation as instantaneous, definite time, or inverse time relays. The document outlines various over current protection schemes used in electrical equipment like transformers and generators.
This document discusses out-of-step (OOS) protection fundamentals. It explains that power swings can cause undesired relay operation and lead to cascading outages. It discusses relay elements prone to operate during power swings like distance and overcurrent relays. It describes stable and unstable power swings and the need for OOS protection to separate asynchronous areas. The document outlines various OOS protection functions like power swing blocking and out-of-step tripping and discusses their benefits. It analyzes relay and generator performance during OOS conditions using system examples. Finally, it recommends protection system and other grid improvements to preserve stability.
System protection is used to detect problems in power system components and isolate faulty equipment to maintain reliable power. The key elements of a protection system include differential relays to protect generators and transformers from internal faults, overcurrent and distance relays to protect transmission lines from external faults, and bus differential relays to protect distribution buses. Protective devices are needed to maintain acceptable operation, isolate damaged equipment, and minimize harm to personnel and property.
This document discusses restricted earth fault (REF) protection schemes for transformers and generators. It explains that a REF scheme is needed to detect internal earth faults since they may not cause current to flow through the external overcurrent protection. A REF scheme works by summing the currents entering and exiting a protected zone using two sets of current transformers, and tripping if the sums are unequal, indicating an internal fault. Key elements of a REF scheme include the REF relay, stabilizing resistor to avoid spurious trips from CT mismatches, and specifying a high knee point voltage for the CTs. Examples of REF schemes for generators and transformer configurations are also provided.
The document discusses transformer protection. It describes various failures that can occur in transformers such as winding failures, bushing failures, and tap changer failures. It provides statistics on historical transformer failures. It also discusses different types of protection for transformers including electrical protection methods like differential protection, overcurrent protection, overexcitation protection and thermal protection. Internal short circuits, system short circuits, and abnormal conditions are some of the issues addressed by transformer protection schemes.
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
Part 1. Generator Protection
Protection of generators against stator faults
Rotor faults and abnormal conditions
Restricted earth fault and inter-turn fault protection
Numerical examples
The following topics are covered: components of power distribution systems, fuses, padmounted transformers, pole mounted transformers, vault installed transformers, transformer stations protection, transformer connections, thermometers, pressure relief devices, restricted ground faults, differential protection current transformers connections, overexcitation, inrush current, percentage differential relays, gas relays, characteristics of CTs.
The document discusses over current protection in electrical systems. It describes over current as a situation where excess current flows through a conductor, risking heat generation and equipment damage. Possible causes of over current include short circuits, excessive load, incorrect design, or ground faults. Over current relays protect systems by detecting excess current from current transformers and tripping circuit breakers. Relays are classified based on their time of operation as instantaneous, definite time, or inverse time relays. The document outlines various over current protection schemes used in electrical equipment like transformers and generators.
This PPT explains about the circuit breaker, and its types. Then about the need and purpose of the circuit breaker. And finally the testing and types of testing of circuit breakers.
Power System Faults and Protection SystemHarshalJain48
The document discusses various types of faults that can occur in power systems, including symmetrical and unsymmetrical faults. It describes different fault types like line-to-line, line-to-ground, and double line-to-ground faults. Protection devices for power systems are also covered, such as circuit breakers, relays including impedance, distance, and differential relays. Current transformers and potential transformers are explained for their use in protection schemes. Classification of faults by category and probability is presented. Common faults in generators like stator and rotor faults are summarized.
Directional and differential relays operate based on the direction and magnitude of current flow in a circuit. Directional relays only operate when power flows in a specific direction, typically away from a protected zone. Differential relays compare current magnitudes at both ends of a protected zone and operate when there is a difference, indicating an internal fault. Percentage or biased beam differential relays include a restraining coil to prevent operation under heavy load conditions by requiring a higher differential current threshold. Translay systems use voltage balance between relay windings rather than current transformer secondaries to protect long cable runs while avoiding accuracy issues of traditional voltage balance schemes.
Differential protection relays operate by comparing electrical quantities on both sides of a circuit. They provide precise unit protection for equipment. There are several types, including current, voltage, biased, and voltage balance differential relays. Current differential relays compare currents entering and leaving a system, while voltage balance relays use pilot wires and current transformers to compare voltages induced at both ends of a protected feeder. Differential relays have advantages like fast operation for very close internal faults and less incorrect operation during external faults.
The document provides an overview of substation protection basics. It discusses why protection is needed to detect faults and isolate faulty equipment. The main types of faults are described along with the causes of insulation failures. The types of protection principles covered include overcurrent, differential, pilot wire, and distance protection. Key elements of a protection scheme like circuit breakers, relays, batteries, and transformers are also mentioned.
How is power transformer protected??? This provides a basic understanding of power transformer. Furthermore, the protective relay application on power transformer is included.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
This document discusses generator protection techniques. It begins by explaining why protective systems are needed to protect expensive power system elements like generators. It then describes different types of generator faults and various protection schemes. These include stator protection using differential protection and its modifications. Rotor faults and their protections like rotor earth fault protection are also explained. The document provides details on other protections like overcurrent, overvoltage, vibration and overheating protections. It concludes by stating that protective devices help detect faults, notify maintenance, and disconnect faulty elements to ensure continuous and safe operation of power systems.
This document provides an overview of the EE2402 Protection & Switchgear course presented by C.Gokul. It includes the course syllabus, units covered, textbook references and introductory content on power system basics, components, faults, protection elements, relay terminology and essential qualities of protection systems. The key topics discussed are types of faults in power systems, importance of protective schemes, elements of a protection system including current transformers, voltage transformers, relays and circuit breakers. Neutral earthing methods with a focus on Peterson coil are also introduced.
The document discusses transformer protection. It describes different types of faults that can occur in transformers, both internal and external. It then discusses various protection methods for transformers, including differential protection, sudden pressure relays, overcurrent protection, and thermal protection. It also provides details on magnetizing inrush current and how it is influenced by factors like transformer size, system resistance, and residual flux levels.
Why do Transformers Fail?
�The electrical windings and the magnetic core in a transformer are subject to a number of different forces during operation, for example:
�Expansion and contraction due to thermal cycling
�Vibration
�Local heating due to magnetic flux
�Impact forces due to through-fault current
�Excessive heating due to overloading or inadequate cooling
POWER SYSTEM PROTECTION
Protection Devices and the Lightning,. protection,
Lightning protection, Introduction
Air Break Switches
Disconnect switches
Grounding switches
Current limiting reactors
Grounding transformers
Co-ordination of protective devices
Grounding of electrical installations
Electric shock
Lightning protection
Lightning Arrestor
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
Vacuum circuit breakers use vacuum to extinguish the arc when opening contacts. They have fixed contacts, moving contacts, and an arc shield mounted inside a vacuum chamber. When a fault is detected, the contacts separate and the arc is quickly extinguished in the vacuum. This allows vacuum circuit breakers to reliably interrupt high fault currents. They have advantages over other circuit breakers like being compact, reliable, and able to interrupt heavy fault currents without fire hazards.
Protection of transmission lines(encrypted)Rohini Haridas
This document discusses protection methods for transmission lines. It describes:
1. Transmission lines require more protective schemes than other equipment due to their long lengths and exposure, making faults more common.
2. Key methods of transmission line protection include time-graded overcurrent protection, differential protection, current-graded overcurrent protection, and distance protection.
3. Distance protection uses impedance relays that can discriminate between faults along the line and those near the end, providing more selective operation than overcurrent protection alone. It describes implementations using simple impedance, reactance, and mho relays.
The document outlines various components of a power system protection system. It discusses the need for protection to maintain reliable power supply and minimize equipment damage. The key elements to be protected include generators, transformers, transmission lines, and busbars. Protection schemes for each element are then described, such as differential protection for generators and transformers, Buchholz relays for transformers, and distance and line differential protection for transmission lines.
The document discusses substations and their components. It defines a substation as an assembly of apparatus that transforms electrical energy from one form to another, such as changing voltage levels. Substations contain step-up transformers to increase voltage for transmission and step-down transformers to decrease voltage for distribution to consumers. The document describes various types of substations and explains their functions. It also provides details about components within substations such as circuit breakers, transformers, buses, isolators and instrument transformers.
This document discusses basic protection and relaying schemes used in power systems. It begins by explaining why protection systems are needed to handle severe disturbances that could jeopardize the power system. The key elements of a protection system are then introduced, including protective relays, circuit breakers, and current/voltage transducers. Common protection schemes like overcurrent, directional overcurrent, distance, and differential protection are described at a high level. The advantages of digital relays over electromechanical relays are also briefly mentioned. Overall, the document provides a high-level overview of protection systems and some of the basic schemes used to protect different components in a power grid.
Voltages and currents present at the generator's rated voltage and current are provided as examples. Sample relay setting calculations are shown for generator protection elements including 59N neutral overvoltage, 27TN third harmonic undervoltage, 46 negative sequence overcurrent, and coordination between protective devices. Formulas for calculating voltage and current settings from generator nameplate data are demonstrated.
A fault in a power system is any abnormal condition involving electrical failure of equipment like transformers or generators. There are two main types of faults: open circuit faults caused by a failure of conductors, and short circuit faults resulting from insulation or conducting path failures. Unsymmetrical faults like single-line-to-ground are the most common, accounting for 70-80% of faults, while symmetrical three-phase faults are rare but severe. Faults can be caused by weather, equipment failures, human errors, or fires and can damage equipment if not cleared quickly.
The document discusses various types of underground transmission line faults including short circuits caused by insulation failures, open circuits from broken wires or blown fuses, symmetrical faults affecting all phases equally, and unsymmetrical faults including line to ground, line to line, and double line to ground faults. It also mentions over voltage from poor power regulation, under voltage from increased loads or transformer issues, and over current faults from short circuits. Insulation heating problems from air infiltration or moisture are discussed. The document provides a circuit diagram for testing faults and lists components used. Causes of faults include broken conductors and safety issues are among the effects.
This PPT explains about the circuit breaker, and its types. Then about the need and purpose of the circuit breaker. And finally the testing and types of testing of circuit breakers.
Power System Faults and Protection SystemHarshalJain48
The document discusses various types of faults that can occur in power systems, including symmetrical and unsymmetrical faults. It describes different fault types like line-to-line, line-to-ground, and double line-to-ground faults. Protection devices for power systems are also covered, such as circuit breakers, relays including impedance, distance, and differential relays. Current transformers and potential transformers are explained for their use in protection schemes. Classification of faults by category and probability is presented. Common faults in generators like stator and rotor faults are summarized.
Directional and differential relays operate based on the direction and magnitude of current flow in a circuit. Directional relays only operate when power flows in a specific direction, typically away from a protected zone. Differential relays compare current magnitudes at both ends of a protected zone and operate when there is a difference, indicating an internal fault. Percentage or biased beam differential relays include a restraining coil to prevent operation under heavy load conditions by requiring a higher differential current threshold. Translay systems use voltage balance between relay windings rather than current transformer secondaries to protect long cable runs while avoiding accuracy issues of traditional voltage balance schemes.
Differential protection relays operate by comparing electrical quantities on both sides of a circuit. They provide precise unit protection for equipment. There are several types, including current, voltage, biased, and voltage balance differential relays. Current differential relays compare currents entering and leaving a system, while voltage balance relays use pilot wires and current transformers to compare voltages induced at both ends of a protected feeder. Differential relays have advantages like fast operation for very close internal faults and less incorrect operation during external faults.
The document provides an overview of substation protection basics. It discusses why protection is needed to detect faults and isolate faulty equipment. The main types of faults are described along with the causes of insulation failures. The types of protection principles covered include overcurrent, differential, pilot wire, and distance protection. Key elements of a protection scheme like circuit breakers, relays, batteries, and transformers are also mentioned.
How is power transformer protected??? This provides a basic understanding of power transformer. Furthermore, the protective relay application on power transformer is included.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
This document discusses generator protection techniques. It begins by explaining why protective systems are needed to protect expensive power system elements like generators. It then describes different types of generator faults and various protection schemes. These include stator protection using differential protection and its modifications. Rotor faults and their protections like rotor earth fault protection are also explained. The document provides details on other protections like overcurrent, overvoltage, vibration and overheating protections. It concludes by stating that protective devices help detect faults, notify maintenance, and disconnect faulty elements to ensure continuous and safe operation of power systems.
This document provides an overview of the EE2402 Protection & Switchgear course presented by C.Gokul. It includes the course syllabus, units covered, textbook references and introductory content on power system basics, components, faults, protection elements, relay terminology and essential qualities of protection systems. The key topics discussed are types of faults in power systems, importance of protective schemes, elements of a protection system including current transformers, voltage transformers, relays and circuit breakers. Neutral earthing methods with a focus on Peterson coil are also introduced.
The document discusses transformer protection. It describes different types of faults that can occur in transformers, both internal and external. It then discusses various protection methods for transformers, including differential protection, sudden pressure relays, overcurrent protection, and thermal protection. It also provides details on magnetizing inrush current and how it is influenced by factors like transformer size, system resistance, and residual flux levels.
Why do Transformers Fail?
�The electrical windings and the magnetic core in a transformer are subject to a number of different forces during operation, for example:
�Expansion and contraction due to thermal cycling
�Vibration
�Local heating due to magnetic flux
�Impact forces due to through-fault current
�Excessive heating due to overloading or inadequate cooling
POWER SYSTEM PROTECTION
Protection Devices and the Lightning,. protection,
Lightning protection, Introduction
Air Break Switches
Disconnect switches
Grounding switches
Current limiting reactors
Grounding transformers
Co-ordination of protective devices
Grounding of electrical installations
Electric shock
Lightning protection
Lightning Arrestor
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
Vacuum circuit breakers use vacuum to extinguish the arc when opening contacts. They have fixed contacts, moving contacts, and an arc shield mounted inside a vacuum chamber. When a fault is detected, the contacts separate and the arc is quickly extinguished in the vacuum. This allows vacuum circuit breakers to reliably interrupt high fault currents. They have advantages over other circuit breakers like being compact, reliable, and able to interrupt heavy fault currents without fire hazards.
Protection of transmission lines(encrypted)Rohini Haridas
This document discusses protection methods for transmission lines. It describes:
1. Transmission lines require more protective schemes than other equipment due to their long lengths and exposure, making faults more common.
2. Key methods of transmission line protection include time-graded overcurrent protection, differential protection, current-graded overcurrent protection, and distance protection.
3. Distance protection uses impedance relays that can discriminate between faults along the line and those near the end, providing more selective operation than overcurrent protection alone. It describes implementations using simple impedance, reactance, and mho relays.
The document outlines various components of a power system protection system. It discusses the need for protection to maintain reliable power supply and minimize equipment damage. The key elements to be protected include generators, transformers, transmission lines, and busbars. Protection schemes for each element are then described, such as differential protection for generators and transformers, Buchholz relays for transformers, and distance and line differential protection for transmission lines.
The document discusses substations and their components. It defines a substation as an assembly of apparatus that transforms electrical energy from one form to another, such as changing voltage levels. Substations contain step-up transformers to increase voltage for transmission and step-down transformers to decrease voltage for distribution to consumers. The document describes various types of substations and explains their functions. It also provides details about components within substations such as circuit breakers, transformers, buses, isolators and instrument transformers.
This document discusses basic protection and relaying schemes used in power systems. It begins by explaining why protection systems are needed to handle severe disturbances that could jeopardize the power system. The key elements of a protection system are then introduced, including protective relays, circuit breakers, and current/voltage transducers. Common protection schemes like overcurrent, directional overcurrent, distance, and differential protection are described at a high level. The advantages of digital relays over electromechanical relays are also briefly mentioned. Overall, the document provides a high-level overview of protection systems and some of the basic schemes used to protect different components in a power grid.
Voltages and currents present at the generator's rated voltage and current are provided as examples. Sample relay setting calculations are shown for generator protection elements including 59N neutral overvoltage, 27TN third harmonic undervoltage, 46 negative sequence overcurrent, and coordination between protective devices. Formulas for calculating voltage and current settings from generator nameplate data are demonstrated.
A fault in a power system is any abnormal condition involving electrical failure of equipment like transformers or generators. There are two main types of faults: open circuit faults caused by a failure of conductors, and short circuit faults resulting from insulation or conducting path failures. Unsymmetrical faults like single-line-to-ground are the most common, accounting for 70-80% of faults, while symmetrical three-phase faults are rare but severe. Faults can be caused by weather, equipment failures, human errors, or fires and can damage equipment if not cleared quickly.
The document discusses various types of underground transmission line faults including short circuits caused by insulation failures, open circuits from broken wires or blown fuses, symmetrical faults affecting all phases equally, and unsymmetrical faults including line to ground, line to line, and double line to ground faults. It also mentions over voltage from poor power regulation, under voltage from increased loads or transformer issues, and over current faults from short circuits. Insulation heating problems from air infiltration or moisture are discussed. The document provides a circuit diagram for testing faults and lists components used. Causes of faults include broken conductors and safety issues are among the effects.
1. The document discusses protective schemes for electrical power systems. It describes how protective relays and circuit breakers are used to isolate faulty elements of a power system to prevent damage and failure.
2. Faults can occur due to insulation failures or conductor failures and cause issues like equipment damage, fire hazards, voltage reductions, and loss of stability if not cleared quickly.
3. Protective relays monitor current, voltage, phase angle and frequency to detect faults. When a fault is detected, the relays signal circuit breakers to isolate the faulty section within seconds to prevent cascading issues.
This document discusses power system faults and protection. It defines faults as defects in electrical circuits that divert current from its intended path. The most common faults are short circuits caused by insulation or conducting path failures. Switchgear such as circuit breakers, fuses and relays are used to isolate faulty elements and ensure continuity of power supply. Protective relays detect faults using changes in current, voltage, phase angle or frequency and must clear faults within fractions of a second to prevent equipment damage. Common faults include short circuits, over/under voltage/frequency, and overheating.
An electrical substation uses components like circuit breakers, busbars, and insulators to control the transmission, transformation, and distribution of power. There are two main types of substation insulation systems: air insulated (AIS) and gas insulated (GIS). AIS uses air as insulation between live components, while GIS uses sulfur hexafluoride gas to insulate live components within a sealed metal enclosure. GIS systems require less space than AIS but have higher installation costs. Protective devices in substations include circuit breakers, disconnectors, earthing switches, and surge arresters, which work to isolate faulty sections of the electrical network to prevent damage.
International Journal of Engineering Research and DevelopmentIJERD Editor
Electrical, Electronics and Computer Engineering,
Information Engineering and Technology,
Mechanical, Industrial and Manufacturing Engineering,
Automation and Mechatronics Engineering,
Material and Chemical Engineering,
Civil and Architecture Engineering,
Biotechnology and Bio Engineering,
Environmental Engineering,
Petroleum and Mining Engineering,
Marine and Agriculture engineering,
Aerospace Engineering.
The document discusses faults that occur in power systems. It defines electrical faults as abnormal conditions caused by equipment failures, human errors, or environmental conditions. There are two main types of faults: symmetrical faults, which are rare but severe, and unsymmetrical faults, which are more common and less severe. Unsymmetrical faults include line to ground, double line to ground, and line to line faults. Faults can be caused by weather, equipment failures, human errors, or fires and can result in overcurrent, danger to personnel, loss of equipment, and electrical fires. Proper protection devices are needed to detect and isolate faults to maintain reliability and prevent damage.
Electrical fault is the deviation of voltages and currents from nominal values or states. Under normal operating conditions, power system equipment or lines carry normal voltages and currents which results in a safer operation of the system.
The document discusses short circuits (faults) in electrical systems. It defines a short circuit as a low resistance path allowing current to flow along an unintended path. Short circuits can damage equipment and endanger safety if fault currents exceed ratings. The document then provides details on types of short circuits including shunt faults like line-to-ground and line-to-line, and series faults like open circuits. Short circuit studies are important to ensure protection devices and equipment can withstand fault currents.
Short circuit analysis is performed so that existing and new equipment ratings were sufficient to with stand the available short circuit current. short circuit studies are performed using power system software as per IEEE standards.
Over voltages can be caused by internal factors like switching operations or insulation failures, or external factors like lightning. Lightning arrestors protect equipment by diverting high voltage surges to ground. They break down temporarily during over voltages and regain insulation at normal voltages. Insulation coordination determines equipment insulation strength to withstand normal operating voltages and temporary over voltages based on factors like highest system frequency, temporary over voltages, and transient surges. Equipment is tested and rated with a basic insulation level to ensure it can withstand impulse voltages above that level.
This document provides summaries of common electrical components and concepts. It defines a fuse, circuit breaker, relay, and contactor. It also describes suppression diodes, wiring standards including American wire gauge and three-phase power, current transformers, phase monitoring relays, ground fault interrupters, emergency off switches, cable basics, heat shrink tubing, busbars, and the Restriction of Hazardous Substances Directive.
This document discusses various methods of neutral grounding systems for electrical power systems, including their advantages and disadvantages. It describes ungrounded systems, solidly grounded systems, and various resistance grounded systems such as low resistance, high resistance, and resonant grounding. Resistance grounding limits fault currents to reduce equipment damage while still allowing faults to be detected. High resistance grounding further limits currents to below 10 amps, requiring a detection system since faults will not trip breakers. Resonant grounding uses inductive reactance to cancel out the capacitive fault current. Earthing transformers provide an alternative return path for faults on delta windings.
Power System Transient - Introduction.pptxssuser6453eb
This document provides an introduction to power system transients. It discusses the sources of transients, both internal like capacitor switching and external like lightning. It classifies transients into three categories based on speed: ultrafast surges, medium-fast short-circuit phenomena, and slow transient stability issues. The effects of transients are outlined, such as damage to insulation, semiconductors, and contacts. The importance of studying transients for insulation design is emphasized to prevent breakdown under overvoltage conditions.
Multi – Grounding in the Distribution System.pptxMarlonAgustin3
The document discusses grounding and fault clearing in distribution systems. It defines grounding as connecting electrical systems and equipment to earth. Distribution system grounding is important for fault detection and clearing to limit outages. Systems use multiple grounding points along the neutral to keep voltage rises low during faults. Faults can be phase-to-ground or phase-to-phase and are cleared using fuses, reclosers, and substation circuit breakers in a coordinated manner to isolate damage while attempting to save downstream protective devices.
Module 1 Power System Protection(18EE72).pptxssuser139a56
This document provides an overview of a course on power system protection. It introduces topics that will be covered, including introduction to power systems, causes and effects of faults, protection schemes, and types of relays. The course textbook is also listed. The document provides definitions of key terms and concepts in power system protection.
Transients can cause slow degradation, erratic operation, or catastrophic failure in electrical parts, insulation dielectrics, and electrical contacts used in switches and relays. The possible occurrence of transients must be considered in the overall electronic design. Required circuit performance and reliability must be assured both during and after the transient
Transient voltages, also called surges or spikes, are momentary changes in voltage or current that occur over a short period of time, usually less than 1/60th of a second. They are generated by both external sources like lightning and utility switching and internal sources like motor starts and static discharge. Transients can travel through a facility's electrical system and affect electronic equipment, causing erratic operation, lock ups, premature failure or decreased efficiency. Effective transient voltage suppression equipment can significantly increase the life of electrical and electronic systems and provide a strong return on investment.
Similar to Lecture-PS-faults-description-recorded-30032020-110109pm.pptx (20)
Understanding Inductive Bias in Machine LearningSUTEJAS
This presentation explores the concept of inductive bias in machine learning. It explains how algorithms come with built-in assumptions and preferences that guide the learning process. You'll learn about the different types of inductive bias and how they can impact the performance and generalizability of machine learning models.
The presentation also covers the positive and negative aspects of inductive bias, along with strategies for mitigating potential drawbacks. We'll explore examples of how bias manifests in algorithms like neural networks and decision trees.
By understanding inductive bias, you can gain valuable insights into how machine learning models work and make informed decisions when building and deploying them.
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsVictor Morales
K8sGPT is a tool that analyzes and diagnoses Kubernetes clusters. This presentation was used to share the requirements and dependencies to deploy K8sGPT in a local environment.
Batteries -Introduction – Types of Batteries – discharging and charging of battery - characteristics of battery –battery rating- various tests on battery- – Primary battery: silver button cell- Secondary battery :Ni-Cd battery-modern battery: lithium ion battery-maintenance of batteries-choices of batteries for electric vehicle applications.
Fuel Cells: Introduction- importance and classification of fuel cells - description, principle, components, applications of fuel cells: H2-O2 fuel cell, alkaline fuel cell, molten carbonate fuel cell and direct methanol fuel cells.
International Conference on NLP, Artificial Intelligence, Machine Learning an...gerogepatton
International Conference on NLP, Artificial Intelligence, Machine Learning and Applications (NLAIM 2024) offers a premier global platform for exchanging insights and findings in the theory, methodology, and applications of NLP, Artificial Intelligence, Machine Learning, and their applications. The conference seeks substantial contributions across all key domains of NLP, Artificial Intelligence, Machine Learning, and their practical applications, aiming to foster both theoretical advancements and real-world implementations. With a focus on facilitating collaboration between researchers and practitioners from academia and industry, the conference serves as a nexus for sharing the latest developments in the field.
Comparative analysis between traditional aquaponics and reconstructed aquapon...bijceesjournal
The aquaponic system of planting is a method that does not require soil usage. It is a method that only needs water, fish, lava rocks (a substitute for soil), and plants. Aquaponic systems are sustainable and environmentally friendly. Its use not only helps to plant in small spaces but also helps reduce artificial chemical use and minimizes excess water use, as aquaponics consumes 90% less water than soil-based gardening. The study applied a descriptive and experimental design to assess and compare conventional and reconstructed aquaponic methods for reproducing tomatoes. The researchers created an observation checklist to determine the significant factors of the study. The study aims to determine the significant difference between traditional aquaponics and reconstructed aquaponics systems propagating tomatoes in terms of height, weight, girth, and number of fruits. The reconstructed aquaponics system’s higher growth yield results in a much more nourished crop than the traditional aquaponics system. It is superior in its number of fruits, height, weight, and girth measurement. Moreover, the reconstructed aquaponics system is proven to eliminate all the hindrances present in the traditional aquaponics system, which are overcrowding of fish, algae growth, pest problems, contaminated water, and dead fish.
Literature Review Basics and Understanding Reference Management.pptxDr Ramhari Poudyal
Three-day training on academic research focuses on analytical tools at United Technical College, supported by the University Grant Commission, Nepal. 24-26 May 2024
Using recycled concrete aggregates (RCA) for pavements is crucial to achieving sustainability. Implementing RCA for new pavement can minimize carbon footprint, conserve natural resources, reduce harmful emissions, and lower life cycle costs. Compared to natural aggregate (NA), RCA pavement has fewer comprehensive studies and sustainability assessments.
Embedded machine learning-based road conditions and driving behavior monitoringIJECEIAES
Car accident rates have increased in recent years, resulting in losses in human lives, properties, and other financial costs. An embedded machine learning-based system is developed to address this critical issue. The system can monitor road conditions, detect driving patterns, and identify aggressive driving behaviors. The system is based on neural networks trained on a comprehensive dataset of driving events, driving styles, and road conditions. The system effectively detects potential risks and helps mitigate the frequency and impact of accidents. The primary goal is to ensure the safety of drivers and vehicles. Collecting data involved gathering information on three key road events: normal street and normal drive, speed bumps, circular yellow speed bumps, and three aggressive driving actions: sudden start, sudden stop, and sudden entry. The gathered data is processed and analyzed using a machine learning system designed for limited power and memory devices. The developed system resulted in 91.9% accuracy, 93.6% precision, and 92% recall. The achieved inference time on an Arduino Nano 33 BLE Sense with a 32-bit CPU running at 64 MHz is 34 ms and requires 2.6 kB peak RAM and 139.9 kB program flash memory, making it suitable for resource-constrained embedded systems.
Introduction- e - waste – definition - sources of e-waste– hazardous substances in e-waste - effects of e-waste on environment and human health- need for e-waste management– e-waste handling rules - waste minimization techniques for managing e-waste – recycling of e-waste - disposal treatment methods of e- waste – mechanism of extraction of precious metal from leaching solution-global Scenario of E-waste – E-waste in India- case studies.
2. Faults in Power Systems
Types of Faults
Open Circuit Faults
Causes
Effects
Short Circuit Faults
Causes
Effects
3. Introduction to Electrical Faults
Electrical networks, machines and equipment are
often subjected to various types of faults while they
are in operation. When a fault occurs, the
characteristic values (such as impedance) of the
machines may change from existing values to different
values till the fault is cleared.
There may be lot of probabilities of faults to appear in
the power system network, including lighting, wind,
tree falling on lines, apparatus failure, etc.
4. Introduction to Electrical Faults
A fault in an electric power system can be defined as ,
any abnormal condition of the system that involves the
electrical failure of the equipment, such as,
transformers, generators, busbars, etc.
The fault inception also involves in insulation failures
and conducting path failures which results short circuit
and open circuit of conductors
5. Introduction to Electrical Faults
Under normal or safe operating conditions, the electric
equipment in a power system network operate at
normal voltage and current ratings. Once the fault
takes place in a circuit or device, voltage and current
values deviates from their nominal ranges.
The faults in power system causes over current, under
voltage, unbalance of the phases, reversed power and
high voltage surges. This results in the interruption of
the normal operation of the network, failure of
equipments, electrical fires, etc.
6. Introduction to Electrical Faults
Usually power system networks are protected with
switchgear protection equipment such as circuit
breakers and relays in order to limit the loss of
service due to the electrical failures.
7. Types of Faults
Electrical faults in three-phase power system mainly
classified into two types, namely open and short
circuit faults. Further, these faults can be symmetrical
or unsymmetrical faults.
Open Circuit Faults (Series Faults)
These faults occur due to the failure of one or more
conductors. It can be the open circuit faults for single,
two and three phases (or conductors) open condition.
8. Open Circuit Faults (Series Faults)
The most common causes of these faults include joint
failures of cables and overhead lines, and failure of
one or more phase of circuit breaker and also due to
melting of a fuse or conductor in one or more phases.
Open circuit faults are also called as series faults.
These are unsymmetrical or unbalanced type of faults
except three phase open fault.
10. Open Circuit Faults (Series Faults)
Consider that a transmission line is working with a
balanced load before the occurrence of open circuit fault.
If one of the phase gets melted, the actual loading of the
alternator is reduced and this cause to raise the
acceleration of the alternator, thereby it runs at a speed
slightly greater than synchronous speed. This over speed
causes over voltages in other transmission lines.
Thus, single and two phase open conditions can produce
the unbalance of the power system voltages and currents
that causes great damage to the equipment.
11. Open Circuit Faults (Series Faults)
Causes
Broken conductor and malfunctioning of circuit breaker in one or more
phases.
Effects
Abnormal operation of the system
Danger to the personnel as well as animals
Exceeding the voltages beyond normal values in certain parts of the
network, which further leads to insulation failures and developing of short
circuit faults.
Although open circuit faults can be tolerated for longer periods than short
circuit faults, these must be removed as early as possible to reduce the
greater damage.
12. Short Circuit Faults (Shunt Faults)
A short circuit can be defined as an abnormal connection of
very low impedance between two points of different potential,
whether made intentionally or accidentally.
These are the most common and severe kind of faults, resulting
in the flow of abnormal high currents through the equipment or
transmission lines. If these faults are allowed to persist even for
a short period, it leads to the extensive damage to the
equipment.
Short circuit faults are also called as shunt faults. These faults
are caused due to the insulation failure between phase
conductors or between earth and phase conductors or both.
13. Short Circuit Faults (Shunt Faults)
The various possible short circuit fault conditions include
three phase to earth, three phase clear of earth, phase to
phase, single phase to earth, two phase to earth and
phase to phase plus single phase to earth as shown in
figure.
The three phase fault clear of earth and three phase fault
to earth are balanced or symmetrical short circuit faults
while other remaining faults are unsymmetrical faults.
16. Short Circuit Faults (Shunt Faults)
Causes
These may be due to internal or external effects:
Internal effects include breakdown of transmission lines or
equipment, aging of insulation, deterioration of insulation
in generator, transformer and other electrical equipment,
improper installations and inadequate design.
External effects include overloading of equipment,
insulation failure due to lighting surges and mechanical
damage by public.
17. Short Circuit Faults (Shunt Faults)
Effects:
Arcing faults can lead to fire and explosion in equipment
such as transformers and circuit breakers.
Abnormal currents cause the equipment to get
overheated, which further leads to reduction of life span of
their insulation.
The operating voltages of the system can go below or
above their acceptance values that creates harmful effect
to the service rendered by the power system.
The power flow is severely restricted or even completely
blocked as long as the short circuit fault persists.
18. Symmetrical and Unsymmetrical Faults
Symmetrical and Unsymmetrical Faults
As discussed above that faults are mainly classified into open and
short circuit faults and again these can be symmetrical or
unsymmetrical faults.
Symmetrical Faults
A symmetrical fault gives rise to symmetrical fault currents that
are displaced with 120^0 each other. Symmetrical fault is also
called as balanced fault. This fault occurs when all the three
phases are simultaneously short circuited.
These faults rarely occur in practice as compared with
unsymmetrical faults.
20. Symmetrical Faults
A rough occurrence of symmetrical faults is in the
range of 2 to 5% of the total system faults. However, if
these faults occur, they cause a very severe damage
to the equipment even though the system remains in
balanced condition.
The analysis of these faults is required for selecting
the rupturing capacity of the circuit breakers, choosing
set-phase relays and other protective switchgear.
These faults are analyzed on per phase basis using
bus impedance matrix or Thevenins’s theorem.
21. Unsymmetrical Faults
The most common faults that occur in the power system network are
unsymmetrical faults. This kind of fault gives rise to unsymmetrical
fault currents (having different magnitudes with unequal phase
displacement). These faults are also called as unbalanced faults as it
causes unbalanced currents in the system.
Unsymmetrical faults include both open circuit faults (single and two
phase open condition) and short circuit faults (excluding L-L-L-G and
L-L-L).
A single line-to-ground (LG) fault is one of the most common faults
and experiences show that 70-80 percent of the faults that occur in
power system are of this type. This forms a short circuit path between
the line and ground.
22. Unsymmetrical Faults
A line to line fault occurs when a live conductor get in contact with other
live conductor. Heavy winds are the major cause for this fault during
which swinging of overhead conductors may touch together. These are
less severe faults and its occurrence range may be between 15-20%.
In double line to ground faults, two lines come into the contact with
each other as well as with ground. These are severe faults and the
occurrence these faults is about 10% when compared with total system
faults.
Unsymmetrical faults are analyzed using methods of unsymmetrical
components in order to determine the voltage and currents in all parts
of the system. The analysis of these faults is more difficult compared to
symmetrical faults.
This analysis is necessary for determining the size of a circuit breaker
for largest short circuit current. The greater current usually occurs for
either L-G or L-L fault.
23. Protection Devices
When the fault occurs in any part of the system, it must
be cleared in a very short period in order to avoid
greater damage to equipment and personnel and also
to avoid interruption of power to the customers.
The fault clearing system uses various protection
devices such as relays and circuit breakers to detect
and clear the fault.
24. Protection Devices
Fuse
It opens the circuit whenever a fault exists in the system. It consists of a
thin copper wire enclosed in a glass or a casing with two metallic
contacts. The high fault current rises the temperature of the wire and
hence it melts. A fuse necessitates the manual replacement of wire each
time when it blows.
Circuit Breaker
It is the most common protection device that can make or break the
circuit either manually or through remote control under normal operating
conditions.
There are several types of circuit breakers available depending on the
operating voltage, including air brake, oil, vacuum and SF6 circuit
breakers.
25. Protection Devices
Protective Relays
These are the fault detecting devices. These devices detect the
fault and initiate the operation of the circuit breaker so as to isolate
the faulty circuit. A relay consists of a magnetic coil and contacts.
The fault current energizes the coil and this causes to produce the
field, thereby the contacts get operated.
Some of the types of protective relays include:
Magnitude relays
Impedance relays
Directional relays
Pilot relays
Differential relays
26. Protection Devices
Lighting Arrestor
Surges in the power system network caused when
lightning strikes on transmission lines and equipment.
This causes high voltage and currents in the system.
These lighting faults are reduced by placing lighting
arrestors at transmission equipment.
27. Cause of Short Circuit Insulation Failure
• Over-voltages caused by Lightning or Switching
Surges
• Insulation contamination salt spray, pollution
• Mechanical Causes Over-heating, abrasion
Short Circuit Analysis
28. Faults on Transmission Lines
Most common Lines are exposed to elements of nature
(60-70%).
Lightning strokes Over voltages cause insulators to
flash over line to ground short circuit or line to line
short circuit.
High winds Topple tower, tree falls on line.
Winds and ice loading Mechanical failure of insulator
29. Short circuit in other elements
Fog, salt spray, dirty insulator Conduction path
insulation failure
Cables (10-15%), circuit breakers (10-12%),
generators, motors, transformers etc (10-15%),
Much less common Over loading for
extended periods deterioration of insulation
Mechanical failure.
30. Consequences of Short Circuit
Currents several magnitude larger than normal
operating current.
Thermal damage to equipment.
Windings and bus-bars Mechanical damage due
to
high magnetic forces caused by high current.
Faulted section must be removed from service as soon
as possible (3-5 cycles).
31. L-G L-L L-L-G 3ϕ-G
75-80% 5-7% 10-12% 8-10%
Asymmetrical Faults
Symmetrical Faults
a
b
c
Types of Short Circuit
32. The selection of circuit breakers
From the viewpoint of current the two factors that need
to be considered in selecting circuit breakers are:
The maximum instantaneous current which the
breaker must carry (withstand) and
The total current when the breaker contacts open to
interrupt the circuit.