SlideShare a Scribd company logo
Faults in Power System
Faults in Power Systems
 Types of Faults
 Open Circuit Faults
 Causes
 Effects
 Short Circuit Faults
 Causes
 Effects
Introduction to Electrical Faults
 Electrical networks, machines and equipment are
often subjected to various types of faults while they
are in operation. When a fault occurs, the
characteristic values (such as impedance) of the
machines may change from existing values to different
values till the fault is cleared.
 There may be lot of probabilities of faults to appear in
the power system network, including lighting, wind,
tree falling on lines, apparatus failure, etc.
Introduction to Electrical Faults
 A fault in an electric power system can be defined as ,
any abnormal condition of the system that involves the
electrical failure of the equipment, such as,
transformers, generators, busbars, etc.
 The fault inception also involves in insulation failures
and conducting path failures which results short circuit
and open circuit of conductors
Introduction to Electrical Faults
 Under normal or safe operating conditions, the electric
equipment in a power system network operate at
normal voltage and current ratings. Once the fault
takes place in a circuit or device, voltage and current
values deviates from their nominal ranges.
 The faults in power system causes over current, under
voltage, unbalance of the phases, reversed power and
high voltage surges. This results in the interruption of
the normal operation of the network, failure of
equipments, electrical fires, etc.
Introduction to Electrical Faults
 Usually power system networks are protected with
switchgear protection equipment such as circuit
breakers and relays in order to limit the loss of
service due to the electrical failures.
Types of Faults
 Electrical faults in three-phase power system mainly
classified into two types, namely open and short
circuit faults. Further, these faults can be symmetrical
or unsymmetrical faults.
Open Circuit Faults (Series Faults)
 These faults occur due to the failure of one or more
conductors. It can be the open circuit faults for single,
two and three phases (or conductors) open condition.
Open Circuit Faults (Series Faults)
 The most common causes of these faults include joint
failures of cables and overhead lines, and failure of
one or more phase of circuit breaker and also due to
melting of a fuse or conductor in one or more phases.
 Open circuit faults are also called as series faults.
These are unsymmetrical or unbalanced type of faults
except three phase open fault.
Open Circuit Faults (Series Faults)
Open Circuit Faults (Series Faults)
 Consider that a transmission line is working with a
balanced load before the occurrence of open circuit fault.
If one of the phase gets melted, the actual loading of the
alternator is reduced and this cause to raise the
acceleration of the alternator, thereby it runs at a speed
slightly greater than synchronous speed. This over speed
causes over voltages in other transmission lines.
 Thus, single and two phase open conditions can produce
the unbalance of the power system voltages and currents
that causes great damage to the equipment.
Open Circuit Faults (Series Faults)
Causes
Broken conductor and malfunctioning of circuit breaker in one or more
phases.
Effects
 Abnormal operation of the system
 Danger to the personnel as well as animals
 Exceeding the voltages beyond normal values in certain parts of the
network, which further leads to insulation failures and developing of short
circuit faults.
Although open circuit faults can be tolerated for longer periods than short
circuit faults, these must be removed as early as possible to reduce the
greater damage.
Short Circuit Faults (Shunt Faults)
 A short circuit can be defined as an abnormal connection of
very low impedance between two points of different potential,
whether made intentionally or accidentally.
 These are the most common and severe kind of faults, resulting
in the flow of abnormal high currents through the equipment or
transmission lines. If these faults are allowed to persist even for
a short period, it leads to the extensive damage to the
equipment.
 Short circuit faults are also called as shunt faults. These faults
are caused due to the insulation failure between phase
conductors or between earth and phase conductors or both.
Short Circuit Faults (Shunt Faults)
 The various possible short circuit fault conditions include
three phase to earth, three phase clear of earth, phase to
phase, single phase to earth, two phase to earth and
phase to phase plus single phase to earth as shown in
figure.
 The three phase fault clear of earth and three phase fault
to earth are balanced or symmetrical short circuit faults
while other remaining faults are unsymmetrical faults.
Short Circuit Faults (Shunt Faults)
Short Circuit Faults (Shunt Faults)
Short Circuit Faults (Shunt Faults)
Causes
These may be due to internal or external effects:
 Internal effects include breakdown of transmission lines or
equipment, aging of insulation, deterioration of insulation
in generator, transformer and other electrical equipment,
improper installations and inadequate design.
 External effects include overloading of equipment,
insulation failure due to lighting surges and mechanical
damage by public.
Short Circuit Faults (Shunt Faults)
Effects:
 Arcing faults can lead to fire and explosion in equipment
such as transformers and circuit breakers.
 Abnormal currents cause the equipment to get
overheated, which further leads to reduction of life span of
their insulation.
 The operating voltages of the system can go below or
above their acceptance values that creates harmful effect
to the service rendered by the power system.
 The power flow is severely restricted or even completely
blocked as long as the short circuit fault persists.
Symmetrical and Unsymmetrical Faults
Symmetrical and Unsymmetrical Faults
As discussed above that faults are mainly classified into open and
short circuit faults and again these can be symmetrical or
unsymmetrical faults.
Symmetrical Faults
A symmetrical fault gives rise to symmetrical fault currents that
are displaced with 120^0 each other. Symmetrical fault is also
called as balanced fault. This fault occurs when all the three
phases are simultaneously short circuited.
These faults rarely occur in practice as compared with
unsymmetrical faults.
Symmetrical Faults
Symmetrical Faults
 A rough occurrence of symmetrical faults is in the
range of 2 to 5% of the total system faults. However, if
these faults occur, they cause a very severe damage
to the equipment even though the system remains in
balanced condition.
 The analysis of these faults is required for selecting
the rupturing capacity of the circuit breakers, choosing
set-phase relays and other protective switchgear.
These faults are analyzed on per phase basis using
bus impedance matrix or Thevenins’s theorem.
Unsymmetrical Faults
 The most common faults that occur in the power system network are
unsymmetrical faults. This kind of fault gives rise to unsymmetrical
fault currents (having different magnitudes with unequal phase
displacement). These faults are also called as unbalanced faults as it
causes unbalanced currents in the system.
 Unsymmetrical faults include both open circuit faults (single and two
phase open condition) and short circuit faults (excluding L-L-L-G and
L-L-L).
 A single line-to-ground (LG) fault is one of the most common faults
and experiences show that 70-80 percent of the faults that occur in
power system are of this type. This forms a short circuit path between
the line and ground.
Unsymmetrical Faults
 A line to line fault occurs when a live conductor get in contact with other
live conductor. Heavy winds are the major cause for this fault during
which swinging of overhead conductors may touch together. These are
less severe faults and its occurrence range may be between 15-20%.
 In double line to ground faults, two lines come into the contact with
each other as well as with ground. These are severe faults and the
occurrence these faults is about 10% when compared with total system
faults.
 Unsymmetrical faults are analyzed using methods of unsymmetrical
components in order to determine the voltage and currents in all parts
of the system. The analysis of these faults is more difficult compared to
symmetrical faults.
 This analysis is necessary for determining the size of a circuit breaker
for largest short circuit current. The greater current usually occurs for
either L-G or L-L fault.
Protection Devices
When the fault occurs in any part of the system, it must
be cleared in a very short period in order to avoid
greater damage to equipment and personnel and also
to avoid interruption of power to the customers.
The fault clearing system uses various protection
devices such as relays and circuit breakers to detect
and clear the fault.
Protection Devices
Fuse
It opens the circuit whenever a fault exists in the system. It consists of a
thin copper wire enclosed in a glass or a casing with two metallic
contacts. The high fault current rises the temperature of the wire and
hence it melts. A fuse necessitates the manual replacement of wire each
time when it blows.
Circuit Breaker
It is the most common protection device that can make or break the
circuit either manually or through remote control under normal operating
conditions.
There are several types of circuit breakers available depending on the
operating voltage, including air brake, oil, vacuum and SF6 circuit
breakers.
Protection Devices
Protective Relays
These are the fault detecting devices. These devices detect the
fault and initiate the operation of the circuit breaker so as to isolate
the faulty circuit. A relay consists of a magnetic coil and contacts.
The fault current energizes the coil and this causes to produce the
field, thereby the contacts get operated.
Some of the types of protective relays include:
 Magnitude relays
 Impedance relays
 Directional relays
 Pilot relays
 Differential relays
Protection Devices
Lighting Arrestor
Surges in the power system network caused when
lightning strikes on transmission lines and equipment.
This causes high voltage and currents in the system.
These lighting faults are reduced by placing lighting
arrestors at transmission equipment.
Cause of Short Circuit Insulation Failure
• Over-voltages caused by Lightning or Switching
Surges
• Insulation contamination salt spray, pollution
• Mechanical Causes Over-heating, abrasion
Short Circuit Analysis
Faults on Transmission Lines
Most common Lines are exposed to elements of nature
(60-70%).
Lightning strokes Over voltages cause insulators to
flash over line to ground short circuit or line to line
short circuit.
High winds Topple tower, tree falls on line.
Winds and ice loading Mechanical failure of insulator
Short circuit in other elements
Fog, salt spray, dirty insulator Conduction path
insulation failure
Cables (10-15%), circuit breakers (10-12%),
generators, motors, transformers etc (10-15%),
Much less common Over loading for
extended periods deterioration of insulation
Mechanical failure.
Consequences of Short Circuit
Currents several magnitude larger than normal
operating current.
Thermal damage to equipment.
Windings and bus-bars Mechanical damage due
to
high magnetic forces caused by high current.
Faulted section must be removed from service as soon
as possible (3-5 cycles).
L-G L-L L-L-G 3ϕ-G
75-80% 5-7% 10-12% 8-10%
Asymmetrical Faults
Symmetrical Faults
a
b
c
Types of Short Circuit
The selection of circuit breakers
From the viewpoint of current the two factors that need
to be considered in selecting circuit breakers are:
 The maximum instantaneous current which the
breaker must carry (withstand) and
 The total current when the breaker contacts open to
interrupt the circuit.

More Related Content

What's hot

Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
Kabilesh K
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection System
HarshalJain48
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
UtthejNani1
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
kishore kish
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
Salim Palayi
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
Ang Sovann
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
SARAVANAN A
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
Rahuldey1991
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
Power System Operation
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
Ameen San
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
srini09
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
Harshit Srivastava
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
Rohini Haridas
 
Power system protection
Power system protectionPower system protection
Power system protection
Akbar HilalAbadi
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
Himansu Pradhan
 
CURRENT LIMITING REACTORS
CURRENT  LIMITING  REACTORSCURRENT  LIMITING  REACTORS
CURRENT LIMITING REACTORS
BhashiniPriyadas
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
Biswajit Pratihari
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
michaeljmack
 

What's hot (20)

Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection System
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)Protection of transmission lines(encrypted)
Protection of transmission lines(encrypted)
 
Power system protection
Power system protectionPower system protection
Power system protection
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
CURRENT LIMITING REACTORS
CURRENT  LIMITING  REACTORSCURRENT  LIMITING  REACTORS
CURRENT LIMITING REACTORS
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 

Similar to Lecture-PS-faults-description-recorded-30032020-110109pm.pptx

Kinds of Faults in the power system.pptx
Kinds of Faults in the power system.pptxKinds of Faults in the power system.pptx
Kinds of Faults in the power system.pptx
MarlonAgustin3
 
Electrical transmission line fault.pdf
Electrical transmission line fault.pdfElectrical transmission line fault.pdf
Electrical transmission line fault.pdf
aliahmad216280
 
Project
ProjectProject
Project
mkanth
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protection
SaifUrrehman183
 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)
siddharth sharma
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
IJERD Editor
 
unit1-200424112829 (1).pdf
unit1-200424112829 (1).pdfunit1-200424112829 (1).pdf
unit1-200424112829 (1).pdf
rupasharma39
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
Vinod Srivastava
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
JatmylHarnero1
 
Short circuit analysis
Short circuit analysisShort circuit analysis
Short circuit analysis
VB Engineering
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 Webinar
Transcat
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
Jaydeep Chauhan
 
Electrical basics
Electrical basicsElectrical basics
Electrical basics
Ganesh Kumar
 
s.pdf
s.pdfs.pdf
s.pdf
epaysokhan
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
Power System Operation
 
Power System Transient - Introduction.pptx
Power System Transient - Introduction.pptxPower System Transient - Introduction.pptx
Power System Transient - Introduction.pptx
ssuser6453eb
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptx
MarlonAgustin3
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
ssuser139a56
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
Hilaire (Ananda) Perera P.Eng.
 
electrical transients in power system
electrical transients in power systemelectrical transients in power system
electrical transients in power system
Vinayaka Shetty
 

Similar to Lecture-PS-faults-description-recorded-30032020-110109pm.pptx (20)

Kinds of Faults in the power system.pptx
Kinds of Faults in the power system.pptxKinds of Faults in the power system.pptx
Kinds of Faults in the power system.pptx
 
Electrical transmission line fault.pdf
Electrical transmission line fault.pdfElectrical transmission line fault.pdf
Electrical transmission line fault.pdf
 
Project
ProjectProject
Project
 
Introduction to power system protection
Introduction to power system protectionIntroduction to power system protection
Introduction to power system protection
 
GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)GIS substation Information (Detailed Report)
GIS substation Information (Detailed Report)
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
unit1-200424112829 (1).pdf
unit1-200424112829 (1).pdfunit1-200424112829 (1).pdf
unit1-200424112829 (1).pdf
 
Faults on Power System
Faults on Power SystemFaults on Power System
Faults on Power System
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Short circuit analysis
Short circuit analysisShort circuit analysis
Short circuit analysis
 
Transcat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 WebinarTranscat and Megger: Power Quality 101 Webinar
Transcat and Megger: Power Quality 101 Webinar
 
Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)Over voltage(Switch Gear and Protection)
Over voltage(Switch Gear and Protection)
 
Electrical basics
Electrical basicsElectrical basics
Electrical basics
 
s.pdf
s.pdfs.pdf
s.pdf
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Transient - Introduction.pptx
Power System Transient - Introduction.pptxPower System Transient - Introduction.pptx
Power System Transient - Introduction.pptx
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptx
 
Module 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptxModule 1 Power System Protection(18EE72).pptx
Module 1 Power System Protection(18EE72).pptx
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
electrical transients in power system
electrical transients in power systemelectrical transients in power system
electrical transients in power system
 

Recently uploaded

学校原版美国波士顿大学毕业证学历学位证书原版一模一样
学校原版美国波士顿大学毕业证学历学位证书原版一模一样学校原版美国波士顿大学毕业证学历学位证书原版一模一样
学校原版美国波士顿大学毕业证学历学位证书原版一模一样
171ticu
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
SUTEJAS
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
ihlasbinance2003
 
basic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdfbasic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdf
NidhalKahouli2
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
Hitesh Mohapatra
 
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsKuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
Victor Morales
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
JamalHussainArman
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
KrishnaveniKrishnara1
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
gerogepatton
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
bijceesjournal
 
Casting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdfCasting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdf
zubairahmad848137
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
Dr Ramhari Poudyal
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
MIGUELANGEL966976
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
Aditya Rajan Patra
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
IJECEIAES
 
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have oneISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
Las Vegas Warehouse
 
spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
Madan Karki
 
IEEE Aerospace and Electronic Systems Society as a Graduate Student Member
IEEE Aerospace and Electronic Systems Society as a Graduate Student MemberIEEE Aerospace and Electronic Systems Society as a Graduate Student Member
IEEE Aerospace and Electronic Systems Society as a Graduate Student Member
VICTOR MAESTRE RAMIREZ
 
Modelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdfModelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdf
camseq
 
22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt
KrishnaveniKrishnara1
 

Recently uploaded (20)

学校原版美国波士顿大学毕业证学历学位证书原版一模一样
学校原版美国波士顿大学毕业证学历学位证书原版一模一样学校原版美国波士顿大学毕业证学历学位证书原版一模一样
学校原版美国波士顿大学毕业证学历学位证书原版一模一样
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
 
basic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdfbasic-wireline-operations-course-mahmoud-f-radwan.pdf
basic-wireline-operations-course-mahmoud-f-radwan.pdf
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
 
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressionsKuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
KuberTENes Birthday Bash Guadalajara - K8sGPT first impressions
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
 
International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...International Conference on NLP, Artificial Intelligence, Machine Learning an...
International Conference on NLP, Artificial Intelligence, Machine Learning an...
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
 
Casting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdfCasting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdf
 
Literature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptxLiterature Review Basics and Understanding Reference Management.pptx
Literature Review Basics and Understanding Reference Management.pptx
 
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdfBPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
BPV-GUI-01-Guide-for-ASME-Review-Teams-(General)-10-10-2023.pdf
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
 
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have oneISPM 15 Heat Treated Wood Stamps and why your shipping must have one
ISPM 15 Heat Treated Wood Stamps and why your shipping must have one
 
spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
 
IEEE Aerospace and Electronic Systems Society as a Graduate Student Member
IEEE Aerospace and Electronic Systems Society as a Graduate Student MemberIEEE Aerospace and Electronic Systems Society as a Graduate Student Member
IEEE Aerospace and Electronic Systems Society as a Graduate Student Member
 
Modelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdfModelagem de um CSTR com reação endotermica.pdf
Modelagem de um CSTR com reação endotermica.pdf
 
22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt
 

Lecture-PS-faults-description-recorded-30032020-110109pm.pptx

  • 2. Faults in Power Systems  Types of Faults  Open Circuit Faults  Causes  Effects  Short Circuit Faults  Causes  Effects
  • 3. Introduction to Electrical Faults  Electrical networks, machines and equipment are often subjected to various types of faults while they are in operation. When a fault occurs, the characteristic values (such as impedance) of the machines may change from existing values to different values till the fault is cleared.  There may be lot of probabilities of faults to appear in the power system network, including lighting, wind, tree falling on lines, apparatus failure, etc.
  • 4. Introduction to Electrical Faults  A fault in an electric power system can be defined as , any abnormal condition of the system that involves the electrical failure of the equipment, such as, transformers, generators, busbars, etc.  The fault inception also involves in insulation failures and conducting path failures which results short circuit and open circuit of conductors
  • 5. Introduction to Electrical Faults  Under normal or safe operating conditions, the electric equipment in a power system network operate at normal voltage and current ratings. Once the fault takes place in a circuit or device, voltage and current values deviates from their nominal ranges.  The faults in power system causes over current, under voltage, unbalance of the phases, reversed power and high voltage surges. This results in the interruption of the normal operation of the network, failure of equipments, electrical fires, etc.
  • 6. Introduction to Electrical Faults  Usually power system networks are protected with switchgear protection equipment such as circuit breakers and relays in order to limit the loss of service due to the electrical failures.
  • 7. Types of Faults  Electrical faults in three-phase power system mainly classified into two types, namely open and short circuit faults. Further, these faults can be symmetrical or unsymmetrical faults. Open Circuit Faults (Series Faults)  These faults occur due to the failure of one or more conductors. It can be the open circuit faults for single, two and three phases (or conductors) open condition.
  • 8. Open Circuit Faults (Series Faults)  The most common causes of these faults include joint failures of cables and overhead lines, and failure of one or more phase of circuit breaker and also due to melting of a fuse or conductor in one or more phases.  Open circuit faults are also called as series faults. These are unsymmetrical or unbalanced type of faults except three phase open fault.
  • 9. Open Circuit Faults (Series Faults)
  • 10. Open Circuit Faults (Series Faults)  Consider that a transmission line is working with a balanced load before the occurrence of open circuit fault. If one of the phase gets melted, the actual loading of the alternator is reduced and this cause to raise the acceleration of the alternator, thereby it runs at a speed slightly greater than synchronous speed. This over speed causes over voltages in other transmission lines.  Thus, single and two phase open conditions can produce the unbalance of the power system voltages and currents that causes great damage to the equipment.
  • 11. Open Circuit Faults (Series Faults) Causes Broken conductor and malfunctioning of circuit breaker in one or more phases. Effects  Abnormal operation of the system  Danger to the personnel as well as animals  Exceeding the voltages beyond normal values in certain parts of the network, which further leads to insulation failures and developing of short circuit faults. Although open circuit faults can be tolerated for longer periods than short circuit faults, these must be removed as early as possible to reduce the greater damage.
  • 12. Short Circuit Faults (Shunt Faults)  A short circuit can be defined as an abnormal connection of very low impedance between two points of different potential, whether made intentionally or accidentally.  These are the most common and severe kind of faults, resulting in the flow of abnormal high currents through the equipment or transmission lines. If these faults are allowed to persist even for a short period, it leads to the extensive damage to the equipment.  Short circuit faults are also called as shunt faults. These faults are caused due to the insulation failure between phase conductors or between earth and phase conductors or both.
  • 13. Short Circuit Faults (Shunt Faults)  The various possible short circuit fault conditions include three phase to earth, three phase clear of earth, phase to phase, single phase to earth, two phase to earth and phase to phase plus single phase to earth as shown in figure.  The three phase fault clear of earth and three phase fault to earth are balanced or symmetrical short circuit faults while other remaining faults are unsymmetrical faults.
  • 14. Short Circuit Faults (Shunt Faults)
  • 15. Short Circuit Faults (Shunt Faults)
  • 16. Short Circuit Faults (Shunt Faults) Causes These may be due to internal or external effects:  Internal effects include breakdown of transmission lines or equipment, aging of insulation, deterioration of insulation in generator, transformer and other electrical equipment, improper installations and inadequate design.  External effects include overloading of equipment, insulation failure due to lighting surges and mechanical damage by public.
  • 17. Short Circuit Faults (Shunt Faults) Effects:  Arcing faults can lead to fire and explosion in equipment such as transformers and circuit breakers.  Abnormal currents cause the equipment to get overheated, which further leads to reduction of life span of their insulation.  The operating voltages of the system can go below or above their acceptance values that creates harmful effect to the service rendered by the power system.  The power flow is severely restricted or even completely blocked as long as the short circuit fault persists.
  • 18. Symmetrical and Unsymmetrical Faults Symmetrical and Unsymmetrical Faults As discussed above that faults are mainly classified into open and short circuit faults and again these can be symmetrical or unsymmetrical faults. Symmetrical Faults A symmetrical fault gives rise to symmetrical fault currents that are displaced with 120^0 each other. Symmetrical fault is also called as balanced fault. This fault occurs when all the three phases are simultaneously short circuited. These faults rarely occur in practice as compared with unsymmetrical faults.
  • 20. Symmetrical Faults  A rough occurrence of symmetrical faults is in the range of 2 to 5% of the total system faults. However, if these faults occur, they cause a very severe damage to the equipment even though the system remains in balanced condition.  The analysis of these faults is required for selecting the rupturing capacity of the circuit breakers, choosing set-phase relays and other protective switchgear. These faults are analyzed on per phase basis using bus impedance matrix or Thevenins’s theorem.
  • 21. Unsymmetrical Faults  The most common faults that occur in the power system network are unsymmetrical faults. This kind of fault gives rise to unsymmetrical fault currents (having different magnitudes with unequal phase displacement). These faults are also called as unbalanced faults as it causes unbalanced currents in the system.  Unsymmetrical faults include both open circuit faults (single and two phase open condition) and short circuit faults (excluding L-L-L-G and L-L-L).  A single line-to-ground (LG) fault is one of the most common faults and experiences show that 70-80 percent of the faults that occur in power system are of this type. This forms a short circuit path between the line and ground.
  • 22. Unsymmetrical Faults  A line to line fault occurs when a live conductor get in contact with other live conductor. Heavy winds are the major cause for this fault during which swinging of overhead conductors may touch together. These are less severe faults and its occurrence range may be between 15-20%.  In double line to ground faults, two lines come into the contact with each other as well as with ground. These are severe faults and the occurrence these faults is about 10% when compared with total system faults.  Unsymmetrical faults are analyzed using methods of unsymmetrical components in order to determine the voltage and currents in all parts of the system. The analysis of these faults is more difficult compared to symmetrical faults.  This analysis is necessary for determining the size of a circuit breaker for largest short circuit current. The greater current usually occurs for either L-G or L-L fault.
  • 23. Protection Devices When the fault occurs in any part of the system, it must be cleared in a very short period in order to avoid greater damage to equipment and personnel and also to avoid interruption of power to the customers. The fault clearing system uses various protection devices such as relays and circuit breakers to detect and clear the fault.
  • 24. Protection Devices Fuse It opens the circuit whenever a fault exists in the system. It consists of a thin copper wire enclosed in a glass or a casing with two metallic contacts. The high fault current rises the temperature of the wire and hence it melts. A fuse necessitates the manual replacement of wire each time when it blows. Circuit Breaker It is the most common protection device that can make or break the circuit either manually or through remote control under normal operating conditions. There are several types of circuit breakers available depending on the operating voltage, including air brake, oil, vacuum and SF6 circuit breakers.
  • 25. Protection Devices Protective Relays These are the fault detecting devices. These devices detect the fault and initiate the operation of the circuit breaker so as to isolate the faulty circuit. A relay consists of a magnetic coil and contacts. The fault current energizes the coil and this causes to produce the field, thereby the contacts get operated. Some of the types of protective relays include:  Magnitude relays  Impedance relays  Directional relays  Pilot relays  Differential relays
  • 26. Protection Devices Lighting Arrestor Surges in the power system network caused when lightning strikes on transmission lines and equipment. This causes high voltage and currents in the system. These lighting faults are reduced by placing lighting arrestors at transmission equipment.
  • 27. Cause of Short Circuit Insulation Failure • Over-voltages caused by Lightning or Switching Surges • Insulation contamination salt spray, pollution • Mechanical Causes Over-heating, abrasion Short Circuit Analysis
  • 28. Faults on Transmission Lines Most common Lines are exposed to elements of nature (60-70%). Lightning strokes Over voltages cause insulators to flash over line to ground short circuit or line to line short circuit. High winds Topple tower, tree falls on line. Winds and ice loading Mechanical failure of insulator
  • 29. Short circuit in other elements Fog, salt spray, dirty insulator Conduction path insulation failure Cables (10-15%), circuit breakers (10-12%), generators, motors, transformers etc (10-15%), Much less common Over loading for extended periods deterioration of insulation Mechanical failure.
  • 30. Consequences of Short Circuit Currents several magnitude larger than normal operating current. Thermal damage to equipment. Windings and bus-bars Mechanical damage due to high magnetic forces caused by high current. Faulted section must be removed from service as soon as possible (3-5 cycles).
  • 31. L-G L-L L-L-G 3ϕ-G 75-80% 5-7% 10-12% 8-10% Asymmetrical Faults Symmetrical Faults a b c Types of Short Circuit
  • 32. The selection of circuit breakers From the viewpoint of current the two factors that need to be considered in selecting circuit breakers are:  The maximum instantaneous current which the breaker must carry (withstand) and  The total current when the breaker contacts open to interrupt the circuit.