SlideShare a Scribd company logo
1 of 21
Download to read offline
Fully calculated fire fighting systems according
EN 12845 standard
Design and calculations with 4M FINE FIRE software
Fire Department Presentation
Isidoros Siderakis
EngineeringConsultant at 4M SA
mail: isidoros@4m.gr
Athens, October 2018
Basic steps for network designation using
FINE FIRE
1. Hazard selection according building type (LH, OH, HH)
2. Selection of sprinkler type and minimum design density (mm/min)
3. Sprinkler placement, network design and sprinkler group definition
4. Determination and checking of area covered per sprinkler displaying green or red colour
respectively
5. Network calculation
6. Definition of hydraulically most favourable and unfavourable group of sprinkler as well as
four sprinkler under consideration
7. Selection of appropriate fire pump, tank and net positive suction head (NPSH)
8. Get out technical reports, drawings and documentation
1. Hazard classification – Annex A (LH, OH, HH)
2. Select the sprinkler type and define the minimum design
density (§7.1)
FINE FIRE combines rich
libraries with a lot of types
of sprinklers and fire hoses
3. Place the sprinklers, set them to groups and design the
network.(table 37a)
𝑸 = 𝑲 𝑷
Maximum coverage and spacing for sprinkler other than sidewall (table 19)
Defining the fire fighting space area, FINE FIRE
places automatically the correct number of
sprinklers in right distances, following EN 12845
criterion .
4. Determine the area of coverage per sprinkler. Check if each
sprinkler can cover its area. (§ 13.4.1)
The density of discharge shall be taken as the total flow in
litres per minute from a group of four sprinklers which are
most closely adjacent, divided by the area in square metres
covered by the four sprinklers, or, where fewer than four
sprinklers are in open communication, the density of
discharge shall be taken as the lowest value of the flow from
any sprinkler divided by the area covered by the sprinkler.
Check of coverage area per sprinkler
FINE FIRE provides automated processes in order to
check automatically the area of coverage per
sprinkler and export the drawings. Drawings
updated in order to indicate the efficient sprinkler
placemenet with juct one click.
5. Network calculations
PxK=Q
5
1,85
1,85 4,87
5 06, 10 x
P xLxQ
C dx

Hydraulic calculation taking into account Hazen-Williams formula
Detailed calculation
Total flow required = 260+285+315= 860 lpm> 720 (12 * 60) lpm
Total flow required > Theoretical flow
Detailed calculation
Inserting data and exporting calculation automatically
FINE FIRE provides detailed calculations
automatically for all the widely known standards like
EN 12845, NFPA 13, BS 9251, FM Global, AS 2118,
ASIB CEA 4001 and other.
6. Definition of hydraulically most favourable and unfavourable
group of sprinkler as well as four sprinkler under consideration
Hydraulically most unfavourable location
• For gridded installations:
The correct position shall be proved by displacing the area of
operation by one sprinkler pitch in each direction along the range
pipes until the area with the highest pressure requirement is
identified.
• For looped installations:
The correct position shall be proved by displacing the area of
operation by one sprinkler pitch in each direction along the
distribution pipe until the area with the highest pressure
requirement is identified
Hydraulically most favourable location
All possible locations, whether on the distribution pipes, or between distribution pipes where
these are connected by range pipes, shall be considered when determining the hydraulically
most favourable location of the area of operation.
After calculation process, FINE FIRE indicates the most
favourable and unfavourable sprinkler group and update
drawings and calculation sheets. There are no restrictions
regarding the geometry and the complexity of the network.
7. Selection of appropriate fire pump, tank and net positive
suction head (NPSH) (§ 10.6.2.1)
Υπόμνημα
1 Υδραυλικά δυσμενέστερη περιοχή
2 Παροχή σχεδιασμού αντλίας
3 Μέγιστη απαιτούμενη παροχή
4 Υδραυλικά ευμενέστερη περιοχή
Design pump flow Maximum flow demand
FIRE PUMP selection
Basic principles according ΕΝ 12845 (§ 10.6.2.1, 10.7.3)
 The rated duty of the pump shall be a function of the most unfavourable area curve.
A pump is chosen which:
• provides 0,5 bar higher pressure than that required for the most unfavourable area
• has a curve which extends to the point of NPSHr = 16 m
 The Max Demand Flow & Pressure of the selected pump is calculated based on the most
favourable area
 It is checked if the pump can deliver the maximum operating point at all levels of water supply
1NPSHa NPSHreq 
FINE FIRE provides detailed calculation of the Fire Pump
based on the most favourable and unfavourable groups
and NPSH check.
Schematic diagram of a Fire pump selection
8. Get out technical reports, drawings and documentation
Briefly, according paragraph 4.4.3.3, 4.4.4.4-5 for fully calculated pipework, the following
shall be given, with detailed calculations, either on purpose designed work-sheets or as a
computer printout:
a. The program name and version number
b. Detailed and dimensioned working sheets with pipes and sprinklers
c. Detailed and dimensioned working drawings
d. Detailed calculations for the automatic pump set and storage tank
FINE FIRE performs calculations generate all the
required documents in compliance with
EN 12845 the standard.
b. Detailed and dimensioned working sheets with pipes and
sprinklers
i. pipe node or other reference number
ii. the specified design density in millimetres per
minute;
iii. pressures at inlet and outlet in bar
iv. the nominal K-factor
v. Nominal diameter in mm
vi. the Hazen-Williams constant
vii. length in metres
viii. velocity in metres per second (m/s)
ix. static head change in metres
x. friction loss in bar;
xi. numbers, types and equivalent length in metres of
fittings and components
xii. indication of flow direction
i
xii
iv ii,xii vi v viii xivii x iii
ix
© 4M s/n:999723
a
FINE FIRE 14.2
a
c. Detailed and dimensioned working drawings
i. the node or pipe reference scheme used to
identify pipes, junctions, sprinkler heads and
fittings which need hydraulic consideration
ii. the position of the hydraulically most
unfavourable and favourable area of operation
ii. the four sprinklers upon which the design
density is based
iii. the height above datum (e.g. pump axis) of each
point of identified pressure value.
v. the maximum area covered per sprinkler in
square metres (m2)
vi. the hazard class
vii. the specified design density in millimetres per
minute
viii. the number of sprinklers in the area of operation
ix. the sprinkler nominal orifice size in
millimetres(mm)
ii
iii Favourable
group
Unfavourable
group
i
viii
v
iv
vi
ix
vii
d. Detailed calculations for the automatic pump set and storage
tank
For fully calculated networks apart from the supplier’s data it s required the following
diagrams and calculations:
i. Chart with the demand pressure/flow characteristic for the hydraulically most
unfavourable and most favourable area of operation calculated at the control valve 'C'
gauge.η.
ii. the available and the specified NPSH at maximum required flow
FINE FIRE advantages for the user
• Familiar graphical user interface based on AutoCAD® or IntelliCad®
• Compatibility with Revit®, Archicad®, Vectorworks®, SketchUp Pro® or
equivalent, through the IFC import function
• Enables automatic and reliable hydraulic calculation and pipe sizing for all the
widely known standards like EN 12845, NFPA 13, FM GLOBAL, CEA 4001,
AS 2118, BS 9251 and ASIB 11th edition.
• Automatic placement of sprinkler to each space according to the hazard (LH,
OH, HH) of building and the type of sprinkler (roof or sidewall sprinkler)
• Automated processes for the definition and calculation of most favorable and
unfavorable sprinkler group directly from the calculation engine
• Integrated fire pump set calculation with operation diagrams in accordance
with the standard and NPSH calculation
• End to End firefighting design simulation with complete 2D and 3D drawings
and plenty of calculation reports, specifications and results
support@4msa.com
www.4msa.com

More Related Content

What's hot

FIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdfFIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdfrhamset
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Bowen Ngo
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protectionSabrul Jamil
 
Fire Pump Engines Overview
Fire Pump Engines OverviewFire Pump Engines Overview
Fire Pump Engines OverviewJames S Nasby
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxMEP ENGINEER'S SERVICES
 
Carbon dioxide fire suppression
Carbon dioxide fire suppressionCarbon dioxide fire suppression
Carbon dioxide fire suppressiontasander
 
Foam concentrates application rate and their flow rates
Foam concentrates application rate and their flow ratesFoam concentrates application rate and their flow rates
Foam concentrates application rate and their flow rateseSAT Journals
 
Firewater pump presentation ntt
Firewater pump presentation nttFirewater pump presentation ntt
Firewater pump presentation nttThanh Tin Nguyen
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentationakbar_ali
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...RajyogFireServicesPv
 
Fire Protection Training_QPS_26DEC20_Final.pptx
Fire Protection Training_QPS_26DEC20_Final.pptxFire Protection Training_QPS_26DEC20_Final.pptx
Fire Protection Training_QPS_26DEC20_Final.pptxVirenPatel528405
 

What's hot (20)

FIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdfFIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdf
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Chap 7 ventilation and smoke purging system
Chap 7 ventilation and smoke purging systemChap 7 ventilation and smoke purging system
Chap 7 ventilation and smoke purging system
 
Nfpa coods list2
Nfpa coods list2Nfpa coods list2
Nfpa coods list2
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...
 
Chapter 04
Chapter 04Chapter 04
Chapter 04
 
Fire pumps
Fire pumpsFire pumps
Fire pumps
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protection
 
Fire Pump Engines Overview
Fire Pump Engines OverviewFire Pump Engines Overview
Fire Pump Engines Overview
 
2. Hydrant System.pdf
2. Hydrant System.pdf2. Hydrant System.pdf
2. Hydrant System.pdf
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
 
Carbon dioxide fire suppression
Carbon dioxide fire suppressionCarbon dioxide fire suppression
Carbon dioxide fire suppression
 
Foam concentrates application rate and their flow rates
Foam concentrates application rate and their flow ratesFoam concentrates application rate and their flow rates
Foam concentrates application rate and their flow rates
 
Firewater pump presentation ntt
Firewater pump presentation nttFirewater pump presentation ntt
Firewater pump presentation ntt
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
Tank protection
Tank protectionTank protection
Tank protection
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
 
Fire Protection Training_QPS_26DEC20_Final.pptx
Fire Protection Training_QPS_26DEC20_Final.pptxFire Protection Training_QPS_26DEC20_Final.pptx
Fire Protection Training_QPS_26DEC20_Final.pptx
 
Fire Protection
Fire ProtectionFire Protection
Fire Protection
 
Basics of Fire fighting
Basics of Fire fightingBasics of Fire fighting
Basics of Fire fighting
 

Similar to Fully calculated firefighting systems with EN 12845 standard

Fire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxFire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxRafat30
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfSergioPereira229337
 
Numerical analysis for two phase flow distribution headers in heat exchangers
Numerical analysis for two phase flow distribution headers in heat exchangersNumerical analysis for two phase flow distribution headers in heat exchangers
Numerical analysis for two phase flow distribution headers in heat exchangerseSAT Journals
 
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).N.A. Tecnologia
 
Manual de dimensionamento de Traço a Vapor
Manual de dimensionamento de Traço a VaporManual de dimensionamento de Traço a Vapor
Manual de dimensionamento de Traço a VaporPaulo Costa
 
AutoPIPE - ProductDataSheet
AutoPIPE - ProductDataSheetAutoPIPE - ProductDataSheet
AutoPIPE - ProductDataSheetAllwyn Antony
 
Tutorial caesars II
Tutorial caesars IITutorial caesars II
Tutorial caesars IImanuedlf
 
Pressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelPressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelIRJET Journal
 
Effect of spikes integrated to airfoil at supersonic speed
Effect of spikes integrated to airfoil at supersonic speedEffect of spikes integrated to airfoil at supersonic speed
Effect of spikes integrated to airfoil at supersonic speedeSAT Journals
 
Effect of spikes integrated to airfoil at supersonic
Effect of spikes integrated to airfoil at supersonicEffect of spikes integrated to airfoil at supersonic
Effect of spikes integrated to airfoil at supersoniceSAT Publishing House
 
Dust collection system-Field study & proposed Design modification
Dust collection system-Field study & proposed  Design modificationDust collection system-Field study & proposed  Design modification
Dust collection system-Field study & proposed Design modificationHarinder Saini P.Eng., M.Tech., MBA
 
Fleetguard Filter ประเทศไทย
Fleetguard Filter ประเทศไทยFleetguard Filter ประเทศไทย
Fleetguard Filter ประเทศไทยDNTMb Inc.
 
Flow Instruments for Test and Measurement Selection Guide by Badger Meter
Flow Instruments for Test and Measurement Selection Guide by Badger MeterFlow Instruments for Test and Measurement Selection Guide by Badger Meter
Flow Instruments for Test and Measurement Selection Guide by Badger MeterThompson Equipment Company
 
New Thermal Mass Flow Meter From Fox Instruments
New Thermal Mass Flow Meter From Fox InstrumentsNew Thermal Mass Flow Meter From Fox Instruments
New Thermal Mass Flow Meter From Fox InstrumentsClassic Controls, Inc.
 
PipeFab For Revit_AU_LasVegas_2018
PipeFab For Revit_AU_LasVegas_2018PipeFab For Revit_AU_LasVegas_2018
PipeFab For Revit_AU_LasVegas_2018Ibrahem Naeem
 
Technical Data 2468 Pitot Primary Standard
Technical Data 2468 Pitot Primary StandardTechnical Data 2468 Pitot Primary Standard
Technical Data 2468 Pitot Primary StandardPT. Siwali Swantika
 
Real time exhaust analyzer - icat 2014
Real time exhaust analyzer - icat 2014Real time exhaust analyzer - icat 2014
Real time exhaust analyzer - icat 2014Pushkar Limaye
 

Similar to Fully calculated firefighting systems with EN 12845 standard (20)

D48073646
D48073646D48073646
D48073646
 
Fire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptxFire Safety (Common Design Issues) .pptx
Fire Safety (Common Design Issues) .pptx
 
specif-dust-extraction-system.pdf
specif-dust-extraction-system.pdfspecif-dust-extraction-system.pdf
specif-dust-extraction-system.pdf
 
Numerical analysis for two phase flow distribution headers in heat exchangers
Numerical analysis for two phase flow distribution headers in heat exchangersNumerical analysis for two phase flow distribution headers in heat exchangers
Numerical analysis for two phase flow distribution headers in heat exchangers
 
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).
PV Elite 2019 Service Pack 2 (Version 21.00.02.0000).
 
Manual de dimensionamento de Traço a Vapor
Manual de dimensionamento de Traço a VaporManual de dimensionamento de Traço a Vapor
Manual de dimensionamento de Traço a Vapor
 
AutoPIPE - ProductDataSheet
AutoPIPE - ProductDataSheetAutoPIPE - ProductDataSheet
AutoPIPE - ProductDataSheet
 
Tutorial caesars II
Tutorial caesars IITutorial caesars II
Tutorial caesars II
 
Pressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelPressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channel
 
IGRC-KOREA
IGRC-KOREAIGRC-KOREA
IGRC-KOREA
 
Effect of spikes integrated to airfoil at supersonic speed
Effect of spikes integrated to airfoil at supersonic speedEffect of spikes integrated to airfoil at supersonic speed
Effect of spikes integrated to airfoil at supersonic speed
 
Effect of spikes integrated to airfoil at supersonic
Effect of spikes integrated to airfoil at supersonicEffect of spikes integrated to airfoil at supersonic
Effect of spikes integrated to airfoil at supersonic
 
Dust collection system-Field study & proposed Design modification
Dust collection system-Field study & proposed  Design modificationDust collection system-Field study & proposed  Design modification
Dust collection system-Field study & proposed Design modification
 
Fleetguard Filter ประเทศไทย
Fleetguard Filter ประเทศไทยFleetguard Filter ประเทศไทย
Fleetguard Filter ประเทศไทย
 
GE Inspection: Industrial Process Control with Computed Tomography (CT)
GE Inspection: Industrial Process Control with Computed Tomography (CT)GE Inspection: Industrial Process Control with Computed Tomography (CT)
GE Inspection: Industrial Process Control with Computed Tomography (CT)
 
Flow Instruments for Test and Measurement Selection Guide by Badger Meter
Flow Instruments for Test and Measurement Selection Guide by Badger MeterFlow Instruments for Test and Measurement Selection Guide by Badger Meter
Flow Instruments for Test and Measurement Selection Guide by Badger Meter
 
New Thermal Mass Flow Meter From Fox Instruments
New Thermal Mass Flow Meter From Fox InstrumentsNew Thermal Mass Flow Meter From Fox Instruments
New Thermal Mass Flow Meter From Fox Instruments
 
PipeFab For Revit_AU_LasVegas_2018
PipeFab For Revit_AU_LasVegas_2018PipeFab For Revit_AU_LasVegas_2018
PipeFab For Revit_AU_LasVegas_2018
 
Technical Data 2468 Pitot Primary Standard
Technical Data 2468 Pitot Primary StandardTechnical Data 2468 Pitot Primary Standard
Technical Data 2468 Pitot Primary Standard
 
Real time exhaust analyzer - icat 2014
Real time exhaust analyzer - icat 2014Real time exhaust analyzer - icat 2014
Real time exhaust analyzer - icat 2014
 

Recently uploaded

247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 

Recently uploaded (20)

247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 

Fully calculated firefighting systems with EN 12845 standard

  • 1. Fully calculated fire fighting systems according EN 12845 standard Design and calculations with 4M FINE FIRE software Fire Department Presentation Isidoros Siderakis EngineeringConsultant at 4M SA mail: isidoros@4m.gr Athens, October 2018
  • 2. Basic steps for network designation using FINE FIRE 1. Hazard selection according building type (LH, OH, HH) 2. Selection of sprinkler type and minimum design density (mm/min) 3. Sprinkler placement, network design and sprinkler group definition 4. Determination and checking of area covered per sprinkler displaying green or red colour respectively 5. Network calculation 6. Definition of hydraulically most favourable and unfavourable group of sprinkler as well as four sprinkler under consideration 7. Selection of appropriate fire pump, tank and net positive suction head (NPSH) 8. Get out technical reports, drawings and documentation
  • 3. 1. Hazard classification – Annex A (LH, OH, HH)
  • 4. 2. Select the sprinkler type and define the minimum design density (§7.1) FINE FIRE combines rich libraries with a lot of types of sprinklers and fire hoses
  • 5. 3. Place the sprinklers, set them to groups and design the network.(table 37a) 𝑸 = 𝑲 𝑷
  • 6. Maximum coverage and spacing for sprinkler other than sidewall (table 19) Defining the fire fighting space area, FINE FIRE places automatically the correct number of sprinklers in right distances, following EN 12845 criterion .
  • 7. 4. Determine the area of coverage per sprinkler. Check if each sprinkler can cover its area. (§ 13.4.1) The density of discharge shall be taken as the total flow in litres per minute from a group of four sprinklers which are most closely adjacent, divided by the area in square metres covered by the four sprinklers, or, where fewer than four sprinklers are in open communication, the density of discharge shall be taken as the lowest value of the flow from any sprinkler divided by the area covered by the sprinkler. Check of coverage area per sprinkler FINE FIRE provides automated processes in order to check automatically the area of coverage per sprinkler and export the drawings. Drawings updated in order to indicate the efficient sprinkler placemenet with juct one click.
  • 8. 5. Network calculations PxK=Q 5 1,85 1,85 4,87 5 06, 10 x P xLxQ C dx  Hydraulic calculation taking into account Hazen-Williams formula
  • 10. Total flow required = 260+285+315= 860 lpm> 720 (12 * 60) lpm Total flow required > Theoretical flow Detailed calculation
  • 11. Inserting data and exporting calculation automatically FINE FIRE provides detailed calculations automatically for all the widely known standards like EN 12845, NFPA 13, BS 9251, FM Global, AS 2118, ASIB CEA 4001 and other.
  • 12. 6. Definition of hydraulically most favourable and unfavourable group of sprinkler as well as four sprinkler under consideration Hydraulically most unfavourable location • For gridded installations: The correct position shall be proved by displacing the area of operation by one sprinkler pitch in each direction along the range pipes until the area with the highest pressure requirement is identified. • For looped installations: The correct position shall be proved by displacing the area of operation by one sprinkler pitch in each direction along the distribution pipe until the area with the highest pressure requirement is identified Hydraulically most favourable location All possible locations, whether on the distribution pipes, or between distribution pipes where these are connected by range pipes, shall be considered when determining the hydraulically most favourable location of the area of operation. After calculation process, FINE FIRE indicates the most favourable and unfavourable sprinkler group and update drawings and calculation sheets. There are no restrictions regarding the geometry and the complexity of the network.
  • 13. 7. Selection of appropriate fire pump, tank and net positive suction head (NPSH) (§ 10.6.2.1) Υπόμνημα 1 Υδραυλικά δυσμενέστερη περιοχή 2 Παροχή σχεδιασμού αντλίας 3 Μέγιστη απαιτούμενη παροχή 4 Υδραυλικά ευμενέστερη περιοχή Design pump flow Maximum flow demand
  • 14. FIRE PUMP selection Basic principles according ΕΝ 12845 (§ 10.6.2.1, 10.7.3)  The rated duty of the pump shall be a function of the most unfavourable area curve. A pump is chosen which: • provides 0,5 bar higher pressure than that required for the most unfavourable area • has a curve which extends to the point of NPSHr = 16 m  The Max Demand Flow & Pressure of the selected pump is calculated based on the most favourable area  It is checked if the pump can deliver the maximum operating point at all levels of water supply 1NPSHa NPSHreq  FINE FIRE provides detailed calculation of the Fire Pump based on the most favourable and unfavourable groups and NPSH check.
  • 15. Schematic diagram of a Fire pump selection
  • 16. 8. Get out technical reports, drawings and documentation Briefly, according paragraph 4.4.3.3, 4.4.4.4-5 for fully calculated pipework, the following shall be given, with detailed calculations, either on purpose designed work-sheets or as a computer printout: a. The program name and version number b. Detailed and dimensioned working sheets with pipes and sprinklers c. Detailed and dimensioned working drawings d. Detailed calculations for the automatic pump set and storage tank FINE FIRE performs calculations generate all the required documents in compliance with EN 12845 the standard.
  • 17. b. Detailed and dimensioned working sheets with pipes and sprinklers i. pipe node or other reference number ii. the specified design density in millimetres per minute; iii. pressures at inlet and outlet in bar iv. the nominal K-factor v. Nominal diameter in mm vi. the Hazen-Williams constant vii. length in metres viii. velocity in metres per second (m/s) ix. static head change in metres x. friction loss in bar; xi. numbers, types and equivalent length in metres of fittings and components xii. indication of flow direction i xii iv ii,xii vi v viii xivii x iii ix © 4M s/n:999723 a FINE FIRE 14.2 a
  • 18. c. Detailed and dimensioned working drawings i. the node or pipe reference scheme used to identify pipes, junctions, sprinkler heads and fittings which need hydraulic consideration ii. the position of the hydraulically most unfavourable and favourable area of operation ii. the four sprinklers upon which the design density is based iii. the height above datum (e.g. pump axis) of each point of identified pressure value. v. the maximum area covered per sprinkler in square metres (m2) vi. the hazard class vii. the specified design density in millimetres per minute viii. the number of sprinklers in the area of operation ix. the sprinkler nominal orifice size in millimetres(mm) ii iii Favourable group Unfavourable group i viii v iv vi ix vii
  • 19. d. Detailed calculations for the automatic pump set and storage tank For fully calculated networks apart from the supplier’s data it s required the following diagrams and calculations: i. Chart with the demand pressure/flow characteristic for the hydraulically most unfavourable and most favourable area of operation calculated at the control valve 'C' gauge.η. ii. the available and the specified NPSH at maximum required flow
  • 20. FINE FIRE advantages for the user • Familiar graphical user interface based on AutoCAD® or IntelliCad® • Compatibility with Revit®, Archicad®, Vectorworks®, SketchUp Pro® or equivalent, through the IFC import function • Enables automatic and reliable hydraulic calculation and pipe sizing for all the widely known standards like EN 12845, NFPA 13, FM GLOBAL, CEA 4001, AS 2118, BS 9251 and ASIB 11th edition. • Automatic placement of sprinkler to each space according to the hazard (LH, OH, HH) of building and the type of sprinkler (roof or sidewall sprinkler) • Automated processes for the definition and calculation of most favorable and unfavorable sprinkler group directly from the calculation engine • Integrated fire pump set calculation with operation diagrams in accordance with the standard and NPSH calculation • End to End firefighting design simulation with complete 2D and 3D drawings and plenty of calculation reports, specifications and results