SlideShare a Scribd company logo
1 of 46
Download to read offline
FIRE PUMPS
FIRE PUMPS
General
 A centrifugal pump for fire protection shall be
selected to operate at less than or equal to 150% of
the rated capacity. The pump should be selected at
capacities between 90% to 140% of the rated
capacity( clause 5.8.1 ).
 It is a poor design practice to overdesign the fire
pump and the driver and depend on the pressure
relief valve to open and relieve the excess pressure
Requirements of Pump room
 Indoor fire pump units should be physically
separated or protected by fire rated construction.
For a fully sprinklered pump room one hour fire
rating is required.
 Emergency lighting and ventilation are required in
pump room.
 Drainage-Flow should be pitched to adequate
drainage of escaping water from pump and other
accessories.
Piping
 Steel pipe should be used for above ground
applications. For underground applications
NFPA 24 should be followed.
 Steel pipes should be joined by means of
threaded, flanged (flanges welded to pipes
are preferred), grooved joints.
Suction piping
 The size of the suction pipe for a single pump or of
the suction header pipe for multiple pumps
( operating together) should be such that with all
pumps operating at 150% of the rated capacity, the
gauge pressure at the pump suction flanges should
be 0 bar or higher.
 Where the supply is the suction tank with its base at
or above the same elevation as the pump gauge,
pressure at the pump suction flange shall be
permitted to drop to -0.2 bar.
Suction piping………cont’d
 Suction pipe should be sized such that with the
pumps operating at 150% of the rated capacity, the
velocity in that portion of the suction pipe located
within 10 pipe diameters upstream of the suction
flange does not exceed 4.57m/s and the size should
not be less than that specified in section 5.25
 A listed OS&Y gate valve should be installed in the
suction pipe.
Suction piping………cont’d
 No valve other than a listed OS&Y valve should be
installed in the suction pipe within 15.3m.
 Elbows and Tees with a centre line plane parallel to
HSC pump are not permitted within 10 times the
suction pipe diameter.
 Elbows with centre line plane perpendicular to HSC
pump shaft is permitted.
 Where the pump and water tank are on separate
foundations provision shall be made for strain relief.
Suction piping………cont’d
 For pumps taking suction from a water tank a vortex
plate shall be provided at the entrance to the suction
pipe.
Discharge piping
 The size of the pump discharge pipe should not be
less than that given in section 5.25
 Flanges welded to pipes are preferred.
 Butterfly valves are permitted.
 No pressure regulating devices should be installed
in the discharge pipe except as permitted in NFPA
20.
 Pressure relief valves are required for diesel engine
pumps only if the 121% of the shut off head + static
suction pressure exceeds the system components
rating.
Discharge piping………..cont’d
 Size of the relief valve should be as per section 5.25
 Relief valve should be located between check valve
and the pump.
 Relief valve discharge piping returning water back to
the storage tank should be piped independently and
not be combined with the discharge from other relief
valves.
 Flow meter-size of the test line and flow meter
should be as per section 5.25
Jockey pump
 Flow rate of a jockey pump should not be less than
the normal leakage rate.
 Jockey pump should be sized to make up the
allowable leakage rate within 10 minutes or 3.8
litres/min which ever is larger.
 For sprinkler systems jockey pumps are generally
sized to flow an amount of water less than or equal
to that required by a single sprinkler.
Centrifugal Pumps
 Centrifugal pumps shall not be used where a static
suction lift is required.
 Fittings (accessories) to be provided by the
manufacturer or an authorised representative.
1.Automatic air release valve
2.Circulation relief valve
3.Pressure gauges
 Strainer:-Pumps that require removal of the driver to
remove rocks or debris from the pump impeller
should have a pipe lined strainer installed in the
suction line a minimum of 10 pipe diameters from
the suction flange.
Centrifugal Pumps………
cont’d
 Foundation:-The base plate of the pump should be
securely attached to the solid foundation.
 The foundation should be sufficiently substantial to
form a permanent and rigid support for the base
plate.
Vertical shaft turbine pumps
 Wet Pit Installation
 The required submergence should be obtained from
the pump manufacturer.
Electric drive for pumps
 For pumps driven by electric motors where a reliable
power cannot be obtained from reliable power
sources , one of the following arrangements should
be provided.
 Combination of two or more power sources
 One of the approved power sources and an onsite
standby generator.
 An approved combination of feeders constituting two
or more power sources.
Electric drive for pumps…
cont’d
 Combination of one or feeders in combination with
an onsite standby generator
 One of the power source and a redundant fire pump
driven by diesel engine.
 Transfer of power to the fire pump controller
between normal power supply and one alternate
power supply should take place within the pump
room.
Fire pump’s controller
(Electric)
Primary Design
 System operation is Primary
 Protection of connected motor is secondary
Fire pump’s controller
(Electric)………….cont’d
 Controllers should be located as close as is
practical to the motors they control and
should be within the site of the motors.
 Interfacing with fire alarm system.
Pump running
Loss of Phase
Phase reversal
Controller connected to alternate power
supply.
Emergency Starting Circuits
 If the contactor coil does not function for any
reason an emergency mechanical means is
available for closing the contactor
Service Entrance Rating
 Utility can DIRECTLY connect to controller
 Equipped with grounding lug bonded to the
enclosure
 For added safety controller equipped with
isolating switch interlocked with enclosure
door.
Motor Contactor
 No control circuit fuse
 No voltage, frequency or other sensor to
prevent operation of contactor
 No thermal overload relay
 Contactor coil at LINE voltage
Circuit Breaker
 Maintains locked rotor current for:
 8 Seconds Minimum
 20 Seconds Maximum
 LRC=600% of Motor FLA
 Minimum setting is 300% of the motor’s full
load Amps for 30 minutes minimum
Circuit Breaker Type
 Magnetic device only
 No thermal elements are permitted
 Instantaneous Reset
Circuit Breaker Basic Design
 Set to allow operation, not to protect the
connected electric motor
 All motors shall be specifically listed for fire
pump service
 Horsepower and locked rotor current motor
designation shall be as per NEC & NFPA 70
National Electric Code
 All motors shall comply with NEMA standard
MG-1 and be marked as complying with
NEMA Design B standards
 All motors shall be rated for continuous duty
and shall be applied only at voltages of +10
percent of the motor nameplate voltage.
 Electric-motor-induced transients shall be
coordinated with 7-4.3.3 to prevent nuisance
tripping of motor controller protective devices.
Diesel Engine
 Fuel Supply and arrangement
Fuel tank should have a capacity at least 1 gal/hp,
plus 5% volume for expansion and 5% volume for
sump
 For multiple diesel engine pumps, separate fuel line
and separate fuel tank are required.
 Inlet to the fuel supply line should be located so that
its opening is no lower than the level of the engine
fuel pump.
Diesel Engine…..cont’d
 The engine manufacturer’s fuel pump static head
pressure limit should not be exceeded.
 Galvanised steel or copper should not be used for
fuel piping
 No shutoff valve should be installed in the fuel return
line to the tank.
 Air supply and discharge ventilators should be
provided.
Controller for Diesel Engine
 System operation is primary
 Protection of the connected engine is
secondary
Engine Protection Circuits
Allows engine to continue operation:
 When a low oil pressure condition exists
 When a high cooling water temperature
condition exists.

More Related Content

What's hot

Inspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpInspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpklsmani
 
Training Fire Water Pump.ppt
Training Fire Water Pump.pptTraining Fire Water Pump.ppt
Training Fire Water Pump.pptHasanudinUdin7
 
Introductory training on fire water pumping system
Introductory training  on fire water pumping systemIntroductory training  on fire water pumping system
Introductory training on fire water pumping systemSabrul Jamil
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant systemFIRE KNOCK
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentationakbar_ali
 
Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"EzazulHaqueSiddique
 
Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Akshay Jangam
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System DesignMostafa Al Wakeel
 
Fire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfFire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfmohamedibrahim219956
 
Water mist prepared by salah ramadan
Water mist prepared by salah ramadanWater mist prepared by salah ramadan
Water mist prepared by salah ramadanEng Salah Ramadan
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protectionSabrul Jamil
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...RajyogFireServicesPv
 
How to operate Fire Pump
How to operate Fire PumpHow to operate Fire Pump
How to operate Fire Pumpshahidalim
 

What's hot (20)

Inspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pumpInspection, Testing and Maintenance of fire pump
Inspection, Testing and Maintenance of fire pump
 
Fire pumps
Fire pumpsFire pumps
Fire pumps
 
Training Fire Water Pump.ppt
Training Fire Water Pump.pptTraining Fire Water Pump.ppt
Training Fire Water Pump.ppt
 
Introductory training on fire water pumping system
Introductory training  on fire water pumping systemIntroductory training  on fire water pumping system
Introductory training on fire water pumping system
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant system
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"
 
Diesel Fire Pump Controllers
Diesel Fire Pump ControllersDiesel Fire Pump Controllers
Diesel Fire Pump Controllers
 
Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam. Water Mist Systems - Akshay Jangam.
Water Mist Systems - Akshay Jangam.
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System Design
 
Fire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfFire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdf
 
Water mist prepared by salah ramadan
Water mist prepared by salah ramadanWater mist prepared by salah ramadan
Water mist prepared by salah ramadan
 
Fire fighting -2 By Er. Ezaz
Fire fighting -2 By Er. EzazFire fighting -2 By Er. Ezaz
Fire fighting -2 By Er. Ezaz
 
Fire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. EzazFire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. Ezaz
 
Basics of Fire fighting
Basics of Fire fightingBasics of Fire fighting
Basics of Fire fighting
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protection
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
 
Chapter 05
Chapter 05Chapter 05
Chapter 05
 
How to operate Fire Pump
How to operate Fire PumpHow to operate Fire Pump
How to operate Fire Pump
 

Similar to Fire pumps in brief

New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualfujsjefjkskefksem
 
New holland t8020 tractor service repair manual
New holland t8020 tractor service repair manualNew holland t8020 tractor service repair manual
New holland t8020 tractor service repair manualfujsjfjksekem
 
New holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualNew holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualfijsfjskekmme
 
New Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdfNew Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdffusedkdd9idi
 
New Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdfNew Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdffusedkdd9idi
 
New Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdfNew Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdffusedkdd9idi
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdffusedkdd9idi
 
New Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdfNew Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdffusedkdd9idi
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfzui07gang
 
New holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualNew holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualpfiskdmjekm
 
New holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant downloadNew holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant downloadujjdfjkkskedmmed
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualfisejfjsekfksem
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualfjsekksmemm
 
New holland t8050 tractor service repair manual
New holland t8050 tractor service repair manualNew holland t8050 tractor service repair manual
New holland t8050 tractor service repair manualufjkskemfseol
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualfksjksmmde
 
New Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdfNew Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdffusedkdm9id
 
New Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdfNew Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdffusedkdm9id
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdffusedkdm9id
 
New Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdfNew Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdffusedkdm9id
 

Similar to Fire pumps in brief (20)

API 675 over view
API 675 over viewAPI 675 over view
API 675 over view
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manual
 
New holland t8020 tractor service repair manual
New holland t8020 tractor service repair manualNew holland t8020 tractor service repair manual
New holland t8020 tractor service repair manual
 
New holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualNew holland t8040 tractor service repair manual
New holland t8040 tractor service repair manual
 
New Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdfNew Holland T8040 Tractor Service Repair Manual.pdf
New Holland T8040 Tractor Service Repair Manual.pdf
 
New Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdfNew Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdf
 
New Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdfNew Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdf
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 
New Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdfNew Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdf
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 
New holland t8040 tractor service repair manual
New holland t8040 tractor service repair manualNew holland t8040 tractor service repair manual
New holland t8040 tractor service repair manual
 
New holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant downloadNew holland t8040 tractor service repair manual instant download
New holland t8040 tractor service repair manual instant download
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manual
 
New holland t8010 tractor service repair manual
New holland t8010 tractor service repair manualNew holland t8010 tractor service repair manual
New holland t8010 tractor service repair manual
 
New holland t8050 tractor service repair manual
New holland t8050 tractor service repair manualNew holland t8050 tractor service repair manual
New holland t8050 tractor service repair manual
 
New holland t8030 tractor service repair manual
New holland t8030 tractor service repair manualNew holland t8030 tractor service repair manual
New holland t8030 tractor service repair manual
 
New Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdfNew Holland T8020 Tractor Service Repair Manual.pdf
New Holland T8020 Tractor Service Repair Manual.pdf
 
New Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdfNew Holland T8030 Tractor Service Repair Manual.pdf
New Holland T8030 Tractor Service Repair Manual.pdf
 
New Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdfNew Holland T8050 Tractor Service Repair Manual.pdf
New Holland T8050 Tractor Service Repair Manual.pdf
 
New Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdfNew Holland T8010 Tractor Service Repair Manual.pdf
New Holland T8010 Tractor Service Repair Manual.pdf
 

More from Mostafa Al Wakeel

More from Mostafa Al Wakeel (8)

Flexible Ducts
Flexible DuctsFlexible Ducts
Flexible Ducts
 
BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)
 
Basics of building fire protection design
Basics of building fire protection designBasics of building fire protection design
Basics of building fire protection design
 
Air Duct Leakage
Air Duct LeakageAir Duct Leakage
Air Duct Leakage
 
Interactive damper selection guide
Interactive damper selection guideInteractive damper selection guide
Interactive damper selection guide
 
Fire suppression
Fire suppressionFire suppression
Fire suppression
 
Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019
 
Fm 200 calculator
Fm 200 calculatorFm 200 calculator
Fm 200 calculator
 

Recently uploaded

Computer Graphics Introduction To Curves
Computer Graphics Introduction To CurvesComputer Graphics Introduction To Curves
Computer Graphics Introduction To CurvesChandrakantDivate1
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxSCMS School of Architecture
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsvanyagupta248
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...ppkakm
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...gragchanchal546
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfsumitt6_25730773
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Ramkumar k
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdfKamal Acharya
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptxrouholahahmadi9876
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...drmkjayanthikannan
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...ronahami
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiessarkmank1
 
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...vershagrag
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementDr. Deepak Mudgal
 
fitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptfitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptAfnanAhmad53
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxSCMS School of Architecture
 

Recently uploaded (20)

Computer Graphics Introduction To Curves
Computer Graphics Introduction To CurvesComputer Graphics Introduction To Curves
Computer Graphics Introduction To Curves
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
fitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .pptfitting shop and tools used in fitting shop .ppt
fitting shop and tools used in fitting shop .ppt
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 

Fire pumps in brief

  • 2. FIRE PUMPS General  A centrifugal pump for fire protection shall be selected to operate at less than or equal to 150% of the rated capacity. The pump should be selected at capacities between 90% to 140% of the rated capacity( clause 5.8.1 ).  It is a poor design practice to overdesign the fire pump and the driver and depend on the pressure relief valve to open and relieve the excess pressure
  • 3. Requirements of Pump room  Indoor fire pump units should be physically separated or protected by fire rated construction. For a fully sprinklered pump room one hour fire rating is required.  Emergency lighting and ventilation are required in pump room.  Drainage-Flow should be pitched to adequate drainage of escaping water from pump and other accessories.
  • 4. Piping  Steel pipe should be used for above ground applications. For underground applications NFPA 24 should be followed.  Steel pipes should be joined by means of threaded, flanged (flanges welded to pipes are preferred), grooved joints.
  • 5.
  • 6.
  • 7. Suction piping  The size of the suction pipe for a single pump or of the suction header pipe for multiple pumps ( operating together) should be such that with all pumps operating at 150% of the rated capacity, the gauge pressure at the pump suction flanges should be 0 bar or higher.  Where the supply is the suction tank with its base at or above the same elevation as the pump gauge, pressure at the pump suction flange shall be permitted to drop to -0.2 bar.
  • 8. Suction piping………cont’d  Suction pipe should be sized such that with the pumps operating at 150% of the rated capacity, the velocity in that portion of the suction pipe located within 10 pipe diameters upstream of the suction flange does not exceed 4.57m/s and the size should not be less than that specified in section 5.25  A listed OS&Y gate valve should be installed in the suction pipe.
  • 9.
  • 10. Suction piping………cont’d  No valve other than a listed OS&Y valve should be installed in the suction pipe within 15.3m.  Elbows and Tees with a centre line plane parallel to HSC pump are not permitted within 10 times the suction pipe diameter.  Elbows with centre line plane perpendicular to HSC pump shaft is permitted.  Where the pump and water tank are on separate foundations provision shall be made for strain relief.
  • 11.
  • 12. Suction piping………cont’d  For pumps taking suction from a water tank a vortex plate shall be provided at the entrance to the suction pipe.
  • 13.
  • 14. Discharge piping  The size of the pump discharge pipe should not be less than that given in section 5.25  Flanges welded to pipes are preferred.  Butterfly valves are permitted.  No pressure regulating devices should be installed in the discharge pipe except as permitted in NFPA 20.  Pressure relief valves are required for diesel engine pumps only if the 121% of the shut off head + static suction pressure exceeds the system components rating.
  • 15.
  • 16. Discharge piping………..cont’d  Size of the relief valve should be as per section 5.25  Relief valve should be located between check valve and the pump.  Relief valve discharge piping returning water back to the storage tank should be piped independently and not be combined with the discharge from other relief valves.  Flow meter-size of the test line and flow meter should be as per section 5.25
  • 17.
  • 18.
  • 19. Jockey pump  Flow rate of a jockey pump should not be less than the normal leakage rate.  Jockey pump should be sized to make up the allowable leakage rate within 10 minutes or 3.8 litres/min which ever is larger.  For sprinkler systems jockey pumps are generally sized to flow an amount of water less than or equal to that required by a single sprinkler.
  • 20. Centrifugal Pumps  Centrifugal pumps shall not be used where a static suction lift is required.  Fittings (accessories) to be provided by the manufacturer or an authorised representative. 1.Automatic air release valve 2.Circulation relief valve 3.Pressure gauges  Strainer:-Pumps that require removal of the driver to remove rocks or debris from the pump impeller should have a pipe lined strainer installed in the suction line a minimum of 10 pipe diameters from the suction flange.
  • 21. Centrifugal Pumps……… cont’d  Foundation:-The base plate of the pump should be securely attached to the solid foundation.  The foundation should be sufficiently substantial to form a permanent and rigid support for the base plate.
  • 22.
  • 23.
  • 24.
  • 25.
  • 26. Vertical shaft turbine pumps  Wet Pit Installation  The required submergence should be obtained from the pump manufacturer.
  • 27.
  • 28.
  • 29. Electric drive for pumps  For pumps driven by electric motors where a reliable power cannot be obtained from reliable power sources , one of the following arrangements should be provided.  Combination of two or more power sources  One of the approved power sources and an onsite standby generator.  An approved combination of feeders constituting two or more power sources.
  • 30. Electric drive for pumps… cont’d  Combination of one or feeders in combination with an onsite standby generator  One of the power source and a redundant fire pump driven by diesel engine.  Transfer of power to the fire pump controller between normal power supply and one alternate power supply should take place within the pump room.
  • 31. Fire pump’s controller (Electric) Primary Design  System operation is Primary  Protection of connected motor is secondary
  • 32. Fire pump’s controller (Electric)………….cont’d  Controllers should be located as close as is practical to the motors they control and should be within the site of the motors.  Interfacing with fire alarm system. Pump running Loss of Phase Phase reversal Controller connected to alternate power supply.
  • 33. Emergency Starting Circuits  If the contactor coil does not function for any reason an emergency mechanical means is available for closing the contactor
  • 34. Service Entrance Rating  Utility can DIRECTLY connect to controller  Equipped with grounding lug bonded to the enclosure  For added safety controller equipped with isolating switch interlocked with enclosure door.
  • 35. Motor Contactor  No control circuit fuse  No voltage, frequency or other sensor to prevent operation of contactor  No thermal overload relay  Contactor coil at LINE voltage
  • 36. Circuit Breaker  Maintains locked rotor current for:  8 Seconds Minimum  20 Seconds Maximum  LRC=600% of Motor FLA  Minimum setting is 300% of the motor’s full load Amps for 30 minutes minimum
  • 37. Circuit Breaker Type  Magnetic device only  No thermal elements are permitted  Instantaneous Reset
  • 38. Circuit Breaker Basic Design  Set to allow operation, not to protect the connected electric motor
  • 39.  All motors shall be specifically listed for fire pump service  Horsepower and locked rotor current motor designation shall be as per NEC & NFPA 70 National Electric Code  All motors shall comply with NEMA standard MG-1 and be marked as complying with NEMA Design B standards
  • 40.  All motors shall be rated for continuous duty and shall be applied only at voltages of +10 percent of the motor nameplate voltage.  Electric-motor-induced transients shall be coordinated with 7-4.3.3 to prevent nuisance tripping of motor controller protective devices.
  • 41.
  • 42. Diesel Engine  Fuel Supply and arrangement Fuel tank should have a capacity at least 1 gal/hp, plus 5% volume for expansion and 5% volume for sump  For multiple diesel engine pumps, separate fuel line and separate fuel tank are required.  Inlet to the fuel supply line should be located so that its opening is no lower than the level of the engine fuel pump.
  • 43.
  • 44. Diesel Engine…..cont’d  The engine manufacturer’s fuel pump static head pressure limit should not be exceeded.  Galvanised steel or copper should not be used for fuel piping  No shutoff valve should be installed in the fuel return line to the tank.  Air supply and discharge ventilators should be provided.
  • 45. Controller for Diesel Engine  System operation is primary  Protection of the connected engine is secondary
  • 46. Engine Protection Circuits Allows engine to continue operation:  When a low oil pressure condition exists  When a high cooling water temperature condition exists.