IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 3 Ver. III (May. – Jun. 2016), PP 29-33
www.iosrjournals.org
DOI: 10.9790/1676-1103032933 www.iosrjournals.org 29 | Page
Understanding the Concept of Earthing In Electric Power System
Engineering
Ajayi,A1
Jerome,D.K2
, Osayi F.S3
and Izugie F.I4
1,2,3 Department of Electrical and Electronic Engineering, Auchi Polytechnic, Auchi Edo state Nigeria
Abstract: Earthing is the concept of connecting a thing to the earth (or ground). In Power systems,
engineering, ear thing is the one concept that cannot be dispensed with. Generators, reactors and transformers
have to be earthed at their star or neutral point for proper operation and application of earth-fault relays; for
the realization of single phase voltage supply (in the case of transformers); and for the drainage (as much as
possible) of the harmonic voltages that cause distortions in system voltages. Furthermore, the metallic
enclosure and non-conduction parts of every apparatus requires earthing for the protection of personnel and
users from electrical hazards. It is inestimable the quantity and value of lives and properly that would have been
lost to electrical faults but for the application of this concept. Thus, in this paper a detailed discussion of system
and equipment ear thing is presented. The writer recommend the use of chem.-rods for better ear thing, as well
as an appropriate routine earth-point maintenances schedule
Keywords: earth-fault relay, neutral point, harmonic voltage
I. Introduction
Power system engineering is that field of conscious human endeavour in which energy is generated,
converted and transmitted (over a long or short distances) for the purpose of distribution and eventual utilization
for the benefit of man and beast. In this connection however, it is mechanical energy that is generated in the
most cases and converted into electrical energy.
The concept of earthing in power system engineering is as old as this field of endeavour itself. It came
into play from the age-long fact that the earth is a universal sink. Thus, this concept has to do with a connection
to the general mass of earth in such a manner as to ensure immediate drainage of energy into the same without
danger and for the avoidance of danger.
Therefore, earthing (or grounding as also referred to) features prominently in power system protection
schemes. Indeed, the application of earthing is so widespread in electric power systems that at practically every
point therefore, from the generating stations through the transmission lines and substation, to the very points of
utilization, earth connections are made, unfailingly.
Two major categories of earthing are employed in practice, namely, neutral or mains earthing, and
equipment or general earthing as discussed below:
II. Isolated Neutral System
The isolated neutral system is as shown in fig 1 below. With balanced voltages applied to such a line,
the capacitive current will be equal in magnitude. Suppose an earth-fault occurs on one of the conductors, say
line B. there will be capacitance current flow between the line B and earth. And, the voltage across the other two
phases will rise to line voltage values (e.g VRN -√3 VRN.
As shown
Fig 1: Isolated Neutral system and fig. 2. Capacitive currents due
line-to-earth capacitances. to line-to-earth fault at „X‟ on line B
Understanding the Concept of Earthing In Electric Power System Engineering
DOI: 10.9790/1676-1103032933 www.iosrjournals.org 30 | Page
As shown in figure 2; the fault on line B feeds the currents ICGR and ICGY. These being capacitive
currents, no current flows when the line-to-earth capacitance is fully charged. Therefore, arcing occurs at the
faulted point “X” during which period the line capacitance is discharged and capacitive current flow resumes.
The cycle of charging and discharging is repeated as long as the fault remains causing intermittent arcing at the
point of fault and giving rise to abnormally high voltages across the health phases. Ultimately, the aftermath of
this capacitive effect is the damage done to system insulation and consumer‟s appliances especially where
proper over-voltage protection is not provided. Hence, isolated neutral system is not being adopted in practice.
III. Neutral Earthling
Neutral or mains ear thing is the category of ear thing that involves the connection of the star neutral
point of power system lines and apparatus to the general mass of the earth. The two main method of neutral ear
thing are shown below:
IV. Solid Or Effectively- Grounded Earthling
In this method a direct metallic connection is made between the system neutral and the ground (see fig.
3). The ground electrode resistance will have to be very small (usually less than 1 ohm)
Fig 3 Solidly earth star point Fig. 4 Capacitive currents due
And the line-to-earth capacitances to line-to-earth fault on line
Under balanced voltage conditions and perfectly transposed line conductors, the phase-to-ground
capacitive currents will, all the same, be equal and 120o
apart. The star point of the capacitances will be at
ground potential, hence no current flows between the capacitances and the neutral or star point.
Suppose now that a ground point „X‟ (ie. VBN = 0). The ground fault current will consist of two
components, namely; IFBG which flows into the system star point and ICBG which flows into the capacitance star
point. Comparatively, IFBC is a much larger current than ICBG.
The potentials VRN and VYN during the fault and before fault remain the same because the star point or
neutral is not displaced from the ground potential.
Advantages of solid earthing
(i) There is no abnormal voltage rise on the other healthy phases, hence no voltage stress on the system
insulation
(ii) The use of graded insulation is permitted meaning additional savings is power transformers of 132KV and
above.
Disadvantage of solid earthing
(i) On overhead transmission lines, a majority of the faults are to be ground. Thus the number of severe shocks
to the system is relatively much greater than with resistance or reactance grounding.
(ii) The increased ground fault currents affect neighboring telecommunication circuit.
Appraisal
Most of the adverse effects are overcome by the use of high rupturing capacity, high speed circuit breakers and
fast acting protective relays. Therefore, solid earthy for the neutral of power system is being adopted in practice.
Resistance Ear thing
This is one form of impedance ear thing and introduced when it becomes necessary to limit the earth fault
current. The resistance employed may be a solid metallic resistor or a liquid resistor. (Eg. Caustic soda
Understanding the Concept of Earthing In Electric Power System Engineering
DOI: 10.9790/1676-1103032933 www.iosrjournals.org 31 | Page
electrolyte) or (a metallic resistor in transformer oil). The ear thing resistance is connected between the neutral
or star point (N) and the ground (see fig 5)
Fig 5: Resistance Earthing and Fig 6: Capacitance current due to
line –to-earth capacitances line-to-earth faults.
Assume an earth-fault, as usual, at point „X‟ on line B. The magnitude and phase relationship of the
fault current IFBG depends on the relative values of the zero sequence reactance of the power source and the
ohmic value of the earthing resistance. IFBG can be resolved into the components, namely IFBG (0) (not shown ) in
phase with VBN and IFBG (90o
) (not shown ) lagging VBN by 90o
. Furthermore, the choice of the ohmic value of
Rg affects the power dissipation in Rg itself. The common practice is to choose a value of Rg that will limit the
fault current IFBG to the full rating of the full load of the largest generator or transformer in the system.
Therefore, the value of Rg is given by, Rg = VPH / I where: Rg → resistance in ohms: VPH → line-to-neutral
voltage in volts; I → full load current in amperes of largest generator or transformer.
Major Advantages of Resistance Earthing
(i) It permits the use of discriminative protection and control gear.
(ii) Interference with adjoining communication circuits is avoided.
Major Disadvantages of Resistance Earthing
(i) The system neutral will almost invariably be fully displaced in the cases of ground faults, thus necessitating
the use of 100% lightning arresters at an increased cost.
(ii) Graded insulation cannot be used, hence, cost of transformers increases.
Appraisal
(i) Resistance earthing, where it is used, is limited to system voltages of 33KV and below and when the total
system capacity does not exceed 5000 K VA( NORONHA, 1988).
(ii)
V. Reactance Earthling
This is another form of impedance earthing and is also referred to as “Peterson Coil earthing”. The
practice here is the inclusion of a coil in the system neutral such that the reactance current (IFBG) due to the coil
exactly neutralize the network capacitance current (ICBG) at the faulted point „X‟
In actual practice, however, there will always be a small residual current present in the faulted phase
due to the effect of resistance in the arc suppression coil, though too small to maintain an arc.
Fig. 7 Reactance Earthing Fig 8 Capacitance currents due to
And line-to-earth capacitance to line-to earth fault
Equipment Earthing
Understanding the Concept of Earthing In Electric Power System Engineering
DOI: 10.9790/1676-1103032933 www.iosrjournals.org 32 | Page
Equipment (or general ) earthing has to with the earthing or grounding of all the non-current-carrying
metal parts of lines and apparatus used in supply systems and equipment employed in the utilization of electrical
energy as completely different from neutral earthing.
Objects Of Equipment Earthing
The objects of equipment earthing include the following:
(i) To provide protection to plant and personnel from danger due to accidental grounding of live parts of
equipment.
(ii) To cordon off the zone of dead line working to make it safe during working to prevent electrostatic and
electromagnetic induction and also accidental contact from other energized lines and apparatus.
Methods Of Equipment Earthing
This is always done by the method of effective or solid earthing of parts concerned, including: the
frames of generators, reactors, motors; tanks of transformer, circuit breakers, ring main units, enclosures of
magnetic starters, distribution boards, switch-fuses; bodies of domestic appliances like electric cookers, pressing
irons, electric heaters, etc.
General Code Of Practice
It is worthy to give a space, no matter how small, for a discussion of the general code of practice as
affecting earthing in this paper. The subheadings that follow cover those necessary specifications that constitute
the practical approach to earthing generally.
Selection Of Earthing Materials
Materials for the earthing conductor should have (a) high conductivity (b) low rate of corrosion by soil,
and (c) low rate of corrosion due to galvanic action. Hence, copper finds application here since it fulfils all these
requirements. The second best material, at any rate, is galvanized steel.
Size Of The Earthing Conductor
The size of conductor chosen for earthing should be such as would ascertain (i) the thermal stability of
the conductor to earth-fault current, (ii) its mechanical strength, (iii) its durability (for several years) without
causing a break in the grounding circuit due to corrosion (iv) sufficient conductivity so that it does not
contribute substantially to local potential gradient.
The IEE Regulations stipulate that the cross-sectional area of the earthing lead (ie the final conductor
by which the connection to the earth electrode, or other means of erathing is made), if copper, shall not be less
than: 6mm2
for the largest associated copper circuit conductors of 10 to 16mm2
for the largest associated copper
circuit conductors of 25 to 50mm2
; 50mm2
for those of 70 to 150mm2
; and 70mm2
for those of 185 to 630mm2
.
They must be stranded.
Values Of Earth Electrode Resistance
The earth (electrode) resistance should not be more than 5 ohms generally. However, for better
performance at power houses and at substations, its value should be 0.5 ohm and 1.00 ohm, receptively (UPPAL
& LAROIA, 1981). Carbon dust, common salt and water are often used to improve earth resistance.
Burying The Earth Electrode
The earth electrode, if the rod type, is driven vertically into the ground at about 1.5m from the wall of
the building or equipment to be earthed and to a minimum depth of 0.5m and as damp an area or position as
possible. Extension lengths preferably with 70mm2
bare copper may be provided for further depth penetration.
Basic Earth-Test Requirement
The basic earth test is to ascertain that the main protective devices will operate if the value of the earth-
fault current exceeds: (i) 3 x the current of semi-enclosed fuse or any cartridge fuse having a fusing factor of
more than 1:5; or (ii) 2.4 x the rating of the cartridge fusing factor of 1.5 or less; or (iii) 1.5 x tripping current of
the overload circuit breaker.
VI. Conclusion and Recommendation
In power systems engineering, solid or effective earthing is the most commonly adopted method of
earthing, working best with very low earth electrode resistance. The difficulty and cost of realizing acceptably
low earth electrode resistance cannot be over-emphasized, especially in arid areas. But the advent of chem.-rode
in recent times has made the practice a let easier and interesting.
Understanding the Concept of Earthing In Electric Power System Engineering
DOI: 10.9790/1676-1103032933 www.iosrjournals.org 33 | Page
Chem.-rod it an ultra-efficient low surge-impedance chemically-activated grounding electrode. It
continually conditions the surrounding soil, making the soil more conductive than otherwise. With a diameter of
64.3mm, meaning greater surface area and greater contact with earth, one chem.-rod ahs the equivalent
performance of 15 to 20 conventional earthing rods (LEC, 1995). Therefore, its immense usefulness cannot but
be taken due advantages of.
It is rather appalling to observe in most residential and commercial premises that the earthing lead is
never checked for continuity to the rod and nothing is ever done to improve the earth resistance after several
years since installations. Hence, the reason for the several cases of electric shock from refrigerator, deep freezer/
electric pressing irons, electric cookers, kettles, grinders, etc in these premises is not far-fetched. We also see
why noise signal which are supposed to be drained off public address amplifiers through proper earthing remain
to introduce noise into system thus vitiating the system performance at many programmes held in such areas.
The author is particularly concerned about the electric shock hazard. Wherefore it is recommended here that:
1 BEDC(Benin electricity distribution company) meter reader should be made to also inspect the earthing
lead to ascertain its continuity to the rod. Where it is found discontinued, the affected premises should be
disconnected from power supply immediately until the customer makes good the same. This presupposes
that the current practice of bill estimation by BEDC should be discontinued. BEDC meter readers must visit
the premises of customers physically to performs this and other duties
2 Periodic measurement of the earth resistance, say, every 6 month-January (dry season) and July (wet
season) – to ascertain the value of the electrode resistance to earth should also be carried out by the BEDC
meter reader or other official with portable earthing resistance tester. It therefore means that a test point or
head with earth-rod extension lead (of 70mm2 stranded copper, as earlier mentioned) must be made
available and accessible at the customer‟s premises close to the meter area. Where the measured values are
poor, the customer should be advised to improve the same, failing which the affected premised should be
cut off from the general power supply. Apart from common salt, other chemical like magnesium sulfate,
copper sulfate and calcium chloride can be used for each resistance improvement (IEEE std., 1976)
3 Every 3 years of 5 (at most) the main conventional earth electrode should be brought out and maintained (or
changed with the clamps as the case may be) reburied properly
4 The use of Che-Rods should be greatly encouraged every where.
References
[1]. FRANCIS T.G (1971), Electrical Installation Work, Longman Group LTD, London
[2]. IEE (1981), Regulation For Electrical Installation, McKay & Co. United Kingdom
[3]. IEEE Std (1976), Recommended Practice for Electric Power Distribution for Industrial Plants, IEEE Publication, London.
[4]. LIGHTNING ELIMINATORS & CONSULTANTS (L.E.C) – 1995, Spline Ball Ionizer & Chem-Rod, An In-House Publication,
Boulder, Colorade 80303
[5]. NORONHA L.C. (1988), Earthing, An In-house NEPA Publication, Lagos
[6]. NATIONAL ELECTRICA POWER AUTHORITY (1977), Electricity Distribution Manual, An IN-house publication, Lagos
[7]. ROEHELE et al (1988) Switching Manual, Area Brown Beveri Publication, Germany
[8]. UPPAL & LAROIA (1981) Electrical Wiring, Estimating and Costing Khana Publication, Naisarak, Delhi-6

More Related Content

What's hot

Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
YogeshIJTSRD
 
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
International Journal of Power Electronics and Drive Systems
 
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
International Journal of Power Electronics and Drive Systems
 
H1103034350
H1103034350H1103034350
H1103034350
IOSR Journals
 
SIX PHASE TRANSMISSION SYSTEM REPORT
SIX PHASE TRANSMISSION SYSTEM REPORTSIX PHASE TRANSMISSION SYSTEM REPORT
SIX PHASE TRANSMISSION SYSTEM REPORT
S Naibedya Lalatendu
 
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
International Journal of Power Electronics and Drive Systems
 
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
IAES-IJPEDS
 
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
IJERA Editor
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD Editor
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET Journal
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
journalBEEI
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
Alexander Decker
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
researchinventy
 
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation SystemHigh Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
IJRES Journal
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
IJERD Editor
 
M0104198105
M0104198105M0104198105
M0104198105
IOSR Journals
 
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source NetworkWind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
International Journal of Power Electronics and Drive Systems
 
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
imtiyazsayyed
 
Solid state transformer ppt
Solid state transformer pptSolid state transformer ppt
Solid state transformer ppt
AKHILASS
 

What's hot (19)

Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
Analysis and Simulation of Solar PV Connected with Grid Accomplished with Boo...
 
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
Asymmetrical four-wire cascaded h-bridge multi-level inverter based shunt act...
 
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
A Grid-Connected Photovoltaic Interface System for Delivering Active and Reac...
 
H1103034350
H1103034350H1103034350
H1103034350
 
SIX PHASE TRANSMISSION SYSTEM REPORT
SIX PHASE TRANSMISSION SYSTEM REPORTSIX PHASE TRANSMISSION SYSTEM REPORT
SIX PHASE TRANSMISSION SYSTEM REPORT
 
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
 
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
Hysteresis SVM for Coupled Inductor Z Source Diode Clamped 3-Level Inverter B...
 
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
Enhancement in Power Quality With Grid Interconnection of Renewable Energy So...
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
 
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...6.[36 45]seven level modified cascaded inverter for induction motor drive app...
6.[36 45]seven level modified cascaded inverter for induction motor drive app...
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation SystemHigh Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
M0104198105
M0104198105M0104198105
M0104198105
 
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source NetworkWind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
Wind-PV Hybrid Energy Source Fed Three Level NPC with Quasi Z Source Network
 
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
Multilevel Voltage Source Inverter for Grid Connected Photovoltaic System
 
Solid state transformer ppt
Solid state transformer pptSolid state transformer ppt
Solid state transformer ppt
 

Viewers also liked

I1303056370
I1303056370I1303056370
I1303056370
IOSR Journals
 
Modeling and qualitative analysis of malaria epidemiology
Modeling and qualitative analysis of malaria epidemiologyModeling and qualitative analysis of malaria epidemiology
Modeling and qualitative analysis of malaria epidemiology
IOSR Journals
 
Efficient Design of Transceiver for Wireless Body Area Networks
Efficient Design of Transceiver for Wireless Body Area NetworksEfficient Design of Transceiver for Wireless Body Area Networks
Efficient Design of Transceiver for Wireless Body Area Networks
IOSR Journals
 
Efficient design of feedforward network for pattern classification
Efficient design of feedforward network for pattern classificationEfficient design of feedforward network for pattern classification
Efficient design of feedforward network for pattern classification
IOSR Journals
 
B0160709
B0160709B0160709
B0160709
IOSR Journals
 
F0213137
F0213137F0213137
F0213137
IOSR Journals
 
F0153236
F0153236F0153236
F0153236
IOSR Journals
 
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
IOSR Journals
 
D010512129
D010512129D010512129
D010512129
IOSR Journals
 
E017322833
E017322833E017322833
E017322833
IOSR Journals
 
C1802050815
C1802050815C1802050815
C1802050815
IOSR Journals
 
Rainy and Dry Days as a Stochastic Process (Albaha City)
Rainy and Dry Days as a Stochastic Process (Albaha City)Rainy and Dry Days as a Stochastic Process (Albaha City)
Rainy and Dry Days as a Stochastic Process (Albaha City)
IOSR Journals
 
C018141418
C018141418C018141418
C018141418
IOSR Journals
 
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
IOSR Journals
 
L1302037480
L1302037480L1302037480
L1302037480
IOSR Journals
 
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
IOSR Journals
 
A017160104
A017160104A017160104
A017160104
IOSR Journals
 
C013151420
C013151420C013151420
C013151420
IOSR Journals
 
L012648389
L012648389L012648389
L012648389
IOSR Journals
 
I012636670
I012636670I012636670
I012636670
IOSR Journals
 

Viewers also liked (20)

I1303056370
I1303056370I1303056370
I1303056370
 
Modeling and qualitative analysis of malaria epidemiology
Modeling and qualitative analysis of malaria epidemiologyModeling and qualitative analysis of malaria epidemiology
Modeling and qualitative analysis of malaria epidemiology
 
Efficient Design of Transceiver for Wireless Body Area Networks
Efficient Design of Transceiver for Wireless Body Area NetworksEfficient Design of Transceiver for Wireless Body Area Networks
Efficient Design of Transceiver for Wireless Body Area Networks
 
Efficient design of feedforward network for pattern classification
Efficient design of feedforward network for pattern classificationEfficient design of feedforward network for pattern classification
Efficient design of feedforward network for pattern classification
 
B0160709
B0160709B0160709
B0160709
 
F0213137
F0213137F0213137
F0213137
 
F0153236
F0153236F0153236
F0153236
 
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
Longitudinal Skeleton Dimensionality Characteristics of Nigerian Junior Male ...
 
D010512129
D010512129D010512129
D010512129
 
E017322833
E017322833E017322833
E017322833
 
C1802050815
C1802050815C1802050815
C1802050815
 
Rainy and Dry Days as a Stochastic Process (Albaha City)
Rainy and Dry Days as a Stochastic Process (Albaha City)Rainy and Dry Days as a Stochastic Process (Albaha City)
Rainy and Dry Days as a Stochastic Process (Albaha City)
 
C018141418
C018141418C018141418
C018141418
 
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
A study of serum Cadmium and lead in Iraqi postmenopausal women with osteopor...
 
L1302037480
L1302037480L1302037480
L1302037480
 
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
Comparison of 60GHz CSRRs Ground Shield and Patterned Ground Shield On-chip B...
 
A017160104
A017160104A017160104
A017160104
 
C013151420
C013151420C013151420
C013151420
 
L012648389
L012648389L012648389
L012648389
 
I012636670
I012636670I012636670
I012636670
 

Similar to E1103032933

Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
Asad Hussain
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
Muhammad Zaeem Sarfraz
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
jawaharramaya
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
Biswajit Pratihari
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iii
ILDTECH
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
MuhammedArifTanoli
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
Vishwanath Prasad Kurmi
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
Mahesh Chandra Manav
 
Study on grounding system and safety practices
Study on grounding system and safety practicesStudy on grounding system and safety practices
Study on grounding system and safety practices
Faiz Mangalassery
 
Arrester
ArresterArrester
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
Mahesh Chandra Manav
 
EE6701 - HVE
EE6701 - HVEEE6701 - HVE
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
SuhailAbdul2
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral Grounding
Noman Nomi
 
Chapter8 emc
Chapter8 emcChapter8 emc
Chapter8 emc
Vin Voro
 
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKSPARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
International Journal of Technical Research & Application
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
marwadi
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
Bruno De Wachter
 
Earthing
EarthingEarthing
Earthing
Adityareader
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
Eduardo Higino
 

Similar to E1103032933 (20)

Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iii
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
Study on grounding system and safety practices
Study on grounding system and safety practicesStudy on grounding system and safety practices
Study on grounding system and safety practices
 
Arrester
ArresterArrester
Arrester
 
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
 
EE6701 - HVE
EE6701 - HVEEE6701 - HVE
EE6701 - HVE
 
Earthing and grounding.pptx
Earthing and grounding.pptxEarthing and grounding.pptx
Earthing and grounding.pptx
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral Grounding
 
Chapter8 emc
Chapter8 emcChapter8 emc
Chapter8 emc
 
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKSPARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 
Earthing
EarthingEarthing
Earthing
 
Schneider electric : Neutral Earthing
Schneider electric : Neutral EarthingSchneider electric : Neutral Earthing
Schneider electric : Neutral Earthing
 

More from IOSR Journals

A011140104
A011140104A011140104
A011140104
IOSR Journals
 
M0111397100
M0111397100M0111397100
M0111397100
IOSR Journals
 
L011138596
L011138596L011138596
L011138596
IOSR Journals
 
K011138084
K011138084K011138084
K011138084
IOSR Journals
 
J011137479
J011137479J011137479
J011137479
IOSR Journals
 
I011136673
I011136673I011136673
I011136673
IOSR Journals
 
G011134454
G011134454G011134454
G011134454
IOSR Journals
 
H011135565
H011135565H011135565
H011135565
IOSR Journals
 
F011134043
F011134043F011134043
F011134043
IOSR Journals
 
E011133639
E011133639E011133639
E011133639
IOSR Journals
 
D011132635
D011132635D011132635
D011132635
IOSR Journals
 
C011131925
C011131925C011131925
C011131925
IOSR Journals
 
B011130918
B011130918B011130918
B011130918
IOSR Journals
 
A011130108
A011130108A011130108
A011130108
IOSR Journals
 
I011125160
I011125160I011125160
I011125160
IOSR Journals
 
H011124050
H011124050H011124050
H011124050
IOSR Journals
 
G011123539
G011123539G011123539
G011123539
IOSR Journals
 
F011123134
F011123134F011123134
F011123134
IOSR Journals
 
E011122530
E011122530E011122530
E011122530
IOSR Journals
 
D011121524
D011121524D011121524
D011121524
IOSR Journals
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

How to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For FlutterHow to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For Flutter
Daiki Mogmet Ito
 
UiPath Test Automation using UiPath Test Suite series, part 5
UiPath Test Automation using UiPath Test Suite series, part 5UiPath Test Automation using UiPath Test Suite series, part 5
UiPath Test Automation using UiPath Test Suite series, part 5
DianaGray10
 
Large Language Model (LLM) and it’s Geospatial Applications
Large Language Model (LLM) and it’s Geospatial ApplicationsLarge Language Model (LLM) and it’s Geospatial Applications
Large Language Model (LLM) and it’s Geospatial Applications
Rohit Gautam
 
Full-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalizationFull-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalization
Zilliz
 
Artificial Intelligence for XMLDevelopment
Artificial Intelligence for XMLDevelopmentArtificial Intelligence for XMLDevelopment
Artificial Intelligence for XMLDevelopment
Octavian Nadolu
 
TrustArc Webinar - 2024 Global Privacy Survey
TrustArc Webinar - 2024 Global Privacy SurveyTrustArc Webinar - 2024 Global Privacy Survey
TrustArc Webinar - 2024 Global Privacy Survey
TrustArc
 
Securing your Kubernetes cluster_ a step-by-step guide to success !
Securing your Kubernetes cluster_ a step-by-step guide to success !Securing your Kubernetes cluster_ a step-by-step guide to success !
Securing your Kubernetes cluster_ a step-by-step guide to success !
KatiaHIMEUR1
 
Pushing the limits of ePRTC: 100ns holdover for 100 days
Pushing the limits of ePRTC: 100ns holdover for 100 daysPushing the limits of ePRTC: 100ns holdover for 100 days
Pushing the limits of ePRTC: 100ns holdover for 100 days
Adtran
 
RESUME BUILDER APPLICATION Project for students
RESUME BUILDER APPLICATION Project for studentsRESUME BUILDER APPLICATION Project for students
RESUME BUILDER APPLICATION Project for students
KAMESHS29
 
How to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptxHow to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptx
danishmna97
 
Presentation of the OECD Artificial Intelligence Review of Germany
Presentation of the OECD Artificial Intelligence Review of GermanyPresentation of the OECD Artificial Intelligence Review of Germany
Presentation of the OECD Artificial Intelligence Review of Germany
innovationoecd
 
20 Comprehensive Checklist of Designing and Developing a Website
20 Comprehensive Checklist of Designing and Developing a Website20 Comprehensive Checklist of Designing and Developing a Website
20 Comprehensive Checklist of Designing and Developing a Website
Pixlogix Infotech
 
Monitoring Java Application Security with JDK Tools and JFR Events
Monitoring Java Application Security with JDK Tools and JFR EventsMonitoring Java Application Security with JDK Tools and JFR Events
Monitoring Java Application Security with JDK Tools and JFR Events
Ana-Maria Mihalceanu
 
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
Albert Hoitingh
 
UiPath Test Automation using UiPath Test Suite series, part 6
UiPath Test Automation using UiPath Test Suite series, part 6UiPath Test Automation using UiPath Test Suite series, part 6
UiPath Test Automation using UiPath Test Suite series, part 6
DianaGray10
 
20240605 QFM017 Machine Intelligence Reading List May 2024
20240605 QFM017 Machine Intelligence Reading List May 202420240605 QFM017 Machine Intelligence Reading List May 2024
20240605 QFM017 Machine Intelligence Reading List May 2024
Matthew Sinclair
 
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
名前 です男
 
National Security Agency - NSA mobile device best practices
National Security Agency - NSA mobile device best practicesNational Security Agency - NSA mobile device best practices
National Security Agency - NSA mobile device best practices
Quotidiano Piemontese
 
A tale of scale & speed: How the US Navy is enabling software delivery from l...
A tale of scale & speed: How the US Navy is enabling software delivery from l...A tale of scale & speed: How the US Navy is enabling software delivery from l...
A tale of scale & speed: How the US Navy is enabling software delivery from l...
sonjaschweigert1
 
Generative AI Deep Dive: Advancing from Proof of Concept to Production
Generative AI Deep Dive: Advancing from Proof of Concept to ProductionGenerative AI Deep Dive: Advancing from Proof of Concept to Production
Generative AI Deep Dive: Advancing from Proof of Concept to Production
Aggregage
 

Recently uploaded (20)

How to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For FlutterHow to use Firebase Data Connect For Flutter
How to use Firebase Data Connect For Flutter
 
UiPath Test Automation using UiPath Test Suite series, part 5
UiPath Test Automation using UiPath Test Suite series, part 5UiPath Test Automation using UiPath Test Suite series, part 5
UiPath Test Automation using UiPath Test Suite series, part 5
 
Large Language Model (LLM) and it’s Geospatial Applications
Large Language Model (LLM) and it’s Geospatial ApplicationsLarge Language Model (LLM) and it’s Geospatial Applications
Large Language Model (LLM) and it’s Geospatial Applications
 
Full-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalizationFull-RAG: A modern architecture for hyper-personalization
Full-RAG: A modern architecture for hyper-personalization
 
Artificial Intelligence for XMLDevelopment
Artificial Intelligence for XMLDevelopmentArtificial Intelligence for XMLDevelopment
Artificial Intelligence for XMLDevelopment
 
TrustArc Webinar - 2024 Global Privacy Survey
TrustArc Webinar - 2024 Global Privacy SurveyTrustArc Webinar - 2024 Global Privacy Survey
TrustArc Webinar - 2024 Global Privacy Survey
 
Securing your Kubernetes cluster_ a step-by-step guide to success !
Securing your Kubernetes cluster_ a step-by-step guide to success !Securing your Kubernetes cluster_ a step-by-step guide to success !
Securing your Kubernetes cluster_ a step-by-step guide to success !
 
Pushing the limits of ePRTC: 100ns holdover for 100 days
Pushing the limits of ePRTC: 100ns holdover for 100 daysPushing the limits of ePRTC: 100ns holdover for 100 days
Pushing the limits of ePRTC: 100ns holdover for 100 days
 
RESUME BUILDER APPLICATION Project for students
RESUME BUILDER APPLICATION Project for studentsRESUME BUILDER APPLICATION Project for students
RESUME BUILDER APPLICATION Project for students
 
How to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptxHow to Get CNIC Information System with Paksim Ga.pptx
How to Get CNIC Information System with Paksim Ga.pptx
 
Presentation of the OECD Artificial Intelligence Review of Germany
Presentation of the OECD Artificial Intelligence Review of GermanyPresentation of the OECD Artificial Intelligence Review of Germany
Presentation of the OECD Artificial Intelligence Review of Germany
 
20 Comprehensive Checklist of Designing and Developing a Website
20 Comprehensive Checklist of Designing and Developing a Website20 Comprehensive Checklist of Designing and Developing a Website
20 Comprehensive Checklist of Designing and Developing a Website
 
Monitoring Java Application Security with JDK Tools and JFR Events
Monitoring Java Application Security with JDK Tools and JFR EventsMonitoring Java Application Security with JDK Tools and JFR Events
Monitoring Java Application Security with JDK Tools and JFR Events
 
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
Encryption in Microsoft 365 - ExpertsLive Netherlands 2024
 
UiPath Test Automation using UiPath Test Suite series, part 6
UiPath Test Automation using UiPath Test Suite series, part 6UiPath Test Automation using UiPath Test Suite series, part 6
UiPath Test Automation using UiPath Test Suite series, part 6
 
20240605 QFM017 Machine Intelligence Reading List May 2024
20240605 QFM017 Machine Intelligence Reading List May 202420240605 QFM017 Machine Intelligence Reading List May 2024
20240605 QFM017 Machine Intelligence Reading List May 2024
 
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
みなさんこんにちはこれ何文字まで入るの?40文字以下不可とか本当に意味わからないけどこれ限界文字数書いてないからマジでやばい文字数いけるんじゃないの?えこ...
 
National Security Agency - NSA mobile device best practices
National Security Agency - NSA mobile device best practicesNational Security Agency - NSA mobile device best practices
National Security Agency - NSA mobile device best practices
 
A tale of scale & speed: How the US Navy is enabling software delivery from l...
A tale of scale & speed: How the US Navy is enabling software delivery from l...A tale of scale & speed: How the US Navy is enabling software delivery from l...
A tale of scale & speed: How the US Navy is enabling software delivery from l...
 
Generative AI Deep Dive: Advancing from Proof of Concept to Production
Generative AI Deep Dive: Advancing from Proof of Concept to ProductionGenerative AI Deep Dive: Advancing from Proof of Concept to Production
Generative AI Deep Dive: Advancing from Proof of Concept to Production
 

E1103032933

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 3 Ver. III (May. – Jun. 2016), PP 29-33 www.iosrjournals.org DOI: 10.9790/1676-1103032933 www.iosrjournals.org 29 | Page Understanding the Concept of Earthing In Electric Power System Engineering Ajayi,A1 Jerome,D.K2 , Osayi F.S3 and Izugie F.I4 1,2,3 Department of Electrical and Electronic Engineering, Auchi Polytechnic, Auchi Edo state Nigeria Abstract: Earthing is the concept of connecting a thing to the earth (or ground). In Power systems, engineering, ear thing is the one concept that cannot be dispensed with. Generators, reactors and transformers have to be earthed at their star or neutral point for proper operation and application of earth-fault relays; for the realization of single phase voltage supply (in the case of transformers); and for the drainage (as much as possible) of the harmonic voltages that cause distortions in system voltages. Furthermore, the metallic enclosure and non-conduction parts of every apparatus requires earthing for the protection of personnel and users from electrical hazards. It is inestimable the quantity and value of lives and properly that would have been lost to electrical faults but for the application of this concept. Thus, in this paper a detailed discussion of system and equipment ear thing is presented. The writer recommend the use of chem.-rods for better ear thing, as well as an appropriate routine earth-point maintenances schedule Keywords: earth-fault relay, neutral point, harmonic voltage I. Introduction Power system engineering is that field of conscious human endeavour in which energy is generated, converted and transmitted (over a long or short distances) for the purpose of distribution and eventual utilization for the benefit of man and beast. In this connection however, it is mechanical energy that is generated in the most cases and converted into electrical energy. The concept of earthing in power system engineering is as old as this field of endeavour itself. It came into play from the age-long fact that the earth is a universal sink. Thus, this concept has to do with a connection to the general mass of earth in such a manner as to ensure immediate drainage of energy into the same without danger and for the avoidance of danger. Therefore, earthing (or grounding as also referred to) features prominently in power system protection schemes. Indeed, the application of earthing is so widespread in electric power systems that at practically every point therefore, from the generating stations through the transmission lines and substation, to the very points of utilization, earth connections are made, unfailingly. Two major categories of earthing are employed in practice, namely, neutral or mains earthing, and equipment or general earthing as discussed below: II. Isolated Neutral System The isolated neutral system is as shown in fig 1 below. With balanced voltages applied to such a line, the capacitive current will be equal in magnitude. Suppose an earth-fault occurs on one of the conductors, say line B. there will be capacitance current flow between the line B and earth. And, the voltage across the other two phases will rise to line voltage values (e.g VRN -√3 VRN. As shown Fig 1: Isolated Neutral system and fig. 2. Capacitive currents due line-to-earth capacitances. to line-to-earth fault at „X‟ on line B
  • 2. Understanding the Concept of Earthing In Electric Power System Engineering DOI: 10.9790/1676-1103032933 www.iosrjournals.org 30 | Page As shown in figure 2; the fault on line B feeds the currents ICGR and ICGY. These being capacitive currents, no current flows when the line-to-earth capacitance is fully charged. Therefore, arcing occurs at the faulted point “X” during which period the line capacitance is discharged and capacitive current flow resumes. The cycle of charging and discharging is repeated as long as the fault remains causing intermittent arcing at the point of fault and giving rise to abnormally high voltages across the health phases. Ultimately, the aftermath of this capacitive effect is the damage done to system insulation and consumer‟s appliances especially where proper over-voltage protection is not provided. Hence, isolated neutral system is not being adopted in practice. III. Neutral Earthling Neutral or mains ear thing is the category of ear thing that involves the connection of the star neutral point of power system lines and apparatus to the general mass of the earth. The two main method of neutral ear thing are shown below: IV. Solid Or Effectively- Grounded Earthling In this method a direct metallic connection is made between the system neutral and the ground (see fig. 3). The ground electrode resistance will have to be very small (usually less than 1 ohm) Fig 3 Solidly earth star point Fig. 4 Capacitive currents due And the line-to-earth capacitances to line-to-earth fault on line Under balanced voltage conditions and perfectly transposed line conductors, the phase-to-ground capacitive currents will, all the same, be equal and 120o apart. The star point of the capacitances will be at ground potential, hence no current flows between the capacitances and the neutral or star point. Suppose now that a ground point „X‟ (ie. VBN = 0). The ground fault current will consist of two components, namely; IFBG which flows into the system star point and ICBG which flows into the capacitance star point. Comparatively, IFBC is a much larger current than ICBG. The potentials VRN and VYN during the fault and before fault remain the same because the star point or neutral is not displaced from the ground potential. Advantages of solid earthing (i) There is no abnormal voltage rise on the other healthy phases, hence no voltage stress on the system insulation (ii) The use of graded insulation is permitted meaning additional savings is power transformers of 132KV and above. Disadvantage of solid earthing (i) On overhead transmission lines, a majority of the faults are to be ground. Thus the number of severe shocks to the system is relatively much greater than with resistance or reactance grounding. (ii) The increased ground fault currents affect neighboring telecommunication circuit. Appraisal Most of the adverse effects are overcome by the use of high rupturing capacity, high speed circuit breakers and fast acting protective relays. Therefore, solid earthy for the neutral of power system is being adopted in practice. Resistance Ear thing This is one form of impedance ear thing and introduced when it becomes necessary to limit the earth fault current. The resistance employed may be a solid metallic resistor or a liquid resistor. (Eg. Caustic soda
  • 3. Understanding the Concept of Earthing In Electric Power System Engineering DOI: 10.9790/1676-1103032933 www.iosrjournals.org 31 | Page electrolyte) or (a metallic resistor in transformer oil). The ear thing resistance is connected between the neutral or star point (N) and the ground (see fig 5) Fig 5: Resistance Earthing and Fig 6: Capacitance current due to line –to-earth capacitances line-to-earth faults. Assume an earth-fault, as usual, at point „X‟ on line B. The magnitude and phase relationship of the fault current IFBG depends on the relative values of the zero sequence reactance of the power source and the ohmic value of the earthing resistance. IFBG can be resolved into the components, namely IFBG (0) (not shown ) in phase with VBN and IFBG (90o ) (not shown ) lagging VBN by 90o . Furthermore, the choice of the ohmic value of Rg affects the power dissipation in Rg itself. The common practice is to choose a value of Rg that will limit the fault current IFBG to the full rating of the full load of the largest generator or transformer in the system. Therefore, the value of Rg is given by, Rg = VPH / I where: Rg → resistance in ohms: VPH → line-to-neutral voltage in volts; I → full load current in amperes of largest generator or transformer. Major Advantages of Resistance Earthing (i) It permits the use of discriminative protection and control gear. (ii) Interference with adjoining communication circuits is avoided. Major Disadvantages of Resistance Earthing (i) The system neutral will almost invariably be fully displaced in the cases of ground faults, thus necessitating the use of 100% lightning arresters at an increased cost. (ii) Graded insulation cannot be used, hence, cost of transformers increases. Appraisal (i) Resistance earthing, where it is used, is limited to system voltages of 33KV and below and when the total system capacity does not exceed 5000 K VA( NORONHA, 1988). (ii) V. Reactance Earthling This is another form of impedance earthing and is also referred to as “Peterson Coil earthing”. The practice here is the inclusion of a coil in the system neutral such that the reactance current (IFBG) due to the coil exactly neutralize the network capacitance current (ICBG) at the faulted point „X‟ In actual practice, however, there will always be a small residual current present in the faulted phase due to the effect of resistance in the arc suppression coil, though too small to maintain an arc. Fig. 7 Reactance Earthing Fig 8 Capacitance currents due to And line-to-earth capacitance to line-to earth fault Equipment Earthing
  • 4. Understanding the Concept of Earthing In Electric Power System Engineering DOI: 10.9790/1676-1103032933 www.iosrjournals.org 32 | Page Equipment (or general ) earthing has to with the earthing or grounding of all the non-current-carrying metal parts of lines and apparatus used in supply systems and equipment employed in the utilization of electrical energy as completely different from neutral earthing. Objects Of Equipment Earthing The objects of equipment earthing include the following: (i) To provide protection to plant and personnel from danger due to accidental grounding of live parts of equipment. (ii) To cordon off the zone of dead line working to make it safe during working to prevent electrostatic and electromagnetic induction and also accidental contact from other energized lines and apparatus. Methods Of Equipment Earthing This is always done by the method of effective or solid earthing of parts concerned, including: the frames of generators, reactors, motors; tanks of transformer, circuit breakers, ring main units, enclosures of magnetic starters, distribution boards, switch-fuses; bodies of domestic appliances like electric cookers, pressing irons, electric heaters, etc. General Code Of Practice It is worthy to give a space, no matter how small, for a discussion of the general code of practice as affecting earthing in this paper. The subheadings that follow cover those necessary specifications that constitute the practical approach to earthing generally. Selection Of Earthing Materials Materials for the earthing conductor should have (a) high conductivity (b) low rate of corrosion by soil, and (c) low rate of corrosion due to galvanic action. Hence, copper finds application here since it fulfils all these requirements. The second best material, at any rate, is galvanized steel. Size Of The Earthing Conductor The size of conductor chosen for earthing should be such as would ascertain (i) the thermal stability of the conductor to earth-fault current, (ii) its mechanical strength, (iii) its durability (for several years) without causing a break in the grounding circuit due to corrosion (iv) sufficient conductivity so that it does not contribute substantially to local potential gradient. The IEE Regulations stipulate that the cross-sectional area of the earthing lead (ie the final conductor by which the connection to the earth electrode, or other means of erathing is made), if copper, shall not be less than: 6mm2 for the largest associated copper circuit conductors of 10 to 16mm2 for the largest associated copper circuit conductors of 25 to 50mm2 ; 50mm2 for those of 70 to 150mm2 ; and 70mm2 for those of 185 to 630mm2 . They must be stranded. Values Of Earth Electrode Resistance The earth (electrode) resistance should not be more than 5 ohms generally. However, for better performance at power houses and at substations, its value should be 0.5 ohm and 1.00 ohm, receptively (UPPAL & LAROIA, 1981). Carbon dust, common salt and water are often used to improve earth resistance. Burying The Earth Electrode The earth electrode, if the rod type, is driven vertically into the ground at about 1.5m from the wall of the building or equipment to be earthed and to a minimum depth of 0.5m and as damp an area or position as possible. Extension lengths preferably with 70mm2 bare copper may be provided for further depth penetration. Basic Earth-Test Requirement The basic earth test is to ascertain that the main protective devices will operate if the value of the earth- fault current exceeds: (i) 3 x the current of semi-enclosed fuse or any cartridge fuse having a fusing factor of more than 1:5; or (ii) 2.4 x the rating of the cartridge fusing factor of 1.5 or less; or (iii) 1.5 x tripping current of the overload circuit breaker. VI. Conclusion and Recommendation In power systems engineering, solid or effective earthing is the most commonly adopted method of earthing, working best with very low earth electrode resistance. The difficulty and cost of realizing acceptably low earth electrode resistance cannot be over-emphasized, especially in arid areas. But the advent of chem.-rode in recent times has made the practice a let easier and interesting.
  • 5. Understanding the Concept of Earthing In Electric Power System Engineering DOI: 10.9790/1676-1103032933 www.iosrjournals.org 33 | Page Chem.-rod it an ultra-efficient low surge-impedance chemically-activated grounding electrode. It continually conditions the surrounding soil, making the soil more conductive than otherwise. With a diameter of 64.3mm, meaning greater surface area and greater contact with earth, one chem.-rod ahs the equivalent performance of 15 to 20 conventional earthing rods (LEC, 1995). Therefore, its immense usefulness cannot but be taken due advantages of. It is rather appalling to observe in most residential and commercial premises that the earthing lead is never checked for continuity to the rod and nothing is ever done to improve the earth resistance after several years since installations. Hence, the reason for the several cases of electric shock from refrigerator, deep freezer/ electric pressing irons, electric cookers, kettles, grinders, etc in these premises is not far-fetched. We also see why noise signal which are supposed to be drained off public address amplifiers through proper earthing remain to introduce noise into system thus vitiating the system performance at many programmes held in such areas. The author is particularly concerned about the electric shock hazard. Wherefore it is recommended here that: 1 BEDC(Benin electricity distribution company) meter reader should be made to also inspect the earthing lead to ascertain its continuity to the rod. Where it is found discontinued, the affected premises should be disconnected from power supply immediately until the customer makes good the same. This presupposes that the current practice of bill estimation by BEDC should be discontinued. BEDC meter readers must visit the premises of customers physically to performs this and other duties 2 Periodic measurement of the earth resistance, say, every 6 month-January (dry season) and July (wet season) – to ascertain the value of the electrode resistance to earth should also be carried out by the BEDC meter reader or other official with portable earthing resistance tester. It therefore means that a test point or head with earth-rod extension lead (of 70mm2 stranded copper, as earlier mentioned) must be made available and accessible at the customer‟s premises close to the meter area. Where the measured values are poor, the customer should be advised to improve the same, failing which the affected premised should be cut off from the general power supply. Apart from common salt, other chemical like magnesium sulfate, copper sulfate and calcium chloride can be used for each resistance improvement (IEEE std., 1976) 3 Every 3 years of 5 (at most) the main conventional earth electrode should be brought out and maintained (or changed with the clamps as the case may be) reburied properly 4 The use of Che-Rods should be greatly encouraged every where. References [1]. FRANCIS T.G (1971), Electrical Installation Work, Longman Group LTD, London [2]. IEE (1981), Regulation For Electrical Installation, McKay & Co. United Kingdom [3]. IEEE Std (1976), Recommended Practice for Electric Power Distribution for Industrial Plants, IEEE Publication, London. [4]. LIGHTNING ELIMINATORS & CONSULTANTS (L.E.C) – 1995, Spline Ball Ionizer & Chem-Rod, An In-House Publication, Boulder, Colorade 80303 [5]. NORONHA L.C. (1988), Earthing, An In-house NEPA Publication, Lagos [6]. NATIONAL ELECTRICA POWER AUTHORITY (1977), Electricity Distribution Manual, An IN-house publication, Lagos [7]. ROEHELE et al (1988) Switching Manual, Area Brown Beveri Publication, Germany [8]. UPPAL & LAROIA (1981) Electrical Wiring, Estimating and Costing Khana Publication, Naisarak, Delhi-6