DYNAMIC ANALYSIS OF TALL BUILDING LOCATED IN DIFFERENT
SEISMIC ZONES WITH CENTRAL SHEAR WALL AND DIAGONAL
BRACINGS BY USING E-TABS SOFTWARE
MANJULA1, VEERESHAIAH H M2, PAVAN KUMAR M 3 BASAVALINGAPPA 4
1PG Scholar, Department of Civil Engineering, RYMEC, Ballari
2,3,4Assistant Professors, Department of Civil Engineering, RYMEC, Ballari
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - Since land prices are rising quickly and
there is a shortage of available land, tall buildings are
preferred in order to preserve agricultural land inruralareas.
The main factors influencing tall building designarewindand
seismic loads. In the current study, tall buildings were
examined in all seismic zones using ETABS 2017 software
under the influence of seismic loads with a central shear wall
and diagonal bracings, andtheresultswereanalysedusingthe
response spectrum method. In addition, the configurations'
story displacement, story drift, and base shear at foundations
were compared to the seismic parameters derived from the
analysis.
1. INTRODUCTION
Tall buildingsvarydependingonthe environmentin
question. It will be simple to say that a four story building in
a neighborhood of bungalows isa tall building,andthisclaim
will be uncontested. It's comparable to a one-eyed man
ruling a land of the blind.
The construction boom in metro areasoverthepast
20 years has significantly altered the skyline of Indian cities.
The fanciest skyscrapers, home to some of the wealthiest
people in the nation, are now dotted throughout areas that
were previously dominated by low-rise residential
compounds. An approximate count places Kolkata second
with 12 skyscrapers, followed by Mumbai with over 50. The
tallest buildings in India that are currently operational and
livable are listed below, despite the fact that many
skyscrapers are still being built.
1.1 Tube Structure
The tube system is one of thefrequentlyusedlateral
stability systems in tall building designs. It is intended to
function as a hollow cylinder with a vertical cantilever. This
enables the constructionofanendlessstiff"shell" around the
outside of the building
1.2 Types of Tubular Systems
Framed Tube Structures: Closelyspacedcolumnswith2
to 4 m between their centres make up frames, which are
joined by deep girders. The idea is to create a tube-like
structure that functions as a continuous perforated stack or
chimney. Stiff moment resisting frames that form a tube
around the building's perimeter provide the lateral
resistance for this structure.
Braced Tube Structures: By cross-bracing the frame
with X-bracings throughout the entire building, the tubular
structure is further strengthened. Shear lag effects in flange
and web frames combined are essentially eliminated by the
braced tube diagonals because they are connected to the
column at every intersection. Because of the reduced
bending in the frame members, the structure responds to
lateral loads like a braced frame.
Tube- in -Tube Structures: Another type offramedtube,
this one featuring an inner elevator and service core in
addition to an outer-framed tube. The braced frames that
make up the inner tube. In steel-framed buildings, the outer
and inner tubes work together to resist lateral loads as well
as gravity. However, because of its deeper structural depth,
the outer tube always has a significant impact. Hull and core
structures are other names for this class of buildings. The
typical Tube-in-Tube structure consists of an inner tube to
support vertical transportation demand and an outer tube
made up of substantial columns and beams.
Bundled Tube: A bundled tube system can be thought of
as an amalgamation of separate tubes that produces a
multiple cell tube. Large floor areas and great heights are
possible with this system. If internal webs are added to this
system, the shear lag in the flange beams will besignificantly
reduced.
2.LITERATURE SURVEY
S Bhavanishankar, Vinod are carried outwork on
‘Comparative Analysis of Tubular Structures with
Conventional Tall RC Structure’ ETABS V17 program is used
to model and analyse the data in the study. To analyse the
time period, base shear, lateral storey displacement, and
storey drift, a tall RC building with a 21-story 3D model is
taken into consideration, together with simulationsofa tube
framed structure in earthquake zones II and V. As
comparison to a Tall RC Moment - resistant Structural
Frame, the Period Of time of TubeStructurewassignificantly
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 237
lowered. As comparison to High RC Moment - resistant
Structural Frame, High Tubular Buildings' base shear
improved under earthquake loads. When contrastedtoHigh
RC Braced Frames Structures, Tubular Structures' stories
displacement and top storey have decreased, and their top
story displacement and storey drift values are well inside
acceptable ranges. When compared to the Tall RC Moment -
resistant Structure, storey amplitudes for tubular
constructions increased.
Mrunal P Kawade1, Vivek S Bangde, G H Sawai
are carried out work on ‘Seismic Analysis of Tall Building
with Central Core as Tube Structure’ With in study,a seismic
load comparison between a 25-story high rise building with
such a core shear as well as a similarly sized Framed
structure was made. The identical building plan's 8
configurations—rigid frame, flexible framework with core
shear wall, tubes in tube structure, tube mega frame
structure, suspending structure, trussed tube, tube in tube
with outriggers & frame with central core, and outriggers &
belt truss—are compared to one another. Shear walls have
long been recognised as being helpful in the structural
design of multi-story buildings. Shear walls must now be
included in multi-story buildings in order to withstand
lateral stresses. ETABS software was used to simulate the
structures for India's seismic zones V. The study looks at
lateral storey displacement, story drift, base shear, story
shear, and time periods for rigid frames, frame shear walls,
braced frames, suspending structures, tube-in-tube
structures, and tubed mega framed structures in order to
estimate the impact of seismic stresses.Dynamic behavior to
zone V earthquakes were tested according to IS 1893 (part
1): 2016. Frequency Response technique is employed in
nonlinear dynamic.
Sindhu Nachiar S, Anandh S, Sai Pavithra S,
Lakhan Kumar Saini, Elina Thomas, Boojith C S are
carried out work on ‘Comparative Seismic Analysis of
Conventional and RCC Tube in Tube Structure with
Pentagonal and Hexagonal Geometry Subjected To Lateral
Loads in Different Zones’ whereintheylearnedThisproblem
is successfully solved by the tube in tube framed structure,
also called as hulls and core, which comprises of an external
framed tube and a centre core tube that are connected by
floor slabs. In order to achieve higher resilience to
earthquake loading, an RCC polygonal and hexagon tube in
tube construction is contrasted with a traditional polygonal
and hexagon structure. STAAD.Pro is used to do the analysis
methodically. The analysis is done for several earthquake
zones (Zone II to Zone V). The analysis's findings determine
how traditional structures and tube-in-tube interactions
react to earthquakes. From in this analysis, we can also
determine which tube in a tube configuration is more
susceptible to its traditional complement.
Gurudath C, Ganesh Bahadur Khadka, HafizFaiz
Karim are carried out work on ‘Analysis of Multi-Storey
Building with and without Diagrid SystemUsingETABS’Asa
result of its effectiveness and higher standards, the diagrid
structural system that they researchedhasbeen widelyused
for modern tall structures. This is because of the system's
distinctive geometric configuration. For the purpose of
estimating the initial component sizes of R.C.C. diagrid
structures for a G+14 story building using ETABS 2015, this
project proposes a stiffness-based design technique. To
establish the best grid configurationforthediagridstructure
and to further compare it to a traditional R.C.C.structure,the
technique is used to the diagrid. By using the equivalent
static method, a G+14-story building with a 630,660,690-
square-foot perimeter is analysed. In terms of top story
displacement, story drift, story stiffness, and tale
overturning moment, a comparison of results analysis is
offered.
3. OBJECTIVES
1. To ascertain how lateral loads affect symmetrical
tall buildings with rigid frames, tube in tubeframes,
and trussed tube frame structures.
2. To examine how seismicloadsaffectstructureswith
rigid frames, tube-in-tube frames, and trussed tube
frames in relation to RC special moment resisting
frame structures throughout all seismic zones.
3. Using ETABS, compare tall RC special moment
resisting frame constructions with rigidframe,tube
in tube frame, and trussed tube frame buildings.
4. To investigate the horizontal as well as vertical
storey displacement, storey drift,andbaseshearfor
rigid frame, tube in tube frame, and trussed tube
frame structures.
5. To fix the building that is most susceptible tolateral
load among the models that were taken into
consideration.
4. METHODOLOGY
Table -1: Material Properties
Density of RCC 25 KN/m3
Density of Masonry 18 KN/m3
Compressive Strength, fck 40 N/mm2(Beam)
40 N/mm2(Column)
Steel, fy 500 N/mm2&
415 N/mm2
Modulus of Elasticity, Ec 5000*( fck)0.5
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 238
Table -2: Data / Parameters for the Analysis
Storey Height 3m
Wall &Shear wall Thickness 300mm and 400mm
Slab 150mm
Beam 300 x 750mm
Column 500 x 800mm
Frame System Special RC Moment
Resisting Frame
Parapet 750mm
Support Fixed
Buildings 24m x 24m
Spacings 3m
Number of Storey 30
Bracings ISMC 350
Damping 5%
4.1 Layout of Buildings
Fig -1: Plan and 3D Model of Rigid Frame Building
Fig -2: Plan and 3D Model of Tube in Tube Frame Building
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 239
Fig -3: Plan and 3D Model of Trussed Tube Frame Building
(Bracing-630)
5. RESULTS AND DISCUSSIONS
5.1 Comparison of Rigid Frame, TubeinTubeFrame and
Trussed Tube Frame Buildings in Different Seismic
Zones of India
5.1.1 Rigid Frame Building
Chart -1: Displacement for EQX
The displacement increases along with the seismic
zone intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone5.Incomparison
to seismic zone 2, displacement has increased by 37.5%,
58.33%, and 72.22% in seismic zones 3, 4, and 5. The top
story's displacement is taken into account.
Chart -2: Displacement for EQY
The displacement increases along with the seismic
zone intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone5.Incomparison
to seismic zone 2, displacement has increased by 37.5%,
58.33%, and 72.22% in seismic zones 3, 4, and 5. The top
story's displacement is taken into account.
Chart 1 and 2 above show that there is a 21.9%
increase in displacements for all zones when compared to
the EQX and EQY loads. The topstory'sdisplacementistaken
into account.
Chart -3: Drift for EQX
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 240
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increases of 59.86%,
33.36%, and 33.33%, respectively. The drift is taken into
account for tale 1. When compared to the otherstoriesofthe
rigid frame tall building, story 1 is experiencing the greatest
tale drift.
Chart -4: Drift for EQY
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increasesof37.53percent,
58.33 percent, and 72.22 percent, respectively. The drift is
taken into account for tale 1. When compared to the other
stories of the rigid frame tall building,story1isexperiencing
the greatest tale drift.
Chart 3 and 4 above show that there is a 43.84%
increase in drift for all zones when compared to the EQXand
EQY loads. For tale 1, the displacement is taken intoaccount.
Chart -5: Base Shear for EQX
As can be observed from theabovechart, baseshear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.59%, 58.39%, and 72.26%. For narrative 1,
the base shear is taken into account.
Chart -6: Base Shear for EQY
As can be observed from the above chart, base shear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.5%, 58.33%, and 72.22%. For narrative 1,
the base shear is taken into account.
According to the chart 5 and 6 above, thebaseshear
has increased by 1.2% for all zones when compared to the
EQX and EQY loads. For tale 1, the displacement istakeninto
account.
5.1.2 Tube in Tube Frame Building
Chart -7: Displacement for EQX
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 241
The displacement increases along with the seismic
zone intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone5.Incomparison
to seismic zone 2, displacement has increased by 37.5%,
58.33%, and 72.22% in seismic zones 3, 4, and 5. The top
story's displacement is taken into account.
Chart -8: Displacement for EQY
The displacement increases along with the seismic
zone intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone5.Incomparison
to seismic zone 2, displacement has increased by 37.5%,
58.33%, and 72.22% in seismic zones 3, 4, and 5. The top
story's displacement is taken into account.
Chart 7 and 8 above show that there is a 13.32%
increase in displacements for all zones when compared to
the EQX and EQY loads. The topstory'sdisplacementistaken
into account.
Chart -9: Drift for EQX
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increases of 37.99%,
58.69%, and 72.46%, respectively. The drift is taken into
account for narrative 15. When compared to the other
stories of the tall tube-in-tube construction, story 15
experiences the greatest tale drift.
Chart -10: Drift for EQY
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increasesof37.52percent,
58.32 percent, and 72.22 percent, respectively. The drift is
taken into account for narrative 15. When compared to the
other stories of the rigid frame tall skyscraper, story 15 will
experience the greatest tale drift.
Chart 9 and 10 above show that there is a 14.37%
increase in drift for all zones when compared to the EQXand
EQY loads. For tale 1, the displacement is taken intoaccount.
Chart -11: Base Shear for EQX
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 242
As can be observed from theabovechart, baseshear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.49%, 58.33%, and 72.22%. For narrative 1,
the base shear is taken into account.
Chart -12: Base Shear for EQY
As can be observed from theabovechart, baseshear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.5%, 58.33%, and 72.22%. For narrative 1,
the base shear is taken into account.
Chart 11 and 12 above show that the base shearhas
increased by 0.31% for all zones when compared to the EQX
and EQY loads. For tale 1, the displacement is taken into
account.
5.1.3 Trussed Tube Frame Building
Chart -13: Displacement for EQX
The displacement increases along with the seismic
zone intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone 5. Seismic zones
3, 4, and 5 show displacement increases of 37.49%, 58.33%,
and 72.22% in relation to seismic zone 2. The top story's
displacement is taken into account.
Chart -14: Displacement for EQY
The displacement increases along with the seismic zone
intensity, as seen in the above figure, and the highest
displacement was recorded in seismic zone5.Incomparison
to seismic zone 2, displacement has increased by 37.5%,
58.33%, and 72.22% in seismic zones 3, 4, and 5. The top
story's displacement is taken into account.
Chart 13 and 14 above show that there is a 12.6%
increase in displacements for all zones when compared to
the EQX and EQY loads. The topstory'sdisplacementistaken
into account.
Chart -15: Drift for EQX
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 243
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increases of 37.52%,
58.38%, and 72.25%, respectively. The drift is taken into
account for narrative 15. When compared to the other
stories of the rigid frame tall skyscraper, story 15 will
experience the greatest tale drift.
Chart -16: Drift for EQY
As can be observed from the preceding image, drift
increases along with seismic zonestrength,reachingitspeak
in seismic zone 5. In comparison to seismic zone 2, the
seismic zones 3, 4, and 5 had drift increases of 37.57%,
58.35%, and 72.23%, respectively. The drift is taken into
account for narrative 15. When compared to the other
stories of the rigid frame tall skyscraper, story 15 will
experience the greatest tale drift.
Chart 15 and 16 above show that there is a 13.55%
increase in drift for all zones when compared to the EQXand
EQY loads. For narrative 15, the displacement is taken into
account.
Chart -17: Base Shear for EQX
As can be observed from theabovechart, baseshear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.5%, 58.33%, and 72.22%. For narrative 1,
the base shear is taken into account.
Chart -18: Base Shear for EQY
As can be observed from theabovechart, baseshear
increases along with the seismic zone intensity, withseismic
zone 5 experiencing the highestbaseshear.Incomparisonto
seismic zone 2, seismic zones 3, 4, and 5 see increases in
base shear of 37.5%, 58.33%, and 72.22%. For narrative 1,
the base shear is taken into account.
Chart 17 and 18 above show that the base shearhas
increased by 0.28% for all zones when compared to the EQX
and EQY loads. For tale 1, the displacement is taken into
account.
5.2 ComparisonofDifferentSeismicZonesforRigid
Frame, Tube in Tube Frame and Trussed Tube
Frame Building for EQY Load
The EQY load values have been used in this
comparison because, as shown in clauses 5.1.1 to 5.1.3, the
EQY load produces the highest levels of displacement, drift,
and base shear when compared to the EQX load. As a result,
the comparison below is conducted for EQY load.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 244
Chart -19: Displacement
According to chart 19, the trussed frame building
experiences the greatest reduction in displacement across
the whole seismic zone when compared to rigidandtube-in-
tube frame buildings. For all seismic zones, the reduction
from a rigid frame building to a trussed frame building is
consistent at 33.18%. There is a constant decrease of 3.2%
for tube in tube framed structures and trussed tube framed
buildings, and a constant percentage decrease of 30.94%
from rigid frame buildings to tube in tube framed buildings.
Chart -20: Drift
According to chart 20, the trussed frame building
experiences the greatest reduction in drift across the whole
seismic zone when comparedtorigidandtube-in-tubeframe
buildings. For all seismic zones, there is a continuous
reduction of 62.56% from rigid frame to trussed frame
construction. There is a continuous percentage decrease of
62.56% from the rigid frame building to the tube in tube
framed building, and there is a constant decrease of 2.87%
for tube in tube framed buildings and trussed tube framed
structures.
Chart -21: Base Shear
According to chart 21, the trussed frame building
experiences the greatest reduction in drift across the whole
seismic zone when comparedtorigidandtube-in-tubeframe
buildings. When comparing rigid frame buildings to trussed
frame buildings, there is a continuous drop of 5.2% for all
seismic zones. There is a constantpercentagegainof0.034%
for tube in tube framed buildings and trussed tube framed
buildings, and a constant percentage drop of 5.53% for rigid
frame buildings to tube in tube framed buildings.
6. CONCLUSION
Finding the stabilisation system that is most successful is a
difficult undertaking because it seems there is no single
solution that can satisfy all potential criteria. While certain
systems have advantages over others, they are best suited
for some criteria. The findings below can be drawn based on
the analysis covered in chapter 5.
1. As seismic intensity or zones grow, displacement,
drift, and base shear for rigid frame, tube in tube
framed, and trussed framed buildings all rise.
2. For all rigid frame, tube in tube framed, and trussed
framed buildings, there is a continuous increase in
the displacement for both earthquake load in x-
direction and y-direction. When compared to the
other zones, zone 2 has the least displacement.
When compared to zone 2, there is a consistent rise
in displacement of 37.5% (zone 3), 58.33% (zone
4), and 72.22% (zone 5).
3. Compared to zone 2, rigid frame buildings' drift for
earthquake loads in the x-direction increased by
59.86% (zone 3), 33.36% (zone 4), and 33.33%
(zone 5). And when compared to zone 2, the rigid
frame building's earthquake load in the y-direction
increased by 37.53% (zone3),58.33%(zone4),and
72.22% (zone 5).
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 245
The drift for tube in tube framed and
trussed framed buildings is continuouslyincreasing
for both seismic load in x-direction and y-direction.
When compared to the other zones, zone 2 has the
least displacement. Whencomparedtozone2,there
is a consistent rise in displacement of 37.5% (zone
3), 58.33% (zone 4), and 72.22% (zone 5).
4. For all rigid frame, tube in tube framed, and trussed
framed buildings, there is a continuous increase in
the drift for both seismic load in x-direction and y-
direction. When compared to the other zones, zone
2 has the least displacement. When compared to
zone 2, there is a consistent rise in displacement of
37.5% (zone 3), 58.33% (zone4),and72.22%(zone
5).
5. The maximum values obtained for the earthquake
load in the y-direction as compared to the x-
direction are described in Chapter 5
 Throughout the seismic zone, the trussed
frame building experiences the greatest
reduction in displacement as compared to
rigid and tube in tube frame buildings. For
all seismic zones, the reductionfroma rigid
frame building to a trussed frame building
is consistent at 33.18%. There is a constant
decrease of 3.2% for tube in tube framed
structures and trussed tube framed
buildings, and a constant percentage
decrease of 30.94% from rigid frame
buildings to tube in tube framed buildings.
 Throughout the seismic zone, the trussed
frame building exhibits the greatest
reduction in drift when compared to rigid
and tube in tube frame buildings. For all
seismic zones, there is a continuous
reduction of 62.56% from rigid frame to
trussed frame construction. There is a
continuous percentage decreaseof62.56%
from the rigid frame building to the tube in
tube framed building, and there is a
constant decrease of 2.87%fortubeintube
framed buildings and trussed tube framed
structures.
 Throughout the seismic zone, the trussed
frame building exhibits the greatest
reduction in drift when compared to rigid
and tube in tube frame buildings. When
comparing rigid frame buildings totrussed
frame buildings, there is a continuousdrop
of 5.2% for all seismic zones. There is a
constant percentage gain of 0.034% for
tube in tube framed buildings and trussed
tube framed buildings, and a constant
percentage drop of 5.53% for rigid frame
buildings to tube in tube framed buildings.
6. Taking into account the aforementioned details,the
trussed tube frame buildings experienced the
greatest reduction relative to the others. But as
compared to the tube in tube frame buildings, there
is a minor increase in the base shear of 0.034%.
7. The findings show thattrussedtubeframe buildings
are among the most effective lateral load resisting
methods employed in tall buildings across all
seismic zones.
7.REFERENCES
1. S Bhavanishankar, Vinod, “Comparative Analysis of
Tubular Structures with Conventional Tall RC
Structure”, International Research Journal of
Engineering and Technology (IRJET) Volume: 08
Issue: 03 | Mar 2021.
2. Mrunal P Kawade , Vivek S Bangde , G H Sawai,
“Seismic Analysis of Tall Building with Central Core
as Tube Structure”, International Journal of
Progressive Research in Science and Engineering
Volume-1, Issue-6, September-2020.
3. Sindhu Nachiar S, Anandh S, Sai Pavithra S, Lakhan
Kumar Saini, Elina Thomas, Boojith C S,
“Comparative Seismic Analysis of Conventional and
RCC Tube in Tube Structure with Pentagonal and
Hexagonal Geometry Subjected To Lateral Loads in
Different Zones”, International Journal of
Engineering and Advanced Technology (IJEAT)
ISSN: 2249-8958, Volume-8 Issue-4, April 2019.
4. E.H.Ghoniem, Nihal M.Ayyash, Ahmed Essam,
“Seismic Response of High-rise Buildings with
Different Structural Systems”, International Journal
of Engineering and Innovative Technology (IJEIT)
Volume 8, Issue 9, November 2018.
5. Pavithra S E, Dr. S Vijaya, Kavya H K, “Dynamic
Analysis of Hybrid Tall Tube Structural system”,
NOVYI MIR Research Journal, ISSN No: 0130-7673,
Volume 5, Issue 12, 2020.
6. Mr. Dhruvil Y Patel, Mr. Piyush Jain, Dr. V. R. Patel,
“Analysis and Design of RCC Tall-Building with
different structural systems”, International Journal
of Innovative and Emerging Research in
Engineering Volume 4, Issue 5, 2017.
7. Wuit Yi Win Htut, “A Simplified Approach for
Optimization of Tube System in Tall Buildings”,
International Journal for Innovative Research in
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 246
Multidisciplinary Field ISSN – 2455-0620 Volume -
2, Issue - 9, Sept – 2016.
8. Akshay S. Patil, Roshni John, “Performance
Evaluation of Unsymmetrical HighRise Building
with Different Types of Structural Techniques for
Critical Load Condition”, International Journal of
Scientific & Engineering Research Volume 11, Issue
4, April-2020.
9. Neelam.Sathyanarayana, G.Srinath, E.Giriprasad
Goud, “Seismic Comparison Between the Use of
Framed Shear Wall System and Framed Tube
System in Tall Buildings”IndianJ.Sci.Res.17(2):429
- 433, 2018.
10. Deepak Suthar, H.S.Chore, P.A. Dode, “High Rise
Structure Subjected To Seismic Forces And Its
Behavior”, Proceedings of 12 th IRF International
Conference, 29th June-2014.
11. Patil. Kiran Kumar, Chandan Kumar. Patnaikuni,
Balaji .K.V.G.D, B. Santhosh Kumar, “Seismic
Performance of Bundled Tube StructuresinSeismic
Zone IV & Zone V of India”, International Journal of
Advanced Research in Engineering and Technology
(IJARET) Volume 11, Issue 6, June 2020.
12. Jignesha Patel, Roshni J John, “Seismic Analysis of
Frame Tube Structure”, International Journal of
Scientific & Engineering Research, Volume 6, Issue
12, December-2015.
13. Nimmy Dileep, Renjith R, “Analytical Investigation
on the Performance of Tube-In-Tube Structures
Subjected to Lateral Loads”, International Journal of
Technical Research and Applications, Volume 3,
Issue4 July-August 2015.
14. Moreteza Deiranlou, “Evaluation of Seismic
Behavior in Building Tube Structures System with
Respect to Dense Soil-Structure Interaction Effect”,
Open Journal of Civil Engineering, 2015.
15. Shruthi L, S. Vijaya, “Seismic Analysis of Latticed
Shell Tube RC Framed Building”, International
Journal of Engineering Research & Technology
(IJERT) IJERT ISSN: 2278-0181 www.ijert.orgVol.3
Issue 7, July – 2014.
16. Gurudath C, Ganesh Bahadur Khadka, Hafiz Faiz
Karim, “Analysis of Multi-Storey Building with and
without DiagridSystemUsingETABS”,International
Journal Of Innovative Research In Technology,
Volume 5 Issue 12, ISSN: 2349-6002, May 2019.

More Related Content

Similar to DYNAMIC ANALYSIS OF TALL BUILDING LOCATED IN DIFFERENT SEISMIC ZONES WITH CENTRAL SHEAR WALL AND DIAGONAL BRACINGS BY USING E-TABS SOFTWARE

“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
IRJET Journal
 
IRJET- A Performance Study of (G+20) RCC Structure using Framed Bundled B...
IRJET-  	  A Performance Study of (G+20) RCC Structure using Framed Bundled B...IRJET-  	  A Performance Study of (G+20) RCC Structure using Framed Bundled B...
IRJET- A Performance Study of (G+20) RCC Structure using Framed Bundled B...
IRJET Journal
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
IRJET Journal
 
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
IRJET Journal
 
IRJET- Seismic Analysis of a Tall Structure Considering X Type Bracings a...
IRJET-  	  Seismic Analysis of a Tall Structure Considering X Type Bracings a...IRJET-  	  Seismic Analysis of a Tall Structure Considering X Type Bracings a...
IRJET- Seismic Analysis of a Tall Structure Considering X Type Bracings a...
IRJET Journal
 
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss SystemSeismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
IRJET Journal
 
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
IRJET Journal
 
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
IRJET Journal
 
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURESANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
IRJET Journal
 
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
IRJET Journal
 
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’sAnalysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
IRJET Journal
 
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
IRJET Journal
 
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
IRJET Journal
 
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
IRJET Journal
 
IRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
IRJET- Diagrid Structural System for Tall Buildings: State of the Art ReviewIRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
IRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
IRJET Journal
 
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
IRJET-  	  Comparative Study of Effect of Different Positions of Shear Wall o...IRJET-  	  Comparative Study of Effect of Different Positions of Shear Wall o...
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
IRJET Journal
 
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADSSTRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
IRJET Journal
 
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABSSEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
IRJET Journal
 
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
IRJET Journal
 

Similar to DYNAMIC ANALYSIS OF TALL BUILDING LOCATED IN DIFFERENT SEISMIC ZONES WITH CENTRAL SHEAR WALL AND DIAGONAL BRACINGS BY USING E-TABS SOFTWARE (20)

“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
“A REVIEW STUDY ON PUSHOVER ANALYSIS OF SYMMETRIC BUILDING ON FLAT & SLOPING ...
 
IRJET- A Performance Study of (G+20) RCC Structure using Framed Bundled B...
IRJET-  	  A Performance Study of (G+20) RCC Structure using Framed Bundled B...IRJET-  	  A Performance Study of (G+20) RCC Structure using Framed Bundled B...
IRJET- A Performance Study of (G+20) RCC Structure using Framed Bundled B...
 
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
Influence of Concrete and Steel Outrigger and Belt Truss in High Rise Moment ...
 
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
ANALYSIS AND DESIGN OPTIMIZATION OF SHEAR-WALL IN CASE OF HIGH-RISE BUILDING ...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
IRJET- Seismic Analysis of a Tall Structure Considering X Type Bracings a...
IRJET-  	  Seismic Analysis of a Tall Structure Considering X Type Bracings a...IRJET-  	  Seismic Analysis of a Tall Structure Considering X Type Bracings a...
IRJET- Seismic Analysis of a Tall Structure Considering X Type Bracings a...
 
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss SystemSeismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
Seismic Analysis of High Rise Building Using Outriggers and Belt- Truss System
 
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
Wind and Seismic Analysis of Building with Bracing System Resting on Sloping ...
 
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
IRJET- Analysis of G+45 Bundled Tube Structure using Different Bracing System...
 
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURESANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
ANALYSIS AND DESIGN OF HIGH-RISE DIAGRID STRUCTURES
 
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
Comparative Study of Waffle Slab and Conventional Slabs with Bracing System U...
 
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’sAnalysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
Analysis For Retrofitting Of An Existing Failed RC Column Using FEM Software’s
 
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
Wind Braces & Tie Runners as Mittigating Elements in Industrial Sheds Against...
 
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
 
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
Analysis of Seismic Behaviors of RC Frame Structure With Bracing System and W...
 
IRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
IRJET- Diagrid Structural System for Tall Buildings: State of the Art ReviewIRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
IRJET- Diagrid Structural System for Tall Buildings: State of the Art Review
 
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
IRJET-  	  Comparative Study of Effect of Different Positions of Shear Wall o...IRJET-  	  Comparative Study of Effect of Different Positions of Shear Wall o...
IRJET- Comparative Study of Effect of Different Positions of Shear Wall o...
 
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADSSTRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
STRUCTURAL ANALYSIS OF BRIDGES AND PILE FOUNDATION SUBJECTED TO SEISMIC LOADS
 
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABSSEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
SEISMIC EVALUATION OF MULTISTORIED BUILDING WITH FLOATING COLUMNS USING ETABS
 
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
REVIEW PAPER ON SEISMIC RESPONSE OF FLAT SLAB & CONVENTIONAL SLAB WITH DIFFER...
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
IRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
IRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
IRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
IRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
IRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
IRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
IRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
IRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
IRJET Journal
 
Solving Linear Differential Equations with Constant Coefficients
Solving Linear Differential Equations with Constant CoefficientsSolving Linear Differential Equations with Constant Coefficients
Solving Linear Differential Equations with Constant Coefficients
IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 
Solving Linear Differential Equations with Constant Coefficients
Solving Linear Differential Equations with Constant CoefficientsSolving Linear Differential Equations with Constant Coefficients
Solving Linear Differential Equations with Constant Coefficients
 

Recently uploaded

spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
Madan Karki
 
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
ecqow
 
ITSM Integration with MuleSoft.pptx
ITSM  Integration with MuleSoft.pptxITSM  Integration with MuleSoft.pptx
ITSM Integration with MuleSoft.pptx
VANDANAMOHANGOUDA
 
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
insn4465
 
AI assisted telemedicine KIOSK for Rural India.pptx
AI assisted telemedicine KIOSK for Rural India.pptxAI assisted telemedicine KIOSK for Rural India.pptx
AI assisted telemedicine KIOSK for Rural India.pptx
architagupta876
 
Rainfall intensity duration frequency curve statistical analysis and modeling...
Rainfall intensity duration frequency curve statistical analysis and modeling...Rainfall intensity duration frequency curve statistical analysis and modeling...
Rainfall intensity duration frequency curve statistical analysis and modeling...
bijceesjournal
 
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
IJECEIAES
 
cnn.pptx Convolutional neural network used for image classication
cnn.pptx Convolutional neural network used for image classicationcnn.pptx Convolutional neural network used for image classication
cnn.pptx Convolutional neural network used for image classication
SakkaravarthiShanmug
 
Welding Metallurgy Ferrous Materials.pdf
Welding Metallurgy Ferrous Materials.pdfWelding Metallurgy Ferrous Materials.pdf
Welding Metallurgy Ferrous Materials.pdf
AjmalKhan50578
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
IJECEIAES
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
ElakkiaU
 
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
shadow0702a
 
132/33KV substation case study Presentation
132/33KV substation case study Presentation132/33KV substation case study Presentation
132/33KV substation case study Presentation
kandramariana6
 
Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
co23btech11018
 
Null Bangalore | Pentesters Approach to AWS IAM
Null Bangalore | Pentesters Approach to AWS IAMNull Bangalore | Pentesters Approach to AWS IAM
Null Bangalore | Pentesters Approach to AWS IAM
Divyanshu
 
Software Quality Assurance-se412-v11.ppt
Software Quality Assurance-se412-v11.pptSoftware Quality Assurance-se412-v11.ppt
Software Quality Assurance-se412-v11.ppt
TaghreedAltamimi
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
KrishnaveniKrishnara1
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
bijceesjournal
 
Data Driven Maintenance | UReason Webinar
Data Driven Maintenance | UReason WebinarData Driven Maintenance | UReason Webinar
Data Driven Maintenance | UReason Webinar
UReason
 
People as resource Grade IX.pdf minimala
People as resource Grade IX.pdf minimalaPeople as resource Grade IX.pdf minimala
People as resource Grade IX.pdf minimala
riddhimaagrawal986
 

Recently uploaded (20)

spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
 
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
一比一原版(CalArts毕业证)加利福尼亚艺术学院毕业证如何办理
 
ITSM Integration with MuleSoft.pptx
ITSM  Integration with MuleSoft.pptxITSM  Integration with MuleSoft.pptx
ITSM Integration with MuleSoft.pptx
 
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
 
AI assisted telemedicine KIOSK for Rural India.pptx
AI assisted telemedicine KIOSK for Rural India.pptxAI assisted telemedicine KIOSK for Rural India.pptx
AI assisted telemedicine KIOSK for Rural India.pptx
 
Rainfall intensity duration frequency curve statistical analysis and modeling...
Rainfall intensity duration frequency curve statistical analysis and modeling...Rainfall intensity duration frequency curve statistical analysis and modeling...
Rainfall intensity duration frequency curve statistical analysis and modeling...
 
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
Electric vehicle and photovoltaic advanced roles in enhancing the financial p...
 
cnn.pptx Convolutional neural network used for image classication
cnn.pptx Convolutional neural network used for image classicationcnn.pptx Convolutional neural network used for image classication
cnn.pptx Convolutional neural network used for image classication
 
Welding Metallurgy Ferrous Materials.pdf
Welding Metallurgy Ferrous Materials.pdfWelding Metallurgy Ferrous Materials.pdf
Welding Metallurgy Ferrous Materials.pdf
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
 
An Introduction to the Compiler Designss
An Introduction to the Compiler DesignssAn Introduction to the Compiler Designss
An Introduction to the Compiler Designss
 
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
Use PyCharm for remote debugging of WSL on a Windo cf5c162d672e4e58b4dde5d797...
 
132/33KV substation case study Presentation
132/33KV substation case study Presentation132/33KV substation case study Presentation
132/33KV substation case study Presentation
 
Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
 
Null Bangalore | Pentesters Approach to AWS IAM
Null Bangalore | Pentesters Approach to AWS IAMNull Bangalore | Pentesters Approach to AWS IAM
Null Bangalore | Pentesters Approach to AWS IAM
 
Software Quality Assurance-se412-v11.ppt
Software Quality Assurance-se412-v11.pptSoftware Quality Assurance-se412-v11.ppt
Software Quality Assurance-se412-v11.ppt
 
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.pptUnit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
Unit-III-ELECTROCHEMICAL STORAGE DEVICES.ppt
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
 
Data Driven Maintenance | UReason Webinar
Data Driven Maintenance | UReason WebinarData Driven Maintenance | UReason Webinar
Data Driven Maintenance | UReason Webinar
 
People as resource Grade IX.pdf minimala
People as resource Grade IX.pdf minimalaPeople as resource Grade IX.pdf minimala
People as resource Grade IX.pdf minimala
 

DYNAMIC ANALYSIS OF TALL BUILDING LOCATED IN DIFFERENT SEISMIC ZONES WITH CENTRAL SHEAR WALL AND DIAGONAL BRACINGS BY USING E-TABS SOFTWARE

  • 1. © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 236 DYNAMIC ANALYSIS OF TALL BUILDING LOCATED IN DIFFERENT SEISMIC ZONES WITH CENTRAL SHEAR WALL AND DIAGONAL BRACINGS BY USING E-TABS SOFTWARE MANJULA1, VEERESHAIAH H M2, PAVAN KUMAR M 3 BASAVALINGAPPA 4 1PG Scholar, Department of Civil Engineering, RYMEC, Ballari 2,3,4Assistant Professors, Department of Civil Engineering, RYMEC, Ballari ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Since land prices are rising quickly and there is a shortage of available land, tall buildings are preferred in order to preserve agricultural land inruralareas. The main factors influencing tall building designarewindand seismic loads. In the current study, tall buildings were examined in all seismic zones using ETABS 2017 software under the influence of seismic loads with a central shear wall and diagonal bracings, andtheresultswereanalysedusingthe response spectrum method. In addition, the configurations' story displacement, story drift, and base shear at foundations were compared to the seismic parameters derived from the analysis. 1. INTRODUCTION Tall buildingsvarydependingonthe environmentin question. It will be simple to say that a four story building in a neighborhood of bungalows isa tall building,andthisclaim will be uncontested. It's comparable to a one-eyed man ruling a land of the blind. The construction boom in metro areasoverthepast 20 years has significantly altered the skyline of Indian cities. The fanciest skyscrapers, home to some of the wealthiest people in the nation, are now dotted throughout areas that were previously dominated by low-rise residential compounds. An approximate count places Kolkata second with 12 skyscrapers, followed by Mumbai with over 50. The tallest buildings in India that are currently operational and livable are listed below, despite the fact that many skyscrapers are still being built. 1.1 Tube Structure The tube system is one of thefrequentlyusedlateral stability systems in tall building designs. It is intended to function as a hollow cylinder with a vertical cantilever. This enables the constructionofanendlessstiff"shell" around the outside of the building 1.2 Types of Tubular Systems Framed Tube Structures: Closelyspacedcolumnswith2 to 4 m between their centres make up frames, which are joined by deep girders. The idea is to create a tube-like structure that functions as a continuous perforated stack or chimney. Stiff moment resisting frames that form a tube around the building's perimeter provide the lateral resistance for this structure. Braced Tube Structures: By cross-bracing the frame with X-bracings throughout the entire building, the tubular structure is further strengthened. Shear lag effects in flange and web frames combined are essentially eliminated by the braced tube diagonals because they are connected to the column at every intersection. Because of the reduced bending in the frame members, the structure responds to lateral loads like a braced frame. Tube- in -Tube Structures: Another type offramedtube, this one featuring an inner elevator and service core in addition to an outer-framed tube. The braced frames that make up the inner tube. In steel-framed buildings, the outer and inner tubes work together to resist lateral loads as well as gravity. However, because of its deeper structural depth, the outer tube always has a significant impact. Hull and core structures are other names for this class of buildings. The typical Tube-in-Tube structure consists of an inner tube to support vertical transportation demand and an outer tube made up of substantial columns and beams. Bundled Tube: A bundled tube system can be thought of as an amalgamation of separate tubes that produces a multiple cell tube. Large floor areas and great heights are possible with this system. If internal webs are added to this system, the shear lag in the flange beams will besignificantly reduced. 2.LITERATURE SURVEY S Bhavanishankar, Vinod are carried outwork on ‘Comparative Analysis of Tubular Structures with Conventional Tall RC Structure’ ETABS V17 program is used to model and analyse the data in the study. To analyse the time period, base shear, lateral storey displacement, and storey drift, a tall RC building with a 21-story 3D model is taken into consideration, together with simulationsofa tube framed structure in earthquake zones II and V. As comparison to a Tall RC Moment - resistant Structural Frame, the Period Of time of TubeStructurewassignificantly International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 237 lowered. As comparison to High RC Moment - resistant Structural Frame, High Tubular Buildings' base shear improved under earthquake loads. When contrastedtoHigh RC Braced Frames Structures, Tubular Structures' stories displacement and top storey have decreased, and their top story displacement and storey drift values are well inside acceptable ranges. When compared to the Tall RC Moment - resistant Structure, storey amplitudes for tubular constructions increased. Mrunal P Kawade1, Vivek S Bangde, G H Sawai are carried out work on ‘Seismic Analysis of Tall Building with Central Core as Tube Structure’ With in study,a seismic load comparison between a 25-story high rise building with such a core shear as well as a similarly sized Framed structure was made. The identical building plan's 8 configurations—rigid frame, flexible framework with core shear wall, tubes in tube structure, tube mega frame structure, suspending structure, trussed tube, tube in tube with outriggers & frame with central core, and outriggers & belt truss—are compared to one another. Shear walls have long been recognised as being helpful in the structural design of multi-story buildings. Shear walls must now be included in multi-story buildings in order to withstand lateral stresses. ETABS software was used to simulate the structures for India's seismic zones V. The study looks at lateral storey displacement, story drift, base shear, story shear, and time periods for rigid frames, frame shear walls, braced frames, suspending structures, tube-in-tube structures, and tubed mega framed structures in order to estimate the impact of seismic stresses.Dynamic behavior to zone V earthquakes were tested according to IS 1893 (part 1): 2016. Frequency Response technique is employed in nonlinear dynamic. Sindhu Nachiar S, Anandh S, Sai Pavithra S, Lakhan Kumar Saini, Elina Thomas, Boojith C S are carried out work on ‘Comparative Seismic Analysis of Conventional and RCC Tube in Tube Structure with Pentagonal and Hexagonal Geometry Subjected To Lateral Loads in Different Zones’ whereintheylearnedThisproblem is successfully solved by the tube in tube framed structure, also called as hulls and core, which comprises of an external framed tube and a centre core tube that are connected by floor slabs. In order to achieve higher resilience to earthquake loading, an RCC polygonal and hexagon tube in tube construction is contrasted with a traditional polygonal and hexagon structure. STAAD.Pro is used to do the analysis methodically. The analysis is done for several earthquake zones (Zone II to Zone V). The analysis's findings determine how traditional structures and tube-in-tube interactions react to earthquakes. From in this analysis, we can also determine which tube in a tube configuration is more susceptible to its traditional complement. Gurudath C, Ganesh Bahadur Khadka, HafizFaiz Karim are carried out work on ‘Analysis of Multi-Storey Building with and without Diagrid SystemUsingETABS’Asa result of its effectiveness and higher standards, the diagrid structural system that they researchedhasbeen widelyused for modern tall structures. This is because of the system's distinctive geometric configuration. For the purpose of estimating the initial component sizes of R.C.C. diagrid structures for a G+14 story building using ETABS 2015, this project proposes a stiffness-based design technique. To establish the best grid configurationforthediagridstructure and to further compare it to a traditional R.C.C.structure,the technique is used to the diagrid. By using the equivalent static method, a G+14-story building with a 630,660,690- square-foot perimeter is analysed. In terms of top story displacement, story drift, story stiffness, and tale overturning moment, a comparison of results analysis is offered. 3. OBJECTIVES 1. To ascertain how lateral loads affect symmetrical tall buildings with rigid frames, tube in tubeframes, and trussed tube frame structures. 2. To examine how seismicloadsaffectstructureswith rigid frames, tube-in-tube frames, and trussed tube frames in relation to RC special moment resisting frame structures throughout all seismic zones. 3. Using ETABS, compare tall RC special moment resisting frame constructions with rigidframe,tube in tube frame, and trussed tube frame buildings. 4. To investigate the horizontal as well as vertical storey displacement, storey drift,andbaseshearfor rigid frame, tube in tube frame, and trussed tube frame structures. 5. To fix the building that is most susceptible tolateral load among the models that were taken into consideration. 4. METHODOLOGY Table -1: Material Properties Density of RCC 25 KN/m3 Density of Masonry 18 KN/m3 Compressive Strength, fck 40 N/mm2(Beam) 40 N/mm2(Column) Steel, fy 500 N/mm2& 415 N/mm2 Modulus of Elasticity, Ec 5000*( fck)0.5
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 238 Table -2: Data / Parameters for the Analysis Storey Height 3m Wall &Shear wall Thickness 300mm and 400mm Slab 150mm Beam 300 x 750mm Column 500 x 800mm Frame System Special RC Moment Resisting Frame Parapet 750mm Support Fixed Buildings 24m x 24m Spacings 3m Number of Storey 30 Bracings ISMC 350 Damping 5% 4.1 Layout of Buildings Fig -1: Plan and 3D Model of Rigid Frame Building Fig -2: Plan and 3D Model of Tube in Tube Frame Building
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 239 Fig -3: Plan and 3D Model of Trussed Tube Frame Building (Bracing-630) 5. RESULTS AND DISCUSSIONS 5.1 Comparison of Rigid Frame, TubeinTubeFrame and Trussed Tube Frame Buildings in Different Seismic Zones of India 5.1.1 Rigid Frame Building Chart -1: Displacement for EQX The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone5.Incomparison to seismic zone 2, displacement has increased by 37.5%, 58.33%, and 72.22% in seismic zones 3, 4, and 5. The top story's displacement is taken into account. Chart -2: Displacement for EQY The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone5.Incomparison to seismic zone 2, displacement has increased by 37.5%, 58.33%, and 72.22% in seismic zones 3, 4, and 5. The top story's displacement is taken into account. Chart 1 and 2 above show that there is a 21.9% increase in displacements for all zones when compared to the EQX and EQY loads. The topstory'sdisplacementistaken into account. Chart -3: Drift for EQX
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 240 As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increases of 59.86%, 33.36%, and 33.33%, respectively. The drift is taken into account for tale 1. When compared to the otherstoriesofthe rigid frame tall building, story 1 is experiencing the greatest tale drift. Chart -4: Drift for EQY As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increasesof37.53percent, 58.33 percent, and 72.22 percent, respectively. The drift is taken into account for tale 1. When compared to the other stories of the rigid frame tall building,story1isexperiencing the greatest tale drift. Chart 3 and 4 above show that there is a 43.84% increase in drift for all zones when compared to the EQXand EQY loads. For tale 1, the displacement is taken intoaccount. Chart -5: Base Shear for EQX As can be observed from theabovechart, baseshear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.59%, 58.39%, and 72.26%. For narrative 1, the base shear is taken into account. Chart -6: Base Shear for EQY As can be observed from the above chart, base shear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.5%, 58.33%, and 72.22%. For narrative 1, the base shear is taken into account. According to the chart 5 and 6 above, thebaseshear has increased by 1.2% for all zones when compared to the EQX and EQY loads. For tale 1, the displacement istakeninto account. 5.1.2 Tube in Tube Frame Building Chart -7: Displacement for EQX
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 241 The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone5.Incomparison to seismic zone 2, displacement has increased by 37.5%, 58.33%, and 72.22% in seismic zones 3, 4, and 5. The top story's displacement is taken into account. Chart -8: Displacement for EQY The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone5.Incomparison to seismic zone 2, displacement has increased by 37.5%, 58.33%, and 72.22% in seismic zones 3, 4, and 5. The top story's displacement is taken into account. Chart 7 and 8 above show that there is a 13.32% increase in displacements for all zones when compared to the EQX and EQY loads. The topstory'sdisplacementistaken into account. Chart -9: Drift for EQX As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increases of 37.99%, 58.69%, and 72.46%, respectively. The drift is taken into account for narrative 15. When compared to the other stories of the tall tube-in-tube construction, story 15 experiences the greatest tale drift. Chart -10: Drift for EQY As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increasesof37.52percent, 58.32 percent, and 72.22 percent, respectively. The drift is taken into account for narrative 15. When compared to the other stories of the rigid frame tall skyscraper, story 15 will experience the greatest tale drift. Chart 9 and 10 above show that there is a 14.37% increase in drift for all zones when compared to the EQXand EQY loads. For tale 1, the displacement is taken intoaccount. Chart -11: Base Shear for EQX
  • 7. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 242 As can be observed from theabovechart, baseshear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.49%, 58.33%, and 72.22%. For narrative 1, the base shear is taken into account. Chart -12: Base Shear for EQY As can be observed from theabovechart, baseshear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.5%, 58.33%, and 72.22%. For narrative 1, the base shear is taken into account. Chart 11 and 12 above show that the base shearhas increased by 0.31% for all zones when compared to the EQX and EQY loads. For tale 1, the displacement is taken into account. 5.1.3 Trussed Tube Frame Building Chart -13: Displacement for EQX The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone 5. Seismic zones 3, 4, and 5 show displacement increases of 37.49%, 58.33%, and 72.22% in relation to seismic zone 2. The top story's displacement is taken into account. Chart -14: Displacement for EQY The displacement increases along with the seismic zone intensity, as seen in the above figure, and the highest displacement was recorded in seismic zone5.Incomparison to seismic zone 2, displacement has increased by 37.5%, 58.33%, and 72.22% in seismic zones 3, 4, and 5. The top story's displacement is taken into account. Chart 13 and 14 above show that there is a 12.6% increase in displacements for all zones when compared to the EQX and EQY loads. The topstory'sdisplacementistaken into account. Chart -15: Drift for EQX
  • 8. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 243 As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increases of 37.52%, 58.38%, and 72.25%, respectively. The drift is taken into account for narrative 15. When compared to the other stories of the rigid frame tall skyscraper, story 15 will experience the greatest tale drift. Chart -16: Drift for EQY As can be observed from the preceding image, drift increases along with seismic zonestrength,reachingitspeak in seismic zone 5. In comparison to seismic zone 2, the seismic zones 3, 4, and 5 had drift increases of 37.57%, 58.35%, and 72.23%, respectively. The drift is taken into account for narrative 15. When compared to the other stories of the rigid frame tall skyscraper, story 15 will experience the greatest tale drift. Chart 15 and 16 above show that there is a 13.55% increase in drift for all zones when compared to the EQXand EQY loads. For narrative 15, the displacement is taken into account. Chart -17: Base Shear for EQX As can be observed from theabovechart, baseshear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.5%, 58.33%, and 72.22%. For narrative 1, the base shear is taken into account. Chart -18: Base Shear for EQY As can be observed from theabovechart, baseshear increases along with the seismic zone intensity, withseismic zone 5 experiencing the highestbaseshear.Incomparisonto seismic zone 2, seismic zones 3, 4, and 5 see increases in base shear of 37.5%, 58.33%, and 72.22%. For narrative 1, the base shear is taken into account. Chart 17 and 18 above show that the base shearhas increased by 0.28% for all zones when compared to the EQX and EQY loads. For tale 1, the displacement is taken into account. 5.2 ComparisonofDifferentSeismicZonesforRigid Frame, Tube in Tube Frame and Trussed Tube Frame Building for EQY Load The EQY load values have been used in this comparison because, as shown in clauses 5.1.1 to 5.1.3, the EQY load produces the highest levels of displacement, drift, and base shear when compared to the EQX load. As a result, the comparison below is conducted for EQY load.
  • 9. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 244 Chart -19: Displacement According to chart 19, the trussed frame building experiences the greatest reduction in displacement across the whole seismic zone when compared to rigidandtube-in- tube frame buildings. For all seismic zones, the reduction from a rigid frame building to a trussed frame building is consistent at 33.18%. There is a constant decrease of 3.2% for tube in tube framed structures and trussed tube framed buildings, and a constant percentage decrease of 30.94% from rigid frame buildings to tube in tube framed buildings. Chart -20: Drift According to chart 20, the trussed frame building experiences the greatest reduction in drift across the whole seismic zone when comparedtorigidandtube-in-tubeframe buildings. For all seismic zones, there is a continuous reduction of 62.56% from rigid frame to trussed frame construction. There is a continuous percentage decrease of 62.56% from the rigid frame building to the tube in tube framed building, and there is a constant decrease of 2.87% for tube in tube framed buildings and trussed tube framed structures. Chart -21: Base Shear According to chart 21, the trussed frame building experiences the greatest reduction in drift across the whole seismic zone when comparedtorigidandtube-in-tubeframe buildings. When comparing rigid frame buildings to trussed frame buildings, there is a continuous drop of 5.2% for all seismic zones. There is a constantpercentagegainof0.034% for tube in tube framed buildings and trussed tube framed buildings, and a constant percentage drop of 5.53% for rigid frame buildings to tube in tube framed buildings. 6. CONCLUSION Finding the stabilisation system that is most successful is a difficult undertaking because it seems there is no single solution that can satisfy all potential criteria. While certain systems have advantages over others, they are best suited for some criteria. The findings below can be drawn based on the analysis covered in chapter 5. 1. As seismic intensity or zones grow, displacement, drift, and base shear for rigid frame, tube in tube framed, and trussed framed buildings all rise. 2. For all rigid frame, tube in tube framed, and trussed framed buildings, there is a continuous increase in the displacement for both earthquake load in x- direction and y-direction. When compared to the other zones, zone 2 has the least displacement. When compared to zone 2, there is a consistent rise in displacement of 37.5% (zone 3), 58.33% (zone 4), and 72.22% (zone 5). 3. Compared to zone 2, rigid frame buildings' drift for earthquake loads in the x-direction increased by 59.86% (zone 3), 33.36% (zone 4), and 33.33% (zone 5). And when compared to zone 2, the rigid frame building's earthquake load in the y-direction increased by 37.53% (zone3),58.33%(zone4),and 72.22% (zone 5).
  • 10. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 245 The drift for tube in tube framed and trussed framed buildings is continuouslyincreasing for both seismic load in x-direction and y-direction. When compared to the other zones, zone 2 has the least displacement. Whencomparedtozone2,there is a consistent rise in displacement of 37.5% (zone 3), 58.33% (zone 4), and 72.22% (zone 5). 4. For all rigid frame, tube in tube framed, and trussed framed buildings, there is a continuous increase in the drift for both seismic load in x-direction and y- direction. When compared to the other zones, zone 2 has the least displacement. When compared to zone 2, there is a consistent rise in displacement of 37.5% (zone 3), 58.33% (zone4),and72.22%(zone 5). 5. The maximum values obtained for the earthquake load in the y-direction as compared to the x- direction are described in Chapter 5  Throughout the seismic zone, the trussed frame building experiences the greatest reduction in displacement as compared to rigid and tube in tube frame buildings. For all seismic zones, the reductionfroma rigid frame building to a trussed frame building is consistent at 33.18%. There is a constant decrease of 3.2% for tube in tube framed structures and trussed tube framed buildings, and a constant percentage decrease of 30.94% from rigid frame buildings to tube in tube framed buildings.  Throughout the seismic zone, the trussed frame building exhibits the greatest reduction in drift when compared to rigid and tube in tube frame buildings. For all seismic zones, there is a continuous reduction of 62.56% from rigid frame to trussed frame construction. There is a continuous percentage decreaseof62.56% from the rigid frame building to the tube in tube framed building, and there is a constant decrease of 2.87%fortubeintube framed buildings and trussed tube framed structures.  Throughout the seismic zone, the trussed frame building exhibits the greatest reduction in drift when compared to rigid and tube in tube frame buildings. When comparing rigid frame buildings totrussed frame buildings, there is a continuousdrop of 5.2% for all seismic zones. There is a constant percentage gain of 0.034% for tube in tube framed buildings and trussed tube framed buildings, and a constant percentage drop of 5.53% for rigid frame buildings to tube in tube framed buildings. 6. Taking into account the aforementioned details,the trussed tube frame buildings experienced the greatest reduction relative to the others. But as compared to the tube in tube frame buildings, there is a minor increase in the base shear of 0.034%. 7. The findings show thattrussedtubeframe buildings are among the most effective lateral load resisting methods employed in tall buildings across all seismic zones. 7.REFERENCES 1. S Bhavanishankar, Vinod, “Comparative Analysis of Tubular Structures with Conventional Tall RC Structure”, International Research Journal of Engineering and Technology (IRJET) Volume: 08 Issue: 03 | Mar 2021. 2. Mrunal P Kawade , Vivek S Bangde , G H Sawai, “Seismic Analysis of Tall Building with Central Core as Tube Structure”, International Journal of Progressive Research in Science and Engineering Volume-1, Issue-6, September-2020. 3. Sindhu Nachiar S, Anandh S, Sai Pavithra S, Lakhan Kumar Saini, Elina Thomas, Boojith C S, “Comparative Seismic Analysis of Conventional and RCC Tube in Tube Structure with Pentagonal and Hexagonal Geometry Subjected To Lateral Loads in Different Zones”, International Journal of Engineering and Advanced Technology (IJEAT) ISSN: 2249-8958, Volume-8 Issue-4, April 2019. 4. E.H.Ghoniem, Nihal M.Ayyash, Ahmed Essam, “Seismic Response of High-rise Buildings with Different Structural Systems”, International Journal of Engineering and Innovative Technology (IJEIT) Volume 8, Issue 9, November 2018. 5. Pavithra S E, Dr. S Vijaya, Kavya H K, “Dynamic Analysis of Hybrid Tall Tube Structural system”, NOVYI MIR Research Journal, ISSN No: 0130-7673, Volume 5, Issue 12, 2020. 6. Mr. Dhruvil Y Patel, Mr. Piyush Jain, Dr. V. R. Patel, “Analysis and Design of RCC Tall-Building with different structural systems”, International Journal of Innovative and Emerging Research in Engineering Volume 4, Issue 5, 2017. 7. Wuit Yi Win Htut, “A Simplified Approach for Optimization of Tube System in Tall Buildings”, International Journal for Innovative Research in
  • 11. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 12 | Dec 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 246 Multidisciplinary Field ISSN – 2455-0620 Volume - 2, Issue - 9, Sept – 2016. 8. Akshay S. Patil, Roshni John, “Performance Evaluation of Unsymmetrical HighRise Building with Different Types of Structural Techniques for Critical Load Condition”, International Journal of Scientific & Engineering Research Volume 11, Issue 4, April-2020. 9. Neelam.Sathyanarayana, G.Srinath, E.Giriprasad Goud, “Seismic Comparison Between the Use of Framed Shear Wall System and Framed Tube System in Tall Buildings”IndianJ.Sci.Res.17(2):429 - 433, 2018. 10. Deepak Suthar, H.S.Chore, P.A. Dode, “High Rise Structure Subjected To Seismic Forces And Its Behavior”, Proceedings of 12 th IRF International Conference, 29th June-2014. 11. Patil. Kiran Kumar, Chandan Kumar. Patnaikuni, Balaji .K.V.G.D, B. Santhosh Kumar, “Seismic Performance of Bundled Tube StructuresinSeismic Zone IV & Zone V of India”, International Journal of Advanced Research in Engineering and Technology (IJARET) Volume 11, Issue 6, June 2020. 12. Jignesha Patel, Roshni J John, “Seismic Analysis of Frame Tube Structure”, International Journal of Scientific & Engineering Research, Volume 6, Issue 12, December-2015. 13. Nimmy Dileep, Renjith R, “Analytical Investigation on the Performance of Tube-In-Tube Structures Subjected to Lateral Loads”, International Journal of Technical Research and Applications, Volume 3, Issue4 July-August 2015. 14. Moreteza Deiranlou, “Evaluation of Seismic Behavior in Building Tube Structures System with Respect to Dense Soil-Structure Interaction Effect”, Open Journal of Civil Engineering, 2015. 15. Shruthi L, S. Vijaya, “Seismic Analysis of Latticed Shell Tube RC Framed Building”, International Journal of Engineering Research & Technology (IJERT) IJERT ISSN: 2278-0181 www.ijert.orgVol.3 Issue 7, July – 2014. 16. Gurudath C, Ganesh Bahadur Khadka, Hafiz Faiz Karim, “Analysis of Multi-Storey Building with and without DiagridSystemUsingETABS”,International Journal Of Innovative Research In Technology, Volume 5 Issue 12, ISSN: 2349-6002, May 2019.