SlideShare a Scribd company logo
FLOW OF PRESENTATION
PROTECTION
SCHEMES
CURRENT
TRANSFORMER
CT DESIGN
REQUIREMENTS FOR
VARIOUS PROTECTION
PROTECTION SCHEMES
PROTECTION SCHEMES
 Over Current Protection
 Earth Fault Protection
 Unit Protection
 Differential protection
 REF protection
 Line differential (Pilot wire)
 Distance Protection
DIFF. PROTECTION
 Monitors an area limited by CTs which
measure incoming & outgoing currents
 Types
 High impedance
 Low impedance (Biased diff.)
HIGH IMPEDANCE DIFF. PROTECTION
 Scheme used for
 Bus bars,
 generator windings and
 Y-connected or auto
transformer windings.
 CTs must be selected
with
 Same ratio
 Same magnetizing curve
(same Vkmin & same Ie at
Vk/2)
 Same Rctmax.
HIGH IMPEDANCE DIFF. PROTECTION
High impd. Busbar diff. REF protection of T/f
HIGH IMPEDANCE DIFF. PROTECTION
Line or cable diff. protection with pilot wires
LOW IMPEDANCE DIFF. PROTECTION
For double bus bar protection
 Used for
 busbar diff. protection
 EHV lines
 C T s can have
different ratios
 Bias is used to correct
small ratio mismatch
 Larger ratios can be
matched using Aux.
CTs
LOW IMPEDANCE DIFF.
SLOPE CHARACTERISTICS
 Have operating characteristics with pickup increasing with higher through
fault currents. This is defined by a slope of the biascharacteristics.
 The higher the slope, the larger is the tolerance of the relay to errorsand
CT saturation.
 Modern numerical relays using special saturation detectors or special
through fault detectors.
 Automatic slope adjustment is achieved with the help of modern
numerical relays using special saturation detectors or special through fault
detectors.
 low slope is maintained (sensitive differential protection)when
When there is no saturation or
when no through fault is detected,
 High slope is maintained (for good stability)when,
Severe saturation
Through fault detection.
HIGH & LOW IMPEDANCE DIFF. PROTECTION
High impd. diff. Low impd. Diff.
Application • Bus bars, • Bus bars
• Generator windings and • EHV lines
• Y-connected or auto transformer
windings
CT Ratio Matching CT ratio to avoid spill current
during healthy state
CTs can have different ratios
CT saturation Knee point voltage is of concern. Saturation can be tolerated, hence Vk is not
voltage of much concern.
Routing of CT All CT connections are looped in the yard CT wires directly to the relay
connection and single cable taken to the relay
CT ckt. supervision Detected by using a 3 phase rectifier relay A current operated auxiliary relay is used to
to effect the summation of the bus wire detect any unbalance sec current for
voltages and short the pilot wire from the supervision of the CT ckts. Current setting
affected phase of the supvn relay must be less than that of
main diff relay
Cost & space req. Less cost & space. Very costly and space consuming, as it
requires large no. of modules & matching
CTs.
CURRENT TRANSFORMER
is an
which
Current
Transformer
instrument
transformer
transforms current
from one level to
another level.
1000/1A,
 e . g .
200/5A Terminal Box
P
P
S
S
Insulator
Secondary winding
Primary winding
Core
CB
Bus Feeder
CURRENT TRANSFORMER
CONNECTION TYPE
CTS – WINDINGS &
CORES
 C T s
have

1
or more primary
windings (with 1 or more
taps), and

1
or more secondary
different
windings on
cores.
• Types of CTcores
•
•
•
Measuring cores
Protection cores
Protection cores forspecial
CT SECONDARY CURRENT RATING
5A Secondary 1A Secondary
Applications 1. Indoor
switchgear
cubicles
2. Higher primary
current ratings.
Outdoor
When secondary
gets open
low peak voltage high peak voltage
Fine turns ratio
adjustment
not possible when
primary rating is
low
Always possible
SATURATION FACTOR
•Ips/Ipn iscalled
•
•
Instrument Security Factor (FS) for the measuring CTs, and
Accuracy Limit Factor (ALF) for the protective CTs.
•These two saturation factors are practically thesame,
•FS or ALF = (Vsat/Vrated)*Inom.
CT - KNEE POINT VOLTAGE
 CT excitationcurve
 is the magnetizing characteristic (plot between secondary applied voltage and the
corresponding magnetizing current)
 Knee point voltage
 Corresponds to the point on excitation curve beyond which an increase of 10% in exciting e.m.f.
produces an increase of 50% in the excitingcurrent
 is defined as the point on the excitation curve where the tangent is at 45 degree to the abscissa.
 represents the point beyond which the CT becomesnon-linear.
Metering class Protection class Protection special
class
Application Measuring Protection Unit Protection
CT Selection Ratio Ratio Ratio
Accuracy class
(0.1,0.2,0.3, 0.5,1,3,5)
Accuracyclass
(5P, 10P, 15P)
Knee Point Voltage
(Vk)
Burden (15,20,30VA) ALF (5, 10, 15, 20, 25,
30)
CT Secondarywinding
resistance (RCT)
corrected to75OC
ISF (3.5.7) Burden (15,20,30VA) Ie (Excitation current)
at Vk or a stated % of
Vk.
CT Selection example: e.g.: 2000/1, Class 0.2,
20VA, ISF – 5
e.g. : 5P20, 40VA, ALF-
5
e.g. : 200/1, PS Class,
Vk > 200V, RCT < 2.0
ohms, Ie < 30mA at
Vk/4
Applicatio
n
IEC 60044-1 IEC 60044-6 IEEE C57.13 / ANSI
Metering 0.1,0.2,0.3,
0.5,1,3,5
0.3, 0.6, 1.2
(burden @ p.f. 0.9)
Protection 5P, 10P, 15P C100, T100,
C200, T200,
C400, T400,
C800, T800
(burden@ p.f. 0.5)
Protection PX
special
TPS, TPX,
TPY, TPZ
CT - REMANANCE
REMANANCE FLUX IS THE VALUE OF FLUX, THAT
WOULD REMAIN IN THE CORE, 3 MINS AFTER
INTERRUPTION OF EXCITING CURRENT OF
SUFFICIENT MAGNITUDE TO INDUCE THE
SATURATION FLUX.
CT
Class
Air gap Remanance Application
TPS No High upto 85% high impedance circulating
current protection
TPX No High upto 85% line protection.
TPY small Low <10% line protection with auto-
reclose.
TPZ Large Negligible 0% special applications such as
differential protection of
large generators
CT SPECIFICATION – ANSI (IEEE STD C57.13-
1993)
CT classes as per ANSI
CT is furnished with excitation
characteristics which can be used
to “Calculate” the CT
C performance.
same as C rating but the knee-
point voltage must be at least 70%
of the secondary terminal voltage
K rating.
the ratio error must be determined
T by ‘Test’.
ANSI
Volt at Burden
100A (ohm)
C100 100 1
C200 200 2
C400 400 4
C800 800 8
•The standard current transformer secondary winding is rated at 5A as per
ANSI standards. (20times of 5A is max. recommended CT secondary current).
CT SATURATION
In case of Rl (lead
resistance)
Two-way
1Φ to
ground
faults
3Φ faults One-way
 A C saturation
 To avoid saturation, the
CT shall developadequate
voltage such that
Vx > If (Rct+Rl+Rb)
 where,




If = Fault current on CT secondary(Amps)
Rct = CT Secondary resistance(Ohms)
Rl = CT Secondary total leadresistance
(Ohms)
Rb =CT secondary connectedburden
(Ohms)
CT SATURATION
 D C saturation
Decaying dc
current introduces
during a fault.
CT SATURATION - EXCURSION OF FLUX
WAVEFORM Φ
Is well within the saturation
limits with AC current waveforms
shoots past the saturation limits
quickly with DC transients
CT SATURATION
 C T shall have enough capacity t
o
develop the following voltage
not to saturate at all for a
combination of AC and DC
transient.
Vx > If (1+X/R) (Rct+Rl+Rb)
Saturation due to DC transient
distorts the AC waveform
output as well
CT SATURATION – HOW TO
AVOID
• C T SATURATION CAN BE AVOIDED
•  B Y INCREASING THE CT RATIO (THEREBY
REDUCING ACTUALSECONDARY CURRENT
DURING FAULT TO LESS THAN 100A)
•  B Y REDUCING THE SECONDARY CONNECTED
BURDEN
 BY REDUCING THE CONNECTED RELAYBURDEN,
 REDUCING THE LEAD RESISTANCE (BY EITHER



reducing the distance between the relay to the CT,
multiple parallel runs of CT leads,
thicker wire sizeetc.)
 M o s t of the faults are ground faults which
tend t
o
have lesser DC offset and associated
saturation issues. The ground faults tend to have
more resistance (lower X/R ratio)
Protection Current
demand
Operati
ng time
Transient
saturation
AC
saturation
Remarks
Time OC 20-30 In NO YES
High-set 1 cycle YES YES high speed of
Phase or Operation is to be
Ground OC ensured.
Distance 1.5 In YES NO Saturation is accepted
Protection after the operation of the
Zone-1 operation.
Differential YES Saturation voltage is of
protection concern
(Biased)
Differential 1 cycle knee point voltage
protection rather is of concern
(High
impedance)
HIGH IMPEDANCE
DIFF.
Protection
setting VR >K x If x (RL + RCT ) (V
olts)
 If = Secondary Fault current (Amps)
 RL = CT secondary lead resistance (Ohms)
 RCT = CT secondary resistance (Ohms)
 K = Margin Factor (=1 for full saturation)
CT
REQUIREMENTS
-for various Protection applications
 High Impedance Differential
scheme Vk≥2.If.(Rct+2.Rl)
 RCT=CT secondary windingresistance
 Rlead= lead resistance of the farthest CT in parallelgroup
 If= Maximum through fault current up to which relay should remain stable (referred to CTsecondary)
 Biased Differential scheme
Vk≥ K.2.IR.(Rct+2.Rl)
 IR=Relay rated current
 K = Constant specified by the manufacturer usually based on conjunction test (the constant is usually
chosen to ensure positive operation of highest differential unit on severe internal fault with extreme
CT saturation)
 Distance Protection scheme
Vk≥ (1+X/R).If.(Rr+Rct+n.Rl)
 X/R = Primary system reactance/resistance ratio (to account for the DC component ofthe
fault current)
 If= Maximum CT secondary current for fault at zone1 reachpoint
 Zrelay= Relay ohmicburden
If
LIMITED
BY
Transformer Maximum through fault Z1%
current
Busbar Maximum through fault switchgear breaking capacity
current
Generator Maximum through fault
current
Xd”
Motor Maximum starting current 6x load current for DOL
Motors
Shunt reactors Maximum charging current X
Short feeders Maximum through fault for fault at busbar
current

More Related Content

What's hot

Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)
Md Abu Jauad Khan Aliv
 
capacitors
capacitorscapacitors
Power Electronics
Power Electronics Power Electronics
Power Electronics
Mirza Baig
 
Current Transformer and Potential Transformer
Current Transformer and Potential TransformerCurrent Transformer and Potential Transformer
Current Transformer and Potential Transformer
Ridwanul Hoque
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
SURAJ PRASAD
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
Dr. Rohit Babu
 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
siddiqui arshad hussain
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
Rahul Aman
 
Electrical introduction
Electrical introductionElectrical introduction
Electrical introduction
snakeaye
 
Chapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentChapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and current
mukund mukund.m
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
jawaharramaya
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
Slides Hub
 
Types of insulator
Types of insulatorTypes of insulator
Types of insulator
adeelshafiq
 
Network theorems by adi
Network theorems by adiNetwork theorems by adi
Network theorems by adi
Prof. Dr. K. Adisesha
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
Ritesh Verma
 
Hv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generationHv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generation
Asha Anu Kurian
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Md Irshad Ahmad
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
Nageswar Rao
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.
R-One Power
 
Power electronics Phase Controlled Rectifiers - SCR
Power electronics   Phase Controlled Rectifiers - SCRPower electronics   Phase Controlled Rectifiers - SCR
Power electronics Phase Controlled Rectifiers - SCR
Burdwan University
 

What's hot (20)

Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)Instrument Transformer (ALIV - BANGLADESH)
Instrument Transformer (ALIV - BANGLADESH)
 
capacitors
capacitorscapacitors
capacitors
 
Power Electronics
Power Electronics Power Electronics
Power Electronics
 
Current Transformer and Potential Transformer
Current Transformer and Potential TransformerCurrent Transformer and Potential Transformer
Current Transformer and Potential Transformer
 
Distribution systems
Distribution systemsDistribution systems
Distribution systems
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 
Electrical introduction
Electrical introductionElectrical introduction
Electrical introduction
 
Chapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and currentChapter 3 Generation of high voltages and current
Chapter 3 Generation of high voltages and current
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Power System Protection course - Part I
Power System Protection course - Part IPower System Protection course - Part I
Power System Protection course - Part I
 
Types of insulator
Types of insulatorTypes of insulator
Types of insulator
 
Network theorems by adi
Network theorems by adiNetwork theorems by adi
Network theorems by adi
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Hv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generationHv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generation
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.
 
Power electronics Phase Controlled Rectifiers - SCR
Power electronics   Phase Controlled Rectifiers - SCRPower electronics   Phase Controlled Rectifiers - SCR
Power electronics Phase Controlled Rectifiers - SCR
 

Similar to CURRENT TRANSFORMER.pptx

Electronics and Communication Engineering
Electronics and Communication EngineeringElectronics and Communication Engineering
Electronics and Communication Engineering
Ekeeda
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
Slides Hub
 
Current transformer (ct)
Current transformer (ct)Current transformer (ct)
Current transformer (ct)
Jay Ranvir
 
Electrical and Electronics Engineering
Electrical and Electronics EngineeringElectrical and Electronics Engineering
Electrical and Electronics Engineering
Ekeeda
 
ECNG 6503 # 3
ECNG 6503 # 3ECNG 6503 # 3
ECNG 6503 # 3
Chandrabhan Sharma
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
Thien Phan Bản
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
BHAGWAN PRASAD
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
Parth Patel
 
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
Malaiyappasamy Sivashanmugam
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx
jackiewalcutt
 
Apparatus Protection Using Relays for Engineering Students
Apparatus Protection Using Relays for Engineering StudentsApparatus Protection Using Relays for Engineering Students
Apparatus Protection Using Relays for Engineering Students
kannan348865
 
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITSANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
MUFEEDA SHAAMZ
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
hiiarindam
 
Introduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basicsIntroduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basics
Md. Rashedul Islam
 
CURRENT VOLTAGE TRANSFORMER BASICS.pdf
CURRENT VOLTAGE TRANSFORMER BASICS.pdfCURRENT VOLTAGE TRANSFORMER BASICS.pdf
CURRENT VOLTAGE TRANSFORMER BASICS.pdf
EMERSON EDUARDO RODRIGUES
 
Current_Transformer .......................
Current_Transformer .......................Current_Transformer .......................
Current_Transformer .......................
IshuKumar59
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
Satish Pydimarla
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
Power System Operation
 
Current Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirementsCurrent Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirements
ssuser39bdb9
 
Trafo arus
Trafo arusTrafo arus
Trafo arus
Novia Putri
 

Similar to CURRENT TRANSFORMER.pptx (20)

Electronics and Communication Engineering
Electronics and Communication EngineeringElectronics and Communication Engineering
Electronics and Communication Engineering
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Current transformer (ct)
Current transformer (ct)Current transformer (ct)
Current transformer (ct)
 
Electrical and Electronics Engineering
Electrical and Electronics EngineeringElectrical and Electronics Engineering
Electrical and Electronics Engineering
 
ECNG 6503 # 3
ECNG 6503 # 3ECNG 6503 # 3
ECNG 6503 # 3
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
 
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
Electrical Current transformer(CT) and Potential transformer(PT) basics for R...
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx
 
Apparatus Protection Using Relays for Engineering Students
Apparatus Protection Using Relays for Engineering StudentsApparatus Protection Using Relays for Engineering Students
Apparatus Protection Using Relays for Engineering Students
 
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITSANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
ANALYSIS OF PHASE SHIFT AND TRANSIENT RESPONSE IN AC CIRCUITS
 
ct pt testing...........................................
ct pt testing...........................................ct pt testing...........................................
ct pt testing...........................................
 
Introduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basicsIntroduction to system_protection-_protection_basics
Introduction to system_protection-_protection_basics
 
CURRENT VOLTAGE TRANSFORMER BASICS.pdf
CURRENT VOLTAGE TRANSFORMER BASICS.pdfCURRENT VOLTAGE TRANSFORMER BASICS.pdf
CURRENT VOLTAGE TRANSFORMER BASICS.pdf
 
Current_Transformer .......................
Current_Transformer .......................Current_Transformer .......................
Current_Transformer .......................
 
CT & PT.pptx
CT & PT.pptxCT & PT.pptx
CT & PT.pptx
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Current Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirementsCurrent Transformers parameter design and graphs - size and design requirements
Current Transformers parameter design and graphs - size and design requirements
 
Trafo arus
Trafo arusTrafo arus
Trafo arus
 

Recently uploaded

Casting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdfCasting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdf
zubairahmad848137
 
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMSA SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
IJNSA Journal
 
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTCHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
jpsjournal1
 
22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt
KrishnaveniKrishnara1
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
ihlasbinance2003
 
spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
Madan Karki
 
New techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdfNew techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdf
wisnuprabawa3
 
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
insn4465
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
SUTEJAS
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
JamalHussainArman
 
Properties Railway Sleepers and Test.pptx
Properties Railway Sleepers and Test.pptxProperties Railway Sleepers and Test.pptx
Properties Railway Sleepers and Test.pptx
MDSABBIROJJAMANPAYEL
 
A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...
nooriasukmaningtyas
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
mamamaam477
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
bijceesjournal
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
IJECEIAES
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
Hitesh Mohapatra
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
Aditya Rajan Patra
 
Question paper of renewable energy sources
Question paper of renewable energy sourcesQuestion paper of renewable energy sources
Question paper of renewable energy sources
mahammadsalmanmech
 
Recycled Concrete Aggregate in Construction Part II
Recycled Concrete Aggregate in Construction Part IIRecycled Concrete Aggregate in Construction Part II
Recycled Concrete Aggregate in Construction Part II
Aditya Rajan Patra
 
Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
co23btech11018
 

Recently uploaded (20)

Casting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdfCasting-Defect-inSlab continuous casting.pdf
Casting-Defect-inSlab continuous casting.pdf
 
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMSA SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMS
 
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTCHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
 
22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt22CYT12-Unit-V-E Waste and its Management.ppt
22CYT12-Unit-V-E Waste and its Management.ppt
 
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
5214-1693458878915-Unit 6 2023 to 2024 academic year assignment (AutoRecovere...
 
spirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptxspirit beverages ppt without graphics.pptx
spirit beverages ppt without graphics.pptx
 
New techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdfNew techniques for characterising damage in rock slopes.pdf
New techniques for characterising damage in rock slopes.pdf
 
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
哪里办理(csu毕业证书)查尔斯特大学毕业证硕士学历原版一模一样
 
Understanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine LearningUnderstanding Inductive Bias in Machine Learning
Understanding Inductive Bias in Machine Learning
 
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptxML Based Model for NIDS MSc Updated Presentation.v2.pptx
ML Based Model for NIDS MSc Updated Presentation.v2.pptx
 
Properties Railway Sleepers and Test.pptx
Properties Railway Sleepers and Test.pptxProperties Railway Sleepers and Test.pptx
Properties Railway Sleepers and Test.pptx
 
A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...A review on techniques and modelling methodologies used for checking electrom...
A review on techniques and modelling methodologies used for checking electrom...
 
Engine Lubrication performance System.pdf
Engine Lubrication performance System.pdfEngine Lubrication performance System.pdf
Engine Lubrication performance System.pdf
 
Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...Comparative analysis between traditional aquaponics and reconstructed aquapon...
Comparative analysis between traditional aquaponics and reconstructed aquapon...
 
Embedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoringEmbedded machine learning-based road conditions and driving behavior monitoring
Embedded machine learning-based road conditions and driving behavior monitoring
 
Generative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of contentGenerative AI leverages algorithms to create various forms of content
Generative AI leverages algorithms to create various forms of content
 
Recycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part IIIRecycled Concrete Aggregate in Construction Part III
Recycled Concrete Aggregate in Construction Part III
 
Question paper of renewable energy sources
Question paper of renewable energy sourcesQuestion paper of renewable energy sources
Question paper of renewable energy sources
 
Recycled Concrete Aggregate in Construction Part II
Recycled Concrete Aggregate in Construction Part IIRecycled Concrete Aggregate in Construction Part II
Recycled Concrete Aggregate in Construction Part II
 
Computational Engineering IITH Presentation
Computational Engineering IITH PresentationComputational Engineering IITH Presentation
Computational Engineering IITH Presentation
 

CURRENT TRANSFORMER.pptx

  • 1.
  • 2. FLOW OF PRESENTATION PROTECTION SCHEMES CURRENT TRANSFORMER CT DESIGN REQUIREMENTS FOR VARIOUS PROTECTION
  • 4. PROTECTION SCHEMES  Over Current Protection  Earth Fault Protection  Unit Protection  Differential protection  REF protection  Line differential (Pilot wire)  Distance Protection
  • 5. DIFF. PROTECTION  Monitors an area limited by CTs which measure incoming & outgoing currents  Types  High impedance  Low impedance (Biased diff.)
  • 6. HIGH IMPEDANCE DIFF. PROTECTION  Scheme used for  Bus bars,  generator windings and  Y-connected or auto transformer windings.  CTs must be selected with  Same ratio  Same magnetizing curve (same Vkmin & same Ie at Vk/2)  Same Rctmax.
  • 7. HIGH IMPEDANCE DIFF. PROTECTION High impd. Busbar diff. REF protection of T/f
  • 8. HIGH IMPEDANCE DIFF. PROTECTION Line or cable diff. protection with pilot wires
  • 9. LOW IMPEDANCE DIFF. PROTECTION For double bus bar protection  Used for  busbar diff. protection  EHV lines  C T s can have different ratios  Bias is used to correct small ratio mismatch  Larger ratios can be matched using Aux. CTs
  • 10. LOW IMPEDANCE DIFF. SLOPE CHARACTERISTICS  Have operating characteristics with pickup increasing with higher through fault currents. This is defined by a slope of the biascharacteristics.  The higher the slope, the larger is the tolerance of the relay to errorsand CT saturation.  Modern numerical relays using special saturation detectors or special through fault detectors.  Automatic slope adjustment is achieved with the help of modern numerical relays using special saturation detectors or special through fault detectors.  low slope is maintained (sensitive differential protection)when When there is no saturation or when no through fault is detected,  High slope is maintained (for good stability)when, Severe saturation Through fault detection.
  • 11. HIGH & LOW IMPEDANCE DIFF. PROTECTION High impd. diff. Low impd. Diff. Application • Bus bars, • Bus bars • Generator windings and • EHV lines • Y-connected or auto transformer windings CT Ratio Matching CT ratio to avoid spill current during healthy state CTs can have different ratios CT saturation Knee point voltage is of concern. Saturation can be tolerated, hence Vk is not voltage of much concern. Routing of CT All CT connections are looped in the yard CT wires directly to the relay connection and single cable taken to the relay CT ckt. supervision Detected by using a 3 phase rectifier relay A current operated auxiliary relay is used to to effect the summation of the bus wire detect any unbalance sec current for voltages and short the pilot wire from the supervision of the CT ckts. Current setting affected phase of the supvn relay must be less than that of main diff relay Cost & space req. Less cost & space. Very costly and space consuming, as it requires large no. of modules & matching CTs.
  • 12.
  • 13. CURRENT TRANSFORMER is an which Current Transformer instrument transformer transforms current from one level to another level. 1000/1A,  e . g . 200/5A Terminal Box P P S S Insulator Secondary winding Primary winding Core CB Bus Feeder
  • 15. CTS – WINDINGS & CORES  C T s have  1 or more primary windings (with 1 or more taps), and  1 or more secondary different windings on cores. • Types of CTcores • • • Measuring cores Protection cores Protection cores forspecial
  • 16. CT SECONDARY CURRENT RATING 5A Secondary 1A Secondary Applications 1. Indoor switchgear cubicles 2. Higher primary current ratings. Outdoor When secondary gets open low peak voltage high peak voltage Fine turns ratio adjustment not possible when primary rating is low Always possible
  • 17. SATURATION FACTOR •Ips/Ipn iscalled • • Instrument Security Factor (FS) for the measuring CTs, and Accuracy Limit Factor (ALF) for the protective CTs. •These two saturation factors are practically thesame, •FS or ALF = (Vsat/Vrated)*Inom.
  • 18. CT - KNEE POINT VOLTAGE  CT excitationcurve  is the magnetizing characteristic (plot between secondary applied voltage and the corresponding magnetizing current)  Knee point voltage  Corresponds to the point on excitation curve beyond which an increase of 10% in exciting e.m.f. produces an increase of 50% in the excitingcurrent  is defined as the point on the excitation curve where the tangent is at 45 degree to the abscissa.  represents the point beyond which the CT becomesnon-linear.
  • 19.
  • 20. Metering class Protection class Protection special class Application Measuring Protection Unit Protection CT Selection Ratio Ratio Ratio Accuracy class (0.1,0.2,0.3, 0.5,1,3,5) Accuracyclass (5P, 10P, 15P) Knee Point Voltage (Vk) Burden (15,20,30VA) ALF (5, 10, 15, 20, 25, 30) CT Secondarywinding resistance (RCT) corrected to75OC ISF (3.5.7) Burden (15,20,30VA) Ie (Excitation current) at Vk or a stated % of Vk. CT Selection example: e.g.: 2000/1, Class 0.2, 20VA, ISF – 5 e.g. : 5P20, 40VA, ALF- 5 e.g. : 200/1, PS Class, Vk > 200V, RCT < 2.0 ohms, Ie < 30mA at Vk/4
  • 21. Applicatio n IEC 60044-1 IEC 60044-6 IEEE C57.13 / ANSI Metering 0.1,0.2,0.3, 0.5,1,3,5 0.3, 0.6, 1.2 (burden @ p.f. 0.9) Protection 5P, 10P, 15P C100, T100, C200, T200, C400, T400, C800, T800 (burden@ p.f. 0.5) Protection PX special TPS, TPX, TPY, TPZ
  • 22. CT - REMANANCE REMANANCE FLUX IS THE VALUE OF FLUX, THAT WOULD REMAIN IN THE CORE, 3 MINS AFTER INTERRUPTION OF EXCITING CURRENT OF SUFFICIENT MAGNITUDE TO INDUCE THE SATURATION FLUX.
  • 23. CT Class Air gap Remanance Application TPS No High upto 85% high impedance circulating current protection TPX No High upto 85% line protection. TPY small Low <10% line protection with auto- reclose. TPZ Large Negligible 0% special applications such as differential protection of large generators
  • 24. CT SPECIFICATION – ANSI (IEEE STD C57.13- 1993) CT classes as per ANSI CT is furnished with excitation characteristics which can be used to “Calculate” the CT C performance. same as C rating but the knee- point voltage must be at least 70% of the secondary terminal voltage K rating. the ratio error must be determined T by ‘Test’. ANSI Volt at Burden 100A (ohm) C100 100 1 C200 200 2 C400 400 4 C800 800 8 •The standard current transformer secondary winding is rated at 5A as per ANSI standards. (20times of 5A is max. recommended CT secondary current).
  • 25. CT SATURATION In case of Rl (lead resistance) Two-way 1Φ to ground faults 3Φ faults One-way  A C saturation  To avoid saturation, the CT shall developadequate voltage such that Vx > If (Rct+Rl+Rb)  where,     If = Fault current on CT secondary(Amps) Rct = CT Secondary resistance(Ohms) Rl = CT Secondary total leadresistance (Ohms) Rb =CT secondary connectedburden (Ohms)
  • 26. CT SATURATION  D C saturation Decaying dc current introduces during a fault.
  • 27. CT SATURATION - EXCURSION OF FLUX WAVEFORM Φ Is well within the saturation limits with AC current waveforms shoots past the saturation limits quickly with DC transients
  • 28. CT SATURATION  C T shall have enough capacity t o develop the following voltage not to saturate at all for a combination of AC and DC transient. Vx > If (1+X/R) (Rct+Rl+Rb) Saturation due to DC transient distorts the AC waveform output as well
  • 29. CT SATURATION – HOW TO AVOID • C T SATURATION CAN BE AVOIDED •  B Y INCREASING THE CT RATIO (THEREBY REDUCING ACTUALSECONDARY CURRENT DURING FAULT TO LESS THAN 100A) •  B Y REDUCING THE SECONDARY CONNECTED BURDEN  BY REDUCING THE CONNECTED RELAYBURDEN,  REDUCING THE LEAD RESISTANCE (BY EITHER    reducing the distance between the relay to the CT, multiple parallel runs of CT leads, thicker wire sizeetc.)  M o s t of the faults are ground faults which tend t o have lesser DC offset and associated saturation issues. The ground faults tend to have more resistance (lower X/R ratio)
  • 30.
  • 31. Protection Current demand Operati ng time Transient saturation AC saturation Remarks Time OC 20-30 In NO YES High-set 1 cycle YES YES high speed of Phase or Operation is to be Ground OC ensured. Distance 1.5 In YES NO Saturation is accepted Protection after the operation of the Zone-1 operation. Differential YES Saturation voltage is of protection concern (Biased) Differential 1 cycle knee point voltage protection rather is of concern (High impedance)
  • 32. HIGH IMPEDANCE DIFF. Protection setting VR >K x If x (RL + RCT ) (V olts)  If = Secondary Fault current (Amps)  RL = CT secondary lead resistance (Ohms)  RCT = CT secondary resistance (Ohms)  K = Margin Factor (=1 for full saturation)
  • 33. CT REQUIREMENTS -for various Protection applications  High Impedance Differential scheme Vk≥2.If.(Rct+2.Rl)  RCT=CT secondary windingresistance  Rlead= lead resistance of the farthest CT in parallelgroup  If= Maximum through fault current up to which relay should remain stable (referred to CTsecondary)  Biased Differential scheme Vk≥ K.2.IR.(Rct+2.Rl)  IR=Relay rated current  K = Constant specified by the manufacturer usually based on conjunction test (the constant is usually chosen to ensure positive operation of highest differential unit on severe internal fault with extreme CT saturation)  Distance Protection scheme Vk≥ (1+X/R).If.(Rr+Rct+n.Rl)  X/R = Primary system reactance/resistance ratio (to account for the DC component ofthe fault current)  If= Maximum CT secondary current for fault at zone1 reachpoint  Zrelay= Relay ohmicburden
  • 34. If LIMITED BY Transformer Maximum through fault Z1% current Busbar Maximum through fault switchgear breaking capacity current Generator Maximum through fault current Xd” Motor Maximum starting current 6x load current for DOL Motors Shunt reactors Maximum charging current X Short feeders Maximum through fault for fault at busbar current