This document analyzes the lighting, acoustics, and noise levels of a proposed silent reading area and admin office. For the silent area, daylight factor calculations show good natural lighting levels but potential glare issues. Artificial lighting calculations determine 28 downlights are needed. Sound pressure level measurements exceed requirements, but double layered glass and acoustic panels are proposed to mitigate noise. Reverberation time and sound reduction index calculations are also provided to analyze acoustics. For the admin office, daylight is determined to be fair but not adequate, requiring 8 downlights for artificial lighting. Analyses of lighting and acoustics are also provided to ensure compliance with standards.
Asian Architecture: 8D House Case Study Paperdouglasloon
Taylor's University Lakeside Campus
School of Architecture, Building & Design
Bachelor of Science (Hons) in Architecture
Asian Architecture (ARC 60403)
Project Part B: Case Study Paper
Taylor's University Lakeside Campus
School of Architecture, Building and Design
Foundation of Natural and Built Environments
April Intake 2013
Introduction to the Construction Industry
Taylor's University Lakeside Campus
School of Architecture, Building and Design
Foundation of Natural and Built Environments
April Intake 2013
Elements of Natural and Built Environment
Taylor's University Lakeside Campus
School of Architecture, Building and Design
Foundation of Natural and Built Environments
April Intake 2013
Elements of Natural and Built Environment
Taylor's University Lakeside Campus
School of Architecture, Building and Design
Foundation of Natural and Built Environments
April Intake 2013
Creative Thinking Skills
Taylor's University Lakeside Campus
School of Architecture, Building and Design
Foundation of Natural and Built Environments
April Intake 2013
Creative Thinking Skills
Techniques to optimize the pagerank algorithm usually fall in two categories. One is to try reducing the work per iteration, and the other is to try reducing the number of iterations. These goals are often at odds with one another. Skipping computation on vertices which have already converged has the potential to save iteration time. Skipping in-identical vertices, with the same in-links, helps reduce duplicate computations and thus could help reduce iteration time. Road networks often have chains which can be short-circuited before pagerank computation to improve performance. Final ranks of chain nodes can be easily calculated. This could reduce both the iteration time, and the number of iterations. If a graph has no dangling nodes, pagerank of each strongly connected component can be computed in topological order. This could help reduce the iteration time, no. of iterations, and also enable multi-iteration concurrency in pagerank computation. The combination of all of the above methods is the STICD algorithm. [sticd] For dynamic graphs, unchanged components whose ranks are unaffected can be skipped altogether.
Opendatabay - Open Data Marketplace.pptxOpendatabay
Opendatabay.com unlocks the power of data for everyone. Open Data Marketplace fosters a collaborative hub for data enthusiasts to explore, share, and contribute to a vast collection of datasets.
First ever open hub for data enthusiasts to collaborate and innovate. A platform to explore, share, and contribute to a vast collection of datasets. Through robust quality control and innovative technologies like blockchain verification, opendatabay ensures the authenticity and reliability of datasets, empowering users to make data-driven decisions with confidence. Leverage cutting-edge AI technologies to enhance the data exploration, analysis, and discovery experience.
From intelligent search and recommendations to automated data productisation and quotation, Opendatabay AI-driven features streamline the data workflow. Finding the data you need shouldn't be a complex. Opendatabay simplifies the data acquisition process with an intuitive interface and robust search tools. Effortlessly explore, discover, and access the data you need, allowing you to focus on extracting valuable insights. Opendatabay breaks new ground with a dedicated, AI-generated, synthetic datasets.
Leverage these privacy-preserving datasets for training and testing AI models without compromising sensitive information. Opendatabay prioritizes transparency by providing detailed metadata, provenance information, and usage guidelines for each dataset, ensuring users have a comprehensive understanding of the data they're working with. By leveraging a powerful combination of distributed ledger technology and rigorous third-party audits Opendatabay ensures the authenticity and reliability of every dataset. Security is at the core of Opendatabay. Marketplace implements stringent security measures, including encryption, access controls, and regular vulnerability assessments, to safeguard your data and protect your privacy.
Explore our comprehensive data analysis project presentation on predicting product ad campaign performance. Learn how data-driven insights can optimize your marketing strategies and enhance campaign effectiveness. Perfect for professionals and students looking to understand the power of data analysis in advertising. for more details visit: https://bostoninstituteofanalytics.org/data-science-and-artificial-intelligence/
1. 0
School of Architecture, Building and Design
Modern Architecture Studies in Southeast Asia (MASSA) Research Unit
Bachelor of Science (Honours) (Architecture)
Building Science 2 [BLD 61303 / ARC 3413]
PROJECT 02
INTEGRATION PROJECT
Student : Phua Jing Sern 0314572
Tutor : Mr. Sivaraman Kuppusamy
3. 2
1.0Lighting
1.1 Silent Area
1.1.1 Daylight
According to MS1525: Daylight Factor, DF
Zone Daylight Factors (%) Distribution
Very Bright > 6 Very large with thermal and glare
problems
Bright 3 - 6 Good
Average 1 - 3 Fair
Dark 0 - 1 Poor
4. 3
Daylight Factor Calculation
Floor Area (m2) 7m x 13m = 91
Area of façadeexposed to sunlight
(m2)
50m
Area of skylight 0
Exposed façade & skylightarea to
floor area ratio / Daylightfactor, DF
(50+0)/91
= 0.55
= 0.55 x100%
= 5.5%
Natural Illumination Calculation
Illuminance Example
120,000 lux Very Bright Sunlight
110,000 lux Bright Sunlight
20,000 lux Clear Sky
1000 – 2000 lux Overcastday
400 lux Sunrise/ Sunset on clear day
< 200 lux Midday
40 lux Fully overcast
<1 lux Sunset, stormcloud
E External = 20,000 lux
DF = E internal / E external x 100
5.5 = E internal / 20,000 x100
E internal = 5.5 x 20,000 /100
= 1100 lux
The silent area has a daylight factor of 5.5% and natural illumination of 1100 lux. Based on
the requirements of MS 1525, this space has good daylight distribution as the value is in
between 3-6%, but the illuminance value is higher than the required value of 300 lux. This
can cause thermal and glare problems. Low-e coatings of the glass panels are proposed to
minimize the penetration of ultraviolet and infrared rays into spaces.
5. 4
1.1.2 Artificial light
Lumen Method Calculation
Dimension of room( L x W) 7m x 13m
Total floor Area (m2) 91
Room cavity height (m) 4
Reflectance values Ceiling = 0.7
Wall = 0.5
Floor = 0.3
Room index, K K = (7 x 13) / 4(7+13)
= 1
Utilization Factor, UF 0.38
Maintenance Factor, MF 0.8
IlluminanceRequirement 300 - 500
Number of Luminaries N =
300 𝑥 91
4000 𝑥 (0.8𝑥0.38)
= 22.45
~ 23 bulbs
Spacing to height ration (SHR)
SHR =
1
4
x √
91
23
= 0.49
SHR =
𝑆
4
= 0.49
S = 1.96
Fitting Layout Fitting required along 7m wall
= 7/1.96 =3.5
= 4 rows
Fitting required along 13mwall
= 13/1.96 =6.6
= 7 rows
Model DN570B
Input 230 or 240 v / 50-60Hz
Lumen 4000
Weight 2.2 kg
Power 36w (3000k)
6. 5
Fitting layout and SPALI
28 fluorescent lamps are used to illuminate the quiet reading area to achieve the minimum
illuminance of 300 lux stated by MS 1525.With sufficient illuminance, users are able to
utilize the space with comfort.
Referring to the daylight values obtained above, the silent area has a good daylight factor of
5.5%. The artificial lightings calculation also shows a result of the usage of 28 down lights to
illuminate the silent area. PSALI is applied whereby the lightings are controlled with 2
switches; one that is closest to the window wall whereby it can be switched off during the
day, while the rest can be operate with another switch when necessary as well.
7. 6
1.2 Admin Office
1.2.1 Daylight
According to MS1525: Daylight Factor, DF
Zone Daylight Factors (%) Distribution
Very Bright > 6 Very large with thermal and glare
problems
Bright 3 - 6 Good
Average 1 - 3 Fair
Dark 0 - 1 Poor
8. 7
Daylight Factor Calculation
Floor Area (m2) 3.5m x 6m = 21
Area of façade exposed to sunlight (m2) 4
Area of skylight 0
Exposed façade & skylight area to floor area
ratio / Daylight factor, DF
(4+0)/21
= 0.19
= 0.19 x 100%
= 1.9%
Natural Illumination Calculation
Illuminance Example
120,000 lux Very Bright Sunlight
110,000 lux Bright Sunlight
20,000 lux Clear Sky
1000 – 2000 lux Overcast day
400 lux Sunrise / Sunset on clear day
< 200 lux Midday
40 lux Fully overcast
<1 lux Sunset, storm cloud
E External = 20,000 lux
DF = E internal / E external x 100
1.9 = E internal / 20,000 x100
E internal = 1.9 x 20,000 /100
= 380 lux
The admin office has a daylight factor of 1.9% and natural illumination of 380 lux. Based on
the requirements of MS 1525, this is considered as fair yet not adequately lit. Therefore,
artificial lighting is required for the space. The illuminance value fits within the MS 1525
requirement of 300 – 400 lux.
9. 8
1.2.2 Artificial light
Lumen Method Calculation
Dimension of room( L x W) 3.5mx 6m
Total floor Area (m2) 21
Room cavity height (m) 4
Reflectance values Ceiling = 0.7
Wall = 0.5
Floor = 0.3
Room index, K K = (3.5 x 6) / 4(3.5+6)
= 0.6
Utilization Factor, UF 0.27
Maintenance Factor, MF 0.8
IlluminanceRequirement 300 - 500
Number of Luminaries N =
300 𝑥 21
5000 𝑥 (0.8𝑥0.27)
= 5.83
~ 6
Spacing to height ration (SHR)
SHR =
1
4
x √
21
6
= 0.46
SHR =
𝑆
4
= 0.46
S = 1.84
Fitting Layout Fitting required along 3.5mwall
= 3.5/1.84 =1.9
= 2 rows
Fitting required along 6m wall
= 6/1.84 =3.2
= 4 rows
Model LuxiLED G2
Input 110 or 240 v / 50-60Hz
Lumen 5000
Weight 4.6
Power 32W (3000k)
10. 9
Fitting Layout and PSALI
8 down lights are used to illuminate the admin office to achieve the minimum illuminance of
300 lux stated by MS 1525.With sufficientilluminance,office staffs areableto utilizethe space
with comfort.
Referring to the daylight values obtained above, the admin office has a fair yet not adequately
lit daylight factor of 1.9%. Thus the artificial lightings calculation also shows a need of the
usage of 8 down lights to illuminate the admin office. PSALI is applied whereby the lightings
are controlled with 2 switches; one half controls the help desk and the corridor, while the
other half controls the work desks of the staffs. To achieve a uniform lighting and to follow
the requirements of MS 1525, both switches need to be turned on during operating hours.
11. 10
2.0 Acoustic
2.1 Silent Area
2.1.1 SPL – Sound Pressure Level
Sound Pressure Level Formula:
SPL = 10log10
𝐼
𝐼𝑥
SPL = sound pressure level (dB),
I = sound power (intensity)(Watts)
Ix = reference power (Ix is usually taken as 1x10-12 watts)
Peak Hour (Back Alley)
Highest Reading: 70 dB (Moderate sound)
Lowest Reading: 55 dB (Quiet sound)
Highest Reading:
70 = 10log10
𝐼
𝐼𝑥
Antilog 7 =
𝑙
1𝑥10 ^−12
1 X 10^7 =
𝑙
1𝑥10^−12
L = 10^7 x (1x10^-12)
L = 1 x [10^7 + (-12))
L = 1 x 10^-5
Lowest Reading:
55 = 10log10
𝐼
𝐼𝑥
Antilog 5.5 =
𝑙
1𝑥10 ^−12
1 X 10^5.5 =
𝑙
1𝑥10 ^−12
L = 10^5.5 x (1x10^-12)
L = 1 x [10^5.5+ (-12))
L = 1 x 10^-6.5
Total Intensities:
Total intensities, I
= (1x10^-5) + (1 x 10^-6.5)
= 1.03x10^-5
Combined SPL:
SPL = 10log10
𝐼
𝐼𝑥
= 10log10
1.03𝑥10^−5
𝐼𝑥10 ^−12
= 70 dB
12. 11
Non -Peak Hour (Back Alley)
Highest Reading: 55 dB (Quiet sound)
Lowest Reading: 45 dB (Very Quiet sound)
Highest Reading:
55 = 10log10
𝐼
𝐼𝑥
Antilog 5.5 =
𝑙
1𝑥10^−12
1 X 10^5.5 =
𝑙
1𝑥10^−12
L = 10^5.5 x(1x10^-12)
L = 1 x [10^5.5+(-12))
L = 1 x 10^-6.5
LowestReading:
45 = 10log10
𝐼
𝐼𝑥
Antilog 4.5 =
𝑙
1𝑥10^−12
1 X 10^4.5 =
𝑙
1𝑥10^−12
L = 10^4.5 x(1x10^-12)
L = 1 x [10^4.5+(-12))
L = 1 x 10^-7.5
The noise criteria for a reading area is within the range of 35-40. According to the calculation
above, the combined sound pressure level around the silent area during peak and non-peak
hours are 70dB and 55 dB respectively, which exceeds the noise criteria for a reading area.
This can be solved by proposing double layered channel glass which consists of an insulation
layer, preventing the transmission of sound through the vibration of air.
Total Intensities:
Total intensities, I
= (1x10^-6.5) +(1 x 10^-7.5)
= 3.48x10^-7
Combined SPL:
SPL = 10log10
𝐼
𝐼𝑥
= 10log10
3.48𝑥10^−7
𝐼𝑥10^−12
= 55 dB
14. 13
Material Absorption Coefficient under 500 Hz, with 15 users
Building
Component
Material Area S ( m2) Absorption
Coefficient (a)
Sound Absorption
( SA)
Wall Concrete 73.2 0.02 1.46
Glass 47 0.06 2.82
Floor Carpet 91 0.30 27.3
Door Timber 2 0.13 0.26
Ceiling Concrete 91 0.02 1.82
Furniture Desk 18 0.45 8.1
Padded Chair 6 0.77 4.62
Fabric Barrel 96 0.30 28.8
Users - 15 0.46 6.9
Total Absorption 81.88
RT= (0.16 X 364) /81.88
= 0.71s
Material Absorption Coefficient under 2000 Hz, with 15 users
Building
Component
Material Area S ( m2) Absorption
Coefficient (a)
Sound Absorption
( SA)
Wall Concrete 73.2 0.02 1.46
Glass 47 0.03 1.41
Floor Carpet 91 0.50 45.5
Door Timber 2 0.10 0.2
Ceiling Concrete 91 0.02 1.82
Furniture Desk 18 0.45 8.1
Padded Chair 6 0.77 4.62
Fabric Barrel 96 0.50 48
Users - 15 0.51 7.62
Total Absorption 118.73
RT= (0.16 X 364) /118.73
= 0.49s
The reverberation time required for a library reading space is 0.4 – 0.6 seconds. Based on the
calculation, the reverberation of the space under 500 Hz and 2000 Hz is 0.71s and 0.49s
respectively. As they slightly differ from the requirement, acoustic panels are introduced to
amend the issue.
15. 14
2.1.3 Sound Reduction Index (Silent Area)
Volume of Space
V = L x W x H
V = 13m x 7m x 4m
V = 364m3
Assuming that the noise level of a Silent Area is 40 dB, noise level of the external is 75dB. The
sound reduction index of the wall should 75dB- 40dB = 35 dB.
16. 15
Building
Component Material Surface Area
(m2
SRI
( Decibels)
Transmission
Coefficient
( T )
Wall Concrete 73.2 46 2.51 𝑥 10 −5
Wall Glass 47 35 3.16 𝑥 10 −4
Door Plywood 2 31 7.94 𝑥 10 −4
Concrete
SRI = 10 Log (1/T)
46 = 10 log (1/T)
3.98 𝑥 10 4
= 1 / T
T = 2.51 𝑥 10 −5
Glass
SRI = 10 Log (1/T)
35 = 10 log (1/T)
3.16 𝑥 10 3
= 1 / T
T = 3.16 𝑥 10 −4
Timber
SRI = 10 Log (1/T)
31 = 10 log (1/T)
10 3.1
= 10 log10 (1/T)
T = 7.94 𝑥 10 −4
The overall transmission loss from the back lane to the silent area is 38.24 dB. Based on the
previous assumption, according to the noise criteria environment perception, 35 dB is
categorized as whispering sound. Thus the space has an ideal value for a silent reading area
where users can focus on their reading with ease.
Average Transmission Coefficient
= [ 73.2 x ( 2.51 𝑥 10 −5
) ] + [ 47 x
( 3.16 𝑥 10 −4
) ] + [ 2 x (7.94 𝑥 10 −4
) ] /
( 73.2 + 47 + 2)
= 1.50 𝑥 10 −4
Overall SRI
= 10 Log ( 1 / 1.50 𝑥 10 −4
)
= 38.24 Db
External Sound PressureLevel
= 75dB– 38.24dB
= 36.76 dB
17. 16
2.2 Admin Office
2.2.1 SPL – Sound Pressure Level
Sound Pressure Level Formula:
SPL = 10log10
𝐼
𝐼𝑥
SPL = sound pressure level (dB),
I = sound power (intensity)(Watts)
Ix = reference power (Ix is usually taken as 1x10-12 watts)
Peak Hour (Back Alley)
Highest Reading: 70 dB (Moderate sound)
Lowest Reading: 55 dB (Quiet sound)
Highest Reading:
70 = 10log10
𝐼
𝐼𝑥
Antilog 7 =
𝑙
1𝑥10 ^−12
1 X 10^7 =
𝑙
1𝑥10^−12
L = 10^7 x (1x10^-12)
L = 1 x [10^7 + (-12))
L = 1 x 10^-5
Lowest Reading:
55 = 10log10
𝐼
𝐼𝑥
Antilog 5.5 =
𝑙
1𝑥10 ^−12
1 X 10^5.5 =
𝑙
1𝑥10 ^−12
L = 10^5.5 x (1x10^-12)
L = 1 x [10^5.5+ (-12))
L = 1 x 10^-6.5
Total Intensities:
Total intensities, I
= (1x10^-5) + (1 x 10^-6.5)
= 1.03x10^-5
Combined SPL:
SPL = 10log10
𝐼
𝐼𝑥
= 10log10
1.03𝑥10^−5
𝐼𝑥10 ^−12
= 70 dB
18. 17
Non -Peak Hour (Back Alley)
Highest Reading: 55 dB (Quiet sound)
Lowest Reading: 45 dB (Very Quiet sound)
Highest Reading:
55 = 10log10
𝐼
𝐼𝑥
Antilog 5.5 =
𝑙
1𝑥10^−12
1 X 10^5.5 =
𝑙
1𝑥10^−12
L = 10^5.5 x(1x10^-12)
L = 1 x [10^5.5+(-12))
L = 1 x 10^-6.5
LowestReading:
45 = 10log10
𝐼
𝐼𝑥
Antilog 4.5 =
𝑙
1𝑥10^−12
1 X 10^4.5 =
𝑙
1𝑥10^−12
L = 10^4.5 x(1x10^-12)
L = 1 x [10^4.5+(-12))
L = 1 x 10^-7.5
The noise criteria for an admin office is within the range of 50 - 60. According to the
calculation above, the combined sound pressure level around the silent area during peak and
non-peak hours are 70dB and 55 dB respectively, which exceeds the noise criteria for a
reading area. This can be solved by proposing double layered channel glass which consists of
an insulation layer, preventing the transmission of sound through the vibration of air, or a
double façade which acts as a sound barrier.
Total Intensities:
Total intensities, I
= (1x10^-6.5) +(1 x 10^-7.5)
= 3.48x10^-7
Combined SPL:
SPL = 10log10
𝐼
𝐼𝑥
= 10log10
3.48𝑥10^−7
𝐼𝑥10^−12
= 55 dB
20. 19
Material Absorption Coefficient under 500 Hz , with 5 users
Building
Component
Material Area S ( m2) Absorption
Coefficient (a)
Sound Absorption
( SA)
Wall Concrete 65.6 0.02 1.31
Glass 4 0.06 0.24
Floor Carpet 21 0.30 6.3
Door Timber 2 0.13 0.26
Ceiling Concrete 21 0.02 0.42
Furniture Timber Desk 5 0.15 0.75
Padded Chair 3 0.77 2.31
Users - 5 0.46 2.3
Total Absorption 13.39
RT= (0.16 X 84) / 13.39
= 1s
Material Absorption Coefficient under 2000 Hz , with 5 users
Building
Component
Material Area S ( m2) Absorption
Coefficient (a)
Sound Absorption
( SA)
Wall Concrete 65.6 0.02 1.31
Glass 4 0.03 0.12
Floor Carpet 21 0.50 10.5
Door Timber 2 0.10 0.2
Ceiling Concrete 21 0.02 0.42
Furniture Timber Desk 5 0.15 0.75
Padded Chair 3 0.77 2.31
Users - 5 0.51 2.55
Total Absorption 18.16
RT= (0.16 X 84) / 18.16
= 0.74s
The reverberation time required for a library reading space is 0.6 – 0.8 seconds. Based on the
calculation, the reverberation of the space under 500 Hz and 2000 Hz is 1s and 0.7s
respectively. Acoustic panels are introduced to amend the issue.
21. 20
2.2.3 Sound Reduction Index (Admin Office)
Volume of Space
V = L x W x H
V = 6m x 3.5m x 4m
V = 84m3
Assuming that the noise level of an admin office is 40 dB, noise level of the external is 75dB.
The sound reduction index of the wall should 75dB- 40dB = 35 dB.
22. 21
Building
Component Material Surface Area
(m2
SRI
( Decibels)
Transmission
Coefficient
( T )
Wall Concrete 65.6 46 2.51 𝑥 10 −5
Wall Glass 4 35 3.16 𝑥 10 −4
Door Plywood 2 31 7.94 𝑥 10 −4
Concrete
SRI = 10 Log (1/T)
46 = 10 log (1/T)
3.98 𝑥 10 4
= 1 / T
T = 2.51 𝑥 10 −5
Glass
SRI = 10 Log (1/T)
35 = 10 log (1/T)
3.16 𝑥 10 3
= 1 / T
T = 3.16 𝑥 10 −4
Timber
SRI = 10 Log (1/T)
31 = 10 log (1/T)
10 3.1
= 10 log10 (1/T)
T = 7.94 𝑥 10 −4
The overall transmission loss from the back lane to the admin office is 33.97 dB. Based on the
previous assumption, according to the noise criteria environment perception, the admin
officeexceeded the noise criteria, resulting in distracting noises interfering work environment.
This can be solved by having double façade of wooden shutters which can filter and deflect
noise coming from the back lane.
AverageTransmission Coefficient
= [65.6 x ( 2.51 𝑥 10 −5
) ] + [ 4 x
( 3.16 𝑥 10 −4
) ] + [ 2 x (7.94 𝑥 10 −4
) ] /
( 65.6 + 4 + 2)
= 4.00 𝑥 10 −4
OverallSRI
= 10 Log ( 1 / 4.00 𝑥 10 −4
)
= 33.97 Db
External Sound PressureLevel
= 75dB– 33.97dB
= 41.03 dB
23. 22
3.0 References
1. Cavanough, W.J. & Wikes, J.A. (1998). ArchitecturalAcoustics: Principles
and Practice. New York: Wiley and Sons.
2. Absorption Coefficient Building Material Finishes – Sengpiel Berlin (n.d.)
Retrieved November 26 2015 from
http://www.sengpielaudio.com/calculator-RT60Coeff.htm
3. ACE Lamps Lighting (n.d.) Retreived December 6 2015 from
http://www.sengpielaudio.com/calculator-RT60Coeff.htm
4. Ir Izdihar, A. (n.d.) UBBL 2012 Amendments on EE Bylaw 38A and MS
1525:2014. Retrieved December 6 2016 from
http://www.sengpielaudio.com/calculator-RT60Coeff.htm
5. Ir Izdihar, A. (n.d.) UBBL 2012 Amendments on EE Bylaw 38A and MS
1525:2014. Retrieved December 6 2016 from
http://www.sengpielaudio.com/calculator-RT60Coeff.htm