This document discusses transformer switching operations using vacuum circuit breakers (VCBs) and the potential for overvoltage transients. It investigates how LC filters connected at the low voltage side of a transformer in a photovoltaic power plant can affect switching operations and influence transient overvoltages. Simulation results showed that a LC filter rated at 200 μH and 25 μF could successfully mitigate overvoltage transients from transformer de-energization by reducing the rate of rise of the transient recovery voltage. The paper concludes LC filters connected at the low voltage side may be a potential solution for mitigating switching overvoltage transients.