STADIUM



No.                           Description                               Unit       Qty.


      DIVISION 16 - ELECTRICAL (Cont'd)
      16500 - Light Fixtures
      Supply, install and connect the following light as shown in
      the electrical drawings, BOQ, specifications as mentioned
      in the schedule of points.Installation shall be complete in all
      respects such as bulbs, tubes,reflector, control gear,
      connector box,earthing,wiring,foundation,support etc. Light
      fixtures to have all the auxillaries as required for the proper
      and complete installation.For reflected ceiling refer to the
      architectural drawings showing the light fixture. No light
      fixtures are to be approved (even the specified one) unless
      the sample is provided.The engineer shall see the fixture
      and verify the suitability of the fixture for the type of false
      ceiling, location and method of installation before giving
      final approval.

      NOTE: 1. All fluorescent light fixtures shall be provided with
      electronic control gear. 2. All light fittings are to be
      provided with dimmable control gears unless otherwise
      specified. 3.For emergency lightings, fixtures are to be
      intergrated with battery backup(3hrs maintained) and
      selectively installed to match with KFD regulations.

A     Type A                                                               54      No.
B     Type C                                                              106      No.
C     Type D                                                               13      No.
D     Type F                                                              166      No.
E     Type G                                                               89      No.
 F    Type H                                                              177      No.
G     Type J                                                              197      No.
H     Type K                                                                   9   No.
 J    Type M                                                               42      No.
K     Type N                                                               20      No.
 L    Type P                                                               40      No.
M     Type U                                                               82      No.
                              III 4-2/16/14R
      DIVISION 16 - ELECTRICAL (Cont'd)
      16500 - Light Fixtures
A     Type V                                                              531      No.
B     Type W                                                               34      No.
      Type AB (COVE LIGHT TO BE LAYED PARALLALY IN TWO
C                                                                         670       m
      LINE)
D     Type AC                                                                  3   No.
E     Type AF                                                              14      No.
F   Type AG                                                   16   No.
G   Type AH                                                   32   No.
H   Type AJ                                                    6   No.
J   Type AK                                                   40   No.
K   Type AL                                                   12   No.
L   Type AM                                                  136   No.
M   Type AN                                                   16   No.
N   Type AP                                                   56   No.
P   Type AQ                                                   78   No.
Q   Type AR                                                   38   No.
R   Type AS                                                   84   No.
S   Type AT                                                   88   No.
T   Type AU                                                   21   No.
U   Type AV                                                   12   No.
V   AM1                                                        6   No.
                         III 4-2/16/15R
    DIVISION 16 - ELECTRICAL (Cont'd)

    16500 - Light Fixtures Intergrated with Battery Backup

A   Type A                                                    35   No.
B   Type C                                                    14   No.
C   Type D                                                    92   No.
D   Type F                                                    54   No.
E   Type G                                                    15   No.
F   Type H                                                    34   No.
G   Type M                                                    12   No.
H   Type U                                                    12   No.
J   Type V                                                   164   No.
K   Type AC                                                    2   No.
L   Type AF                                                    4   No.
M   Type AV                                                    4   No.
N   Type AT                                                    8   No.
P   Type-Exit                                                 67   No.
                         III 4-2/16/16R
Unit Rate   Amount
 KD/Fils    KD/Fils
INDOOR SPORT FACILITY



                                                                                  Unit Rate
                                                                                         Amount
No.                        Description                            Unit    Qty.
                                                                                 KD/Fils KD/Fils

      DIVISION 16 - ELECTRICAL (Cont'd)
      16500 - Light Fixtures

      Supply, install and connect the following light as
      shown in the electrical drawings, BOQ,
      specifications as mentioned in the schedule of
      points.Installation shall be complete in all respects
      such as bulbs, tubes,reflector, control gear,
      connector box,earthing,wiring,foundation,support
      etc. Light fixtures to have all the auxillaries as
      required for the proper and complete installation.For
      reflected ceiling refer to the architectural drawings
      showing the light fixture. No light fixtures are to be
      approved (even the specified one) unless the
      sample is provided.The engineer shall see the
      fixture and verify the suitability of the fixture for the
      type of false ceiling, location and method of
      installation before giving final approval.


      NOTE: 1. All fluorescent light fixtures shall be
      provided with electronic control gear. 2. All light
      fittings are to be provided with dimmable control
      gears unless otherwise specified. 3.For emergency
      lightings, fixtures are to be intergrated with battery
      backup(3hrs maintained) and selectively installed to
      match with KFD regulations.

A     Type A                                                         92   No.
B     Type B                                                         26   No.
C     Type C                                                         42   No.
D     Type D                                                         12   No.
E     Type F                                                        190   No.
 F    Type G                                                        195   No.
G     Type H                                                        157   No.
H     Type J                                                        120   No.
                           III 4-3/16/13R
      DIVISION 16 - ELECTRICAL (Cont'd)
      16500 - Light Fixtures
A     Type K                                                         30   No.
B     Type L                                                         58   No.
C     Type M                                                         90   No.
D   Type N                                               275   No.
E   Type P                                               92    No.
F   Type Q1                                              48    No.
G   Type R                                                8    No.
H   Type S                                               63    No.
J   Type T                                               262   No.
K   Type U                                               34    No.
L   Type V                                               334   No.
M   Type V1                                              16    No.
N   Type W                                               31    No.
P   Type W3                                              12    No.
Q   Type Z(Each strip with 11 LED'S)                     60    No.
                      III 4-3/16/14R
    DIVISION 16 - ELECTRICAL (Cont'd)
    16500 - Light Fixtures
A   Type AA                                              29    No.
    Type AB (COVE LIGHT TO BE LAYED PARALLALY IN
B                                                        650   m
    TWO LINES)
C   Type AC                                              22    No.
D   Type AD                                              12    No.
E   Type AG                                              83    No.
F   Type AU                                               8    No.
G   Type AW                                              91    No.
H   Type AY                                              90    No.
J   Type F3                                              142   No.
K   Type UW (Underwater Light Fittings)                  62    No.
L   Type Y                                               30    No.
M   Type C1                                              210   No.
    Note: A combination of 3 nos. of Type F3 shall be
    read as Type FL6 and combination of 4 nos. of Type
    F3 shall be read as Type FL7. Refer Light Fixtures
    Specifications for details.
                        III 4-3/16/15R
    DIVISION 16 - ELECTRICAL (Cont'd)
    16500 - Light Fixtures Intergrated with Battery
    Backup
A   Type A                                               30    No.
B   Type B                                               20    m
C   Type C                                                6    No.
D   Type D                                               52    No.
E   Type C1                                              14    No.
F   Type F                                               91    No.
G   Type G                                               31    No.
H   Type H                                               50    No.
J   Type M                        35   No.
K   Type R                         4   No.
L   Type T                        59   No.
M   Type V                       112   No.
N   Type V1                        4   No.
P   Type AC                        8   No.
Q   Type EL                       14   No.
R   Type Exit                     95   No.
                III 4-3/16/16R
Amount
EXTERNAL



                                                                                     Unit Rate
                                                                                            Amount
No.                       Description                             Unit       Qty.
                                                                                    KD/Fils KD/Fils

                BILL NO-4 EXTERNAL WORKS
      DIVISION 16 - ELECTRICAL (Cont'd)
      16500 - Light Fixtures-External And
      Landscaping

      Supply, install and connect the following lights as
      shown in the electrical dwgs, BOQ, specifications as
      mentioned in the schedule of points.Installation shall
      be complete in all respects such as bulbs,
      tubes,reflector, control gear, connector
      box,earthing,wiring,foundation,support,poles,
      masts,winches,frames,structures etc. Light fixtures
      to have all the auxillaries as required for the proper
      and complete installation.No light fixtures are to be
      approved (even the specified one) unless the
      sample is provided.The engineer shall see the
      fixture and verify the suitability of the fixture for the
      type of poles,location and method of installation
      before giving final approval.
      NOTE: 1. All fluorescent light fixtures shall be
      provided with electronic control gear. 2. All light
      fittings are to be provided with dimmable control
      gears unless otherwise specified. 3.For emergency
      lightings, fixtures are to be intergrated with battery
      backup(3hrs maintained) and selectively installed to
      match with KFD regulations.


A     Wiring
        Wiring to external lighting                                 352      No.

      Light Fittings with poles/winches/structures/frames.

B     Type BA                                                        66      No.
C     Type BB                                                        48      No.
D     Type BC                                                       103      No.
E     Type BD                                                        56      No.
 F    Type-BF                                                            7   No.
G     Type-BG                                                        72      No.
Note:1)Refer Tables given under Architectural light
    fittings - Data sheets and specifications for details of
    all the external light fittings.
    2)A single mast with its own sets of luminaries shall
    be treated as single point. Refer Light Fixtures
    Specifications for details.
                          III 4-4/16/1R
    DIVISION 16 - ELECTRICAL (Cont'd)
    16500 - Light Fixtures-External And
    Landscaping
    Main Stadium/Courts-Foot Ball Pitch/Volley
    Ball/Basket Ball/ Tennis/Spectator Gallery etc.(Refer
    Light Specifications)
A   Wiring
       Wiring to external lighting                               142   No.
    Light Fittings with
    poles/structures/winches/masts/frames.
    Type-FL1(Combination of F1-Refer drg.&
B                                                                 4    No.
    specs.for details)

    Type-FL2(Combination of F2-Refer drg.&
C                                                                 4    No.
    specs.for details)

    Type-FL3(Combination of F4-Refer drg.&
D                                                                 8    No.
    specs.for details)

    Type-FL4(Combination of F3-Refer drg.&
E                                                                 8    No.
    specs.for details)

    Type-FL5(Combination of F4-Refer drg.&
F                                                                16    No.
    specs.for details)


G   Type-FL8(Refer drg.&specs.for details)                       68    No.


H   Type-FL9(Refer drg.&specs.for details)                       34    No.

    Note:
    All the light fixture's pricing shall include poles,masts-
    whatever applicable complete in all respect
    including winches,frames,structures etc.subject to
    the approval of Engineer.(Refer Tables&drgs.for
    details)
Amount
S.No.                                      DESCRIPTION                                           UNIT

WIRING DEVICES
        16140 - Socket Outlets
        Supply, installation and connection of 13A switched socket outlets,3pin pattern switch
        combined 240V,single phase including necessary wiring and conduits as mentioned in
        the schedule of points and on drawings, but complete in all respects.

 B      13A Switched Socket Outlet (Single)                                                      1519

 C      13A Switched Socket Outlet (Single-W/P)                                                  124

 D      Junction Box with 20A DP Switch                                                          136

 E      13A Switched Socket Outlet (Explosion Proof)                                              23

 F      13A Switched Socket Outlet (Single-Floor Mounting- W/P)                                   3

 G      13A Switched Socket Outlet(Twin)                                                         107

 H      13A Switched Socket Outlet (Twin-W/P)                                                     6

 A      16A 3Phase Socket -W/P                                                                    2

 B      63A 3Phase 5Pin Socket -W/P                                                               2

        1X13A 3Pin Twin Switched Non-Standard Socket Outlet in 4 Compartment Service
 C                                                                                                16
        Outlet Box Fed From UPS

 D      63A Under Floor Power Track 3.6m Long                                                     4

 E      Exhaust Fan (Gate House-A)                                                                1


                                             TOTAL
                                           DISCOUNT
                                          GRAND TOTAL
QTY




No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

No.

More Related Content

What's hot

Professional practice 2
Professional practice 2Professional practice 2
Professional practice 2
ahmong4
 
Construction contracts docuements_08092008
Construction contracts docuements_08092008Construction contracts docuements_08092008
Construction contracts docuements_08092008
AYM1979
 
M3 EG BQ steel struture
M3 EG BQ steel strutureM3 EG BQ steel struture
M3 EG BQ steel struture
Est
 
Estimation and quantity surveying
Estimation and quantity surveyingEstimation and quantity surveying
Estimation and quantity surveying
Awanish Shukla
 

What's hot (20)

Professional practice 2
Professional practice 2Professional practice 2
Professional practice 2
 
Measurement 4 Tender Document
Measurement 4 Tender Document Measurement 4 Tender Document
Measurement 4 Tender Document
 
Value management presentation
Value management presentationValue management presentation
Value management presentation
 
ECA Presentation
ECA PresentationECA Presentation
ECA Presentation
 
Bills of quantities
Bills of quantitiesBills of quantities
Bills of quantities
 
Quantity Surveyor presentation
Quantity Surveyor presentationQuantity Surveyor presentation
Quantity Surveyor presentation
 
ECA Workshop - Brief
ECA Workshop - BriefECA Workshop - Brief
ECA Workshop - Brief
 
Preparation of boq
Preparation of boqPreparation of boq
Preparation of boq
 
Double Storeyed Building Estimation and Costing by Nafisa Nazneen Choudhury (...
Double Storeyed Building Estimation and Costing by Nafisa Nazneen Choudhury (...Double Storeyed Building Estimation and Costing by Nafisa Nazneen Choudhury (...
Double Storeyed Building Estimation and Costing by Nafisa Nazneen Choudhury (...
 
Estimation and Costing - Contracts
Estimation and Costing - ContractsEstimation and Costing - Contracts
Estimation and Costing - Contracts
 
Construction contracts docuements_08092008
Construction contracts docuements_08092008Construction contracts docuements_08092008
Construction contracts docuements_08092008
 
Quality control IN CONSTRUCTION
Quality control IN CONSTRUCTIONQuality control IN CONSTRUCTION
Quality control IN CONSTRUCTION
 
M3 EG BQ steel struture
M3 EG BQ steel strutureM3 EG BQ steel struture
M3 EG BQ steel struture
 
Residential Building Preliminary Cost Estimate- Excel Template
Residential Building Preliminary Cost Estimate- Excel TemplateResidential Building Preliminary Cost Estimate- Excel Template
Residential Building Preliminary Cost Estimate- Excel Template
 
Estimation and quantity surveying
Estimation and quantity surveyingEstimation and quantity surveying
Estimation and quantity surveying
 
Material required for different items of civil building works
Material required for different items of civil  building worksMaterial required for different items of civil  building works
Material required for different items of civil building works
 
Fidic conditions of contract presentation
Fidic conditions of contract presentationFidic conditions of contract presentation
Fidic conditions of contract presentation
 
Estimating part 1
Estimating part 1Estimating part 1
Estimating part 1
 
BUILDING ESTIMATION (Details Estimate For G+2 Storied Building presentation ...
BUILDING ESTIMATION (Details Estimate For G+2  Storied Building presentation ...BUILDING ESTIMATION (Details Estimate For G+2  Storied Building presentation ...
BUILDING ESTIMATION (Details Estimate For G+2 Storied Building presentation ...
 
Tender Process | A Complete Procurement Guide
Tender Process | A Complete Procurement GuideTender Process | A Complete Procurement Guide
Tender Process | A Complete Procurement Guide
 

Recently uploaded

NewBase 17 May 2024 Energy News issue - 1725 by Khaled Al Awadi_compresse...
NewBase   17 May  2024  Energy News issue - 1725 by Khaled Al Awadi_compresse...NewBase   17 May  2024  Energy News issue - 1725 by Khaled Al Awadi_compresse...
NewBase 17 May 2024 Energy News issue - 1725 by Khaled Al Awadi_compresse...
Khaled Al Awadi
 
Presentation4 (2) survey responses clearly labelled
Presentation4 (2) survey responses clearly labelledPresentation4 (2) survey responses clearly labelled
Presentation4 (2) survey responses clearly labelled
CaitlinCummins3
 
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
prakheeshc
 
Contact +971581248768 for 100% original and safe abortion pills available for...
Contact +971581248768 for 100% original and safe abortion pills available for...Contact +971581248768 for 100% original and safe abortion pills available for...
Contact +971581248768 for 100% original and safe abortion pills available for...
DUBAI (+971)581248768 BUY ABORTION PILLS IN ABU dhabi...Qatar
 
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![© ر
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![©  ر00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![©  ر
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![© ر
nafizanafzal
 
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di BandungObat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
Obat Aborsi Jakarta Wa 085176963835 Apotek Jual Obat Cytotec Di Jakarta
 

Recently uploaded (20)

NewBase 17 May 2024 Energy News issue - 1725 by Khaled Al Awadi_compresse...
NewBase   17 May  2024  Energy News issue - 1725 by Khaled Al Awadi_compresse...NewBase   17 May  2024  Energy News issue - 1725 by Khaled Al Awadi_compresse...
NewBase 17 May 2024 Energy News issue - 1725 by Khaled Al Awadi_compresse...
 
SCI9-Q4-MOD9.pdfetiwtitw3i3uu45w5wtitwjt
SCI9-Q4-MOD9.pdfetiwtitw3i3uu45w5wtitwjtSCI9-Q4-MOD9.pdfetiwtitw3i3uu45w5wtitwjt
SCI9-Q4-MOD9.pdfetiwtitw3i3uu45w5wtitwjt
 
Beyond Numbers A Holistic Approach to Forensic Accounting
Beyond Numbers A Holistic Approach to Forensic AccountingBeyond Numbers A Holistic Approach to Forensic Accounting
Beyond Numbers A Holistic Approach to Forensic Accounting
 
Presentation4 (2) survey responses clearly labelled
Presentation4 (2) survey responses clearly labelledPresentation4 (2) survey responses clearly labelled
Presentation4 (2) survey responses clearly labelled
 
WAM Corporate Presentation May 2024_w.pdf
WAM Corporate Presentation May 2024_w.pdfWAM Corporate Presentation May 2024_w.pdf
WAM Corporate Presentation May 2024_w.pdf
 
Mastering The Art Of 'Closing The Sale'.
Mastering The Art Of 'Closing The Sale'.Mastering The Art Of 'Closing The Sale'.
Mastering The Art Of 'Closing The Sale'.
 
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
A BUSINESS PROPOSAL FOR SLAUGHTER HOUSE WASTE MANAGEMENT IN MYSORE MUNICIPAL ...
 
First Time Home Buyer's Guide - KM Realty Group LLC
First Time Home Buyer's Guide - KM Realty Group LLCFirst Time Home Buyer's Guide - KM Realty Group LLC
First Time Home Buyer's Guide - KM Realty Group LLC
 
10 Easiest Ways To Buy Verified TransferWise Accounts
10 Easiest Ways To Buy Verified TransferWise Accounts10 Easiest Ways To Buy Verified TransferWise Accounts
10 Easiest Ways To Buy Verified TransferWise Accounts
 
Understanding Financial Accounting 3rd Canadian Edition by Christopher D. Bur...
Understanding Financial Accounting 3rd Canadian Edition by Christopher D. Bur...Understanding Financial Accounting 3rd Canadian Edition by Christopher D. Bur...
Understanding Financial Accounting 3rd Canadian Edition by Christopher D. Bur...
 
Contact +971581248768 for 100% original and safe abortion pills available for...
Contact +971581248768 for 100% original and safe abortion pills available for...Contact +971581248768 for 100% original and safe abortion pills available for...
Contact +971581248768 for 100% original and safe abortion pills available for...
 
Presentation on cross cultural negotiations.
Presentation on cross cultural negotiations.Presentation on cross cultural negotiations.
Presentation on cross cultural negotiations.
 
Most Visionary Leaders in Cloud Revolution, Shaping Tech’s Next Era - 2024 (2...
Most Visionary Leaders in Cloud Revolution, Shaping Tech’s Next Era - 2024 (2...Most Visionary Leaders in Cloud Revolution, Shaping Tech’s Next Era - 2024 (2...
Most Visionary Leaders in Cloud Revolution, Shaping Tech’s Next Era - 2024 (2...
 
Progress Report - UKG Analyst Summit 2024 - A lot to do - Good Progress1-1.pdf
Progress Report - UKG Analyst Summit 2024 - A lot to do - Good Progress1-1.pdfProgress Report - UKG Analyst Summit 2024 - A lot to do - Good Progress1-1.pdf
Progress Report - UKG Analyst Summit 2024 - A lot to do - Good Progress1-1.pdf
 
Thompson_Taylor_MBBS_PB1_2024-03 (1)- Project & Portfolio 2.pptx
Thompson_Taylor_MBBS_PB1_2024-03 (1)- Project & Portfolio 2.pptxThompson_Taylor_MBBS_PB1_2024-03 (1)- Project & Portfolio 2.pptx
Thompson_Taylor_MBBS_PB1_2024-03 (1)- Project & Portfolio 2.pptx
 
Navigating Tax Season with Confidence Streamlines CPA Firms
Navigating Tax Season with Confidence Streamlines CPA FirmsNavigating Tax Season with Confidence Streamlines CPA Firms
Navigating Tax Season with Confidence Streamlines CPA Firms
 
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![© ر
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![©  ر00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![©  ر
00971508021841 حبوب الإجهاض في دبي | أبوظبي | الشارقة | السطوة |❇ ❈ ((![© ر
 
Chapter 2 Organization Structure of a Treasury
Chapter 2 Organization Structure of a TreasuryChapter 2 Organization Structure of a Treasury
Chapter 2 Organization Structure of a Treasury
 
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di BandungObat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
Obat Aborsi Bandung 0851\7696\3835 Jual Obat Cytotec Di Bandung
 
Pay after result spell caster (,$+27834335081)@ bring back lost lover same da...
Pay after result spell caster (,$+27834335081)@ bring back lost lover same da...Pay after result spell caster (,$+27834335081)@ bring back lost lover same da...
Pay after result spell caster (,$+27834335081)@ bring back lost lover same da...
 

Stadium lighting boq

  • 1. STADIUM No. Description Unit Qty. DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures Supply, install and connect the following light as shown in the electrical drawings, BOQ, specifications as mentioned in the schedule of points.Installation shall be complete in all respects such as bulbs, tubes,reflector, control gear, connector box,earthing,wiring,foundation,support etc. Light fixtures to have all the auxillaries as required for the proper and complete installation.For reflected ceiling refer to the architectural drawings showing the light fixture. No light fixtures are to be approved (even the specified one) unless the sample is provided.The engineer shall see the fixture and verify the suitability of the fixture for the type of false ceiling, location and method of installation before giving final approval. NOTE: 1. All fluorescent light fixtures shall be provided with electronic control gear. 2. All light fittings are to be provided with dimmable control gears unless otherwise specified. 3.For emergency lightings, fixtures are to be intergrated with battery backup(3hrs maintained) and selectively installed to match with KFD regulations. A Type A 54 No. B Type C 106 No. C Type D 13 No. D Type F 166 No. E Type G 89 No. F Type H 177 No. G Type J 197 No. H Type K 9 No. J Type M 42 No. K Type N 20 No. L Type P 40 No. M Type U 82 No. III 4-2/16/14R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures A Type V 531 No. B Type W 34 No. Type AB (COVE LIGHT TO BE LAYED PARALLALY IN TWO C 670 m LINE) D Type AC 3 No. E Type AF 14 No.
  • 2. F Type AG 16 No. G Type AH 32 No. H Type AJ 6 No. J Type AK 40 No. K Type AL 12 No. L Type AM 136 No. M Type AN 16 No. N Type AP 56 No. P Type AQ 78 No. Q Type AR 38 No. R Type AS 84 No. S Type AT 88 No. T Type AU 21 No. U Type AV 12 No. V AM1 6 No. III 4-2/16/15R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures Intergrated with Battery Backup A Type A 35 No. B Type C 14 No. C Type D 92 No. D Type F 54 No. E Type G 15 No. F Type H 34 No. G Type M 12 No. H Type U 12 No. J Type V 164 No. K Type AC 2 No. L Type AF 4 No. M Type AV 4 No. N Type AT 8 No. P Type-Exit 67 No. III 4-2/16/16R
  • 3. Unit Rate Amount KD/Fils KD/Fils
  • 4.
  • 5. INDOOR SPORT FACILITY Unit Rate Amount No. Description Unit Qty. KD/Fils KD/Fils DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures Supply, install and connect the following light as shown in the electrical drawings, BOQ, specifications as mentioned in the schedule of points.Installation shall be complete in all respects such as bulbs, tubes,reflector, control gear, connector box,earthing,wiring,foundation,support etc. Light fixtures to have all the auxillaries as required for the proper and complete installation.For reflected ceiling refer to the architectural drawings showing the light fixture. No light fixtures are to be approved (even the specified one) unless the sample is provided.The engineer shall see the fixture and verify the suitability of the fixture for the type of false ceiling, location and method of installation before giving final approval. NOTE: 1. All fluorescent light fixtures shall be provided with electronic control gear. 2. All light fittings are to be provided with dimmable control gears unless otherwise specified. 3.For emergency lightings, fixtures are to be intergrated with battery backup(3hrs maintained) and selectively installed to match with KFD regulations. A Type A 92 No. B Type B 26 No. C Type C 42 No. D Type D 12 No. E Type F 190 No. F Type G 195 No. G Type H 157 No. H Type J 120 No. III 4-3/16/13R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures A Type K 30 No. B Type L 58 No. C Type M 90 No.
  • 6. D Type N 275 No. E Type P 92 No. F Type Q1 48 No. G Type R 8 No. H Type S 63 No. J Type T 262 No. K Type U 34 No. L Type V 334 No. M Type V1 16 No. N Type W 31 No. P Type W3 12 No. Q Type Z(Each strip with 11 LED'S) 60 No. III 4-3/16/14R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures A Type AA 29 No. Type AB (COVE LIGHT TO BE LAYED PARALLALY IN B 650 m TWO LINES) C Type AC 22 No. D Type AD 12 No. E Type AG 83 No. F Type AU 8 No. G Type AW 91 No. H Type AY 90 No. J Type F3 142 No. K Type UW (Underwater Light Fittings) 62 No. L Type Y 30 No. M Type C1 210 No. Note: A combination of 3 nos. of Type F3 shall be read as Type FL6 and combination of 4 nos. of Type F3 shall be read as Type FL7. Refer Light Fixtures Specifications for details. III 4-3/16/15R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures Intergrated with Battery Backup A Type A 30 No. B Type B 20 m C Type C 6 No. D Type D 52 No. E Type C1 14 No. F Type F 91 No. G Type G 31 No. H Type H 50 No.
  • 7. J Type M 35 No. K Type R 4 No. L Type T 59 No. M Type V 112 No. N Type V1 4 No. P Type AC 8 No. Q Type EL 14 No. R Type Exit 95 No. III 4-3/16/16R
  • 9. EXTERNAL Unit Rate Amount No. Description Unit Qty. KD/Fils KD/Fils BILL NO-4 EXTERNAL WORKS DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures-External And Landscaping Supply, install and connect the following lights as shown in the electrical dwgs, BOQ, specifications as mentioned in the schedule of points.Installation shall be complete in all respects such as bulbs, tubes,reflector, control gear, connector box,earthing,wiring,foundation,support,poles, masts,winches,frames,structures etc. Light fixtures to have all the auxillaries as required for the proper and complete installation.No light fixtures are to be approved (even the specified one) unless the sample is provided.The engineer shall see the fixture and verify the suitability of the fixture for the type of poles,location and method of installation before giving final approval. NOTE: 1. All fluorescent light fixtures shall be provided with electronic control gear. 2. All light fittings are to be provided with dimmable control gears unless otherwise specified. 3.For emergency lightings, fixtures are to be intergrated with battery backup(3hrs maintained) and selectively installed to match with KFD regulations. A Wiring Wiring to external lighting 352 No. Light Fittings with poles/winches/structures/frames. B Type BA 66 No. C Type BB 48 No. D Type BC 103 No. E Type BD 56 No. F Type-BF 7 No. G Type-BG 72 No.
  • 10. Note:1)Refer Tables given under Architectural light fittings - Data sheets and specifications for details of all the external light fittings. 2)A single mast with its own sets of luminaries shall be treated as single point. Refer Light Fixtures Specifications for details. III 4-4/16/1R DIVISION 16 - ELECTRICAL (Cont'd) 16500 - Light Fixtures-External And Landscaping Main Stadium/Courts-Foot Ball Pitch/Volley Ball/Basket Ball/ Tennis/Spectator Gallery etc.(Refer Light Specifications) A Wiring Wiring to external lighting 142 No. Light Fittings with poles/structures/winches/masts/frames. Type-FL1(Combination of F1-Refer drg.& B 4 No. specs.for details) Type-FL2(Combination of F2-Refer drg.& C 4 No. specs.for details) Type-FL3(Combination of F4-Refer drg.& D 8 No. specs.for details) Type-FL4(Combination of F3-Refer drg.& E 8 No. specs.for details) Type-FL5(Combination of F4-Refer drg.& F 16 No. specs.for details) G Type-FL8(Refer drg.&specs.for details) 68 No. H Type-FL9(Refer drg.&specs.for details) 34 No. Note: All the light fixture's pricing shall include poles,masts- whatever applicable complete in all respect including winches,frames,structures etc.subject to the approval of Engineer.(Refer Tables&drgs.for details)
  • 12. S.No. DESCRIPTION UNIT WIRING DEVICES 16140 - Socket Outlets Supply, installation and connection of 13A switched socket outlets,3pin pattern switch combined 240V,single phase including necessary wiring and conduits as mentioned in the schedule of points and on drawings, but complete in all respects. B 13A Switched Socket Outlet (Single) 1519 C 13A Switched Socket Outlet (Single-W/P) 124 D Junction Box with 20A DP Switch 136 E 13A Switched Socket Outlet (Explosion Proof) 23 F 13A Switched Socket Outlet (Single-Floor Mounting- W/P) 3 G 13A Switched Socket Outlet(Twin) 107 H 13A Switched Socket Outlet (Twin-W/P) 6 A 16A 3Phase Socket -W/P 2 B 63A 3Phase 5Pin Socket -W/P 2 1X13A 3Pin Twin Switched Non-Standard Socket Outlet in 4 Compartment Service C 16 Outlet Box Fed From UPS D 63A Under Floor Power Track 3.6m Long 4 E Exhaust Fan (Gate House-A) 1 TOTAL DISCOUNT GRAND TOTAL