S7 400 h
- 2. Automation and Drives
Benefits
High-available
SIMATIC
Overview Avoidance of control system failures due to individual faults
This is attained primarily through a redundant configuration
Redundancy features
Switchover High-availability is required in the following cases:
Synchronization When processing valuable materials
Self-test When downtimes or production failures would be expensive
Programming When a control system failure would result in high restart costs
CIR
In order to enable operation without supervisory or maintenance personnel
Online repair
Configuration
Communication
Redundant I/O
A&D AS, 07/2004, Chart 2
© Siemens AG 2004 - Subject to change without prior notice
- 3. Automation and Drives
Industries (1)
High-available
SIMATIC
Overview Power generation and distribution
(oil, gas, electricity)
Redundancy features Power plants
Pipelines
Switchover
Offshore
Synchronization
District heating systems
Self-test
Programming Chemical, electrochemical, petrochemical and pharmaceutical
CIR industries
Online repair
Mining
Configuration
Environmental engineering
Communication Water treatment
Refuse incineration
Redundant I/O
Pulp and paper
Steel and metal
A&D AS, 07/2004, Chart 3
© Siemens AG 2004 - Subject to change without prior notice
- 4. Automation and Drives
Industries (2)
High-available
SIMATIC
Overview Food and beverages
Redundancy features
Glass industry
Switchover Semiconductor industry (utilities)
Synchronization
Transport
Self-test Tunnel automation
Programming Marine automation
CIR
Online repair
Airports
Runway lighting
Configuration Baggage transport
Communication
Redundant I/O
A&D AS, 07/2004, Chart 4
© Siemens AG 2004 - Subject to change without prior notice
- 5. Automation and Drives
System architecture
High-available
SIMATIC
Overview
Clients
Redundancy features Management level Parallel redundancy
Switchover
Server
Synchronization PC network/terminal bus Parallel redundancy
With archive-matching
Self-test
High-available
Programming communication
Ethernet
CIR Media
Process level redundancy
Online repair
H CPUs SW redundancy
Configuration Hot stand-by Warm stand-by
Redundant
Communication power supply
ET 200M
Redundant I/O
Field level
Redundant
PROFIBUS
Redundant
IM 153
A&D AS, 07/2004, Chart 5
© Siemens AG 2004 - Subject to change without prior notice
- 6. Automation and Drives
System integration
High-available
SIMATIC
Overview Hidden redundancy
Transparent programming
Redundancy features (programming same as for non-
redundant systems)
Switchover
Standard system parameterization
Synchronization
Self-test
Standard handling
Programming
CIR All SIMATIC programming
Online repair languages can be used without restriction
Configuration
Platform for F and
Communication FH systems
Redundant I/O
A&D AS, 07/2004, Chart 6
© Siemens AG 2004 - Subject to change without prior notice
- 7. Automation and Drives
Bumpless master-stand-by switchover
High-available
SIMATIC
Overview Switchover time
Switchover time < 100ms
Redundancy features
Redundancy features
Outputs are retained during switchover
Switchover
Switchover No information or alarm/interrupt is lost
Synchronization
Self-test
Switchover criteria
Programming
Master failure
CIR
Power supply
Online repair
Rack
Configuration Sync module
Communication
Sync cable
CPU
Redundant I/O
Failure of a DP string or DP slave interface module does not
force a switchover
A&D AS, 07/2004, Chart 7
© Siemens AG 2004 - Subject to change without prior notice
- 8. Automation and Drives
Automatic event synchronization
High-available
SIMATIC
Overview Customer benefits
Redundancy features
Redundancy features
Transparent programming
Allstandard SIMATIC-S7 programming languages
Switchover
No command restrictions
Synchronization
Synchronization
Self-test
Easy porting of the user program
Programming
from standard CPU to high-available CPU
CIR
Online repair Bumpless switchover
No loss of information
Configuration
No loss of alarms/interrupts
Communication
Because all redundancy-specific functions are handled by the
Redundant I/O operating system, the user can feel assured that he/she has done
everything right as far as redundancy is concerned
A&D AS, 07/2004, Chart 8
© Siemens AG 2004 - Subject to change without prior notice
- 9. Automation and Drives
Comprehensive self-test functions
High-available
SIMATIC
Overview Self-test
Redundancy features
Redundancy features Scope:
Switchover CPU
Synchronization Memory
Self-test
Self-test
Synchronization link
Programming
CIR
Online repair
Organization:
Startup self-test
Configuration
Complete test
Communication Self-test in cyclic mode
Redundant I/O
Executes permanently as
background task
Executes in its entirety within a specifiable amount of time (default: 90
minutes)
A&D AS, 07/2004, Chart 9
© Siemens AG 2004 - Subject to change without prior notice
- 10. Automation and Drives
Online programming
High-available
SIMATIC
Overview Online modifications same as for standard system
All modifications are automatically copied to both CPUs
Redundancy features
Redundancy features
Switchover Connecting a PG
Synchronization At MPI interface
Self-test
Via bus
Programming
Programming
CIR
Online repair
Configuration
PROFIBUS/Ethernet
Communication
Redundant I/O
MPI/DP
A&D AS, 07/2004, Chart 10
© Siemens AG 2004 - Subject to change without prior notice
- 11. Automation and Drives
Configuration in RUN (CIR)
High-available
SIMATIC
Overview CPU memory configuration
Redundancy features
Redundancy features Adding or removing:
Switchover Central I/O or CP
Synchronization DP slaves
Self-test
PA interface and PA slaves
Programming
Y-link and slaves
CIR
Modules in modular DP slaves
Online repair
Configuration
CPU parameter
Communication
Redundant I/O
A&D AS, 07/2004, Chart 11
© Siemens AG 2004 - Subject to change without prior notice
- 12. Automation and Drives
Replacing modules in RUN mode
High-available
SIMATIC
Overview Modules which can be removed and inserted in Run mode
I/Oand CP
Redundancy features
Redundancy features
Sync module
Switchover
Redundant IM 153-2
Synchronization
Redundant power supplies
Self-test
Programming
Redundant components which can be replaced with the power
CIR
off:
Online repair
Standard power supplies
Configuration
Central IM
Communication CPU
Redundant I/O
CPU is automatically updated following replacement
(program and data)
A&D AS, 07/2004, Chart 12
© Siemens AG 2004 - Subject to change without prior notice
- 13. Automation and Drives
Configuration
Highlights new CPUs
High-available
SIMATIC
Overview Performance Increase
Average Increase
Redundancy features
417-4H appr. x 2,5-3
Switchover
414-4H appr. x 1,2-2,2
Synchronization More Memeory
Self-test
417-4H from 4 MB to 20MB
Programming
414-4H from 768KB to 1,4MB
CIR
Online repair Higher Reliability
Konfiguration
Configuration Memory with automatic Ewrror Detection and Correction (EDC)
Communication
New Feature
Redundant I/O Distance between the Controller up to 10km (before 500m)
A&D AS, 07/2004, Chart 13
© Siemens AG 2004 - Subject to change without prior notice
- 14. Automation and Drives
Configuration
Technical specifications for the CPUs
High-available
SIMATIC
Overview Two CPU types available
CPU 417-4H with
Redundancy features
20MB onboard
Switchover CPU 414-4H with
Synchronization 1,4MB onboard
Self-test
Programming General
CIR technical specifications,
Online repair e.g. CPU 417-4 or CPU 414-3
Configuration
Configuration
4 integrated interfaces
Communication Two for the Sync modules
One DP interface
Redundant I/O
One MPI/DP interface
A&D AS, 07/2004, Chart 14
© Siemens AG 2004 - Subject to change without prior notice
- 15. Automation and Drives
Configuration
Redundant link
High-available
SIMATIC
Overview
Redundancy features
Switchover
Synchronization
Self-test
Replaceable Sync modules
Programming
CIR
Online repair Fiber-optics (FO)
Configuration
Configuration
Communication
Fiber-optics (FO)
Redundant I/O
A&D AS, 07/2004, Chart 15
© Siemens AG 2004 - Subject to change without prior notice
- 16. Automation and Drives
I/O configuration
Switched I/O: mode of operation
High-available
SIMATIC
Overview Both DP masters are active
and functioning properly
Redundancy features
Reading inputs:
Switchover
The inputs are read only
Synchronization from the preferred channel
Self-test side (active IM)
Programming
Writingoutputs:
CIR
The data are accepted by
Online repair both channels.
Configuration
Configuration Only the data in the preferred
channel are forwarded to the
Communication outputs.
Redundant I/O
A&D AS, 07/2004, Chart 16
© Siemens AG 2004 - Subject to change without prior notice
- 17. Automation and Drives
Redundant I/O
High-available
SIMATIC
Overview
Redundancy features New:
Switchover Redundant IO
Redundant Communication
Synchronization
Self-test
Programming
Redundant Controller
CIR
Online repair
Redundant Profibus
PROFIBUS DP
Configuration
Communication
Sensor/control
Redundant I/O element
Redundant IM
A&D AS, 07/2004, Chart 17
© Siemens AG 2004 - Subject to change without prior notice
- 18. Automation and Drives
Redundant I/O
Possible redundancy structures (2)
High-available
SIMATIC
Overview Distributed switched
H-CPU in single mode
I/O modules
Redundancy features
Switchover
Synchronization
Self-test
Programming
CIR
Online repair
Configuration
Communication
Redundant I/O
A&D AS, 07/2004, Chart 18
© Siemens AG 2004 - Subject to change without prior notice
- 19. Automation and Drives
Redundant I/O
Wiring digital inputs
High-available
SIMATIC
With one sensor With two sensors
Overview
DI DI DI DI
Redundancy features
Switchover
Synchronization
Self-test
Programming DI
CIR
Master I/O
Redundant Profibus
Online repair
Both Inputs are read in parallel.
Configuration The correct value is selected and processed automatically
Communication
Redundant I/O
Redundant I/O
DI
Since the function is not suitable for all module types, the manual or Internet should be
consulted to find out which modules can currently be used.
A&D AS, 07/2004, Chart 19
© Siemens AG 2004 - Subject to change without prior notice
- 20. Automation and Drives
Redundant I/O
Wiring analog inputs
High-available
SIMATIC
With voltage sensor With current sensor With current sensor With 2 sensors
Overview AE-U AE-U AI-I AI-I AE-U AE-U
AE AE
Redundancy features
R
Switchover
U I I
Synchronization 4-wire transducers only
Self-test
Programming AI
CIR
Master I/O
Redundant Profibus
Online repair
The CPU reads both inputs. The correct value is selected
Configuration and processed automatically R I
Communication
Redundant I/O
Redundant I/O
AI
Since the function is not suitable for every module type, the manual or Internet should be
consulted to find out which modules can currently be used.
A&D AS, 07/2004, Chart 20
© Siemens AG 2004 - Subject to change without prior notice
- 21. Automation and Drives
Redundant I/O
Wiring digital outputs
High-available
SIMATIC
With diodes * Without diodes* * Dependant on the
Overview
DQ DQ DQ DQ module type
Redundancy features
Switchover
Synchronization
Self-test
Programming DO
CIR
Master I/O
Redundant Profibus
Online repair Actuator
Both Outputs are set
Configuration
Communication
Redundant I/O
Redundant I/O
DO
Since the function is not suitable for every module type, the manual or Internet should be
consulted to find out which modules can currently be used.
A&D AS, 07/2004, Chart 21
© Siemens AG 2004 - Subject to change without prior notice
- 22. Automation and Drives
Redundant I/O
Wiring analog outputs
High-available
SIMATIC
Overview Each Output outputs half the value.
Redundancy features
When one of the modules fails, the output that is still intact
provides the full value
Switchover
Synchronization
Self-test
Programming AO
CIR
Master I/O
Redundant Profibus
Online repair Actuator
Both Outputs are set
Configuration
I
Communication
Redundant I/O
Redundant I/O
AO
Since the function is not suitable for all module types, the manual or Internet should be
consulted to find out which modules can currently be used
A&D AS, 07/2004, Chart 22
© Siemens AG 2004 - Subject to change without prior notice