Transmission and distribution systems- D.C 2-wire and 3- wire systems, A.C single phase, three phase and 4-wire systems, comparison of copper efficiency. Primary and secondary
distribution systems, concentrated & uniformly distributed loads on distributors fed at both ends, ring distributor, voltage drop and power loss calculation, Kelvin’slaw.
This document discusses the characteristics and performance of power transmission lines. It covers the following key points:
- The design and operation of transmission lines considers voltage drop, line losses, and transmission efficiency, which depend on the line constants R, L, and C.
- Transmission lines are classified as short, medium, or long depending on their length and voltage level. Different methods are used to calculate performance based on how capacitance effects are handled.
- Medium transmission lines consider capacitance effects by lumping the distributed capacitance at points along the line. Methods like end condenser, nominal T, and nominal pi are commonly used for calculations.
- Examples are provided to demonstrate calculations for voltage regulation,
Symmetrical Components
Symmetrical Component Analysis
Synthesis of Unsymmetrical Phases from Their Symmetrical Components
The Symmetrical Components of Unsymmetrical Phasors
Phase Shift of Symmetrical Components in or Transformer Banks
Power in Terms of Symmetrical Components
1. A document discusses fault analysis in power systems, including symmetrical and unsymmetrical faults. Common fault causes include insulation failure, mechanical issues, over/under voltage, and accidents.
2. Key concepts are introduced, such as different types of reactance (subtransient, transient, steady-state) and how fault current transients have both AC and DC components.
3. Two examples are provided to demonstrate how to calculate fault current and MVA for given systems using per unit calculations and reactance values.
This document discusses different types of insulators used in overhead power lines. It describes pin insulators, suspension insulators, strain insulators, and shackle insulators. Suspension insulators consist of multiple porcelain discs connected in series by metal links. The voltage is not uniformly distributed across the discs of a suspension insulator string due to shunt capacitances. Methods to improve string efficiency include using longer cross arms, grading insulators with different capacitances, and adding a guard ring. The document also provides sample one mark and 12 mark questions related to insulators.
This document discusses four types of modifications that can be made to an existing power network to revise the Z-bus representation. Type 1 involves adding a branch impedance between a new bus and the reference bus. Type 2 adds a branch between a new bus and an existing bus. Type 3 adds a branch between an existing bus and the reference bus. Type 4 adds a branch between two existing buses. The document presents figures to illustrate each type and provides the corresponding equations to update the Z-bus matrix for the network.
This document discusses various types of phase controlled converters including single-phase and three-phase semiconverters, full converters, and dual converters. It provides equations for the average and RMS output voltage of single-phase converters with resistive and RL loads. It also derives an expression for the average output voltage of a three-phase half wave converter with continuous and constant load current. Key aspects of three-phase half wave, full wave, and dual converters are summarized.
This document provides an overview of two reaction theory, phasor diagrams, and slip tests for analyzing salient-pole generators. It explains that two reaction theory separates the armature mmf and flux into direct and quadrature axis components. A phasor diagram is also presented. Slip tests are described as a way to measure the direct axis and quadrature axis reactances (Xd and Xq) by taking voltage-to-current ratios at different points in the slip cycle when the armature mmf is aligned with either axis. Cautions for low slip are also noted when conducting these tests. References on electric machinery are listed at the end.
Inductance of transmission line
Flux linkages of one conductor in a group of conductors
Inductance of composite conductor lines
Inductance of 3-phase overhead line
Bundled conductors
This document discusses the characteristics and performance of power transmission lines. It covers the following key points:
- The design and operation of transmission lines considers voltage drop, line losses, and transmission efficiency, which depend on the line constants R, L, and C.
- Transmission lines are classified as short, medium, or long depending on their length and voltage level. Different methods are used to calculate performance based on how capacitance effects are handled.
- Medium transmission lines consider capacitance effects by lumping the distributed capacitance at points along the line. Methods like end condenser, nominal T, and nominal pi are commonly used for calculations.
- Examples are provided to demonstrate calculations for voltage regulation,
Symmetrical Components
Symmetrical Component Analysis
Synthesis of Unsymmetrical Phases from Their Symmetrical Components
The Symmetrical Components of Unsymmetrical Phasors
Phase Shift of Symmetrical Components in or Transformer Banks
Power in Terms of Symmetrical Components
1. A document discusses fault analysis in power systems, including symmetrical and unsymmetrical faults. Common fault causes include insulation failure, mechanical issues, over/under voltage, and accidents.
2. Key concepts are introduced, such as different types of reactance (subtransient, transient, steady-state) and how fault current transients have both AC and DC components.
3. Two examples are provided to demonstrate how to calculate fault current and MVA for given systems using per unit calculations and reactance values.
This document discusses different types of insulators used in overhead power lines. It describes pin insulators, suspension insulators, strain insulators, and shackle insulators. Suspension insulators consist of multiple porcelain discs connected in series by metal links. The voltage is not uniformly distributed across the discs of a suspension insulator string due to shunt capacitances. Methods to improve string efficiency include using longer cross arms, grading insulators with different capacitances, and adding a guard ring. The document also provides sample one mark and 12 mark questions related to insulators.
This document discusses four types of modifications that can be made to an existing power network to revise the Z-bus representation. Type 1 involves adding a branch impedance between a new bus and the reference bus. Type 2 adds a branch between a new bus and an existing bus. Type 3 adds a branch between an existing bus and the reference bus. Type 4 adds a branch between two existing buses. The document presents figures to illustrate each type and provides the corresponding equations to update the Z-bus matrix for the network.
This document discusses various types of phase controlled converters including single-phase and three-phase semiconverters, full converters, and dual converters. It provides equations for the average and RMS output voltage of single-phase converters with resistive and RL loads. It also derives an expression for the average output voltage of a three-phase half wave converter with continuous and constant load current. Key aspects of three-phase half wave, full wave, and dual converters are summarized.
This document provides an overview of two reaction theory, phasor diagrams, and slip tests for analyzing salient-pole generators. It explains that two reaction theory separates the armature mmf and flux into direct and quadrature axis components. A phasor diagram is also presented. Slip tests are described as a way to measure the direct axis and quadrature axis reactances (Xd and Xq) by taking voltage-to-current ratios at different points in the slip cycle when the armature mmf is aligned with either axis. Cautions for low slip are also noted when conducting these tests. References on electric machinery are listed at the end.
Inductance of transmission line
Flux linkages of one conductor in a group of conductors
Inductance of composite conductor lines
Inductance of 3-phase overhead line
Bundled conductors
Chapter 4 mechanical design of transmission linesfiraoltemesgen1
This chapter discusses the mechanical design of transmission lines. It covers various topics such as types of conductors, line supports, spacing between conductors, and sag-tension calculations. The key conductors mentioned are copper, aluminum, and steel. Wooden poles, steel tubular poles, reinforced concrete poles, and steel towers are described as the main types of line supports. The document also discusses the effects of wind and ice loading on transmission lines. Sag-tension calculations are explained using catenary curve equations.
This document discusses parameters of transmission lines and cables. It begins by describing different types of transmission lines based on voltage level, including extra-high voltage lines, high voltage lines, sub-transmission lines, and distribution lines. It then covers the typical components of transmission lines, such as conductors, insulators, towers, and foundations. The document provides examples of commonly used tower designs and conductor types. It concludes by deriving equations to calculate the resistance, inductance, and capacitance of transmission lines based on conductor and geometry properties.
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...Jobin Abraham
This document discusses symmetrical three-phase faults in electrical power systems. It defines a symmetrical fault as one where equal fault currents are produced in each line with 120 degree phase displacement. This is the most severe type of fault. The document covers transient currents on transmission lines during a fault, selection of circuit breakers based on maximum fault currents, fault currents and induced emfs for synchronous machines under no-load and loaded conditions, and provides an algorithm for short circuit studies.
This document provides an overview of transmission lines. It discusses how transmission lines transport electric power from generators to loads over long distances using high voltages. The power is then stepped down at distribution substations before being delivered to customers. Transmission lines can be overhead lines suspended from poles or towers, or buried underground cables. They have series resistance, inductance, and shunt capacitance per unit length that determine their power capacity.
Tap changers are devices fitted to power transformers that allow for regulation of the output voltage. Voltage regulation is achieved by altering the number of turns in one winding of the transformer, which changes the transformer ratios. Tap changers offer variable control to keep the supply voltage within limits. They can be on load or off load tap changers. On load tap changers consist of a diverter switch and selector switch to transfer current between taps without interruption.
The document discusses electromagnetic relays used in power systems. It describes two main operating principles for electromagnetic relays: electromagnetic attraction and electromagnetic induction. Electromagnetic attraction relays operate using an armature attracted to magnet poles, and include attractor-armature, solenoid, and balanced beam types. Electromagnetic induction relays operate on induction motor principles using a pivoted disc and alternating magnetic fields, and include shaded-pole, watt-hour meter, and induction cup structures. The document also defines important relay terms like pick-up current, current setting, and time-setting multiplier.
1) The document discusses inductance in electrical conductors and transmission lines. It defines internal and external inductance and provides formulas to calculate them.
2) Formulas are provided for the inductance of a single-phase two-wire transmission line, as well as a three-phase line with symmetrical and unsymmetrical conductor spacing.
3) Bundled conductors are described as having multiple sub-conductors to reduce losses at high voltages and transmit more power efficiently.
The document compares AC and DC power transmission. It discusses three main factors: economics of transmission, technical performance, and reliability. For economics, DC transmission has lower costs for conductors and insulation for long distance transmission over 500-800 km. However, converter equipment for DC is more expensive. Technically, DC allows faster control of power flow and is not limited by stability with increasing distance. Reliability of DC transmission has also improved with advances in thyristor converters. The document provides details on the technical differences between AC and DC transmission under each of the three factors.
This document discusses different parameter representations for two-port networks:
- Z-parameters (open-circuit impedance parameters) relate terminal voltages to currents.
- Y-parameters (short-circuit admittance parameters) relate terminal currents to voltages.
- T-equivalent and Pi-equivalent models provide lumped-element representations of reciprocal networks.
- h-parameters and g-parameters describe the terminal characteristics of some electronic devices.
- Transmission (ABCD) parameters express source variables in terms of destination variables.
Conversion formulas are provided between the different parameter sets. Examples are included to illustrate determining the parameters for simple circuits.
As we have discussed that out of various triggering methods to turn the SCR, gate triggering is the most efficient and reliable method. Most of the control applications use this type of triggering because the desired instant of SCR turning is possible with gate triggering method.
This document provides an outline and overview of a hands-on relay school covering transmission protection theory including symmetrical components and fault calculations. It discusses power system problems like faults and disturbances, different fault types, and introduces symmetrical components and how they are used to analyze balanced and unbalanced systems. It also covers per unit systems, calculating sequence networks for faults, and evaluating transmission line, generator, and transformer impedances.
The document discusses three-phase circuits and provides information on:
- The advantages of three-phase supply systems such as higher efficiency of power transfer and smoother load characteristics.
- Key concepts like phase sequence, balanced/unbalanced supply and load, and the relationships between line and phase voltages and currents.
- How to calculate power in a balanced three-phase system and use two wattmeters to measure total power and power factor.
1. The document discusses symmetrical components, which allow representation of unbalanced three-phase quantities as the sum of three balanced components.
2. It introduces the positive, negative, and zero sequence components and the transformation matrix used to relate the symmetrical components to the original unbalanced quantities.
3. Symmetrical components are useful for simplifying analysis of unbalanced conditions like single line-to-ground faults in power systems. Sequence impedances can be used to model devices and transmission lines.
1) The document discusses the working principle, types, EMF equation, and equivalent circuit of transformers. It describes how transformers work by mutual induction between two inductively coupled coils.
2) Transformers can be classified by construction (shell, core, berry types) and by functioning (step-up, step-down, isolation transformers). The EMF equation defines the transformation ratio between primary and secondary voltages and currents.
3) Equivalent circuits are used to model transformer behavior on no-load and load conditions. Losses are represented by resistances while the magnetizing current is modeled by a reactance. Secondary parameters can be referred to the primary for analysis.
This document discusses the key parameters - resistance, inductance, and capacitance - of overhead transmission lines.
It first defines each parameter and explains that they are uniformly distributed along the line. Resistance is opposition to current flow, inductance is flux linkages per ampere, and capacitance is charge per voltage.
It then goes on to provide formulas for calculating the resistance, inductance, and capacitance of different types of transmission lines. It also discusses factors like skin effect that impact the resistance and analyses methods for determining flux linkages to calculate inductance.
This document discusses voltage drop calculation for lighting and convenience socket circuits. It defines key terms like voltage drop and nominal system voltage. It provides the Philippine Electrical Code provisions limiting voltage drop to 3% for feeders and branch circuits, and 5% total. Formulas are given for calculating voltage drop based on current, conductor length, material properties, and cross-sectional area. Sample calculations demonstrate applying the formulas. The document also introduces VPCM, JGC Philippines' in-house software for automating voltage drop calculations, and generating outputs like block diagrams, panel schedules, and cable schedules.
This power point presentation provides an overview of fault analysis and sequence networks in power systems. It defines different types of faults including open circuit faults, short circuit faults, symmetrical faults, and unsymmetrical faults. Symmetrical faults involve all three phases and remain balanced, while unsymmetrical faults involve one or two phases. Sequence networks, including positive, negative, and zero sequence networks are used for fault analysis. The presentation describes each type of fault and sequence network in detail.
Types of conductors, line parameters, calculation of inductance and capacitance of single and double circuit transmission lines, three phase lines with bundle conductors. Skin effect and
proximity effect.
This document provides an overview of transmission line modeling and analysis. It begins with assigning homework problems and then reviews electric field concepts such as Gauss's law and voltage difference calculations. Models for transmission line capacitance and inductance are developed considering both single and multi-conductor cases. Examples are provided to demonstrate how to calculate per phase capacitance, resistance, and inductance values for different conductor types using data from standard tables. Additional transmission line topics like multi-circuit lines, underground cables, and corona discharge are also briefly discussed.
Chapter 4 mechanical design of transmission linesfiraoltemesgen1
This chapter discusses the mechanical design of transmission lines. It covers various topics such as types of conductors, line supports, spacing between conductors, and sag-tension calculations. The key conductors mentioned are copper, aluminum, and steel. Wooden poles, steel tubular poles, reinforced concrete poles, and steel towers are described as the main types of line supports. The document also discusses the effects of wind and ice loading on transmission lines. Sag-tension calculations are explained using catenary curve equations.
This document discusses parameters of transmission lines and cables. It begins by describing different types of transmission lines based on voltage level, including extra-high voltage lines, high voltage lines, sub-transmission lines, and distribution lines. It then covers the typical components of transmission lines, such as conductors, insulators, towers, and foundations. The document provides examples of commonly used tower designs and conductor types. It concludes by deriving equations to calculate the resistance, inductance, and capacitance of transmission lines based on conductor and geometry properties.
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...Jobin Abraham
This document discusses symmetrical three-phase faults in electrical power systems. It defines a symmetrical fault as one where equal fault currents are produced in each line with 120 degree phase displacement. This is the most severe type of fault. The document covers transient currents on transmission lines during a fault, selection of circuit breakers based on maximum fault currents, fault currents and induced emfs for synchronous machines under no-load and loaded conditions, and provides an algorithm for short circuit studies.
This document provides an overview of transmission lines. It discusses how transmission lines transport electric power from generators to loads over long distances using high voltages. The power is then stepped down at distribution substations before being delivered to customers. Transmission lines can be overhead lines suspended from poles or towers, or buried underground cables. They have series resistance, inductance, and shunt capacitance per unit length that determine their power capacity.
Tap changers are devices fitted to power transformers that allow for regulation of the output voltage. Voltage regulation is achieved by altering the number of turns in one winding of the transformer, which changes the transformer ratios. Tap changers offer variable control to keep the supply voltage within limits. They can be on load or off load tap changers. On load tap changers consist of a diverter switch and selector switch to transfer current between taps without interruption.
The document discusses electromagnetic relays used in power systems. It describes two main operating principles for electromagnetic relays: electromagnetic attraction and electromagnetic induction. Electromagnetic attraction relays operate using an armature attracted to magnet poles, and include attractor-armature, solenoid, and balanced beam types. Electromagnetic induction relays operate on induction motor principles using a pivoted disc and alternating magnetic fields, and include shaded-pole, watt-hour meter, and induction cup structures. The document also defines important relay terms like pick-up current, current setting, and time-setting multiplier.
1) The document discusses inductance in electrical conductors and transmission lines. It defines internal and external inductance and provides formulas to calculate them.
2) Formulas are provided for the inductance of a single-phase two-wire transmission line, as well as a three-phase line with symmetrical and unsymmetrical conductor spacing.
3) Bundled conductors are described as having multiple sub-conductors to reduce losses at high voltages and transmit more power efficiently.
The document compares AC and DC power transmission. It discusses three main factors: economics of transmission, technical performance, and reliability. For economics, DC transmission has lower costs for conductors and insulation for long distance transmission over 500-800 km. However, converter equipment for DC is more expensive. Technically, DC allows faster control of power flow and is not limited by stability with increasing distance. Reliability of DC transmission has also improved with advances in thyristor converters. The document provides details on the technical differences between AC and DC transmission under each of the three factors.
This document discusses different parameter representations for two-port networks:
- Z-parameters (open-circuit impedance parameters) relate terminal voltages to currents.
- Y-parameters (short-circuit admittance parameters) relate terminal currents to voltages.
- T-equivalent and Pi-equivalent models provide lumped-element representations of reciprocal networks.
- h-parameters and g-parameters describe the terminal characteristics of some electronic devices.
- Transmission (ABCD) parameters express source variables in terms of destination variables.
Conversion formulas are provided between the different parameter sets. Examples are included to illustrate determining the parameters for simple circuits.
As we have discussed that out of various triggering methods to turn the SCR, gate triggering is the most efficient and reliable method. Most of the control applications use this type of triggering because the desired instant of SCR turning is possible with gate triggering method.
This document provides an outline and overview of a hands-on relay school covering transmission protection theory including symmetrical components and fault calculations. It discusses power system problems like faults and disturbances, different fault types, and introduces symmetrical components and how they are used to analyze balanced and unbalanced systems. It also covers per unit systems, calculating sequence networks for faults, and evaluating transmission line, generator, and transformer impedances.
The document discusses three-phase circuits and provides information on:
- The advantages of three-phase supply systems such as higher efficiency of power transfer and smoother load characteristics.
- Key concepts like phase sequence, balanced/unbalanced supply and load, and the relationships between line and phase voltages and currents.
- How to calculate power in a balanced three-phase system and use two wattmeters to measure total power and power factor.
1. The document discusses symmetrical components, which allow representation of unbalanced three-phase quantities as the sum of three balanced components.
2. It introduces the positive, negative, and zero sequence components and the transformation matrix used to relate the symmetrical components to the original unbalanced quantities.
3. Symmetrical components are useful for simplifying analysis of unbalanced conditions like single line-to-ground faults in power systems. Sequence impedances can be used to model devices and transmission lines.
1) The document discusses the working principle, types, EMF equation, and equivalent circuit of transformers. It describes how transformers work by mutual induction between two inductively coupled coils.
2) Transformers can be classified by construction (shell, core, berry types) and by functioning (step-up, step-down, isolation transformers). The EMF equation defines the transformation ratio between primary and secondary voltages and currents.
3) Equivalent circuits are used to model transformer behavior on no-load and load conditions. Losses are represented by resistances while the magnetizing current is modeled by a reactance. Secondary parameters can be referred to the primary for analysis.
This document discusses the key parameters - resistance, inductance, and capacitance - of overhead transmission lines.
It first defines each parameter and explains that they are uniformly distributed along the line. Resistance is opposition to current flow, inductance is flux linkages per ampere, and capacitance is charge per voltage.
It then goes on to provide formulas for calculating the resistance, inductance, and capacitance of different types of transmission lines. It also discusses factors like skin effect that impact the resistance and analyses methods for determining flux linkages to calculate inductance.
This document discusses voltage drop calculation for lighting and convenience socket circuits. It defines key terms like voltage drop and nominal system voltage. It provides the Philippine Electrical Code provisions limiting voltage drop to 3% for feeders and branch circuits, and 5% total. Formulas are given for calculating voltage drop based on current, conductor length, material properties, and cross-sectional area. Sample calculations demonstrate applying the formulas. The document also introduces VPCM, JGC Philippines' in-house software for automating voltage drop calculations, and generating outputs like block diagrams, panel schedules, and cable schedules.
This power point presentation provides an overview of fault analysis and sequence networks in power systems. It defines different types of faults including open circuit faults, short circuit faults, symmetrical faults, and unsymmetrical faults. Symmetrical faults involve all three phases and remain balanced, while unsymmetrical faults involve one or two phases. Sequence networks, including positive, negative, and zero sequence networks are used for fault analysis. The presentation describes each type of fault and sequence network in detail.
Types of conductors, line parameters, calculation of inductance and capacitance of single and double circuit transmission lines, three phase lines with bundle conductors. Skin effect and
proximity effect.
This document provides an overview of transmission line modeling and analysis. It begins with assigning homework problems and then reviews electric field concepts such as Gauss's law and voltage difference calculations. Models for transmission line capacitance and inductance are developed considering both single and multi-conductor cases. Examples are provided to demonstrate how to calculate per phase capacitance, resistance, and inductance values for different conductor types using data from standard tables. Additional transmission line topics like multi-circuit lines, underground cables, and corona discharge are also briefly discussed.
This document discusses electromagnetic transmission lines and the Smith chart. It introduces equivalent electrical circuit models for coaxial cables, microstrip lines, and twin lead transmission lines using distributed inductors and capacitors. The telegrapher's equations are derived from Kirchhoff's laws. For sinusoidal waves on the transmission lines, phasor analysis is used. Key concepts covered include characteristic impedance, propagation velocity, wavelength, and modeling forward and backward traveling waves.
This document contains lecture notes on electrostatics and the application of Gauss' law from a course on electromagnetic theory taught by Arpan Deyasi. It defines line charge density, surface charge density, and volume charge density. It then uses Gauss' law to derive expressions for the electric field and potential due to different charge distributions, including line charges, surface charges on a ring and plane, and volume charges in a cylinder and sphere. Example problems are worked through applying Gauss' law to find electric fields and potentials for these various charge distributions.
The document discusses various circuit analysis theorems including Thévenin's theorem, Norton's theorem, and superposition theorem. Thévenin's theorem states that any linear bilateral network can be reduced to an equivalent circuit with a voltage source and series resistance. Norton's theorem is the dual of Thévenin's theorem, representing an equivalent circuit with a current source and parallel conductance. Superposition theorem allows analyzing circuit responses by separately applying each independent source and summing the responses.
This document discusses simultaneous AC-DC power transmission through overhead transmission lines. It proposes a scheme where conductors can carry both AC and DC power independently. The DC power is injected at the neutral point of zig-zag transformers to avoid core saturation. Simulation studies are carried out to control the independent AC and DC power flows. This scheme allows existing transmission lines to be upgraded for higher power transfer without modifications to the lines, increasing their utilization.
The document provides the solution to a physics problem involving two resistors connected in series and parallel configurations. When connected in series, their effective resistance is 3 ohms, and when connected in parallel it is 2/3 ohms. Using these values and equations for series and parallel resistances, the problem determines that the individual resistances of the two resistors are 2 ohms and 1 ohm.
This document contains a series of questions and answers related to electronic devices and circuits. It includes questions about semiconductor charge densities, the mass action law, Einstein's relationship for semiconductors, PN junction characteristics such as reverse saturation current and depletion layer widths, and properties of diodes, rectifiers and other components. Definitions and equations are provided as answers to explain concepts like diffusion length, transformer utilization factor, and the advantages of different rectifier circuits.
Threshold voltage model for hetero-gate-dielectric tunneling field effect tra...IJECEIAES
In this paper, a two dimensional analytical model of the threshold voltage for HGD TFET structure has been proposed. We have also presented the analytical models for the tunneling width and the channel potential. The potential model is used to develop the physics based model of threshold voltage by exploring the transition between linear to exponential dependence of drain current on the gate bias. The proposed model depends on the drain voltage, gate dielectric near the source and drain, silicon film thickness, work function of gate metal and oxide thickness. The accuracy of the proposed model is verified by simulation results of 2-D ATLAS simulator. Due to the reduction of the equivalent oxide thickness, the coupling between the gate and the channel junction enhances which results in lower threshold voltage. Tunneling width becomes narrower at a given gate voltage for the optimum channel concentration of 10 16 /cm 3 . The higher concentration in the source (N s ) causes a steep bending in the conduction and valence bands compared to the lower concentration which results in smaller tunneling width at the source-channel interface.
An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. ... The majority of these systems rely upon three-phase AC power—the standard for large-scale power transmission and distribution across the modern world.
This document proposes and validates an equivalent circuit model for a wireless power transfer system capable of transferring 220W of power over a 30cm air gap with 95% efficiency. The model represents the transmitter and receiver coils as inductors with low mutual coupling. Analytical expressions for the model are derived and validated using finite element analysis and experimental results. Loss analysis is also performed to investigate skin effect and proximity effect losses at high operating frequencies. A new coil spatial design is proposed to reduce such losses compared to conventional coil designs.
The document discusses the calculation of inductance for transmission lines. It begins by deriving the inductance of a single wire, accounting for flux both inside and outside the wire. It then extends this to calculate the inductance of a two-conductor line, where the fluxes partially cancel each other out. Finally, it presents a general formula for the inductance of a multi-conductor transmission line with an arbitrary geometry, including the effects of mutual inductance between the phases. As an example, it calculates the inductance and reactance of a typical 3-phase 60Hz line with a bundled conductor configuration.
This document summarizes a research paper that proposes a method for enhancing power system stability by controlling high-voltage direct current (HVDC) power flow through existing alternating current (AC) transmission lines. The method involves converting existing double circuit AC lines into composite AC-DC lines by allowing the lines to simultaneously carry AC power and superimposed DC power. This is done without requiring any changes to the conductors, insulators, or towers of the original AC line. The addition of controlled DC power flow improves stability and allows the lines to be loaded closer to their thermal limits. Simulation and experimental studies were carried out to validate the coordinated and independent control of AC and DC power flows through the converted lines.
Kinetics of X-ray conductivity for an ideal wide-gap semiconductor irradiated...Andrii Sofiienko
This document discusses the development of a kinetic theory to describe the X-ray conductivity (XRC) of semiconductors and dielectrics when irradiated by X-rays. It begins by outlining the need for such a theory and which characteristics it should describe. It then presents the initial stages of developing the theory, including modeling an ideal semiconductor at low excitation levels and deriving expressions for the spatial distribution of free electrons and holes and their lifetimes. The document also examines how the electric field of free charge carriers affects the distributions as excitation increases and considers incorporating the Coulomb interaction between carriers.
This document summarizes a lecture on developing transmission line models. It begins by providing reading assignments and homework/exam due dates for an electrical engineering power systems analysis course. It then discusses developing inductance models for single and multiple conductor transmission lines. Key points include deriving the inductance of a single wire, considering flux linkages both inside and outside the wire. It then extends this to models for two conductor lines, accounting for flux cancellation between conductors. Finally, it discusses modeling multi-conductor bundle lines by considering the mutual inductances between conductors.
The document discusses the conductor material required for various overhead and underground transmission line systems. It derives the ratios of conductor material required for different AC and DC systems by equating power transmitted and line losses. For overhead lines, DC two-wire with mid-point earthed requires 0.25 times the material of DC two-wire with one end earthed. Single phase AC two-wire requires 1/√2 times and three phase three-wire requires 1/3 times the material of DC two-wire with one end earthed. Similarly, it compares underground cable systems and provides a table comparing all the transmission systems.
1) The document discusses different types of capacitors including parallel plate, cylindrical, and spherical capacitors. Equations for electrostatic potential and electric field are derived for each type.
2) Examples problems are worked out on determining the capacitance of a parallel plate capacitor when a dielectric slab is inserted, and the capacitance of a coaxial cylindrical capacitor with dielectrics of different permittivities in each region.
3) Key equations presented include the capacitance of parallel plate, cylindrical, and spherical capacitors in terms of their geometric parameters and dielectric properties.
CURRENT ELECTRICITY/ELECTROSTATICS FOR CBSE FREE REVISION SHEET BY ANURAG TY...ANURAG TYAGI CLASSES (ATC)
This document contains a sample physics exam paper on electrostatics for Class 12. It has questions ranging from 1 to 5 marks testing various concepts related to electric field, electric potential, electric dipoles, capacitors and electrostatics. The paper tests calculations of electric field, potential, capacitance and energy for different electrostatic configurations. It also has questions on Gauss's law, parallel plate capacitors, charging of capacitors, Van de Graaff generator and motion of electric dipoles in uniform electric fields.
Similar to POWER SUPPLY SYSTEMS& DISTRIBUTION SYSTEMS (20)
Using recycled concrete aggregates (RCA) for pavements is crucial to achieving sustainability. Implementing RCA for new pavement can minimize carbon footprint, conserve natural resources, reduce harmful emissions, and lower life cycle costs. Compared to natural aggregate (NA), RCA pavement has fewer comprehensive studies and sustainability assessments.
Comparative analysis between traditional aquaponics and reconstructed aquapon...bijceesjournal
The aquaponic system of planting is a method that does not require soil usage. It is a method that only needs water, fish, lava rocks (a substitute for soil), and plants. Aquaponic systems are sustainable and environmentally friendly. Its use not only helps to plant in small spaces but also helps reduce artificial chemical use and minimizes excess water use, as aquaponics consumes 90% less water than soil-based gardening. The study applied a descriptive and experimental design to assess and compare conventional and reconstructed aquaponic methods for reproducing tomatoes. The researchers created an observation checklist to determine the significant factors of the study. The study aims to determine the significant difference between traditional aquaponics and reconstructed aquaponics systems propagating tomatoes in terms of height, weight, girth, and number of fruits. The reconstructed aquaponics system’s higher growth yield results in a much more nourished crop than the traditional aquaponics system. It is superior in its number of fruits, height, weight, and girth measurement. Moreover, the reconstructed aquaponics system is proven to eliminate all the hindrances present in the traditional aquaponics system, which are overcrowding of fish, algae growth, pest problems, contaminated water, and dead fish.
TIME DIVISION MULTIPLEXING TECHNIQUE FOR COMMUNICATION SYSTEMHODECEDSIET
Time Division Multiplexing (TDM) is a method of transmitting multiple signals over a single communication channel by dividing the signal into many segments, each having a very short duration of time. These time slots are then allocated to different data streams, allowing multiple signals to share the same transmission medium efficiently. TDM is widely used in telecommunications and data communication systems.
### How TDM Works
1. **Time Slots Allocation**: The core principle of TDM is to assign distinct time slots to each signal. During each time slot, the respective signal is transmitted, and then the process repeats cyclically. For example, if there are four signals to be transmitted, the TDM cycle will divide time into four slots, each assigned to one signal.
2. **Synchronization**: Synchronization is crucial in TDM systems to ensure that the signals are correctly aligned with their respective time slots. Both the transmitter and receiver must be synchronized to avoid any overlap or loss of data. This synchronization is typically maintained by a clock signal that ensures time slots are accurately aligned.
3. **Frame Structure**: TDM data is organized into frames, where each frame consists of a set of time slots. Each frame is repeated at regular intervals, ensuring continuous transmission of data streams. The frame structure helps in managing the data streams and maintaining the synchronization between the transmitter and receiver.
4. **Multiplexer and Demultiplexer**: At the transmitting end, a multiplexer combines multiple input signals into a single composite signal by assigning each signal to a specific time slot. At the receiving end, a demultiplexer separates the composite signal back into individual signals based on their respective time slots.
### Types of TDM
1. **Synchronous TDM**: In synchronous TDM, time slots are pre-assigned to each signal, regardless of whether the signal has data to transmit or not. This can lead to inefficiencies if some time slots remain empty due to the absence of data.
2. **Asynchronous TDM (or Statistical TDM)**: Asynchronous TDM addresses the inefficiencies of synchronous TDM by allocating time slots dynamically based on the presence of data. Time slots are assigned only when there is data to transmit, which optimizes the use of the communication channel.
### Applications of TDM
- **Telecommunications**: TDM is extensively used in telecommunication systems, such as in T1 and E1 lines, where multiple telephone calls are transmitted over a single line by assigning each call to a specific time slot.
- **Digital Audio and Video Broadcasting**: TDM is used in broadcasting systems to transmit multiple audio or video streams over a single channel, ensuring efficient use of bandwidth.
- **Computer Networks**: TDM is used in network protocols and systems to manage the transmission of data from multiple sources over a single network medium.
### Advantages of TDM
- **Efficient Use of Bandwidth**: TDM all
Embedded machine learning-based road conditions and driving behavior monitoringIJECEIAES
Car accident rates have increased in recent years, resulting in losses in human lives, properties, and other financial costs. An embedded machine learning-based system is developed to address this critical issue. The system can monitor road conditions, detect driving patterns, and identify aggressive driving behaviors. The system is based on neural networks trained on a comprehensive dataset of driving events, driving styles, and road conditions. The system effectively detects potential risks and helps mitigate the frequency and impact of accidents. The primary goal is to ensure the safety of drivers and vehicles. Collecting data involved gathering information on three key road events: normal street and normal drive, speed bumps, circular yellow speed bumps, and three aggressive driving actions: sudden start, sudden stop, and sudden entry. The gathered data is processed and analyzed using a machine learning system designed for limited power and memory devices. The developed system resulted in 91.9% accuracy, 93.6% precision, and 92% recall. The achieved inference time on an Arduino Nano 33 BLE Sense with a 32-bit CPU running at 64 MHz is 34 ms and requires 2.6 kB peak RAM and 139.9 kB program flash memory, making it suitable for resource-constrained embedded systems.
Understanding Inductive Bias in Machine LearningSUTEJAS
This presentation explores the concept of inductive bias in machine learning. It explains how algorithms come with built-in assumptions and preferences that guide the learning process. You'll learn about the different types of inductive bias and how they can impact the performance and generalizability of machine learning models.
The presentation also covers the positive and negative aspects of inductive bias, along with strategies for mitigating potential drawbacks. We'll explore examples of how bias manifests in algorithms like neural networks and decision trees.
By understanding inductive bias, you can gain valuable insights into how machine learning models work and make informed decisions when building and deploying them.
A SYSTEMATIC RISK ASSESSMENT APPROACH FOR SECURING THE SMART IRRIGATION SYSTEMSIJNSA Journal
The smart irrigation system represents an innovative approach to optimize water usage in agricultural and landscaping practices. The integration of cutting-edge technologies, including sensors, actuators, and data analysis, empowers this system to provide accurate monitoring and control of irrigation processes by leveraging real-time environmental conditions. The main objective of a smart irrigation system is to optimize water efficiency, minimize expenses, and foster the adoption of sustainable water management methods. This paper conducts a systematic risk assessment by exploring the key components/assets and their functionalities in the smart irrigation system. The crucial role of sensors in gathering data on soil moisture, weather patterns, and plant well-being is emphasized in this system. These sensors enable intelligent decision-making in irrigation scheduling and water distribution, leading to enhanced water efficiency and sustainable water management practices. Actuators enable automated control of irrigation devices, ensuring precise and targeted water delivery to plants. Additionally, the paper addresses the potential threat and vulnerabilities associated with smart irrigation systems. It discusses limitations of the system, such as power constraints and computational capabilities, and calculates the potential security risks. The paper suggests possible risk treatment methods for effective secure system operation. In conclusion, the paper emphasizes the significant benefits of implementing smart irrigation systems, including improved water conservation, increased crop yield, and reduced environmental impact. Additionally, based on the security analysis conducted, the paper recommends the implementation of countermeasures and security approaches to address vulnerabilities and ensure the integrity and reliability of the system. By incorporating these measures, smart irrigation technology can revolutionize water management practices in agriculture, promoting sustainability, resource efficiency, and safeguarding against potential security threats.
Introduction- e - waste – definition - sources of e-waste– hazardous substances in e-waste - effects of e-waste on environment and human health- need for e-waste management– e-waste handling rules - waste minimization techniques for managing e-waste – recycling of e-waste - disposal treatment methods of e- waste – mechanism of extraction of precious metal from leaching solution-global Scenario of E-waste – E-waste in India- case studies.
2. Unit-i Electric Power Generation& Economic
Considerations
Unit-ii Power Supply Systems& Distribution
Systems
Unit-iii Inductance & Capacitance Calculations
Unit-iv Performance Of Transmission Lines
Unit-v Overhead Line Insulators
6 October 2020 D.Rajesh Asst.Prof. EEE Department 2
3. POWER SUPPLY SYSTEMS& DISTRIBUTION
SYSTEMS:
Transmission and distribution systems- D.C 2-wire
and 3- wire systems, A.C single phase , three phase
and 4-wire systems, comparison of copper efficiency.
Primary and secondary distribution systems,
concentrated & uniformly distributed loads on
distributors fed at both ends, ring distributor,
voltage drop and power loss calculation,
Kelvin’slaw.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 3
4. Power
Transmission
D.C
D.C. two-wire
D.C. two-wire
with mid-point
earthed
D.C. three-wire
A.C
Single-phase A.C.
system
Single-phase two-
wire
Single-phase two-
wire with mid-
point earthed
Single-phase
three-wire
Two-phase A.C.
system
Two-phase four-
wire
Two-phase three
wire.
Three-phase A.C.
system
Three-phase
three-wire
Three-phase four-
wire
6 October 2020 D.Rajesh Asst.Prof. EEE Department 4
5. 6 October 2020 D.Rajesh Asst.Prof. EEE Department 5
Overhead
Under ground
6. (i) Same power (P watts) transmitted by each system.
(ii) The distance (l metres) over which power is
transmitted remains the same.
(iii) The line losses (W watts) are the same in each
case.
(iv) The maximum voltage between any conductor
and earth (𝑉
𝑚) is the same in each case.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 6
7. Max. voltage between conductors = 𝑉
𝑚 ,
Power to be transmitted = P= 𝑉
𝑚𝐼1 1
∴ Load current, 𝐼1 = P/ 𝑉
𝑚
If 𝑅1 is the resistance of each line conductor, then,
𝑅1 = ρ l/ 𝑎1
where 𝑎1 is the area of X-section of the conductor.
copper losses in line W = 𝐼1
2
𝑅1 + 𝐼1
2
𝑅1
=2𝐼1
2
𝑅1
6 October 2020 D.Rajesh Asst.Prof. EEE Department 7
1
1
2
8. The maximum voltage between any conductor and earth is 𝑉
𝑚 so that maximum
voltage between conductors is 2 𝑉
𝑚. 𝑅2 is the resistance of each line conductor
Power to be transmitted
P= 𝑉
𝑚𝐼2+ 𝑉
𝑚𝐼2=2 𝑉
𝑚𝐼2
Load current, 𝐼2 = P/2 𝑉
𝑚
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 3
2𝑉
𝑚𝐼2= 𝑉
𝑚𝐼1
𝐼2 =
𝐼1
2
copper losses in line W = 𝐼2
2
𝑅2+ 𝐼2
2
𝑅2 = 2 𝐼2
2
𝑅2
From eq 4
W=2(
𝐼1
2
)2
𝑅2 =
𝐼1
2
2
𝑅2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 8
3
4
5
9. Compare eq 2 & 5
2𝐼1
2
𝑅1 = (
𝐼1
2
2
) 𝑅2
𝑅1
𝑅2
=
1
4
𝑎1
𝑎2
=4 (where R = ρ l/ 𝑎)
𝑎1=X-area of conductor in 2 wire dc system
𝑎2= X-area of conductor in 2 wire dc system with mid-point earthed
Then
volume of copper wire Two−wire D.C system with mid−point earthed
volume of copper wire Two−wire D.C system
=
𝑎2∗𝑙2
𝑎1∗𝑙1
=
1
4
𝑎1∗2𝑙
𝑎1∗2𝑙
=
1
4
where 𝑙1 = 𝑙2=l+l
Hence, the volume of conductor material required in Two−wire D.C system with
mid−point earthed is one-fourth of that required in a two-wire D.C system with
one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 9
10. If the load is balanced, the current in the neutral wire is zero. Assuming balanced loads,
Power to be transmitted
P= 𝑉
𝑚𝐼3+ 𝑉
𝑚𝐼3=2 𝑉
𝑚𝐼3 6
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 6
2𝑉
𝑚𝐼3= 𝑉
𝑚𝐼1
𝐼3 =
𝐼1
2
7
Let 𝑅3 is the resistance of each line conductor,
the area of X-section of neutral wire to be half that of the outer wire,
copper losses in line W = 𝐼3
2
𝑅3+ 𝐼3
2
𝑅3 = 2𝐼3
2
𝑅3 8
From eq 7
W=2(
𝐼1
2
)2
𝑅3 =
𝐼1
2
2
𝑅3 9
6 October 2020 D.Rajesh Asst.Prof. EEE Department 10
11. Compare eq 2 & 8
2𝐼1
2
𝑅1 =
𝐼1
2
2
𝑅3
𝑅1
𝑅3
=
1
4
𝑅3 = ρ l/ 𝑎3 where 𝑎3 is the area of X-section of the conductor.
𝑎1
𝑎3
=4
Then
volume of copper wire Three−wire D.C
volume of copper wire Two−wire D.C system
=
𝑎3∗𝑙3
𝑎1∗𝑙1
=
1
4
𝑎1∗2.5𝑙
𝑎1∗2𝑙
=
2.5
8
where 𝑙3=l+l+0.5l
=0.3125
Hence, the volume of conductor material required in Three−wire D.C system is 0.3125
times of that required in a two-wire D.C system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 11
12. The maximum voltage between conductors is 𝑉
𝑚, so that r.m.s. value of voltage
between them is
𝑉𝑚
2
. Assuming the load power factor to be cos φ, load current 𝐼4
Power supplied P=
𝑉𝑚
2
𝐼4 cos φ 10
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 10
𝑉𝑚
2
𝐼4 cos φ= 𝑉
𝑚𝐼1
𝐼4=
2𝐼1
cos φ
11
Let 𝑅4 is the resistance of each line conductor
copper losses in line W = 𝐼4
2
𝑅4+ 𝐼4
2
𝑅4 = 2𝐼4
2
𝑅4
=2(
2𝐼1
cos φ
)2 𝑅4 =4
𝐼1
2
𝑐𝑜𝑠2φ
𝑅4 12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 12
13. Comparing copper losses with 2 wire d.c system
4
𝐼1
2
𝑐𝑜𝑠2φ
𝑅4= 2𝐼1
2
𝑅1
𝑅4
𝑅1
=
𝑐𝑜𝑠2φ
2
𝑎4
𝑎1
=
2
𝑐𝑜𝑠2φ
13
volume of copper wire 1−phase 2− wire
volume of copper wire Two−wire D.C system
=
𝑎4𝑙4
𝑎1𝑙1
=
2
𝑐𝑜𝑠2φ𝑎12𝑙
𝑎12𝑙
=
2
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required in this system is
2
𝑐𝑜𝑠2φ
times
that of 2-wire d.c. system with the one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 13
14. The two wires possess equal and opposite voltages to earth (i.e., 𝑉
𝑚).
Therefore, the maximum voltage between the two wires is
𝑉𝑚
2
. The
r.m.s. value of voltage between conductors is =2
𝑉𝑚
2
= 2 𝑉
𝑚.
Assuming the power factor of the load to be cos φ, load current 𝐼5
Power supplied P= 2 𝑉
𝑚𝐼5 cos φ 14
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 14
2 𝑉
𝑚𝐼5 cos φ= 𝑉
𝑚𝐼1
𝐼5=
𝐼1
2 cos φ
15
6 October 2020 D.Rajesh Asst.Prof. EEE Department 14
15. Let 𝑅5 is the resistance of each line conductor
copper losses in line W = 𝐼5
2
𝑅5+ 𝐼5
2
𝑅5 = 2𝐼5
2
𝑅5
=2(
𝐼1
2 cos φ
)2 𝑅5 =
𝐼1
2
𝑐𝑜𝑠2φ
𝑅5
Comparing copper losses with 2 wire d.c system
𝐼1
2
𝑐𝑜𝑠2φ
𝑅5 =2𝐼1
2
𝑅1
𝑅5
𝑅1
= 2𝑐𝑜𝑠2φ
𝑎5
𝑎1
=
1
2𝑐𝑜𝑠2φ
volume of copper wire 1−phase 2− wire 𝑤𝑖𝑡ℎ 𝑚𝑖𝑑 − 𝑝𝑜𝑖𝑛𝑡 𝑒𝑎𝑟𝑡ℎ𝑒𝑑
volume of copper wire Two−wire D.C system
𝑎5𝑙5
𝑎1𝑙1
=
1
2𝑐𝑜𝑠2φ 𝑎12𝑙
𝑎12𝑙
=
1
2𝑐𝑜𝑠2φ
Hence the volume of conductor material required in this system is
1
2𝑐𝑜𝑠2φ
times that of 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 15
16. If the load is balanced, the current through the neutral wire is zero.
Assuming balanced load,
The two wires possess equal and opposite voltages to earth (i.e., 𝑉
𝑚).
Therefore, the maximum voltage between the two wires is
𝑉𝑚
2
. The r.m.s.
value of voltage between conductors is 2
𝑉𝑚
2
= 2 𝑉
𝑚. Assuming the
power factor of the load to be cos φ, load current 𝐼6
Power supplied P= 2 𝑉
𝑚𝐼6 cos φ 16
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 16
2 𝑉
𝑚𝐼6 cos φ= 𝑉
𝑚𝐼1
𝐼6=
𝐼1
2 cos φ
17
6 October 2020 D.Rajesh Asst.Prof. EEE Department 16
17. Let 𝑅6 is the resistance of each line conductor
copper losses in line W = 𝐼6
2
𝑅6+ 𝐼6
2
𝑅6 = 2𝐼6
2
𝑅6
=2(
𝐼1
2 cos φ
)2 𝑅6 =
𝐼1
2
𝑐𝑜𝑠2φ
𝑅6
Comparing copper losses with 2 wire d.c system
𝐼1
2
𝑐𝑜𝑠2φ
𝑅6 =2𝐼1
2
𝑅1
𝑅6
𝑅1
= 2𝑐𝑜𝑠2φ
𝑎6
𝑎1
=
1
2𝑐𝑜𝑠2φ
volume of copper wire 1−phase3−wire system
volume of copper wire Two−wire D.C system
𝑎6𝑙6
𝑎1𝑙1
=
1
2𝑐𝑜𝑠2φ 𝑎12.5𝑙
𝑎12𝑙
=
0.625
𝑐𝑜𝑠2φ
Hence the volume of conductr material required in this system is
0.625
𝑐𝑜𝑠2φ
times that of 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 17
18. This system can be considered as two independent single-
phase systems, each transmitting one half of the total power.
As the voltage is same (𝑉
𝑚) as in a Single phase 2-wire system
with mid-point earthed, so the current will be half of the
Single phase system
i.e. 𝐼7=
𝐼5
2
=
𝐼1
2 cos φ
2
=
𝐼1
2 2 cos φ
If the current density remains constant the
X-area will be half of the single-phase system
i.e. 𝑎7=
𝑎5
2
=
1
2𝑐𝑜𝑠2φ 𝑎1
2
=
𝑎1
4𝑐𝑜𝑠2φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 18
19. Since wires are four
Then
volume of copper wireTwo phase, 4−wire a.c. system
volume of copper wire Two−wire D.C system
𝑎7𝑙7
𝑎1𝑙1
=
1
4𝑐𝑜𝑠2φ 𝑎14𝑙
𝑎12𝑙
=
1
2𝑐𝑜𝑠2φ
Hence the volume of conductor material required in this system
is
1
2𝑐𝑜𝑠2φ
times that of 2-wire d.c. system with one conductor
earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 19
20. The third or neutral wire is taken from the junction of two-phase windings whose
voltages are in quadrature with each other. Obviously, each phase transmits one
half of the total power. The R.M.S. voltage between outgoing conductor and
neutral =
𝑉𝑚
2
, Let 𝑅8 is the resistance of each line conductor
Total power transmitted=2
𝑉𝑚
2
𝐼8 cos φ
Comparing the power with 2-wire D.C
2
𝑉𝑚
2
𝐼8 cos φ= 𝑉
𝑚𝐼1
𝐼8 =
𝐼1
2cos φ
The middle wire will act as a common return and the current through it will be
𝐼8
2
+ 𝐼8
2
= 2 𝐼8
6 October 2020 D.Rajesh Asst.Prof. EEE Department 20
21. Assuming the current density to be constant, the area of X-section of the neutral wire will be
2 times that of either of the outers.
∴ Resistance of neutral wire=
𝑅8
2
Copper losses in this system
W= 𝐼8
2
𝑅8+ 𝐼8
2
𝑅8 + ( 2 𝐼8)2𝑅8
2
= 2𝐼8
2
𝑅8+ 2𝐼8
2
𝑅8=(2+ 2) 𝐼8
2
𝑅8
Where 𝐼8 =
𝐼1
2cos φ
W=(2+ 2) (
𝐼1
2cos φ)2 𝑅8=(2+ 2)
𝐼1
2𝑅8
2𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
(2+ 2)
𝐼1
2𝑅8
2𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅8
𝑅1
=
4𝑐𝑜𝑠2φ
(2+ 2)
𝑎8
𝑎1
=
(2+ 2)
4𝑐𝑜𝑠2φ
volume of copper wireTwo phase, 3−wire a.c. system
volume of copper wire Two−wire D.C system
𝑎8𝑙8
𝑎1𝑙1
=
(2+ 2)
4𝑐𝑜𝑠2φ 𝑎1(2+ 2)𝑙
𝑎12𝑙
=
1.457
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system is
1.457
𝑐𝑜𝑠2φ times that of 2-wire d.c.
system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 21
22. This system is almost universally adopted for transmission of electric power.
The 3-phase, 3- wire system may be star connected or delta connected.
Maximum voltage between each conductor and neutral =𝑉
𝑚
Let 𝑅9 is the resistance of each line conductor
R.M.S. voltage per phase =
𝑉𝑚
2
Power supplied=3(
𝑉𝑚
2
I9cos φ )
Comparing the power with 2-wire D.C
3
𝑉𝑚
2
𝐼9 cos φ= 𝑉
𝑚𝐼1
𝐼9 =
2𝐼1
3cos φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 22
23. Total copper losses= 3𝐼9
2
𝑅9 =3 (
2𝐼1
3cos φ
)2 𝑅9=
2𝐼1
2
𝑅9
3𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
2𝐼1
2
𝑅9
3𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅9
𝑅1
= 3𝑐𝑜𝑠2φ
𝑎9
𝑎1
=
1
3𝑐𝑜𝑠2φ
volume of copper wire3−Phase, 3−wire system
volume of copper wire Two−wire D.C system
=
𝑎9𝑙9
𝑎1𝑙1
=
1
3𝑐𝑜𝑠2φ𝑎13𝑙
𝑎12𝑙
=
0.5
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system is
0.5
𝑐𝑜𝑠2φ times that required for 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 23
24. In this case, 4th or neutral wire is taken from the neutral point. The area of X-
section of the neutral wire is generally one-half that of the line conductor. If the
loads are balanced, then current through the neutral wire is zero. Assuming
balanced loads and p.f. of the load as cos φ,
Let 𝑅10 is the resistance of each line conductor
R.M.S. voltage per phase =
𝑉𝑚
2
Power supplied=3(
𝑉𝑚
2
I10cos φ )
Comparing the power with 2-wire D.C
3
𝑉𝑚
2
𝐼10 cos φ= 𝑉
𝑚𝐼1
𝐼10 =
2𝐼1
3cos φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 24
25. Total copper losses= 3𝐼10
2
𝑅10 =3 (
2𝐼1
3cos φ
)2 𝑅10=
2𝐼1
2
𝑅10
3𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
2𝐼1
2
𝑅10
3𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅10
𝑅1
= 3𝑐𝑜𝑠2φ
𝑎10
𝑎1
=
1
3𝑐𝑜𝑠2φ
volume of copper wire3−Phase, 3−wire system
volume of copper wire Two−wire D.C system
=
𝑎10𝑙10
𝑎1𝑙1
=
1
3𝑐𝑜𝑠2φ𝑎13.5𝑙
𝑎12𝑙
=
0.583
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system is
0.583
𝑐𝑜𝑠2φ times that required for 2-wire d.c. system with one conductor earthed.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 25
26. In the under-ground system the maximum stress exists
on the insulation between the conductors.
(i) Same power (P watts) transmitted by each system.
(ii) The distance (l meters) over which power is
transmitted remains the same.
(iii) The line losses (W watts) are the same in each case.
(iv) The maximum voltage between conductors (𝑉
𝑚) is
the same in each case.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 26
27. Max. voltage between conductors = 𝑉
𝑚 ,
Power to be transmitted = P= 𝑉
𝑚𝐼1 1
∴ Load current, 𝐼1 = P/ 𝑉
𝑚
If 𝑅1 is the resistance of each line conductor, then,
𝑅1 = ρ l/ 𝑎1
where 𝑎1 is the area of X-section of the conductor.
copper losses in line W = 𝐼1
2
𝑅1 + 𝐼1
2
𝑅1
=2𝐼1
2
𝑅1
6 October 2020 D.Rajesh Asst.Prof. EEE Department 27
1
1
2
28. Maximum voltage between conductors is 𝑉
𝑚. 𝑅2 is the resistance of each line
conductor
Power to be transmitted
P= 𝑉
𝑚𝐼2
Load current, 𝐼2 = P/ 𝑉
𝑚
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 3
𝑉
𝑚𝐼2= 𝑉
𝑚𝐼1
𝐼2 = 𝐼1
copper losses in line W = 𝐼2
2
𝑅2+ 𝐼2
2
𝑅2 = 2 𝐼2
2
𝑅2
From eq 4
W=2( 𝐼1)2 𝑅2 =2𝐼1
2
𝑅2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 28
3
4
5
29. Compare eq 2 & 5
2𝐼1
2
𝑅1 = (𝐼1
2
) 𝑅2
𝑅1
𝑅2
=1
𝑎1
𝑎2
=1 (where R = ρ l/ 𝑎)
𝑎1=X-area of conductor in 2 wire dc system
𝑎2= X-area of conductor in 2 wire dc system with mid-point earthed
Then
volume of copper wire Two−wire D.C system with mid−point earthed
volume of copper wire Two−wire D.C system
=
𝑎2∗𝑙2
𝑎1∗𝑙1
=
𝑎1∗2𝑙
𝑎1∗2𝑙
=1 where 𝑙1 = 𝑙2=l+l
Hence, the volume of conductor material required in this system is the same as
that for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 29
30. If the load is balanced, the current in the neutral wire is zero. Assuming balanced loads,
Power to be transmitted
P= 𝑉
𝑚𝐼3 6
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 6
𝑉
𝑚𝐼3= 𝑉
𝑚𝐼1
𝐼3 = 𝐼1 7
Let 𝑅3 is the resistance of each line conductor,
the area of X-section of neutral wire to be half that of the outer wire,
copper losses in line W = 𝐼3
2
𝑅3+ 𝐼3
2
𝑅3 = 2𝐼3
2
𝑅3 8
From eq 7
W=2( 𝐼1)2
𝑅3 =2𝐼1
2
𝑅3 9
6 October 2020 D.Rajesh Asst.Prof. EEE Department 30
31. Compare eq 2 & 8
2𝐼1
2
𝑅1 = 2(𝐼1
2
) 𝑅3
𝑅1
𝑅3
=1
𝑎1
𝑎3
=1 𝑅3 = ρ l/ 𝑎3
where 𝑎3 is the area of X-section of the conductor.
Then
volume of copper wire Three−wire D.C
volume of copper wire Two−wire D.C system
=
𝑎3∗𝑙3
𝑎1∗𝑙1
=
𝑎1∗2.5𝑙
𝑎1∗2𝑙
=
2.5
2
where 𝑙3=l+l+0.5l
=1.25
Hence, the volume of conductor material required in the system is 1·25 times
that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 31
32. The maximum voltage between conductors is 𝑉
𝑚, so that r.m.s. value of voltage
between them is
𝑉𝑚
2
. Assuming the load power factor to be cos φ, load current 𝐼4
Power supplied P=
𝑉𝑚
2
𝐼4 cos φ 10
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 10
𝑉𝑚
2
𝐼4 cos φ= 𝑉
𝑚𝐼1
𝐼4=
2𝐼1
cos φ
11
Let 𝑅4 is the resistance of each line conductor
copper losses in line W = 𝐼4
2
𝑅4+ 𝐼4
2
𝑅4 = 2𝐼4
2
𝑅4
=2(
2𝐼1
cos φ
)2 𝑅4 =4
𝐼1
2
𝑐𝑜𝑠2φ
𝑅4 12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 32
33. Comparing copper losses with 2 wire d.c system
4
𝐼1
2
𝑐𝑜𝑠2φ
𝑅4= 2𝐼1
2
𝑅1
𝑅4
𝑅1
=
𝑐𝑜𝑠2φ
2
𝑎4
𝑎1
=
2
𝑐𝑜𝑠2φ
13
volume of copper wire 1−phase 2− wire
volume of copper wire Two−wire D.C system
=
𝑎4𝑙4
𝑎1𝑙1
=
2
𝑐𝑜𝑠2φ𝑎12𝑙
𝑎12𝑙
=
2
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required in this system is
2
𝑐𝑜𝑠2φ
times
that of 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 33
34. The maximum value of voltage between the outers is 𝑉
𝑚.
Therefore, the r.m.s. value of voltage is
𝑉𝑚
2
Assuming the power factor of the load to be cos φ, load current 𝐼5
Power supplied P=
𝑉𝑚
2
𝐼5 cos φ 14
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 14
𝑉𝑚
2
𝐼5 cos φ= 𝑉
𝑚𝐼1
𝐼5=
2𝐼1
cos φ
15
6 October 2020 D.Rajesh Asst.Prof. EEE Department 34
35. Let 𝑅5 is the resistance of each line conductor
copper losses in line W = 𝐼5
2
𝑅5+ 𝐼5
2
𝑅5 = 2𝐼5
2
𝑅5
=2(
2𝐼1
cos φ
)2 𝑅5 =
4𝐼1
2
𝑐𝑜𝑠2φ
𝑅5
Comparing copper losses with 2 wire d.c system
4𝐼1
2
𝑐𝑜𝑠2φ
𝑅5 =2𝐼1
2
𝑅1
𝑅5
𝑅1
=
𝑐𝑜𝑠2φ
2
𝑎5
𝑎1
=
2
𝑐𝑜𝑠2φ
volume of copper wire 1−phase 2− wire 𝑤𝑖𝑡ℎ 𝑚𝑖𝑑 − 𝑝𝑜𝑖𝑛𝑡 𝑒𝑎𝑟𝑡ℎ𝑒𝑑
volume of copper wire Two−wire D.C system
𝑎5𝑙5
𝑎1𝑙1
=
2
𝑐𝑜𝑠2φ 𝑎12𝑙
𝑎12𝑙
=
2
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required in this system is
2
𝑐𝑜𝑠2φ
times that required in 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 35
36. If the load is balanced, the current through the neutral wire is zero.
Assuming balanced load,
The maximum value of voltage between the outers is 𝑉
𝑚. Therefore, the
r.m.s. value of voltage is
𝑉𝑚
2
.
Assuming the power factor of the load to be cos φ, load current 𝐼6
Power supplied P=
𝑉𝑚
2
𝐼6 cos φ 16
Since from assumption 1 the power transmitted is same
for all systems so from eq 1& 16
𝑉𝑚
2
𝐼6 cos φ= 𝑉
𝑚𝐼1
𝐼6=
2𝐼1
cos φ
17
6 October 2020 D.Rajesh Asst.Prof. EEE Department 36
37. Let 𝑅6 is the resistance of each line conductor
copper losses in line W = 𝐼6
2
𝑅6+ 𝐼6
2
𝑅6 = 2𝐼6
2
𝑅6
=2(
2𝐼1
cos φ
)2 𝑅6 =
4𝐼1
2
𝑐𝑜𝑠2φ
𝑅6
Comparing copper losses with 2 wire d.c system
4𝐼1
2
𝑐𝑜𝑠2φ
𝑅6 =2𝐼1
2
𝑅1
𝑅6
𝑅1
=
𝑐𝑜𝑠2φ
2
𝑎6
𝑎1
=
2
𝑐𝑜𝑠2φ
volume of copper wire 1−phase 2− wire 𝑤𝑖𝑡ℎ 𝑚𝑖𝑑 − 𝑝𝑜𝑖𝑛𝑡 𝑒𝑎𝑟𝑡ℎ𝑒𝑑
volume of copper wire Two−wire D.C system
𝑎6𝑙6
𝑎1𝑙1
= =
2
𝑐𝑜𝑠2φ 𝑎12.5𝑙
𝑎12𝑙
=
2.5
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required in this system is
2.5
𝑐𝑜𝑠2φ
times that required in 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 37
38. This system can be considered as two independent single-phase
systems, each transmitting one half of the total power.
Current (𝐼7) in each conductor will be half that in single-phase 2-
wire system. Consequently, area of X-section of each conductor is
also half but as there are four wires, so volume of conductor material
used is the same as in a single phase, 2-wire system
i.e. 𝐼7=
𝐼5
2
=
2𝐼1
cos φ
2
=
𝐼1
2 cos φ
If the current density remains constant the
X-area will be half of the single-phase system
i.e. 𝑎7=
𝑎5
2
=
2
𝑐𝑜𝑠2φ
2
=
1
𝑐𝑜𝑠2φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 38
39. Since wires are four
Then
volume of copper wireTwo phase, 4−wire a.c. system
volume of copper wire Two−wire D.C system
𝑎7𝑙7
𝑎1𝑙1
=
1
𝑐𝑜𝑠2φ 𝑎14𝑙
𝑎12𝑙
=
2
𝑐𝑜𝑠2φ
Hence, volume of conductor material required in this
system is
2
𝑐𝑜𝑠2φ
times that required in 2- wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 39
40. Let us suppose that maximum voltage between the outers is 𝑉
𝑚. Then
maximum voltage between either outer and neutral wire is
𝑉𝑚
2
R.M.S. voltage between outer and neutral wire=
𝑉𝑚
2
2
=
𝑉𝑚
2
Total power transmitted=2
𝑉𝑚
2
𝐼8 cos φ = 𝑉
𝑚 𝐼8 cos φ
Comparing the power with 2-wire D.C
𝑉
𝑚 𝐼8 cos φ= 𝑉
𝑚𝐼1
𝐼8 =
𝐼1
cos φ
The middle wire will act as a common return and the current through it will be
𝐼8
2
+ 𝐼8
2
= 2 𝐼8
6 October 2020 D.Rajesh Asst.Prof. EEE Department 40
41. Assuming the current density to be constant, the area of X-section of the neutral wire will be
2 times that of either of the outers.
∴ Resistance of neutral wire=
𝑅8
2
Copper losses in this system
W= 𝐼8
2
𝑅8+ 𝐼8
2
𝑅8 + ( 2 𝐼8)2𝑅8
2
= 2𝐼8
2
𝑅8+ 2𝐼8
2
𝑅8=(2+ 2) 𝐼8
2
𝑅8
Where 𝐼8 =
𝐼1
cos φ
W=(2+ 2) (
𝐼1
cos φ)2
𝑅8=(2+ 2)
𝐼1
2𝑅8
𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
(2+ 2)
𝐼1
2𝑅8
𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅8
𝑅1
=
2𝑐𝑜𝑠2φ
(2+ 2)
𝑎8
𝑎1
=
(2+ 2)
2𝑐𝑜𝑠2φ
volume of copper wireTwo phase, 3−wire a.c. system
volume of copper wire Two−wire D.C system
𝑎8𝑙8
𝑎1𝑙1
=
(2+ 2)
2𝑐𝑜𝑠2φ 𝑎1(2+ 2)𝑙
𝑎12𝑙
=
2.914
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system is
2.914
𝑐𝑜𝑠2φ times that of 2-wire d.c.
system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 41
42. This system is almost universally adopted for transmission of electric power. The 3-phase,
3- wire system may be star connected or delta connected.
Maximum voltage between conductors =𝑉
𝑚, Let 𝑅9 is the resistance of each line conductor
Then maximum voltage between each phase and neutral is
𝑉𝑚
3
R.M.S. voltage per phase =
𝑉𝑚
3
2
=
𝑉𝑚
6
Power supplied=3(
𝑉𝑚
6
I9cos φ )
Comparing the power with 2-wire D.C
3
𝑉𝑚
6
𝐼9 cos φ= 𝑉
𝑚𝐼1
𝐼9 =
6𝐼1
3cos φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 42
43. Total copper losses= 3𝐼9
2
𝑅9 =3 (
6𝐼1
3cos φ
)2 𝑅9=
2𝐼1
2
𝑅9
𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
2𝐼1
2
𝑅9
𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅9
𝑅1
= 𝑐𝑜𝑠2φ
𝑎9
𝑎1
=
1
𝑐𝑜𝑠2φ
volume of copper wire3−Phase, 3−wire system
volume of copper wire Two−wire D.C system
=
𝑎9𝑙9
𝑎1𝑙1
=
1
𝑐𝑜𝑠2φ𝑎13𝑙
𝑎12𝑙
=
1.5
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system is
1.5
𝑐𝑜𝑠2φ times that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 43
44. In this case, 4th or neutral wire is taken from the neutral point. The area of X-
section of the neutral wire is generally one-half that of the line conductor. If the
loads are balanced, then current through the neutral wire is zero. Assuming
balanced loads and p.f. of the load as cos φ,
Let 𝑅10 is the resistance of each line conductor
R.M.S. voltage per phase =
𝑉𝑚
6
Power supplied=3(
𝑉𝑚
6
I10cos φ )
Comparing the power with 2-wire D.C
3
𝑉𝑚
6
𝐼10 cos φ= 𝑉
𝑚𝐼1
𝐼10 =
6𝐼1
3cos φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 44
45. Total copper losses= 3𝐼10
2
𝑅10 =3 (
6𝐼1
3cos φ
)2 𝑅10=
2𝐼1
2
𝑅10
𝑐𝑜𝑠2φ
Comparing copper losses with 2 wire d.c system
2𝐼1
2
𝑅10
𝑐𝑜𝑠2φ
= 2𝐼1
2
𝑅1
𝑅10
𝑅1
= 𝑐𝑜𝑠2φ
𝑎10
𝑎1
=
1
𝑐𝑜𝑠2φ
volume of copper wire3−Phase, 3−wire system
volume of copper wire Two−wire D.C system
=
𝑎10𝑙10
𝑎1𝑙1
=
1
𝑐𝑜𝑠2φ𝑎13.5𝑙
𝑎12𝑙
=
1.75
𝑐𝑜𝑠2φ
Hence, the volume of conductor material required for this system
is
1.75
𝑐𝑜𝑠2φtimes that required for 2-wire d.c. system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 45
46. System Same maximum
voltage to earth
Same maximum
voltage
between conductors
1. D.C. system
(i) Two-wire
(ii) Two-wire mid-point earthed
(iii) 3-wire
1
0.25
0.3125
1
1
1.25
2. Single phase system
(i) Two-wire
(ii) Two-wire mid-point earthed
(iii) 3-wire
2
𝑐𝑜𝑠2φ
0.5
𝑐𝑜𝑠2φ
1.625
𝑐𝑜𝑠2φ
2
𝑐𝑜𝑠2φ
0.5
𝑐𝑜𝑠2φ
2.5
𝑐𝑜𝑠2φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 46
47. System Same maximum voltage to
earth
Same maximum voltage
between conductors
3. Two-phase system
(i) 2–phase 4-wire
(ii)2-phase 3-wire
0.5
𝑐𝑜𝑠2φ
1.457
𝑐𝑜𝑠2φ
2
𝑐𝑜𝑠2φ
2.914
𝑐𝑜𝑠2φ
4. Three-phase system
(i) 3-phase 3-wire
(ii)3-phase 4-wire
,
0.5
𝑐𝑜𝑠2φ
0.583
𝑐𝑜𝑠2φ
1.5
𝑐𝑜𝑠2φ
1.75
𝑐𝑜𝑠2φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 47
48. What is the percentage saving in feeder copper if
the line voltage in a 2-wire d.c. system is raised
from 200 volts to 400 volts for the same power
transmitted over the same distance and having the
same power loss ?
6 October 2020 D.Rajesh Asst.Prof. EEE Department 48
49. (i) Conductors
(ii) Step-up and step-down transformers
(iii) Line insulators
(iv) Support
(v) Protective devices
(vi) Voltage regulating devices
6 October 2020 D.Rajesh Asst.Prof. EEE Department 49
50. The following two fundamental economic
principles which closely influence the electrical
design of a transmission line
(i) Economic choice of transmission voltage
(ii) Economic choice of conductor size
6 October 2020 D.Rajesh Asst.Prof. EEE Department 50
51. The effect of increased voltage level of
transmission on
1. Volume of conductor material
used for transmission
2. Line Drop
6 October 2020 D.Rajesh Asst.Prof. EEE Department 51
52. Let a 3-phase A.C. system is used for the transmission, The resistance per conductor is given by
R= ρ l/A
Power transmitted P= 3𝑉𝐼cos φ
I=
𝑃
3𝑉cos φ
Total copper losses 𝑃𝑐𝑢= 3𝐼2R =3(
𝑃
3𝑉cos φ
)2ρ l
𝐴
A=
𝑃2ρ l
𝑃𝑐𝑢𝑉2𝑐𝑜𝑠2φ
The volume of copper used is V=3(A*l)
Volume of copper=
3𝑃2ρ 𝑙2
𝑃𝑐𝑢𝑉2𝑐𝑜𝑠2φ
Volume of copper 𝛼
1
𝑉2𝑐𝑜𝑠2φ
6 October 2020 D.Rajesh Asst.Prof. EEE Department 52
Thus greater is the
transmission voltage level,
lesser is the volume of the
copper required.
53. Line Drop=IR=I ρ l/A
Current density(J)=
𝐼
𝐴
Then Line Drop=
𝐼ρ l
𝐼
𝐽
= Jρ l
%Line Drop=
Jρ l
𝑉
*100
Higher the transmission voltage level, then lesser the
%Line Drop
6 October 2020 D.Rajesh Asst.Prof. EEE Department 53
54. The most economical area of conductor is that
for which the total annual cost of transmission
line is minimum . This is known as Kelvin’s
Law
The total annual cost of transmission line can
be divided broadly into two parts viz.,
Annual charge on capital outlay
Annual cost of energy wasted in the conductor.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 54
55. This is on account of interest and depreciation on the capital cost of
complete installation of transmission line. In case of overhead system,
it will be the annual interest and depreciation on the capital cost of
conductors, supports and insulators and the cost of their erection.
Now, for an overhead line, insulator cost is constant, the conductor
cost is proportional to the area of X-section and the cost of supports
and their erection is partly constant annual charge.
Transmission line can be expressed as :
𝐴𝑛𝑛𝑢𝑎𝑙 𝑐ℎ𝑎𝑟𝑔𝑒 = 𝑃1 + 𝑃2𝑎
𝑃1 constant depending on the copper conductor
𝑃2 constant depending on the X-area of the conductor
a is the area of X-section of the conductor
6 October 2020 D.Rajesh Asst.Prof. EEE Department 55
56. This is on account of energy lost mainly in the conductor due to 𝐼2R losses.
Assuming a constant current in the conductor throughout the year,
The energy lost in the conductor is proportional to resistance.
where R = ρ l/ 𝑎
The energy lost in the conductor is inversely proportional to area of X-section.
energy lost α
1
𝑎
Thus, the annual cost of energy wasted in an overhead transmission line can
be expressed as :
Annual cost of energy wasted =
𝑃3
𝑎
where P3 is a constant.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 56
57. Total annual cost, C=𝑃1 + 𝑃2𝑎+
𝑃3
𝑎
only area of X-section a is variable. Therefore, the total annual cost of
transmission line will be minimum if differentiation of C w.r.t. a is zero i.e.
ⅆ𝐶
ⅆ𝑎
=0
ⅆ
ⅆ𝑎
(𝑃1 + 𝑃2𝑎+
𝑃3
𝑎
)=0
𝑃2𝑎 −
𝑃3
𝑎2=0
𝑃2𝑎 =
𝑃3
𝑎2
i.e. Variable part of annual charge = Annual cost of energy wasted
Therefore Kelvin’s Law can also be stated
The most economical area of conductor is that for which the variable part of
annual charge is equal to the cost of energy losses per year.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 57
58. The straight line shows the relation between the
annual charge (i.e., 𝑃1 + 𝑃2𝑎) and the area of X-
section a of the conductor
The rectangular hyperbola
gives the relation between
annual cost of energy wasted (
𝑃3
𝑎
)
and X-sectional area a.
Curve 3 shows the relation between total annual
cost of transmission line and area of X-section a.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 58
59. (i) It is not easy to estimate the energy loss in the line without actual load
curves, which are not available at the time of estimation.
(ii) The assumption that annual cost on account of interest and
depreciation on the capital outlay is in the form 𝑃1 + 𝑃2𝑎 is strictly
speaking not true. For instance, in cables neither the cost of cable dielectric
and sheath nor the cost of laying vary in this manner.
(iii) This law does not take into account several physical factors like safe
current density, mechanical strength, corona loss etc.
(iv) The conductor size determined by this law may not always be
practicable one because it may be too small for the safe carrying of
necessary current.
(v) Interest and depreciation on the capital outlay cannot be determined
accurately.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 59
60. A 2-conductor cable 1 km long is required to supply a constant current
of 200 A throughout the year. The cost of cable including installation is
Rs. (20 a + 20) per meter where ‘a’ is the area of X-section of the
conductor in 𝑐𝑚2
. The cost of energy is 5P per kWh and interest and
depreciation charges amount to 10%. Calculate the most economical
conductor size. Assume resistivity of conductor material to be 1·73 μ Ω
cm.
economical conductor size a =?
Energy lost per annum=2𝐼2
𝑅𝑡
Resistance of one conductor=ρ l/ 𝑎
=
1.73∗10−6∗105
𝑎
=
0.173
𝑎
Ω
Energy lost per annum= 2∗ 2002
∗
0.173
𝑎
∗ 8760
=
121238.4
𝑎
kWh
6 October 2020 D.Rajesh Asst.Prof. EEE Department 60
61. Annual cost of energy lost = Cost per kWh × Annual energy loss
=Rs 0.05*
121238.4
𝑎
kWh=Rs
6062
𝑎
The capital cost (variable) of the cable is given to be Rs 20 a per metre.
Therefore, for 1 km length of the cable, the capital cost (variable) is Rs. 20 a ×
1000 = Rs. 20,000 a.
Variable annual charge = Annual interest and depreciation on
capital cost (variable) of cable
= Rs 0·1 × 20,000 a
= Rs 2000 a
According to Kelvin’s law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy lost
2000 a =
6062
𝑎
a=
6062
2000
=1.74 𝑐𝑚2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 61
62. A 2-wire feeder carries a constant current of 250 A throughout the year.
The portion of capital cost which is proportional to area of X-section is
Rs 5 per kg of copper conductor. The interest and depreciation total
10% per annum and the cost of energy is 5P per kWh. Find the most
economical area of X-section of the conductor. Given that the density of
copper is 8·93gm/ 𝑐𝑚3
and its specific resistance is 1·73 × 10−8
Ω m.
Consider 1 metre length of the feeder. Let a be the most economical
area of X-section of each conductor in 𝑚2
Energy lost per annum=2𝐼2
𝑅𝑡
Resistance of one conductor=ρ l/ 𝑎
=
1.73∗10−8∗1
𝑎
=
1.73∗10−8
𝑎
Ω
Energy lost per annum= 2∗ 2502
∗
1.73∗10−8
𝑎
∗ 8760
=
18,94,350
𝑎
∗ 10−8
kWh
6 October 2020 D.Rajesh Asst.Prof. EEE Department 62
63. Annual cost of energy lost = Cost per kWh × Annual energy loss
=Rs 0.05*
18,94,350
𝑎
∗ 10−8
kWh=Rs
94,717.5
𝑎
∗ 10−8
Mass of 1 metre feeder = 2 (Volume × density)
= 2 × a × 1 × 8·93 × 103kg
= 17·86 × 103 a kg
Capital cost (variable) = Rs 5 × 17·86 × 103
a
= Rs 89·3 × 103
a
Variable annual charge = 10% of capital cost (variable)
= 0·1 × 89·3 × 103 a = Rs 8930 a
According to Kelvin’s law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy lost
8930 a =
94,717.5
𝑎
∗ 10−8
a=
94,717.5
8930
∗ 10−8
=3.25∗ 10−4
𝑚2
= 3.25 𝑐𝑚2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 63
64. Determine the most economical cross-section for a 3-phase
transmission line, 1 km long to supply at a constant voltage of
110 kV for the following daily load cycle :
6 hours 20 MW at p.f. 0·8 lagging
12 hours 5 MW at p.f. 0·8 lagging
6 hours 6 MW at p.f. 0·8 lagging
The line is used for 365 days yearly. The cost per km of line
including erection is Rs (9000 +6000 a) where ‘a’ is the area of X-
section of conductor in cm2. The annual rate of interest and
depreciation is 10% and the energy costs 6P per kWh. The
resistance per km of each conductor is0·176/a.
Power transmitted P= 3𝑉𝐼cos φ
Energy lost per annum=3R(𝐼2
𝑡)
6 October 2020 D.Rajesh Asst.Prof. EEE Department 64
65. The load currents at various loads are :
At 20 MW, 𝐼1=
𝑃
3𝑉cos φ
=
20∗106
3∗110∗103∗0.8
= 131.2𝐴
At 5 MW, 𝐼1=
𝑃
3𝑉cos φ
=
5∗106
3∗110∗103∗0.8
= 32.8𝐴
At 6 MW, 𝐼1=
𝑃
3𝑉cos φ
=
6∗106
3∗110∗103∗0.8
= 39.36𝐴
Energy loss per day in 3-phase line
=3*
0.176
𝑎
(131.22
∗ 6+ 32.82
∗ 12+ 36.362
∗ 6)
=
66.26
𝑎
kWh
Energy lost per annum =
66.26
𝑎
*365= =
24,184.9
𝑎
kWh
Annual cost of energy=Rs
6
100
∗
24,184.9
𝑎
= =
1451.09
𝑎
Variable annual charge = 10% of capital cost (variable) of line
= Rs 0·1 × 6000 a = Rs 600 a
According to Kelvin’s law, for most economical X-section of the conductor,
Variable annual charge = Annual cost of energy
600 a=
1451.09
𝑎
a=
1451.09
600
=1.56 𝑐𝑚2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 65
66. The conveyance of electric power from a power station to
consumers’ premises is known as electric supply system.
Electric supply system consist of three principle components:
1) Power station
2) Transmission lines
3) Distribution system
The electric supply system can be broadly classified into:
1) DC or AC system
2)Overhead or underground system
6 October 2020 D.Rajesh Asst.Prof. EEE Department 66
67. Different blocks of typical acpowersupply scheme are asper
following::
1)Generating Station:
Ingenerating station power is producedby three phase alternators
operating inparallel.
The usual generation voltage is 11kV.
Foreconomy in the transmission of electric power, the generation
voltage is stepped upto 132 kVor more at generating station with the
help of three phase transformer.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 67
68. 2)Primarytransmission:
Theelectric power at 132 kVis transmitted by 3-phase,3 wire overhead system to the out
3)Secondary transmission:
Atthe receiving station the voltage is reduced to33kV by step down transformer.
4)Primary distribution:
Atthe substation voltage is reduced 33kV to 11kV.The11kV line run along important
roadsides to city. This forms the primary distribution.
69. 5)Secondarydistribution:
Theelectric power form primary distribution line is delivered to distribution substation. The
substation is located nearthe consumers location and step down the voltage to 400V, 3-
phase ,4-wire for secondary distribution.
The voltage between any two phases is 400V and between any phase and neutral is 230V.
70. Basis for Comparison AC Transmission Line DC Transmission Line
Definition The ac transmission line transmit the
alternating current.
The dc transmission line is used for
transmitting the direct current.
Number of Conductors Three Two
Inductance & surges Have Don’t Have
Voltage drop High Low
Skin Effect Occurs Absent
Need of Insulation More Less
Interference Have Don’t Have
Corona Loss Occur Don’t occur
Dielectric Loss Have Don’t have
Synchronizing and Stability Problem No difficulties Difficulties
Cost Expensive Cheap
Length of conductors Small More
Repairing and Maintenance Easy and Inexpensive Difficult and Expensive
Transformer Requires Not Requires
6 October 2020 D.Rajesh Asst.Prof. EEE Department 70
73. Which distributes
electric power for
local use is known as
distribution system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 73
74. (i) Feeders. A feeder is a
conductor which connects the
sub-station to the area where
power is to be distributed.
(ii) Distributor. A distributor is
a conductor from which
tappings are taken for supply
to the consumers.
(iii) Service mains. A service
mains is generally a small cable
which connects the distributor
to the consumers’ terminals.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 74
80. (i) Radial System.
In this system, separate feeders radiate from a single substation and feed
the distributors at one end only.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 80
81. Limitations
(a) The end of the distributor nearest to the feeding point will be
heavily loaded.
(b) The consumers are dependent on a single feeder and single
distributor. Therefore, any fault on the feeder or distributor cuts off
supply to the consumers who are on the side of the fault away from
the substation.
(c) The consumers at the distant end of the distributor would be
subjected to serious voltage fluctuations when the load on the
distributor changes.
Due to these limitations, this system is used for short
distances only.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 81
82. (ii) Ring main system.
In this system, the primaries of distribution transformers form a loop. The
loop circuit starts from the substation bus-bars, makes a loop through the area to be served,
and returns to the substation.
✓ substation supplies to the
closed feeder LMNOPQRS.
✓ The distributors are tapped
from different points M, O and Q
of the feeder through distribution
transformers.
➢ There are less voltage fluctuations
at consumer’s terminals.
➢ The system is very reliable as each
distributor is fed via two feeders.
➢ In the event of fault
on any section of the feeder,
the continuity of supply is maintained.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 82
83. (iii) Interconnected system. When the feeder ring is energized by two or
more than two generating stations or substations, it is called inter-connected
system.
(a) It increases the service reliability.
(b) Any area fed from one generating station during peak load hours can be fed
from the other generating station. This reduces reserve power capacity and
increase efficiency of the system.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 83
84. (i) Proper voltage.
One important requirement of a distribution system is that voltage
variations at consumer’s terminals should be as low as possible.
The changes in voltage are generally caused due to the variation of
load on the system.
Low voltage causes loss of revenue, inefficient lighting and possible
burning out of motors.
High voltage causes lamps to burn out permanently and may cause
failure of other appliances.
Thus, if the declared voltage is 230 V, then the highest voltage of the
consumer should not exceed 244 V while the lowest voltage of the
consumer should not be less than 216 V.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 84
85. (ii) Availability of power on demand. Power must be
available to the consumers in any amount that they
may require from time to time.
(iii) Reliability. Modern industry is almost dependent
on electric power for its operation.
The reliability can be improved to a considerable extent
by
(a) interconnected system
(b) reliable automatic control system
(c) providing additional reserve facilities.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 85
86. (i) Distributor fed at one end
(ii) Distributor fed at both ends
(iii) Distributor fed at the centre
(iv) Ring distributor.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 86
87. (i) Distributor fed
at one end
6 October 2020 D.Rajesh Asst.Prof. EEE Department 87
(ii) Distributor
fed at both ends
88. (iii) Distributor
fed at the centre
6 October 2020 D.Rajesh Asst.Prof. EEE Department 88
(iv) Ring
distributor
90. 2-wire d.c. distributor AB fed at one end A and having concentrated loads 𝐼1,
𝐼2, 𝐼3 and 𝐼4 tapped off at points C, D, E and F respectively.
Let 𝑟1 , 𝑟2, 𝑟3 𝑎𝑛𝑑 𝑟4 be the resistances of both wires (go and return) of the sections AC,
CD, DE and EF of the distributor respectively.
Current fed from point A = 𝐼1 + 𝐼2 + 𝐼3 + 𝐼4 Current in section AC = 𝐼1 + 𝐼2 + 𝐼3 + 𝐼4
Current in section CD = 𝐼2 + 𝐼3 + 𝐼4 Current in section DE = 𝐼3 + 𝐼4
Current in section EF = 𝐼4
Voltage drop in section AC = 𝑟1 (𝐼1 + 𝐼2 + 𝐼3 + 𝐼4)
Voltage drop in section CD = 𝑟2 (𝐼2 + 𝐼3 + 𝐼4) Voltage drop in section DE = 𝑟3 (𝐼3 + 𝐼4)
Voltage drop in section EF = 𝑟4 𝐼4
∴ Total voltage drop in the distributor
=𝑟1 (𝐼1 + 𝐼2 + 𝐼3 + 𝐼4)+𝑟2 (𝐼2 + 𝐼3 + 𝐼4)+𝑟3 (𝐼3 + 𝐼4)+ 𝑟4 𝐼4
6 October 2020 D.Rajesh Asst.Prof. EEE Department 90
91. 2-wire d.c. distributor AB fed at one end A and
loaded uniformly with i amperes per metre length.
The load tapped is i amperes. Let 𝑙 metres be the
length of the distributor and r ohm be the
resistance per metre run.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 91
92. Consider a point C on the distributor at a distance x metres from the feeding point A
Then current at point C is
= i 𝑙− i x amperes = i (𝑙− x) amperes
Now, consider a small length dx near point C. Its resistance is r dx and the voltage drop over
length dx is
dv = i (𝑙 − x) r dx = i r (𝑙 − x) dx
Total voltage drop in the distributor upto point C is
v =0
𝑥
ir (l − x)dx =ir 𝑙𝑥 −
𝑥2
2
The voltage drop upto point B (i.e. over the whole distributor) can be obtained by putting x = 𝑙 in
the above expression.
∴ Voltage drop over the distributor AB
= ir 𝑙 ∗ 𝑙 −
𝑙2
2
=
1
2
𝑖𝑟𝑙2
=
1
2
𝑖𝑙 𝑟𝑙 =
1
2
𝐼𝑅
Thus, in a uniformly loaded distributor fed at one end, the total voltage drop is equal to that
produced by the whole of the load assumed to be concentrated at the middle point.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 92
93. The two ends of the distributor may be supplied
with (i) equal voltages (ii) unequal voltages.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 93
94. Consider a distributor AB fed at both ends with equal voltages V volts and having
concentrated loads 𝐼1, 𝐼2, 𝐼3, 𝐼4 and 𝐼5 at points C, D, E, F and G respectively
As we move away from one of the feeding points, say A, p.d. goes on decreasing till it
reaches the minimum value at some load point, say E, and then again starts rising and
becomes V volts as we reach the other feeding point B.
All the currents tapped off between points A and E (minimum p.d. point) will be
supplied from the feeding point A while those tapped off between B and E will be
supplied from the feeding point B.
The current tapped off at point E itself will be partly supplied from A and partly from
B. If these currents are x and y respectively, then,
x+y= 𝐼3
Therefore, we arrive at a very important conclusion that at the point of minimum
potential, current comes from both ends of the distributor.
Voltage drop from feeding point A to the point of minimum potential difference is
equal to the voltage drop from feeding point B to the point of minimum potential
difference
6 October 2020 D.Rajesh Asst.Prof. EEE Department 94
95. Distributor AB fed with unequal voltages ; end A being fed at 𝑉1volts
and end B at 𝑉2 volts.
In order to determine the point of minimum potential, assume of 𝐼𝐴
amperes is supplied from feeding point A
Let r be the resistance of each conductor per unit length(l=1) for both go
& return
Resistance of portions AC,CD, DE,EF,FB are 𝑟1 , 𝑟2, 𝑟3 , 𝑟4, 𝑎𝑛𝑑 𝑟5
respectively
Voltage drop between A and B = Voltage drop over AB
𝑉1 − 𝑉2 = 𝐼𝐴𝑟1+(𝐼𝐴- 𝐼1) 𝑟2 + (𝐼𝐴- 𝐼1- 𝐼2) 𝑟3 + (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3) 𝑟4+ (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3 − 𝐼4) 𝑟5
The load point at which currents are coming from both sides of the
distributor will be the point of minimum potential
6 October 2020 D.Rajesh Asst.Prof. EEE Department 95
96. A 2-wire d.c. street mains AB, 600 m long is fed from both ends at 220 V. Loads of 20
A, 40 A, 50 A and 30 A are tapped at distances of 100m, 250m, 400m and 500 m from
the end A respectively. If the area of X-section of distributor conductor is 1𝑐𝑚2
, find
the minimum consumer voltage. Take ρ = 1·7 × 10−6 Ω cm.
Voltage drop between A and B = Voltage drop over AB
R= ρ l/A
Resistance of section AC of distributor=2×
1·7 × 10−6∗100∗102
1
= 3·4 × 10−2 Ω
Resistance of section CD of distributor =0.051 Ω
Resistance of section DE of distributor =0.051 Ω
Resistance of section EF of distributor =0.034 Ω
Resistance of section FB of distributor =0.034 Ω
Voltage drop between A and B = Voltage drop over AB
𝑉𝐴 − 𝑉𝐵 = 𝐼𝐴𝑟1+(𝐼𝐴- 𝐼1) 𝑟2 + (𝐼𝐴- 𝐼1- 𝐼2) 𝑟3 + (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3) 𝑟4+ (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3 − 𝐼4) 𝑟5
220-200=0.034 𝐼𝐴+(𝐼𝐴-20)0.051+ (𝐼𝐴-60)0.051+(𝐼𝐴-110)0.034+(𝐼𝐴-140)0.034
𝐼𝐴=61.7A
6 October 2020 D.Rajesh Asst.Prof. EEE Department 96
97. Actual distribution of currents in the various sections of the
distributor is
Current in section EF, 𝐼𝐸𝐹 = 𝐼𝐴−110 =61·7−110 =−48·3A from E to F
= 48·3 A from F to E
Current in section DE, 𝐼𝐷𝐸 = 𝐼𝐴 −60=61.7-60=1.7A from D to E
6 October 2020 D.Rajesh Asst.Prof. EEE Department 97
It is clear that currents are coming to load point E from both sides i.e.
from point D and point F. Hence, E is the point of minimum potential.
∴ Minimum consumer voltage,
𝑉𝐸 = 𝑉𝐴-(𝐼𝐴𝐶 𝑟1+ 𝐼𝐶𝐷 𝑟2+ 𝐼𝐷𝐸 𝑟3)
=220-(61·7 × 0·034 + 41·7 × 0·051 + 1·7 × 0·051]
=215.69V
98. A two-wire d.c. distributor AB, 600 metres long is loaded as under :
Distance from A (metres) : 150 300 350 450
Loads in Amperes : 100 200 250 300
The feeding point A is maintained at 440 V and that of B at 430 V. If
each conductor has a resistance of 0·01 Ω per 100 metres, calculate :
(i) the currents supplied from A to B,
(ii) the power dissipated in the distributor.
Let 𝐼𝐴amperes be the current supplied from the feeding point A. Then currents in the
various sections of the distributor are
Resistance of 100 m length of distributor (both wires)
= 2 × 0·01 = 0·02 Ω
Resistance of section AC, 𝑟1 = 0·02 × 150/100 = 0·03 Ω
Resistance of section CD, 𝑟2 = 0·02 × 150/100 = 0·03 Ω
Resistance of section DE, 𝑟3= 0·02 × 50/100 = 0·01 Ω
Resistance of section EF, 𝑟4= 0·02 × 100/100 = 0·02 Ω
Resistance of section FB, 𝑟5= 0·02 × 150/100 = 0·03 Ω
6 October 2020 D.Rajesh Asst.Prof. EEE Department 98
99. Voltage drop between A and B = Voltage drop over AB
𝑉𝐴 − 𝑉𝐵 = 𝐼𝐴𝑟1+(𝐼𝐴- 𝐼1) 𝑟2 + (𝐼𝐴- 𝐼1- 𝐼2) 𝑟3 + (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3) 𝑟4+ (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3 − 𝐼4) 𝑟5
440-430=0.03 𝐼𝐴+(𝐼𝐴-100)0.03+ (𝐼𝐴-300)0.01+(𝐼𝐴-550)0.02+(𝐼𝐴-850)0.03
𝐼𝐴=437.5A
The actual distribution of currents in the various sections of the distributor are
Current supplied from end A, 𝐼𝐴 = 𝐼𝐴𝐶 = 437·5 A
Current supplied from end B, 𝐼𝐵 = 𝐼𝐹𝐵 = 𝐼𝐴 -850= - 412·5 A
𝐼𝐶𝐷 = 337.5𝐴 𝐼𝐷𝐸 = 137.5𝐴 𝐼𝐸𝐹 = −112.5𝐴
Therefore E is the point of minimum potential.
Power loss in the distributor
=𝐼𝐴𝐶
2
𝑟1+ 𝐼𝐶𝐷
2
𝑟2 + 𝐼𝐷𝐸
2
𝑟3+ 𝐼𝐸𝐹
2
𝑟4+ 𝐼𝐹𝐵
2
𝑟5
=(437.5)2
∗ 0.03 + 337.5 2
∗ 0.03 + 137.5 2
∗ 0.01 + 112.5 2
∗ 0.02 + (412.5)2
∗ 0.03
=14.705kW
6 October 2020 D.Rajesh Asst.Prof. EEE Department 99
100. (i) Distributor fed at both ends with equal voltages.
Consider a distributor AB of length 𝑙 metres, having resistance r
ohms per metre run and with uniform loading of 𝑖 amperes per
metre run.
Let the distributor be fed at the feeding points A and B at equal
voltages, say V volts.
The total current supplied to the distributor is 𝑖𝑙.
As the two end voltages are equal, therefore, current supplied from
each feeding point is
𝑖𝑙
2
i.e.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 100
101. Consider a point C at a distance x metres from the feeding point A. Then
current at point C is
=
𝑖𝑙
2
- 𝑖𝑥= 𝑖(
𝑙
2
-𝑥)
Now, consider a small length dx near point C. Its resistance is r dx and the
voltage drop over length dx is
dv = i (
𝑙
2
− x) r dx = i r (
𝑙
2
− x) dx
Total voltage drop in the distributor upto point C is
v =
0
𝑥
ir (
𝑙
2
− x)dx =ir
𝑙𝑥
2
−
𝑥2
2
=
𝑖𝑟
2
(𝑙𝑥- 𝑥2)
Obviously, the point of minimum potential will be the mid-point. Therefore,
maximum voltage drop will occur at mid-point i.e. where x =
𝑙
2
Max. voltage drop=
𝑖𝑟
2
(𝑙𝑥- 𝑥2)=
𝑖𝑟
2
(𝑙
𝑙
2
- (
𝑙
2
)2)=
1
8
𝑖𝑟𝑙2=
1
8
𝑖𝑙 𝑟𝑙 =
1
8
IR
Minimum voltage=V-
1
8
IR volts
6 October 2020 D.Rajesh Asst.Prof. EEE Department 101
102. (ii) Distributor fed at both ends with unequal voltages.
Consider a distributor AB of length l metres having resistance r
ohms per metre run and with a uniform loading of i amperes
permetre run. Let the distributor be fed from feeding points A and B
at voltages 𝑉𝐴 and 𝑉𝐵 respectively.
Suppose that the point of minimum potential C is situated at a
distance x metres from the feeding point A. Then current supplied
by the feeding point A will be i x.
∴ Voltage drop in section AC=
1
2
𝑖𝑟𝑥2 volts
As the distance of C from feeding point B is (l − x), therefore, current
fed from B is i (l − x).
∴ Voltage drop in section BC =
1
2
𝑖𝑟(𝑙 − 𝑥)2
volts
6 October 2020 D.Rajesh Asst.Prof. EEE Department 102
103. Voltage at point C, 𝑉𝐶 = 𝑉𝐴 − Drop over AC
= 𝑉𝐴 -
1
2
𝑖𝑟𝑥2
Voltage at point C, 𝑉𝐶 = 𝑉𝐵 − Drop over BC
= 𝑉𝐵 -
1
2
𝑖𝑟(𝑙 − 𝑥)2
From above equations we get,
𝑉𝐴 -
1
2
𝑖𝑟𝑥2 = 𝑉𝐵 -
1
2
𝑖𝑟(𝑙 − 𝑥)2
𝑉𝐴- 𝑉𝐵 =
1
2
𝑖𝑟𝑥2
-
1
2
𝑖𝑟(𝑙 − 𝑥)2
=
1
2
𝑖𝑟𝑥2
-
1
2
𝑖𝑟𝑙2
-
1
2
𝑖𝑟𝑥2
+
1
2
𝑖𝑟2𝑙𝑥
= 𝑖𝑟𝑙 {𝑥-
1
2
𝑙 }
𝑥=
𝑉𝐴− 𝑉𝐵
𝑖𝑟𝑙
+
𝑙
2
The point on the distributor where minimum potential occurs can be calculated
6 October 2020 D.Rajesh Asst.Prof. EEE Department 103
104. Expression for the power loss in a uniformly loaded distributor fed at both ends
current supplied from each feeding point is
𝑖𝑙
2
Consider a small length dx of the distributor at point P which is at a distance x from
the feeding end A.
Resistance of length dx = r dx
Current in length dx =
𝑖𝑙
2
- 𝑖𝑥= 𝑖(
𝑙
2
-𝑥)
Power loss in length dx
= (current in dx)2 × Resistance of dx
= 𝑖(
𝑙
2
−𝑥)
2
×rdx
Total power loss in the distributor is=
0
𝑙
𝑖(
𝑙
2
−𝑥)
2
×rdx
=𝑖2
𝑟
0
𝑙 𝑙2
4
− 𝑙𝑥 + 𝑥2
𝑑𝑥
= 𝑖2𝑟
𝑙2𝑥
4
−
𝑙𝑥2
2
+
𝑥3
3
𝑙
0
P=
𝑖2𝑟𝑙3
12
6 October 2020 D.Rajesh Asst.Prof. EEE Department 104
105. A 2-wire d.c. distributor AB 500 metres long is fed from both ends and is loaded uniformly
at the rate of 1·0 A/metre. At feeding point A, the voltage is maintained at 255 V and at B
at 250 V. If the resistance of each conductor is 0·1 Ω per kilometre, determine :
(i) the minimum voltage and the point where it occurs
(ii) the currents supplied from feeding points A and B
Let the minimum potential occur at a point C distant x metres from the feeding point A.
𝑥=
𝑉𝐴− 𝑉𝐵
𝑖𝑟𝑙
+
𝑙
2
Resistance of distributor/m, r = 2 × 0·1/1000 = 0·0002 Ω
𝑥=
255− 250
1∗0.0002∗500
+
500
2
=300m
i.e. minimum potential occurs at 300 m from point A.
Minimum voltage, 𝑉𝐶 = 𝑉𝐴 -
1
2
𝑖𝑟𝑥2 = 𝑉𝐵 -
1
2
𝑖𝑟(𝑙 − 𝑥)2
255-
1∗0.0002∗ (300)2
2
=246V
Current supplied from A = i x = 1 × 300 = 300 A
Current supplied from B = i (𝑙 − x) = 1 (500 − 300)
= 200 A
6 October 2020 D.Rajesh Asst.Prof. EEE Department 105
106. A 800 metres 2-wire d.c. distributor AB fed from both ends is uniformly
loaded at the rate of 1·25 A/metre run. Calculate the voltage at the
feeding points A and B if the minimum potential of 220 V occurs at
point C at a distance of 450 metres from the end A. Resistance of each
conductor is 0·05 Ω/km.
Minimum voltage, 𝑉𝐶 = 𝑉𝐴 -
1
2
𝑖𝑟𝑥2
= 𝑉𝐵 -
1
2
𝑖𝑟(𝑙 − 𝑥)2
For 𝑉𝐴
𝑉𝐶 = 𝑉𝐴 -
1
2
𝑖𝑟𝑥2
𝑉𝐴=220+
1.25∗0.0001∗ (450)2
2
=232.65V
For 𝑉𝐵
𝑉𝐶 = 𝑉𝐵 -
1
2
𝑖𝑟(𝑙 − 𝑥)2
𝑉𝐵 =220+
1.25∗0.0001∗ (800−450)2
2
=227.65V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 106
107. (i) A uniformly loaded distributor is fed at the centre. Show that maximum
voltage drop = I R/8 where I is the total current fed to the distributor and R
is the total resistance of the distributor.
(ii) A 2-wire d.c. distributor 1000 metres long is fed at the centre and is
loaded uniformly at the rate of 1·25 A/metre. If the resistance of each
conductor is 0·05 Ω/km, find the maximum voltage drop in the distributor.
∴ Max. voltage drop = Voltage drop in half distributor
=
1
2
(
𝑖𝑙
2
)(
𝑟𝑙
2
) =
1
8
𝑖𝑙 𝑟𝑙 =
1
8
IR
where i l = I, the total current fed to the distributor
r l = R, the total resistance of the distributor
(ii) Total current fed to the distributor is
I = i l = 1·25 × 1000 = 1250 A
Total resistance of the distributor is
R = r l = 2 × 0·05 × 1 = 0·1 Ω
Max. voltage drop =
1
8
IR
=
1
8
*1250*0.1
=15.62V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 107
108. A two-wire d.c. distributor cable 1000 metres long is loaded with 0·5
A/metre. Resistance of each conductor is 0·05 Ω/km. Calculate the
maximum voltage drop if the distributor is fed from both ends with
equal voltages of 220 V. What is the minimum voltage and where it
occurs ?
Current loading, i = 0·5 A/m
Resistance of distributor/m, r = 2 × 0·05/1000 = 0·1 × 10−3
Ω
Length of distributor, l = 1000 m
Total current supplied by distributor, I = i l = 0·5 × 1000 = 500 A
Total resistance of the distributor, R = r l = 0·1 × 10−3 × 1000 = 0·1 Ω
∴ Max. voltage drop =
1
8
IR
= 6·25 V
Minimum voltage will occur at the mid-point of the distributor and
its value is
= 220 − 6·25 = 213·75 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 108
109. The total drop over any section of the distributor
is equal to the sum of drops due to concentrated
and uniform loading in that section.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 109
110. Two conductors of a d.c. distributor cable AB 1000 m long have a total
resistance of 0·1 Ω. The ends A and B are fed at 240 V. The cable is
uniformly loaded at 0·5 A per metre length and has concentrated loads
of 120 A, 60 A, 100 A and 40 A at points distant 200 m, 400 m, 700 m and
900 m respectively from the end A. Calculate (i) the point of minimum
potential (ii) currents supplied from ends A and B (iii) the value of
minimum potential.
Distributor resistance per metre length, r = 0·1/1000 = 10−4
Ω
(i) Point of minimum potential. The point of minimum potential is not
affected by the uniform loading of the distributor. Therefore, let us
consider the concentrated loads.
Suppose the current supplied by end A is 𝐼𝐴. Then currents in the
various sections will be
6 October 2020 D.Rajesh Asst.Prof. EEE Department 110
111. Voltage drop between A and B = Voltage drop over AB
𝑉𝐴 − 𝑉𝐵 = 𝐼𝐴𝑟1+(𝐼𝐴- 𝐼1) 𝑟2 + (𝐼𝐴- 𝐼1- 𝐼2) 𝑟3 + (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3)
𝑟4+ (𝐼𝐴- 𝐼1- 𝐼2- 𝐼3 − 𝐼4) 𝑟5
0= 10−4(
)
200 𝐼𝐴+(𝐼𝐴−120)200+
(𝐼𝐴−180)300+(𝐼𝐴−280)200+(𝐼𝐴−320)100
𝐼𝐴=166A
The actual distribution of currents in the various sections of the
distributor due to concentrated loading.
It is clear from this figure that D is the point of minimum
potential.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 111
112. (ii) The feeding point A will supply 166 A due to concentrated loading
plus 0·5 × 400 = 200 A due to uniform loading.
∴ Current supplied byA, 𝐼𝐴 = 166 + 200 = 366 A
The feeding point B will supply a current of 154 A due to concentrated
loading plus 0·5 × 600 = 300 A due to uniform loading.
∴ Current supplied by B, 𝐼𝐵 = 154 + 300 = 454 A
(iii) ∴ Minimum potential, 𝑉𝐷 = 𝑉𝐴 − Drop in AD due to conc. loading –
Drop in AD due to uniform loading 𝑉𝐷
Now, Drop in AD due to conc. loading = 𝐼𝐴𝐶 𝑅𝐴𝐶 + 𝐼𝐶𝐷 𝑅𝐶𝐷
= 166 × 10−4
× 200 + 46 × 10−4
× 200
= 3·32 + 0·92 = 4·24 V
Drop in AD due to uniform loading =
1
2
𝑖𝑟𝑙2
=
1
2
0.5 ∗ 10−4
∗ (400)2
=4V
∴ 𝑉𝐷 = 240 − 4·24 − 4 = 231·76 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 112
113. A d.c. 2-wire distributor AB is 500m long and is fed at
both ends at 240 V. The distributor is loaded as shown
in Fig. The resistance of the distributor (go and return)
is 0·001Ω per metre. Calculate (i) the point of minimum
voltage and (ii) the value of this voltage.
Let D be the point of minimum potential and let x be the
current flowing in section CD. Then current supplied by
end B will be (60 − x).
6 October 2020 D.Rajesh Asst.Prof. EEE Department 113
114. (i) If r is the resistance of the distributor (go and return) per metre length,
then,
Voltage drop in length AD = 𝐼𝐴𝐶 𝑅𝐴𝐶 + 𝐼𝐶𝐷 𝑅𝐶𝐷
=(100+x)*100r+x*150r
Voltage drop in length BD=
1
2
𝑖𝑟𝑙2
+(60-x)*250r
=
1
2
1 ∗ 𝑟 ∗ (200)2 +(60-x)*250r
Since the feeding points A and B are at the same potential
(100+x)*100r+x*150r=
1
2
1 ∗ 𝑟 ∗ (200)2 +(60-x)*250r
X=50A
The actual directions of currents in the various sections of the distributor are
currents supplied by A and B meet at D. Hence point D is the point of minimum
6 October 2020 D.Rajesh Asst.Prof. EEE Department 114
115. (ii) Total current = 160 + 1 × 200 = 360 A
Current supplied by A, 𝐼𝐴 = 100 + x = 100 + 50 = 150 A
Current supplied by B, 𝐼𝐵 = 360 − 150 = 210 A
Minimum potential, 𝑉𝐷 = 𝑉𝐴 − (𝐼𝐴𝐶 𝑅𝐴𝐶 + 𝐼𝐶𝐷 𝑅𝐶𝐷 )
= 240 − 150 × (100 × 0·001) − 50 × (150 × 0·001)
= 240 − 15 − 7·5 = 217·5 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 115
116. A distributor arranged to form a closed loop and
fed at one or more points is called a ring
distributor.
For the purpose of calculating voltage distribution,
the distributor can be considered as consisting of a
series of open distributors fed at both ends.
The principal advantage of ring distributor is that
by proper choice in the number of feeding points,
great economy in copper can be affected.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 116
117. Sometimes a ring distributor has to
serve a large area. In such a case,
voltage drops in the various
sections of the distributor may
become excessive.
In order to reduce voltage drops in
various sections, distant points of
the distributor are joined through a
conductor called interconnector.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 117
118. The ring distributor ABCDEA. The points B and D of the ring distributor are joined
through an interconnector BD.
Network can be obtained by applying Thevenin’s theorem.
(i) Consider the interconnector BD to be disconnected and find the potential difference
between B and D. This gives Thevenin’s equivalent circuit voltage 𝐸0.
(ii) Next, calculate the resistance viewed from points B and D of the network composed
of distribution lines only. This gives Thevenin’s equivalent circuit series resistance 𝑅0.
(iii) If 𝑅𝐵𝐷 is the resistance of the interconnector BD, then Thevenin’s equivalent circuit
will be
∴ Current in interconnector BD =
𝐸0
𝑅0+𝑅𝐵𝐷
Therefore, current distribution in each section and the voltage of load points can be
calculated.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 118
119. A 2-wire d.c. distributor ABCDEA in the form of a ring main is fed at
point A at 220 V and is loaded as under :
10A at B ; 20A at C ; 30A at D and 10 A at E.
The resistances of various sections (go and return) are : AB = 0·1 Ω ; BC
= 0·05 Ω ; CD = 0·01 Ω ; DE = 0·025 Ω and EA = 0·075 Ω. Determine :
(i) the point of minimum potential
(ii) current in each section of distributor
Let us suppose that current I flows in section AB of the distributor. Then
currents in the various sections of the distributor are
According to Kirchhoff’s voltage law, the voltage drop in the closed
loop ABCDEA is zero i.e.
𝐼𝐴𝐵𝑅𝐴𝐵+𝐼𝐵𝐶𝑅𝐵𝐶+ 𝐼𝐶𝐷𝑅𝐶𝐷+ 𝐼𝐷𝐸𝑅𝐷𝐸 + 𝐼𝐸𝐴𝑅𝐸𝐴 =0
0.1𝐼+(𝐼-10)0.05+ (𝐼-30)0.01+(𝐼-60)0.025+(𝐼-70)0.075=0
0.26 𝐼 = 7.55
𝐼 = 29.04A
6 October 2020 D.Rajesh Asst.Prof. EEE Department 119
120. (ii) Current in section AB = I = 29·04 A from A to B
Current in section BC = I − 10 = 29·04 − 10 = 19·04 A from B to C
Current in section CD = I − 30 = 29·04 − 30 = − 0·96 A = 0·96 A from D to C
Current in section DE = I − 60 = 29·04 − 60 = − 30·96 A = 30·96 A from E to D
Current in section EA = I − 70 = 29·04 − 70 = − 40·96 A = 40·96 A from A to E
6 October 2020 D.Rajesh Asst.Prof. EEE Department 120
∴ C is the point of minimum potential.
121. A d.c. ring main ABCDA is fed from point A from a 250 V supply and the resistances
(including both lead and return) of various sections are as follows : AB = 0·02 Ω ; BC =
0·018 Ω ; CD = 0·025 Ω and DA = 0·02 Ω. The main supplies loads of 150 A at B ; 300 A
at C and 250 A at D. Determine the voltage at each load point. If the points A and C are
linked through an interconnector of resistance 0·02 Ω, determine the new voltage at
each load point.
Without Interconnector.
Let us suppose that a current I flows in section AB of the distributor. Then currents in
various sections of the distributor will be
According to Kirchhoff’s voltage law, the voltage drop in the closed loop ABCDA is
zero i.e.
𝐼𝐴𝐵𝑅𝐴𝐵+𝐼𝐵𝐶𝑅𝐵𝐶+ 𝐼𝐶𝐷𝑅𝐶𝐷+ 𝐼𝐷𝐴𝑅𝐷𝐴 =0
0.02𝐼+(𝐼-150)0.018+ (𝐼-450)0.025+(𝐼-700)0.02=0
0·083 I = 27·95
∴ I = 27·95/0·083 = 336·75 A
6 October 2020 D.Rajesh Asst.Prof. EEE Department 121
122. The actual distribution of currents are ..
Current in section AB = I = 336.75 A from A to B
Current in section BC = I − 150 = 336.75 − 150 = 186.75 A from B to C
Current in section CD = I − 450 = 336.75 − 450 = − 113.25 A = 113.25 A from D to C
Current in section DA = I − 700 = 336.75 − 700 = − 363.25A = 363.25 A from A to D
Voltage drop in AB = 336·75 × 0·02 = 6·735 V
Voltage drop in BC = 186·75 × 0·018 = 3·361 V
Voltage drop in CD = 113·25 × 0·025 = 2·831 V
Voltage drop in DA = 363·25 × 0·02 = 7·265 V
∴ Voltage at point B = 250 − 6·735 = 243·265 V
Voltage at point C = 243·265 − 3·361 = 239·904 V
Voltage at point D = 239·904 + 2·831 = 242·735 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 122
123. With Interconnector.
The ring distributor with interconnector AC. The current in the interconnector can be
found by applying Thevenin’s theorem.
𝐸0 = Voltage between points A and C
= 250 − 239·904 = 10·096 V
𝑅0 = Resistance viewed from points A and C
=
0.02+0.018 0.02+0.025
0.02+0.018 + 0.02+0.025
= 0.02Ω
𝑅𝐴𝐶 = Resistance of interconnector = 0·02 Ω
From Thevenin’s equivalent circuit Current in interconnector AC is
𝐸0
𝑅0 + 𝑅𝐴𝐶
=
10.096
0.02 + 0.02
= 252.4𝐴 𝑓𝑟𝑜𝑚 𝐴 𝑡𝑜 𝐶
Let us suppose that current in section AB is 𝐼1 . Then current in section BC will be 𝐼1 − 150.
As the voltage drop round the closed mesh ABCA is zero,
0.02𝐼1+(𝐼1-150)0.018-0.02*252.4=0
0.038 𝐼1=7.748
𝐼1=203.15A
6 October 2020 D.Rajesh Asst.Prof. EEE Department 123
124. The actual distribution of currents are ..
Current in section AB = 𝐼1 = 203.15A from A to B
Current in section BC = 𝐼1 − 150 = 203.15 − 150 = 53.15 A from B to C
Current in section CD = 𝐼1 − 450+252.4 = 203.15− 450 +252.4= 5.55A C to D
Current in section DA = 𝐼1 − 700 = 203.15+252.5 − 700 = − 244.45A = 244.45A
from A to D
Drop in AB = 203·15 × 0·02 = 4·063 V
Drop in BC = 53·15 × 0·018= 0·960 V
Drop in AD = 244·45 × 0·02 = 4·9 V
∴ Potential of B = 250 − 4·063= 245·93 V
Potential of C = 245·93 − 0·96 = 244·97 V
Potential of D = 250 − 4·9 = 245·1 V
It may be seen that with the use of interconnector, the voltage drops in the various
sections of the distributor are reduced.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 124
125. A.C. distribution calculations differ from those of d.c. distribution in the
following respects :
(i) In case of d.c. system, the voltage drop is due to resistance alone.
However, in a.c. system, the voltage drops are due to the combined effects of
resistance, inductance and capacitance.
(ii) In a d.c. system, additions and subtractions of currents or voltages are
done arithmetically but in case of a.c. system, these operations are done
vectorially.
(iii) In an a.c. system, power factor (p.f.) has to be taken into account. Loads
tapped off form the distributor are generally at different power factors. There
are two ways of referring power factor viz
(a) It may be referred to supply or receiving end voltage which is
regarded as the reference vector.
(b) It may be referred to the voltage at the load point itself.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 125
126. The power factors of load currents may be
given
(i) w.r.t. receiving or sending end voltage
or
(ii) w.r.t. to load voltage itself.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 126
127. (i) Power factors referred to receiving end voltage.
Consider an a.c. distributor AB with concentrated loads of 𝐼1and 𝐼2 tapped off at
points C and B. Taking the receiving end voltage 𝑉𝐵 as the reference vector, let
lagging power factors at C and B be cos φ1 and cos φ2 w.r.t. 𝑉𝐵 . Let 𝑅1, 𝑋1 and
𝑅2, 𝑋2 be the resistance and reactance of sections AC and CB of the distributor.
Impedance of section AC, 𝑍𝐴𝐶= 𝑅1 + j 𝑋1
Impedance of section CB,𝑍𝐶𝐵 = 𝑅2 + j 𝑋2
Load current at point C, 𝐼1 = 𝐼1 (cos φ1 − j sin φ1)
Load current at point B, 𝐼2 = 𝐼2 (cos φ2 − j sin φ2)
Current in section CB, 𝐼𝐶𝐵= 𝐼2 = 𝐼2 (cos φ2 − j sin φ2)
Current in section AC, 𝐼𝐴𝐶 = 𝐼1+ 𝐼2
=𝐼1 (cos φ1 − j sin φ1)+𝐼2 (cos φ2 − j sin φ2)
6 October 2020 D.Rajesh Asst.Prof. EEE Department 127
128. φ1
Voltage drop in section CB,
𝑉𝐶𝐵= 𝐼𝐶𝐵 𝑍𝐶𝐵= 𝐼2 (cos φ2 − j sin φ2) (𝑅2 + j 𝑋2 )
Voltage drop in section AC,
𝑉𝐴𝐶= 𝐼𝐴𝐶 𝑍𝐴𝐶=(𝐼1+ 𝐼2) 𝑍𝐴𝐶
=𝐼1 (cos φ1 − j sin φ1)+𝐼2 (cos φ2 − j sin φ2)(𝑅1 + j 𝑋1 )
Sending end voltage, 𝑉𝐴= 𝑉𝐵 + 𝑉𝐶𝐵 + 𝑉𝐴𝐶
Sending end current, 𝐼𝐴= 𝐼1+ 𝐼2
6 October 2020 D.Rajesh Asst.Prof. EEE Department 128
𝑉𝑩
𝐼𝟐
𝐼𝟏
𝐼𝑨𝑪
φ2
θ
129. φ1
(ii) Power factors referred to respective load voltages.
Suppose the power factors of loads are referred to their respective load voltages. Then φ1 is the phase angle
between V𝐶 and I1 and φ2 is the phase angle between V𝐵 and I2. The vector diagram under these conditions is
Voltage drop in section CB,
𝑉𝐶𝐵= 𝐼2 𝑍𝐶𝐵= 𝐼2 (cos φ2 − j sin φ2) (𝑅2 + j 𝑋2 )
Voltage at point C = 𝑉𝐵 + Drop in section CB = V𝐶 ∠ α (say)
Now 𝐼1 = 𝐼1 ∠ − φ1 w.r.t. voltage V𝐶
∴ . 𝐼1 = 𝐼1 ∠ − (φ1 − α) w.r.t. voltage V𝐵
i.e. 𝐼1 = 𝐼1 [cos (φ1 − α) − j sin (φ1 − α)]
Now 𝐼𝐴𝐶 = 𝐼1+ 𝐼2
=𝐼1 [cos (φ1 − α) − j sin (φ1 − α)]+ 𝐼2 (cos φ2 − j sin φ2)
Voltage drop in section AC,
𝑉𝐴𝐶= 𝐼𝐴𝐶 𝑍𝐴𝐶
∴ Voltage at point A = V𝐵 + Drop in CB + Drop in AC
6 October 2020 D.Rajesh Asst.Prof. EEE Department 129
𝑉𝑩
𝐼𝟐
𝐼𝟏
𝐼𝑨𝑪
φ2
α
130. A single phase a.c. distributor AB 300 metres long is fed from end A and is loaded as under :
(i) 100 A at 0·707 p.f. lagging 200 m from point A (ii) 200 A at 0·8 p.f. lagging 300 m from point A
The load resistance and reactance of the distributor is 0·2 Ω and 0·1 Ω per kilometre. Calculate the
total voltage drop in the distributor. The load power factors refer to the voltage at the far end.
Impedance of distributor/km = (0·2 + j 0·1) Ω
Impedance of section AC, 𝑍𝐴𝐶 = (0·2 + j 0·1) × 200/1000 = (0·04 + j 0·02) Ω
Impedance of section CB, 𝑍𝐶𝐵 = (0·2 + j 0·1) × 100/1000 = (0·02 + j 0·01) Ω
Taking voltage at the far end B as the reference vector, we have, Load current at point B,
𝐼2 = 𝐼2 (cos φ2 − j sin φ2) = 200 (0·8 − j 0·6) = (160 − j 120) A
Load current at point C, 𝐼1 = 𝐼1 (cos φ1 − j sin φ1) = 100 (0·707 − j 0·707) = (70·7− j 70·7) A
Current in section CB,𝐼𝐶𝐵= 𝐼2 = (160 − j 120) A
Current in section AC,𝐼𝐴𝐶= 𝐼1+ 𝐼2
= (70·7 − j 70·7) + (160 − j 120)= (230·7 − j 190·7) A
Voltage drop in section CB, 𝑉𝐶𝐵= 𝐼𝐶𝐵 𝑍𝐶𝐵 = (160 − j 120) (0·02 + j 0·01) = (4·4 − j 0·8) volts
Voltage drop in section AC, 𝑉𝐴𝐶= 𝐼𝐴𝐶 𝑍𝐴𝐶 = (230·7 − j 190·7) (0·04 + j 0·02) = (13·04 − j 3·01) volts
Voltage drop in the distributor = 𝑉𝐴𝐶 + 𝑉𝐶𝐵 = (13·04 − j 3·01) + (4·4 − j 0·8) = (17·44 − j 3·81) volts
Magnitude of drop = 17.44 2 + 3.81 2 = 17·85 V
6 October 2020 D.Rajesh Asst.Prof. EEE Department 130
131. A single phase ring distributor ABC is fed at A. The loads at B
and C are 20 A at 0.8 p.f. lagging and 15 A at 0.6 p.f. lagging
respectively ; both expressed with reference to the voltage at
A. The total impedance of the three sections AB, BC and CA
are (1 + j 1), (1+ j2) and (1 + j3) ohms respectively. Find the
total current fed at A and the current in each section. Use
Thevenin’s theorem to obtain the results.
6 October 2020 D.Rajesh Asst.Prof. EEE Department 131