SlideShare a Scribd company logo
Technical Application Papers




                         2 Energy production
                         2.1	 Circuit equivalent to the cell                                Therefore the current supplied to the load is given by:
2 Energy production




                                                                                                                                                       Q.Voc
                         A photovoltaic cell can be considered as a current gen-                                                                   . .
                         erator and can be represented by the equivalent circuit                                   I = Ig - Id - Il = Ig - ID . e A k T -1 - Gl . Voc                     [2.3]
                         of Figure 2.1.
                         The current I at the outgoing terminals is equal to the
                         current generated through the PV effect Ig by the ideal            In the usual cells, the last term, i.e. the leakage current
                         current generator, decreased by the diode current Id and           to earth Il, is negligible with respect to the other two cur-
                         by the leakage current Il.                                         rents. As a consequence, the saturation current of the
                         The resistance series Rs represents the internal resist-           diode can be experimentally determined by applying the
                         ance to the flow of generated current and depends on               no-load voltage Voc to a not-illuminated cell and measur-
                         the thick of the junction P-N, on the present impurities           ing the current flowing inside the cell.
                         and on the contact resistances.
                         The leakage conductance Gl takes into account the cur-
                         rent to earth under normal operation conditions.                   2.2	 Voltage-current characteristic of the module
                         In an ideal cell we would have Rs=0 and Gl=0. On the con-
                         trary, in a high-quality silicon cell we have Rs=0.05÷0.10Ω        The voltage-current characteristic curve of a PV module
                         and Gl=3÷5mS. The conversion efficiency of the PV cell             is shown in Figure 2.2. Under short-circuit conditions
                         is greatly affected also by a small variation of Rs, whereas       the generated current is at the highest (Isc), whereas with
                         it is much less affected by a variation of Gl.                     the circuit open the voltage (Voc=open circuit voltage) is
                                                                                            at the highest. Under the two above mentioned condi-
                                                                                            tions the electric power produced in the module is null,
                         Figure 2.1
                                                                                            whereas under all the other conditions, when the voltage
                            Ig                                          Rs                  increases, the produced power rises too: at first it reaches
                                                                                            the maximum power point (Pm) and then it falls suddenly
                                                                             I              near to the no-load voltage value.
                                        Id               II
                                                                                            Figure 2.2
                                                                                                        4.5
                                                                                                                  Cell temp. = 25 °C                                Pm = I m * V m
                                                                                 Voc
                                                                                                        4.0                        Incid. irrad. = 1000 W/m2
                                                         GI                                            ISC                                                              59.9 W
                                                                                                        3.5

                                                                                                        3.0         Im
                                                                                                                                                                                      P=I*V
                                                                                                        2.5
                                                                                         Current [A]




                                                                                                        2.0

                         The no-load voltage Voc occurs when the load does not                          1.5
                         absorb any current (I=0) and is given by the relation:                         1.0

                                                              II                                        0.5
                                                                                                                                                                            Vm
                                                 Voc =                           [2.1]
                                                              GI                                        0.0
                                                                                                              0                5                10             15                20    VOC    25
                                                                                                                                              Voltage [V]
                         The diode current is given by the classic formula for the
                         direct current:                                                    Therefore, the characteristic data of a solar module can
                                                       Q.V         oc            [2.2]
                                                                                            be summarized as follows:
                                                          . .
                                             Id = ID . e A k T -1                           •	Isc 	 short-circuit current;
                                                                                            •	Voc	 no-load voltage;
                         where:                                                             •	Pm 	maximum produced power under standard condi-
                         •	 ID is the saturation current of the diode;                              tions (STC);
                         •	 Q is the charge of the electron (1.6 . 10-19 C)                 •	Im	 current produced at the maximum power point;
                         •	 A is the identity factor of the diode and depends on            •	Vm	 voltage at the maximum power point;
                            the recombination factors inside the diode itself (for          •	FF	 filling factor: it is a parameter which determines the
                            crystalline silicon is about 2)                                         form of the characteristic curve V-I and it is the ratio
                                                                        J                           between the maximum power and the product
                         •	 k is the Boltzmann constant (1.38 . 10-23       )
                         •	 T is the absolute temperature in K degree
                                                                        K                   		 (Voc . Isc ) of the no-load voltage multiplied by the
                                                                                                    short-circuit current.
                      18 Photovoltaic plants
If a voltage is applied from the outside to a PV cell in                 The currents Ig and Ir, which come from the PV generator
reverse direction with respect to standard operation,                    and the network respectively, converge in the node N of




                                                                                                                                           2 Energy production
the produced current remains constant and the power                      Figure 2.4 and the current Iu absorbed by the consumer
is absorbed by the cell. When a certain value of inverse                 plant comes out from the node:
voltage (“breakdown” voltage) is exceeded, the junction
P-N is perforated, as it occurs in a diode, and the current                                       Iu = Ig + Ir                   [2.4]
reaches a high value thus damaging the cell. In absence
of light, the generated current is null for reverse voltage              Since the current on the load is also the ratio between
up to the “breakdown” voltage, then there is a discharge                 the network voltage U and the load resistance Ru:
current similarly to the lightening conditions (Figure 2.3
– left quadrant).
                                                                                                          U
                                                                                                  Iu =                           [2.5]
Figure 2.3                                                                                               Ru
Current [A]
                                                                         the relation among the currents becomes:

                     Current [A]                                                                         U
                                                                                                 Ir =            - Ig            [2.6]
                                                                                                         Ru

                                                                         If in the [2.6] we put Ig = 0, as it occurs during the night
                                                                         hours, the current absorbed from the grid results:


                                                                                                          U
                                                                                                  Ir =                           [2.7]
                                                           Voltage [V]                                   Ru
              Vinv                 0                     Voc
                                                                         On the contrary, if all the current generated by the PV
                                                                         plant is absorbed by the consumer plant, the current
                                                                         supplied by the grid shall be null and consequently the
2.3	 Grid connection scheme                                              formula [2.6] becomes:

A PV plant connected to the grid and supplying a con-                                                     U
                                                                                                  Ig =                           [2.8]
sumer plant can be represented in a simplified way by                                                    Ru
the scheme of Figure 2.4.
The supply network (assumed to be at infinite short-cir-
cuit power) is schematized by means of an ideal voltage                  When the insolation increases, if the generated current
generator the value of which is independent of the load                  Ig becomes higher then that required by the load Iu, the
conditions of the consumer plant. On the contrary, the                   current Ir becomes negative, that is no more drawn from
PV generator is represented by an ideal current generator                the grid but put into it.
(with constant current and equal insolation) whereas the                 Multiplying the terms of the [2.4] by the network voltage
consumer plant by a resistance Ru.                                       U, the previous considerations can be made also for the
                                                                         powers, assuming as:
                                                                                         U2
                                                                         • Pu = U . Iu =    the power absorbed by the user plant;
Figure 2.4                                                               	               Ru
                          Ig                    Ir
                                       N                                 •	 Pg = U . Ig the power generated by the PV plant;

                                           Iu                            •	 Pr = U . Ir the power delivered by the grid.

PV
generator                                            U         Network
                                           RU




                                                                                                                  Photovoltaic plants 19
Technical Application Papers




                          2.4	 Nominal peak power                                                                        Remarkable values of AM are (Figure 2.6):
                                                                                                                         AM = 0 outside the atmosphere where P = 0;
2 Energy production




                          The nominal peak power (kWp) is the electric power                                             AM = 1 at sea level in a day with clear sky and the sun
                          that a PV plant is able to deliver under standard testing                                             at the zenith (P = Po, sen(h) = 1);
                          conditions (STC):                                                                              AM = 2 at sea level in a beautiful day with the sun at 30°
                          •	 1 kW/m2 insolation perpendicular to the panels;                                                                                                  1
                                                                                                                                angle above the horizon (P = Po, sen(h) =       ).
                          •	 25°C temperature in the cells;                                                                                                                   2
                          •	 air mass (AM) equal to 1.5.                                                                 Figure 2.6

                          The air mass influences the PV energy production since
                          it represents an index of the trend of the power spectral
                          density of solar radiation. As a matter of fact the latter                                                                               Upper limit of the
                                                                                                                                                                   absorbing atmosphere
                          has a spectrum with a characteristic W/m2-wavelength
                          which varies also as a function of the air density. In the                                                   AM = AM1 = 0
                          diagram of Figure 2.5 the red surface represents the
                          radiation perpendicular to the Earth surface absorbed                                                                                          )
                                                                                                                                                                     n(h
                          by the atmosphere whereas the blue surface represents                                                                                  /se
                                                                                                                                        AM = AM1 = 1         =1
                          the solar radiation which really reaches the Earth surface;                                                                      AM      Zenith angle surface
                                                                                                                                                             h
                          the difference between the trend of the two curves gives                                                                                  Local horizon
                          and indication of the spectrum variation due to the air                                                                                                    m
                                                                                                                                                                                  0k
                          mass1.                                                                                                                                                10
                          Figure 2.5
                                             [W/m2]                                                                                        Earth surface




                                                  1800
                         Power spectral density




                                                                   1350 [W/m2] (AM0)

                                                  1200                                                                   2.5	 Expected energy production per year
                                                                                  2
                                                                       1000 [W/m ] (AM1)
                                                                                                                         From an energetic point of view, the design principle
                                                   800
                                                                                                                         usually adopted for a PV generator is maximizing the
                                                                            Radiation visible to the naked eye           pick up of the available annual solar radiation. In some
                                                                                                                         cases (e.g. stand-alone PV plants) the design criterion
                                                   400
                                                                                                                         could be optimizing the energy production over definite
                                                                                                                         periods of the year.
                                                                                                                         The electric power that a PV installation can produce in
                                                    0                                                                    a year depends above all on:
                                                         0.3 0.5     1.0         1.5          2.0        2.5
                                                                                                       Wavelength
                                                                                                                         •	 availability of the solar radiation;
                                                                                                                         •	 orientation and inclination of the modules;
                          The air mass index AM is calculated as follows:                                                •	 efficiency of the PV installation.

                                                                                  P                                      Since solar radiation is variable in time, to determine the
                                                                    AM =                                         [2.9]   electric energy which the plant can produce in a fixed
                                                                             Posen (h)
                                                                                                                         time interval, the solar radiation relevant to that interval
                          where:                                                                                         is taken into consideration, assuming that the perform-
                          P	 is the atmospheric pressure measured at the point                                           ances of the modules are proportional to insolation.
                              and instant considered [Pa];                                                               The values of the average solar radiation in Italy can be
                          Po	 is the reference atmospheric pressure at the sea level                                     deduced from:
                              [1.013 . 105 Pa];                                                                          •	 the Std. UNI 10349: heating and cooling of the build-
                          h	 is the zenith angle, i.e. the elevation angle of the Sun                                       ings. Climatic data;
                              above the local horizon at the instant considered.                                         •	 the European Solar Atlas based on the data registered
                                                                                                                            by the CNR-IFA (Institute of Atmospheric Physics) in the
                                                                                                                            period 1966-1975. It reports isoradiation maps of the
                          1
                           The holes in the insolation correspond to the frequencies of the solar radiation absorbed
                          by the water vapor present in the atmosphere.                                                     Italian and European territory on horizontal or inclined
                                                                                                                            surface;
                      20 Photovoltaic plants
•	 the ENEA data bank: since 1994 ENEA collects the data                              where:
   of the solar radiation in Italy through the imagines of                            hBOS (Balance Of System) is the overall efficiency of all the




                                                                                                                                                                              2 Energy production
   the Meteosat satellite. The maps obtained up to now                                components of the PV plants on the load side of the pan-
   have been collected in two publications: one relevant                              els (inverter, connections, losses due to the temperature
   to the year 1994 and another one relevant to the period                            effect, losses due to dissymetries in the performances,
                                                                                      losses due to shading and low solar radiation, losses
   1995-1999.
                                                                                      due to reflection…). Such efficiency, in a plant properly
                                                                                      designed and installed, may range from 0.75 to 0.85.
The Tables 2.1 and 2.2 represent respectively, for differ-
ent Italian sites, the values of the average annual solar
                                                                                      Instead, taking into consideration the average daily in-
radiation on the horizontal plane [kWh/m2] from the Std.
                                                                                      solation Emg, to calculate the expected produced energy
UNI 10349 and mean daily values month by month [kWh/
                                                                                      per year for each kWp:
m2/day] from ENEA source.
The annual solar radiation for a given site may vary from
a source to the other also by 10%, since it derives from                                                Ep = Emg . 365 . hBOS [kWh/kWp]                              [2.11]
the statistical processing of data gathered over different
                                                                                      Example 2.1
periods; moreover, these data are subject to the variation
                                                                                      We want to determine the annual mean power produced
of the weather conditions from one year to the other. As
                                                                                      by a 3kWp PV plant, on a horizontal plane, in Bergamo.
a consequence the insolation values have a probabilistic
                                                                                      The efficiency of the plant components is equal to
meaning, that is they represent an expected value, not
                                                                                      0.75.
a definite one.
                                                                                      From the Table in the Std. UNI 10349, an annual mean
Starting from the mean annual radiation Ema, to obtain
                                                                                      radiation of 1276 kWh/m2 is obtained. Assuming to be
the expected produced energy per year Ep for each kWp
                                                                                      under the standard conditions of 1 kW/m2, the expected
the following formula is applied:
                                                                                      annual mean production obtained is equal to:
                Ep = Ema . hBOS [kWh/kWp]                                  [2.10]
                                                                                                          Ep = 3 . 1276 . 0.75 = 3062 kWh
Table 2.1
                                           Annual solar radiation on the horizontal plane - UNI 10349
                Annual solar                       Annual solar                        Annual solar                          Annual solar                     Annual solar
Site             radiation       Site               radiation     Site                  radiation       Site                  radiation     Site               radiation
                 (kWh/m2)                           (kWh/m2)                            (kWh/m2)                              (kWh/m2)                         (kWh/m2)
Agrigento          1923          Caltanisetta         1831        Lecce                   1639          Pordenone               1291        Savona               1384
Alessandria        1275          Cuneo                1210        Livorno                 1511          Prato                   1350        Taranto              1681
Ancona             1471          Como                 1252        Latina                  1673          Parma                   1470        Teramo               1487
Aosta              1274          Cremona              1347        Lucca                   1415          Pistoia                 1308        Trento               1423
Ascoli Piceno      1471          Cosenza              1852        Macerata                1499          Pesaro-Urbino           1411        Torino               1339
L’Aquila           1381          Catania              1829        Messina                 1730          Pavia                   1316        Trapani              1867
Arezzo             1329          Catanzaro            1663        Milan                   1307          Potenza                 1545        Terni                1409
Asti               1300          Enna                 1850        Mantova                 1316          Ravenna                 1411        Trieste              1325
Avellino           1559          Ferrara              1368        Modena                  1405          Reggio Calabria         1751        Treviso              1385
Bari               1734          Foggia               1630        Massa Carrara           1436          Reggio Emilia           1427        Udine                1272
Bergamo            1275          Florence             1475        Matera                  1584          Ragusa                  1833        Varese               1287
Belluno            1272          Forlì                1489        Naples                  1645          Rieti                   1366        Verbania             1326
Benevento          1510          Frosinone            1545        Novara                  1327          Rome                    1612        Vercelli             1327
Bologna            1420          Genoa                1425        Nuoro                   1655          Rimini                  1455        Venice               1473
Brindisi           1668          Gorizia              1326        Oristano                1654          Rovigo                  1415        Vicenza              1315
Brescia            1371          Grosseto             1570        Palermo                 1784          Salerno                 1419        Verona               1267
Bolzano            1329          Imperia              1544        Piacenza                1400          Siena                   1400        Viterbo              1468
Cagliari           1635          Isernia              1464        Padova                  1266          Sondrio                 1442
Campobasso         1597          Crotone              1679        Pescara                 1535          La Spezia               1452
Caserta            1678          Lecco                1271        Perugia                 1463          Siracusa                1870
Chieti             1561          Lodi                 1311        Pisa                    1499          Sassari                 1669


Table 2.2

Site            January        February    March        April            May        June         July          August     September     October    November      December
Milan            1.44            2.25      3.78         4.81             5.67       6.28         6.31           5.36        3.97         2.67        1.64          1.19
Venice           1.42            2.25      3.67         4.72             5.75       6.31         6.36           5.39        4.08         2.72        1.64          1.14
Bologna          1.50            2.28      3.81         4.81             5.86       6.42         6.47           5.47        4.19         2.81        1.72          1.25
Florence         1.58            2.33      3.75         4.72             5.86       6.39         6.44           5.50        4.17         2.86        1.83          1.39
Rome             1.92            2.61      3.94         4.92             6.08       6.56         6.58           5.72        4.39         3.17        2.11          1.58
Naples           1.92            2.67      3.92         5.03             6.08       6.64         6.58           5.81        4.50         3.28        2.17          1.69
Bari             1.86            2.58      3.97         5.08             6.08       6.69         6.64           5.81        4.53         3.25        2.08          1.69
Messina          2.11           2.94       4.19         5.19             6.22       6.69         6.67           5.89        4.64         3.53        2.36          1.94
Siracusa         2.36           3.22       4.33         5.39             6.36       6.78         6.75           6.00        4.81         3.69        2.58          2.17


                                                                                                                                            Photovoltaic plants 21
Technical Application Papers




                         2.6	 Inclination and orientation of the panels                              Finding the complementary angle of α (90°-α), it is pos-
2 Energy production




                                                                                                     sible to obtain the tilt angle β, of the panels with respect
                         The maximum efficiency of a solar panel would be                            to the horizontal plane (IEC/TS 61836) so that the panels
                         reached if the angle of incidence of solar rays were always                 are struck perpendicularly by the solar rays in the above
                         90°. In fact the incidence of solar radiation varies both                   mentioned moment2.
                         according to latitude as well as to the solar declination                   However, it is not sufficient to know the angle α to deter-
                         during the year. In fact, since the Earth’s rotation axis is                mine the optimum orientation of the panels. It is neces-
                         tilted by about 23.45° with respect to the plane of the                     sary to take into consideration also the Sun path through
                         Earth orbit about the Sun, at definite latitude the height of               the sky over the different periods of the year and therefore
                         the Sun on the horizon varies daily. The Sun is positioned                  the tilt angle should be calculated taking into considera-
                         at 90° angle of incidence with respect to the Earth surface                 tion all the days of the year3 (Figure 2.8). This allows to
                         (Zenith) at the equator in the two days of the equinox and                  obtain an annual total radiation captured by the panels
                         along the tropics at the solstices (Figure 2.7).                            (and therefore the annual energy production) higher than
                                                                                                     that obtained under the previous irradiance condition
                                                                                                     perpendicular to the panels during the solstice.
                         Figure 2.7


                                                                                                     Figure 2.8
                                      N
                                                                                                                                        solar path at 45ϒ North latitude
                                                                                                                                                         'a1
                                                                      Summer solstice at the
                                                                      Tropic of Cancer                                                                           12
                                                                                                                                                     11
                                                                      21st or 22nd June
                                                       °                                                                                10
                                                , 45                  Vernal equinox
                                          +23
                                                    0°                20th or 21st March                                            9                            12
                                                                                                    Solar height




                                          -23                         Autumnal equinox                                                                     11
                                             , 45
                                                  °                   22nd or 23rd September                                                     10
                                                                                                                                8

                                                                      Winter solstice at the                                                 9




                                                                                                                                                                                           21
                                                                                                                            7
                                                                      Tropic of Capricorn




                                                                                                                                                                                           Ju
                                                                                                                                                            11   12




                                                                                                                                                                                            ne
                                                                      22nd or 23rd December                                             8


                                                                                                                                                                                21
                                                                                                                        6                             10
                                                                                                                                                                                                 W
                                                                                                                                                                                 Ma
                                                                                                      E                                          9
                                                                                                                                                                      21


                                      S                                                                                                                                                          E
                                                                                                                                                                                     rch
                                                                                                                                    7
                                                                                                      A
                                                                                                                                                                       De



                                                                                                      S                                      8                                                   S
                                                                                                                                                                           ce



                                                                                                                                6
                                                                                                                                                                           m



                                                                                                      T                                                                                          T
                                                                                                                                                                            be



                                                                                                                   0ϒ
                                                                                                                                                                                r




                         Outside the Tropics latitude, the Sun cannot reach the
                         Zenith above the Earth’s surface, but it shall be at its                    The fixed panels should be oriented as much as possible
                         highest point (depending on the latitude) with reference                    to south in the northern hemisphere4 so as to get a better
                         to the summer solstice day in the northern hemisphere                       insolation of the panel surface at noon local hour and a
                         and in the winter solstice day in the southern hemisphere.                  better global daily insolation of the panels.
                         Therefore, if we wish to incline the panels so that they                    The orientation of the panels may be indicated with the
                         can be struck perpendicularly by the solar rays at noon                     Azimuth5 angle (γ) of deviation with respect to the opti-
                         of the longest day of the year it is necessary to know                      mum direction to south (for the locations in the northern
                         the maximum height (in degrees) which the Sun reaches                       hemisphere) or to north (for the locations in the southern
                         above the horizon in that instant, obtained by the follow-                  hemisphere).
                         ing formula:

                                                       a = 90° - lat + d                   [2.12]
                         where:                                                                     2
                                                                                                      On gabled roofs the tilt angle is determined by the inclination of the roof itself.
                         lat	 is the value (in degrees) of latitude of the installation             3
                                                                                                      In Italy the optimum tilted angle is about 30°.
                                                                                                    4
                                                                                                      Since the solar irradiance is maximum at noon, the collector surface must be oriented
                              site of the panels;                                                   to south as much as possible. On the contrary, in the southern hemisphere, the optimum
                                                                                                    orientation is obviously to north.
                         d	 is the angle of solar declination [23.45°]                              5
                                                                                                      In astronomy the Azimuth angle is defined as the angular distance along the horizon,
                                                                                                    measured from north (0°) to east, of the point of intersection of the vertical circle passing
                                                                                                    through the object.




                      22 Photovoltaic plants
Positive values of the Azimuth angles show an orienta-                                           A non–horizontal panel receives, besides direct and dif-
tion to west, whereas negative values an orientation to                                          fuse radiation, also the radiation reflected by the surface




                                                                                                                                                                                  2 Energy production
east (IEC 61194).                                                                                surrounding it (albedo component). Usually an albedo
As regards ground-mounted panels, the combination                                                coefficient of 0.2 is assumed.
of inclination and orientation determines the exposition                                         For a first evaluation of the annual production capability
of the panels themselves (Figure 2.9). On the contrary,                                          of electric power of a PV installation it is usually sufficient
when the panels are installed on the roofs of buildings,                                         to apply to the annual mean radiation on the horizontal
the exposition is determined by the inclination and the                                          plan (Tables 2.1-2.2) the correction coefficients of the
orientation of the roof pitches. Good results are obtained                                       Tables 2.3, 2.4 and 2.56.
through collectors oriented to south-east or to south-                                           6
                                                                                                     Albedo assumed equal to 0.2.
west with a deviation with respect to the south up to 45°
                                                                                                 Table 2.3 – Northern Italy: 44°N latitude
(Figure 2.10). Greater deviations can be compensated by                                                                                      Orientation
means of a slight enlargement of the collector surface.                                                                   0°                                          ± 90°
                                                                                                     Inclination       (south)      ± 15°       ± 30°      ± 45°   (east; west)
Figure 2.9                                                                                                0°             1.00       1.00        1.00       1.00       1.00
                                                                                                         10°             1.07       1.06        1.06       1.04       0.99
                                                                                                         15°             1.09       1.09        1.07       1.06       0.98
                                                       β                                                 20°             1.11       1.10        1.09       1.07       0.96
                                                                                                         30°             1.13       1.12        1.10       1.07       0.93
                                                                                                         40°             1.12       1.11        1.09       1.05       0.89
                                                                                                         50°             1.09       1.08        1.05       1.02       0.83
                                                                                                         60°             1.03       0.99        0.96       0.93       0.77
                                                                                                         70°             0.95       0.95        0.93       0.89       0.71
                                                                                                         90°             0.74       0.74        0.73       0.72       0.57

                                                                                                 Table 2.4 - Central Italy: 41°N latitude
                                                                                                                                             Orientation
                                  γ                                                                                       0°                                          ± 90°
                                                                                                     Inclination       (south)      ± 15°       ± 30°      ± 45°   (east; west)
                                                                                                          0°             1.00       1.00        1.00       1.00       1.00
                        SOUTH
                                                                                                         10°             1.07       1.07        1.06       1.04       0.99
                                                                                                         15°             1.09       1.09        1.08       1.06       0.97
Figure 2.10                                                                                              20°             1.11       1.11        1.09       1.07       0.96
                                                                                                         30°             1.13       1.12        1.10       1.07       0.92
                                                                                                         40°             1.12       1.12        1.09       1.05       0.87
                                             -170ϒ




                                         North
                                 +170ϒ




                                                      0ϒ
                   +16




                                                                                                         50°             1.09       1.08        1.05       1.01       0.82
                                                            0ϒ
                                                     -16
                     +1




                                                                                                         60°             1.03       1.02        0.99       0.96       0.76
                      0ϒ




                                                           -15
                       50




                                                                   ϒ




                                                                                                         70°             0.94       0.94        0.92       0.88       0.70
                        +1




                                                                 40
                         ϒ




             +1
                          40




                                                                              ϒ
                                                             -1




               30                                                        30                              90°             0.72       0.72        0.71       0.70       0.56
                            ϒ




                 ϒ                                                     -1
          +1                                                                      0ϒ
            20
              ϒ                                                             -12                  Table 2.5 - Southern Italy: 38°N latitude
        +11                                                                           0ϒ                                                     Orientation
           0ϒ                                                                 -11
                                                                                                                          0°                                          ± 90°
      +100ϒ                                                                       -100ϒ              Inclination       (south)      ± 15°       ± 30°      ± 45°   (east; west)
                                                                                                          0°             1.00       1.00        1.00       1.00       1.00
     West                                  10ϒ20ϒ30ϒ40ϒ50ϒ60ϒ70ϒ80ϒ90ϒ            East                   10°             1.06       1.06        1.05       1.04       0.99
                                                                                  -80ϒ                   15°             1.08       1.08        1.07       1.05       0.97
       +80ϒ                                                                                              20°             1.10       1.09        1.08       1.06       0.96
           ϒ                                                                  -70                        30°             1.11       1.10        1.08       1.06       0.92
        +70                                                                      ϒ
                                                                                                         40°             1.10       1.09        1.07       1.03       0.87
                                                                            -60
                0ϒ                                                                ϒ                      50°             1.06       1.05        1.03       0.99       0.82
              +6                                                   -5
                                                                        0ϒ                               60°             0.99       0.99        0.96       0.93       0.75
                   0ϒ
                 +5                                                                                      70°             0.91       0.91        0.88       0.86       0.69
                                                     -4
                         0ϒ




                                                                                                         90°             0.68       0.68        0.68       0.67       0.55
                                                        0ϒ
                       +4




                                                         -30
                      0ϒ




                                                           -20
                     ϒ
                    +3




                                              -10ϒ



                                                            ϒ
                                +10ϒ
                  +20




                                         South                                                   Example 2.2
                                                               ϒ




                                                                                                 We wish to determine the annual mean energy produced
                                                                                                 by the PV installation of the previous example, now ar-
 Annual insolation in %
                                                                                                 ranged with +15° orientation and 30° inclination.
       30         40      50     60         70         40         80              90       100

                                                                                                 From Table 2.3 an increasing coefficient equal to 1.12
                                                                                                 is obtained. Multiplying this coefficient by the energy
 Tilt angle                                                                                      expected on horizontal plan obtained in the previous
     10ϒ         20ϒ     30ϒ    40ϒ        50ϒ        60ϒ        70ϒ          80ϒ          90ϒ   example, the expected production capability becomes:

       : Example: 30ϒ'a1; 45ϒ south-west; ⊕ 95%
                             'a1           'c                                                                  E = 1.12 . Ep = 1.12 . 3062 ≈ 3430 kWh

                                                                                                                                                   Photovoltaic plants 23
Technical Application Papers




                         2.7	 Voltages and currents in a PV plant                            2.8	 Variation in the produced energy
2 Energy production




                         PV modules generate a current from 4 to 10A at a volt-              The main factors which influence the electric energy
                         age from 30 to 40V.                                                 produced by a PV installation are:
                         To get the projected peak power, the panels are electri-            •	 irradiance
                         cally connected in series to form the strings, which are            •	 temperature of the modules
                         connected in parallel. The trend is developing strings              •	 shading.
                         constituted by as many panels as possible, given the
                         complexity and cost of wiring, in particular of the paral-          2.8.1	 Irradiance
                         leling switchboards between the strings.                            As a function of the irradiance incident on the PV cells,
                         The maximum number of panels which can be connected                 the characteristic curve V-I of them changes as shown
                         in series (and therefore the highest reachable voltage)             in Figure 2.11.
                         to form a string is determined by the operation range of            When the irradiance decreases, the generated PV cur-
                         the inverter (see Chapter 3) and by the availability of the         rent decreases proportionally, whereas the variation of
                         disconnection and protection devices suitable for the               the no-load voltage is very small.
                         voltage reached.
                         In particular, the voltage of the inverter is bound, due to         As a matter of fact, the conversion efficiency is not
                         reasons of efficiency, to its power: generally, when using          influenced by the variation of the irradiance within the
                         inverter with power lower than 10 kW, the voltage range             standard operation range of the cells, which means that
                         most commonly used is from 250V to 750V, whereas if                 the conversion efficiency is the same both in a clear as
                         the power of the inverter exceeds 10 kW, the voltage                well as in a cloudy day.
                         range usually is from 500V to 900V.                                 Therefore the smaller power generated with cloudy
                                                                                             sky is referable not to a drop of the efficiency but to a
                                                                                             reduced generation of current because of lower solar
                                                                                             irradiance.

                         Figure 2.11
                                       3.5                                                                                                   1000 W/m2
                                                                                                                                              900 W/m2
                                                                                                                                              800 W/m2
                                        3
                                                                                                                                              700 W/m2
                                                                                                                                              600 W/m2
                                                                                                                                              500 W/m2
                                       2.5



                                        2
                         Current [A]




                                       1.5



                                        1



                                       0.5



                                        0
                                             0   2    4       6        8      10       12     14      16      18      20      22
                                                                               Voltage [V]




                      24 Photovoltaic plants
2.8.2	 Temperature of the modules                                                         2.8.3	 Shading




                                                                                                                                                       2 Energy production
Contrary to the previous case, when the temperature of                                    Taking into consideration the area occupied by the mod-
the modules increases, the produced current remains                                       ules of a PV plant, part of them (one or more cells) may
practically unchanged, whereas the voltage decreases                                      be shaded by trees, fallen leaves, chimneys, clouds or
and with it there is a reduction in the performances of                                   by PV panels installed nearby.
the panels in terms of produced electric power (Figure                                    In case of shading, a PV cell consisting in a junction
2.12).                                                                                    P-N stops producing energy and becomes a passive
                                                                                          load. This cell behaves as a diode which blocks the
Figure 2.12
                                                                                          current produced by the other cells connected in series
      3
                                                                                          thus jeopardizing the whole production of the module.
                 E = 1000 W/m2                                                            Moreover the diode is subject to the voltage of the other
                                                                                          cells which may cause the perforation of the junction
                                                                                          due to localized overheating (hot spot) and damages to
      2                                                              20
                                                                                          the module.
                                                                     40                   In order to avoid that one or more shaded cells thwart the
                                                                     60                   production of a whole string, some diodes which by-pass
                                                                    80                    the shaded or damaged part of module are inserted at
      1
                                                                   100                    the module level. Thus the functioning of the module is
                                                                                          guaranteed even if with reduced efficiency. In theory it
                                                                                          would be necessary to insert a by-pass diode in parallel
                                                                        Voltage
                                                                                          to each single cell, but this would be too onerous for the
      0
                          0.2               0.4              0.6
                                                                                          ratio costs/benefits. Therefore 2÷4 by-pass diodes are
                                                                                          usually installed for each module (Figure 2.13).
The variation in the no-load voltage Voc of a PV mod-
ule with respect to the standard conditions Voc,stc, as a
function of the operating temperature of the cells Tcell,
is expressed by the following formula (Guidelines CEI
82-25, II ed.):                                                                           Figure 2.13
                                                                                                                            By-pass diode
                  Voc(T) = Voc,stc - NS . b . (25-Tcel)                        [2.13]
where:
β is the variation coefficient of the voltage according to
temperature and depends on the typology of PV module
(usually -2.2 mV/°C/cell for crystalline silicon modules and
about -1.5 ÷ -1.8 mV/°C/cell for thin film modules);                                              Solar radiation
Ns is the number of cells in series in the module.

Therefore, to avoid an excessive reduction in the perform-
ances, it is opportune to keep under control the service
                                                                                                                             Shadow
temperature trying to give the panels good ventilation
to limit the temperature variation on them. In this way
it is possible to reduce the loss of energy owing to the
                                                                                              +                                                –
temperature (in comparison with the temperature of 25°C
under standard conditions) to a value around 7%7.
                                                                                          I                                                        I


7
   The reduction in efficiency when the temperature increases can be estimated as 0.4 	
to 0.6 for each °C.




                                                                                                                             Photovoltaic plants 25

More Related Content

What's hot

Gq3112761281
Gq3112761281Gq3112761281
Gq3112761281
IJERA Editor
 
Induction Lamp Story
Induction Lamp StoryInduction Lamp Story
Induction Lamp Story
joycelite
 
EWB practical workbook
EWB practical  workbookEWB practical  workbook
EWB practical workbook
serjani
 
BTC108 3 Capacitance
BTC108 3 CapacitanceBTC108 3 Capacitance
BTC108 3 CapacitanceJames Uren
 
5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application
Abdo Brahmi
 
Ade manual final
Ade manual finalAde manual final
Ade manual final
Devendra Kushwaha
 
Led book
Led bookLed book
Led book
vigyanashram
 
BEE introduction slides
BEE introduction slidesBEE introduction slides
BEE introduction slides
BLESSINAR0
 
Interpret the diode equivalent circuit
Interpret the diode equivalent circuitInterpret the diode equivalent circuit
Interpret the diode equivalent circuit
manojmanoj218596
 
The Study of MOSFET Parallelism in High Frequency DC/DC Converter
The Study of MOSFET Parallelism in High Frequency DC/DC ConverterThe Study of MOSFET Parallelism in High Frequency DC/DC Converter
The Study of MOSFET Parallelism in High Frequency DC/DC Converter
IDES Editor
 
Diode
DiodeDiode
Lecture-7 : Semiconductor Power Switching Devices-4
Lecture-7 : Semiconductor Power Switching Devices-4Lecture-7 : Semiconductor Power Switching Devices-4
Lecture-7 : Semiconductor Power Switching Devices-4
rsamurti
 
Ece
EceEce
Automatic low power emergency light
Automatic low power emergency lightAutomatic low power emergency light
Automatic low power emergency lightviv3ksharma
 
automatic light control at night ppt by Shubhan raj
automatic light control at night ppt by Shubhan rajautomatic light control at night ppt by Shubhan raj
automatic light control at night ppt by Shubhan raj
Shubham Raj
 
Zener diodes
Zener diodesZener diodes
Zener diodes
Touqeer Jumani
 
Eo24881888
Eo24881888Eo24881888
Eo24881888
IJERA Editor
 
Analog circuits-lab-possible-viva-questions
Analog circuits-lab-possible-viva-questionsAnalog circuits-lab-possible-viva-questions
Analog circuits-lab-possible-viva-questions
padmajasiva
 

What's hot (20)

Gq3112761281
Gq3112761281Gq3112761281
Gq3112761281
 
Induction Lamp Story
Induction Lamp StoryInduction Lamp Story
Induction Lamp Story
 
EWB practical workbook
EWB practical  workbookEWB practical  workbook
EWB practical workbook
 
BTC108 3 Capacitance
BTC108 3 CapacitanceBTC108 3 Capacitance
BTC108 3 Capacitance
 
5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application
 
Ade manual final
Ade manual finalAde manual final
Ade manual final
 
Led book
Led bookLed book
Led book
 
BEE introduction slides
BEE introduction slidesBEE introduction slides
BEE introduction slides
 
Report
ReportReport
Report
 
Interpret the diode equivalent circuit
Interpret the diode equivalent circuitInterpret the diode equivalent circuit
Interpret the diode equivalent circuit
 
The Study of MOSFET Parallelism in High Frequency DC/DC Converter
The Study of MOSFET Parallelism in High Frequency DC/DC ConverterThe Study of MOSFET Parallelism in High Frequency DC/DC Converter
The Study of MOSFET Parallelism in High Frequency DC/DC Converter
 
Electronic letter box
Electronic letter boxElectronic letter box
Electronic letter box
 
Diode
DiodeDiode
Diode
 
Lecture-7 : Semiconductor Power Switching Devices-4
Lecture-7 : Semiconductor Power Switching Devices-4Lecture-7 : Semiconductor Power Switching Devices-4
Lecture-7 : Semiconductor Power Switching Devices-4
 
Ece
EceEce
Ece
 
Automatic low power emergency light
Automatic low power emergency lightAutomatic low power emergency light
Automatic low power emergency light
 
automatic light control at night ppt by Shubhan raj
automatic light control at night ppt by Shubhan rajautomatic light control at night ppt by Shubhan raj
automatic light control at night ppt by Shubhan raj
 
Zener diodes
Zener diodesZener diodes
Zener diodes
 
Eo24881888
Eo24881888Eo24881888
Eo24881888
 
Analog circuits-lab-possible-viva-questions
Analog circuits-lab-possible-viva-questionsAnalog circuits-lab-possible-viva-questions
Analog circuits-lab-possible-viva-questions
 

Viewers also liked

Minoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di PratoMinoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di Prato
minoranzacreativa
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
Kim Loan Nguyen
 
How Podcasting Can Build a Community
How Podcasting Can Build a CommunityHow Podcasting Can Build a Community
How Podcasting Can Build a Community
For Immediate Release Podcast Network
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
Kim Loan Nguyen
 
Setting up the Arduino ATTiny
Setting up the Arduino ATTinySetting up the Arduino ATTiny
Setting up the Arduino ATTiny
Brian Huang
 
NSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and ArduinoNSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and Arduino
Brian Huang
 
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMiniT21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
Brian Huang
 
Strategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the ClassroomStrategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the Classroom
Brian Huang
 
ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)
Brian Huang
 
Open-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics EducationOpen-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics Education
Brian Huang
 
Introduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPadIntroduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPad
Brian Huang
 
Scratch for Data Logging and Graphing
Scratch for Data Logging and GraphingScratch for Data Logging and Graphing
Scratch for Data Logging and Graphing
Brian Huang
 
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 BostonMaker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Brian Huang
 
Pop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurusPop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurus
Brian Huang
 
ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)
Brian Huang
 

Viewers also liked (19)

Minoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di PratoMinoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di Prato
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
 
Lezione 1
Lezione 1Lezione 1
Lezione 1
 
Pv lez 6
Pv lez 6Pv lez 6
Pv lez 6
 
How Podcasting Can Build a Community
How Podcasting Can Build a CommunityHow Podcasting Can Build a Community
How Podcasting Can Build a Community
 
Chapter 02
Chapter 02Chapter 02
Chapter 02
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
 
Setting up the Arduino ATTiny
Setting up the Arduino ATTinySetting up the Arduino ATTiny
Setting up the Arduino ATTiny
 
NSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and ArduinoNSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and Arduino
 
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMiniT21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
 
Pv 3 lez
Pv 3 lezPv 3 lez
Pv 3 lez
 
Strategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the ClassroomStrategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the Classroom
 
ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)
 
Open-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics EducationOpen-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics Education
 
Introduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPadIntroduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPad
 
Scratch for Data Logging and Graphing
Scratch for Data Logging and GraphingScratch for Data Logging and Graphing
Scratch for Data Logging and Graphing
 
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 BostonMaker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
 
Pop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurusPop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurus
 
ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)
 

Similar to Lezione 2

Unit5-Transformers.ppt
Unit5-Transformers.pptUnit5-Transformers.ppt
Unit5-Transformers.ppt
MdSazibMollik
 
Unit1-Transformers.ppt
Unit1-Transformers.pptUnit1-Transformers.ppt
Unit1-Transformers.ppt
MdSazibMollik
 
Physica curckts
Physica curcktsPhysica curckts
Physica curckts12B-129-El
 
227 sample chapter
227 sample chapter227 sample chapter
227 sample chapter
Ankit Dubey
 
bee ppt - lokesh (73).pptx
bee ppt - lokesh (73).pptxbee ppt - lokesh (73).pptx
bee ppt - lokesh (73).pptx
DanyDany88
 
Lab - 03
Lab - 03Lab - 03
Lab - 03
MD Jakaria
 
03
0303
Network theorems for electrical engineering
Network theorems for electrical engineeringNetwork theorems for electrical engineering
Network theorems for electrical engineeringKamil Hussain
 
Snubbing Methods
Snubbing MethodsSnubbing Methods
Snubbing MethodsRic Barline
 
Transformers devices and its efficiency of it
Transformers devices and its efficiency of itTransformers devices and its efficiency of it
Transformers devices and its efficiency of it
nsp945
 
Transformers 25.02.2020.pptx
Transformers 25.02.2020.pptxTransformers 25.02.2020.pptx
Transformers 25.02.2020.pptx
PraveenKumarB30
 
Chapter 1 techniques of dc circuit analysis
Chapter 1 techniques of dc circuit analysisChapter 1 techniques of dc circuit analysis
Chapter 1 techniques of dc circuit analysis
Amirul Faiz Amil Azman
 
Fuzzy intelligent controller for the maximum power point tracking of a photov...
Fuzzy intelligent controller for the maximum power point tracking of a photov...Fuzzy intelligent controller for the maximum power point tracking of a photov...
Fuzzy intelligent controller for the maximum power point tracking of a photov...
Alexander Decker
 
11.fuzzy intelligent controller for the maximum power point tracking of a pho...
11.fuzzy intelligent controller for the maximum power point tracking of a pho...11.fuzzy intelligent controller for the maximum power point tracking of a pho...
11.fuzzy intelligent controller for the maximum power point tracking of a pho...Alexander Decker
 
transformer working principle
transformer working principletransformer working principle
transformer working principle
md akkas ali
 
Direct current circuits
Direct current circuitsDirect current circuits
Direct current circuitsJFG407
 
P25079084
P25079084P25079084
P25079084
IJERA Editor
 

Similar to Lezione 2 (20)

Unit5-Transformers.ppt
Unit5-Transformers.pptUnit5-Transformers.ppt
Unit5-Transformers.ppt
 
Unit1-Transformers.ppt
Unit1-Transformers.pptUnit1-Transformers.ppt
Unit1-Transformers.ppt
 
Power Sharing
Power SharingPower Sharing
Power Sharing
 
Physica curckts
Physica curcktsPhysica curckts
Physica curckts
 
227 sample chapter
227 sample chapter227 sample chapter
227 sample chapter
 
bee ppt - lokesh (73).pptx
bee ppt - lokesh (73).pptxbee ppt - lokesh (73).pptx
bee ppt - lokesh (73).pptx
 
Lecture 5
Lecture 5Lecture 5
Lecture 5
 
Lab - 03
Lab - 03Lab - 03
Lab - 03
 
03
0303
03
 
Lecture 4
Lecture 4 Lecture 4
Lecture 4
 
Network theorems for electrical engineering
Network theorems for electrical engineeringNetwork theorems for electrical engineering
Network theorems for electrical engineering
 
Snubbing Methods
Snubbing MethodsSnubbing Methods
Snubbing Methods
 
Transformers devices and its efficiency of it
Transformers devices and its efficiency of itTransformers devices and its efficiency of it
Transformers devices and its efficiency of it
 
Transformers 25.02.2020.pptx
Transformers 25.02.2020.pptxTransformers 25.02.2020.pptx
Transformers 25.02.2020.pptx
 
Chapter 1 techniques of dc circuit analysis
Chapter 1 techniques of dc circuit analysisChapter 1 techniques of dc circuit analysis
Chapter 1 techniques of dc circuit analysis
 
Fuzzy intelligent controller for the maximum power point tracking of a photov...
Fuzzy intelligent controller for the maximum power point tracking of a photov...Fuzzy intelligent controller for the maximum power point tracking of a photov...
Fuzzy intelligent controller for the maximum power point tracking of a photov...
 
11.fuzzy intelligent controller for the maximum power point tracking of a pho...
11.fuzzy intelligent controller for the maximum power point tracking of a pho...11.fuzzy intelligent controller for the maximum power point tracking of a pho...
11.fuzzy intelligent controller for the maximum power point tracking of a pho...
 
transformer working principle
transformer working principletransformer working principle
transformer working principle
 
Direct current circuits
Direct current circuitsDirect current circuits
Direct current circuits
 
P25079084
P25079084P25079084
P25079084
 

Recently uploaded

The geography of Taylor Swift - some ideas
The geography of Taylor Swift - some ideasThe geography of Taylor Swift - some ideas
The geography of Taylor Swift - some ideas
GeoBlogs
 
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCECLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
BhavyaRajput3
 
Embracing GenAI - A Strategic Imperative
Embracing GenAI - A Strategic ImperativeEmbracing GenAI - A Strategic Imperative
Embracing GenAI - A Strategic Imperative
Peter Windle
 
Thesis Statement for students diagnonsed withADHD.ppt
Thesis Statement for students diagnonsed withADHD.pptThesis Statement for students diagnonsed withADHD.ppt
Thesis Statement for students diagnonsed withADHD.ppt
EverAndrsGuerraGuerr
 
The approach at University of Liverpool.pptx
The approach at University of Liverpool.pptxThe approach at University of Liverpool.pptx
The approach at University of Liverpool.pptx
Jisc
 
A Strategic Approach: GenAI in Education
A Strategic Approach: GenAI in EducationA Strategic Approach: GenAI in Education
A Strategic Approach: GenAI in Education
Peter Windle
 
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
MysoreMuleSoftMeetup
 
How to Make a Field invisible in Odoo 17
How to Make a Field invisible in Odoo 17How to Make a Field invisible in Odoo 17
How to Make a Field invisible in Odoo 17
Celine George
 
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdfAdversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
Po-Chuan Chen
 
Introduction to AI for Nonprofits with Tapp Network
Introduction to AI for Nonprofits with Tapp NetworkIntroduction to AI for Nonprofits with Tapp Network
Introduction to AI for Nonprofits with Tapp Network
TechSoup
 
Language Across the Curriculm LAC B.Ed.
Language Across the  Curriculm LAC B.Ed.Language Across the  Curriculm LAC B.Ed.
Language Across the Curriculm LAC B.Ed.
Atul Kumar Singh
 
"Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe..."Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe...
SACHIN R KONDAGURI
 
Additional Benefits for Employee Website.pdf
Additional Benefits for Employee Website.pdfAdditional Benefits for Employee Website.pdf
Additional Benefits for Employee Website.pdf
joachimlavalley1
 
special B.ed 2nd year old paper_20240531.pdf
special B.ed 2nd year old paper_20240531.pdfspecial B.ed 2nd year old paper_20240531.pdf
special B.ed 2nd year old paper_20240531.pdf
Special education needs
 
1.4 modern child centered education - mahatma gandhi-2.pptx
1.4 modern child centered education - mahatma gandhi-2.pptx1.4 modern child centered education - mahatma gandhi-2.pptx
1.4 modern child centered education - mahatma gandhi-2.pptx
JosvitaDsouza2
 
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
siemaillard
 
The Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official PublicationThe Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official Publication
Delapenabediema
 
678020731-Sumas-y-Restas-Para-Colorear.pdf
678020731-Sumas-y-Restas-Para-Colorear.pdf678020731-Sumas-y-Restas-Para-Colorear.pdf
678020731-Sumas-y-Restas-Para-Colorear.pdf
CarlosHernanMontoyab2
 
Sha'Carri Richardson Presentation 202345
Sha'Carri Richardson Presentation 202345Sha'Carri Richardson Presentation 202345
Sha'Carri Richardson Presentation 202345
beazzy04
 
Lapbook sobre os Regimes Totalitários.pdf
Lapbook sobre os Regimes Totalitários.pdfLapbook sobre os Regimes Totalitários.pdf
Lapbook sobre os Regimes Totalitários.pdf
Jean Carlos Nunes Paixão
 

Recently uploaded (20)

The geography of Taylor Swift - some ideas
The geography of Taylor Swift - some ideasThe geography of Taylor Swift - some ideas
The geography of Taylor Swift - some ideas
 
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCECLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
CLASS 11 CBSE B.St Project AIDS TO TRADE - INSURANCE
 
Embracing GenAI - A Strategic Imperative
Embracing GenAI - A Strategic ImperativeEmbracing GenAI - A Strategic Imperative
Embracing GenAI - A Strategic Imperative
 
Thesis Statement for students diagnonsed withADHD.ppt
Thesis Statement for students diagnonsed withADHD.pptThesis Statement for students diagnonsed withADHD.ppt
Thesis Statement for students diagnonsed withADHD.ppt
 
The approach at University of Liverpool.pptx
The approach at University of Liverpool.pptxThe approach at University of Liverpool.pptx
The approach at University of Liverpool.pptx
 
A Strategic Approach: GenAI in Education
A Strategic Approach: GenAI in EducationA Strategic Approach: GenAI in Education
A Strategic Approach: GenAI in Education
 
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
Mule 4.6 & Java 17 Upgrade | MuleSoft Mysore Meetup #46
 
How to Make a Field invisible in Odoo 17
How to Make a Field invisible in Odoo 17How to Make a Field invisible in Odoo 17
How to Make a Field invisible in Odoo 17
 
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdfAdversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
Adversarial Attention Modeling for Multi-dimensional Emotion Regression.pdf
 
Introduction to AI for Nonprofits with Tapp Network
Introduction to AI for Nonprofits with Tapp NetworkIntroduction to AI for Nonprofits with Tapp Network
Introduction to AI for Nonprofits with Tapp Network
 
Language Across the Curriculm LAC B.Ed.
Language Across the  Curriculm LAC B.Ed.Language Across the  Curriculm LAC B.Ed.
Language Across the Curriculm LAC B.Ed.
 
"Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe..."Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe...
 
Additional Benefits for Employee Website.pdf
Additional Benefits for Employee Website.pdfAdditional Benefits for Employee Website.pdf
Additional Benefits for Employee Website.pdf
 
special B.ed 2nd year old paper_20240531.pdf
special B.ed 2nd year old paper_20240531.pdfspecial B.ed 2nd year old paper_20240531.pdf
special B.ed 2nd year old paper_20240531.pdf
 
1.4 modern child centered education - mahatma gandhi-2.pptx
1.4 modern child centered education - mahatma gandhi-2.pptx1.4 modern child centered education - mahatma gandhi-2.pptx
1.4 modern child centered education - mahatma gandhi-2.pptx
 
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
 
The Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official PublicationThe Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official Publication
 
678020731-Sumas-y-Restas-Para-Colorear.pdf
678020731-Sumas-y-Restas-Para-Colorear.pdf678020731-Sumas-y-Restas-Para-Colorear.pdf
678020731-Sumas-y-Restas-Para-Colorear.pdf
 
Sha'Carri Richardson Presentation 202345
Sha'Carri Richardson Presentation 202345Sha'Carri Richardson Presentation 202345
Sha'Carri Richardson Presentation 202345
 
Lapbook sobre os Regimes Totalitários.pdf
Lapbook sobre os Regimes Totalitários.pdfLapbook sobre os Regimes Totalitários.pdf
Lapbook sobre os Regimes Totalitários.pdf
 

Lezione 2

  • 1. Technical Application Papers 2 Energy production 2.1 Circuit equivalent to the cell Therefore the current supplied to the load is given by: 2 Energy production Q.Voc A photovoltaic cell can be considered as a current gen- . . erator and can be represented by the equivalent circuit I = Ig - Id - Il = Ig - ID . e A k T -1 - Gl . Voc [2.3] of Figure 2.1. The current I at the outgoing terminals is equal to the current generated through the PV effect Ig by the ideal In the usual cells, the last term, i.e. the leakage current current generator, decreased by the diode current Id and to earth Il, is negligible with respect to the other two cur- by the leakage current Il. rents. As a consequence, the saturation current of the The resistance series Rs represents the internal resist- diode can be experimentally determined by applying the ance to the flow of generated current and depends on no-load voltage Voc to a not-illuminated cell and measur- the thick of the junction P-N, on the present impurities ing the current flowing inside the cell. and on the contact resistances. The leakage conductance Gl takes into account the cur- rent to earth under normal operation conditions. 2.2 Voltage-current characteristic of the module In an ideal cell we would have Rs=0 and Gl=0. On the con- trary, in a high-quality silicon cell we have Rs=0.05÷0.10Ω The voltage-current characteristic curve of a PV module and Gl=3÷5mS. The conversion efficiency of the PV cell is shown in Figure 2.2. Under short-circuit conditions is greatly affected also by a small variation of Rs, whereas the generated current is at the highest (Isc), whereas with it is much less affected by a variation of Gl. the circuit open the voltage (Voc=open circuit voltage) is at the highest. Under the two above mentioned condi- tions the electric power produced in the module is null, Figure 2.1 whereas under all the other conditions, when the voltage Ig Rs increases, the produced power rises too: at first it reaches the maximum power point (Pm) and then it falls suddenly I near to the no-load voltage value. Id II Figure 2.2 4.5 Cell temp. = 25 °C Pm = I m * V m Voc 4.0 Incid. irrad. = 1000 W/m2 GI ISC 59.9 W 3.5 3.0 Im P=I*V 2.5 Current [A] 2.0 The no-load voltage Voc occurs when the load does not 1.5 absorb any current (I=0) and is given by the relation: 1.0 II 0.5 Vm Voc = [2.1] GI 0.0 0 5 10 15 20 VOC 25 Voltage [V] The diode current is given by the classic formula for the direct current: Therefore, the characteristic data of a solar module can Q.V oc [2.2] be summarized as follows: . . Id = ID . e A k T -1 • Isc short-circuit current; • Voc no-load voltage; where: • Pm maximum produced power under standard condi- • ID is the saturation current of the diode; tions (STC); • Q is the charge of the electron (1.6 . 10-19 C) • Im current produced at the maximum power point; • A is the identity factor of the diode and depends on • Vm voltage at the maximum power point; the recombination factors inside the diode itself (for • FF filling factor: it is a parameter which determines the crystalline silicon is about 2) form of the characteristic curve V-I and it is the ratio J between the maximum power and the product • k is the Boltzmann constant (1.38 . 10-23 ) • T is the absolute temperature in K degree K (Voc . Isc ) of the no-load voltage multiplied by the short-circuit current. 18 Photovoltaic plants
  • 2. If a voltage is applied from the outside to a PV cell in The currents Ig and Ir, which come from the PV generator reverse direction with respect to standard operation, and the network respectively, converge in the node N of 2 Energy production the produced current remains constant and the power Figure 2.4 and the current Iu absorbed by the consumer is absorbed by the cell. When a certain value of inverse plant comes out from the node: voltage (“breakdown” voltage) is exceeded, the junction P-N is perforated, as it occurs in a diode, and the current Iu = Ig + Ir [2.4] reaches a high value thus damaging the cell. In absence of light, the generated current is null for reverse voltage Since the current on the load is also the ratio between up to the “breakdown” voltage, then there is a discharge the network voltage U and the load resistance Ru: current similarly to the lightening conditions (Figure 2.3 – left quadrant). U Iu = [2.5] Figure 2.3 Ru Current [A] the relation among the currents becomes: Current [A] U Ir = - Ig [2.6] Ru If in the [2.6] we put Ig = 0, as it occurs during the night hours, the current absorbed from the grid results: U Ir = [2.7] Voltage [V] Ru Vinv 0 Voc On the contrary, if all the current generated by the PV plant is absorbed by the consumer plant, the current supplied by the grid shall be null and consequently the 2.3 Grid connection scheme formula [2.6] becomes: A PV plant connected to the grid and supplying a con- U Ig = [2.8] sumer plant can be represented in a simplified way by Ru the scheme of Figure 2.4. The supply network (assumed to be at infinite short-cir- cuit power) is schematized by means of an ideal voltage When the insolation increases, if the generated current generator the value of which is independent of the load Ig becomes higher then that required by the load Iu, the conditions of the consumer plant. On the contrary, the current Ir becomes negative, that is no more drawn from PV generator is represented by an ideal current generator the grid but put into it. (with constant current and equal insolation) whereas the Multiplying the terms of the [2.4] by the network voltage consumer plant by a resistance Ru. U, the previous considerations can be made also for the powers, assuming as: U2 • Pu = U . Iu = the power absorbed by the user plant; Figure 2.4 Ru Ig Ir N • Pg = U . Ig the power generated by the PV plant; Iu • Pr = U . Ir the power delivered by the grid. PV generator U Network RU Photovoltaic plants 19
  • 3. Technical Application Papers 2.4 Nominal peak power Remarkable values of AM are (Figure 2.6): AM = 0 outside the atmosphere where P = 0; 2 Energy production The nominal peak power (kWp) is the electric power AM = 1 at sea level in a day with clear sky and the sun that a PV plant is able to deliver under standard testing at the zenith (P = Po, sen(h) = 1); conditions (STC): AM = 2 at sea level in a beautiful day with the sun at 30° • 1 kW/m2 insolation perpendicular to the panels; 1 angle above the horizon (P = Po, sen(h) = ). • 25°C temperature in the cells; 2 • air mass (AM) equal to 1.5. Figure 2.6 The air mass influences the PV energy production since it represents an index of the trend of the power spectral density of solar radiation. As a matter of fact the latter Upper limit of the absorbing atmosphere has a spectrum with a characteristic W/m2-wavelength which varies also as a function of the air density. In the AM = AM1 = 0 diagram of Figure 2.5 the red surface represents the radiation perpendicular to the Earth surface absorbed ) n(h by the atmosphere whereas the blue surface represents /se AM = AM1 = 1 =1 the solar radiation which really reaches the Earth surface; AM Zenith angle surface h the difference between the trend of the two curves gives Local horizon and indication of the spectrum variation due to the air m 0k mass1. 10 Figure 2.5 [W/m2] Earth surface 1800 Power spectral density 1350 [W/m2] (AM0) 1200 2.5 Expected energy production per year 2 1000 [W/m ] (AM1) From an energetic point of view, the design principle 800 usually adopted for a PV generator is maximizing the Radiation visible to the naked eye pick up of the available annual solar radiation. In some cases (e.g. stand-alone PV plants) the design criterion 400 could be optimizing the energy production over definite periods of the year. The electric power that a PV installation can produce in 0 a year depends above all on: 0.3 0.5 1.0 1.5 2.0 2.5 Wavelength • availability of the solar radiation; • orientation and inclination of the modules; The air mass index AM is calculated as follows: • efficiency of the PV installation. P Since solar radiation is variable in time, to determine the AM = [2.9] electric energy which the plant can produce in a fixed Posen (h) time interval, the solar radiation relevant to that interval where: is taken into consideration, assuming that the perform- P is the atmospheric pressure measured at the point ances of the modules are proportional to insolation. and instant considered [Pa]; The values of the average solar radiation in Italy can be Po is the reference atmospheric pressure at the sea level deduced from: [1.013 . 105 Pa]; • the Std. UNI 10349: heating and cooling of the build- h is the zenith angle, i.e. the elevation angle of the Sun ings. Climatic data; above the local horizon at the instant considered. • the European Solar Atlas based on the data registered by the CNR-IFA (Institute of Atmospheric Physics) in the period 1966-1975. It reports isoradiation maps of the 1 The holes in the insolation correspond to the frequencies of the solar radiation absorbed by the water vapor present in the atmosphere. Italian and European territory on horizontal or inclined surface; 20 Photovoltaic plants
  • 4. • the ENEA data bank: since 1994 ENEA collects the data where: of the solar radiation in Italy through the imagines of hBOS (Balance Of System) is the overall efficiency of all the 2 Energy production the Meteosat satellite. The maps obtained up to now components of the PV plants on the load side of the pan- have been collected in two publications: one relevant els (inverter, connections, losses due to the temperature to the year 1994 and another one relevant to the period effect, losses due to dissymetries in the performances, losses due to shading and low solar radiation, losses 1995-1999. due to reflection…). Such efficiency, in a plant properly designed and installed, may range from 0.75 to 0.85. The Tables 2.1 and 2.2 represent respectively, for differ- ent Italian sites, the values of the average annual solar Instead, taking into consideration the average daily in- radiation on the horizontal plane [kWh/m2] from the Std. solation Emg, to calculate the expected produced energy UNI 10349 and mean daily values month by month [kWh/ per year for each kWp: m2/day] from ENEA source. The annual solar radiation for a given site may vary from a source to the other also by 10%, since it derives from Ep = Emg . 365 . hBOS [kWh/kWp] [2.11] the statistical processing of data gathered over different Example 2.1 periods; moreover, these data are subject to the variation We want to determine the annual mean power produced of the weather conditions from one year to the other. As by a 3kWp PV plant, on a horizontal plane, in Bergamo. a consequence the insolation values have a probabilistic The efficiency of the plant components is equal to meaning, that is they represent an expected value, not 0.75. a definite one. From the Table in the Std. UNI 10349, an annual mean Starting from the mean annual radiation Ema, to obtain radiation of 1276 kWh/m2 is obtained. Assuming to be the expected produced energy per year Ep for each kWp under the standard conditions of 1 kW/m2, the expected the following formula is applied: annual mean production obtained is equal to: Ep = Ema . hBOS [kWh/kWp] [2.10] Ep = 3 . 1276 . 0.75 = 3062 kWh Table 2.1 Annual solar radiation on the horizontal plane - UNI 10349 Annual solar Annual solar Annual solar Annual solar Annual solar Site radiation Site radiation Site radiation Site radiation Site radiation (kWh/m2) (kWh/m2) (kWh/m2) (kWh/m2) (kWh/m2) Agrigento 1923 Caltanisetta 1831 Lecce 1639 Pordenone 1291 Savona 1384 Alessandria 1275 Cuneo 1210 Livorno 1511 Prato 1350 Taranto 1681 Ancona 1471 Como 1252 Latina 1673 Parma 1470 Teramo 1487 Aosta 1274 Cremona 1347 Lucca 1415 Pistoia 1308 Trento 1423 Ascoli Piceno 1471 Cosenza 1852 Macerata 1499 Pesaro-Urbino 1411 Torino 1339 L’Aquila 1381 Catania 1829 Messina 1730 Pavia 1316 Trapani 1867 Arezzo 1329 Catanzaro 1663 Milan 1307 Potenza 1545 Terni 1409 Asti 1300 Enna 1850 Mantova 1316 Ravenna 1411 Trieste 1325 Avellino 1559 Ferrara 1368 Modena 1405 Reggio Calabria 1751 Treviso 1385 Bari 1734 Foggia 1630 Massa Carrara 1436 Reggio Emilia 1427 Udine 1272 Bergamo 1275 Florence 1475 Matera 1584 Ragusa 1833 Varese 1287 Belluno 1272 Forlì 1489 Naples 1645 Rieti 1366 Verbania 1326 Benevento 1510 Frosinone 1545 Novara 1327 Rome 1612 Vercelli 1327 Bologna 1420 Genoa 1425 Nuoro 1655 Rimini 1455 Venice 1473 Brindisi 1668 Gorizia 1326 Oristano 1654 Rovigo 1415 Vicenza 1315 Brescia 1371 Grosseto 1570 Palermo 1784 Salerno 1419 Verona 1267 Bolzano 1329 Imperia 1544 Piacenza 1400 Siena 1400 Viterbo 1468 Cagliari 1635 Isernia 1464 Padova 1266 Sondrio 1442 Campobasso 1597 Crotone 1679 Pescara 1535 La Spezia 1452 Caserta 1678 Lecco 1271 Perugia 1463 Siracusa 1870 Chieti 1561 Lodi 1311 Pisa 1499 Sassari 1669 Table 2.2 Site January February March April May June July August September October November December Milan 1.44 2.25 3.78 4.81 5.67 6.28 6.31 5.36 3.97 2.67 1.64 1.19 Venice 1.42 2.25 3.67 4.72 5.75 6.31 6.36 5.39 4.08 2.72 1.64 1.14 Bologna 1.50 2.28 3.81 4.81 5.86 6.42 6.47 5.47 4.19 2.81 1.72 1.25 Florence 1.58 2.33 3.75 4.72 5.86 6.39 6.44 5.50 4.17 2.86 1.83 1.39 Rome 1.92 2.61 3.94 4.92 6.08 6.56 6.58 5.72 4.39 3.17 2.11 1.58 Naples 1.92 2.67 3.92 5.03 6.08 6.64 6.58 5.81 4.50 3.28 2.17 1.69 Bari 1.86 2.58 3.97 5.08 6.08 6.69 6.64 5.81 4.53 3.25 2.08 1.69 Messina 2.11 2.94 4.19 5.19 6.22 6.69 6.67 5.89 4.64 3.53 2.36 1.94 Siracusa 2.36 3.22 4.33 5.39 6.36 6.78 6.75 6.00 4.81 3.69 2.58 2.17 Photovoltaic plants 21
  • 5. Technical Application Papers 2.6 Inclination and orientation of the panels Finding the complementary angle of α (90°-α), it is pos- 2 Energy production sible to obtain the tilt angle β, of the panels with respect The maximum efficiency of a solar panel would be to the horizontal plane (IEC/TS 61836) so that the panels reached if the angle of incidence of solar rays were always are struck perpendicularly by the solar rays in the above 90°. In fact the incidence of solar radiation varies both mentioned moment2. according to latitude as well as to the solar declination However, it is not sufficient to know the angle α to deter- during the year. In fact, since the Earth’s rotation axis is mine the optimum orientation of the panels. It is neces- tilted by about 23.45° with respect to the plane of the sary to take into consideration also the Sun path through Earth orbit about the Sun, at definite latitude the height of the sky over the different periods of the year and therefore the Sun on the horizon varies daily. The Sun is positioned the tilt angle should be calculated taking into considera- at 90° angle of incidence with respect to the Earth surface tion all the days of the year3 (Figure 2.8). This allows to (Zenith) at the equator in the two days of the equinox and obtain an annual total radiation captured by the panels along the tropics at the solstices (Figure 2.7). (and therefore the annual energy production) higher than that obtained under the previous irradiance condition perpendicular to the panels during the solstice. Figure 2.7 Figure 2.8 N solar path at 45ϒ North latitude 'a1 Summer solstice at the Tropic of Cancer 12 11 21st or 22nd June ° 10 , 45 Vernal equinox +23 0° 20th or 21st March 9 12 Solar height -23 Autumnal equinox 11 , 45 ° 22nd or 23rd September 10 8 Winter solstice at the 9 21 7 Tropic of Capricorn Ju 11 12 ne 22nd or 23rd December 8 21 6 10 W Ma E 9 21 S E rch 7 A De S 8 S ce 6 m T T be 0ϒ r Outside the Tropics latitude, the Sun cannot reach the Zenith above the Earth’s surface, but it shall be at its The fixed panels should be oriented as much as possible highest point (depending on the latitude) with reference to south in the northern hemisphere4 so as to get a better to the summer solstice day in the northern hemisphere insolation of the panel surface at noon local hour and a and in the winter solstice day in the southern hemisphere. better global daily insolation of the panels. Therefore, if we wish to incline the panels so that they The orientation of the panels may be indicated with the can be struck perpendicularly by the solar rays at noon Azimuth5 angle (γ) of deviation with respect to the opti- of the longest day of the year it is necessary to know mum direction to south (for the locations in the northern the maximum height (in degrees) which the Sun reaches hemisphere) or to north (for the locations in the southern above the horizon in that instant, obtained by the follow- hemisphere). ing formula: a = 90° - lat + d [2.12] where: 2 On gabled roofs the tilt angle is determined by the inclination of the roof itself. lat is the value (in degrees) of latitude of the installation 3 In Italy the optimum tilted angle is about 30°. 4 Since the solar irradiance is maximum at noon, the collector surface must be oriented site of the panels; to south as much as possible. On the contrary, in the southern hemisphere, the optimum orientation is obviously to north. d is the angle of solar declination [23.45°] 5 In astronomy the Azimuth angle is defined as the angular distance along the horizon, measured from north (0°) to east, of the point of intersection of the vertical circle passing through the object. 22 Photovoltaic plants
  • 6. Positive values of the Azimuth angles show an orienta- A non–horizontal panel receives, besides direct and dif- tion to west, whereas negative values an orientation to fuse radiation, also the radiation reflected by the surface 2 Energy production east (IEC 61194). surrounding it (albedo component). Usually an albedo As regards ground-mounted panels, the combination coefficient of 0.2 is assumed. of inclination and orientation determines the exposition For a first evaluation of the annual production capability of the panels themselves (Figure 2.9). On the contrary, of electric power of a PV installation it is usually sufficient when the panels are installed on the roofs of buildings, to apply to the annual mean radiation on the horizontal the exposition is determined by the inclination and the plan (Tables 2.1-2.2) the correction coefficients of the orientation of the roof pitches. Good results are obtained Tables 2.3, 2.4 and 2.56. through collectors oriented to south-east or to south- 6 Albedo assumed equal to 0.2. west with a deviation with respect to the south up to 45° Table 2.3 – Northern Italy: 44°N latitude (Figure 2.10). Greater deviations can be compensated by Orientation means of a slight enlargement of the collector surface. 0° ± 90° Inclination (south) ± 15° ± 30° ± 45° (east; west) Figure 2.9 0° 1.00 1.00 1.00 1.00 1.00 10° 1.07 1.06 1.06 1.04 0.99 15° 1.09 1.09 1.07 1.06 0.98 β 20° 1.11 1.10 1.09 1.07 0.96 30° 1.13 1.12 1.10 1.07 0.93 40° 1.12 1.11 1.09 1.05 0.89 50° 1.09 1.08 1.05 1.02 0.83 60° 1.03 0.99 0.96 0.93 0.77 70° 0.95 0.95 0.93 0.89 0.71 90° 0.74 0.74 0.73 0.72 0.57 Table 2.4 - Central Italy: 41°N latitude Orientation γ 0° ± 90° Inclination (south) ± 15° ± 30° ± 45° (east; west) 0° 1.00 1.00 1.00 1.00 1.00 SOUTH 10° 1.07 1.07 1.06 1.04 0.99 15° 1.09 1.09 1.08 1.06 0.97 Figure 2.10 20° 1.11 1.11 1.09 1.07 0.96 30° 1.13 1.12 1.10 1.07 0.92 40° 1.12 1.12 1.09 1.05 0.87 -170ϒ North +170ϒ 0ϒ +16 50° 1.09 1.08 1.05 1.01 0.82 0ϒ -16 +1 60° 1.03 1.02 0.99 0.96 0.76 0ϒ -15 50 ϒ 70° 0.94 0.94 0.92 0.88 0.70 +1 40 ϒ +1 40 ϒ -1 30 30 90° 0.72 0.72 0.71 0.70 0.56 ϒ ϒ -1 +1 0ϒ 20 ϒ -12 Table 2.5 - Southern Italy: 38°N latitude +11 0ϒ Orientation 0ϒ -11 0° ± 90° +100ϒ -100ϒ Inclination (south) ± 15° ± 30° ± 45° (east; west) 0° 1.00 1.00 1.00 1.00 1.00 West 10ϒ20ϒ30ϒ40ϒ50ϒ60ϒ70ϒ80ϒ90ϒ East 10° 1.06 1.06 1.05 1.04 0.99 -80ϒ 15° 1.08 1.08 1.07 1.05 0.97 +80ϒ 20° 1.10 1.09 1.08 1.06 0.96 ϒ -70 30° 1.11 1.10 1.08 1.06 0.92 +70 ϒ 40° 1.10 1.09 1.07 1.03 0.87 -60 0ϒ ϒ 50° 1.06 1.05 1.03 0.99 0.82 +6 -5 0ϒ 60° 0.99 0.99 0.96 0.93 0.75 0ϒ +5 70° 0.91 0.91 0.88 0.86 0.69 -4 0ϒ 90° 0.68 0.68 0.68 0.67 0.55 0ϒ +4 -30 0ϒ -20 ϒ +3 -10ϒ ϒ +10ϒ +20 South Example 2.2 ϒ We wish to determine the annual mean energy produced by the PV installation of the previous example, now ar- Annual insolation in % ranged with +15° orientation and 30° inclination. 30 40 50 60 70 40 80 90 100 From Table 2.3 an increasing coefficient equal to 1.12 is obtained. Multiplying this coefficient by the energy Tilt angle expected on horizontal plan obtained in the previous 10ϒ 20ϒ 30ϒ 40ϒ 50ϒ 60ϒ 70ϒ 80ϒ 90ϒ example, the expected production capability becomes: : Example: 30ϒ'a1; 45ϒ south-west; ⊕ 95% 'a1 'c E = 1.12 . Ep = 1.12 . 3062 ≈ 3430 kWh Photovoltaic plants 23
  • 7. Technical Application Papers 2.7 Voltages and currents in a PV plant 2.8 Variation in the produced energy 2 Energy production PV modules generate a current from 4 to 10A at a volt- The main factors which influence the electric energy age from 30 to 40V. produced by a PV installation are: To get the projected peak power, the panels are electri- • irradiance cally connected in series to form the strings, which are • temperature of the modules connected in parallel. The trend is developing strings • shading. constituted by as many panels as possible, given the complexity and cost of wiring, in particular of the paral- 2.8.1 Irradiance leling switchboards between the strings. As a function of the irradiance incident on the PV cells, The maximum number of panels which can be connected the characteristic curve V-I of them changes as shown in series (and therefore the highest reachable voltage) in Figure 2.11. to form a string is determined by the operation range of When the irradiance decreases, the generated PV cur- the inverter (see Chapter 3) and by the availability of the rent decreases proportionally, whereas the variation of disconnection and protection devices suitable for the the no-load voltage is very small. voltage reached. In particular, the voltage of the inverter is bound, due to As a matter of fact, the conversion efficiency is not reasons of efficiency, to its power: generally, when using influenced by the variation of the irradiance within the inverter with power lower than 10 kW, the voltage range standard operation range of the cells, which means that most commonly used is from 250V to 750V, whereas if the conversion efficiency is the same both in a clear as the power of the inverter exceeds 10 kW, the voltage well as in a cloudy day. range usually is from 500V to 900V. Therefore the smaller power generated with cloudy sky is referable not to a drop of the efficiency but to a reduced generation of current because of lower solar irradiance. Figure 2.11 3.5 1000 W/m2 900 W/m2 800 W/m2 3 700 W/m2 600 W/m2 500 W/m2 2.5 2 Current [A] 1.5 1 0.5 0 0 2 4 6 8 10 12 14 16 18 20 22 Voltage [V] 24 Photovoltaic plants
  • 8. 2.8.2 Temperature of the modules 2.8.3 Shading 2 Energy production Contrary to the previous case, when the temperature of Taking into consideration the area occupied by the mod- the modules increases, the produced current remains ules of a PV plant, part of them (one or more cells) may practically unchanged, whereas the voltage decreases be shaded by trees, fallen leaves, chimneys, clouds or and with it there is a reduction in the performances of by PV panels installed nearby. the panels in terms of produced electric power (Figure In case of shading, a PV cell consisting in a junction 2.12). P-N stops producing energy and becomes a passive load. This cell behaves as a diode which blocks the Figure 2.12 current produced by the other cells connected in series 3 thus jeopardizing the whole production of the module. E = 1000 W/m2 Moreover the diode is subject to the voltage of the other cells which may cause the perforation of the junction due to localized overheating (hot spot) and damages to 2 20 the module. 40 In order to avoid that one or more shaded cells thwart the 60 production of a whole string, some diodes which by-pass 80 the shaded or damaged part of module are inserted at 1 100 the module level. Thus the functioning of the module is guaranteed even if with reduced efficiency. In theory it would be necessary to insert a by-pass diode in parallel Voltage to each single cell, but this would be too onerous for the 0 0.2 0.4 0.6 ratio costs/benefits. Therefore 2÷4 by-pass diodes are usually installed for each module (Figure 2.13). The variation in the no-load voltage Voc of a PV mod- ule with respect to the standard conditions Voc,stc, as a function of the operating temperature of the cells Tcell, is expressed by the following formula (Guidelines CEI 82-25, II ed.): Figure 2.13 By-pass diode Voc(T) = Voc,stc - NS . b . (25-Tcel) [2.13] where: β is the variation coefficient of the voltage according to temperature and depends on the typology of PV module (usually -2.2 mV/°C/cell for crystalline silicon modules and about -1.5 ÷ -1.8 mV/°C/cell for thin film modules); Solar radiation Ns is the number of cells in series in the module. Therefore, to avoid an excessive reduction in the perform- ances, it is opportune to keep under control the service Shadow temperature trying to give the panels good ventilation to limit the temperature variation on them. In this way it is possible to reduce the loss of energy owing to the + – temperature (in comparison with the temperature of 25°C under standard conditions) to a value around 7%7. I I 7 The reduction in efficiency when the temperature increases can be estimated as 0.4 to 0.6 for each °C. Photovoltaic plants 25