SlideShare a Scribd company logo
DC Supply
System &
Batteries
Manoj Barsaiyan
DGM, PMI
Battery Is Considered To Be The “HEART” Of
The Power Plant
 Battery provides the ultimate and
final DC back-up for emergency oil
pumps and other emergency
equipment.
 DC power for operation of all
switchgear protection and relays.
 Power for emergency lighting
within the generating station
building.
 Uninterrupted power for C & I
equipment and the ups systems.
 Power for vital communication
equipment (PLCC), essential for re-
synchronizing the unit with the grid
or for reviving the grid in the case
of a major grid failure.
What If The Battery Fails In An Emergency
 Unit Battery
 The emergency oil pump will not
operate which may lead to seizure of
the rotor bearings
 Loss of hundreds of crore of rupees
towards repairing the rotor and
generation revenue loss while the unit
is out of service.
 Switchgear associated with generator
may not trip which could lead to
generating transformer damage
 Failure of instrumentation and control
 Total darkness in the powerhouse
What If The Battery Fails In An Emergency
(contd.)
 Substation
 Switchgear and relays will not operate
causing extensive damage to
transformers and power lines
 PLCC
 Extremely difficult to resynchronize the
unit with the grid
 Major setback in the process of reviving
the grid in the event of a regional grid
failure
 If the battery fails while the unit is in
operation, it may become essential to
shutdown
DC SYSTEM IS
DESIGNED
• TO SUPPLY HIGH STANDARD OF RELIABLE &
SECURE DC POWER
• TO PROVIDE CONTINUOUS & QUALITY
POWER AS AND WHEN REQUIRED
• UNDER NORMAL & ABNORMAL OPERATING
CONDITIONS
• ULTIMATE & FINAL DC BACK-UP POWER TO
EQUIPMENT AND DC DRIVES WHEN TOTAL AC
SUPPLY FAILS
• HENCE THEY ARE BATTERY BACKED
DUTIES
• TO SUPPLY EQUIPMENT WHICH REQUIRES DC
DURING NORMAL CONDITIONS
• TO SUPPLY STANDBY EQUIPMENT/DC DRIVES
• TO SUPPLY STARTERS OF VARIOUS
EQUIPMENT
• TO SUPPLY EQUIPMENT WHEN AC SUPPLIES
HAVE BEEN LOST
Types of Power Supplies
In a Power Plant
• 11KV/3.3KV/415V AC Power Supply
• 415V AC Emergency Supply(DG)
• DC Power Supply
• UPS Supply
DC Power Supply
• Various Critical Drives
• Emergency DC Lighting
• Switchgear Control Supply for closing & tripping
• Control, Protection And Interlocks
• Indication, Annunciation & Alarm System
• Public Address System
• DAS And Communication System
DC Supplies……………Why?
• Emergency Lube Oil Pump
• Emergency Jacking Oil Pump
• Emergency Scanner Air Fan
• Emergency Seal Oil Pump
• Breaker/Unit Protections
• Emergency Lighting
The Ultimate Backup
In case of unit tripping / grid failure, either station
changeover takes place / DG would start.
Normally, grid supply would be restored in minimum
possible time and DG would shut down.
In case of DG failure, the DC backup comes in to
service to facilitate safe shut down.
Selection of voltage
DC POWER SUPPLY
• In power plant D.C. pumps, lighting require comparatively
high voltage due to their high power requirement. Hence as
a standard these applications are designed with 220V level.
• It is desirable to have comparatively lower voltage-
24V/48V/110V for control/indications/annunciation due to
safety reasons. However to avoid multiplicity of DC supplies
(particularly we require two control supplies), we have
adopted uniform 220V DC voltage for plant electrical
systems for switchgear control, protection and interlock
operation.
DC POWER SUPPLY
SCHEME
1. Earlier concept;
• 1X100% battery bank along with its chargers for each unit with inter-
unit interconnection through high capacity DC bus bar.
• In view of large size of above DC loads of each unit and the large unit
pitch it is necessary to provide a separate DC system (battery
+chargers) to enhance the plant’s overall reliability.
2) Present concept;
• In view of the reasons explained above 2x100% capacity DC system is
provided for each unit and switchyard separately.
• Minor DC loads of offsite areas in the plant i.e. WTP, Ash handling are
fed from plant DC system as it is now restricted to limited area
switchgear rooms, as control now no longer relay based.
The Single Most Important Feature Of Storage
Batteries For Power Sector and Other Critical
Standby Application Is
Reliability
 Reliable standby power source
 Deliver power as and when called for
 Full capacity at any point of time in service life
 Predictability
EITHER
SUDDEN DISRUPTION OF MAINS POWER TAKES PLACE
OR
CONVENIENT AVAILABILITY OF MAINS POWER IS NOT THERE
THIS CLEARLY DEFINES TWO REGIMES OF APPLICATION
STANDBY APPLICATION
CYCLIC APPLICATION
UPS, INVERTERS, TELEPHONE
EXCHANGES, POWER STATIONS,
SWITCHING
CELL PHONES, TOYS, FORK
LIFTS, ELECTRIC VEHICLES,
SOLAR PHOTOVOLTAICS
STORAGE BATTERY
WHEN ?
STORAGE BATTERY FUNDAMENTAL
An ELECTRICAL STORAGE CELL consists of two dissimilar electrodes immersed
in electrolyte. Stores Electrical Energy in the form of Chemical Energy.
When the circuit is made between its +ve & -ve electrodes, it triggers a chemical
reaction inside the cell & delivers electricity – Direct Current (D.C.) through the circuit.
CHEMICAL ENERGY ELECTRICAL ENERGY
Anode
Electrolyte
Cathode
A BATTERY is an array of similar/identical objects The
battery, we are talking about is an electrical storage
battery comprising of an array of electrical storage cells
STORAGE BATTERY FUNDAMENTAL
Battery
INDUSTRIAL
POWER
LEAD – ACID
NICKEL – CADMIUM
PORTABLE
POWER
LITHIUM ION
NICKEL – METAL HYDRIDE
NICKEL CADMIUM
HIGH END
APPLICATION –
TORPEDOES, SPACE
SILVER - ZINC
NICHE POWER
GENERATION
FUEL CELLS
Application Pattern:
LEAD ACID
NICKEL CADMIUM
General Battery Technologies
Most Popular Electrochemical Couples
used worldwide in Industrial Application
Types of Batteries
Lead Acid Nickel - Cadmium
Flat Plate
Tubular
Plante
VRLA
Pocket Plate
Tubular Plate
Sintered Plate
BASIC ELECTROCHEMISTRY
PbO2 + Pb + 2H2SO4 PbSO4 + PbSO4 + 2H2O
CHARGED DISCHARGED
ELECTROLYTE TAKES ACTIVE PART IN REACTION – SPECIFIC GRAVITY
CHANGES WITH STATE OF CHARGE – EASY MONITORING AND INDICATION
OF STATE OF CHARGE (SOC)
2NiOOH + 2H2O + Cd 2Ni(OH)2 + Cd(OH)2
NEG. NEG.
POS POS
DISCHARGED
CHARGED
ELECTROLYTE DOES NOT TAKE ACTIVE PART IN REACTION – SPECIFIC
GRAVITY DOES NOT CHANGE WITH STATE OF CHARGE – NO DIRECT &
EASY METHOD OF MEASURING STATE OF CHARGE
NEG. NEG.
POS POS
LEAD ACID
NICKEL CADMIUM
More than 90% of applications world-wide use
Lead-acid
Reasons:
 LOW COST
 APPLICATION VERSATILITY
 ABUNDANT RAW MATERIAL
 WELL DEVELOPED SERVICING RECYCLING
INFRASTRUCTURE
Advantage “Lead Acid”
Technology Wise Categorisation
Industrial Lead Acid Battery
FLOODED VRLA
FLAT TUBULAR PLANTE
The Lead-Acid Technology
LEAD ACID BATTERY AN OVERVIEW
ACTIVE
MATERIAL
TAKES ACTIVE PART IN
REACTION TO STORE &
SUPPLY ENERGY
SUPPORT
STRUCTURE
ENABLES ELECTRONIC
CONDUCTION
1
2
PROVIDES MECHANICAL
SUPPORT TO ACTIVE
MATERIAL
ACTIVE MATERIAL
SUPPORT STRUCTURE
PLATES ARE
CONSTITUTED
OF
FLAT PASTED POSITIVE AND NEGATIVE
FLAT PLATE
A CHEMICAL BONDING HOLDS THE ACTIVE
MATERIAL IN PLACE THROUGHOUT THE
SERVICE LIFE
WIRE-MESH LIKE SUPPORT
STRUCTURE – GRID CAST OF LEAD
ALLOY, ANTIMONY OR CALCIUM
ACTIVE MATERIAL
PASTED ON GRID -
EXTERNALLY
FLAT POSITIVE PLATE
MOST SUITABLE FOR HIGH CURRENT, SHORT DURATION
APPLICATION viz. SLI, SHALLOW DUTY INVERTER ETC.
ADVANTAGES
MINIMUM LEAD MOST ECONOMIC & HIGHEST
ENERGY DENSITY
EXCELLENT HIGH RATE
DISCHARGE PERFORMANCE
AND CHARGE ACCEPTANCE
LARGE ACTIVE
SURFACE AREA
LIMITATIONS
ACTIVE MATERIAL
SHEDDING
LIMITED CYCLING
CAPABILITY
EASY ACCESS OF
ACID TO LEAD GRID
EASY CORROSION – LOW
LIFE EXPECTANCY
THE SUPPORT STRUCTURE IS IN THE
FORM OF CAST ROD ELECTRODES
CALLED SPINES JOINED AT THE TOP BY
A BUS BAR. ALLOY USED IS MOSTLY
ANTIMONIAL LEAD.
INDIVIDUAL SPINES ENGULFED IN A
MICROPOROUS PLURITUBULAR
GAUNTLET
ANNULAR SPACE BETWEEN SPINE AND
GAUNTLET FILLED WITH ACTIVE
MATERIAL. BOTTOM OF THE GAUNTLET
SEALED WITH A PLASTIC PLUG CALLED
BOTTOM BAR
TUBULAR POSITIVE PLATE
 Active material is held around the spines with the help of polyester tubes called
gauntlet.
 Annular space between the spine & gauntlet is filled with active
material.
Spine
Gauntlet
Active Material
Plastic Bottom Bar
A
A’
B B’
Gauntlet
Active
Material
Spine
Section A A’
Section B B’
TUBULAR POSITIVE PLATE
Lead Top Bar
EXTENDED SERVICE LIFE. IT IS DESIGNED FOR DEEP CYCLING
LOOSE PACKING OF
ACTIVE MATERIAL
POSSIBLE
ADVANTAGES
NO ACTIVE MATERIAL
SHEDDING
BEST SUITED FOR
CYCLING – 1500 CYCLES
@ 80% DOD
SPINE DEEPLY
EMBEDDED IN ACTIVE
MATERIAL – LOW SPINE
CORROSION
EXTREME TEMPERATURE
OPERATION
RESISTANT TO OVER-
CHARGE
RECOVERY FROM DEEP
DISCHARGE
PSOC OPERATION
TUBULAR POSITIVE PLATE WHY ?
MODEST HIGH RATE DISCHARGE
PERFORMANCE.
REQUIRES PERIODIC EQUALIZING AND/OR
BOOST CHARGING
REQUIRES PERIODIC TOPPING UP
“ANTIMONY POISONING” LEADS TO SLOWLY
DECLINING VOLTAGE PROFILE AND
INCREASING WATER LOSS AS THE BATTERY
AGES.
TUBULAR POSITIVE PLATE WHY NOT ?
LIMITATIONS
CAST OF 99.99%
PURE LEAD
LAMELLAR GRID
STRUCTURE –
ENHANCED ACTIVE
SURFACE AREA
INTEGRAL GRID
ACTIVE MATERIAL
PLANTE
PLANTE POSITIVE PLATE
CAST OF 99.99%
PURE LEAD
LAMELLAR GRID
STRUCTURE –
ENHANCED ACTIVE
SURFACE AREA
INTEGRAL GRID
ACTIVE MATERIAL
PLANTE
Lug
Support Bar
Lamellar Surface
PLANTE POSITIVE PLATE
POSITIVE PLATE HANGING FROM
CONTAINER SHOULDER
GAP BETWEEN POSITIVE PLATE
BOTTOM & MUD RIB FOR CREEP
GROWTH ALLOWANCE
POSITIVE PLATE
HANGING FROM
CONTAINER SHOULDER
TO PROVIDE SPACE FOR
CREEP GROWTH
INEVITABLE TO PURE
LEAD POSITIVE
PLANTE
HANGING PLATE DESIGN
1. In case of loss of active material due to
shedding, next layer of pure lead is converted to
lead-dioxide thereby ensuring no loss of
capacity – feature of continuous regeneration of
active material.
1. Across its life time Plante cells therefore
perform at full capacity – there is no aging
unlike all other lead-acid products.
1. No aging factor required for capacity calculation
Integral Grid-Active Material
Plante
CONTINUOUS REGENERATION OF ACTIVE MATERIAL
PLANTE NO LOSS IN CAPACITY
TOTAL LEAD-DI-OXIDE CONTENT FAIRLY
CONSTANT THROUGHOUT THE LIFE
SPAN INDICATING A CONSTANT
CAPACITY OUTPUT
CAPACITY DEGRADATION OVER LIFE AGEING FACTOR
TUBULAR : 20% 1.25
VRLA : 20% 1.25
Ni-Cd : 20% 1.25
PLANTE : ZERO 1.00
HIGH SURFACE AREA
HIGH CHARGING RATES POSSIBLE.
CHARGING AT 0.25 C10 AMPS UPTO
2.4 VOLTS PER CELL WITHOUT
PROBLEM
NO ANTIMONY POISONING
HIGH FLOAT POTENTIAL POSSIBLE.
PLANTE FAST RECHARGE
LIFE EXPECTANCY OF 18 TO 20 YEARS PLUS.
PLANTE LONG LIFE
VERY THICK POSITIVE – ENOUGH CUSHION AGAINST
CORROSSION
LOW SUSCEPTIBILITY TO OVERCHARGE DUE TO
VERY LOW EQUILIBRIUM FLOAT CURRENT OF THE
ORDER OF 1 mA/AH UNDER NORMAL FLOAT
CONDITION
LOW FLOAT CURRENT AND HIGH PURITY OF LEAD
LOWERS THE CORROSSION RATE
RELIABILITY - REITERATED
PLANTE EASY MONITORING
TRANSPARENT SAN (STYRENE ACRYLONITRILE)
CONTAINER – EASY VISUAL MONITORING OF CELL INSIDE
ANY ODD BEHAVIOUR CAN BE MONITORED AND
CORRECTED MUCH BEFORE IT SHOWS UP AS A
FAILURE MODE
EASY CLEANING OF CELLS FROM UNAVODABLE
SLUDGE DEPOSITION TO AVOID SHORT CIRCUIT
AND RELATED TROUBLES
SEALED ! CAN BE KEPT IN ANY ORIENTATION.
NO TOPPING-UP REQUIRED EVER “MAINTENANCE-FREE”.
A ZERO EMISSION PRODUCT.
BATTERY COMES CHARGED.
COMPACT.
WHAT IS VRLA ?
1. No topping up ever
2. No emission of fumes
3. Supplied factory charged
4. Excellent ‘high rate discharge’ performance
5. Excellent charge acceptance
6. Excellent deep cycle life
7. Low Self-discharge
8. Designed to suit float and moderate cyclic duty
9. Compact – low foot print
10. Long Life
Advantage VRLA
VRLA
CONSTRUCTION OF A VALVE REGULATED LEAD ACID CELL
AGM Separator
PbO2 Positive Plate
Pb Negative Plate
1. No means of state-of-charge assessment
1. Vulnerable to prolonged operation at high
temperature
1. Sensitive to both under and over charge
1. Recovery from over discharged condition is
difficult
1. Can have a catastrophic failure in case of charger
malfunction and/or abnormally high
temperature operation – a failure mode known
as ‘thermal runaway’
VRLA Limitations
VRLA
The VRLA Mechanism
Some fundamental requirements of a VRLA
1. Absence of free electrolyte – this can be done by two
process
a. Gel b. AGM
2. Entire element is held under tight compression
Under the above circumstance an oxygen bubble
evolved at the positive electrode diffuses to negative
electrode to react with the freshly formed pure lead
as follows:
O2 + Pb  (PbO) + SO4 + H+  PbSO4 + H2O
This is unique to VRLA – PbSO4 forms on the negative
electrode both on discharge as well as on charge!
The Lead Acid VRLA ….contd
The preceding analysis explains the limitations of a VRLA:
The recharge voltage and/or operating temperature
has to be carefully regulated since a higher voltage or
the higher temperature will raise the potential of both
positive and negative electrodes leading to:
- Excessive recombination, rise in temperature, loss of
water, so far as oxygen is concerned
- As far as hydrogen is concerned there is no recombination
reaction for it thereby resulting in net loss of the gas and in
effect water i.e. accelerated aging shall take place.
- In effect, VRLAs charge ‘slow’ at float voltage only.
A note on “Gel” tubular VRLA
Gel tubular VRLA share most of the advantage features of
AGM VRLA except for:
a. High Rate Performance is modest
b. Charge acceptance is lower
c. Compatibility to fast charging is poor
d. Uses more lead, hence more bulky and expensive
On the positive side, Gel products are less affected by high
temperature operation – basic electrolyte content being
higher vis-à-vis VRLA and hence also eliminates the
possibility of catastrophic failure due to ‘thermal runaway’
Factors that limit the life of a lead-acid battery (conventional)
• Positive Grid/Spine Corrosion
• Degradation of Positive/Negative Active Material
• Corrosion of positive pillars, group bar
• Mechanical degradation of cover/lid leading to leakage etc.
• Internal shorts due to separator degradation
• Internal shorts due to excessive sedimentation
• Internal short/terminal damage due to plate growth
Factors that lead to ‘Premature’ Battery Failure
• Wrong type selection
• Wrong sizing of battery
• Improper operation - over discharge
- under/over charging
• Improper maintenance – topping up
- equalization/boost
• Poor quality acid/water
INTRODUCTION TO Ni-Cd BATTERIES
Nickel Cadmium Technologies
 Pocket Plate
 Sintered Plate
 Fibre Plate
Technologies
Nickel-cadmium development
 Pocket Plate (PP) – 1st generation (1893)
• Industrial applications
 Sintered Plate (SP) – 2nd generation (1934)
• Aviation applications
 Fibre Plate (FP) – 3rd generation (1978)
• AGV, Rail & Industry applications
Technologies
Nickel-cadmium chemistry
 Positive active material : Nickel Hydroxide
 Negative active material : Cadmium Hydroxide
 Electrolyte : Potassium hydroxide
(KOH)
 Nominal voltage : 1.2 volts
2NiO-OH + 2H2O +Cd= 2Ni(OH)2+ Cd(OH)2
When the cell is charged, the active material initially present as
hydroxides are changed. On discharge, the process is reversed.
Pocket Plate Technology
Pocket Plate battery
Key features
 Proven technology
 Exceptional reliability and long lifetime
 Low internal resistance
 Wide operating temperature range
 Fast recharge capability
 Resistance to electrical and mechanical abuse
 Specific designs to applications
 Easy installation and low maintenance
 Environmentally safe
Pocket Plate battery
Key features : How?
 Do not suffer from sudden death failure
 Electrolyte does not participate in the electro-chemistry,
Its simply an ion carrier. No need to measure Sp. Gravity
in service
 All internal components are made with steel structure
 No component is affected by electrochemical reaction or
by electrolytic aging
Pocket Plate battery
Construction
Splash guard
Prevents electrolyte splashing and
possible short-circuit caused by
external objects accidentally falling
into the cell
Plate Groups
Welded construction imparts high
mechanical strength to withstand severe
vibrations
Plate
Made of Double perforated steel strips,
encompass the active materials
Fusion welded to lids, makes the cell
mechanically sturdy and facilitate visual
electrolyte level inspection
Translucent polypropylene
container
Nickel-plated terminal posts provide good
electrical conductivity
Prevents explosion & electrolyte
contamination
Polypropylene Grid Separator
Separates the plates and insulate the
frames from each other and allows free
electrolyte flow
Flame Arresting Vent
Terminal Arrangement
Pocket Plate battery
Operating features : Charge
 Ensures the readiness of battery in short time, after one
black out
 Flexible boost charge voltage 1.45 – 1.70V/cell
 Float voltage 1.40 – 1.42V/cell
 Discharge End voltage range from 1.14 – 0.65V/cell
 Tolerates deep discharges - can be deep cycled.
 Excellent low temperature discharge capability
 85% capacity available even at -20°C operation
Pocket Plate battery
Operating features : Lifetime
 Life of Ni-Cd batteries is more than 20 years under float
conditions with many number of industrial applications
 Cyclic life
 Excellent cyclic capability
Depth of Discharge Number of cycles
20% 8000
40% 3200
60% 2000
80% 1000
 Lesser the DOD, higher would be the cyclic life
Pocket Plate battery
Operating features : Installation
 A simple bolted connector assembly system
 Stepped arrangement for easy maintenance & electrolyte
visibility
 Various options for battery racks to fit into available room
space
 No need for special acid / alkali proof flooring
 Battery can be installed in the same room as other
electronic equipment
Pocket Plate battery
Operating features : Installation
2 Step – 2 tier
Pocket Plate battery
Operating features : Installation
4 Step – 1 tier
Pocket Plate battery
Operating features : Installation
3 Step – 2 tier
Pocket Plate battery
Low maintenance
 No need of measuring of specific gravity
 Large electrolyte reserve
 Air conditioned environment is not essential
 Natural ventilation is sufficient
 “Flip open” vent caps to simplify topping-up
 Long topping-up intervals
Pocket Plate battery
Environmentally safe
 No emission of corrosive gases
 Low emission of explosive gases
 Explosion proof vents
 Protection against accidental shorts
 More than 99% of metals contained in batteries can be
recycled
Comparison of Batteries
Tubular VRLA PLANTE NI-CD
1.Application Ideal for float as well
as frequent charge/deep
discharge cycling
duties
For relatively short
time backup with
moderate depth of
discharge
Ideal for meeting
duty cycle in float
operation
Better suited for very
high rate of discharge
under extreme
condition/cyclic duty.
2.Reliability Quite reliable Generally reliable,
however prone to
unexpected
malfunctioning
Most reliable in
float operations
Reliable during routine
duty cycles
3.Monitoring
state of
charge
Can be done by
measuring electrolyte
specific gravity
Cannot be determined
externally, acts as a
blackbox
Can be done by
measuring
electrolyte specific
gravity,visual
monitoring through
transparent
containers
Cannot be determined
externally, acts as a
blackbox
4.Susceptibili
ty to high
temperatures
Satisfactory operations
up to 48/50 deg. C
electrolyte
temperature,Best
among lead acid.
Prolonged operation
at high temperature
curtails battery life
Satisfactory
operations up to
48/50 deg. C
electrolyte
temperature
Satisfactory operations
up to 48/50 deg. C
electrolyte
temperature.Wide
temperature range
5.Discharge
performance
Standard, but inferior to
Plante
Best Superior to Tubular
but inferior to
VRLA
Very Good
Tubular VRLA PLANTE NI-CD
6.Maintenance
requirement
Topping up upto 3-4
times/year
No topping up
required
Topping up upto
once in a year
Topping up upto
once in a year
7.Ageing Degrades gradually,
10-12 years service
life
Degrades
gradually,8-10 years
service life
No capacity loss,15-
20 years service life
Slight capacity
loss,15-20 years
service life
8.Sensitivity to over
charge and
undercharge
Moderately
sensitive ,Best
among lead acid
Extremely sensitive Moderately
sensitive
Better than lead
acid batteries
9.Thermal runaway Not susceptible Very susceptible Not susceptible Not susceptible
10.Space
requirement
High Low High Moderate
Comparison of Batteries – Contd.
Battery Manufacturers
Lead Acid NI-CD
Plante Tubular VRLA Pocket plate VR NI-CD
Exide,
Kolkata
HBL,
Hyderabad
AmaraRaja,
Tirupati
HBL,
Hyderabad
HBL,
Hyderabad
Exide,
Kolkata
HBL, Hyderabad AMCO Saft AMCO Saft
Kirloskar,
Bangalore
Exide, Kolkata
BUI,Pune
Comparison of Battery Prices
Lead Acid Plante 30-32/- Per AH
Tubular 13-14/- Per AH
VRLA 12-13/- Per AH
NI-CD Pocket plate 28-30/-Per AH
VR NI-CD 33-35/-Per AH
BATTERY SIZING
FOR STANDBY APPLICATION
SIZING FACTORS PARAMETERS
PRIMARY
LOAD CURRENT
LOAD DURATION
NOMINAL SYSTEM VOLTAGE
MINIMUM SYSTEM VOLTAGE
MINIMUM OPERATING TEMPERATURE
DESIGN MARGIN
AGING FACTOR
SECONDARY
FACTORS SPECIFIC TO APPLICATION
Selection Parameters
DEPTH OF DISCHARGE
FREQUENCY OF DISCHARGE
APPLICATION CRITICALITY
CHARGING CONSTRAINT
MAINTENANCE CONSTRAINT
OPERATING CLIMATIC CONDITIONS
SPACE AVAILABLITY
SELECTION OF THE RIGHT TYPE OF TECHNOLOGY AND
DESIGN PRECEDES THE SIZING EXERCISE
PARAMETERS
TO BE
CONSIDERED
FOR SELECTION
1. A storage battery can store electrical energy
and deliver it back when needed.
2. Capacity of a storage battery is expressed
in Ah at a particular rate of discharge.
3. Normally, for standby application, the capacity
of a storage battery is declared at 10 hour rate
of discharge or at C10.
.
5. A 1000 Ah battery at 10 hour rate of discharge
would mean that it can deliver 100 Amps current
for 10 hours continuously up to an end cell
voltage of 1.85 Volts per cell for flooded
batteries or 1.75 Volts per cell for VRLA
batteries.
6. However, this battery cannot supply 1000 Amps
current for 1 hour since this relationship is not
linear.
7. Higher the current, lower is the duration.
8. For a NDP cell, C10 capacity gets de - rated
to 50% at C1. In other words, 1000 Ah NDP
battery at C10 becomes 500 Ah at C1.
It means the same battery can deliver 500
Amps current for 1 hour and the end voltage
goes down to 1.75 volts.
9. Capacity available from a battery therefore
depends on the discharge current and the
end cell voltage.
Here comes the concept of K factors.
10. K factors estimate the available capacity at
different discharge rate and end cell voltages.
This factor is the ratio of rated capacity to the
amperes that can be supplied for ‘t’ minutes
to a given ecv.
Rated Capacity
K factor =
Required discharge current
1000
K factor for 1 hour discharge =
500
= 2
Battery sizing is all about calculating rated
capacity of a battery for a given discharge
current to an end cell voltage.
If we want to draw ‘I’ current for ‘t’ period
of time to an end cell voltage of ‘a’ volts
per cell, then the rated C10 capacity is
C10 = I x K, where K is the discharge
factor for ‘t’ duration to an end cell voltage
of ‘a’.
K-FACTOR DEPENDS ON:
• TYPE OF CELL
• END OF DISCHARGE VOLTAGE
• DURATION OF LOAD
Sizing Parameters
APPLICATION
PARAMETERS
DUTY CYCLE – LOAD CURRENT
AND DURATION PATTERN
OPERATING DC BUS VOLTAGE
WINDOW – MAXIMUM & MINIMUM
DC BUS VOLTAGES
MINIMUM AMBIENT TEMPERATURE
DESIGN MARGIN
BATTERY
PARAMETERS
CHARGING VOLTAGE REQUIREMENT
DISCHARGE CHARACTERISTICS
FACTOR FOR AGING PHENOMENON
FACTOR FOR STATE-OF-CHARGE IF
REQUIRED
79
SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION
STEP 1 CALCULATION OF NUMBER OF CELLS
:
NUMBER OF CELLS =
MAXIMUM DC BUS VOLTAGE
RECOMMENDED FLOAT VOLTAGE OF EACH CELL
NO OF CELLS FOR PLANTE =
242
2.25
= 108
NO OF CELLS FOR NICD = = 173
242
1.40
80
SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION
STEP 2 WORKING OUT END CELL VOLTAGE
:
END CELL VOLTAGE =
MINIMUM DC BUS VOLTAGE
NUMBER OF CELLS (FOUND FROM STEP NO 1)
END CELL VOLTAGE FOR PLANTE =
192
108
= 1.78
END CELL VOLTAGE FOR NICD = = 1.11
192
173
81
SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION
STEP 3 CALCULATION OF AH CAPACITY
:
AH CAPACITY = K FACTOR x LOAD CURRENT
STEP 4 : APPLY DESIGN MARGIN
DESIGN MARGIN IS BASICALLY THE FACTOR OF SAFETY AND
INSURANCE AGAINST ANY POSSIBLE INCREASE IN LOAD AND
LESS-THAN-OPTIMUM OPERATING CONDITIONS OF THE
BATTERY DUE TO IMPROPER MAINTENANCE, RECENT
DISCHARGE OR AMBIENT TEMPERATURES LOWER THAN
ANTICIPATED OR BOTH.
82
SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION
STEP 5 APPLY TEMPERATURE CORRECTION FACTOR
:
AT LOWER TEMPERATURE, CAPACITY OF ANY STORAGE BATTERY
DECREASES . SINCE THE SYSTEM MUST WORK PROPERLY AT LOWEST
AMBIENT TEMERATURE ALSO, RAW CAPACITY NEEDS TO BE
ADJUSTED BY APPLYING SUITABLE TEMPERATURE CORRECTION
STEP 6 APPLY AGING MARGIN
:
CAPACITY OF ANY STORAGE BATTERY (EXCEPT PLANTE)DECREASES
WITH AGE. SINCE THE SYSTEM REQUIREMENT DOES NOT CHANGE
AND A BATTERY SHOULD BE REPLACED WHEN IT REACHES 80%
VALUE, 25% AGING MARGIN IS CONSIDERED FOR TUBULAR, VRLA
AND NICD BATTERIES.
CALCULATION OF NUMBER OF CELLS & ECV
VMAX / VC
NUMBER OF CELLS (NC)
VMIN / NC
END OF DISCHARGE
VOLTAGE (ECV)
MIN. DC BUS
VOLTAGE (VMIN)
CHARGING
VOLTAGE PER
CELL (VC)
MAX. DC BUS
VOLTAGE (VMAX)
CALCULATION OF RAW CAPACITY
END CELL VOLTAGE (ECV)
BACK-UP DURATION
SELECTED CELL TYPE
CAPACITY FACTOR
‘F’
LOAD CURRENT ‘I’
BASIC RATED CAPACITY OF CELL
C = I x F
CALCULATION OF FINAL CAPACITY
BASIC RATED CAPACITY OF CELL
C = I x F
FINAL CALCULATED CAPACITY
CF = C x A x D x KT
AGING FACTOR, A
DESIGN MARGIN, D
TEMPERATURE
CORRECTION FACTOR,
KT
• ALL TYPES OF BATTERY LOSES CAPACITY WITH AGING
(EXCEPT PLANTE)
• THE END OF LIFE IS DEFINED AS THE TIME WHEN THE
BATTERY CAPACITY REACHES 80% OF ITS RATED CAPACITY
• THE BATTERY IS EXPECTED TO PERFORM THE DESIGNED
DUTY EVEN AT THE END OF LIFE SITUATION
• THE CAPACITY THUS NEEDS TO BE UPRATED TO TAKE CARE
OF THIS INEVITABLE DEGRADATION
AGING FACTOR
RELEVANCE OF FACTORS
MINIMUM OPERATING TEMPERATURE
• ENERGY OUTPUT FROM A BATTERY IS DIRECTLY
PROPORTIONAL TO THE AMBIENT TEMPERATURE
• AT LOWER AMBIENT CAPACITY DECREASES – SO DOES
THE BACK-UP AVAILABILITY
• CAPACITY RATED AT STANDARD AMBIENT THUS NEEDS
TO BE UPRATED FOR SAME OPERATION AT LOWER
AMBIENT
• A TEMPERATURE CORRECTION FACTOR THUS IS
REQUIRED TO TAKE CARE OF THIS INEVITABLE CAPACITY
LOSS
RELEVANCE OF FACTORS
CORRECTION FACTOR FOR MINIMUM AMBIENT
TEMPERATURE OF T 0C
KT = 1+ {(27 – T) X FT} / 100
WHERE
KT = TEMPERATURE CORRECTION FACTOR
T = MINIMUM AMBIENT TEMPERATURE
FT = TEMPERATURE CO-EFFICIENT VALID FOR THE TYPE OF
BATTERY SELECTED IN % PER DEGREE C
RELEVANCE OF FACTORS
• FOR TUBULAR 0.43% PER DEG. C @ C10 (AS PER IS1651)
• FOR PLANTE 0.9% PER DEG. C @ C10 (AS PER IS1652)
• FOR VRLA 0.43% PER DEG. C @ C10 (AS PER IS15549)
•AS A STANDARD PRACTICE, A BUILD-UP OF 10% - 15% IS
GENERALLY ACCEPTED.
DESIGN MARGIN
CATERS TO
A. UNPLANNED AUGMENTATION OF PLANT INSTALLATION.
B. ABERRATION OF EQUIPMENT PERFORMANCE/DUTY.
C. UNEXPECTED LOWER AMBIENT THAN DESIGNED FOR.
RELEVANCE OF FACTORS
DC System
• Battery
• Battery Charger
DC SYSTEM
• BATTERY CHARGERS [TWO/THREE]
• BATTERY BANKS [ONE/TWO]
• DC DISTRIBUTION BOARDS [ONE/TWO]
• DC FUSE BOARDS
• UN EARTHED SYSTEM
• CHARGER TROUBLE, DC EARTH FAULT AND
DC VOLTAGE ABNORMAL ALARMS IN UCB
220 V DC SYSTEM
Charger I
440 V
220 V DC
Charger II
Battery
Bank
Battery
Bank
Feeders
440 V
220 V DC
Feeders
DCDB
Typical UPS System
Module
Power supply
440 V
AC
220 V
DC Battery 220 V DC
220 V
AC UPS
All Unit Controls
&
Protection
48 V, 15V, 24 V, DC
Converter
Inverter
ACDB
X X
X X
X X
X X
DG-1 DG-3 DG-2
DG SWGR-1 DG SWGR-2
UNIT EMER
SWGR-1 UNIT EMER
SWGR-2
UNIT EMER
SWGR-3
UNIT EMER
SWGR-4
220 V DC
• FSSS
• HT Breakers
• Vacuum Breakers
• HOTV/HORV
• Deaerator Overflow Valve
• GRP
• HP Heater Protections
• DC Fans & Pumps
• Extraction FCNRV V/V’s
• SADC
• Trim Device
• Load Shedding Relay
• Scanner Air Fan Outlet & Emergency Damper
• All DC Lights
220 V Supplies
EMCC USS
MAIN CHARGER RESERVE CHARGER
UPS CHARGER-1 UPS CHARGER -2
DAS UPS CHARGER –1 DAS UPS CHARGER-2
+/- 24 VA DC CHARGER +/- 24 VB DC
CHARGER
DG SET BATTERY
SYSTEM
UNINTERRUPTED POWER
SUPPLY
• An uninterruptible power supply (UPS),
uninterruptible power source or sometimes
called a battery backup is a device which
maintains a continuous supply of electric power to
connected equipment by supplying power from a
separate source when utility power is not available.
CAPACITY
• UPS units come in sizes ranging from units which
will back up a single computer without monitor
(around 200 VA) to units which will power entire
data centers or buildings (several megawatts).
• Larger UPS units typically work in conjunction with
generators.
UPS DESIGNS
• The general categories of modern UPS systems
are on-line or off-line, the latter often referred to as
standby.
ON-LINE UPS
• ON-LINE UPS SYSTEMS PROVIDE THE HIGHEST LEVEL OF
PROTECTION FOR MOST IMPORTANT EQUIPMENT.
• THESE SYSTEMS USE A COMBINED DOUBLE-CONVERSION(AC
TO DC/DC TO AC) WHICH CONTINUOUSLY POWERS THE
LOAD,TO PROVIDE BOTH CONDITIONED POWER AND OUTAGE
PROTECTION.
• THEY PROVIDE PROTECTION AND ISOLATION FROM ALL
TYPES OF POWER PROBLEMS,INCLUDING POWER
SURGES,HIGH VOLTAGE SPIKE,SWITCHING
TRANSIENTS,NOISE FREQUENCY VARIATION ETC.
• THESE SYSTEMS ARE OFTEN USED FOR MISSION-CRITICAL
APPLICATION THAT REQUIRE HIGH PRODUCTIVITY AND
SYSTEM AVAILABILITY.
MAJOR COMPONENTS OF UPS
• CHARGER
• BATTERY
• INVERTER
• STATIC SWITCH
• ALTERNATE SUPPLY
BATTERY CHARGERS
 Diode Rectifier
 Thyristor Rectifier
 Diode and DC/DC Converter
(Chopper)
 Active Rectifier (IGBT)
 SMPS – Switch Mode Power Supply
TECHNOLOGY ASSESSMENT
TECHNOLOGY COMPARISON
 Power Factor
 Efficiency
 Harmonic Distortion
 Reliability / Availability / Service
Support
 Space Requirements
 System Cost
POWER FACTOR COMPARISON
 Diode : Good
 Thyristor : Low
 Diode and Chopper : Good
 Active Rectifier : Best
 SMPS : Good
EFFICIENCY COMPARISON
 Diode : High
 Thyristor Medium : High
 Diode and Chopper : Low
 Active Rectifier Medium : Low
 SMPS : High
HARMONIC COMPARISON
 Diode : Medium
 Thyristor : High
 Diode and Chopper : Medium
 Active Rectifier : Low
 SMPS : Low
RELIABILITY COMPARISON
Based Upon Component Count of Rectifier
Devices
 Diode : High
 Thyristor : High
 Diode and Chopper : Low
 Active Rectifier : Medium
 SMPS : Medium
SERVICE SKILL COMPARISON
 Diode : Low
 Thyristor : Medium
 Diode and Chopper : High
 Active Rectifier : High
 SMPS : High
SYSTEM COST COMPARISON
 Diode Rectifier : 105%
 Thyristor Rectifier : 100%
 Diode & Chopper : 124%
 Active Rectifier : 115%
 SMPS : 105%
Based upon past projects, component count and further
developments.
SPACE COMPARISON
Diode : Average
Thyristor : Larger
– (with power factor compensation included)
Diode and Chopper : Larger
Active Rectifier : Average
SMPS : Less
CONCLUSIONS
Considerations :
 Total System Requirements
 Future Provision of System Requirements
 Customer’s Experience / Background
 Technology comparison for exact project
 All Technologies Will continue for near future
FLOAT CUM BOOST
CHARGERS-FCBC
• Voltage
• Current
SIZING IN FLOAT MODE
In float mode the charger shall be capable of meeting the
trickle charging of both the battery banks, station
continuous load current and starting current of largest DC
drive.
SIZING IN BOOST MODE
In boost mode charger shall be capable of boost charging a
fully discharged battery in 8-10 hours.
CHARGER OPERATION
• CHARGER-FLOAT/BOOST
• CONTROLLER -AUTO/MANUAL
CHARGER OPERATION
• Float mode/controller auto mode-charger supplies
at constant voltage(set),with current limiter in
function.
• Boost mode/controller in auto mode-charger
supplies at constant current(set),with voltage limiter
in function
PERFORMANCE FEATURES
• Soft start feature-set voltage in 15 sec.
• Load limiter-80%-100%
• AVR-better then 1% of set voltage
• Voltage limiter
• When energising the charger with fully charged
battery connected plus 10% load shall not result in
output voltage greater than 110% of voltage setting &
charger to stablise to set value in 15 sec.
• With change in load from 20% to 100 % and vice-
versa, the momentary output voltage shall remain
within 94% to 106% and should stablise in 2 sec.
• Ripple content-less than 1%
ANNUNCIATIONS
• A.C. Supply Failure
• Rectifier Fuse Failure
• Surge Circuit Fuse Failure
• Filter Fuse Failure
• Load Limiter Operated
• Charger Trip
• Battery On Boost
Battery Charger Manufacturers
•AMARRAJA ,Tirupati
•HBL,Hyderabad
•Chabi Electricals,Jalgaon
•Caldyne,Kolkata
•Dubas
Battery
Battery
Voltage
stabilizer
ACDB-1
ACDB-2
UNIT UNINTERRUPTED POWER SUPPLY
415 V AC
EMCC
CHARGER –2 INVERTER-2
STATIC SWITCH
CHARGER-1 INVERTER-1
USS
SSVS
240 V AC
ALT
SUPPLY
Manual
Bypass
switch
INVERTER
• Inverters takes an input 210 to 280 V DC from chargers
or battery and converts them to 240V AC.
• First the DC voltage is converted to square wave using
SCRs.
• The SCRs gate pulses can be controlled to slightly alter
frequency.
• In latest UPS inverters IGBTs are being used.
Battery Capacity
• Expressed in ampere hour(AH)
• Duration of discharge-10 hr for Plante/5 hr for Ni-
Cd
• End cell voltage-1.85 volt for Lead acid plante/1.0
volt for Ni-Cd
• Ambient temperature-27 deg cent.
• Electrolyte specific gravity-1.2+-.005 lead acid
plante cells
SELECTION OF BATTERY
TYPE IN POWER PLANT
• Power plant batteries standby duty require high discharge
performance with continuously connected on float mode operation.
• Expected Life of lead acid tubular is of the order of 8-10 years so in
a power plant life of 25 years minimum two replacement would be
required.
• Lead acid PLANTE and Ni-Cd (alkaline) have expected life of 15-20
years hence only one replacement would be required in whole plant
life.
• In addition lead acid plante have much better discharge
performance than tubular type for the specified emergency duration.
• In view of above plante type lead acid or Ni-Cd high discharge
batteries are specified for power plant applications.
• Wherever there is space constraints VRLA batteries may be an
option however this has also expected life of 8-10 years.
CHARGING OF BATTERIES
Nominal Voltage
Float Voltage
Boost Voltage
Float Current
Boost Current
Lead Acid - Plante Ni - Cd
2.0V
2.1V - 2.25V
2.3V - 2.7V
1.4mA / AH
140mA / AH
1.2V
1.40V - 1.42V
1.5V - 1.7V
2.0mA / AH
200mA / AH
CHARGER OPERATION
• Float mode/controller auto mode-charger supplies
at constant voltage(set),with current limiter in
function.
• Boost mode/controller in auto mode-charger
supplies at constant current(set),with voltage limiter
in function
220 V FLOAT CUM BOOST
BATTERY CHARGER
(i) Manufacture UPTRON POWERTRONICS LTD,Sahibabad
(ii) A.C. input 415 V ± 10%, 3 ø, 50 Hz±5%, 69.7 A
(iii) D.C. output voltage Float 220- 250 V
Boost 200- 300 V
Current Float 110A
Boost 80 A
(iv) Ripple 1% peak to peak without battery
(v) Efficiency at full load More than 85%
(vi) Voltage setting range
(manual)
220 – 300 V
(vii) Current setting range 50% to 100% of rated current
(viii) Cooling AN
(ix) Max. ambient temp. 500 C
(x) Response time Less than 750 mSec
THANK YOU

More Related Content

What's hot

Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
opjit88
 
Reactive power
Reactive powerReactive power
Reactive power
Ashutosh Tripathi
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
kaushal boghani
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
Rahul Ruddra
 
Protective relay
Protective relay Protective relay
Protective relay
Uday Wankar
 
Battery Types and Battery technology
Battery Types and Battery technologyBattery Types and Battery technology
Battery Types and Battery technology
SRM UNIVERSITY
 
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
Yuvraj Singh
 
High Voltage Direct Current Transmission System
High Voltage Direct Current Transmission SystemHigh Voltage Direct Current Transmission System
High Voltage Direct Current Transmission System
Nadeem Khilji
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
Power System Operation
 
Hv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generationHv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generation
Asha Anu Kurian
 
Solar charge-controller-presentation
Solar charge-controller-presentationSolar charge-controller-presentation
Solar charge-controller-presentation
Borshon sen
 
HVDC
HVDC HVDC
Energy storage technologies
Energy storage technologiesEnergy storage technologies
Energy storage technologies
srikanth reddy
 
Voltage and Frequency Control of the Grid
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
Leonardo ENERGY
 
Electrical Engineering Interview Questions
Electrical Engineering Interview QuestionsElectrical Engineering Interview Questions
Electrical Engineering Interview Questions
ashiesh0007
 
voltage and power stability of hvdc system
voltage and power stability of hvdc systemvoltage and power stability of hvdc system
voltage and power stability of hvdc system
chandan kumar
 
Gss herapura report
Gss herapura reportGss herapura report
About Solar Inverter
About Solar Inverter About Solar Inverter
About Solar Inverter
Edgefxkits & Solutions
 
Hvdc transmission & its applications
Hvdc transmission & its applicationsHvdc transmission & its applications
Hvdc transmission & its applications
Pooja Dubey
 

What's hot (20)

Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Reactive power
Reactive powerReactive power
Reactive power
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Protective relay
Protective relay Protective relay
Protective relay
 
Battery Types and Battery technology
Battery Types and Battery technologyBattery Types and Battery technology
Battery Types and Battery technology
 
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
Report on the IMPROVING THE EFFICIENCY OF SOLAR PHOTOVOLTAIC POWER GENERATION...
 
132 kv
132 kv132 kv
132 kv
 
High Voltage Direct Current Transmission System
High Voltage Direct Current Transmission SystemHigh Voltage Direct Current Transmission System
High Voltage Direct Current Transmission System
 
Protection of Transmission lines
Protection of Transmission linesProtection of Transmission lines
Protection of Transmission lines
 
Hv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generationHv module 3 Impulse voltage generation
Hv module 3 Impulse voltage generation
 
Solar charge-controller-presentation
Solar charge-controller-presentationSolar charge-controller-presentation
Solar charge-controller-presentation
 
HVDC
HVDC HVDC
HVDC
 
Energy storage technologies
Energy storage technologiesEnergy storage technologies
Energy storage technologies
 
Voltage and Frequency Control of the Grid
Voltage and Frequency Control of the GridVoltage and Frequency Control of the Grid
Voltage and Frequency Control of the Grid
 
Electrical Engineering Interview Questions
Electrical Engineering Interview QuestionsElectrical Engineering Interview Questions
Electrical Engineering Interview Questions
 
voltage and power stability of hvdc system
voltage and power stability of hvdc systemvoltage and power stability of hvdc system
voltage and power stability of hvdc system
 
Gss herapura report
Gss herapura reportGss herapura report
Gss herapura report
 
About Solar Inverter
About Solar Inverter About Solar Inverter
About Solar Inverter
 
Hvdc transmission & its applications
Hvdc transmission & its applicationsHvdc transmission & its applications
Hvdc transmission & its applications
 

Similar to DC Supply System, Batteries,UPS - Copy.pdf

Solar ppt
Solar pptSolar ppt
DC SUPPLY SYSTEM.ppt
DC SUPPLY SYSTEM.pptDC SUPPLY SYSTEM.ppt
DC SUPPLY SYSTEM.ppt
banukiransamboju
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
Bhushan Kumbhalkar
 
Piezoelectric Energy Harvesting.
Piezoelectric Energy Harvesting.Piezoelectric Energy Harvesting.
Piezoelectric Energy Harvesting.
Adityanarayan PS Jagdev
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power
 
Hybrid Cooler
Hybrid CoolerHybrid Cooler
Hybrid Cooler
IRJET Journal
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover
IJSRED
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
michaeljmack
 
IRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfIRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdf
PowerSystemDynamicsS
 
Heavy water plant and there electrical systam
Heavy water plant and there electrical systam Heavy water plant and there electrical systam
Heavy water plant and there electrical systam
mohit Navriya
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
IRJET Journal
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
Himansu Pradhan
 
Guidelines for power plants (smps)
Guidelines for power plants (smps)Guidelines for power plants (smps)
Guidelines for power plants (smps)Shiv Chaudhary
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: Technical
Staco Energy
 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
JoeChueng
 
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.pptPV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
ArpoMukherjee1
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
Shuvam Pathania
 

Similar to DC Supply System, Batteries,UPS - Copy.pdf (20)

Solar ppt
Solar pptSolar ppt
Solar ppt
 
DC SUPPLY SYSTEM.ppt
DC SUPPLY SYSTEM.pptDC SUPPLY SYSTEM.ppt
DC SUPPLY SYSTEM.ppt
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Piezoelectric Energy Harvesting.
Piezoelectric Energy Harvesting.Piezoelectric Energy Harvesting.
Piezoelectric Energy Harvesting.
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...
 
Hybrid Cooler
Hybrid CoolerHybrid Cooler
Hybrid Cooler
 
Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover Implementation of a Microcontroller Base Single Phase Automatic Changeover
Implementation of a Microcontroller Base Single Phase Automatic Changeover
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
IRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdfIRPTF_Workshop_Presentations (1).pdf
IRPTF_Workshop_Presentations (1).pdf
 
Heavy water plant and there electrical systam
Heavy water plant and there electrical systam Heavy water plant and there electrical systam
Heavy water plant and there electrical systam
 
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC GeneratorZVS Circuit based – Cockcroft Walton High Voltage DC Generator
ZVS Circuit based – Cockcroft Walton High Voltage DC Generator
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Guidelines for power plants (smps)
Guidelines for power plants (smps)Guidelines for power plants (smps)
Guidelines for power plants (smps)
 
Product: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: TechnicalProduct: Power Factor & Harmonics: StacoSine: Technical
Product: Power Factor & Harmonics: StacoSine: Technical
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
ntpc ppt
ntpc pptntpc ppt
ntpc ppt
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.pptPV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
PV SYSTEMS, COMPONENTS DEVICES AND APPLICATIONS.ppt
 
havells ppt
havells ppthavells ppt
havells ppt
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 

Recently uploaded

Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
PrashantGoswami42
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
ssuser9bd3ba
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
Kamal Acharya
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
R&R Consult
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
Pipe Restoration Solutions
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
ShahidSultan24
 

Recently uploaded (20)

Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
 
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxCFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptx
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
The Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdfThe Benefits and Techniques of Trenchless Pipe Repair.pdf
The Benefits and Techniques of Trenchless Pipe Repair.pdf
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
addressing modes in computer architecture
addressing modes  in computer architectureaddressing modes  in computer architecture
addressing modes in computer architecture
 

DC Supply System, Batteries,UPS - Copy.pdf

  • 2. Battery Is Considered To Be The “HEART” Of The Power Plant  Battery provides the ultimate and final DC back-up for emergency oil pumps and other emergency equipment.  DC power for operation of all switchgear protection and relays.  Power for emergency lighting within the generating station building.  Uninterrupted power for C & I equipment and the ups systems.  Power for vital communication equipment (PLCC), essential for re- synchronizing the unit with the grid or for reviving the grid in the case of a major grid failure.
  • 3. What If The Battery Fails In An Emergency  Unit Battery  The emergency oil pump will not operate which may lead to seizure of the rotor bearings  Loss of hundreds of crore of rupees towards repairing the rotor and generation revenue loss while the unit is out of service.  Switchgear associated with generator may not trip which could lead to generating transformer damage  Failure of instrumentation and control  Total darkness in the powerhouse
  • 4. What If The Battery Fails In An Emergency (contd.)  Substation  Switchgear and relays will not operate causing extensive damage to transformers and power lines  PLCC  Extremely difficult to resynchronize the unit with the grid  Major setback in the process of reviving the grid in the event of a regional grid failure  If the battery fails while the unit is in operation, it may become essential to shutdown
  • 5. DC SYSTEM IS DESIGNED • TO SUPPLY HIGH STANDARD OF RELIABLE & SECURE DC POWER • TO PROVIDE CONTINUOUS & QUALITY POWER AS AND WHEN REQUIRED • UNDER NORMAL & ABNORMAL OPERATING CONDITIONS • ULTIMATE & FINAL DC BACK-UP POWER TO EQUIPMENT AND DC DRIVES WHEN TOTAL AC SUPPLY FAILS • HENCE THEY ARE BATTERY BACKED
  • 6. DUTIES • TO SUPPLY EQUIPMENT WHICH REQUIRES DC DURING NORMAL CONDITIONS • TO SUPPLY STANDBY EQUIPMENT/DC DRIVES • TO SUPPLY STARTERS OF VARIOUS EQUIPMENT • TO SUPPLY EQUIPMENT WHEN AC SUPPLIES HAVE BEEN LOST
  • 7. Types of Power Supplies In a Power Plant • 11KV/3.3KV/415V AC Power Supply • 415V AC Emergency Supply(DG) • DC Power Supply • UPS Supply
  • 8. DC Power Supply • Various Critical Drives • Emergency DC Lighting • Switchgear Control Supply for closing & tripping • Control, Protection And Interlocks • Indication, Annunciation & Alarm System • Public Address System • DAS And Communication System
  • 9. DC Supplies……………Why? • Emergency Lube Oil Pump • Emergency Jacking Oil Pump • Emergency Scanner Air Fan • Emergency Seal Oil Pump • Breaker/Unit Protections • Emergency Lighting
  • 10. The Ultimate Backup In case of unit tripping / grid failure, either station changeover takes place / DG would start. Normally, grid supply would be restored in minimum possible time and DG would shut down. In case of DG failure, the DC backup comes in to service to facilitate safe shut down.
  • 11. Selection of voltage DC POWER SUPPLY • In power plant D.C. pumps, lighting require comparatively high voltage due to their high power requirement. Hence as a standard these applications are designed with 220V level. • It is desirable to have comparatively lower voltage- 24V/48V/110V for control/indications/annunciation due to safety reasons. However to avoid multiplicity of DC supplies (particularly we require two control supplies), we have adopted uniform 220V DC voltage for plant electrical systems for switchgear control, protection and interlock operation.
  • 12. DC POWER SUPPLY SCHEME 1. Earlier concept; • 1X100% battery bank along with its chargers for each unit with inter- unit interconnection through high capacity DC bus bar. • In view of large size of above DC loads of each unit and the large unit pitch it is necessary to provide a separate DC system (battery +chargers) to enhance the plant’s overall reliability. 2) Present concept; • In view of the reasons explained above 2x100% capacity DC system is provided for each unit and switchyard separately. • Minor DC loads of offsite areas in the plant i.e. WTP, Ash handling are fed from plant DC system as it is now restricted to limited area switchgear rooms, as control now no longer relay based.
  • 13. The Single Most Important Feature Of Storage Batteries For Power Sector and Other Critical Standby Application Is Reliability  Reliable standby power source  Deliver power as and when called for  Full capacity at any point of time in service life  Predictability
  • 14. EITHER SUDDEN DISRUPTION OF MAINS POWER TAKES PLACE OR CONVENIENT AVAILABILITY OF MAINS POWER IS NOT THERE THIS CLEARLY DEFINES TWO REGIMES OF APPLICATION STANDBY APPLICATION CYCLIC APPLICATION UPS, INVERTERS, TELEPHONE EXCHANGES, POWER STATIONS, SWITCHING CELL PHONES, TOYS, FORK LIFTS, ELECTRIC VEHICLES, SOLAR PHOTOVOLTAICS STORAGE BATTERY WHEN ?
  • 15. STORAGE BATTERY FUNDAMENTAL An ELECTRICAL STORAGE CELL consists of two dissimilar electrodes immersed in electrolyte. Stores Electrical Energy in the form of Chemical Energy. When the circuit is made between its +ve & -ve electrodes, it triggers a chemical reaction inside the cell & delivers electricity – Direct Current (D.C.) through the circuit. CHEMICAL ENERGY ELECTRICAL ENERGY Anode Electrolyte Cathode
  • 16. A BATTERY is an array of similar/identical objects The battery, we are talking about is an electrical storage battery comprising of an array of electrical storage cells STORAGE BATTERY FUNDAMENTAL
  • 18. INDUSTRIAL POWER LEAD – ACID NICKEL – CADMIUM PORTABLE POWER LITHIUM ION NICKEL – METAL HYDRIDE NICKEL CADMIUM HIGH END APPLICATION – TORPEDOES, SPACE SILVER - ZINC NICHE POWER GENERATION FUEL CELLS Application Pattern:
  • 19. LEAD ACID NICKEL CADMIUM General Battery Technologies Most Popular Electrochemical Couples used worldwide in Industrial Application
  • 20. Types of Batteries Lead Acid Nickel - Cadmium Flat Plate Tubular Plante VRLA Pocket Plate Tubular Plate Sintered Plate
  • 21. BASIC ELECTROCHEMISTRY PbO2 + Pb + 2H2SO4 PbSO4 + PbSO4 + 2H2O CHARGED DISCHARGED ELECTROLYTE TAKES ACTIVE PART IN REACTION – SPECIFIC GRAVITY CHANGES WITH STATE OF CHARGE – EASY MONITORING AND INDICATION OF STATE OF CHARGE (SOC) 2NiOOH + 2H2O + Cd 2Ni(OH)2 + Cd(OH)2 NEG. NEG. POS POS DISCHARGED CHARGED ELECTROLYTE DOES NOT TAKE ACTIVE PART IN REACTION – SPECIFIC GRAVITY DOES NOT CHANGE WITH STATE OF CHARGE – NO DIRECT & EASY METHOD OF MEASURING STATE OF CHARGE NEG. NEG. POS POS LEAD ACID NICKEL CADMIUM
  • 22. More than 90% of applications world-wide use Lead-acid Reasons:  LOW COST  APPLICATION VERSATILITY  ABUNDANT RAW MATERIAL  WELL DEVELOPED SERVICING RECYCLING INFRASTRUCTURE Advantage “Lead Acid”
  • 23. Technology Wise Categorisation Industrial Lead Acid Battery FLOODED VRLA FLAT TUBULAR PLANTE The Lead-Acid Technology
  • 24. LEAD ACID BATTERY AN OVERVIEW ACTIVE MATERIAL TAKES ACTIVE PART IN REACTION TO STORE & SUPPLY ENERGY SUPPORT STRUCTURE ENABLES ELECTRONIC CONDUCTION 1 2 PROVIDES MECHANICAL SUPPORT TO ACTIVE MATERIAL ACTIVE MATERIAL SUPPORT STRUCTURE PLATES ARE CONSTITUTED OF FLAT PASTED POSITIVE AND NEGATIVE
  • 25. FLAT PLATE A CHEMICAL BONDING HOLDS THE ACTIVE MATERIAL IN PLACE THROUGHOUT THE SERVICE LIFE WIRE-MESH LIKE SUPPORT STRUCTURE – GRID CAST OF LEAD ALLOY, ANTIMONY OR CALCIUM ACTIVE MATERIAL PASTED ON GRID - EXTERNALLY
  • 26. FLAT POSITIVE PLATE MOST SUITABLE FOR HIGH CURRENT, SHORT DURATION APPLICATION viz. SLI, SHALLOW DUTY INVERTER ETC. ADVANTAGES MINIMUM LEAD MOST ECONOMIC & HIGHEST ENERGY DENSITY EXCELLENT HIGH RATE DISCHARGE PERFORMANCE AND CHARGE ACCEPTANCE LARGE ACTIVE SURFACE AREA LIMITATIONS ACTIVE MATERIAL SHEDDING LIMITED CYCLING CAPABILITY EASY ACCESS OF ACID TO LEAD GRID EASY CORROSION – LOW LIFE EXPECTANCY
  • 27. THE SUPPORT STRUCTURE IS IN THE FORM OF CAST ROD ELECTRODES CALLED SPINES JOINED AT THE TOP BY A BUS BAR. ALLOY USED IS MOSTLY ANTIMONIAL LEAD. INDIVIDUAL SPINES ENGULFED IN A MICROPOROUS PLURITUBULAR GAUNTLET ANNULAR SPACE BETWEEN SPINE AND GAUNTLET FILLED WITH ACTIVE MATERIAL. BOTTOM OF THE GAUNTLET SEALED WITH A PLASTIC PLUG CALLED BOTTOM BAR TUBULAR POSITIVE PLATE
  • 28.  Active material is held around the spines with the help of polyester tubes called gauntlet.  Annular space between the spine & gauntlet is filled with active material. Spine Gauntlet Active Material Plastic Bottom Bar A A’ B B’ Gauntlet Active Material Spine Section A A’ Section B B’ TUBULAR POSITIVE PLATE Lead Top Bar
  • 29. EXTENDED SERVICE LIFE. IT IS DESIGNED FOR DEEP CYCLING LOOSE PACKING OF ACTIVE MATERIAL POSSIBLE ADVANTAGES NO ACTIVE MATERIAL SHEDDING BEST SUITED FOR CYCLING – 1500 CYCLES @ 80% DOD SPINE DEEPLY EMBEDDED IN ACTIVE MATERIAL – LOW SPINE CORROSION EXTREME TEMPERATURE OPERATION RESISTANT TO OVER- CHARGE RECOVERY FROM DEEP DISCHARGE PSOC OPERATION TUBULAR POSITIVE PLATE WHY ?
  • 30. MODEST HIGH RATE DISCHARGE PERFORMANCE. REQUIRES PERIODIC EQUALIZING AND/OR BOOST CHARGING REQUIRES PERIODIC TOPPING UP “ANTIMONY POISONING” LEADS TO SLOWLY DECLINING VOLTAGE PROFILE AND INCREASING WATER LOSS AS THE BATTERY AGES. TUBULAR POSITIVE PLATE WHY NOT ? LIMITATIONS
  • 31. CAST OF 99.99% PURE LEAD LAMELLAR GRID STRUCTURE – ENHANCED ACTIVE SURFACE AREA INTEGRAL GRID ACTIVE MATERIAL PLANTE PLANTE POSITIVE PLATE
  • 32. CAST OF 99.99% PURE LEAD LAMELLAR GRID STRUCTURE – ENHANCED ACTIVE SURFACE AREA INTEGRAL GRID ACTIVE MATERIAL PLANTE Lug Support Bar Lamellar Surface PLANTE POSITIVE PLATE
  • 33. POSITIVE PLATE HANGING FROM CONTAINER SHOULDER GAP BETWEEN POSITIVE PLATE BOTTOM & MUD RIB FOR CREEP GROWTH ALLOWANCE POSITIVE PLATE HANGING FROM CONTAINER SHOULDER TO PROVIDE SPACE FOR CREEP GROWTH INEVITABLE TO PURE LEAD POSITIVE PLANTE HANGING PLATE DESIGN
  • 34. 1. In case of loss of active material due to shedding, next layer of pure lead is converted to lead-dioxide thereby ensuring no loss of capacity – feature of continuous regeneration of active material. 1. Across its life time Plante cells therefore perform at full capacity – there is no aging unlike all other lead-acid products. 1. No aging factor required for capacity calculation Integral Grid-Active Material Plante
  • 35. CONTINUOUS REGENERATION OF ACTIVE MATERIAL PLANTE NO LOSS IN CAPACITY TOTAL LEAD-DI-OXIDE CONTENT FAIRLY CONSTANT THROUGHOUT THE LIFE SPAN INDICATING A CONSTANT CAPACITY OUTPUT CAPACITY DEGRADATION OVER LIFE AGEING FACTOR TUBULAR : 20% 1.25 VRLA : 20% 1.25 Ni-Cd : 20% 1.25 PLANTE : ZERO 1.00
  • 36. HIGH SURFACE AREA HIGH CHARGING RATES POSSIBLE. CHARGING AT 0.25 C10 AMPS UPTO 2.4 VOLTS PER CELL WITHOUT PROBLEM NO ANTIMONY POISONING HIGH FLOAT POTENTIAL POSSIBLE. PLANTE FAST RECHARGE
  • 37. LIFE EXPECTANCY OF 18 TO 20 YEARS PLUS. PLANTE LONG LIFE VERY THICK POSITIVE – ENOUGH CUSHION AGAINST CORROSSION LOW SUSCEPTIBILITY TO OVERCHARGE DUE TO VERY LOW EQUILIBRIUM FLOAT CURRENT OF THE ORDER OF 1 mA/AH UNDER NORMAL FLOAT CONDITION LOW FLOAT CURRENT AND HIGH PURITY OF LEAD LOWERS THE CORROSSION RATE
  • 38. RELIABILITY - REITERATED PLANTE EASY MONITORING TRANSPARENT SAN (STYRENE ACRYLONITRILE) CONTAINER – EASY VISUAL MONITORING OF CELL INSIDE ANY ODD BEHAVIOUR CAN BE MONITORED AND CORRECTED MUCH BEFORE IT SHOWS UP AS A FAILURE MODE EASY CLEANING OF CELLS FROM UNAVODABLE SLUDGE DEPOSITION TO AVOID SHORT CIRCUIT AND RELATED TROUBLES
  • 39. SEALED ! CAN BE KEPT IN ANY ORIENTATION. NO TOPPING-UP REQUIRED EVER “MAINTENANCE-FREE”. A ZERO EMISSION PRODUCT. BATTERY COMES CHARGED. COMPACT. WHAT IS VRLA ?
  • 40. 1. No topping up ever 2. No emission of fumes 3. Supplied factory charged 4. Excellent ‘high rate discharge’ performance 5. Excellent charge acceptance 6. Excellent deep cycle life 7. Low Self-discharge 8. Designed to suit float and moderate cyclic duty 9. Compact – low foot print 10. Long Life Advantage VRLA VRLA
  • 41. CONSTRUCTION OF A VALVE REGULATED LEAD ACID CELL AGM Separator PbO2 Positive Plate Pb Negative Plate
  • 42. 1. No means of state-of-charge assessment 1. Vulnerable to prolonged operation at high temperature 1. Sensitive to both under and over charge 1. Recovery from over discharged condition is difficult 1. Can have a catastrophic failure in case of charger malfunction and/or abnormally high temperature operation – a failure mode known as ‘thermal runaway’ VRLA Limitations VRLA
  • 43. The VRLA Mechanism Some fundamental requirements of a VRLA 1. Absence of free electrolyte – this can be done by two process a. Gel b. AGM 2. Entire element is held under tight compression Under the above circumstance an oxygen bubble evolved at the positive electrode diffuses to negative electrode to react with the freshly formed pure lead as follows: O2 + Pb  (PbO) + SO4 + H+  PbSO4 + H2O This is unique to VRLA – PbSO4 forms on the negative electrode both on discharge as well as on charge!
  • 44. The Lead Acid VRLA ….contd The preceding analysis explains the limitations of a VRLA: The recharge voltage and/or operating temperature has to be carefully regulated since a higher voltage or the higher temperature will raise the potential of both positive and negative electrodes leading to: - Excessive recombination, rise in temperature, loss of water, so far as oxygen is concerned - As far as hydrogen is concerned there is no recombination reaction for it thereby resulting in net loss of the gas and in effect water i.e. accelerated aging shall take place. - In effect, VRLAs charge ‘slow’ at float voltage only.
  • 45. A note on “Gel” tubular VRLA Gel tubular VRLA share most of the advantage features of AGM VRLA except for: a. High Rate Performance is modest b. Charge acceptance is lower c. Compatibility to fast charging is poor d. Uses more lead, hence more bulky and expensive On the positive side, Gel products are less affected by high temperature operation – basic electrolyte content being higher vis-à-vis VRLA and hence also eliminates the possibility of catastrophic failure due to ‘thermal runaway’
  • 46. Factors that limit the life of a lead-acid battery (conventional) • Positive Grid/Spine Corrosion • Degradation of Positive/Negative Active Material • Corrosion of positive pillars, group bar • Mechanical degradation of cover/lid leading to leakage etc. • Internal shorts due to separator degradation • Internal shorts due to excessive sedimentation • Internal short/terminal damage due to plate growth
  • 47. Factors that lead to ‘Premature’ Battery Failure • Wrong type selection • Wrong sizing of battery • Improper operation - over discharge - under/over charging • Improper maintenance – topping up - equalization/boost • Poor quality acid/water
  • 49. Nickel Cadmium Technologies  Pocket Plate  Sintered Plate  Fibre Plate
  • 50. Technologies Nickel-cadmium development  Pocket Plate (PP) – 1st generation (1893) • Industrial applications  Sintered Plate (SP) – 2nd generation (1934) • Aviation applications  Fibre Plate (FP) – 3rd generation (1978) • AGV, Rail & Industry applications
  • 51. Technologies Nickel-cadmium chemistry  Positive active material : Nickel Hydroxide  Negative active material : Cadmium Hydroxide  Electrolyte : Potassium hydroxide (KOH)  Nominal voltage : 1.2 volts 2NiO-OH + 2H2O +Cd= 2Ni(OH)2+ Cd(OH)2 When the cell is charged, the active material initially present as hydroxides are changed. On discharge, the process is reversed.
  • 53. Pocket Plate battery Key features  Proven technology  Exceptional reliability and long lifetime  Low internal resistance  Wide operating temperature range  Fast recharge capability  Resistance to electrical and mechanical abuse  Specific designs to applications  Easy installation and low maintenance  Environmentally safe
  • 54. Pocket Plate battery Key features : How?  Do not suffer from sudden death failure  Electrolyte does not participate in the electro-chemistry, Its simply an ion carrier. No need to measure Sp. Gravity in service  All internal components are made with steel structure  No component is affected by electrochemical reaction or by electrolytic aging
  • 55. Pocket Plate battery Construction Splash guard Prevents electrolyte splashing and possible short-circuit caused by external objects accidentally falling into the cell Plate Groups Welded construction imparts high mechanical strength to withstand severe vibrations Plate Made of Double perforated steel strips, encompass the active materials Fusion welded to lids, makes the cell mechanically sturdy and facilitate visual electrolyte level inspection Translucent polypropylene container Nickel-plated terminal posts provide good electrical conductivity Prevents explosion & electrolyte contamination Polypropylene Grid Separator Separates the plates and insulate the frames from each other and allows free electrolyte flow Flame Arresting Vent Terminal Arrangement
  • 56. Pocket Plate battery Operating features : Charge  Ensures the readiness of battery in short time, after one black out  Flexible boost charge voltage 1.45 – 1.70V/cell  Float voltage 1.40 – 1.42V/cell  Discharge End voltage range from 1.14 – 0.65V/cell  Tolerates deep discharges - can be deep cycled.  Excellent low temperature discharge capability  85% capacity available even at -20°C operation
  • 57. Pocket Plate battery Operating features : Lifetime  Life of Ni-Cd batteries is more than 20 years under float conditions with many number of industrial applications  Cyclic life  Excellent cyclic capability Depth of Discharge Number of cycles 20% 8000 40% 3200 60% 2000 80% 1000  Lesser the DOD, higher would be the cyclic life
  • 58. Pocket Plate battery Operating features : Installation  A simple bolted connector assembly system  Stepped arrangement for easy maintenance & electrolyte visibility  Various options for battery racks to fit into available room space  No need for special acid / alkali proof flooring  Battery can be installed in the same room as other electronic equipment
  • 59. Pocket Plate battery Operating features : Installation 2 Step – 2 tier
  • 60. Pocket Plate battery Operating features : Installation 4 Step – 1 tier
  • 61. Pocket Plate battery Operating features : Installation 3 Step – 2 tier
  • 62. Pocket Plate battery Low maintenance  No need of measuring of specific gravity  Large electrolyte reserve  Air conditioned environment is not essential  Natural ventilation is sufficient  “Flip open” vent caps to simplify topping-up  Long topping-up intervals
  • 63. Pocket Plate battery Environmentally safe  No emission of corrosive gases  Low emission of explosive gases  Explosion proof vents  Protection against accidental shorts  More than 99% of metals contained in batteries can be recycled
  • 64. Comparison of Batteries Tubular VRLA PLANTE NI-CD 1.Application Ideal for float as well as frequent charge/deep discharge cycling duties For relatively short time backup with moderate depth of discharge Ideal for meeting duty cycle in float operation Better suited for very high rate of discharge under extreme condition/cyclic duty. 2.Reliability Quite reliable Generally reliable, however prone to unexpected malfunctioning Most reliable in float operations Reliable during routine duty cycles 3.Monitoring state of charge Can be done by measuring electrolyte specific gravity Cannot be determined externally, acts as a blackbox Can be done by measuring electrolyte specific gravity,visual monitoring through transparent containers Cannot be determined externally, acts as a blackbox 4.Susceptibili ty to high temperatures Satisfactory operations up to 48/50 deg. C electrolyte temperature,Best among lead acid. Prolonged operation at high temperature curtails battery life Satisfactory operations up to 48/50 deg. C electrolyte temperature Satisfactory operations up to 48/50 deg. C electrolyte temperature.Wide temperature range 5.Discharge performance Standard, but inferior to Plante Best Superior to Tubular but inferior to VRLA Very Good
  • 65. Tubular VRLA PLANTE NI-CD 6.Maintenance requirement Topping up upto 3-4 times/year No topping up required Topping up upto once in a year Topping up upto once in a year 7.Ageing Degrades gradually, 10-12 years service life Degrades gradually,8-10 years service life No capacity loss,15- 20 years service life Slight capacity loss,15-20 years service life 8.Sensitivity to over charge and undercharge Moderately sensitive ,Best among lead acid Extremely sensitive Moderately sensitive Better than lead acid batteries 9.Thermal runaway Not susceptible Very susceptible Not susceptible Not susceptible 10.Space requirement High Low High Moderate Comparison of Batteries – Contd.
  • 66. Battery Manufacturers Lead Acid NI-CD Plante Tubular VRLA Pocket plate VR NI-CD Exide, Kolkata HBL, Hyderabad AmaraRaja, Tirupati HBL, Hyderabad HBL, Hyderabad Exide, Kolkata HBL, Hyderabad AMCO Saft AMCO Saft Kirloskar, Bangalore Exide, Kolkata BUI,Pune
  • 67. Comparison of Battery Prices Lead Acid Plante 30-32/- Per AH Tubular 13-14/- Per AH VRLA 12-13/- Per AH NI-CD Pocket plate 28-30/-Per AH VR NI-CD 33-35/-Per AH
  • 69. SIZING FACTORS PARAMETERS PRIMARY LOAD CURRENT LOAD DURATION NOMINAL SYSTEM VOLTAGE MINIMUM SYSTEM VOLTAGE MINIMUM OPERATING TEMPERATURE DESIGN MARGIN AGING FACTOR SECONDARY FACTORS SPECIFIC TO APPLICATION
  • 70. Selection Parameters DEPTH OF DISCHARGE FREQUENCY OF DISCHARGE APPLICATION CRITICALITY CHARGING CONSTRAINT MAINTENANCE CONSTRAINT OPERATING CLIMATIC CONDITIONS SPACE AVAILABLITY SELECTION OF THE RIGHT TYPE OF TECHNOLOGY AND DESIGN PRECEDES THE SIZING EXERCISE PARAMETERS TO BE CONSIDERED FOR SELECTION
  • 71. 1. A storage battery can store electrical energy and deliver it back when needed. 2. Capacity of a storage battery is expressed in Ah at a particular rate of discharge. 3. Normally, for standby application, the capacity of a storage battery is declared at 10 hour rate of discharge or at C10. .
  • 72. 5. A 1000 Ah battery at 10 hour rate of discharge would mean that it can deliver 100 Amps current for 10 hours continuously up to an end cell voltage of 1.85 Volts per cell for flooded batteries or 1.75 Volts per cell for VRLA batteries. 6. However, this battery cannot supply 1000 Amps current for 1 hour since this relationship is not linear. 7. Higher the current, lower is the duration.
  • 73. 8. For a NDP cell, C10 capacity gets de - rated to 50% at C1. In other words, 1000 Ah NDP battery at C10 becomes 500 Ah at C1. It means the same battery can deliver 500 Amps current for 1 hour and the end voltage goes down to 1.75 volts. 9. Capacity available from a battery therefore depends on the discharge current and the end cell voltage. Here comes the concept of K factors.
  • 74. 10. K factors estimate the available capacity at different discharge rate and end cell voltages. This factor is the ratio of rated capacity to the amperes that can be supplied for ‘t’ minutes to a given ecv. Rated Capacity K factor = Required discharge current 1000 K factor for 1 hour discharge = 500 = 2
  • 75. Battery sizing is all about calculating rated capacity of a battery for a given discharge current to an end cell voltage. If we want to draw ‘I’ current for ‘t’ period of time to an end cell voltage of ‘a’ volts per cell, then the rated C10 capacity is C10 = I x K, where K is the discharge factor for ‘t’ duration to an end cell voltage of ‘a’.
  • 76. K-FACTOR DEPENDS ON: • TYPE OF CELL • END OF DISCHARGE VOLTAGE • DURATION OF LOAD
  • 77. Sizing Parameters APPLICATION PARAMETERS DUTY CYCLE – LOAD CURRENT AND DURATION PATTERN OPERATING DC BUS VOLTAGE WINDOW – MAXIMUM & MINIMUM DC BUS VOLTAGES MINIMUM AMBIENT TEMPERATURE DESIGN MARGIN BATTERY PARAMETERS CHARGING VOLTAGE REQUIREMENT DISCHARGE CHARACTERISTICS FACTOR FOR AGING PHENOMENON FACTOR FOR STATE-OF-CHARGE IF REQUIRED
  • 78. 79 SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION STEP 1 CALCULATION OF NUMBER OF CELLS : NUMBER OF CELLS = MAXIMUM DC BUS VOLTAGE RECOMMENDED FLOAT VOLTAGE OF EACH CELL NO OF CELLS FOR PLANTE = 242 2.25 = 108 NO OF CELLS FOR NICD = = 173 242 1.40
  • 79. 80 SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION STEP 2 WORKING OUT END CELL VOLTAGE : END CELL VOLTAGE = MINIMUM DC BUS VOLTAGE NUMBER OF CELLS (FOUND FROM STEP NO 1) END CELL VOLTAGE FOR PLANTE = 192 108 = 1.78 END CELL VOLTAGE FOR NICD = = 1.11 192 173
  • 80. 81 SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION STEP 3 CALCULATION OF AH CAPACITY : AH CAPACITY = K FACTOR x LOAD CURRENT STEP 4 : APPLY DESIGN MARGIN DESIGN MARGIN IS BASICALLY THE FACTOR OF SAFETY AND INSURANCE AGAINST ANY POSSIBLE INCREASE IN LOAD AND LESS-THAN-OPTIMUM OPERATING CONDITIONS OF THE BATTERY DUE TO IMPROPER MAINTENANCE, RECENT DISCHARGE OR AMBIENT TEMPERATURES LOWER THAN ANTICIPATED OR BOTH.
  • 81. 82 SIZING OF STORAGE BATTERY FOR STANDBY FLOAT APPLICATION STEP 5 APPLY TEMPERATURE CORRECTION FACTOR : AT LOWER TEMPERATURE, CAPACITY OF ANY STORAGE BATTERY DECREASES . SINCE THE SYSTEM MUST WORK PROPERLY AT LOWEST AMBIENT TEMERATURE ALSO, RAW CAPACITY NEEDS TO BE ADJUSTED BY APPLYING SUITABLE TEMPERATURE CORRECTION STEP 6 APPLY AGING MARGIN : CAPACITY OF ANY STORAGE BATTERY (EXCEPT PLANTE)DECREASES WITH AGE. SINCE THE SYSTEM REQUIREMENT DOES NOT CHANGE AND A BATTERY SHOULD BE REPLACED WHEN IT REACHES 80% VALUE, 25% AGING MARGIN IS CONSIDERED FOR TUBULAR, VRLA AND NICD BATTERIES.
  • 82. CALCULATION OF NUMBER OF CELLS & ECV VMAX / VC NUMBER OF CELLS (NC) VMIN / NC END OF DISCHARGE VOLTAGE (ECV) MIN. DC BUS VOLTAGE (VMIN) CHARGING VOLTAGE PER CELL (VC) MAX. DC BUS VOLTAGE (VMAX)
  • 83. CALCULATION OF RAW CAPACITY END CELL VOLTAGE (ECV) BACK-UP DURATION SELECTED CELL TYPE CAPACITY FACTOR ‘F’ LOAD CURRENT ‘I’ BASIC RATED CAPACITY OF CELL C = I x F
  • 84. CALCULATION OF FINAL CAPACITY BASIC RATED CAPACITY OF CELL C = I x F FINAL CALCULATED CAPACITY CF = C x A x D x KT AGING FACTOR, A DESIGN MARGIN, D TEMPERATURE CORRECTION FACTOR, KT
  • 85. • ALL TYPES OF BATTERY LOSES CAPACITY WITH AGING (EXCEPT PLANTE) • THE END OF LIFE IS DEFINED AS THE TIME WHEN THE BATTERY CAPACITY REACHES 80% OF ITS RATED CAPACITY • THE BATTERY IS EXPECTED TO PERFORM THE DESIGNED DUTY EVEN AT THE END OF LIFE SITUATION • THE CAPACITY THUS NEEDS TO BE UPRATED TO TAKE CARE OF THIS INEVITABLE DEGRADATION AGING FACTOR RELEVANCE OF FACTORS
  • 86. MINIMUM OPERATING TEMPERATURE • ENERGY OUTPUT FROM A BATTERY IS DIRECTLY PROPORTIONAL TO THE AMBIENT TEMPERATURE • AT LOWER AMBIENT CAPACITY DECREASES – SO DOES THE BACK-UP AVAILABILITY • CAPACITY RATED AT STANDARD AMBIENT THUS NEEDS TO BE UPRATED FOR SAME OPERATION AT LOWER AMBIENT • A TEMPERATURE CORRECTION FACTOR THUS IS REQUIRED TO TAKE CARE OF THIS INEVITABLE CAPACITY LOSS RELEVANCE OF FACTORS
  • 87. CORRECTION FACTOR FOR MINIMUM AMBIENT TEMPERATURE OF T 0C KT = 1+ {(27 – T) X FT} / 100 WHERE KT = TEMPERATURE CORRECTION FACTOR T = MINIMUM AMBIENT TEMPERATURE FT = TEMPERATURE CO-EFFICIENT VALID FOR THE TYPE OF BATTERY SELECTED IN % PER DEGREE C RELEVANCE OF FACTORS • FOR TUBULAR 0.43% PER DEG. C @ C10 (AS PER IS1651) • FOR PLANTE 0.9% PER DEG. C @ C10 (AS PER IS1652) • FOR VRLA 0.43% PER DEG. C @ C10 (AS PER IS15549)
  • 88. •AS A STANDARD PRACTICE, A BUILD-UP OF 10% - 15% IS GENERALLY ACCEPTED. DESIGN MARGIN CATERS TO A. UNPLANNED AUGMENTATION OF PLANT INSTALLATION. B. ABERRATION OF EQUIPMENT PERFORMANCE/DUTY. C. UNEXPECTED LOWER AMBIENT THAN DESIGNED FOR. RELEVANCE OF FACTORS
  • 89. DC System • Battery • Battery Charger
  • 90. DC SYSTEM • BATTERY CHARGERS [TWO/THREE] • BATTERY BANKS [ONE/TWO] • DC DISTRIBUTION BOARDS [ONE/TWO] • DC FUSE BOARDS • UN EARTHED SYSTEM • CHARGER TROUBLE, DC EARTH FAULT AND DC VOLTAGE ABNORMAL ALARMS IN UCB
  • 91. 220 V DC SYSTEM Charger I 440 V 220 V DC Charger II Battery Bank Battery Bank Feeders 440 V 220 V DC Feeders DCDB
  • 92. Typical UPS System Module Power supply 440 V AC 220 V DC Battery 220 V DC 220 V AC UPS All Unit Controls & Protection 48 V, 15V, 24 V, DC Converter Inverter ACDB
  • 93. X X X X X X X X DG-1 DG-3 DG-2 DG SWGR-1 DG SWGR-2 UNIT EMER SWGR-1 UNIT EMER SWGR-2 UNIT EMER SWGR-3 UNIT EMER SWGR-4
  • 94. 220 V DC • FSSS • HT Breakers • Vacuum Breakers • HOTV/HORV • Deaerator Overflow Valve • GRP • HP Heater Protections • DC Fans & Pumps • Extraction FCNRV V/V’s • SADC • Trim Device • Load Shedding Relay • Scanner Air Fan Outlet & Emergency Damper • All DC Lights
  • 95. 220 V Supplies EMCC USS MAIN CHARGER RESERVE CHARGER UPS CHARGER-1 UPS CHARGER -2 DAS UPS CHARGER –1 DAS UPS CHARGER-2 +/- 24 VA DC CHARGER +/- 24 VB DC CHARGER DG SET BATTERY SYSTEM
  • 96. UNINTERRUPTED POWER SUPPLY • An uninterruptible power supply (UPS), uninterruptible power source or sometimes called a battery backup is a device which maintains a continuous supply of electric power to connected equipment by supplying power from a separate source when utility power is not available.
  • 97. CAPACITY • UPS units come in sizes ranging from units which will back up a single computer without monitor (around 200 VA) to units which will power entire data centers or buildings (several megawatts). • Larger UPS units typically work in conjunction with generators.
  • 98. UPS DESIGNS • The general categories of modern UPS systems are on-line or off-line, the latter often referred to as standby.
  • 99. ON-LINE UPS • ON-LINE UPS SYSTEMS PROVIDE THE HIGHEST LEVEL OF PROTECTION FOR MOST IMPORTANT EQUIPMENT. • THESE SYSTEMS USE A COMBINED DOUBLE-CONVERSION(AC TO DC/DC TO AC) WHICH CONTINUOUSLY POWERS THE LOAD,TO PROVIDE BOTH CONDITIONED POWER AND OUTAGE PROTECTION. • THEY PROVIDE PROTECTION AND ISOLATION FROM ALL TYPES OF POWER PROBLEMS,INCLUDING POWER SURGES,HIGH VOLTAGE SPIKE,SWITCHING TRANSIENTS,NOISE FREQUENCY VARIATION ETC. • THESE SYSTEMS ARE OFTEN USED FOR MISSION-CRITICAL APPLICATION THAT REQUIRE HIGH PRODUCTIVITY AND SYSTEM AVAILABILITY.
  • 100. MAJOR COMPONENTS OF UPS • CHARGER • BATTERY • INVERTER • STATIC SWITCH • ALTERNATE SUPPLY
  • 102.  Diode Rectifier  Thyristor Rectifier  Diode and DC/DC Converter (Chopper)  Active Rectifier (IGBT)  SMPS – Switch Mode Power Supply TECHNOLOGY ASSESSMENT
  • 103. TECHNOLOGY COMPARISON  Power Factor  Efficiency  Harmonic Distortion  Reliability / Availability / Service Support  Space Requirements  System Cost
  • 104. POWER FACTOR COMPARISON  Diode : Good  Thyristor : Low  Diode and Chopper : Good  Active Rectifier : Best  SMPS : Good
  • 105. EFFICIENCY COMPARISON  Diode : High  Thyristor Medium : High  Diode and Chopper : Low  Active Rectifier Medium : Low  SMPS : High
  • 106. HARMONIC COMPARISON  Diode : Medium  Thyristor : High  Diode and Chopper : Medium  Active Rectifier : Low  SMPS : Low
  • 107. RELIABILITY COMPARISON Based Upon Component Count of Rectifier Devices  Diode : High  Thyristor : High  Diode and Chopper : Low  Active Rectifier : Medium  SMPS : Medium
  • 108. SERVICE SKILL COMPARISON  Diode : Low  Thyristor : Medium  Diode and Chopper : High  Active Rectifier : High  SMPS : High
  • 109. SYSTEM COST COMPARISON  Diode Rectifier : 105%  Thyristor Rectifier : 100%  Diode & Chopper : 124%  Active Rectifier : 115%  SMPS : 105% Based upon past projects, component count and further developments.
  • 110. SPACE COMPARISON Diode : Average Thyristor : Larger – (with power factor compensation included) Diode and Chopper : Larger Active Rectifier : Average SMPS : Less
  • 111. CONCLUSIONS Considerations :  Total System Requirements  Future Provision of System Requirements  Customer’s Experience / Background  Technology comparison for exact project  All Technologies Will continue for near future
  • 112. FLOAT CUM BOOST CHARGERS-FCBC • Voltage • Current
  • 113. SIZING IN FLOAT MODE In float mode the charger shall be capable of meeting the trickle charging of both the battery banks, station continuous load current and starting current of largest DC drive.
  • 114. SIZING IN BOOST MODE In boost mode charger shall be capable of boost charging a fully discharged battery in 8-10 hours.
  • 116. CHARGER OPERATION • Float mode/controller auto mode-charger supplies at constant voltage(set),with current limiter in function. • Boost mode/controller in auto mode-charger supplies at constant current(set),with voltage limiter in function
  • 117. PERFORMANCE FEATURES • Soft start feature-set voltage in 15 sec. • Load limiter-80%-100% • AVR-better then 1% of set voltage • Voltage limiter • When energising the charger with fully charged battery connected plus 10% load shall not result in output voltage greater than 110% of voltage setting & charger to stablise to set value in 15 sec. • With change in load from 20% to 100 % and vice- versa, the momentary output voltage shall remain within 94% to 106% and should stablise in 2 sec. • Ripple content-less than 1%
  • 118. ANNUNCIATIONS • A.C. Supply Failure • Rectifier Fuse Failure • Surge Circuit Fuse Failure • Filter Fuse Failure • Load Limiter Operated • Charger Trip • Battery On Boost
  • 119. Battery Charger Manufacturers •AMARRAJA ,Tirupati •HBL,Hyderabad •Chabi Electricals,Jalgaon •Caldyne,Kolkata •Dubas
  • 120. Battery Battery Voltage stabilizer ACDB-1 ACDB-2 UNIT UNINTERRUPTED POWER SUPPLY 415 V AC EMCC CHARGER –2 INVERTER-2 STATIC SWITCH CHARGER-1 INVERTER-1 USS SSVS 240 V AC ALT SUPPLY Manual Bypass switch
  • 121. INVERTER • Inverters takes an input 210 to 280 V DC from chargers or battery and converts them to 240V AC. • First the DC voltage is converted to square wave using SCRs. • The SCRs gate pulses can be controlled to slightly alter frequency. • In latest UPS inverters IGBTs are being used.
  • 122. Battery Capacity • Expressed in ampere hour(AH) • Duration of discharge-10 hr for Plante/5 hr for Ni- Cd • End cell voltage-1.85 volt for Lead acid plante/1.0 volt for Ni-Cd • Ambient temperature-27 deg cent. • Electrolyte specific gravity-1.2+-.005 lead acid plante cells
  • 123. SELECTION OF BATTERY TYPE IN POWER PLANT • Power plant batteries standby duty require high discharge performance with continuously connected on float mode operation. • Expected Life of lead acid tubular is of the order of 8-10 years so in a power plant life of 25 years minimum two replacement would be required. • Lead acid PLANTE and Ni-Cd (alkaline) have expected life of 15-20 years hence only one replacement would be required in whole plant life. • In addition lead acid plante have much better discharge performance than tubular type for the specified emergency duration. • In view of above plante type lead acid or Ni-Cd high discharge batteries are specified for power plant applications. • Wherever there is space constraints VRLA batteries may be an option however this has also expected life of 8-10 years.
  • 124. CHARGING OF BATTERIES Nominal Voltage Float Voltage Boost Voltage Float Current Boost Current Lead Acid - Plante Ni - Cd 2.0V 2.1V - 2.25V 2.3V - 2.7V 1.4mA / AH 140mA / AH 1.2V 1.40V - 1.42V 1.5V - 1.7V 2.0mA / AH 200mA / AH
  • 125. CHARGER OPERATION • Float mode/controller auto mode-charger supplies at constant voltage(set),with current limiter in function. • Boost mode/controller in auto mode-charger supplies at constant current(set),with voltage limiter in function
  • 126. 220 V FLOAT CUM BOOST BATTERY CHARGER (i) Manufacture UPTRON POWERTRONICS LTD,Sahibabad (ii) A.C. input 415 V ± 10%, 3 ø, 50 Hz±5%, 69.7 A (iii) D.C. output voltage Float 220- 250 V Boost 200- 300 V Current Float 110A Boost 80 A (iv) Ripple 1% peak to peak without battery (v) Efficiency at full load More than 85% (vi) Voltage setting range (manual) 220 – 300 V (vii) Current setting range 50% to 100% of rated current (viii) Cooling AN (ix) Max. ambient temp. 500 C (x) Response time Less than 750 mSec