FIRE PROTECTION SYSTEMS
2
Fire Protection System Design
Strategy
 Comprehensive Strategy
 Prevent fires from starting in the first place
 Education
 Administrative procedures
 Signage
 Inspections
 Fire safety program
 Fire alarm and detection systems
 Detect fires early to initiate quick evacuation
 Design safe egress from building
 Exits, Stairwells, Corridors
 Emergency lighting and ventilation
3
Design Strategies (cont’d)
 Fire suppression systems
 Sprinkler
 Standpipe and Hose
 Chemical
 Smoke Control systems
 Remove smoke from exits
 Provide fleeing occupants with breathable air
4
Design Strategies (cont’d)
 Compartmentalization
 Break a building into small compartments to contain fire and
smoke
 Fire Separation
 Fire rated wall, floor, ceiling assemblies that impede
the spread of fire
 Use of non-combustible materials
 Use of low flame spread and smoke developed
finish material
5
Flame Spread
 ASTM E84 – Test Method for Surface-Burning
Characteristics of Building Materials (Steiner tunnel test).
Rates surface-burning characteristics of building materials
and interior finishes, and provides data on smoke density.
 Flame spread classifications:
 Class A: 0-25
 Class B: 26-75
 Class C: 76-200
 Local building codes generally restrict use of materials in
different occupancies based upon flame spread and smoke
developed ratings.
 For example, NYSED Manual of Planning Standards requires finishes
in corridors, passageways, stairways to be Class A.
6
Sources of Ignition
 Spontaneous Combustion
 Electrical Sources
 Arcing
 Lightning
 Mechanical
 Friction
 Other
 Intentional (arson)
 Cigarettes
7
Fire Issues
 Products of combustion – CO, CO2, other
gases
 Fire quickly consumes oxygen
 Lack of oxygen
 Rapid deterioration of human capabilities
 Muscle control
 Thinking, consciousness, etc.
 Poor visibility
8
Fire Issues (cont’d)
 Vertical shafts promote spread of smoke, heat
 Elevators
 Escalators
 Atriums
 HVAC systems can spread smoke
 Windowless buildings – prevent entry by firefighters
 Interior finishes – can spread fire, give off smoke
 High rise buildings (g.t. six stories) – complicate
firefighting, rescue
9
Fire Alarm and Detection Systems
 Design Standards
 Fire Code of NYS – defines minimum standards where fire alarm and
detection system is required, general design requirements
 NFPA 72 – National Fire Alarm Code – defines specific design
standards
 Functions of a fire alarm and detection system:
 Initiate alarm
 Manually
 Automatically
 Notify occupants
 Audible alarms
 Visual alarms
10
Functions (cont’d)
 Automatically signal fire department or central station
 Recall elevators
 Supervise special systems:
 Fire pump operation, power availability
 Sprinkler system status
 Unlock doors
 Automatically close doors that are part of fire separations
 Automatically release smoke relief hatches
 Control operation of HVAC supply and exhaust fans
 Total shut down
 Special smoke management systems
11
Typical Fire Alarm System
12
Fire Alarm Control Panel
13
Fire Alarm Systems (cont’d)
 Types
 Conventional (off/on “dumb” devices)
 Addressable
 Analog
 Digital
 Equipment
 Manual Fire Alarm Boxes (Pull Stations)
 Mounting – not less than 3.5 and not more than 4.5 ft above floor
level (ADA requires maximum 48” high forward reach)
 Spacing:
 At exit doorways within 5’ of each exit doorway on each floor; on both
sides of opening 40 feet and wider, and within 5 feet each side
 Additional boxes such that distance of travel to any box less than 200
feet on same floor
14
Manual Alarm Station at Exit
15
Fire Alarm Systems (cont’d)
 Heat Detectors
 Applications
 Where smoke is ordinarily present
 Top of elevator shafts where sprinklers are present
 Types
 Fixed
 Combination fixed/rate of rise
 Location
 On ceiling not less than 4” from sidewall, or on sidewall between
4” and 12” of ceiling
16
Fixed Type Heat Detector
17
Fire Alarm Systems (Cont’d)
 Heat Detectors (cont’d)
 Typical Spacing
 Fixed: 15’x15’
 Combination fixed/rate of rise: 50’x50’
 All points on ceiling within 0.7 x listed spacing
 Special considerations – beam construction,
sloped ceilings – refer to NFPA 72 for spacing
requirements.
18
Smoke From Cooking Appliances Can
Set Off Smoke Detector
19
Stages of a Fire
 Incipient – invisible combustion gases,
without smoke or flame, no appreciable heat
release
 Smoldering – heat still absent, combustion
gases now visible as smoke
 Flame – actual fire is produced, a column of
gases made luminous by intense heat
 Heat – follows concurrently or just after flame
stage – tremendous amounts of heat released
20
Smoke Detectors
 Types
 Spot
 Beam
 Design:
 Ionization
 Photoelectric
 Spot Detector Accessories
 Integral alarm
 Typical use – motels and similar sleeping spaces
21
Photoelectric Spot Smoke Detector
with Integral Alarm
 Photoelectric detectors
operate using principle of
“smoke obscuration”
 Smoke interposed in light
beam between small
emitter and detector
 Decreased light intensity at
detector causes alarm to
sound
 Device in photo also
includes integral alarm –
used in motels and similar
sleeping spaces.
22
Principle of Operation – Ionization
Detector
23
Smoke Detectors (cont’d)
 Applications
 Spot detectors
 For general fire detection
 Close doors, operate smoke dampers
 Beam detectors
 High ceilings where spot detectors impractical
 Location
 On ceiling not less than 4” from sidewall, or on sidewall between
4” and 12” of ceiling
24
Smoke Detector Mounted on Wall
25
Smoke Detectors (cont’d)
 Typical Spacing (spot)
 30’x30’
 All points on ceiling within 0.7 x listed spacing
 g.t. 3’-0” from HVAC diffusers, supply grilles
 Special considerations – beam construction,
sloped ceilings – refer to NFPA 72 for spacing
requirements.
26
Typical “Listed” Smoke Detector
Spacing
27
Incorrect Application of Smoke
Detector
 Area covered = 60’ x
15’ = 900 s.f.
 Distance to corner
exceeds 0.7 x listed
spacing (0.7 x 30 =
21’)
 Two smoke detectors
would be required for
this room.
28
Beam Smoke Detector
 Smoke rising to ceiling will
obscure light beam.
 Receiver will detect change
in beam intensity and cause
alarm to sound.
 Often used in atrium
spaces, high “cathedral
ceilings”, similar spaces.
29
Notification Appliances
 Audible
 Refer to NFPA 72 for sound pressure levels
 Mounting
 Wall – top not less than 90” a.f.f., not less than 6”
below ceiling (where ceiling heights allow)
 If combined with visual appliances, entire lens of
visual appliance not less than 80” nor greater than 96”
a.f.f.
 Spacing
 Such that they can be heard throughout building
 Refer to NFPA 72 for specific requirements
30
Audible Visual Device in School
Cafeteria
31
Audible Visual Fire Alarm Appliance
32
Notification Appliances (cont’d)
 Visual Appliances
 Location
 Wall mounted – entire lens 80” -96” a.f.f.
 Ceiling mounted permitted when device is specifically listed for
this application.
 Spacing
 Refer to NFPA 72
 When two or more in same field of view, must be synchronized
(can be harmful to persons with epilepsy)
33
Remote Annunciator Panel at School
80
 An annunciator panel
displays at remote entries
and other locations the
zone or device that is in
alarm – generally located at
main entries.
34
FIRE SUPPRESSION
SYSTEMS
35
Types of Fire Suppression Systems
 Standpipe and Hose Systems
A reliable water supply, piping, hose connections to
permit manual extinguishing of a fire.
 Sprinkler Systems
A reliable water supply, piping, sprinklers, to permit
automatic extinguishing of a fire.
 Chemical Extinguishing Systems
Both manual and automatic systems
Use a chemical extinguishing agent where water is not
effective, or cannot be used.
36
Standpipe and Hose Systems
Classification:
Class I – 2-1/2” hose connections for firefighter’s
use, 100 psi at uppermost hose connection.
Class II – 1-1/2” hose connections for occupant use,
100 psi at uppermost hose connection.
Class III – 2-1/2” and 1-1/2” hose connections for
both firefighter’s and occupant use.
37
Diagram of a Typical Standpipe
System
38
Standpipe Hose Valve at Intermediate
Stairwell Landing
39
Typical Backflow Preventer for Fire
Protection Service
 A backflow preventer
prevents water
contained in building
piping systems from
flowing back into the
community water main.
 Water piping in
buildings may contain
foul and/or hazardous
materials.
40
Classification (cont’d)
 Type I and III standpipes are the most
common.
 Design Standard
• NFPA 14 Standard for the Installation of
Standpipe, Private Hydrant, and Hose Systems.
• Current edition is 2003
• As of 2004, NYS Building Code adopts the 2000
edition.
41
Combined Systems
 A combined system is a standpipe that also supplies
automatic sprinklers on each floor.
 Combined systems were first permitted by NFPA in
1976 to encourage owners of high rise buildings that
already had standpipes to install sprinkler systems.
 A sprinkler crossmain is connected to the standpipe
at each floor. A typical connection detail is
contained in NFPA 14 Figure A-5-9.1.3.1 (a) and
(b).
42
Diagram of a Typical Combined
Sprinkler and Standpipe System
43
A Typical Flow Control Assembly
Located in a Stairwell
44
Buildings that Require Standpipe
and Hose Systems
 Buildings where standpipes and hose systems are
required:
 Any building where the highest floor level is 30 ft. or more
above the lowest level of fire department vehicle access.
 Places of Assembly
 Covered Mall Buildings (e.g. Shopping Malls)
 Stages
 Underground Buildings
 Check the applicable building ordinance for specifics
(NYS 905.3)
45
Water Supplies
 Water supply must be among the following:
• Public waterworks with adequate pressure
• Automatic fire pump connected to public
waterworks
• Manually controlled fire pump in combination
with pressure tanks.
• Pressure tanks installed in accordance with NFPA
22
46
Water Supplies (cont’d.)
• Manually controlled fire pumps operated by
remote control devices at each hose station.
• Gravity tanks in accordance with NFPA 22
• Automatic fire pumps connected to the public
waterworks are the most common.
47
Water Supply Capacity
 Water supply capacity
• The capacity of the supply is calculated as
follows:
 500 gpm for the first standpipe
 250 gpm for each additional standpipe
 Not to exceed 1250 gpm
 Water supply must have minimum 30 minutes
duration for calculated flow
48
Additional Classification of Standpipes
 Wet
• The standpipe system is always filled with water.
 Dry
• The standpipe system contains no water.
• Generally used only in unheated buildings (e.g., parking
garages.)
 Automatic
• Water supply capable of supplying system demand
automatically.
• Most common type
49
Additional Classification of Standpipes
(Cont’d)
 Manual
• Connected to small water supply to maintain water in the
system, but inadequate to meet demand.
• Relies on fire department pumper to supply necessary
system demand.
 Other types: semi-automatic dry, manual-dry (see
NFPA 14 for explanations.)
 The Building Ordinance (NYS Building Code)
prescribes which type is required.
50
Fire Pumps
 Fire Pumps
• Since most water main pressures are generally
less than 100 psi at the street, a fire pump is
usually required to provide adequate pressure.
• Fire pumps must be provided with an emergency
power source.
• Fire pumps generally require a separate, fire rated
(2 hr.) room or enclosure.
51
Typical Electric Fire Pump Installation
52
Location of Hose Connections
 Location of Hose Connections
• Height: not less than 3 ft and not more than 5 ft above
floor (usually 4 ft).
 Class I Systems
• In exit stairways at each intermediate landing between
floor levels.
• Each side of wall adjacent to exit openings of horizontal
exits.
• Each exit passageway at entrance from building areas into
passageway.
53
Location of Hose Connections (Cont’d)
 In covered mall buildings at entrance to each exit
passageway or exit corridor, and exterior public
entrances to mall.
 At highest landing of stairways with access to roof,
and on roof where stairways do not access the roof.
 Additional 2-1/2” hose connection at hydraulically
most remote riser to facilitate testing.
 See NFPA 14 for more requirements.
54
Location of Hose Connections
(Cont’d)
 Class II Systems
• 1-1/2” hose stations so that all portions of each
floor level are within 130 ft of a hose connection.
 Class III Systems
• As required for both Class I and Class I Systems
55
Drainage of Standpipes
 Each standpipe to be equipped with a means
for draining
 Usually a drain valve is located at lowest
point of standpipe, downstream of isolation
valve
 Drain to an approved location
• Often drained to spill at grade
56
Fire Department Connections
 At least one fire department connection for
each zone of each Class I and Class III system
 High rise buildings require two remotely
located fire department connections for each
zone
 Height: +18” to +48” above adjoining grade
57
Fire Department Connections (Cont’d)
 A check valve is required downstream.
 No shutoff valve is permitted between the fire
department connection and the system.
 Dry piping between connection and check
valve should be galvanized steel.
 Signage is required at each connection. See
NFPA 14, Ch. 4-3.5.2 for details.
58
Sprinkler Systems
 Definition and purpose – a reliable water supply, piping,
sprinklers, valves and accessories for the purpose of
automatically extinguishing a fire.
 Governing Design Standards
 Local building code or ordinance – prescribes where sprinkler
systems are required
 NFPA 13 Standard for the Installation of Sprinkler Systems –
prescribes how sprinkler systems are to be designed and constructed
 Factory Mutual (FM) – An insurance company standards
organization; it may, through the building owner’s insurance
company, impose additional restrictions/requirements for overall
building fire protection systems.
59
Sprinkler Systems (cont’d)
 Types of sprinkler systems:
 Wet
 Dry
 Pre-action
 Deluge
60
Sprinkler Systems (cont’d)
 Wet system
 Piping is filled with water under pressure at all
times.
 When one or more sprinkler heads open, water is
automatically discharged.
 Used in heated buildings or portions of buildings
that are heated.
 Most common type of system.
61
Diagram of a Wet Pipe Sprinkler
System with Water Motor Alarm
 Both pendant and
upright sprinklers may
be used.
 During operation, the
alarm check valve
diverts a small portion
of water to the water
motor alarm – does not
rely on electricity to
sound alarm.
62
A Typical Wet Pipe Sprinkler Alarm
Valve Installation
63
Wet Pipe Alarm Valve
64
Wet Pipe Sprinkler with Electric
Alarm
 An electric alarm bell is
operated through a water
flow switch inserted into
the main riser.
 When a sprinkler opens,
water flow activates flow
switch, and alarm sounds.
 Requires a reliable source
of power from an
emergency source.
65
Sprinkler systems (cont’d)
 Dry system
 Piping is filled with compressed air.
 A dry system valve blocks the entry of water into the
piping. Air pressure in the piping holds the valve closed.
 When one or more sprinkler heads open
 Air is first released through the head(s)
 Air pressure in the piping system drops.
 Dry system valve swings open.
 Water floods the piping system.
 Used in unheated buildings, or portions of buildings that
are not heated, e.g., attics.
66
Diagram of a Dry Pipe Sprinkler
System
 Upright heads must be
used, in order to allow
the piping to drain
completely.
67
Sprinkler systems (cont’d)
 Pre-action system
 Requires operation of both a fire detector and
a sprinkler head opening before water is
released.
 Piping is filled with pressurized air.
 A fire detection system (smoke, heat detectors, manual
pull station) is wired to the pre-action valve; valve is
opened only when fire detection system is activated.
 Water floods piping.
68
Pre-action system (cont’d)
 Water is released from each sprinkler head that
opens.
 Used for rooms that contain valuable equipment
or materials that could be damaged be release of
water, where fire detection must be verified
independently.
 Main frame computer rooms
 Laboratories
69
Diagram of a Pre-Action System
70
Sprinkler Systems (cont’d)
 Deluge System
 All sprinklers are open
 When water fills the piping system, all sprinklers
discharge water simultaneously
 Diagram is similar to pre-action system
 Applications:
 Where severe fire hazard exists that can be
extinguished safely with water
 E.g. – a Fireworks Factory
71
Sprinkler systems (cont’d)
 Where required:
 Governed by the local building code or ordinance
 If not required by code, insurance companies
often offer reduced rates, or won’t insure
buildings without sprinkler systems.
72
Some Sprinkler Types
 Recessed Pendant
Sprinkler
 Glass tube holds metal disc
seated in valve seat
 Glycerin in glass tube
expands when heated and
will shatter glass
 Water is released
 Spray pattern is established
by deflector
73
Recessed Pendant Sprinkler with Brass
Finish
74
Old Style Sprinkler with Fusible Link,
(Upright Style Shown)
75
Sprinkler with Wire Guard and
Deflector Disk (Pendant Style Shown)
 This sprinkler would be
used to protect combustible
materials in storage racks
 Wire guard protects
sprinkler from damage as
racks are loaded/unloaded
 Deflector plate prevents
water may be discharged
from above from cooling
this sprinkler and
preventing its operation
76
Concealed Sprinkler
 Decorative white disk is
soldered to the sprinkler
body – solder melts first,
plate falls to floor,
exposing sprinkler
 Exposed sprinkler will now
operate like a standard
sprinkler - releases water as
temperature increases
 Can be used in Light
Hazard Occupancies
77
Partial Data Sheet for a Typical
Concealed Sprinkler
78
Sidewall Sprinkler
79
Sprinkler systems (cont’d)
 Requirements for water supply capacity and
spacing of sprinklers depend upon the
building’s occupancy classification
 Occupancy Classes:
 Light
 Ordinary Group 1
 Ordinary Group 2
 Extra Group 1
 Extra Group 2
80
Light Hazard
 Quantity and/or combustibility of contents is
low; fires with relatively low rates of heat
release are expected.
 Examples:
 Churches
 Libraries
 Restaurant seating areas
81
Ordinary Hazard
 Group 1 – combustibility is low, quantity of
combustibles is moderate, stockpiles of
combustibles do not exceed 8 ft, fires with
moderate rates of heat release expected.
 Examples:
 Automobile parking and showrooms
 Bakeries
 Restaurant service areas
82
Ordinary Hazard (cont’d)
 Group 2 – quantity and combustibility of
contents moderate to high, stockpiles do not
exceed 12 ft, fires with moderate to high rates
of heat release expected.
 Examples:
 Chemical plants - ordinary
 Dry Cleaners
 Library large stack room areas
83
Extra Hazard
 Group 1 – combustibility is low, quantity of
combustibles is very high, dust, lint or other
materials are present, possibility of rapidly
developing fires with high rates of heat release, but
little or now combustible or flammable liquids.
 Examples:
 Aircraft hangers
 Plywood and particle board manufacturing
 Printing
84
Extra Hazard (cont’d)
 Group 2 – moderate to substantial amounts of
flammable or combustible liquids
 Examples:
 Flammable liquids spraying
 Plastics processing
 Varnish and paint dipping
 In all cases, refer to NFPA 13 and AHJ (Authority
Having Jurisdiction) for quidance in assessing
occupancy classification
85
Sprinkler systems (cont’d)
 Maximum Area of Coverage (Standard Spray
Upright and Pendant Sprinklers)
 Light hazard: 225 s.f., maximum 15’ between sprinklers
 Ordinary hazard: 130 s.f., maximum 15’ between
sprinklers
 Extra hazard: 90 s.f., maximum 12’ between sprinklers
(see NFPA 13 for exceptions)
 Protection Area per sprinklers:
 S x L, where S = spacing between sprinklers or twice
distance to end wall, whichever is greater.
 L = spacing between branch lines or twice the distance to
end wall, whichever is greater.
86
Sprinkler systems (cont’d)
 Maximum distance from walls: less than ½ spacing.
 Minimum distance to walls: 4”
 Where walls are angled or irregular, the maximum
distance to any point on floor – 0.75 spacing, with
maximum perpendicular distance to wall not
exceeded.
 Minimum distance between sprinklers: 6’ (see
exceptions NFPA 13)
87
Sprinkler Location
 Deflector position
 Standard spray pendant or upright heads:
minimum 1” to maximum 12” from ceiling.
 Standard spray sidewall sprinklers: minimum 4”
to maximum 6” from ceiling. (In special
situations, 6 to 12” – see NFPA 13)
 Critical point – the farther the sprinkler is from
the ceiling, the longer it will take for the heat to
collect at the ceiling plane and set off the
sprinkler.
88
Typical Symbols
89
Sprinkler Spacing Examples
 Light Hazard Occupancy
 225 s.f. per sprinkler
 Maximum 15’ between
branch lines and between
sprinklers on branch lines
 Maximum 15/2 = 7.5 from
wall to outermost sprinkler
and branch lines
 Here, S=L=15’
90
Sprinkler Spacing Example No. 2
 Occupancy Hazard:
Ordinary Group 1
 Maximum coverage
per sprinkler: 130 s.f.
 Maximum spacing: 15’
91
Example No. 2 – Proposed Solution
 Area of coverage is 10’x
13’ = 130 s.f.
 Maximum spacing is 13’,
which is less than the
maximum 15’ allowed
 Maximum distance to wall
is 6.5’, which is ½ the
largest spacing (13’)
 Yet this solution does not
comply with NFPA 13!
92
Example No. 2 (cont’d)
 Area of coverage of
sprinkler in NW corner
is: (6+5) x 13 = 141 s.f.
 The number of
sprinklers required is
actually (41’ x
39’)/130 s.f. per
sprinkler = 12.3; the
proposed solution has
just 12
93
Example No. 2 (cont’d)
 Here is one correct
solution.
 More sprinklers are
required in order to
comply with both
spacing and area of
coverage requirements.
 S=12’ (2 x 6); L=9’-8”
 A=12’ x 9’-8” =
116.04 s.f
94
Example No. 2 (cont’d)
 If a 2’x2’ suspended
tile ceiling is used, the
sprinklers will not be
centered within the
tiles.
95
Example No. 2 (conclusion)
 Since we have more
sprinklers than are needed,
we can shift the centerlines
slightly to achieve center of
tile placement of
sprinklers.
 In this example, the dashed
area represents greatest
coverage, = (5’-6” +5’-0”)
x (5’-0” + 6’-0”) = 126.5
s.f.
96
Sprinkler Systems (cont’d)
 Sprinkler Classifications
 Design and performance
 Area of coverage
 Speed of response
 Standard response
 Fast response
 Orientation
 Concealed
 Flush
 Pendent
 Recessed
 Sidewall
 Upright
97
Sprinkler Classifications (cont’d)
 Special service conditions
 Dry
 Corrosion resistant
 Intermediate level sprinkler/rack storage sprinkler

More Related Content

What's hot

Introductory training on fire water pumping system
Introductory training  on fire water pumping systemIntroductory training  on fire water pumping system
Introductory training on fire water pumping systemSabrul Jamil
 
Fire alarm system and common types of detectors
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectorsMuhammad Farid
 
Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"EzazulHaqueSiddique
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...RajyogFireServicesPv
 
Fire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfFire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfmohamedibrahim219956
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systemsMark Mikhaiel
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant systemFarahNaz96
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONASGHAR KHALIL
 
Smoke extraction in buildings
Smoke extraction in buildingsSmoke extraction in buildings
Smoke extraction in buildingsvysakhmanohar
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildingsHetvi Trada
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant systemFIRE KNOCK
 
Fire safety in building
Fire safety in buildingFire safety in building
Fire safety in buildingArvind Kumar
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System DesignMostafa Al Wakeel
 

What's hot (20)

Fire pumps
Fire pumpsFire pumps
Fire pumps
 
Fire fighting
Fire fightingFire fighting
Fire fighting
 
Fire fighting system
Fire fighting systemFire fighting system
Fire fighting system
 
Introductory training on fire water pumping system
Introductory training  on fire water pumping systemIntroductory training  on fire water pumping system
Introductory training on fire water pumping system
 
Fire alarm system and common types of detectors
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectors
 
Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"Fire Fighting "A Complete Handbook"
Fire Fighting "A Complete Handbook"
 
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...Fire Hydrant System/Sprinkler System Fire Fighting Systems  Fire Hydrant Syst...
Fire Hydrant System/Sprinkler System Fire Fighting Systems Fire Hydrant Syst...
 
Fire protection system ppt.
Fire protection system ppt.Fire protection system ppt.
Fire protection system ppt.
 
Fire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdfFire_Fighting_Course_Prepared_by.pdf
Fire_Fighting_Course_Prepared_by.pdf
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systems
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant system
 
Fire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptxFire Detection and Alarm System (FDAS).pptx
Fire Detection and Alarm System (FDAS).pptx
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATION
 
Smoke extraction in buildings
Smoke extraction in buildingsSmoke extraction in buildings
Smoke extraction in buildings
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildings
 
Fire hydrant system
Fire hydrant systemFire hydrant system
Fire hydrant system
 
Fire safety in building
Fire safety in buildingFire safety in building
Fire safety in building
 
Fire Protection System Design
Fire Protection System DesignFire Protection System Design
Fire Protection System Design
 
Fire protection
Fire protectionFire protection
Fire protection
 
Fundamentals of Fire Alarm System
Fundamentals of Fire Alarm SystemFundamentals of Fire Alarm System
Fundamentals of Fire Alarm System
 

Similar to Fire protection systems

Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdfssuser06d7b51
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfnipunwijewardhana
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Shubham .
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm systemsingh1515
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Mohammed Ullah
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Jed Concepcion
 
UNIT-V FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATIONUNIT-V    FIRE SAFETY INSTALLATION
UNIT-V FIRE SAFETY INSTALLATIONkarthi keyan
 
Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemSabrul Jamil
 
FDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFathimaNasi
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm systemsakshisankpal
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm systemsakshisankpal
 
Burglar alarm basics-6
Burglar alarm basics-6Burglar alarm basics-6
Burglar alarm basics-6grantlerc
 
Fm 403 Mod 10 Fire & Life Safety Systems
Fm 403 Mod 10   Fire & Life Safety SystemsFm 403 Mod 10   Fire & Life Safety Systems
Fm 403 Mod 10 Fire & Life Safety Systemsehamer
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfRiyaVerma238431
 
Class 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm SystemClass 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm Systemirfanmechengr
 

Similar to Fire protection systems (20)

FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
Fire safety
Fire safety Fire safety
Fire safety
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
UNIT-V FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATIONUNIT-V    FIRE SAFETY INSTALLATION
UNIT-V FIRE SAFETY INSTALLATION
 
UNIT-5.pptx
UNIT-5.pptxUNIT-5.pptx
UNIT-5.pptx
 
Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm System
 
FDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm system
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Chapter 08
Chapter 08Chapter 08
Chapter 08
 
Burglar alarm basics-6
Burglar alarm basics-6Burglar alarm basics-6
Burglar alarm basics-6
 
Fm 403 Mod 10 Fire & Life Safety Systems
Fm 403 Mod 10   Fire & Life Safety SystemsFm 403 Mod 10   Fire & Life Safety Systems
Fm 403 Mod 10 Fire & Life Safety Systems
 
topic 3-fire fighting.pdf
topic 3-fire fighting.pdftopic 3-fire fighting.pdf
topic 3-fire fighting.pdf
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
 
Class 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm SystemClass 1 | NFPA 72 | Overview Fire Alarm System
Class 1 | NFPA 72 | Overview Fire Alarm System
 

Recently uploaded

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 

Recently uploaded (20)

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 

Fire protection systems

  • 2. 2 Fire Protection System Design Strategy  Comprehensive Strategy  Prevent fires from starting in the first place  Education  Administrative procedures  Signage  Inspections  Fire safety program  Fire alarm and detection systems  Detect fires early to initiate quick evacuation  Design safe egress from building  Exits, Stairwells, Corridors  Emergency lighting and ventilation
  • 3. 3 Design Strategies (cont’d)  Fire suppression systems  Sprinkler  Standpipe and Hose  Chemical  Smoke Control systems  Remove smoke from exits  Provide fleeing occupants with breathable air
  • 4. 4 Design Strategies (cont’d)  Compartmentalization  Break a building into small compartments to contain fire and smoke  Fire Separation  Fire rated wall, floor, ceiling assemblies that impede the spread of fire  Use of non-combustible materials  Use of low flame spread and smoke developed finish material
  • 5. 5 Flame Spread  ASTM E84 – Test Method for Surface-Burning Characteristics of Building Materials (Steiner tunnel test). Rates surface-burning characteristics of building materials and interior finishes, and provides data on smoke density.  Flame spread classifications:  Class A: 0-25  Class B: 26-75  Class C: 76-200  Local building codes generally restrict use of materials in different occupancies based upon flame spread and smoke developed ratings.  For example, NYSED Manual of Planning Standards requires finishes in corridors, passageways, stairways to be Class A.
  • 6. 6 Sources of Ignition  Spontaneous Combustion  Electrical Sources  Arcing  Lightning  Mechanical  Friction  Other  Intentional (arson)  Cigarettes
  • 7. 7 Fire Issues  Products of combustion – CO, CO2, other gases  Fire quickly consumes oxygen  Lack of oxygen  Rapid deterioration of human capabilities  Muscle control  Thinking, consciousness, etc.  Poor visibility
  • 8. 8 Fire Issues (cont’d)  Vertical shafts promote spread of smoke, heat  Elevators  Escalators  Atriums  HVAC systems can spread smoke  Windowless buildings – prevent entry by firefighters  Interior finishes – can spread fire, give off smoke  High rise buildings (g.t. six stories) – complicate firefighting, rescue
  • 9. 9 Fire Alarm and Detection Systems  Design Standards  Fire Code of NYS – defines minimum standards where fire alarm and detection system is required, general design requirements  NFPA 72 – National Fire Alarm Code – defines specific design standards  Functions of a fire alarm and detection system:  Initiate alarm  Manually  Automatically  Notify occupants  Audible alarms  Visual alarms
  • 10. 10 Functions (cont’d)  Automatically signal fire department or central station  Recall elevators  Supervise special systems:  Fire pump operation, power availability  Sprinkler system status  Unlock doors  Automatically close doors that are part of fire separations  Automatically release smoke relief hatches  Control operation of HVAC supply and exhaust fans  Total shut down  Special smoke management systems
  • 13. 13 Fire Alarm Systems (cont’d)  Types  Conventional (off/on “dumb” devices)  Addressable  Analog  Digital  Equipment  Manual Fire Alarm Boxes (Pull Stations)  Mounting – not less than 3.5 and not more than 4.5 ft above floor level (ADA requires maximum 48” high forward reach)  Spacing:  At exit doorways within 5’ of each exit doorway on each floor; on both sides of opening 40 feet and wider, and within 5 feet each side  Additional boxes such that distance of travel to any box less than 200 feet on same floor
  • 15. 15 Fire Alarm Systems (cont’d)  Heat Detectors  Applications  Where smoke is ordinarily present  Top of elevator shafts where sprinklers are present  Types  Fixed  Combination fixed/rate of rise  Location  On ceiling not less than 4” from sidewall, or on sidewall between 4” and 12” of ceiling
  • 16. 16 Fixed Type Heat Detector
  • 17. 17 Fire Alarm Systems (Cont’d)  Heat Detectors (cont’d)  Typical Spacing  Fixed: 15’x15’  Combination fixed/rate of rise: 50’x50’  All points on ceiling within 0.7 x listed spacing  Special considerations – beam construction, sloped ceilings – refer to NFPA 72 for spacing requirements.
  • 18. 18 Smoke From Cooking Appliances Can Set Off Smoke Detector
  • 19. 19 Stages of a Fire  Incipient – invisible combustion gases, without smoke or flame, no appreciable heat release  Smoldering – heat still absent, combustion gases now visible as smoke  Flame – actual fire is produced, a column of gases made luminous by intense heat  Heat – follows concurrently or just after flame stage – tremendous amounts of heat released
  • 20. 20 Smoke Detectors  Types  Spot  Beam  Design:  Ionization  Photoelectric  Spot Detector Accessories  Integral alarm  Typical use – motels and similar sleeping spaces
  • 21. 21 Photoelectric Spot Smoke Detector with Integral Alarm  Photoelectric detectors operate using principle of “smoke obscuration”  Smoke interposed in light beam between small emitter and detector  Decreased light intensity at detector causes alarm to sound  Device in photo also includes integral alarm – used in motels and similar sleeping spaces.
  • 22. 22 Principle of Operation – Ionization Detector
  • 23. 23 Smoke Detectors (cont’d)  Applications  Spot detectors  For general fire detection  Close doors, operate smoke dampers  Beam detectors  High ceilings where spot detectors impractical  Location  On ceiling not less than 4” from sidewall, or on sidewall between 4” and 12” of ceiling
  • 25. 25 Smoke Detectors (cont’d)  Typical Spacing (spot)  30’x30’  All points on ceiling within 0.7 x listed spacing  g.t. 3’-0” from HVAC diffusers, supply grilles  Special considerations – beam construction, sloped ceilings – refer to NFPA 72 for spacing requirements.
  • 26. 26 Typical “Listed” Smoke Detector Spacing
  • 27. 27 Incorrect Application of Smoke Detector  Area covered = 60’ x 15’ = 900 s.f.  Distance to corner exceeds 0.7 x listed spacing (0.7 x 30 = 21’)  Two smoke detectors would be required for this room.
  • 28. 28 Beam Smoke Detector  Smoke rising to ceiling will obscure light beam.  Receiver will detect change in beam intensity and cause alarm to sound.  Often used in atrium spaces, high “cathedral ceilings”, similar spaces.
  • 29. 29 Notification Appliances  Audible  Refer to NFPA 72 for sound pressure levels  Mounting  Wall – top not less than 90” a.f.f., not less than 6” below ceiling (where ceiling heights allow)  If combined with visual appliances, entire lens of visual appliance not less than 80” nor greater than 96” a.f.f.  Spacing  Such that they can be heard throughout building  Refer to NFPA 72 for specific requirements
  • 30. 30 Audible Visual Device in School Cafeteria
  • 31. 31 Audible Visual Fire Alarm Appliance
  • 32. 32 Notification Appliances (cont’d)  Visual Appliances  Location  Wall mounted – entire lens 80” -96” a.f.f.  Ceiling mounted permitted when device is specifically listed for this application.  Spacing  Refer to NFPA 72  When two or more in same field of view, must be synchronized (can be harmful to persons with epilepsy)
  • 33. 33 Remote Annunciator Panel at School 80  An annunciator panel displays at remote entries and other locations the zone or device that is in alarm – generally located at main entries.
  • 35. 35 Types of Fire Suppression Systems  Standpipe and Hose Systems A reliable water supply, piping, hose connections to permit manual extinguishing of a fire.  Sprinkler Systems A reliable water supply, piping, sprinklers, to permit automatic extinguishing of a fire.  Chemical Extinguishing Systems Both manual and automatic systems Use a chemical extinguishing agent where water is not effective, or cannot be used.
  • 36. 36 Standpipe and Hose Systems Classification: Class I – 2-1/2” hose connections for firefighter’s use, 100 psi at uppermost hose connection. Class II – 1-1/2” hose connections for occupant use, 100 psi at uppermost hose connection. Class III – 2-1/2” and 1-1/2” hose connections for both firefighter’s and occupant use.
  • 37. 37 Diagram of a Typical Standpipe System
  • 38. 38 Standpipe Hose Valve at Intermediate Stairwell Landing
  • 39. 39 Typical Backflow Preventer for Fire Protection Service  A backflow preventer prevents water contained in building piping systems from flowing back into the community water main.  Water piping in buildings may contain foul and/or hazardous materials.
  • 40. 40 Classification (cont’d)  Type I and III standpipes are the most common.  Design Standard • NFPA 14 Standard for the Installation of Standpipe, Private Hydrant, and Hose Systems. • Current edition is 2003 • As of 2004, NYS Building Code adopts the 2000 edition.
  • 41. 41 Combined Systems  A combined system is a standpipe that also supplies automatic sprinklers on each floor.  Combined systems were first permitted by NFPA in 1976 to encourage owners of high rise buildings that already had standpipes to install sprinkler systems.  A sprinkler crossmain is connected to the standpipe at each floor. A typical connection detail is contained in NFPA 14 Figure A-5-9.1.3.1 (a) and (b).
  • 42. 42 Diagram of a Typical Combined Sprinkler and Standpipe System
  • 43. 43 A Typical Flow Control Assembly Located in a Stairwell
  • 44. 44 Buildings that Require Standpipe and Hose Systems  Buildings where standpipes and hose systems are required:  Any building where the highest floor level is 30 ft. or more above the lowest level of fire department vehicle access.  Places of Assembly  Covered Mall Buildings (e.g. Shopping Malls)  Stages  Underground Buildings  Check the applicable building ordinance for specifics (NYS 905.3)
  • 45. 45 Water Supplies  Water supply must be among the following: • Public waterworks with adequate pressure • Automatic fire pump connected to public waterworks • Manually controlled fire pump in combination with pressure tanks. • Pressure tanks installed in accordance with NFPA 22
  • 46. 46 Water Supplies (cont’d.) • Manually controlled fire pumps operated by remote control devices at each hose station. • Gravity tanks in accordance with NFPA 22 • Automatic fire pumps connected to the public waterworks are the most common.
  • 47. 47 Water Supply Capacity  Water supply capacity • The capacity of the supply is calculated as follows:  500 gpm for the first standpipe  250 gpm for each additional standpipe  Not to exceed 1250 gpm  Water supply must have minimum 30 minutes duration for calculated flow
  • 48. 48 Additional Classification of Standpipes  Wet • The standpipe system is always filled with water.  Dry • The standpipe system contains no water. • Generally used only in unheated buildings (e.g., parking garages.)  Automatic • Water supply capable of supplying system demand automatically. • Most common type
  • 49. 49 Additional Classification of Standpipes (Cont’d)  Manual • Connected to small water supply to maintain water in the system, but inadequate to meet demand. • Relies on fire department pumper to supply necessary system demand.  Other types: semi-automatic dry, manual-dry (see NFPA 14 for explanations.)  The Building Ordinance (NYS Building Code) prescribes which type is required.
  • 50. 50 Fire Pumps  Fire Pumps • Since most water main pressures are generally less than 100 psi at the street, a fire pump is usually required to provide adequate pressure. • Fire pumps must be provided with an emergency power source. • Fire pumps generally require a separate, fire rated (2 hr.) room or enclosure.
  • 51. 51 Typical Electric Fire Pump Installation
  • 52. 52 Location of Hose Connections  Location of Hose Connections • Height: not less than 3 ft and not more than 5 ft above floor (usually 4 ft).  Class I Systems • In exit stairways at each intermediate landing between floor levels. • Each side of wall adjacent to exit openings of horizontal exits. • Each exit passageway at entrance from building areas into passageway.
  • 53. 53 Location of Hose Connections (Cont’d)  In covered mall buildings at entrance to each exit passageway or exit corridor, and exterior public entrances to mall.  At highest landing of stairways with access to roof, and on roof where stairways do not access the roof.  Additional 2-1/2” hose connection at hydraulically most remote riser to facilitate testing.  See NFPA 14 for more requirements.
  • 54. 54 Location of Hose Connections (Cont’d)  Class II Systems • 1-1/2” hose stations so that all portions of each floor level are within 130 ft of a hose connection.  Class III Systems • As required for both Class I and Class I Systems
  • 55. 55 Drainage of Standpipes  Each standpipe to be equipped with a means for draining  Usually a drain valve is located at lowest point of standpipe, downstream of isolation valve  Drain to an approved location • Often drained to spill at grade
  • 56. 56 Fire Department Connections  At least one fire department connection for each zone of each Class I and Class III system  High rise buildings require two remotely located fire department connections for each zone  Height: +18” to +48” above adjoining grade
  • 57. 57 Fire Department Connections (Cont’d)  A check valve is required downstream.  No shutoff valve is permitted between the fire department connection and the system.  Dry piping between connection and check valve should be galvanized steel.  Signage is required at each connection. See NFPA 14, Ch. 4-3.5.2 for details.
  • 58. 58 Sprinkler Systems  Definition and purpose – a reliable water supply, piping, sprinklers, valves and accessories for the purpose of automatically extinguishing a fire.  Governing Design Standards  Local building code or ordinance – prescribes where sprinkler systems are required  NFPA 13 Standard for the Installation of Sprinkler Systems – prescribes how sprinkler systems are to be designed and constructed  Factory Mutual (FM) – An insurance company standards organization; it may, through the building owner’s insurance company, impose additional restrictions/requirements for overall building fire protection systems.
  • 59. 59 Sprinkler Systems (cont’d)  Types of sprinkler systems:  Wet  Dry  Pre-action  Deluge
  • 60. 60 Sprinkler Systems (cont’d)  Wet system  Piping is filled with water under pressure at all times.  When one or more sprinkler heads open, water is automatically discharged.  Used in heated buildings or portions of buildings that are heated.  Most common type of system.
  • 61. 61 Diagram of a Wet Pipe Sprinkler System with Water Motor Alarm  Both pendant and upright sprinklers may be used.  During operation, the alarm check valve diverts a small portion of water to the water motor alarm – does not rely on electricity to sound alarm.
  • 62. 62 A Typical Wet Pipe Sprinkler Alarm Valve Installation
  • 64. 64 Wet Pipe Sprinkler with Electric Alarm  An electric alarm bell is operated through a water flow switch inserted into the main riser.  When a sprinkler opens, water flow activates flow switch, and alarm sounds.  Requires a reliable source of power from an emergency source.
  • 65. 65 Sprinkler systems (cont’d)  Dry system  Piping is filled with compressed air.  A dry system valve blocks the entry of water into the piping. Air pressure in the piping holds the valve closed.  When one or more sprinkler heads open  Air is first released through the head(s)  Air pressure in the piping system drops.  Dry system valve swings open.  Water floods the piping system.  Used in unheated buildings, or portions of buildings that are not heated, e.g., attics.
  • 66. 66 Diagram of a Dry Pipe Sprinkler System  Upright heads must be used, in order to allow the piping to drain completely.
  • 67. 67 Sprinkler systems (cont’d)  Pre-action system  Requires operation of both a fire detector and a sprinkler head opening before water is released.  Piping is filled with pressurized air.  A fire detection system (smoke, heat detectors, manual pull station) is wired to the pre-action valve; valve is opened only when fire detection system is activated.  Water floods piping.
  • 68. 68 Pre-action system (cont’d)  Water is released from each sprinkler head that opens.  Used for rooms that contain valuable equipment or materials that could be damaged be release of water, where fire detection must be verified independently.  Main frame computer rooms  Laboratories
  • 69. 69 Diagram of a Pre-Action System
  • 70. 70 Sprinkler Systems (cont’d)  Deluge System  All sprinklers are open  When water fills the piping system, all sprinklers discharge water simultaneously  Diagram is similar to pre-action system  Applications:  Where severe fire hazard exists that can be extinguished safely with water  E.g. – a Fireworks Factory
  • 71. 71 Sprinkler systems (cont’d)  Where required:  Governed by the local building code or ordinance  If not required by code, insurance companies often offer reduced rates, or won’t insure buildings without sprinkler systems.
  • 72. 72 Some Sprinkler Types  Recessed Pendant Sprinkler  Glass tube holds metal disc seated in valve seat  Glycerin in glass tube expands when heated and will shatter glass  Water is released  Spray pattern is established by deflector
  • 73. 73 Recessed Pendant Sprinkler with Brass Finish
  • 74. 74 Old Style Sprinkler with Fusible Link, (Upright Style Shown)
  • 75. 75 Sprinkler with Wire Guard and Deflector Disk (Pendant Style Shown)  This sprinkler would be used to protect combustible materials in storage racks  Wire guard protects sprinkler from damage as racks are loaded/unloaded  Deflector plate prevents water may be discharged from above from cooling this sprinkler and preventing its operation
  • 76. 76 Concealed Sprinkler  Decorative white disk is soldered to the sprinkler body – solder melts first, plate falls to floor, exposing sprinkler  Exposed sprinkler will now operate like a standard sprinkler - releases water as temperature increases  Can be used in Light Hazard Occupancies
  • 77. 77 Partial Data Sheet for a Typical Concealed Sprinkler
  • 79. 79 Sprinkler systems (cont’d)  Requirements for water supply capacity and spacing of sprinklers depend upon the building’s occupancy classification  Occupancy Classes:  Light  Ordinary Group 1  Ordinary Group 2  Extra Group 1  Extra Group 2
  • 80. 80 Light Hazard  Quantity and/or combustibility of contents is low; fires with relatively low rates of heat release are expected.  Examples:  Churches  Libraries  Restaurant seating areas
  • 81. 81 Ordinary Hazard  Group 1 – combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not exceed 8 ft, fires with moderate rates of heat release expected.  Examples:  Automobile parking and showrooms  Bakeries  Restaurant service areas
  • 82. 82 Ordinary Hazard (cont’d)  Group 2 – quantity and combustibility of contents moderate to high, stockpiles do not exceed 12 ft, fires with moderate to high rates of heat release expected.  Examples:  Chemical plants - ordinary  Dry Cleaners  Library large stack room areas
  • 83. 83 Extra Hazard  Group 1 – combustibility is low, quantity of combustibles is very high, dust, lint or other materials are present, possibility of rapidly developing fires with high rates of heat release, but little or now combustible or flammable liquids.  Examples:  Aircraft hangers  Plywood and particle board manufacturing  Printing
  • 84. 84 Extra Hazard (cont’d)  Group 2 – moderate to substantial amounts of flammable or combustible liquids  Examples:  Flammable liquids spraying  Plastics processing  Varnish and paint dipping  In all cases, refer to NFPA 13 and AHJ (Authority Having Jurisdiction) for quidance in assessing occupancy classification
  • 85. 85 Sprinkler systems (cont’d)  Maximum Area of Coverage (Standard Spray Upright and Pendant Sprinklers)  Light hazard: 225 s.f., maximum 15’ between sprinklers  Ordinary hazard: 130 s.f., maximum 15’ between sprinklers  Extra hazard: 90 s.f., maximum 12’ between sprinklers (see NFPA 13 for exceptions)  Protection Area per sprinklers:  S x L, where S = spacing between sprinklers or twice distance to end wall, whichever is greater.  L = spacing between branch lines or twice the distance to end wall, whichever is greater.
  • 86. 86 Sprinkler systems (cont’d)  Maximum distance from walls: less than ½ spacing.  Minimum distance to walls: 4”  Where walls are angled or irregular, the maximum distance to any point on floor – 0.75 spacing, with maximum perpendicular distance to wall not exceeded.  Minimum distance between sprinklers: 6’ (see exceptions NFPA 13)
  • 87. 87 Sprinkler Location  Deflector position  Standard spray pendant or upright heads: minimum 1” to maximum 12” from ceiling.  Standard spray sidewall sprinklers: minimum 4” to maximum 6” from ceiling. (In special situations, 6 to 12” – see NFPA 13)  Critical point – the farther the sprinkler is from the ceiling, the longer it will take for the heat to collect at the ceiling plane and set off the sprinkler.
  • 89. 89 Sprinkler Spacing Examples  Light Hazard Occupancy  225 s.f. per sprinkler  Maximum 15’ between branch lines and between sprinklers on branch lines  Maximum 15/2 = 7.5 from wall to outermost sprinkler and branch lines  Here, S=L=15’
  • 90. 90 Sprinkler Spacing Example No. 2  Occupancy Hazard: Ordinary Group 1  Maximum coverage per sprinkler: 130 s.f.  Maximum spacing: 15’
  • 91. 91 Example No. 2 – Proposed Solution  Area of coverage is 10’x 13’ = 130 s.f.  Maximum spacing is 13’, which is less than the maximum 15’ allowed  Maximum distance to wall is 6.5’, which is ½ the largest spacing (13’)  Yet this solution does not comply with NFPA 13!
  • 92. 92 Example No. 2 (cont’d)  Area of coverage of sprinkler in NW corner is: (6+5) x 13 = 141 s.f.  The number of sprinklers required is actually (41’ x 39’)/130 s.f. per sprinkler = 12.3; the proposed solution has just 12
  • 93. 93 Example No. 2 (cont’d)  Here is one correct solution.  More sprinklers are required in order to comply with both spacing and area of coverage requirements.  S=12’ (2 x 6); L=9’-8”  A=12’ x 9’-8” = 116.04 s.f
  • 94. 94 Example No. 2 (cont’d)  If a 2’x2’ suspended tile ceiling is used, the sprinklers will not be centered within the tiles.
  • 95. 95 Example No. 2 (conclusion)  Since we have more sprinklers than are needed, we can shift the centerlines slightly to achieve center of tile placement of sprinklers.  In this example, the dashed area represents greatest coverage, = (5’-6” +5’-0”) x (5’-0” + 6’-0”) = 126.5 s.f.
  • 96. 96 Sprinkler Systems (cont’d)  Sprinkler Classifications  Design and performance  Area of coverage  Speed of response  Standard response  Fast response  Orientation  Concealed  Flush  Pendent  Recessed  Sidewall  Upright
  • 97. 97 Sprinkler Classifications (cont’d)  Special service conditions  Dry  Corrosion resistant  Intermediate level sprinkler/rack storage sprinkler