SlideShare a Scribd company logo
1 of 88
Fire Sprinkler Systems
Guy R. Grant, PE
University of Illinois at Urbana-Champaign
Why would I want to pay for a
fire protection system in my
building when I have smoke
detectors?
For people and facilities
A fire protection system does more than protect the
building. It is also a key component in the life
safety strategy against fires. It both notifies the
occupants of a fire and it suppresses the fire. For
instance, if the building is a low-rise office or
school building, fire sprinklers are proven to be
greater value than smoke detectors. Consequently,
having sprinklers in these buildings will allow the
designer longer travel distances to exits whereas
having smoke detectors in these buildings affords
the designer no such benefits.
Importance of Fire Sprinklers
• Automatic sprinklers are widely recognized as the
number one tool of fire protection
• In over one hundred years of use, there has never
been a multiple fatality of building occupants from
fire in a building with a properly designed,
installed, and maintained sprinkler system
• Sprinklers respond to a fire while it is still small,
preventing the fire from developing into a major
threat
How reliable are sprinklers?
• Records of fires in buildings with
supervised automatic fire sprinkler systems
have indicated successful extinguishment or
control in more than 99% of fire incidents.
No other fire protection system or feature
has a comparable record of reliability.
• Most fires are contained by one or two
sprinklers.
What about water damage?
• Because sprinklers attack the fire while it is still
small, the total amount of water needed for fire
suppression is small (often less than 50 gallons per
minute)
• Without sprinkler protection, a fire is permitted to
grow and the fire department will typically apply
hundreds of gallons of water per minute during their
operations
• For this reason, total amounts of water used in
sprinklered buildings approximate one-tenth the
amounts used for fires in nonsprinklered buildings
What about water damage?
• The likelihood of a sprinkler discharging water in
the absence of a fire is very small
• Each model of sprinkler is subjected to rigorous
laboratory tests to guarantee long-term integrity,
and every single sprinkler is hydrostatically tested
at twice the maximum system water pressure prior
to leaving the factory
• Sprinkler guards should be used in environments
where sprinklers could be damaged
Aren’t Sprinkler Systems
Expensive?
• No, in fact sprinklers can often reduce the total
cost of construction
• Typically, sprinkler systems can be installed for
about 1% of building cost, or less than $2 per
square foot
• If the decision to install sprinklers is made early
enough in the planning process, sprinklers can
actually reduce total construction costs through
the use of code incentives or “trade-ups”
Aren’t Sprinkler Systems
Expensive?
• In recognition of the superior fire protection
afforded by sprinklers, codes permit reductions in
fire resistance ratings, longer exit travel distances,
and a wider range of interior finish materials in
sprinklered buildings
• Insurance rates are substantially less for
sprinklered facilities
• These incentives make it possible to build a safer
building for less money
The best fire protection system is…
…the one that works when it’s
needed.
Reliability
• Chose the appropriate system for the application.
• The right system is typically the most cost
effective one from a risk management perspective.
• Design the simplest system that can be used.
• Proper inspection, maintenance, and testing is a
must.
Sprinkler System Components
• Basic components:
– Sprinklers
– System piping
– A dependable water source
– Most systems also require an alarm and
system control valves
Sprinkler Head Components
• The typical sprinkler
consists of a frame,
thermal operated
linkage, cap, orifice, and
deflector
• Styles of each
component may vary
but the basic principles
of each remain the same
Sprinkler Head Components
• Frame
– The frame provides the main structural
component which holds the sprinkler together.
– The water supply pipe connects to the sprinkler
at the base of the frame
– The frame holds the thermal linkage and cap in
place, and supports the deflector during
discharge
Sprinkler Head Components
• Thermal linkage
– The thermal linkage is the component which
controls water release
– Under normal conditions the linkage holds the
cap in place and prevents water flow
– Common linkage styles include soldered metal
levers, frangible glass bulbs, and solder pellets
Sprinkler Head Components
• Cap
– The cap provides the water tight seal which is
located over the sprinkler orifice.
– This component is held in place by the thermal
linkage
– Operation of the linkage causes the cap to fall
from position and permit water flow
Sprinkler Head Components
• Orifice
– A machined opening at the base of the sprinkler frame
– It is from this opening which extinguishing water flows
• Deflector
– The deflector is mounted on the frame opposite the
orifice
– The purpose of this component is to break up the water
stream discharging from the orifice into a more
efficient extinguishing pattern
– Deflector styles determine how the sprinkler is
mounted
Types of Sprinkler Heads
• Common sprinkler mounting styles include
Upright
Sidewall
Pendent
How does a fire sprinkler work?
The typical sprinkler head consists of a
plug held in place by a trigger mechanism.
The most common type of trigger is a
glass bulb filled with a
liquid that expands
when heated.
A less commonly used
type of trigger consists
of two metal plates held together
by a solder link. When the solder
melts, two spring arms pull the
plates apart, releasing the plug.
How does a fire sprinkler work?
The liquid in the glass bulb is designed
to expand ad break the tube at a certain
temperature. The most common are
designed to break at 155 degrees.
How does a fire sprinkler work?
The plug is forced out by the pressurized
water behind it and deflected away. The
water sprays over the deflector plate
which is designed to distribute it in an
even pattern directly over the source of the
fire. Contrary to what is sometimes shown
on television shows, all sprinklers in the
building do not operate simultaneously.
Sprinkler System Components
• Other major components include
– Control valves : A sprinkler system must be
capable of shut down after the fire has been
controlled, and for periodic maintenance and
modification. Control valves provide this
function.
– Alarms : Alarms alert building occupants and
emergency forces when a sprinkler water flow
occurs. Alarms are also provided to alert
building management when a sprinkler valve is
closed
Sprinkler System Components
• Drain and test connections : Most sprinkler
systems have provisions to drain pipes during
system maintenance. Test connections are usually
provided to simulate the flow of a sprinkler flow,
thereby verifying the working condition of alarms
• Fire hose connections: Fire fighters will often
supplement sprinkler systems with hoses.
Firefighting tasks are enhanced by installing hose
connections to sprinkler system piping.
Sprinkler System Components
• Backflow preventer: The normal backflow
requirement for an automatic fire sprinkler system
is a double check valve assembly. A backflow
preventer prevents the backflow of polluted water
into the potable water supply. A reduced pressure
type backflow preventer is required if the piping
does or can contain hazardous substances.
Types of sprinkler systems
• Wet
• Dry
• Deluge
• Pre-action
• Water Mist
Wet Pipe Sprinkler Systems
• A wet pipe sprinkler system uses automatic
sprinklers attached to a piping system filled with
water and connected to a water supply so that water
discharges immediately from sprinklers opened by
heat from a fire
• Most common type of system
• Used for buildings where there is no risk of freezing
• Quick to react because water under pressure is
always in the pipework
• Wet pipe systems required for multi-story or high-
rise building and for life safety, such as those
installed in shopping centers
Dry Pipe Sprinkler System
• A dry pipe sprinkler system is one in which pipes
are filled with pressurized air, rather than water
• This air holds a remote valve, known as a dry pipe
valve, in a closed position
• The dry-pipe valve prevents water from entering
the pipe until a fire causes one or more sprinkler to
operate. Once this happens, the air escapes and the
dry pipe valve releases.
• Water then enters the pipe, flowing through open
sprinklers onto the fire.
• Used where there is a risk of frost damage
• WARNING: Frequent operation of compressor
means trouble! Get help immediately!
Deluge Sprinkler Systems
• The arrangement of deluge system piping is
similar to a wet or dry pipe system with two
major differences:
– Standard sprinklers are used but they are all open.
The activating elements (fusible link or glass bulb)
have been removed so that when the control valve is
opened, water will flow from all of the sprinklers
and deluge the are with water
– The deluge valve is normally closed. The valve is
opened by the activation of a separate fire detection
system
Deluge Sprinkler Systems
• The detection system is installed in the
same area as the sprinklers
• Deluge systems are used in places that are
considered high hazard areas such as power
plants, aircraft hangars, and chemical
storage or processing facilities.
• Deluge systems are needed where high
velocity suppression is necessary to prevent
fire spread.
Pre-action Sprinkler Systems
• The pre-action sprinkler system is similar to the
deluge sprinkler system except that the sprinklers
are not open; they are closed sprinklers with
fusible links or glass bulbs
• For a single interlocked system, the pre-action
valve is normally closed and operated by a
separate fire detection system. Activation of a fire
detector will open the pre-action valve, allowing
water to enter the system piping.
Pre-action Sprinkler Systems
• Water will not flow from the sprinklers
until heat from the fire activates the
operating element in individual sprinklers
• Used where it is not acceptable to have the
pipes full of water until there is a fire (e.g.
computer suites)
• Double interlock only for areas subject to
freezing!
Water Mist Systems
• Water mist systems include many of the same
elements found in automatic sprinkler systems, but
the application of water is different
• These systems use very fine water spray (mist)
that absorbs heat, displaces oxygen, or blocks
radiant heat to control, suppress, or extinguish
fires
• Water mist systems are typically used for small
confined areas, such as inside equipment
enclosures or cabinets
Other related systems…
• Standpipe system
• Clean Agent system
Standpipe System
• Standpipes are an arrangement of piping,
valves, hose connections and allied
equipment installed in a building or
structure with the hose connections located
in such a manner that the water can be
discharged through attached hoses and
nozzles
Standpipe Systems
• Standpipe systems provide fire hose
connections within a building or industrial
complex
• Hose connections are fed by a supply pipe
(often referred to as a riser) and are located
throughout the facility, usually on each
floor
Standpipe Systems
• Four methods in which water is supplied to
standpipes:
– Wet standpipe in which water is supplied
directly from a water main (or through a fire
pump if higher pressures are needed). Water
supply valve is always open and the system is
always under water pressure
– Dry manual standpipe in which there is no
permanent water supply. Water must be
supplied by the fire department
Standpipe Systems
• Four methods (cont.)
– Dry standpipe in which a connection to a water
main is provided by a manual control valve
which is kept closed. The standpipe system
remains dry until needed
– Dry automatic standpipe in which the valve
controlling water to the system is automatic, as
with a dry pipe valve. Water is admitted to the
system when a hose valve is opened and air
pressure in the system is released
Clean Agent System
• Commonly comprised of inert gases or safer
HCFCs
• Can dilute the amount of oxygen to prevent
combustion or can cool reactants on the
molecular level below the heat of combustion.
Clean Agent Systems
• Clean, nonconductive, noncorrosive – good
for important electronics
• Environmentally friendlier than Halon
• React quickly – triggered by smoke and/or
heat detectors
• High first cost – costly to recharge
• One shot to extinguish fire - best if coupled
with sprinklers
Design of Sprinkler Systems
• Sprinkler system piping is installed in
accordance with one of two methods:
– Pipe schedule system
– Hydraulically designed system
• Pipe schedule systems are not allowed for
new installations
• The first step is to determine the
classification of hazard
A Design Application
• Large drop sprinklers attack the fire plume
that develops in atriums due to the delay in
sprinkler operation from the height issue
• Ordinary Group II Hazard Classification
(.20 gpm/ft2
over 1500 ft2
) provides an
adequate amount of water to suppress
typical atrium fuel loadings
Occupancy Classifications
• The occupancy or use of the building will
predominantly determine the type of system
required:
– Light Hazard
– Ordinary Hazard
• Group 1
• Group 2
– Extra Hazard
• Group 1
• Group 2
Pipe – Schedule System
• The number of sprinklers fed by a given
pipe size is determined by schedules given
in sprinkler installation rules
• Installation rules vary with the occupancy
of the area to be protected
Hydraulically Designed System
• Most sprinklers require 7 psi (minimum) to
operate
• Quick analysis:
– Determine worst hazard (ex: Small office
building is Light Hazard throughout)
– Select design density and corresponding area of
sprinkler operation (our ex: .10 gpm/ft2
/1500 ft2)
– Determine inside water demand (.1 x 1500 x 1.25
= 187.5 gpm)
Hydraulically Designed System
• Quick analysis (cont.):
– Add pipe, fittings, devices, backflow preventer,
and elevator losses
– 21 + 7 psi = 28 @ 187.5 gpm
– Add 100 gpm for hoses
– 28 @ 287.5 gpm at city
psix 21)'15433.0(455 ≈+++
(pipe) (ftgs) (BFP) (elev.)
Hydraulically Designed System
• Note: Building square footage has little
effect on the need for a fire pump.
However, the hazard classification and
building height do have a significant effect
on whether a fire pump is needed.
Do I really need a fire pump?
• Installing a fire pump is often the default rather
than something that must prove it’s needed
• Many are not comfortable deciding if a fire
protection system can do without one.
• Fire pumps are great when needed but not
desired if not needed.
Cost
Reliability
How do I know if a pump is needed?
• Look at highest fire hazard classifications
• Look at available flow and pressure from
utility
• Look at building elevations
• Perform basic hydraulic calculations
• Can standpipe design be manual wet?
Basic Fire Pump Calculations
Basic Fire Pump Calculations
Density Diversity
Basic Fire Pump Calculations
Basic Fire Pump Calculations
54
-0.6
-4.0 (BFP)
-17.3
-15
-7.0
10.1psi cushion
Fire Pump Selection
• Consider resulting city water pressure when pump
is flowing 150% of its rating (city water pressure
must not drop below 20 psi)
• Consider resulting system water pressure when at
pump churn (standard fittings and components are
only rated for 175 psi)
• Jockey (maintenance) pump should be selected to
maintain system pressure above fire pump starting
pressure
Water Supply Requirements
• Every automatic sprinkler system shall have
at least one automatic water supply
• Water supply treatment
– Water supplies and environmental conditions
will be evaluated for the existence of microbes
and conditions that contribute to
microbiologically influenced corrosion (MIC)
Installation of Sprinkler Systems
• Basic requirements include
– Position, location, spacing, and use of sprinklers
• Determination of the protection area of coverage
• Maximum/Minimum distance between sprinklers
• Maximum/Minimum distance of sprinkler from
walls
– System protection area limitations
– Application of sprinkler types
• Requirements may vary depending on type
of system used
• For any system, pre-lubed grooved
couplings are recommended
Wet Pipe Sprinkler System
Requirements
• Must be reliably heated. Overhangs and
chases on exterior walls cannot be trusted
• Normal black steel piping is fine for wet
systems
• CPVC can be used in many applications
Dry Pipe Sprinkler System
Requirements
• Gridded dry pipe system are not allowed
• Air pressure should be maintained on dry pipe
systems throughout the year
• The compressed air supply should be from a
source available at all times – Initial charge with
Nitrogen
• Galvanized black steel pipe
• Dry systems should be drained completely to
minimize corrosion – No roll groove ends
• Use accelerators only when absolutely necessary
Inspection, Testing, &
Maintenance of Sprinkler Systems
• Maintaining adequate fire protection systems is as
critical as the original decision to install these systems
• Because fire suppression, detection, and alarm systems
are generally not used on a routine basis, their state of
readiness is not immediately apparent
• The periodic inspection, testing, and maintenance of
fire detection and suppression systems are essential to
ensure successful performance when these systems are
needed
Inspection
• Visual examination of the sprinkler system
to verify that it appears to be in operating
condition and free of physical damage
• Visual examination of storage and general
environment surrounding sprinkler system
Inspection
• Sprinklers
– Inspected from floor level annually
– Should not show signs of leakage
– Should be free of corrosion, foreign materials,
paint, and physical damage
– Should be installed in the proper orientation
Inspection
• Pipe and Fittings
– Should be in good condition
– Free of mechanical damage, leakage, corrosion,
and misalignment
– Piping should not be subjected to external loads
by materials either resting on the pipe or hung
from the pipe
Inspection
• Hangers and Seismic Bracing
– Should not be damaged or loose
• Gauges
– Wet pipe systems : Should be inspected
monthly to ensure that they are in good
condition and that normal water supply
pressure is being maintained
– Dry, pre-action, and deluge systems : Should be
inspected weekly to ensure that normal air and
water pressures are being maintained
Testing
• Sprinklers
– Sample sprinklers submitted to a recognized testing
laboratory acceptable to the authority having jurisdiction for
field service testing
– Test procedures repeated at 10-year intervals
– If one sprinkler within a representative sample fails to meet
the test requirement, all sprinklers represented by that
sample shall be replaced
• Drains
– Put ITC (Inspector’s Test Connection) for wet systems at
the riser. Reduces corrosion in piping, lessens chances of
obstructions to sprinklers and it makes testing easier
– System main drain must discharge to a place that can accept
full flow under pressure and gravity drain completely
Testing
• Pumps, alarms, and valves also need to be tested
and exercised on schedule for reliability and
longevity. Keep records on all tests
• NFPA 25 provides descriptions of these tests and
recommended forms
Maintenance
Fire protection systems require little
maintenance when properly cared for.
• Sprinklers
– Replacement sprinklers shall have the proper
characteristics for the application intended. They
should be the same type as the adjacent existing
sprinklers.
– A supply of spare sprinklers (never fewer than 6)
shall be maintained on the premises so that any
sprinklers that have operated or been damaged in
any way can be promptly replaced
• Dry pipe systems shall be kept dry at all
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• Over the past years an increasing number of
leaks and other corrosion related problems
have been associated with microbial or
bacterial activity in fire protection piping
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• What is Microbiologically Influenced
Corrosion (MIC)?
– MIC is one of the many forms of corrosion that
can affect sprinkler systems
– MIC is not a new corrosion mechanism;
however, its association to fire protection
piping is relatively new
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How does MIC affect sprinkler systems?
– Because of its nature and the complexity of fire
protection piping, MIC is not easily controlled
in fire protection systems
– MIC can affect any piping within the sprinkler
system, however, branchlines and risers seem
to be more seriously affected
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How does MIC affect sprinkler systems?
– MIC generally results in the growth of biofilms
and nodules within the piping
– Nodules and biofilm may result in increased
friction loss, and affect the ability of the pipe to
carry the necessary flow
– MIC may also affect sprinklers and valves, and
block water motor gongs, and alarm lines and
other components of a fire protection system
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How to protect sprinkler systems from MIC
– Existing sprinkler systems:
• Investigate for possible corrosion problems and
obstructed waterways, pinhole leaks, or other signs of
corrosion in pipes, valves or sprinkler heads
• Flush sprinkler systems where investigation reveals
obstructions of the waterway
• Replace any section of piping that contains obstructions
that cannot become removed by flushing procedures*
• Reinvestigate systems for waterway obstruction annually.
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How to protect sprinkler systems from MIC
– New Sprinkler Systems:
• Use new, clean, coated pipe for all new sprinkler
system installations and retrofits
• Do not use chlorine for disinfecting purposes
• Do not leave open pipe exposed where it could
accumulate dust, dirt, water and other residue prior to
installation
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How to protect sprinkler systems from MIC
– New wet-pipe sprinkler systems:
• Avoid repeated cycles of system shutdowns where
the system is drained and recharged
• Avoid air gaps (pockets) within the system, which
can expose piping to dry/wet conditions. Air gaps can
be avoided by providing means for air release at the
highest point of each branchline
Prevention and Control of Internal
Corrosion in Sprinkler Systems
• How to protect sprinkler systems from MIC
– New dry pipe and pre-action systems:
• Avoid the use of roll grooved joints. Roll grooved
joints in a dry sprinkler system promote water
accumulation that can result in preferred corrosion
sites
• Install pipe with proper pitch to promote drainage of
all testing water and water vapor condensate within
piping
• Keep low point drains clean and drain condensate as
needed to prevent water accumulation
Prevention and Control of Internal
Corrosion in Sprinkler Systems
Heavy tubercle formation in
a 8 in. sprinkler pipe
Corrosion at roll groove in a
wet pipe system
Earthquake Protection
• Uncontrolled differential movement can cause
damage when fire protection systems are not
provided in a systematic manner with the
necessary features that incorporate sway bracing,
flexibility, clearances, and anchorage where
needed
• The most common type of damage is water
damage due to water leakage from broken
overhead sprinkler piping or sprinklers, primarily
due to lack of sway bracing where needed
Earthquake Protection
• How to adequately protect sprinkler
systems from earthquake damage
– Brace piping or equipment to minimize
uncontrolled differential movement between
piping or equipment and the structure to which
it is attached
– Provide flexibility on piping systems and on
other equipment where differential movement
between portions of those piping systems or
equipment is expected
Earthquake Protection
• How to adequately protect sprinkler
systems from earthquake damage
– Provide clearance between piping or equipment
and structural members, walls, floors, or other
objects so that potential damage from impact is
minimized
– Provide anchorage to minimize potential sliding
and/or overturning
Earthquake Protection
• How to adequately protect sprinkler
systems from earthquake damage
– Use appropriate types of pipe hangers and sway
bracing, properly locate them, and properly
attach them to the structure to minimize the
potential for pullout
– Use appropriate types of piping and pipe
joining methods to minimize potential pipe
breaks
What to do with a broken fire
line under floor?
1. Replaced RPZ with DDC BFP
2. Fed 4” HDPE thru 6” DI pipe
References
• Factory Mutual Global Property Loss
Prevention Data Books
• National Fire Protection Association
National Fire Codes Pamphlets 13, 14 and
25

More Related Content

What's hot

Fire protection system...
Fire protection system...Fire protection system...
Fire protection system...AnkitaGorhe
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systemsMark Mikhaiel
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxMEP ENGINEER'S SERVICES
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildingsHetvi Trada
 
Active fire protection system
Active fire protection systemActive fire protection system
Active fire protection systemgauravashist
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Bowen Ngo
 
Clean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire SuppressionClean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire SuppressionBen Adams
 
Fire protection system
Fire protection systemFire protection system
Fire protection systemDeepak Thapa
 
Fire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyFire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyMuhammad Muhyuddin
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONASGHAR KHALIL
 
FIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGFIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGKuldeep Kumar
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm SystemsJ.T.A.JONES
 

What's hot (20)

Fire protection system...
Fire protection system...Fire protection system...
Fire protection system...
 
Fire fighting systems
Fire fighting systemsFire fighting systems
Fire fighting systems
 
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptxFIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
FIRE FIGHTING NOTES PART 01 BY ER. EZAZUL HAQUE SIDDIQUE pptx
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
fire protection
fire protectionfire protection
fire protection
 
Basics of Fire fighting
Basics of Fire fightingBasics of Fire fighting
Basics of Fire fighting
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildings
 
Active fire protection system
Active fire protection systemActive fire protection system
Active fire protection system
 
Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...Nfpa20 standard for the installation of stationary pumps for fire protection ...
Nfpa20 standard for the installation of stationary pumps for fire protection ...
 
Sprinkler system
Sprinkler systemSprinkler system
Sprinkler system
 
Fire Protection
Fire ProtectionFire Protection
Fire Protection
 
Clean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire SuppressionClean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire Suppression
 
fire protection
fire protectionfire protection
fire protection
 
Fire protection system
Fire protection systemFire protection system
Fire protection system
 
Fire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyFire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughly
 
1 Fire safety design principles
1  Fire safety design principles1  Fire safety design principles
1 Fire safety design principles
 
Fire fighting system
Fire fighting systemFire fighting system
Fire fighting system
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATION
 
FIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDINGFIRE SAFETY PLAN IN A BUILDING
FIRE SAFETY PLAN IN A BUILDING
 
Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 

Similar to Fire Protection System Design

Overview of Automatic Fire Sprinkler Systems.pptx
Overview of Automatic Fire Sprinkler Systems.pptxOverview of Automatic Fire Sprinkler Systems.pptx
Overview of Automatic Fire Sprinkler Systems.pptxM&E Engineer
 
BS2 group assignment
BS2 group assignment BS2 group assignment
BS2 group assignment jk tan
 
Bs powerpoint slides
Bs powerpoint slidesBs powerpoint slides
Bs powerpoint slideslohwenjun
 
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptxGlyzaMayeBMagdua
 
FIRE FIGHTING Syllabus for for suppresion.pdf
FIRE FIGHTING Syllabus for for suppresion.pdfFIRE FIGHTING Syllabus for for suppresion.pdf
FIRE FIGHTING Syllabus for for suppresion.pdfKj Aswin
 
Fire Protection System.pptx
Fire Protection System.pptxFire Protection System.pptx
Fire Protection System.pptxSatyamRaj25
 
Fighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered BuildingsFighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered BuildingsAaron Johnson
 
Fire Protection Systems Areeba Siddiqui.pptx
Fire Protection Systems Areeba Siddiqui.pptxFire Protection Systems Areeba Siddiqui.pptx
Fire Protection Systems Areeba Siddiqui.pptxAreeba Siddiqui
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentationakbar_ali
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)Esa Shaikh
 
Water_Detection_System.pptx
Water_Detection_System.pptxWater_Detection_System.pptx
Water_Detection_System.pptxABHILASH183001
 
UNIT III PRINCIPLES OF ILLUMINATION
UNIT III	PRINCIPLES OF ILLUMINATION	UNIT III	PRINCIPLES OF ILLUMINATION
UNIT III PRINCIPLES OF ILLUMINATION karthi keyan
 

Similar to Fire Protection System Design (20)

MODULE - 5 (2).pdf
MODULE - 5 (2).pdfMODULE - 5 (2).pdf
MODULE - 5 (2).pdf
 
Overview of Automatic Fire Sprinkler Systems.pptx
Overview of Automatic Fire Sprinkler Systems.pptxOverview of Automatic Fire Sprinkler Systems.pptx
Overview of Automatic Fire Sprinkler Systems.pptx
 
BS2 group assignment
BS2 group assignment BS2 group assignment
BS2 group assignment
 
Bs powerpoint slides
Bs powerpoint slidesBs powerpoint slides
Bs powerpoint slides
 
fire fighting System
fire fighting Systemfire fighting System
fire fighting System
 
2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a2.5 suppression.sprinklers.wk12a
2.5 suppression.sprinklers.wk12a
 
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx
21.3_Active Fire Protection and Suppression_MAGDUA&MANILA.pptx
 
FIRE FIGHTING Syllabus for for suppresion.pdf
FIRE FIGHTING Syllabus for for suppresion.pdfFIRE FIGHTING Syllabus for for suppresion.pdf
FIRE FIGHTING Syllabus for for suppresion.pdf
 
fire hydrant system .pptx
fire hydrant system .pptxfire hydrant system .pptx
fire hydrant system .pptx
 
Fire Protection System.pptx
Fire Protection System.pptxFire Protection System.pptx
Fire Protection System.pptx
 
PWD training
PWD trainingPWD training
PWD training
 
Firefighting & HVAC.pdf
Firefighting & HVAC.pdfFirefighting & HVAC.pdf
Firefighting & HVAC.pdf
 
Fighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered BuildingsFighting Fires in Sprinklered Buildings
Fighting Fires in Sprinklered Buildings
 
Fire Protection Systems Areeba Siddiqui.pptx
Fire Protection Systems Areeba Siddiqui.pptxFire Protection Systems Areeba Siddiqui.pptx
Fire Protection Systems Areeba Siddiqui.pptx
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
Fs sprinkler systems
Fs sprinkler systemsFs sprinkler systems
Fs sprinkler systems
 
Chapter 05
Chapter 05Chapter 05
Chapter 05
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)
 
Water_Detection_System.pptx
Water_Detection_System.pptxWater_Detection_System.pptx
Water_Detection_System.pptx
 
UNIT III PRINCIPLES OF ILLUMINATION
UNIT III	PRINCIPLES OF ILLUMINATION	UNIT III	PRINCIPLES OF ILLUMINATION
UNIT III PRINCIPLES OF ILLUMINATION
 

More from Mostafa Al Wakeel

More from Mostafa Al Wakeel (9)

Flexible Ducts
Flexible DuctsFlexible Ducts
Flexible Ducts
 
BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)BMS Design (BAS-Building Automation System)
BMS Design (BAS-Building Automation System)
 
Basics of building fire protection design
Basics of building fire protection designBasics of building fire protection design
Basics of building fire protection design
 
Air Duct Leakage
Air Duct LeakageAir Duct Leakage
Air Duct Leakage
 
Fire pumps in brief
Fire pumps in briefFire pumps in brief
Fire pumps in brief
 
Interactive damper selection guide
Interactive damper selection guideInteractive damper selection guide
Interactive damper selection guide
 
Fire suppression
Fire suppressionFire suppression
Fire suppression
 
Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019Engineer Mostafa Al Wakeel C.V.-2019
Engineer Mostafa Al Wakeel C.V.-2019
 
Fm 200 calculator
Fm 200 calculatorFm 200 calculator
Fm 200 calculator
 

Recently uploaded

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixingviprabot1
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 

Recently uploaded (20)

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Effects of rheological properties on mixing
Effects of rheological properties on mixingEffects of rheological properties on mixing
Effects of rheological properties on mixing
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 

Fire Protection System Design

  • 1. Fire Sprinkler Systems Guy R. Grant, PE University of Illinois at Urbana-Champaign
  • 2. Why would I want to pay for a fire protection system in my building when I have smoke detectors?
  • 3. For people and facilities A fire protection system does more than protect the building. It is also a key component in the life safety strategy against fires. It both notifies the occupants of a fire and it suppresses the fire. For instance, if the building is a low-rise office or school building, fire sprinklers are proven to be greater value than smoke detectors. Consequently, having sprinklers in these buildings will allow the designer longer travel distances to exits whereas having smoke detectors in these buildings affords the designer no such benefits.
  • 4. Importance of Fire Sprinklers • Automatic sprinklers are widely recognized as the number one tool of fire protection • In over one hundred years of use, there has never been a multiple fatality of building occupants from fire in a building with a properly designed, installed, and maintained sprinkler system • Sprinklers respond to a fire while it is still small, preventing the fire from developing into a major threat
  • 5.
  • 6. How reliable are sprinklers? • Records of fires in buildings with supervised automatic fire sprinkler systems have indicated successful extinguishment or control in more than 99% of fire incidents. No other fire protection system or feature has a comparable record of reliability. • Most fires are contained by one or two sprinklers.
  • 7. What about water damage? • Because sprinklers attack the fire while it is still small, the total amount of water needed for fire suppression is small (often less than 50 gallons per minute) • Without sprinkler protection, a fire is permitted to grow and the fire department will typically apply hundreds of gallons of water per minute during their operations • For this reason, total amounts of water used in sprinklered buildings approximate one-tenth the amounts used for fires in nonsprinklered buildings
  • 8. What about water damage? • The likelihood of a sprinkler discharging water in the absence of a fire is very small • Each model of sprinkler is subjected to rigorous laboratory tests to guarantee long-term integrity, and every single sprinkler is hydrostatically tested at twice the maximum system water pressure prior to leaving the factory • Sprinkler guards should be used in environments where sprinklers could be damaged
  • 9. Aren’t Sprinkler Systems Expensive? • No, in fact sprinklers can often reduce the total cost of construction • Typically, sprinkler systems can be installed for about 1% of building cost, or less than $2 per square foot • If the decision to install sprinklers is made early enough in the planning process, sprinklers can actually reduce total construction costs through the use of code incentives or “trade-ups”
  • 10. Aren’t Sprinkler Systems Expensive? • In recognition of the superior fire protection afforded by sprinklers, codes permit reductions in fire resistance ratings, longer exit travel distances, and a wider range of interior finish materials in sprinklered buildings • Insurance rates are substantially less for sprinklered facilities • These incentives make it possible to build a safer building for less money
  • 11. The best fire protection system is…
  • 12. …the one that works when it’s needed.
  • 13. Reliability • Chose the appropriate system for the application. • The right system is typically the most cost effective one from a risk management perspective. • Design the simplest system that can be used. • Proper inspection, maintenance, and testing is a must.
  • 14. Sprinkler System Components • Basic components: – Sprinklers – System piping – A dependable water source – Most systems also require an alarm and system control valves
  • 15. Sprinkler Head Components • The typical sprinkler consists of a frame, thermal operated linkage, cap, orifice, and deflector • Styles of each component may vary but the basic principles of each remain the same
  • 16. Sprinkler Head Components • Frame – The frame provides the main structural component which holds the sprinkler together. – The water supply pipe connects to the sprinkler at the base of the frame – The frame holds the thermal linkage and cap in place, and supports the deflector during discharge
  • 17. Sprinkler Head Components • Thermal linkage – The thermal linkage is the component which controls water release – Under normal conditions the linkage holds the cap in place and prevents water flow – Common linkage styles include soldered metal levers, frangible glass bulbs, and solder pellets
  • 18. Sprinkler Head Components • Cap – The cap provides the water tight seal which is located over the sprinkler orifice. – This component is held in place by the thermal linkage – Operation of the linkage causes the cap to fall from position and permit water flow
  • 19. Sprinkler Head Components • Orifice – A machined opening at the base of the sprinkler frame – It is from this opening which extinguishing water flows • Deflector – The deflector is mounted on the frame opposite the orifice – The purpose of this component is to break up the water stream discharging from the orifice into a more efficient extinguishing pattern – Deflector styles determine how the sprinkler is mounted
  • 20. Types of Sprinkler Heads • Common sprinkler mounting styles include Upright Sidewall Pendent
  • 21. How does a fire sprinkler work? The typical sprinkler head consists of a plug held in place by a trigger mechanism. The most common type of trigger is a glass bulb filled with a liquid that expands when heated. A less commonly used type of trigger consists of two metal plates held together by a solder link. When the solder melts, two spring arms pull the plates apart, releasing the plug.
  • 22. How does a fire sprinkler work? The liquid in the glass bulb is designed to expand ad break the tube at a certain temperature. The most common are designed to break at 155 degrees.
  • 23. How does a fire sprinkler work? The plug is forced out by the pressurized water behind it and deflected away. The water sprays over the deflector plate which is designed to distribute it in an even pattern directly over the source of the fire. Contrary to what is sometimes shown on television shows, all sprinklers in the building do not operate simultaneously.
  • 24. Sprinkler System Components • Other major components include – Control valves : A sprinkler system must be capable of shut down after the fire has been controlled, and for periodic maintenance and modification. Control valves provide this function. – Alarms : Alarms alert building occupants and emergency forces when a sprinkler water flow occurs. Alarms are also provided to alert building management when a sprinkler valve is closed
  • 25. Sprinkler System Components • Drain and test connections : Most sprinkler systems have provisions to drain pipes during system maintenance. Test connections are usually provided to simulate the flow of a sprinkler flow, thereby verifying the working condition of alarms • Fire hose connections: Fire fighters will often supplement sprinkler systems with hoses. Firefighting tasks are enhanced by installing hose connections to sprinkler system piping.
  • 26. Sprinkler System Components • Backflow preventer: The normal backflow requirement for an automatic fire sprinkler system is a double check valve assembly. A backflow preventer prevents the backflow of polluted water into the potable water supply. A reduced pressure type backflow preventer is required if the piping does or can contain hazardous substances.
  • 27. Types of sprinkler systems • Wet • Dry • Deluge • Pre-action • Water Mist
  • 28. Wet Pipe Sprinkler Systems • A wet pipe sprinkler system uses automatic sprinklers attached to a piping system filled with water and connected to a water supply so that water discharges immediately from sprinklers opened by heat from a fire • Most common type of system • Used for buildings where there is no risk of freezing • Quick to react because water under pressure is always in the pipework • Wet pipe systems required for multi-story or high- rise building and for life safety, such as those installed in shopping centers
  • 29. Dry Pipe Sprinkler System • A dry pipe sprinkler system is one in which pipes are filled with pressurized air, rather than water • This air holds a remote valve, known as a dry pipe valve, in a closed position • The dry-pipe valve prevents water from entering the pipe until a fire causes one or more sprinkler to operate. Once this happens, the air escapes and the dry pipe valve releases. • Water then enters the pipe, flowing through open sprinklers onto the fire. • Used where there is a risk of frost damage • WARNING: Frequent operation of compressor means trouble! Get help immediately!
  • 30. Deluge Sprinkler Systems • The arrangement of deluge system piping is similar to a wet or dry pipe system with two major differences: – Standard sprinklers are used but they are all open. The activating elements (fusible link or glass bulb) have been removed so that when the control valve is opened, water will flow from all of the sprinklers and deluge the are with water – The deluge valve is normally closed. The valve is opened by the activation of a separate fire detection system
  • 31. Deluge Sprinkler Systems • The detection system is installed in the same area as the sprinklers • Deluge systems are used in places that are considered high hazard areas such as power plants, aircraft hangars, and chemical storage or processing facilities. • Deluge systems are needed where high velocity suppression is necessary to prevent fire spread.
  • 32. Pre-action Sprinkler Systems • The pre-action sprinkler system is similar to the deluge sprinkler system except that the sprinklers are not open; they are closed sprinklers with fusible links or glass bulbs • For a single interlocked system, the pre-action valve is normally closed and operated by a separate fire detection system. Activation of a fire detector will open the pre-action valve, allowing water to enter the system piping.
  • 33. Pre-action Sprinkler Systems • Water will not flow from the sprinklers until heat from the fire activates the operating element in individual sprinklers • Used where it is not acceptable to have the pipes full of water until there is a fire (e.g. computer suites) • Double interlock only for areas subject to freezing!
  • 34. Water Mist Systems • Water mist systems include many of the same elements found in automatic sprinkler systems, but the application of water is different • These systems use very fine water spray (mist) that absorbs heat, displaces oxygen, or blocks radiant heat to control, suppress, or extinguish fires • Water mist systems are typically used for small confined areas, such as inside equipment enclosures or cabinets
  • 35. Other related systems… • Standpipe system • Clean Agent system
  • 36. Standpipe System • Standpipes are an arrangement of piping, valves, hose connections and allied equipment installed in a building or structure with the hose connections located in such a manner that the water can be discharged through attached hoses and nozzles
  • 37. Standpipe Systems • Standpipe systems provide fire hose connections within a building or industrial complex • Hose connections are fed by a supply pipe (often referred to as a riser) and are located throughout the facility, usually on each floor
  • 38. Standpipe Systems • Four methods in which water is supplied to standpipes: – Wet standpipe in which water is supplied directly from a water main (or through a fire pump if higher pressures are needed). Water supply valve is always open and the system is always under water pressure – Dry manual standpipe in which there is no permanent water supply. Water must be supplied by the fire department
  • 39. Standpipe Systems • Four methods (cont.) – Dry standpipe in which a connection to a water main is provided by a manual control valve which is kept closed. The standpipe system remains dry until needed – Dry automatic standpipe in which the valve controlling water to the system is automatic, as with a dry pipe valve. Water is admitted to the system when a hose valve is opened and air pressure in the system is released
  • 40. Clean Agent System • Commonly comprised of inert gases or safer HCFCs • Can dilute the amount of oxygen to prevent combustion or can cool reactants on the molecular level below the heat of combustion.
  • 41. Clean Agent Systems • Clean, nonconductive, noncorrosive – good for important electronics • Environmentally friendlier than Halon • React quickly – triggered by smoke and/or heat detectors • High first cost – costly to recharge • One shot to extinguish fire - best if coupled with sprinklers
  • 42. Design of Sprinkler Systems • Sprinkler system piping is installed in accordance with one of two methods: – Pipe schedule system – Hydraulically designed system • Pipe schedule systems are not allowed for new installations • The first step is to determine the classification of hazard
  • 43. A Design Application • Large drop sprinklers attack the fire plume that develops in atriums due to the delay in sprinkler operation from the height issue • Ordinary Group II Hazard Classification (.20 gpm/ft2 over 1500 ft2 ) provides an adequate amount of water to suppress typical atrium fuel loadings
  • 44. Occupancy Classifications • The occupancy or use of the building will predominantly determine the type of system required: – Light Hazard – Ordinary Hazard • Group 1 • Group 2 – Extra Hazard • Group 1 • Group 2
  • 45. Pipe – Schedule System • The number of sprinklers fed by a given pipe size is determined by schedules given in sprinkler installation rules • Installation rules vary with the occupancy of the area to be protected
  • 46. Hydraulically Designed System • Most sprinklers require 7 psi (minimum) to operate • Quick analysis: – Determine worst hazard (ex: Small office building is Light Hazard throughout) – Select design density and corresponding area of sprinkler operation (our ex: .10 gpm/ft2 /1500 ft2) – Determine inside water demand (.1 x 1500 x 1.25 = 187.5 gpm)
  • 47. Hydraulically Designed System • Quick analysis (cont.): – Add pipe, fittings, devices, backflow preventer, and elevator losses – 21 + 7 psi = 28 @ 187.5 gpm – Add 100 gpm for hoses – 28 @ 287.5 gpm at city psix 21)'15433.0(455 ≈+++ (pipe) (ftgs) (BFP) (elev.)
  • 48. Hydraulically Designed System • Note: Building square footage has little effect on the need for a fire pump. However, the hazard classification and building height do have a significant effect on whether a fire pump is needed.
  • 49. Do I really need a fire pump? • Installing a fire pump is often the default rather than something that must prove it’s needed • Many are not comfortable deciding if a fire protection system can do without one. • Fire pumps are great when needed but not desired if not needed. Cost Reliability
  • 50. How do I know if a pump is needed? • Look at highest fire hazard classifications • Look at available flow and pressure from utility • Look at building elevations • Perform basic hydraulic calculations • Can standpipe design be manual wet?
  • 51. Basic Fire Pump Calculations
  • 52. Basic Fire Pump Calculations Density Diversity
  • 53. Basic Fire Pump Calculations
  • 54.
  • 55. Basic Fire Pump Calculations 54 -0.6 -4.0 (BFP) -17.3 -15 -7.0 10.1psi cushion
  • 56. Fire Pump Selection • Consider resulting city water pressure when pump is flowing 150% of its rating (city water pressure must not drop below 20 psi) • Consider resulting system water pressure when at pump churn (standard fittings and components are only rated for 175 psi) • Jockey (maintenance) pump should be selected to maintain system pressure above fire pump starting pressure
  • 57. Water Supply Requirements • Every automatic sprinkler system shall have at least one automatic water supply • Water supply treatment – Water supplies and environmental conditions will be evaluated for the existence of microbes and conditions that contribute to microbiologically influenced corrosion (MIC)
  • 58. Installation of Sprinkler Systems • Basic requirements include – Position, location, spacing, and use of sprinklers • Determination of the protection area of coverage • Maximum/Minimum distance between sprinklers • Maximum/Minimum distance of sprinkler from walls – System protection area limitations – Application of sprinkler types • Requirements may vary depending on type of system used • For any system, pre-lubed grooved couplings are recommended
  • 59. Wet Pipe Sprinkler System Requirements • Must be reliably heated. Overhangs and chases on exterior walls cannot be trusted • Normal black steel piping is fine for wet systems • CPVC can be used in many applications
  • 60. Dry Pipe Sprinkler System Requirements • Gridded dry pipe system are not allowed • Air pressure should be maintained on dry pipe systems throughout the year • The compressed air supply should be from a source available at all times – Initial charge with Nitrogen • Galvanized black steel pipe • Dry systems should be drained completely to minimize corrosion – No roll groove ends • Use accelerators only when absolutely necessary
  • 61. Inspection, Testing, & Maintenance of Sprinkler Systems • Maintaining adequate fire protection systems is as critical as the original decision to install these systems • Because fire suppression, detection, and alarm systems are generally not used on a routine basis, their state of readiness is not immediately apparent • The periodic inspection, testing, and maintenance of fire detection and suppression systems are essential to ensure successful performance when these systems are needed
  • 62. Inspection • Visual examination of the sprinkler system to verify that it appears to be in operating condition and free of physical damage • Visual examination of storage and general environment surrounding sprinkler system
  • 63. Inspection • Sprinklers – Inspected from floor level annually – Should not show signs of leakage – Should be free of corrosion, foreign materials, paint, and physical damage – Should be installed in the proper orientation
  • 64. Inspection • Pipe and Fittings – Should be in good condition – Free of mechanical damage, leakage, corrosion, and misalignment – Piping should not be subjected to external loads by materials either resting on the pipe or hung from the pipe
  • 65. Inspection • Hangers and Seismic Bracing – Should not be damaged or loose • Gauges – Wet pipe systems : Should be inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained – Dry, pre-action, and deluge systems : Should be inspected weekly to ensure that normal air and water pressures are being maintained
  • 66. Testing • Sprinklers – Sample sprinklers submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service testing – Test procedures repeated at 10-year intervals – If one sprinkler within a representative sample fails to meet the test requirement, all sprinklers represented by that sample shall be replaced • Drains – Put ITC (Inspector’s Test Connection) for wet systems at the riser. Reduces corrosion in piping, lessens chances of obstructions to sprinklers and it makes testing easier – System main drain must discharge to a place that can accept full flow under pressure and gravity drain completely
  • 67. Testing • Pumps, alarms, and valves also need to be tested and exercised on schedule for reliability and longevity. Keep records on all tests • NFPA 25 provides descriptions of these tests and recommended forms
  • 68. Maintenance Fire protection systems require little maintenance when properly cared for. • Sprinklers – Replacement sprinklers shall have the proper characteristics for the application intended. They should be the same type as the adjacent existing sprinklers. – A supply of spare sprinklers (never fewer than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced • Dry pipe systems shall be kept dry at all
  • 69. Prevention and Control of Internal Corrosion in Sprinkler Systems • Over the past years an increasing number of leaks and other corrosion related problems have been associated with microbial or bacterial activity in fire protection piping
  • 70. Prevention and Control of Internal Corrosion in Sprinkler Systems • What is Microbiologically Influenced Corrosion (MIC)? – MIC is one of the many forms of corrosion that can affect sprinkler systems – MIC is not a new corrosion mechanism; however, its association to fire protection piping is relatively new
  • 71. Prevention and Control of Internal Corrosion in Sprinkler Systems • How does MIC affect sprinkler systems? – Because of its nature and the complexity of fire protection piping, MIC is not easily controlled in fire protection systems – MIC can affect any piping within the sprinkler system, however, branchlines and risers seem to be more seriously affected
  • 72. Prevention and Control of Internal Corrosion in Sprinkler Systems • How does MIC affect sprinkler systems? – MIC generally results in the growth of biofilms and nodules within the piping – Nodules and biofilm may result in increased friction loss, and affect the ability of the pipe to carry the necessary flow – MIC may also affect sprinklers and valves, and block water motor gongs, and alarm lines and other components of a fire protection system
  • 73. Prevention and Control of Internal Corrosion in Sprinkler Systems • How to protect sprinkler systems from MIC – Existing sprinkler systems: • Investigate for possible corrosion problems and obstructed waterways, pinhole leaks, or other signs of corrosion in pipes, valves or sprinkler heads • Flush sprinkler systems where investigation reveals obstructions of the waterway • Replace any section of piping that contains obstructions that cannot become removed by flushing procedures* • Reinvestigate systems for waterway obstruction annually.
  • 74. Prevention and Control of Internal Corrosion in Sprinkler Systems • How to protect sprinkler systems from MIC – New Sprinkler Systems: • Use new, clean, coated pipe for all new sprinkler system installations and retrofits • Do not use chlorine for disinfecting purposes • Do not leave open pipe exposed where it could accumulate dust, dirt, water and other residue prior to installation
  • 75. Prevention and Control of Internal Corrosion in Sprinkler Systems • How to protect sprinkler systems from MIC – New wet-pipe sprinkler systems: • Avoid repeated cycles of system shutdowns where the system is drained and recharged • Avoid air gaps (pockets) within the system, which can expose piping to dry/wet conditions. Air gaps can be avoided by providing means for air release at the highest point of each branchline
  • 76. Prevention and Control of Internal Corrosion in Sprinkler Systems • How to protect sprinkler systems from MIC – New dry pipe and pre-action systems: • Avoid the use of roll grooved joints. Roll grooved joints in a dry sprinkler system promote water accumulation that can result in preferred corrosion sites • Install pipe with proper pitch to promote drainage of all testing water and water vapor condensate within piping • Keep low point drains clean and drain condensate as needed to prevent water accumulation
  • 77. Prevention and Control of Internal Corrosion in Sprinkler Systems Heavy tubercle formation in a 8 in. sprinkler pipe Corrosion at roll groove in a wet pipe system
  • 78. Earthquake Protection • Uncontrolled differential movement can cause damage when fire protection systems are not provided in a systematic manner with the necessary features that incorporate sway bracing, flexibility, clearances, and anchorage where needed • The most common type of damage is water damage due to water leakage from broken overhead sprinkler piping or sprinklers, primarily due to lack of sway bracing where needed
  • 79. Earthquake Protection • How to adequately protect sprinkler systems from earthquake damage – Brace piping or equipment to minimize uncontrolled differential movement between piping or equipment and the structure to which it is attached – Provide flexibility on piping systems and on other equipment where differential movement between portions of those piping systems or equipment is expected
  • 80. Earthquake Protection • How to adequately protect sprinkler systems from earthquake damage – Provide clearance between piping or equipment and structural members, walls, floors, or other objects so that potential damage from impact is minimized – Provide anchorage to minimize potential sliding and/or overturning
  • 81. Earthquake Protection • How to adequately protect sprinkler systems from earthquake damage – Use appropriate types of pipe hangers and sway bracing, properly locate them, and properly attach them to the structure to minimize the potential for pullout – Use appropriate types of piping and pipe joining methods to minimize potential pipe breaks
  • 82. What to do with a broken fire line under floor? 1. Replaced RPZ with DDC BFP 2. Fed 4” HDPE thru 6” DI pipe
  • 83.
  • 84.
  • 85.
  • 86.
  • 87.
  • 88. References • Factory Mutual Global Property Loss Prevention Data Books • National Fire Protection Association National Fire Codes Pamphlets 13, 14 and 25

Editor's Notes

  1. 1:16,000,000 are defective!
  2. More $ for lab buildings/fire pumps Trade-ups: unrated wall/ceiling/door construction,
  3. Red-155F/165F Green-200/212F Blue-286F
  4. Insert new calc slides after this slide
  5. Insert calcs on form
  6. -In branchlines, the presence of air gaps in wet systems or undrained water in dry pipe systems is believed to be a contributing factor -In risers, the higher exposure to oxygenation compared to other parts of the system is believed to be a contributing factor
  7. -The biofilm produced will generally present itself as a black slime that, in certain cases, can be flushed out. - Nodules, on the other hand, are hard, well-adhered to the pipe wall, and will not flush out
  8. -*Replacement pipe also my eventually corrode if the causes for corrosion are not addressed
  9. Applies to other piping systems, too!
  10. Add pipe repair slides after this slide