BUILDING SERVICES
FIRE SAFETY
INSTALLATION
UNIT – 5
FIRE SAFETY INSTALLATION
Fire prevention and control systems - Fire alarms - Electrical alarm
circuits -Smoke extraction and ventilation -Gas extinguishers - Types of
detectors - Gas installation and components.
FIRE PREVENTION AND CONTROL SYSTEMS
• Stipulation of the various fire protection measures for building, to
minimise the loss of life & property and effects of fire on surrounding
area, are broadly based on following aspects/ philosophy.
Fire Tetrahedron
Extinguishing of fire
•Cooling – fire extinguishing by the application of water acts by removing heat from the
fuel faster than combustion generates it.
•Oxygen starving (பட்டினி) – application of carbon dioxides is intended primarily to
starve the fire of oxygen. Ex., putting fire blanket to cut off the oxygen
supply.
•Remove fuel source – a forest fire may be fought by starting smaller fires in advance of
the main blaze, to deprive it of fuel. Ex., physical removing fuel
•Interference of Chemical reaction – other gaseous fire suppression agents, such as halon
or HFC-225, interfere with the chemical reaction itself.
Fire hydrants systems
Rising Mians
(a) Dry riser (RED)
• Any floor is at a habitable height beyond 24 m and not exceeding 60 m above the ground level.
• For a building under purpose group of the fire code, having a habitable height exceeding 10 m but
not exceeding 60 m.
(b)Wet riser (Yellow)
• Any floor exceeding habitable height of 60 m above ground level
• Wet rising main zone heights exceeding 76 m may be permitted when a listed
pressure regulating device, which controls nozzle pressure under both flow and no flow
conditions is installed at each outlet in house rise buildings, the following requirements are
also applicable to wet risers:
• The maximum zone height shall not exceed 120 m
• The pressure regulating device is arranged to regulate pressure at the hose valve
outlet to a running pressure not exceeding 5.5 bar
• The pressure on the inlet side of the pressure regulating device does not exceed the
working pressure rating of the device
• All other pipe fitting and devices on the system are rated for not less than the
maximum system pressure.
Fire Safety precautions
• Don't overload outlets with multiple outlet cords or plugs. If
additional outlets are required, use an IS marked multi-outlet "power strip"
with its own built-in circuit breaker.
• Careless smoking, use of candles and incense, and unattended
cooking appliances remain major causes of fatal fires in residential
buildings. Use of fire crackers, hot work, and open fire is prohibited in all
buildings.
• Keep walkways, stairwells and exits free from obstructions at all
times.
• Report immediately if you observe/noticed damaged fire equipment
and other fire hazards to Campus security and Fire Safety wing.
• Do not open fire hydrant/hose reel water for unnecessarily use.
• Do not misuse of Fire Extinguisher.
Dry Pipe System
•Above the control valves, system is charged with compressed air/nitrogen instead of water
•Dry pipe valve held closed by air pressure
•Upon activation of sprinkler head, air is released and water flows into the pipe work
•For areas subjected to freezing temperatures.
Pre-Action System
• For areas where accidental discharge of water is unacceptable.
• Pipes filled with low pressure air.
• Heat/ smoke detector send signal to valve to release water to pipe work and sound alarm.
• When sprinkler burst, water is discharged.
• Prevent unwanted water flow when a pipe or sprinkler is accidently broken.
(d). Deluge System
• Pipes are usually empty, sprinkler are open
• Detectors activate control valve to allow water to flow
• Water is discharged simultaneously through all the open sprinklers in
the area.
•Thus, providing fast and total wetting of protected areas.
•For areas that required total coverage (extra high hazard area such as
aircraft hangers, power generating stations, and petrochemical facilities).
Fire protection equipment
 Automatic fire detection system
 Automatic sprinkler system
 Automatic release mechanism
 Automatic self-closing device
• Basement
 Boundary
 Cavity
 Ceiling
 Circulation space
.
•
Common Fire
Hazards
• Kitchen fire from unattended cooking, such as frying, boiling and simmering.
• Electrical systems that are overloaded, resulting in hot wiring or connections, or failed components.
• Combustible storage areas with insufficient protection.
• Combustibles near equipment that generates heat, flame, or sparks.
• Candles and other often flames
• Smoking (cigarettes, cigars, pipes, lighters, etc.).
• Equipment that generates heat and utilizes combustible materials.
• Flammable liquids and aerosols.
• Flammable solvent (and rags soaked with solvent) placed in enclosed trash cans.
• Fireplace chimneys not properly or regularly cleaned.
• Cooking appliances-stoves, ovens.
• Heating appliances-fireplaces, wood burning stoves, furnaces, boilers, portable heaters.
• Household appliances-clothes dryers, curling irons, hair dryers, refrigerators, freezers.
• Chimneys that concentrate creosote.
• Electrical wiring in poor condition.
• Leaking Batteries.
• Personal ignition sources-matches, lighters
• Electronic and electrical equipment
• Exterior cooking equipment-barbecue
FIRE ALARM
Fire alarm systems generally use visual and audio signalization to warn the
occupants of the building. Some fire alarm systems may also disable elevators,
which under most circumstances, are unsafe to use during a fire.
Fire Alarm Control Panels
(a) Function of control panel
• It is the brain of the fire detection and alarm system
• Responsible for monitoring the various alarm input devices such
as manual and automatic detection components
• Activates alarm output devices such as horns bells warning lights
emergency telephone diallers and building controls
(b) Design
• Control panels may range from simple units with a single input
and output zone, to complex computer driven systems that monitor
several buildings over an entire campus.
Types of arrangements
• Conventional (Older technology)
• Addressable (Newer technology)
Conventional Systems
(a) Conventional
• Point wired – have a dedicated writing back to the signal processing
• One or more circuits are routed through the protected space of the building.
• Along each circuit, one or more detection devices are placed
(b) Factors for selection & placement
• Depends on need for automatic or manual initiation
• Ambient temperature & environment conditions
• Anticipated type of fire
• Desired speed of response
(c) Fire occurrence situation
• One or more detectors will operate
• Action will close the circuit which the fire control panel recognizes as an emergency condition
• Panel will then activate one or more signalling alarm circuits to sound building alarm and
summon emergency help
• Panel may also send the signal to another alarm panel so that it can be monitored from a
remote point.
(d) Fault monitoring
• To help ensure that the system is functioning properly
these systems monitor the condition of each circuit by sending a
small current through the wires.
• Should a fault occur, such as due to a wiring break this
current cannot proceed and is registered as a trouble condition
• The indication is a need for service somewhere along the
respective circuit
Addressable systems
(a) Addressable systems
• State of the art in fire detection and alarm technology
• Monitors and controls the capabilities of each alarm initiating and signalling device through
microprocessor and systems software
• Major differences involve the way in which each device is monitored
• Each initiating device (automatic detector, manual station, sprinkler water flow switches) is given a
specific identification or address
• This address is correspondingly programmed into the control panels memory with information such
as the type of device its location and specific response details such as which alarm devices are to be
activated.
(b) Operations
•The control panels microprocessors send a constant interrogation signal over each circuit
•Each initiating devices is contracted to inquires its status (normal or emergency)
•This activates monitoring process occurs in rapid succession providing system updates every 5 to 10
seconds
•Therefore, instead of merely showing a fault along a wire they will indicate the location of the
problem
•This permits faster diagnosis of the trouble and allows a quicker repair and return to normal.
ELECTRICAL ALARM CIRCUITS
Fire Alarm Control Panels
(a) Function of control panel
• Control panel is the brain of the fire detection and alarm system
• Responsible for monitoring the various alarm input devices such
as manual and automatic detection components
• Activates alarm output devices such as horns bells warning lights
emergency telephone diallers and building controls
(b) Design
• Control panels may range from simple units with a single input
and output zone, to complex computer driven systems that monitor
several buildings over an entire campus.
FIRE PREVENTION IN VENTILATING SYSTEMS
Closed Alarm Circuit
PRESSURISATION OF ESCAPE ROUTES
SMOKE EXTRACTOR AND FIRE VENTILATOR
• Number and area of ventilators - estimates are based on providing a smoke-
free layer about 3 m above floor level.
Smoke Reservoir
GAS EXTINGUISHING SYSTEMS – HALON & HALON
SUBSTITUTES
PORTABLE FIRE EXTINGUISHERS (ACID BASED)
• A portable fire extinguisher must contain the type of fire extinguishing agent suitable
for the fire it is required to extinguish. It must also be clearly identifiable by colour
coding for its intended purpose.
Portable fire Extinguishers
Extinguishing agent Extinguisher colour Application
Water Red
Carbonaceous fires,
paper, wood, etc.,
Foam Red with cream band
Ditto and flammable
liquids, oils, fats, etc.,
Carbon dioxide Red with black band
Electrical fires a
flammable liquid
Dry chemicals Red with blue band All fires
Striking type soda – acid
water portable fire
extinguisher
Inversion type soda-and acid water portable fire extinguisher
PORTABLE FIRE EXTINGUISHERS (CHEMICAL BASED)
TYPES OF DETECTORS Ionisation smoke detector
Light Scattering Smoke Detector
Fusible Alloy Heat Detector
Bi-metal Coil Heat Detector
LIGHT OBSCURING AND LASER BEAM DETECTORS
Light Obscuring Detector
LIGHT OBSCURING AND LASER BEAM DETECTORS
Laser Beam Detector
Components of an Infra-red detector
Infra-red Detector for large and small areas
Ultra-violet detector
GAS INSTALLATION
Typical House Installation
Use condensate receiver

More Related Content

Similar to UNIT-5.pptx

Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm SystemsJ.T.A.JONES
 
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Gan Chun Chet
 
Bs ii-presentation
Bs ii-presentationBs ii-presentation
Bs ii-presentationLee Chun Yee
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfRiyaVerma238431
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Jed Concepcion
 
Building vertival transport.pdf
Building vertival transport.pdfBuilding vertival transport.pdf
Building vertival transport.pdfMohsinAhmed969174
 
Fire safety in hospitals
Fire safety in hospitalsFire safety in hospitals
Fire safety in hospitalsKomal Gupta
 
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxFIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxNeerajTiwari965955
 
Fire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, ApplicationsFire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, ApplicationsMohamed Gamal
 
BUILDING SERVICE GROUP ASSIGNMENT
BUILDING SERVICE GROUP ASSIGNMENTBUILDING SERVICE GROUP ASSIGNMENT
BUILDING SERVICE GROUP ASSIGNMENTXinYee Khoo
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)Esa Shaikh
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm systemsingh1515
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfnipunwijewardhana
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technologyArman Nasar
 

Similar to UNIT-5.pptx (20)

Fire Detection and Alarm Systems
Fire Detection and Alarm SystemsFire Detection and Alarm Systems
Fire Detection and Alarm Systems
 
Fire safety
Fire safety Fire safety
Fire safety
 
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
Fire and Gas Detection System : Part 3_Technical Features, Locating Detectors...
 
fire fighting System
fire fighting Systemfire fighting System
fire fighting System
 
Firefighting & HVAC.pdf
Firefighting & HVAC.pdfFirefighting & HVAC.pdf
Firefighting & HVAC.pdf
 
Bs ii-presentation
Bs ii-presentationBs ii-presentation
Bs ii-presentation
 
FIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdfFIRE DETECTION & ALARM SYSTEMS.pdf
FIRE DETECTION & ALARM SYSTEMS.pdf
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
Building vertival transport.pdf
Building vertival transport.pdfBuilding vertival transport.pdf
Building vertival transport.pdf
 
PWD training
PWD trainingPWD training
PWD training
 
MEP- Building services
MEP- Building servicesMEP- Building services
MEP- Building services
 
Fire safety in hospitals
Fire safety in hospitalsFire safety in hospitals
Fire safety in hospitals
 
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptxFIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
FIRE PREVENTION & FIRE FIGHTING EQUIPMENT-N PPT.pptx
 
Fire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, ApplicationsFire Alarm ... Design, Components, Applications
Fire Alarm ... Design, Components, Applications
 
BUILDING SERVICE GROUP ASSIGNMENT
BUILDING SERVICE GROUP ASSIGNMENTBUILDING SERVICE GROUP ASSIGNMENT
BUILDING SERVICE GROUP ASSIGNMENT
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)
 
Oil production3
Oil production3Oil production3
Oil production3
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
 

More from Muthukumar P

More from Muthukumar P (9)

UNIT-4.pptx
UNIT-4.pptxUNIT-4.pptx
UNIT-4.pptx
 
UNIT-3.pptx
UNIT-3.pptxUNIT-3.pptx
UNIT-3.pptx
 
UNIT-2.pptx
UNIT-2.pptxUNIT-2.pptx
UNIT-2.pptx
 
UNIT-1.pptx
UNIT-1.pptxUNIT-1.pptx
UNIT-1.pptx
 
UNIT- V.pptx
UNIT- V.pptxUNIT- V.pptx
UNIT- V.pptx
 
UNIT- IV.pptx
UNIT- IV.pptxUNIT- IV.pptx
UNIT- IV.pptx
 
UNIT- III.pptx
UNIT- III.pptxUNIT- III.pptx
UNIT- III.pptx
 
UNIT - II.pptx
UNIT - II.pptxUNIT - II.pptx
UNIT - II.pptx
 
UNIT - I.pptx
UNIT - I.pptxUNIT - I.pptx
UNIT - I.pptx
 

Recently uploaded

Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfROCENODodongVILLACER
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 

Recently uploaded (20)

Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Risk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdfRisk Assessment For Installation of Drainage Pipes.pdf
Risk Assessment For Installation of Drainage Pipes.pdf
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 

UNIT-5.pptx

  • 2. FIRE SAFETY INSTALLATION Fire prevention and control systems - Fire alarms - Electrical alarm circuits -Smoke extraction and ventilation -Gas extinguishers - Types of detectors - Gas installation and components.
  • 3. FIRE PREVENTION AND CONTROL SYSTEMS • Stipulation of the various fire protection measures for building, to minimise the loss of life & property and effects of fire on surrounding area, are broadly based on following aspects/ philosophy.
  • 5. Extinguishing of fire •Cooling – fire extinguishing by the application of water acts by removing heat from the fuel faster than combustion generates it. •Oxygen starving (பட்டினி) – application of carbon dioxides is intended primarily to starve the fire of oxygen. Ex., putting fire blanket to cut off the oxygen supply. •Remove fuel source – a forest fire may be fought by starting smaller fires in advance of the main blaze, to deprive it of fuel. Ex., physical removing fuel •Interference of Chemical reaction – other gaseous fire suppression agents, such as halon or HFC-225, interfere with the chemical reaction itself.
  • 7. Rising Mians (a) Dry riser (RED) • Any floor is at a habitable height beyond 24 m and not exceeding 60 m above the ground level. • For a building under purpose group of the fire code, having a habitable height exceeding 10 m but not exceeding 60 m. (b)Wet riser (Yellow) • Any floor exceeding habitable height of 60 m above ground level • Wet rising main zone heights exceeding 76 m may be permitted when a listed pressure regulating device, which controls nozzle pressure under both flow and no flow conditions is installed at each outlet in house rise buildings, the following requirements are also applicable to wet risers: • The maximum zone height shall not exceed 120 m • The pressure regulating device is arranged to regulate pressure at the hose valve outlet to a running pressure not exceeding 5.5 bar • The pressure on the inlet side of the pressure regulating device does not exceed the working pressure rating of the device • All other pipe fitting and devices on the system are rated for not less than the maximum system pressure.
  • 8.
  • 9.
  • 10. Fire Safety precautions • Don't overload outlets with multiple outlet cords or plugs. If additional outlets are required, use an IS marked multi-outlet "power strip" with its own built-in circuit breaker. • Careless smoking, use of candles and incense, and unattended cooking appliances remain major causes of fatal fires in residential buildings. Use of fire crackers, hot work, and open fire is prohibited in all buildings. • Keep walkways, stairwells and exits free from obstructions at all times. • Report immediately if you observe/noticed damaged fire equipment and other fire hazards to Campus security and Fire Safety wing. • Do not open fire hydrant/hose reel water for unnecessarily use. • Do not misuse of Fire Extinguisher.
  • 11.
  • 12. Dry Pipe System •Above the control valves, system is charged with compressed air/nitrogen instead of water •Dry pipe valve held closed by air pressure •Upon activation of sprinkler head, air is released and water flows into the pipe work •For areas subjected to freezing temperatures.
  • 13. Pre-Action System • For areas where accidental discharge of water is unacceptable. • Pipes filled with low pressure air. • Heat/ smoke detector send signal to valve to release water to pipe work and sound alarm. • When sprinkler burst, water is discharged. • Prevent unwanted water flow when a pipe or sprinkler is accidently broken.
  • 14. (d). Deluge System • Pipes are usually empty, sprinkler are open • Detectors activate control valve to allow water to flow • Water is discharged simultaneously through all the open sprinklers in the area. •Thus, providing fast and total wetting of protected areas. •For areas that required total coverage (extra high hazard area such as aircraft hangers, power generating stations, and petrochemical facilities).
  • 15. Fire protection equipment  Automatic fire detection system  Automatic sprinkler system  Automatic release mechanism  Automatic self-closing device • Basement  Boundary  Cavity  Ceiling  Circulation space . •
  • 16. Common Fire Hazards • Kitchen fire from unattended cooking, such as frying, boiling and simmering. • Electrical systems that are overloaded, resulting in hot wiring or connections, or failed components. • Combustible storage areas with insufficient protection. • Combustibles near equipment that generates heat, flame, or sparks. • Candles and other often flames • Smoking (cigarettes, cigars, pipes, lighters, etc.). • Equipment that generates heat and utilizes combustible materials. • Flammable liquids and aerosols. • Flammable solvent (and rags soaked with solvent) placed in enclosed trash cans. • Fireplace chimneys not properly or regularly cleaned. • Cooking appliances-stoves, ovens. • Heating appliances-fireplaces, wood burning stoves, furnaces, boilers, portable heaters. • Household appliances-clothes dryers, curling irons, hair dryers, refrigerators, freezers. • Chimneys that concentrate creosote. • Electrical wiring in poor condition. • Leaking Batteries. • Personal ignition sources-matches, lighters • Electronic and electrical equipment • Exterior cooking equipment-barbecue
  • 17. FIRE ALARM Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which under most circumstances, are unsafe to use during a fire.
  • 18. Fire Alarm Control Panels (a) Function of control panel • It is the brain of the fire detection and alarm system • Responsible for monitoring the various alarm input devices such as manual and automatic detection components • Activates alarm output devices such as horns bells warning lights emergency telephone diallers and building controls (b) Design • Control panels may range from simple units with a single input and output zone, to complex computer driven systems that monitor several buildings over an entire campus.
  • 19. Types of arrangements • Conventional (Older technology) • Addressable (Newer technology)
  • 20. Conventional Systems (a) Conventional • Point wired – have a dedicated writing back to the signal processing • One or more circuits are routed through the protected space of the building. • Along each circuit, one or more detection devices are placed (b) Factors for selection & placement • Depends on need for automatic or manual initiation • Ambient temperature & environment conditions • Anticipated type of fire • Desired speed of response (c) Fire occurrence situation • One or more detectors will operate • Action will close the circuit which the fire control panel recognizes as an emergency condition • Panel will then activate one or more signalling alarm circuits to sound building alarm and summon emergency help • Panel may also send the signal to another alarm panel so that it can be monitored from a remote point.
  • 21. (d) Fault monitoring • To help ensure that the system is functioning properly these systems monitor the condition of each circuit by sending a small current through the wires. • Should a fault occur, such as due to a wiring break this current cannot proceed and is registered as a trouble condition • The indication is a need for service somewhere along the respective circuit
  • 22. Addressable systems (a) Addressable systems • State of the art in fire detection and alarm technology • Monitors and controls the capabilities of each alarm initiating and signalling device through microprocessor and systems software • Major differences involve the way in which each device is monitored • Each initiating device (automatic detector, manual station, sprinkler water flow switches) is given a specific identification or address • This address is correspondingly programmed into the control panels memory with information such as the type of device its location and specific response details such as which alarm devices are to be activated. (b) Operations •The control panels microprocessors send a constant interrogation signal over each circuit •Each initiating devices is contracted to inquires its status (normal or emergency) •This activates monitoring process occurs in rapid succession providing system updates every 5 to 10 seconds •Therefore, instead of merely showing a fault along a wire they will indicate the location of the problem •This permits faster diagnosis of the trouble and allows a quicker repair and return to normal.
  • 24. Fire Alarm Control Panels (a) Function of control panel • Control panel is the brain of the fire detection and alarm system • Responsible for monitoring the various alarm input devices such as manual and automatic detection components • Activates alarm output devices such as horns bells warning lights emergency telephone diallers and building controls (b) Design • Control panels may range from simple units with a single input and output zone, to complex computer driven systems that monitor several buildings over an entire campus.
  • 25. FIRE PREVENTION IN VENTILATING SYSTEMS
  • 28.
  • 29.
  • 30. SMOKE EXTRACTOR AND FIRE VENTILATOR • Number and area of ventilators - estimates are based on providing a smoke- free layer about 3 m above floor level.
  • 32.
  • 33. GAS EXTINGUISHING SYSTEMS – HALON & HALON SUBSTITUTES
  • 34.
  • 35. PORTABLE FIRE EXTINGUISHERS (ACID BASED) • A portable fire extinguisher must contain the type of fire extinguishing agent suitable for the fire it is required to extinguish. It must also be clearly identifiable by colour coding for its intended purpose.
  • 36. Portable fire Extinguishers Extinguishing agent Extinguisher colour Application Water Red Carbonaceous fires, paper, wood, etc., Foam Red with cream band Ditto and flammable liquids, oils, fats, etc., Carbon dioxide Red with black band Electrical fires a flammable liquid Dry chemicals Red with blue band All fires
  • 37.
  • 38. Striking type soda – acid water portable fire extinguisher
  • 39. Inversion type soda-and acid water portable fire extinguisher
  • 40. PORTABLE FIRE EXTINGUISHERS (CHEMICAL BASED)
  • 41. TYPES OF DETECTORS Ionisation smoke detector
  • 43. Fusible Alloy Heat Detector
  • 44. Bi-metal Coil Heat Detector
  • 45. LIGHT OBSCURING AND LASER BEAM DETECTORS Light Obscuring Detector
  • 46. LIGHT OBSCURING AND LASER BEAM DETECTORS Laser Beam Detector
  • 47. Components of an Infra-red detector
  • 48. Infra-red Detector for large and small areas