International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072
© 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 653
Evolution of a 1250-kVa Superconducting Transformer and its
Exhibition at the superconducting Substation
Anas Abdul Azeez
Electrical and Electronics Engineering Department, APJ Abdul Kalam Technological University
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract- A three-phase high temperature
superconducting (HTS) transformer of 1250-kVA/10.5-
kV/0.4-kV has been designed and manufactured. The
windings of the three phase HTS transformer made of
reinforced copper alloy. The formation of the primary and
secondary windings of the HTS transformer is solenoid and
double pancake, respectively. The core consists of three-limb
and is made of domain-refined high-induction-type grain-
oriented silicon sheet steel .The cryostat is fabricated of
glass-fiber-reinforced plastics. From the transformer tests,
the no-load loss is about 2319.2 W at an exciting current of
0.254% of the rated current. The short-circuit impedance of
the HTS transformer is about 5.6% of the rated value. The
average load loss is 249.6 W. In addition, the leakage
current between the primary and secondary windings of the
HTS transformer is about 12.6 mA under the situation of 35
kV/1 min/50 Hz.
Key Words: Bi2223/Ag hermetic tapes, high-temperature
superconducting (HTS) transformer, superconducting
power substation, transformer test.
1.INTRODUCTION
POWER transformers are one of the most important and
significant devices for electrical application. Different
types of transformers are constructed for different
applications. There are many number of service-ready
prototype high-temperature Superconducting (HTS)
transformers have been introduced. The usage of HTS
transformer results show that it is possible to reduce the
energy loss in transformers by 60% or more by replacing
the HTS windings over conventional winding With the
discovery of High temperature superconductor (HTS)
having higher temperature, the electrical applications of
low temperature superconductor (LTS) have diminished
than high temperature superconductor (HTS). HTS
transformer has been expected to be one of the most
wanted HTS device applications. Recently research and
development about the relevance of HTS transformer have
been progressed actively in the world. The market for HTS
transformers will become higher and larger with the
continued manufacturing of HTS transformers
A transformer is an electrical device which is used in
transferring of power from one circuit to another through
the basic principle of electromagnetic induction. The
power transfer is done without frequency change. In an
electrical system, the term power transformer is used to
provide a different range of AC supplies of several voltages
and appropriate values of current from the public
electricity supply. Usually transformer is denoted with kVa
rating, 500kVa or greater. The Power transformer is a kind
of transformer, which is used to transfer electrical energy
in any part of the electrical or electronic system between
the generator and the distribution primary circuits. The
power transformers are used in distribution systems to
interface step up and step down voltages. One of the
common type of power transformer used is liquid
immersed and the life span of these transformers is
around 30 years. Power transformers are classified into
three types based on the ranges. They are small, medium
and large power transformers
HTS transformers are classified into three : 1) on the basis
of windings of different materials, HTS transformers can
be classified into HTS conventional transformers were the
windings made by HTS materials and HTS hybrid
transformers were the windings are made by HTS and
copper materials; 2) on the basis of having a magnetic
core or not, HTS transformers can be classified into HTS
core-type transformers and HTS air-core transformers; 3)
on the basis of different application fields, HTS
transformers can be classified into HTS power
transformers and HTS traction transformers.
The evolution of the 1250-kVA/10.5-kV/0.4-kV HTS
Transformer is described in this paper, and from the
testing results it is proved that the developed HTS
transformer meets the requirement for operating in the
grid. By considering the economic efficiency, the HTS
conductor Bi2223 from Sumiton other than YBCO is used
for the windings. The core of 630-kVA/10.5/0.4-kV HTS
power transformer is made of amorphous alloy and the
core of the 1250-kVA HTS transformer is made of domain-
refined high-induction-type grain oriented silicon sheet
steel.
Fig -1: Arrangement of the 1250-kVA/10.5-kV/0.4-kV HTS
transformer.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072
© 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 654
Table -1: Specification of the 1250kVa HTS transformer
thing Designed value
No. of phase 3
Rated capacity 1250kVa
Rated frequency 50Hz
Rated voltage
(prim./second.)
10.5kV/0.5kV
Rated current
(prim./second.)
69A/1804A
connection Y-Y
impedance 6%(std. level)
Operating temperature 77K(LN2)
Fig -2: Arrangement of the core.
2. DESIGN AND FABRICATION OF THE
TRANSFORMER
BA three-phase HTS power transformer with a capacity of
1250 kVA/10.5 kV/0.4 kV of 77 K is constructed. Liquefied
nitrogen is used as coolant. Fig. 1 shows the arrangement
of the 1250-kVA/10.5-kV/0.4-kVHTS transformer. Here
the HTS transformer is a three-phase three-limb
transformer with Y–Y connection. By comparing with the
conventional transformers, the primary and secondary
windings of the HTS transformer are made of HTS tapes,
and liquefied nitrogen (LN2) at a temperature of77 K is
used as the cooling and insulation medium. The
specifications of the Superconducting transformer are
presented in Table I.
2.1 Iron
Fig. 2 shows the arrangement of the core, where
the core is naturally air cooled. The core of the previously
constructed 630-kVA HTS transformer is made of an
amorphous alloy core.
TABLE 2: SYMBOLS
By looking through the mechanical and magnetic
characteristics of amorphous alloy, the core of a three-
phase transformer is usually wound with five limbs, which
thereby increases the width and weight of the
transformer. Since the HTS transformer is not that reliable
as a conventional transformer, the convenience for
assembling and maintaining is important. However, the
construction of amorphous alloy cores by rolling is not as
convenient for assembly and maintenance as silicon sheet
steel construction. Therefore the core loss of an
amorphous alloy core is much smaller when compared
with the silicon sheet steel, conventional silicon sheet steel
is used for the construction of core 1250-kVA HTS
transformer. The core is constructed from domain-refined
high-induction-type grain oriented silicon sheet steel
B27R085 from Baosteel. The guaranteed value of the core
loss is 0.85 W/kg at a maximum magnetic induction of 1.7
T. at a frequency of 50 Hz. the lamination factor fd is 0.97.
the power for each limb Pzh (in kilovolt amperes) is 417
kVA. The diameter D0 of the core limb is taken to be310
mm. Thus, the effective cross sectional area of core limb
Szh is 698.30 cm2, and the no. of turn of low-voltage
winding Nl is 10, whereas the turn potential et is 23.09 V.
the no. of turn of high-voltage winding Nh becomes 262,
and the magnetic flux density of the core Bm is 1.49 T.
2.2 Windings
Fig. 3 shows the arrangement of the winding, where the
primary and secondary windings are solenoid and double
pancake. Both of the primary and secondary windings of
the HTS transformer are made of Bi2223 HT-CA 50 from
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072
© 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 655
Sumitomo with critical current around 170 A (77 K, self-
field), and the features of the windings are presented in
Table IV.
HTS wires which are commonly used in high voltage
power transformer can be classified into two types: the 1st
one is generation of Bismuth Strontium Copper Oxides
(BSCCO) HTS wires, and the 2nd one is generation of
Yttrium-Barium- Copper Oxide (YBCO) HTS wires]. For
BSCCO, it is mainly used in two forms: Bi2Sr2CaCu2O
(Bi2212) and Bi2Sr2Ca2Cu3O (Bi2223). At present,
Bi2223 has been more applied than Bi2212 because its
critical temperature is 20 K higher than Bi2212. To deal
with high voltage, the superconducting power
Transformer needs windings that have hundreds of turns.
HTS winding with YBCO wires have higher current density
and better current magnetic field characteristics than
BSCCO wires.
Fig-3: Arrangement of the winding.
TABLE 3: Specification OF THE CORE
TABLE -4: SPECIFICATIONS OF WINDINGS
2.3. Cryostat
Fig. 5 shows the arrangement of the cryostat. To reduce
the eddy-current loss, the cryostat is to be made of non-
metal materials since the magnetic field is alternating.
Thus, fiberglass and epoxy that can be applied at a
cryogenic environment are used to construct the cryostat
of the HTS transformer. Fig. 6 shows the arrangement of
the primary current lead. Since the rated current of the
primary winding is 69 A and a φ 6-mm Copper wire is
used as the current lead. The current lead has to endure a
35-kV/1-min/50-Hz voltage at both cryogenic and room
temperatures. So a resin impregnated paper bushing is
applied. To avoid the failure of insulation caused by
possible condensate water on the bushing, a low-
temperature endurable non-metal insulator is developed
to reduce the possible discharge along the dielectric
surface of the bushing.
Fig-6: Arrangement of the primary current lead.
(a) (b)
Fig.-7: Secondary current lead.
(a) Arrangement. (b) Schematic.
3. TESTS OF THE TRANSFORMER
Tests on transformer includes: No-Load Test Short-
Circuit Test Insulation Test
TABLE-5: INSULATION RESISTANCE
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072
© 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 656
TABLE-6: TEST RESULTS FOR THE 1250-kVA HTS
TRANSFORMER
3.1. No-Load Test
These tests include insulation resistance among the
primary and secondary windings and core (ground),
transformer ratio and connection group, and the no-load
current and loss test. The tests are carried out under the
condition that the windings are completely immersed in
liquefied nitrogen (LN2) for more than 24 hr Table V
shows the insulation test results including the insulation
resistance between the primary and secondary winding,
the primary winding and iron connected with ground, and
the secondary winding and core connected with ground.
It’s not that difficult to find that the tested values are far
above the required values. The main test results of no-load
tests for the HTS transformer are shown in Table VI.
3.2. Short-Circuit Test
The conventional electric method with a power analyzer
was applied in the short-circuit test .and the HTS
transformer was excited from the primary side at 69 A/50
Hz for 24 h. The accuracy of the applied power analyzer is
0.3% under the power factor of 0.01.According to the
insulation test, the short-circuit impedance of the HTS
transformer is 5.6% of the rated value, and the average
load loss is 249.6W, which includes the ac loss of windings
and the joule heat of current leads.
Fig-8: Showing Insulation between the primary and
secondary windings
3.3. Insulation Test
Fig. 9 shows the insulation between the primary and
secondary windings of the HTS transformer under the
condition of 35 kV/1 min/50 Hz. It is able to see that the
leakage current is about 12.6mAat the voltage of 35 kV,
4. EXHIBITION OF THE TRANSFORMER
After all the tests conducted, the constructed HTS
transformer was assembled in the superconducting power
substation.
Connection
Fig. 11 presents the accessing of the developed HTS
transformer in the superconducting power substation.
Here the 10.5-kV/1.5-kV superconducting fault current
limiter (SFCL), the 1250-kVA/10.5-kV/0.4-kV
superconducting transformer, and the 10.5-kV/1.5-kA
superconducting cable are connected in series. The
input10.5-kV bus is connected with the bridge-type SFCL,
which is used for the application of fault current
limitation. The output of the SFCL is then connected to the
constructed HTS transformer with a Y–Y connection group
in series, and the voltage is transferred to0.4 kV; the
power is supplied to the load through the three-phase
superconducting cable
Fig-11: Accessing of the superconducting transformer.
5. CONCLUSION
The evolution of a 1250-kVA/10.5-kV/0.4-kV HTS
transformer and its exhibition at a superconducting power
substation shows that it is now possible to operate HTS
transformers in the network. While comparing with the
conventional power transformer at the same rated
capacity, the potential load loss, size, and weight savings of
the HTS transformer are of great interest. Here, LN2 used
as coolant and dielectric also provides fire safety to the
conventional oil-immersed-type transformer, which is of
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072
© 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 657
considerable interest for underground substations or
some sensitive regions.
6. REFERENCES
[1] H. Ma, T. K. Saha, C. Ekanayake, and D. Martin, “Smart
transformer forsmart grid intelligent framework and
techniques for power transformer asset management,”
IEEE Trans. Smart Grid, vol. 6, no. 2, pp. 1026–1034, Mar.
2015.
[2] L. Ernesto, B. Alfredo Ursa, L. Marroyo, and P. Sanchis,
“Analytical design methodology for litz-wired high-
frequency power transformers,”IEEE Trans. Ind. Electron.,
vol. 62, no. 4, pp. 2103–2113, Apr. 2015.
[3] B. Zhao, Q. Song, and W. Liu, “A practical solution of
high-frequency link bidirectional solid-state transformer
based on advanced compon entsin hybrid microgrid,” IEEE
Trans. Ind. Electron., vol. 62, no. 7,pp. 4587–4597, Jul.
2015.
[4] A. Lapthorn, P. Bodger, and W. Enright, “A 15-kVA high-
temperature superconducting partial-core transformer-
Part 1: Transformer modeling,”IEEE Trans. Power Del., vol.
28, no. 1, pp. 245–252, Jan. 2013.
[5]S.S. Kalsi, Applications of High Temperature
Superconductors to ElectricPower Equipment. Hoboken,
NJ, USA: Wiley, 2011, ch. 7.
:

More Related Content

What's hot

G032037050
G032037050G032037050
G032037050inventy
 
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...elelijjournal
 
Iaetsd a transformerless single-stage
Iaetsd a transformerless single-stageIaetsd a transformerless single-stage
Iaetsd a transformerless single-stageIaetsd Iaetsd
 
A bridgeless cuk converter based induction motor drive for pfc applications
A bridgeless cuk converter based induction motor drive for pfc applicationsA bridgeless cuk converter based induction motor drive for pfc applications
A bridgeless cuk converter based induction motor drive for pfc applicationsIAEME Publication
 
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...Journal For Research
 
Bus duct fabrication
Bus duct fabricationBus duct fabrication
Bus duct fabricationSTUPIDPANDEY
 
IRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step DownIRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step DownIRJET Journal
 
Multilevel inverters and their types
Multilevel inverters and their typesMultilevel inverters and their types
Multilevel inverters and their typesMOHDFAIZAN75
 
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...Review of Integrated Power Factor Correction (PFC) Boost converter topologies...
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...IJARBEST JOURNAL
 
STATE-SPACE AVERAGING METHOD
STATE-SPACE AVERAGING METHOD STATE-SPACE AVERAGING METHOD
STATE-SPACE AVERAGING METHOD Slobodan Cuk
 
A three level quasi-two-stage single-phase pfc converter with flexible output...
A three level quasi-two-stage single-phase pfc converter with flexible output...A three level quasi-two-stage single-phase pfc converter with flexible output...
A three level quasi-two-stage single-phase pfc converter with flexible output...LeMeniz Infotech
 
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...paperpublications3
 
A Low Cost Single-Switch Bridgeless Boost PFC Converter
A Low Cost Single-Switch Bridgeless Boost PFC ConverterA Low Cost Single-Switch Bridgeless Boost PFC Converter
A Low Cost Single-Switch Bridgeless Boost PFC ConverterIJPEDS-IAES
 
Production and distribution of electricity
Production and distribution of electricityProduction and distribution of electricity
Production and distribution of electricityVesa Linja-aho
 

What's hot (20)

Gss report
Gss reportGss report
Gss report
 
G032037050
G032037050G032037050
G032037050
 
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Iaetsd a transformerless single-stage
Iaetsd a transformerless single-stageIaetsd a transformerless single-stage
Iaetsd a transformerless single-stage
 
A bridgeless cuk converter based induction motor drive for pfc applications
A bridgeless cuk converter based induction motor drive for pfc applicationsA bridgeless cuk converter based induction motor drive for pfc applications
A bridgeless cuk converter based induction motor drive for pfc applications
 
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...
IMPLEMENTATION OF DISCONTINUOUS INDUCTOR CURRENT MODE IN CUK CONVERTERS FED B...
 
Bus duct fabrication
Bus duct fabricationBus duct fabrication
Bus duct fabrication
 
A Novel Single Phase bridgeless AC/DC PFC converter for Low Total Harmonics D...
A Novel Single Phase bridgeless AC/DC PFC converter for Low Total Harmonics D...A Novel Single Phase bridgeless AC/DC PFC converter for Low Total Harmonics D...
A Novel Single Phase bridgeless AC/DC PFC converter for Low Total Harmonics D...
 
Tl book
Tl bookTl book
Tl book
 
Distribution system 2
Distribution system  2Distribution system  2
Distribution system 2
 
IRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step DownIRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step Down
 
Multilevel inverters and their types
Multilevel inverters and their typesMultilevel inverters and their types
Multilevel inverters and their types
 
Comparison of Z-Source EZ-Source and TZ-Source Inverter Systems for Wind Ener...
Comparison of Z-Source EZ-Source and TZ-Source Inverter Systems for Wind Ener...Comparison of Z-Source EZ-Source and TZ-Source Inverter Systems for Wind Ener...
Comparison of Z-Source EZ-Source and TZ-Source Inverter Systems for Wind Ener...
 
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...Review of Integrated Power Factor Correction (PFC) Boost converter topologies...
Review of Integrated Power Factor Correction (PFC) Boost converter topologies...
 
STATE-SPACE AVERAGING METHOD
STATE-SPACE AVERAGING METHOD STATE-SPACE AVERAGING METHOD
STATE-SPACE AVERAGING METHOD
 
A three level quasi-two-stage single-phase pfc converter with flexible output...
A three level quasi-two-stage single-phase pfc converter with flexible output...A three level quasi-two-stage single-phase pfc converter with flexible output...
A three level quasi-two-stage single-phase pfc converter with flexible output...
 
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
 
A Low Cost Single-Switch Bridgeless Boost PFC Converter
A Low Cost Single-Switch Bridgeless Boost PFC ConverterA Low Cost Single-Switch Bridgeless Boost PFC Converter
A Low Cost Single-Switch Bridgeless Boost PFC Converter
 
Production and distribution of electricity
Production and distribution of electricityProduction and distribution of electricity
Production and distribution of electricity
 

Similar to Evolution of a 1250-kVA Superconducting Transformer

Hts transformer
Hts transformerHts transformer
Hts transformerARGHA SAHA
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Projectsagnikchoudhury
 
ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...IJECEIAES
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Projectsagnikchoudhury
 
Design Approach To High Voltage High Power Steam-Turbine Driven Alternator
Design Approach To High Voltage High Power Steam-Turbine Driven AlternatorDesign Approach To High Voltage High Power Steam-Turbine Driven Alternator
Design Approach To High Voltage High Power Steam-Turbine Driven AlternatorIJPEDS-IAES
 
eBook - Electrical Engineering, Power Electronics.pdf
eBook - Electrical Engineering, Power Electronics.pdfeBook - Electrical Engineering, Power Electronics.pdf
eBook - Electrical Engineering, Power Electronics.pdfGollapalli Sreenivasulu
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptxpramod719257
 
A Study of Superconducting Transformer with Short-Circuit Current Limitation
A Study of Superconducting Transformer with Short-Circuit Current Limitation A Study of Superconducting Transformer with Short-Circuit Current Limitation
A Study of Superconducting Transformer with Short-Circuit Current Limitation IJECEIAES
 
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.ppt
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.pptOPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.ppt
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.pptMadavanR1
 
high temp superconducting transformer for railway application.ppt
high temp superconducting transformer for railway application.ppthigh temp superconducting transformer for railway application.ppt
high temp superconducting transformer for railway application.pptvaibhavn55
 
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...IJPEDS-IAES
 
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...IRJET Journal
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training reportMuntazir Mehdi
 
Design of a Non-Ideal Buck Converter
Design of a Non-Ideal Buck ConverterDesign of a Non-Ideal Buck Converter
Design of a Non-Ideal Buck ConverterIRJET Journal
 

Similar to Evolution of a 1250-kVA Superconducting Transformer (20)

Hts transformer
Hts transformerHts transformer
Hts transformer
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Project
 
ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Project
 
Design Approach To High Voltage High Power Steam-Turbine Driven Alternator
Design Approach To High Voltage High Power Steam-Turbine Driven AlternatorDesign Approach To High Voltage High Power Steam-Turbine Driven Alternator
Design Approach To High Voltage High Power Steam-Turbine Driven Alternator
 
eBook - Electrical Engineering, Power Electronics.pdf
eBook - Electrical Engineering, Power Electronics.pdfeBook - Electrical Engineering, Power Electronics.pdf
eBook - Electrical Engineering, Power Electronics.pdf
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptx
 
Bidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid ApplicationsBidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid Applications
 
A Study of Superconducting Transformer with Short-Circuit Current Limitation
A Study of Superconducting Transformer with Short-Circuit Current Limitation A Study of Superconducting Transformer with Short-Circuit Current Limitation
A Study of Superconducting Transformer with Short-Circuit Current Limitation
 
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.ppt
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.pptOPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.ppt
OPERATING PRINCIPLES OF TRANSFORMER AND CONSTRUCTION.ppt
 
Du36723729
Du36723729Du36723729
Du36723729
 
high temp superconducting transformer for railway application.ppt
high temp superconducting transformer for railway application.ppthigh temp superconducting transformer for railway application.ppt
high temp superconducting transformer for railway application.ppt
 
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...
Towards More Reliable Renewable Power Systems - Thermal Performance Evaluatio...
 
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...
Brushless DC Motor Drive using an Isolated-Luo Converter for Power Factor Cor...
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report
 
power electronics.pdf
power electronics.pdfpower electronics.pdf
power electronics.pdf
 
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
Analysis, Design and Investigation on a New Single-Phase Switched Quasi Z-Sou...
 
Shivesh ntpc ppt
Shivesh ntpc pptShivesh ntpc ppt
Shivesh ntpc ppt
 
Design of a Non-Ideal Buck Converter
Design of a Non-Ideal Buck ConverterDesign of a Non-Ideal Buck Converter
Design of a Non-Ideal Buck Converter
 
Solid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix ConverterSolid-State Transformer (S2T) of Single Phase Matrix Converter
Solid-State Transformer (S2T) of Single Phase Matrix Converter
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTUREIRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsIRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASIRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProIRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemIRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesIRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web applicationIRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignIRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 

Recently uploaded (20)

Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

Evolution of a 1250-kVA Superconducting Transformer

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072 © 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 653 Evolution of a 1250-kVa Superconducting Transformer and its Exhibition at the superconducting Substation Anas Abdul Azeez Electrical and Electronics Engineering Department, APJ Abdul Kalam Technological University ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract- A three-phase high temperature superconducting (HTS) transformer of 1250-kVA/10.5- kV/0.4-kV has been designed and manufactured. The windings of the three phase HTS transformer made of reinforced copper alloy. The formation of the primary and secondary windings of the HTS transformer is solenoid and double pancake, respectively. The core consists of three-limb and is made of domain-refined high-induction-type grain- oriented silicon sheet steel .The cryostat is fabricated of glass-fiber-reinforced plastics. From the transformer tests, the no-load loss is about 2319.2 W at an exciting current of 0.254% of the rated current. The short-circuit impedance of the HTS transformer is about 5.6% of the rated value. The average load loss is 249.6 W. In addition, the leakage current between the primary and secondary windings of the HTS transformer is about 12.6 mA under the situation of 35 kV/1 min/50 Hz. Key Words: Bi2223/Ag hermetic tapes, high-temperature superconducting (HTS) transformer, superconducting power substation, transformer test. 1.INTRODUCTION POWER transformers are one of the most important and significant devices for electrical application. Different types of transformers are constructed for different applications. There are many number of service-ready prototype high-temperature Superconducting (HTS) transformers have been introduced. The usage of HTS transformer results show that it is possible to reduce the energy loss in transformers by 60% or more by replacing the HTS windings over conventional winding With the discovery of High temperature superconductor (HTS) having higher temperature, the electrical applications of low temperature superconductor (LTS) have diminished than high temperature superconductor (HTS). HTS transformer has been expected to be one of the most wanted HTS device applications. Recently research and development about the relevance of HTS transformer have been progressed actively in the world. The market for HTS transformers will become higher and larger with the continued manufacturing of HTS transformers A transformer is an electrical device which is used in transferring of power from one circuit to another through the basic principle of electromagnetic induction. The power transfer is done without frequency change. In an electrical system, the term power transformer is used to provide a different range of AC supplies of several voltages and appropriate values of current from the public electricity supply. Usually transformer is denoted with kVa rating, 500kVa or greater. The Power transformer is a kind of transformer, which is used to transfer electrical energy in any part of the electrical or electronic system between the generator and the distribution primary circuits. The power transformers are used in distribution systems to interface step up and step down voltages. One of the common type of power transformer used is liquid immersed and the life span of these transformers is around 30 years. Power transformers are classified into three types based on the ranges. They are small, medium and large power transformers HTS transformers are classified into three : 1) on the basis of windings of different materials, HTS transformers can be classified into HTS conventional transformers were the windings made by HTS materials and HTS hybrid transformers were the windings are made by HTS and copper materials; 2) on the basis of having a magnetic core or not, HTS transformers can be classified into HTS core-type transformers and HTS air-core transformers; 3) on the basis of different application fields, HTS transformers can be classified into HTS power transformers and HTS traction transformers. The evolution of the 1250-kVA/10.5-kV/0.4-kV HTS Transformer is described in this paper, and from the testing results it is proved that the developed HTS transformer meets the requirement for operating in the grid. By considering the economic efficiency, the HTS conductor Bi2223 from Sumiton other than YBCO is used for the windings. The core of 630-kVA/10.5/0.4-kV HTS power transformer is made of amorphous alloy and the core of the 1250-kVA HTS transformer is made of domain- refined high-induction-type grain oriented silicon sheet steel. Fig -1: Arrangement of the 1250-kVA/10.5-kV/0.4-kV HTS transformer.
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072 © 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 654 Table -1: Specification of the 1250kVa HTS transformer thing Designed value No. of phase 3 Rated capacity 1250kVa Rated frequency 50Hz Rated voltage (prim./second.) 10.5kV/0.5kV Rated current (prim./second.) 69A/1804A connection Y-Y impedance 6%(std. level) Operating temperature 77K(LN2) Fig -2: Arrangement of the core. 2. DESIGN AND FABRICATION OF THE TRANSFORMER BA three-phase HTS power transformer with a capacity of 1250 kVA/10.5 kV/0.4 kV of 77 K is constructed. Liquefied nitrogen is used as coolant. Fig. 1 shows the arrangement of the 1250-kVA/10.5-kV/0.4-kVHTS transformer. Here the HTS transformer is a three-phase three-limb transformer with Y–Y connection. By comparing with the conventional transformers, the primary and secondary windings of the HTS transformer are made of HTS tapes, and liquefied nitrogen (LN2) at a temperature of77 K is used as the cooling and insulation medium. The specifications of the Superconducting transformer are presented in Table I. 2.1 Iron Fig. 2 shows the arrangement of the core, where the core is naturally air cooled. The core of the previously constructed 630-kVA HTS transformer is made of an amorphous alloy core. TABLE 2: SYMBOLS By looking through the mechanical and magnetic characteristics of amorphous alloy, the core of a three- phase transformer is usually wound with five limbs, which thereby increases the width and weight of the transformer. Since the HTS transformer is not that reliable as a conventional transformer, the convenience for assembling and maintaining is important. However, the construction of amorphous alloy cores by rolling is not as convenient for assembly and maintenance as silicon sheet steel construction. Therefore the core loss of an amorphous alloy core is much smaller when compared with the silicon sheet steel, conventional silicon sheet steel is used for the construction of core 1250-kVA HTS transformer. The core is constructed from domain-refined high-induction-type grain oriented silicon sheet steel B27R085 from Baosteel. The guaranteed value of the core loss is 0.85 W/kg at a maximum magnetic induction of 1.7 T. at a frequency of 50 Hz. the lamination factor fd is 0.97. the power for each limb Pzh (in kilovolt amperes) is 417 kVA. The diameter D0 of the core limb is taken to be310 mm. Thus, the effective cross sectional area of core limb Szh is 698.30 cm2, and the no. of turn of low-voltage winding Nl is 10, whereas the turn potential et is 23.09 V. the no. of turn of high-voltage winding Nh becomes 262, and the magnetic flux density of the core Bm is 1.49 T. 2.2 Windings Fig. 3 shows the arrangement of the winding, where the primary and secondary windings are solenoid and double pancake. Both of the primary and secondary windings of the HTS transformer are made of Bi2223 HT-CA 50 from
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072 © 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 655 Sumitomo with critical current around 170 A (77 K, self- field), and the features of the windings are presented in Table IV. HTS wires which are commonly used in high voltage power transformer can be classified into two types: the 1st one is generation of Bismuth Strontium Copper Oxides (BSCCO) HTS wires, and the 2nd one is generation of Yttrium-Barium- Copper Oxide (YBCO) HTS wires]. For BSCCO, it is mainly used in two forms: Bi2Sr2CaCu2O (Bi2212) and Bi2Sr2Ca2Cu3O (Bi2223). At present, Bi2223 has been more applied than Bi2212 because its critical temperature is 20 K higher than Bi2212. To deal with high voltage, the superconducting power Transformer needs windings that have hundreds of turns. HTS winding with YBCO wires have higher current density and better current magnetic field characteristics than BSCCO wires. Fig-3: Arrangement of the winding. TABLE 3: Specification OF THE CORE TABLE -4: SPECIFICATIONS OF WINDINGS 2.3. Cryostat Fig. 5 shows the arrangement of the cryostat. To reduce the eddy-current loss, the cryostat is to be made of non- metal materials since the magnetic field is alternating. Thus, fiberglass and epoxy that can be applied at a cryogenic environment are used to construct the cryostat of the HTS transformer. Fig. 6 shows the arrangement of the primary current lead. Since the rated current of the primary winding is 69 A and a φ 6-mm Copper wire is used as the current lead. The current lead has to endure a 35-kV/1-min/50-Hz voltage at both cryogenic and room temperatures. So a resin impregnated paper bushing is applied. To avoid the failure of insulation caused by possible condensate water on the bushing, a low- temperature endurable non-metal insulator is developed to reduce the possible discharge along the dielectric surface of the bushing. Fig-6: Arrangement of the primary current lead. (a) (b) Fig.-7: Secondary current lead. (a) Arrangement. (b) Schematic. 3. TESTS OF THE TRANSFORMER Tests on transformer includes: No-Load Test Short- Circuit Test Insulation Test TABLE-5: INSULATION RESISTANCE
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072 © 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 656 TABLE-6: TEST RESULTS FOR THE 1250-kVA HTS TRANSFORMER 3.1. No-Load Test These tests include insulation resistance among the primary and secondary windings and core (ground), transformer ratio and connection group, and the no-load current and loss test. The tests are carried out under the condition that the windings are completely immersed in liquefied nitrogen (LN2) for more than 24 hr Table V shows the insulation test results including the insulation resistance between the primary and secondary winding, the primary winding and iron connected with ground, and the secondary winding and core connected with ground. It’s not that difficult to find that the tested values are far above the required values. The main test results of no-load tests for the HTS transformer are shown in Table VI. 3.2. Short-Circuit Test The conventional electric method with a power analyzer was applied in the short-circuit test .and the HTS transformer was excited from the primary side at 69 A/50 Hz for 24 h. The accuracy of the applied power analyzer is 0.3% under the power factor of 0.01.According to the insulation test, the short-circuit impedance of the HTS transformer is 5.6% of the rated value, and the average load loss is 249.6W, which includes the ac loss of windings and the joule heat of current leads. Fig-8: Showing Insulation between the primary and secondary windings 3.3. Insulation Test Fig. 9 shows the insulation between the primary and secondary windings of the HTS transformer under the condition of 35 kV/1 min/50 Hz. It is able to see that the leakage current is about 12.6mAat the voltage of 35 kV, 4. EXHIBITION OF THE TRANSFORMER After all the tests conducted, the constructed HTS transformer was assembled in the superconducting power substation. Connection Fig. 11 presents the accessing of the developed HTS transformer in the superconducting power substation. Here the 10.5-kV/1.5-kV superconducting fault current limiter (SFCL), the 1250-kVA/10.5-kV/0.4-kV superconducting transformer, and the 10.5-kV/1.5-kA superconducting cable are connected in series. The input10.5-kV bus is connected with the bridge-type SFCL, which is used for the application of fault current limitation. The output of the SFCL is then connected to the constructed HTS transformer with a Y–Y connection group in series, and the voltage is transferred to0.4 kV; the power is supplied to the load through the three-phase superconducting cable Fig-11: Accessing of the superconducting transformer. 5. CONCLUSION The evolution of a 1250-kVA/10.5-kV/0.4-kV HTS transformer and its exhibition at a superconducting power substation shows that it is now possible to operate HTS transformers in the network. While comparing with the conventional power transformer at the same rated capacity, the potential load loss, size, and weight savings of the HTS transformer are of great interest. Here, LN2 used as coolant and dielectric also provides fire safety to the conventional oil-immersed-type transformer, which is of
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 05 Issue: 11 | Nov 2018 www.irjet.net p-ISSN: 2395-0072 © 2018, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 657 considerable interest for underground substations or some sensitive regions. 6. REFERENCES [1] H. Ma, T. K. Saha, C. Ekanayake, and D. Martin, “Smart transformer forsmart grid intelligent framework and techniques for power transformer asset management,” IEEE Trans. Smart Grid, vol. 6, no. 2, pp. 1026–1034, Mar. 2015. [2] L. Ernesto, B. Alfredo Ursa, L. Marroyo, and P. Sanchis, “Analytical design methodology for litz-wired high- frequency power transformers,”IEEE Trans. Ind. Electron., vol. 62, no. 4, pp. 2103–2113, Apr. 2015. [3] B. Zhao, Q. Song, and W. Liu, “A practical solution of high-frequency link bidirectional solid-state transformer based on advanced compon entsin hybrid microgrid,” IEEE Trans. Ind. Electron., vol. 62, no. 7,pp. 4587–4597, Jul. 2015. [4] A. Lapthorn, P. Bodger, and W. Enright, “A 15-kVA high- temperature superconducting partial-core transformer- Part 1: Transformer modeling,”IEEE Trans. Power Del., vol. 28, no. 1, pp. 245–252, Jan. 2013. [5]S.S. Kalsi, Applications of High Temperature Superconductors to ElectricPower Equipment. Hoboken, NJ, USA: Wiley, 2011, ch. 7. :