SlideShare a Scribd company logo
1 of 42
Contents
1. Measurement connection
2. StartMask
3. Calibration
4. Measurement
5. Evaluation “Quick Overview”
One of the most important parts of the PD measurement is ensuring a
good connection to the test-object.
A faulty connection to the test-object could cause the following problems:
 increased Background noise;
 PD‘s at the near termination;
 no PD‘s;
 „not loading“ the test-object.
Measurement connection
Earthing requirements:
 when having a corroded earthing or sheath, remove corrosion (on the place where
the connectors will be connected)
 otherwise increased Background noise
 when possible always connect the sheath of the extension-cable directly on the
sheath of the test object
 Otherwise increased damping of the signals
 always connect the earthing of the test-van itself on the same point as the sheath of
the extension cable
 because of loop, increased Background noise
Measurement connection
Earthing
Copper corosion
With the connection of the extension cable it should be observed that the
unshielded part of the cable does not touch or is close to earthed
components.
Earthed components are:
- Floor
- Switchgear
- Cabledrum
- Sheath of the extension cable
A minimum clearance of 5 till 10cm is strictly
necessary.
(between unshielded part and earthed component)
Measurement connection
Connecting extension cable
But like this:
Measurement connection
Connecting extension cable
During the measurement the following requirements apply.
 Current-transformers (CT‘s) can be left connected;
 Voltage-transformers (VT‘s) must be disconnected;
 Surge-arresters ideally have to be disconnected. They can be left connected,
however the chance exists that the cable at voltages >= U0 cannot be loaded
anymore since the leakage current through the surge-arrester is to high;
 Other two phases have to be earthed during the measurement.
What kind of field-distribution we have got in joints???
Measurement connection
Connection during measurement
Needs to be applied for „short“ cables to decrease the frequency:
 e.g. XLPE cables < 300m
 at Error message: “Frequency too high, please use additional capacitor!”
Important, earth properly!!! -> otherwise PD can be created
Test
Object
Measurement connection
Additional capacitor
Contents
1. Measurement connection
2. StartMask
3. Calibration
4. Measurement
5. Evaluation “Quick Overview”
Important for the measurement!
 Data entry of U0 (for 20kV cables enter 11.6kV as
U0)
 Data entry of the cable-length
Joint-entry; acc. to position from near
termination.
Load loading an existing Startmask (e.g.
created by the Excel-Macro);
Clone (Copying) copying an existing
Startmask (creating new folder with
current date and time);
OK accepting the standard definition;
New creating a new Startmask;
Hint: With three one-phase cables first
enter the data as a single three-phase
cable afterwards change it to three one-
phase cables.
Generating Startmask
Contents
1. Measurement connection
2. StartMask
3. Calibration
4. Measurement
5. Evaluation “Quick Overview”
Goal of the calibration is to:
 measure according to the international norm IEC 60270;
 determine the propagation velocity v of the cable, which is required for the
localization.
Additionally joints can be recognized in this modus.
However attention has to be paid!!!!!
Faulty calibrations can lead to:
 Extremely high background noise;
 A scattered PD-Mapping (PD‘s not on straight line) because of difference in v ‘s.
Calibration
 Connect between core and sheath;
 Twist connection cables as far as possible;
 Always keep the frequency on 100Hz.
SebaKMT recommends to calibrate the Calibrator every two years
and to replace the batteries every year (no matter what the battery
indication shows).
Calibration
Connection
100Hz
500pC
 Always start calibration with the highest value (100nC).
Note: The only exception is cables shorter than 300m, then start with 500pC.
 SebaKMT recommends to calibrate the entire range from 100nC to 200
(100)pC. This to avoid time-consuming re-calibration.
 Especially 100 und 200pC can sometimes not be calibrated because of
high background noise activity. „What doesn‘t go, does not go…“
 When the automatic calibration takes to long it is better to stop the
automatic calibration and continue manually. Best practice is to use the
PgUp and PgDn keys instead of the logarithmic slide-bar on the left hand
side!!!
Calibration
The calibration
One calibration for all
phases is sufficient.
At three singe-phase
cables change Phase
to „All“.
Calibration
The calibration
Press arrow in upper
right-hand corner.
 move yellow marker
to the maximum of
the reflection of the
joint and the distance
of the joint can be
read.
Calibration
Joint recognition
Check VHF
For cables shorter
then 100m the
following settings
are required:
1)Press setup and
check if VHF is
turned on;
(is automatically
turned on for cables shorter
than 500m)
2)Adjust slide-bar to
short cable;
3)Then continue
with the calibration. 1
2
Calibration
Calibration of short cable lengths
For long cables or cables with a high attenuation it could happen that the
endreflection is not visible anymore. How to set the second marker then?
Approach in such cases:
a) Set 100nC, stop automatic calibration and
manually increase the amplification until an
end-reflection becomes visible.
b) Move second marker to the correct position
and adjust amplification level back to 80%
level.
c) Notice the v and position the marker for
further calibrations based on this v.
When at a) no end-reflection could have been
recognized, the second marker has to be set,
based on a v of 160m/µsec.
Of course always measure from both ends!!!
Calibration
Calibration of long cable lengths
Cable-data:
Voltage: 20kV
Type: NA2XS(f)2Y
Year: 2006
Length: 3500m
Joints: 6 pieces
All_1000.cal
N:...All_1000.cal Monday, May 26, 2008 8:16 PM
Time (us)
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
Range
[%]
100
90
80
70
60
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
One side will do.
Calibration
Example attenuation of the cable
Cable-data:
Voltage: 10kV
Type: NAKBA
Year: 1970
Length: 570m
Joints: 3 pieces
All_1000.cal
N:...All_1000.cal 09/04/2010 08:35
Time (us)
12
11
10
9
8
7
6
5
4
3
2
1
0
Range
[%]
100
90
80
70
60
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
Measurement from both sides
recommended!!
Calibration
Example attenuation of the cable
Cable-data:
Voltage: 11,6kV
Type: NA2XS2Y
Year: 1993
Length: 2370m
Joints: - pieces
All_1000.cal
N:...All_1000.cal Sunday, January 18, 2009 13:33
Time (us)
50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Range
[%]
100
90
80
70
60
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
Calibration
Example attenuation of the cable
The calibration provides the user from valuable information. Based on the
calibration it e.g. becomes clear if a measurement has to be performed from
both sides yes or no.
This decision for measuring from both ends is depending on the attenuation
of the cable.
The attenuation is influenced by several factors:
 Cable-type (Isolation)
 Cable condition (new, aged)
 Voltage class
 Manufacturer
 Number of joints
Generally we recommend to measure cables from both sides if they are
longer then 2km. However as the following examples will show that this will
not always be correct!!!! Better is to always make the decision based on the
calibration itself.
Calibration
What can we learn from the calibration?
Contents
1. Measurement connection
2. StartMask
3. Calibration
4. Measurement
5. Evaluation “Quick Overview”
Settings:
Display modus: 16 AC-Cycles
Phase: L1
PD-Range: lowest one
Voltage entry: U0
Measurement
Measurment approach
Measurement
0kV
0,5U0
- Determine PDIV
- Save PDIV
- Increase voltage with 0,1U0
and every time save data
1U0
1,3U0
1,5U0
Save
PD existing No PD
- Determine PDIV
- Save PDIV
- Increase voltage with 0,1U0
and every time save data
- Determine and save PDIV
- Increase voltage with 0,1U0
and every time save data
- Determine and save PDEV
PD existing No PD
Save
PD existing No PD
Measurement
Measurment approach
Summary Data Collection Procedure
PDIV Less Than Uo Condition
Test Voltage Function Key Freq
0Uo F7 1
↑Uo →PDIV F8 1
1.0Uo F7 5
1.3Uo
F7 5
F9 1
PDIV More Than Uo Condition
Test Voltage Function Key Freq
0Uo F7 1
↑Uo →PDIV
F8 1
F7 5
1.3Uo
F7 5
F9 1
Practical tips:
 Always select the proper PD-range, e.g. do not save PD‘s of 200pC
height with a PD-range of 5nC.
Or the other way around save PD‘s which are higher then the selected
PD-range!!!
 Save as PDIV if from 2 of the 3 measurements PD is present;
 Only save PDEV when PDIV ≥ U0;
 Also for the PDEV perform 3 measurements and take the average value;
 In total three data-sets have to be saved if the cable is PD-free (0kV, U0
and1.3U0).
Measurement
Practical tips
 Determining the extinction voltage is then possible if PD‘s occur over
more then two AC cycles.
 PDEV must not necessarily be saved at 1.3U0, if PD‘s occur over more
then two AC cycles directly determine the PDEV and save it.
 Of major importance is to select the correct PD-range (500pC). Only in
this case PD‘s may clip. Goal is to determine the PDEV, not to save data
for the TDR analysis!!!
Selecting faulty PD-range will in most cases result in a PDEV higher then the PDIV, which is not possible!!!
Measurement
Determination of PDEV
0
0
V0
t → s
t → s
kV
↑
V
i↑
PDIV
PDEV
0
0
V0
t → s
t → s
kV
↑
V
i↑
PDEV
PDIV
PDIV – Partial Discharge Inception Voltage; the voltage where the first discharges
appear (incept).
PDEV – Partial Discharge Extinction Voltage; the voltage where the discharges
disappear (extinct). In practice 10 to 35% below inception voltage.
PDEV below U0.
Dangerous
situation!! PD
remains after
overvoltage.
PDEV above U0.
PD only occurs
during
overvoltage
Measurement
Importance of PDEV
Dielectric losses are the losses that occur in the insulation material.
An increase in tanδ as function of the operating voltage like in the picture
below, means aged insulation or local weak-spots.
Values measured with the OWTS are given in percentages, according to the
value of the dielectric losses the following distinctions can be made:
Tan delta Condition of the cable
0.1 < tan δ < 0.9% dry
0.9% < tan δ < 2% moisture
tan δ > 2% wet
Measurement
Dielectric loss summary
Contents
1. Measurement connection
2. StartMask
3. Calibration
4. Measurement
5. Evaluation “Quick Overview”
The purpose of the Quick overview is to give a first estimation of the
condition of the cable.
Based on this overview direct measures can be scheduled e.g. replacement
of PD-affected joints.
However because it is an automatically compiled PD-mapping, a manual
evaluation is still required/ advised!!!
Evaluation „Quick Overview“
Evaluation „Quick Overview“
Step 1: Select data
Correctly set
Bandwidth!!!
Select Quick
Overview and
press Accept
Evaluation „Quick Overview“
Step 2: Start quick overview
 Check PD-concentrations
by right-clicking on PD spot
with the Mouse and select
„View PD-Pulse“
 With help from the
„Threshold“ function PD-
concentrations can be
displayed more clearly
 Based on these results
direct measures can be
scheduled e.g. replacement
of PD affected joints
 However a manual
evaluation is always
required.
Evaluation „Quick Overview“
Step 3: Check quick overview result
Before
adaptation
Evaluation „Quick Overview“
Step 3: Example threshold
After adaptation
Threshold-level of
510pC
Evaluation „Quick Overview“
Step 3: Example threshold
The Cluster Strength is a new feature (only available as a Beta Version
and only functions when having OWTS Explorer V4.0) which looks to PD
concentrations.
If there is a weak spot, there will always be several PD pulses.
The software skips the cable parts where the PD concentration looking to
the cable length is 2 or less.
If two or less the PD will not be shown in the PD Mapping.
This new feature significantly increases the usability of the quick
overview function.
Note: scattered PD in paper-mass will also not be shown in a PD
mapping
Evaluation „Quick Overview“
New: Cluster strength (Beta Version only)
“Threshold” 0 pC and “Cluster strength” 0
Evaluation „Quick Overview“
New: Cluster strength (Beta Version only)
“Threshold” 0 pC and “Cluster strength” 40 (default)
Evaluation „Quick Overview“
New: Cluster strength (Beta Version only)
Manual evaluation
Evaluation „Quick Overview“
New: Cluster strength (Beta Version only)
L1
L2
L3
PD mapping for
3phase20100720_man.3PF
Location (m)
2.000
1.900
1.800
1.700
1.600
1.500
1.400
1.300
1.200
1.100
1.000
900
800
700
600
500
400
300
200
100
0
PD
(pC)
1.200
1.100
1.000
900
800
700
600
500
400
300
200
100
0

More Related Content

What's hot

2. RCA - Huong dan phan tich rca
2. RCA - Huong dan phan tich rca2. RCA - Huong dan phan tich rca
2. RCA - Huong dan phan tich rcaLy Quoc Trung
 
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...Nguyen Thanh Tu Collection
 
Giáo trình hóa lý tập 1 nguyễn đình huề-100205
Giáo trình hóa lý  tập 1   nguyễn đình huề-100205Giáo trình hóa lý  tập 1   nguyễn đình huề-100205
Giáo trình hóa lý tập 1 nguyễn đình huề-100205HoaPinky
 
אישור תואר וציונים
אישור תואר וציוניםאישור תואר וציונים
אישור תואר וציוניםAlon Zinger
 
Plano caballete
Plano caballetePlano caballete
Plano caballetenanumus
 
Marti misterija lms 019 tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)
Marti misterija lms 019   tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)Marti misterija lms 019   tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)
Marti misterija lms 019 tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)zoran radovic
 

What's hot (6)

2. RCA - Huong dan phan tich rca
2. RCA - Huong dan phan tich rca2. RCA - Huong dan phan tich rca
2. RCA - Huong dan phan tich rca
 
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...
BẢN DỊCH TIẾNG VIỆT BÀI TẬP CHUẨN BỊ OLYMPIAD HÓA HỌC QUỐC TẾ AL-BERUNIY 2023...
 
Giáo trình hóa lý tập 1 nguyễn đình huề-100205
Giáo trình hóa lý  tập 1   nguyễn đình huề-100205Giáo trình hóa lý  tập 1   nguyễn đình huề-100205
Giáo trình hóa lý tập 1 nguyễn đình huề-100205
 
אישור תואר וציונים
אישור תואר וציוניםאישור תואר וציונים
אישור תואר וציונים
 
Plano caballete
Plano caballetePlano caballete
Plano caballete
 
Marti misterija lms 019 tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)
Marti misterija lms 019   tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)Marti misterija lms 019   tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)
Marti misterija lms 019 tajanstvena ubistva (nebody-bds &amp; emeri)(7.3 mb)
 

Similar to OWTS M28.ppt

Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Thorne & Derrick International
 
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkei
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkeiLss6330 catalogue noiseken_Lightning_surge_simulator_denkei
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkeiNIHON DENKEI SINGAPORE
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems SafetyTalia Carbis
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSData Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSPT. Siwali Swantika
 
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...Thorne & Derrick International
 
dt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdfdt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdfssuserbfa471
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cableSyed Atif Naseem
 
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...Fluke Networks
 
Digital clampmeters
Digital clampmetersDigital clampmeters
Digital clampmetersmecoinst
 
P D Measurements On H V Joints
P D  Measurements On  H V JointsP D  Measurements On  H V Joints
P D Measurements On H V JointsAol_Amil
 
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618PT. Siwali Swantika
 
Cable preparation in CCTV
Cable preparation in CCTVCable preparation in CCTV
Cable preparation in CCTVhepzijustin
 

Similar to OWTS M28.ppt (20)

ESDEMC CDE IEEE Symposium 2014
ESDEMC CDE IEEE Symposium 2014ESDEMC CDE IEEE Symposium 2014
ESDEMC CDE IEEE Symposium 2014
 
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
Adoption of Best Practices for Cable Testing and Condition Monitoring In The ...
 
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkei
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkeiLss6330 catalogue noiseken_Lightning_surge_simulator_denkei
Lss6330 catalogue noiseken_Lightning_surge_simulator_denkei
 
Electrical testing
Electrical testingElectrical testing
Electrical testing
 
SebKMT Cable Sheath testers & Fault Locators
SebKMT Cable Sheath testers & Fault LocatorsSebKMT Cable Sheath testers & Fault Locators
SebKMT Cable Sheath testers & Fault Locators
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
 
HVDCT LAB MANUAL.docx
HVDCT LAB MANUAL.docxHVDCT LAB MANUAL.docx
HVDCT LAB MANUAL.docx
 
Katalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamikaKatalog fluke-1621-earth-ground-tester-by-tridinamika
Katalog fluke-1621-earth-ground-tester-by-tridinamika
 
Executive summary
Executive summaryExecutive summary
Executive summary
 
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUSData Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
Data Teknis Gossen Metrawatt Multimeter : METRAHIT T-COM PLUS
 
Cable test set_easytest_20_kv
Cable test set_easytest_20_kvCable test set_easytest_20_kv
Cable test set_easytest_20_kv
 
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...
SEBA KMT Cable Fault Locators, Surge Generators (Thumpers) - SEBA KMT Cable F...
 
B1102030610
B1102030610B1102030610
B1102030610
 
dt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdfdt830d-multimeter-datasheet.pdf
dt830d-multimeter-datasheet.pdf
 
Insulation testing of power cable
Insulation testing of power cableInsulation testing of power cable
Insulation testing of power cable
 
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...
How to Use the DTX-MFM2 Fiber Modules to Test Installed Corning Multimode Pre...
 
Digital clampmeters
Digital clampmetersDigital clampmeters
Digital clampmeters
 
P D Measurements On H V Joints
P D  Measurements On  H V JointsP D  Measurements On  H V Joints
P D Measurements On H V Joints
 
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Fluke 1621. Hubungi PT. Siwali Swantika 021-45850618
 
Cable preparation in CCTV
Cable preparation in CCTVCable preparation in CCTV
Cable preparation in CCTV
 

Recently uploaded

Independent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging StationIndependent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging Stationsiddharthteach18
 
Artificial intelligence presentation2-171219131633.pdf
Artificial intelligence presentation2-171219131633.pdfArtificial intelligence presentation2-171219131633.pdf
Artificial intelligence presentation2-171219131633.pdfKira Dess
 
engineering chemistry power point presentation
engineering chemistry  power point presentationengineering chemistry  power point presentation
engineering chemistry power point presentationsj9399037128
 
Final DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualFinal DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualBalamuruganV28
 
Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...IJECEIAES
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...drjose256
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptamrabdallah9
 
5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...archanaece3
 
Software Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfSoftware Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfssuser5c9d4b1
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniR. Sosa
 
handbook on reinforce concrete and detailing
handbook on reinforce concrete and detailinghandbook on reinforce concrete and detailing
handbook on reinforce concrete and detailingAshishSingh1301
 
Interfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfInterfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfragupathi90
 
Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..MaherOthman7
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1T.D. Shashikala
 
21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological university21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological universityMohd Saifudeen
 
Worksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxWorksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxMustafa Ahmed
 
Seizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networksSeizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networksIJECEIAES
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxMustafa Ahmed
 
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTUUNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTUankushspencer015
 
analog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptxanalog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptxKarpagam Institute of Teechnology
 

Recently uploaded (20)

Independent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging StationIndependent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging Station
 
Artificial intelligence presentation2-171219131633.pdf
Artificial intelligence presentation2-171219131633.pdfArtificial intelligence presentation2-171219131633.pdf
Artificial intelligence presentation2-171219131633.pdf
 
engineering chemistry power point presentation
engineering chemistry  power point presentationengineering chemistry  power point presentation
engineering chemistry power point presentation
 
Final DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualFinal DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manual
 
Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.ppt
 
5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...5G and 6G refer to generations of mobile network technology, each representin...
5G and 6G refer to generations of mobile network technology, each representin...
 
Software Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdfSoftware Engineering Practical File Front Pages.pdf
Software Engineering Practical File Front Pages.pdf
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney Uni
 
handbook on reinforce concrete and detailing
handbook on reinforce concrete and detailinghandbook on reinforce concrete and detailing
handbook on reinforce concrete and detailing
 
Interfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfInterfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdf
 
Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..
 
Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1Research Methodolgy & Intellectual Property Rights Series 1
Research Methodolgy & Intellectual Property Rights Series 1
 
21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological university21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological university
 
Worksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxWorksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptx
 
Seizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networksSeizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networks
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTUUNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
 
analog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptxanalog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptx
 

OWTS M28.ppt

  • 1. Contents 1. Measurement connection 2. StartMask 3. Calibration 4. Measurement 5. Evaluation “Quick Overview”
  • 2.
  • 3. One of the most important parts of the PD measurement is ensuring a good connection to the test-object. A faulty connection to the test-object could cause the following problems:  increased Background noise;  PD‘s at the near termination;  no PD‘s;  „not loading“ the test-object. Measurement connection
  • 4. Earthing requirements:  when having a corroded earthing or sheath, remove corrosion (on the place where the connectors will be connected)  otherwise increased Background noise  when possible always connect the sheath of the extension-cable directly on the sheath of the test object  Otherwise increased damping of the signals  always connect the earthing of the test-van itself on the same point as the sheath of the extension cable  because of loop, increased Background noise Measurement connection Earthing Copper corosion
  • 5. With the connection of the extension cable it should be observed that the unshielded part of the cable does not touch or is close to earthed components. Earthed components are: - Floor - Switchgear - Cabledrum - Sheath of the extension cable A minimum clearance of 5 till 10cm is strictly necessary. (between unshielded part and earthed component) Measurement connection Connecting extension cable
  • 6. But like this: Measurement connection Connecting extension cable
  • 7. During the measurement the following requirements apply.  Current-transformers (CT‘s) can be left connected;  Voltage-transformers (VT‘s) must be disconnected;  Surge-arresters ideally have to be disconnected. They can be left connected, however the chance exists that the cable at voltages >= U0 cannot be loaded anymore since the leakage current through the surge-arrester is to high;  Other two phases have to be earthed during the measurement. What kind of field-distribution we have got in joints??? Measurement connection Connection during measurement
  • 8. Needs to be applied for „short“ cables to decrease the frequency:  e.g. XLPE cables < 300m  at Error message: “Frequency too high, please use additional capacitor!” Important, earth properly!!! -> otherwise PD can be created Test Object Measurement connection Additional capacitor
  • 9. Contents 1. Measurement connection 2. StartMask 3. Calibration 4. Measurement 5. Evaluation “Quick Overview”
  • 10. Important for the measurement!  Data entry of U0 (for 20kV cables enter 11.6kV as U0)  Data entry of the cable-length Joint-entry; acc. to position from near termination. Load loading an existing Startmask (e.g. created by the Excel-Macro); Clone (Copying) copying an existing Startmask (creating new folder with current date and time); OK accepting the standard definition; New creating a new Startmask; Hint: With three one-phase cables first enter the data as a single three-phase cable afterwards change it to three one- phase cables. Generating Startmask
  • 11. Contents 1. Measurement connection 2. StartMask 3. Calibration 4. Measurement 5. Evaluation “Quick Overview”
  • 12. Goal of the calibration is to:  measure according to the international norm IEC 60270;  determine the propagation velocity v of the cable, which is required for the localization. Additionally joints can be recognized in this modus. However attention has to be paid!!!!! Faulty calibrations can lead to:  Extremely high background noise;  A scattered PD-Mapping (PD‘s not on straight line) because of difference in v ‘s. Calibration
  • 13.  Connect between core and sheath;  Twist connection cables as far as possible;  Always keep the frequency on 100Hz. SebaKMT recommends to calibrate the Calibrator every two years and to replace the batteries every year (no matter what the battery indication shows). Calibration Connection 100Hz 500pC
  • 14.  Always start calibration with the highest value (100nC). Note: The only exception is cables shorter than 300m, then start with 500pC.  SebaKMT recommends to calibrate the entire range from 100nC to 200 (100)pC. This to avoid time-consuming re-calibration.  Especially 100 und 200pC can sometimes not be calibrated because of high background noise activity. „What doesn‘t go, does not go…“  When the automatic calibration takes to long it is better to stop the automatic calibration and continue manually. Best practice is to use the PgUp and PgDn keys instead of the logarithmic slide-bar on the left hand side!!! Calibration The calibration
  • 15. One calibration for all phases is sufficient. At three singe-phase cables change Phase to „All“. Calibration The calibration
  • 16. Press arrow in upper right-hand corner.  move yellow marker to the maximum of the reflection of the joint and the distance of the joint can be read. Calibration Joint recognition
  • 17. Check VHF For cables shorter then 100m the following settings are required: 1)Press setup and check if VHF is turned on; (is automatically turned on for cables shorter than 500m) 2)Adjust slide-bar to short cable; 3)Then continue with the calibration. 1 2 Calibration Calibration of short cable lengths
  • 18. For long cables or cables with a high attenuation it could happen that the endreflection is not visible anymore. How to set the second marker then? Approach in such cases: a) Set 100nC, stop automatic calibration and manually increase the amplification until an end-reflection becomes visible. b) Move second marker to the correct position and adjust amplification level back to 80% level. c) Notice the v and position the marker for further calibrations based on this v. When at a) no end-reflection could have been recognized, the second marker has to be set, based on a v of 160m/µsec. Of course always measure from both ends!!! Calibration Calibration of long cable lengths
  • 19. Cable-data: Voltage: 20kV Type: NA2XS(f)2Y Year: 2006 Length: 3500m Joints: 6 pieces All_1000.cal N:...All_1000.cal Monday, May 26, 2008 8:16 PM Time (us) 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 Range [%] 100 90 80 70 60 50 40 30 20 10 0 -10 -20 -30 -40 -50 -60 -70 -80 -90 -100 One side will do. Calibration Example attenuation of the cable
  • 20. Cable-data: Voltage: 10kV Type: NAKBA Year: 1970 Length: 570m Joints: 3 pieces All_1000.cal N:...All_1000.cal 09/04/2010 08:35 Time (us) 12 11 10 9 8 7 6 5 4 3 2 1 0 Range [%] 100 90 80 70 60 50 40 30 20 10 0 -10 -20 -30 -40 -50 -60 -70 -80 -90 -100 Measurement from both sides recommended!! Calibration Example attenuation of the cable
  • 21. Cable-data: Voltage: 11,6kV Type: NA2XS2Y Year: 1993 Length: 2370m Joints: - pieces All_1000.cal N:...All_1000.cal Sunday, January 18, 2009 13:33 Time (us) 50 48 46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0 Range [%] 100 90 80 70 60 50 40 30 20 10 0 -10 -20 -30 -40 -50 -60 -70 -80 -90 -100 Calibration Example attenuation of the cable
  • 22. The calibration provides the user from valuable information. Based on the calibration it e.g. becomes clear if a measurement has to be performed from both sides yes or no. This decision for measuring from both ends is depending on the attenuation of the cable. The attenuation is influenced by several factors:  Cable-type (Isolation)  Cable condition (new, aged)  Voltage class  Manufacturer  Number of joints Generally we recommend to measure cables from both sides if they are longer then 2km. However as the following examples will show that this will not always be correct!!!! Better is to always make the decision based on the calibration itself. Calibration What can we learn from the calibration?
  • 23. Contents 1. Measurement connection 2. StartMask 3. Calibration 4. Measurement 5. Evaluation “Quick Overview”
  • 24. Settings: Display modus: 16 AC-Cycles Phase: L1 PD-Range: lowest one Voltage entry: U0 Measurement Measurment approach
  • 26. 0kV 0,5U0 - Determine PDIV - Save PDIV - Increase voltage with 0,1U0 and every time save data 1U0 1,3U0 1,5U0 Save PD existing No PD - Determine PDIV - Save PDIV - Increase voltage with 0,1U0 and every time save data - Determine and save PDIV - Increase voltage with 0,1U0 and every time save data - Determine and save PDEV PD existing No PD Save PD existing No PD Measurement Measurment approach
  • 27. Summary Data Collection Procedure PDIV Less Than Uo Condition Test Voltage Function Key Freq 0Uo F7 1 ↑Uo →PDIV F8 1 1.0Uo F7 5 1.3Uo F7 5 F9 1 PDIV More Than Uo Condition Test Voltage Function Key Freq 0Uo F7 1 ↑Uo →PDIV F8 1 F7 5 1.3Uo F7 5 F9 1
  • 28. Practical tips:  Always select the proper PD-range, e.g. do not save PD‘s of 200pC height with a PD-range of 5nC. Or the other way around save PD‘s which are higher then the selected PD-range!!!  Save as PDIV if from 2 of the 3 measurements PD is present;  Only save PDEV when PDIV ≥ U0;  Also for the PDEV perform 3 measurements and take the average value;  In total three data-sets have to be saved if the cable is PD-free (0kV, U0 and1.3U0). Measurement Practical tips
  • 29.  Determining the extinction voltage is then possible if PD‘s occur over more then two AC cycles.  PDEV must not necessarily be saved at 1.3U0, if PD‘s occur over more then two AC cycles directly determine the PDEV and save it.  Of major importance is to select the correct PD-range (500pC). Only in this case PD‘s may clip. Goal is to determine the PDEV, not to save data for the TDR analysis!!! Selecting faulty PD-range will in most cases result in a PDEV higher then the PDIV, which is not possible!!! Measurement Determination of PDEV
  • 30. 0 0 V0 t → s t → s kV ↑ V i↑ PDIV PDEV 0 0 V0 t → s t → s kV ↑ V i↑ PDEV PDIV PDIV – Partial Discharge Inception Voltage; the voltage where the first discharges appear (incept). PDEV – Partial Discharge Extinction Voltage; the voltage where the discharges disappear (extinct). In practice 10 to 35% below inception voltage. PDEV below U0. Dangerous situation!! PD remains after overvoltage. PDEV above U0. PD only occurs during overvoltage Measurement Importance of PDEV
  • 31. Dielectric losses are the losses that occur in the insulation material. An increase in tanδ as function of the operating voltage like in the picture below, means aged insulation or local weak-spots. Values measured with the OWTS are given in percentages, according to the value of the dielectric losses the following distinctions can be made: Tan delta Condition of the cable 0.1 < tan δ < 0.9% dry 0.9% < tan δ < 2% moisture tan δ > 2% wet Measurement Dielectric loss summary
  • 32. Contents 1. Measurement connection 2. StartMask 3. Calibration 4. Measurement 5. Evaluation “Quick Overview”
  • 33. The purpose of the Quick overview is to give a first estimation of the condition of the cable. Based on this overview direct measures can be scheduled e.g. replacement of PD-affected joints. However because it is an automatically compiled PD-mapping, a manual evaluation is still required/ advised!!! Evaluation „Quick Overview“
  • 35. Correctly set Bandwidth!!! Select Quick Overview and press Accept Evaluation „Quick Overview“ Step 2: Start quick overview
  • 36.  Check PD-concentrations by right-clicking on PD spot with the Mouse and select „View PD-Pulse“  With help from the „Threshold“ function PD- concentrations can be displayed more clearly  Based on these results direct measures can be scheduled e.g. replacement of PD affected joints  However a manual evaluation is always required. Evaluation „Quick Overview“ Step 3: Check quick overview result
  • 38. After adaptation Threshold-level of 510pC Evaluation „Quick Overview“ Step 3: Example threshold
  • 39. The Cluster Strength is a new feature (only available as a Beta Version and only functions when having OWTS Explorer V4.0) which looks to PD concentrations. If there is a weak spot, there will always be several PD pulses. The software skips the cable parts where the PD concentration looking to the cable length is 2 or less. If two or less the PD will not be shown in the PD Mapping. This new feature significantly increases the usability of the quick overview function. Note: scattered PD in paper-mass will also not be shown in a PD mapping Evaluation „Quick Overview“ New: Cluster strength (Beta Version only)
  • 40. “Threshold” 0 pC and “Cluster strength” 0 Evaluation „Quick Overview“ New: Cluster strength (Beta Version only)
  • 41. “Threshold” 0 pC and “Cluster strength” 40 (default) Evaluation „Quick Overview“ New: Cluster strength (Beta Version only)
  • 42. Manual evaluation Evaluation „Quick Overview“ New: Cluster strength (Beta Version only) L1 L2 L3 PD mapping for 3phase20100720_man.3PF Location (m) 2.000 1.900 1.800 1.700 1.600 1.500 1.400 1.300 1.200 1.100 1.000 900 800 700 600 500 400 300 200 100 0 PD (pC) 1.200 1.100 1.000 900 800 700 600 500 400 300 200 100 0