Remediation of Old Substations for Arc Flash Hazard
Zakir Husain, Deepak Kumar, Khushbu Thakur
Departement of Electrical Engineering, National Institute of Technology, Hamirpur, HP, India
Article Info ABSTRACT
Article history:
Received Jan 11, 2014
Revised Feb 21, 2014
Accepted Mar 8, 2014
Arc Flash is much different from the conventional shock hazard in the sense
that it doesn’t involve direct contact of human beings with the live or
energized part. The arcing energy involves high temperature of up to or
beyond 20000K. This paper presents a case study of arc flash hazard analysis
carried out in older industrial plant and the technological and work procedure
changes that can be incorporated to reduce the incident energy level and thus
provide a safer environment for the working personnels in plant.
Keyword:
Flash Protection Boundary
Incident Energy
PCC
Relay coordination
Copyright © 2014 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
1. INTRODUCTION
Arc Flash Hazard even after extensive study remains an unexplored area in most of the substations
in India as the switchgears used are almost 30 years old with protection system designed to address short-
circuit fault isolation. Thus arc flash hazard levels for these existing substations is quite high allowing almost
no work to be done in live panels even with PPEs of 20cal/cm2. However for maintenance activities in the
vicinity of live areas and for online condition monitoring techniques like thermography the Switchgear
Panels are to be opened and their thermal imaging is to be taken in their live condition thus making it unsafe
for the operators. In order to mitigate this problem, certain changes can be made in these existing switchgears
as well as in Protection settings to make them safer for human operations and also the cost involved can be
justified with the savings in cost by avoiding failure and consequent damage.
There are several methods suggested till now to carry out the arc flash calculation [1]-[4]. However,
IEEE method based on experimental results and empirical formulas derived therein are found to be most
accurate
First step is to carry out arc flash hazard analysis of the existing switchgear so that the problem areas
can be identified and improvements or changes can then be suggested as per feasibility.
2. ARC FLASH HAZARD ANALYSIS
In order to carry out the arc flash hazard analysis, first of all data collection is the single most
important and cumbersome task which takes a lot of time and if maintained properly can lead to easy
incorporation for future changes. In an old Industrial substation/plant, the arc flash analysis can be carried out
in the following stepwise manner so as not to miss anything:
The whole plant/substation should be divided into sections or areas. Individual working personnel
most familiar should be given areas to gather data for all equipments in that particular area so that no
equipment is missed out. While carrying out this survey, the equipments should also be labeled by their
 ISSN: 2252-8792
IJAPE Vol. 3, No. 1, April 2014 : 23 – 32
24
voltage and source feed, if not already done. A spreadsheet should be made and following data should be
captured in that.
a. Generator
i. Rating (MVA)
ii. Sub-transient reactance
iii. Bus to which connected
b. Transformer
i. Rating (MVA)
ii. Voltage Ratio
iii. Percentage impedance
iv. Bus to and from
c. Transmission Line
i. Length (km)
ii. Type of Conductor
iii. Impedance (Ω/km)
iv. Number of lines in parallel
d. Motor
i. Rating (kW)
ii. Type of motor
iii. Ratio of starting current to rated current
e. Cable
i. Size of cable
ii. Material
iii. Make
iv. Rating (A)
v. Length of cable
vi. Number of runs
vii. Bus to and from
f. Relay
i. Type (Electromechanical/Solid state/Numerical)
ii. Setting range
iii. Setting (PSM, TMS/Set current, time)
g. CT
i. Ratio
ii. Secondary rating
h. Breaker
i. Breaking capacity
ii. Trip units, if any
i. Bus
i. Names
ii. kV Level
iii. Design Fault withstand levels
iv. Conductor gaps
v. Switchgear type (Box or Open)
The data captured above can be used to prepare an updated single line diagram incorporating the
ratings of equipment and the relay settings. Also, various configurations of operation of Power system should
be mentioned on the SLD (Single Line Diagram) indicating the status of breakers, transformers etc. during
these configurations. Separate SLDs can be made for this purpose.
There should be a listing of jobs being carried out in plant at various times including any switching
operations, maintenance jobs, testing etc.
The listing should also include the nature of job i.e. whether it is to be done online/offline. Most of
the jobs to be carried out in a substation can be done in de-energized state thus making the job safe for the
workers. For further insurance of safety for such kind of jobs, prior to carrying out the job, the de-energized
state should be confirmed by a tested voltage detector. This will avoid human errors like working on the
neighboring compartment, any breaker accidentally remaining closed etc. Also the voltage detector should be
tested near any live equipment every time it is being used to ensure it does not give erroneous indication.
Proper grounding should be provided not by insulation stick but by fixed clips to ensure the system is
grounded while carrying out the job. The removal of grounding should be ensured before restoration of
supply (to be incorporated in check sheet).
IJAPE ISSN: 2252-8792 
Remediation of Old Substations for Arc Flash Hazard (Zakir Husain)
25
Thus, Jobs to be done in live state are very limited. Out of these, the remote operation and remote
racking of breakers can further reduce the exposure level of workers. The remote operation can be
implemented by making simple changes in the control circuit of the equipment while it is taken out for
maintenance. Remote racking, while not always physically possible in existing plants, can always be
considered a possibility and retrofitting feasibility should be checked. Such Jobs require bare minimum
change to the existing equipment and are most economical. They should be identified from the list of jobs
and changes should be planned in a phase wise manner during their scheduled outage.
Fig. 1. Remote Power Racking Unit
Only those jobs should be highlighted which cannot be done in de-energized condition. The fault
levels at these job locations should be calculated by carrying out Short circuit study. It should be ascertained
that the Buses/cables/Breakers/CT secondary are designed for withstanding these fault levels as in any old
substation many loads are added later on or the buses are extended without paying much attention to the
design withstand fault levels. Relay coordination for the existing relay settings should be confirmed before
carrying arc flash analysis. Any adjustments in relay settings, if required, should be made at this point.
The arc fault current levels should be calculated at the identified job locations as per IEEE 1584.
The time of operation as per the relay settings for the arc fault current should be determined.
The incident energy and flash protection boundary can then be calculated by the empirical equations
given by IEEE 1584 and the areas with energy levels > 1.2 cal/cm2 are to be identified.
At this point, the identified locations with incident energy levels > 1.2 cal/cm2 should be checked
for these points, if applicable, to bring down the energy levels:
1. While carrying out any switching actions there should be well documented procedures/ checksheets
marking even the switch and compartment number to avoid human mistakes.
2. During maintenance of a breaker if any check on live bus bar is to be made to check pitting, it should be
made by two-pronged shutter lifter made of insulator.
3. Only Trained Personnels should be allowed for such jobs in presence of a standby person to avoid
errors. Personnels should be given live demo on spare on decommissioned equipment.
4. Provision of viewing window with better emissivity for jobs like thermography so that the panel
compartment is not required to be opened
5. Provision of Maintenance bypass switch to incorporate an alternate set of relay settings for
instantaneous operation of relay in the event of fault while working on the system. These settings
should be normalized after the job is finished.
6. Retrofitting to arc resistant switchgears in specific problematic areas.
7. Use of Category III or IV multimeter.
8. If there is a load mixup of areas in MCCs, this should be rectified in any scheduled outage so that it
does not cause heartburn.
9. Provision of fused incoming and change fuses of normal type with current limiting type (class RK1).
10. In earlier designs the LV motors are provided with only short-circuit (cleared by fuses) and thermal
protection (cleared by contactor). While for faults involving two phases and single-phase ground, the
fuse will take a lot of time for clearing the fault. Thus the cost vs benefit for providing additional relay
protection on high rating motors for fast isolation should be carefully considered. For this, the LV
 ISSN: 2252-8792
IJAPE Vol. 3, No. 1, April 2014 : 23 – 32
26
contactors breaking capacity in case of faults should be checked. Other Solutions - Temporary Reduced
Settings, Arc Sensing Relays, Zone Selective Interlocking, Arc Containment Device and PPEs. The
temporary reduced settings of relay requires specific capable trip systems and does not provide
protection if the event does not occur during the planned activity. The provision of light sensors along
with current input from CT and Zone selective interlocking can also be used for instantaneous tripping
purpose for the arc fault. However for higher hazard risk category jobs even the 3-cycle time to be
taken by breaker to clear the fault will not be acceptable. Thus in such cases, arc containment device
can be used. The last line of defense can be PPE to be used while working. In market as of now even
40cal/cm2 suits are available. But these suits are very bulky and may lead to difficulty in carrying out
the job. Thus, after reducing the energy levels as much as possible by other means as described above,
the PPE should be chosen. After this, as per The National Electrical Code (NEC), Section 110.16, a Arc
Flash Hazard Warning label should be placed on the equipment to warn the qualified persons of
potential electric arc hazards. It should be placed so as to be clearly visible, should include the Hazard
risk category, flash protection boundary and recommended PPEs required if work is to be done in
normal working distance. Here for study a sample single line diagram is taken where the bolted fault
levels and protective device ratings are calculated for different possible configurations for operating the
Power System. Other Solutions - Temporary Reduced Settings, Arc Sensing Relays, Zone Selective
Interlocking, Arc Containment Device and PPEs. The temporary reduced settings of relay requires
specific capable trip systems and does not provide protection if the event does not occur during the
planned activity. The provision of light sensors along with current input from CT and Zone selective
interlocking can also be used for instantaneous tripping purpose for the arc fault.
However for higher hazard risk category jobs even the 3-cycle time to be taken by breaker to clear
the fault will not be acceptable. Thus in such cases, arc containment device can be used. The last line of
defense can be PPE to be used while working. In market as of now even 40cal/cm2 suits are available. But
these suits are very bulky and may lead to difficulty in carrying out the job. Thus, after reducing the energy
levels as much as possible by other means as described above, the PPE should be chosen. After this, as per
The National Electrical Code (NEC), Section 110.16, a Arc Flash Hazard Warning label should be placed on
the equipment to warn the qualified persons of potential electric arc hazards. It should be placed so as to be
clearly visible, should include the Hazard risk category, flash protection boundary and recommended PPEs
required if work is to be done in normal working distance. Here for study a sample single line diagram is
taken where the bolted fault levels and protective device ratings are calculated for different possible
configurations for operating the Power System.
3. SAMPLE SYSTEM FAULT CALCULATION
The Single Line diagram for the sample system is as shown below:
Fig. 2. ingle Line Diagram of a Sample system
IJAPE ISSN: 2252-8792 
Remediation of Old Substations for Arc Flash Hazard (Zakir Husain)
27
The Sample system consists of a plant having Captive Power Generation of 31.5MVA in order to
self-sustain the plant along with running it in parallel with the grid for improved reliability.
The Power from grid is being received by the plant at 33kV level and then is being step down to
11kV, 6.6kV and 415V for subsequent distribution to loads.
At each distribution level there are 2 transformers each individually capable of feeding the load. The
extra capacity is provided for future usage.
Now short circuit study is carried out on the given system to calculate bolted fault current levels.
Here, Different operating configurations and their impact on Bolted fault current and arc flash levels is
considered. The different cases considered are:
Case 1: T1, T3, T5 in line
Case 2: T1, T3, T4, T5, T6 in line
Case 3: T1, T2, T3, T5 in line
Case 4: All Transformers in line
Thus bolted fault current levels of the buses are as given in Table I. Here Bus 1 is not considered as it
is directly connected to the grid and any work on it will be done after disconnecting from the grid.
TABLE I. FAULT CURRENT WHEN SYSTEM RUNNING IN PARALLEL WITH GRID
Bus Name
Voltage
level (kV)
Bolted Fault Current (kA)
Case 1 Case 2 Case 3 Case 4
Bus 2 11 16.87 22.47
Bus 3 6.6 10.93 15.2 11.42 16.5
PCC 0.415 28.9 54.32 29.39 56.02
As can be seen the fault levels vary widely with different operating configurations and also with the
rating of different equipment like transformer, generator chosen during system design. The least fault level of
system is there when only one transformer is operated. But this will decrease the reliability of the system as
this transformer failure can lead to complete loss of power. Further even with one transformer operation the
fault current levels will change with system operation in parallel with grid or in isolated condition (as shown in
Table II).
Case 5: Isolated + T3, T5 in line
Case 6: Isolated + All Transformers in line
TABLE II. FAULT CURRENT WHEN SYSTEM RUNNING IN ISOLATED CONDITION
Bus Name Voltage level (kV)
Bolted Fault Current (kA)
Case 5 Case 6
Bus 2 11 11.25
Bus 3 6.6 6.4 9.55
PCC 0.415 28.012 51.19
Thus, a compromise has to be reached between reliability and fault level of system. The design of the
system as well as the configuration in which it is operated has a major impact on the arc flash levels. The study
should be carried out for arc flash current levels and energies keeping all the scenarios of system operation in
mind so as to ascertain the best operating scenario.
4. PROTECTIVE DEVICE COORDINATION
Relays provided at different levels, their settings and characteristics data for the SLD given is
determined based on the load data, fault levels, relay coordination [6] etc. The coordination curves are as given
below. As of now, arc flash protection is not taken into consideration and calculations are done only for bolted
fault current levels.
 ISSN: 2252-8792
IJAPE Vol. 3, No. 1, April 2014 : 23 – 32
28
Fig. 1. Relay Coordination of 415V system before arc flash calculations are taken into consideration
Fig. 2. Relay Coordination of 6.6kV system before arc flash calculations are taken into consideration
During the relay selection and coordination when arc flash current is not taken into account, the two
most important features to be kept in mind are that the selective coordination should be strictly followed i.e.
the breaker closest to the fault should operate first and if it fails to operate, only then the upstream breaker
should operate and in the event of starting of highest rating motor while other connected loads are running,
the relay should have a time delay greater than the starting time of the machine so as to avoid erroneous
operation of the protection system when there is no fault.
IJAPE ISSN: 2252-8792 
Remediation of Old Substations for Arc Flash Hazard (Zakir Husain)
29
5. ARC FLASH CALCULATION
Many methods for Arc fault Hazard level calculation have been given till now. Ralph Lee’s method is
one of the first methods but it gives conservative results and is only referred for voltage levels beyond 15kV
for which the tests by IEEE were not carried out. The IEEE 1584 method till now is the most accurate method
as it has been found out on the basis of regression analysis of the experimental data obtained by carrying out
the test.
As per IEEE 1584 [1], the empirical equations for arc flash levels are as given below:
a. Arc Fault Current and Clearing time
For PCC (< 1kV system),
Arc Fault Current,
Ia = 10 (K + 0.662 log (I
bf
) + 0.0966V + 0.000526G + 0.5588V log (I
bf
) – 0.00304G log (I
bf
))
Where, K = -0.153 for open configuration and -0.097 for box configuration
V = system voltage in kV,
G = conductor gap in mm
I
bf = Bolted Fault Current
I
a = Arc fault Current
For Voltages >1kV and < 15kV,
Ia = 10 (0.00402 + 0.983 log (I
bf
))
The fault clearing time for Ia and 85% of Ia can be checked from the relay operation curve.
From this calculated arc fault current and the fault clearing time, the incident energy at a distance of
610mm from the source of arc is ca lculated as given below:
b. Normalized Incident Energy and Incident energy at working distance
Normalized Energy,
En = 10 (K1 + K2 + 1.081 log Ia + 0.0011G)
Where,
K1 = -0.792 for open configuration and
-0.555 for box configuration,
K2 = 0 for ungrounded and high resistance grounding and
-0.113, grounded system
En is in J/cm2
(5 J/cm2
= 1.2 cal/cm2
)
Incident energy, E = 4.184CfEn (t/0.2) (610x
/Dx
)
Where, Cf = calculation factor
= 1, > 1kV
= 1.5, <= 1kV
x = 1.473, switchgear (<1kV)
= 0.973, switchgear (>5 – 15 kV)
D = working distance in mm
En = normalized incident energy
For V> 15kV, Ralph Lee’s method [2] is used for Incident energy calculation
E = 2.142 X 106
V Ibf (t/D2
)
The arc flash current, its clearing time, incident energy released at working distance are provided in the
Table III, IV and V for different buses at various bolted fault current levels for configurations considered
above.
 ISSN: 2252-8792
IJAPE Vol. 3, No. 1, April 2014 : 23 – 32
30
TABLE III. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (BUS 2)
Bus No.
Voltage
(kV)
Case
Bolted Fault
Current (kA)
Arc Fault
Current (kA)
100% and
85%
Time of clearing
arc fault current
(sec)
Incident Energy
released at
working distance
(cal/cm2)
Bus 2 11
1 16.87
16.23 0.1 2.184
13.79 0.1 1.832
2 16.87
16.23 0.1 2.184
13.79 0.1 1.832
3 22.47
21.51 0.1 2.962
18.28 0.1 2.484
4 22.47
21.51 0.1 2.962
18.28 0.1 2.484
5 11.25
10.9 0.1 1.42
9.26 0.1 1.191
6 11.25
10.9 0.1 1.42
9.26 0.1 1.191
TABLE IV. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (BUS 3)
Bus No.
Voltage
(kV)
Case
Bolted Fault
Current (kA)
Arc Fault
Current (kA)
100% and
85%
Time of
clearing arc
fault current
(sec)
Incident Energy
released at working
distance (cal/cm2)
Bus 3 6.6
1 10.93
10.59 0.2232 2.72178
9 0.2382 2.4367
2 15.2
14.65 0.1982 3.4312
12.45 0.21 3.0498
3 11.42
11.06 0.2196 2.8056
9.4 0.234 2.5079
4 16.5
15.88 0.1928 3.6419
13.5 0.204 3.2326
5 6.4
6.26 0.2801 1.9341
5.32 0.3038 1.7597
6 9.55
9.28 0.2353 2.4859
7.88 0.252 2.2334
TABLE V. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (PCC)
Bus No.
Voltage
(kV)
Case
Bolted Fault
Current (kA)
Arc Fault
Current (kA)
100% and
85%
Time of
clearing arc
fault current
(sec)
Incident Energy
released at working
distance (cal/cm2)
PCC 0.415
1 28.9
14.16 0.6608 19.9886
12.04 0.7137 18.1105
2 54.32
23.73 0.5345 28.2471
20.17 0.5689 25.2211
3 29.39
14.36 0.6567 20.1637
12.2 0.7088 18.2563
4 56.02
24.33 0.5295 28.7558
20.68 0.5633 25.6626
5 28.012
13.8 0.6686 19.6742
11.73 0.7226 17.8383
6 51.19
22.604 0.5444 27.3
19.21 0.58 24.3988
From the above tables, it can be clearly seen that the most favorable scheme of operation under
normal condition is Case 1 with one transformer only in operation. When work is to be done on energized
equipment, the best mode of operation is Case 5 i.e. in isolated condition with only one transformer in
operation to feed each bus.
Any changes in the setting of the relay to bring down the clearing time so as to lower the incident
energy in older plants with limited range of settings in the existing electromechanical relays results in Relay
coordination disturbance and may lead to operation of the relay even under through fault conditions and
isolation of even normal areas.
Under these limitations two possible actions that can be taken are:
IJAPE ISSN: 2252-8792 
Remediation of Old Substations for Arc Flash Hazard (Zakir Husain)
31
Zone Selective Interlocking
Zone Selective Interlocking (ZSI) can be incorporated in such a case so that if the breaker nearest to
the fault senses it will give locking command to the upstream breaker and will clear the fault without any
intentional time delay irrespective of the setting of the relay.
Temporary Reduced Setting
Another feasible solution for this is by providing maintenance bypass switch which will provide a
different set of relay settings during any maintenance activity thus giving instantaneous clearance of arc fault
or by providing unit differential protection on the bus, the fault current levels and thus the incident energy
can be reduced substantially. The levels thus reduced are given in Table VI.
TABLE VI. FINAL ARC FLASH LEVELS AS PER IEEE 1584 BY LOWERING CLEARING TIME
Bus
No.
Voltage
(kV)
Bolted Fault
Current (kA)
Arc Fault
Current
(kA)
Time of clearing
arc fault current
(sec)
Incident Energy
released at working
distance (cal/cm2)
Bus 2 11 16.87 16.2283 0.1 2.184
Bus 3 6.6 10.93 10.5921 0.1 1.22
PCC 0.415 28.9 14.1615 0.1 3.025
The Flash Protection Boundary is defined as an approach limit at a distance from live parts that are
uninsulated or exposed within which a person could receive a second degree burn (IEEE 1584[1]). It can be
calculates as.
c. Flash Protection Boundary
DB = [4.184Cf En (t/0.2) (610x
/EB)] 1/x
Or by Lee’s method,
DB = [2.142 X 106
V Ibf (t/EB)]1/2
Where,
EB = 5 J/cm2
for bare skin (second degree burns, curable)
= 33.33 J/cm2
for PPE of 8 cal/cm2
Thus, flash protection boundary i.e. safe working distance for bare skin and with PPE of 8 cal/cm2
[5] before and after remediation is shown in Table VII and VIII.
TABLE VII. FLASH PROTECTION BOUNDARY BEFORE REMEDIATION
Bus No. Voltage (kV)
Flash Protection Boundary (m)
IEEE 1584
1.2 cal/cm2
(bare skin) 8 cal/cm2
(PPE)
Bus 2 11 1.68 0.24
Bus 3 6.6 2.1 0.3
PCC 0.415 3.4 1.065
TABLE VIII. FLASH PROTECTION BOUNDARY AFTER REMEDIATION
Bus No. Voltage (kV)
Flash Protection Boundary (m)
IEEE 1584
1.2 cal/cm2
(bare skin) 8 cal/cm2
(PPE)
Bus 2 11 1.68 0.24
Bus 3 6.6 0.925 0.132
PCC 0.415 1.071 0.337
As can be seen from above the approach distances and incident energies reduced considerably for
the 415V PCC system and 6.6kV Bus. With PPEs of 8 cal/cm2, the work can be safely done without any
harm to the operators.
 ISSN: 2252-8792
IJAPE Vol. 3, No. 1, April 2014 : 23 – 32
32
Arc Containment Device [6]
Another solution that can be used is the arc containment device [6] which is essentially an enclosure
containing electrodes. With the help of trigerring through light sensors and CT input the plasma gun can be
used to divert the arc from the switchgear to this device with impedance lower than the arcing impedance.
Thus arc current starts passing through this chamber and the interruption of arc takes place in 7-8ms as
compared to almost 100ms taken by the breaker. This leads to drastic reduction of the arc energy and safety
of workers. The calculations are shown in Table IX with a clearing time of 10ms.
TABLE IX. FLASH PROTECTION BOUNDARY AFTER REMEDIATION WITH THE HELP OF ARC CONTAINMENT
DEVICE
Bus No. Voltage (kV)
Flash Protection
Boundary (m)
IEEE 1584
1.2 cal/cm2
(bare
skin)
Bus 2 11 0.158
Bus 3 6.6 0.087
PCC 0.415 0.263
But prior to using the arc containment device, its effect on the BIL of the system or any other
harmful effects during normal operation of the Power system should be considered. Care should be taken so
that this unit does not operate under normal switching operations. For this test should be carried out after
commissioning and before taking into line. Also, there should be provision of checking the condition of
electrodes and replacement if required during routine maintenance or after failure.
7. CONCLUSION
Safety of working personnel is paramount while carrying out any job on electrical equipment and
any mistake could lead to damage to both personnel working in the vicinity and equipment. To avoid such
occurrences, As much as possible, the maintenance work on any electrical system should be carried out after
de-energizing the equipment to be taken for maintenance and proper work procedures and checks should be
put into practice prior to starting the job. However, if it is impossible to avoid working on live panels like in
case of Thermography etc., It has been found from the above calculations that by minor changes in the
Protection logic of the existing system the safety of the working personnel can be ensured.
REFERENCES
[1] IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE Std 1584-2002.
[2] R. H. Lee. “The Other Electrical Hazard: Electric Arc Burns”, IEEE Power Systems Protection Committee Annual
Conf. and Record, Philadelphia, PA, Oct. 5-9,1981.
[3] Doughty,R.L.,Neal,T.E.,and Floyd,H.L. “Predicting incident energy to better manage the electric arc hazard on
600-V power distribution systems”, IEEE Transactions on Industry Applications, Vol/Issue: 36(1). Pp. 257-269,
2000.
[4] NFPA 70E, Electrical Safety in Workplace, 2009.
[5] J.C. Das. “Protection planning and system design to reduce arc flash incident energy in a multivoltage level
distribution system to 8 cal/cm2 (HRC2) or less-Part 1. Methodology”, In conf. record, IEEE Pulp and Paper
Industry Conference, San Antonio, 2010.
[6] Roscoe, G. Papallo T. and Marcelo Valdes P.E. Arc Flash Energy Mitigation by Fast Energy Capture.

More Related Content

What's hot

Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and groundingmichaeljmack
 
Interconnet protection of
Interconnet protection ofInterconnet protection of
Interconnet protection ofmichaeljmack
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
Transformer Maintenance and Testing
Transformer Maintenance and TestingTransformer Maintenance and Testing
Transformer Maintenance and TestingGPTraining
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingAsif Eqbal
 
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...IRJET Journal
 
Live line maintenance in power sector
Live line maintenance in power sectorLive line maintenance in power sector
Live line maintenance in power sectorUMESH THAKARE
 
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Living Online
 
Live Line Maintenance
Live Line MaintenanceLive Line Maintenance
Live Line MaintenanceGAURAV KUMAR
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Rajeev Kumar Raj
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
Generator grounding
Generator groundingGenerator grounding
Generator groundingmichaeljmack
 
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalDo's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalJim White
 
Schneider Electric Services_Modernization and Upgrade Solutions.pptx
Schneider Electric Services_Modernization and Upgrade Solutions.pptxSchneider Electric Services_Modernization and Upgrade Solutions.pptx
Schneider Electric Services_Modernization and Upgrade Solutions.pptxSchneider Electric
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPTAbdullah Al Dushaishi
 

What's hot (20)

Ieee pes psrc
Ieee pes psrcIeee pes psrc
Ieee pes psrc
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and grounding
 
Interconnet protection of
Interconnet protection ofInterconnet protection of
Interconnet protection of
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
L.v tech presentation 2
L.v tech presentation 2L.v tech presentation 2
L.v tech presentation 2
 
Transformer Maintenance and Testing
Transformer Maintenance and TestingTransformer Maintenance and Testing
Transformer Maintenance and Testing
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizing
 
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
Mitigation of Voltage Sags & Swells in LV Distribution System Using Dynamic V...
 
Live line maintenance in power sector
Live line maintenance in power sectorLive line maintenance in power sector
Live line maintenance in power sector
 
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
 
IEEE 519 92 vs 14
IEEE 519 92 vs 14IEEE 519 92 vs 14
IEEE 519 92 vs 14
 
Live Line Maintenance
Live Line MaintenanceLive Line Maintenance
Live Line Maintenance
 
Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.Numerical analysis of short circuit testing & verification of a MCCB.
Numerical analysis of short circuit testing & verification of a MCCB.
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Out of step
Out of stepOut of step
Out of step
 
Generator grounding
Generator groundingGenerator grounding
Generator grounding
 
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions FinalDo's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
Do's and Don'ts of Personal Protective Grounding IEEE IAS Transactions Final
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Schneider Electric Services_Modernization and Upgrade Solutions.pptx
Schneider Electric Services_Modernization and Upgrade Solutions.pptxSchneider Electric Services_Modernization and Upgrade Solutions.pptx
Schneider Electric Services_Modernization and Upgrade Solutions.pptx
 
Switchgear Installation Precomissioning Inspection.PPT
Switchgear Installation  Precomissioning Inspection.PPTSwitchgear Installation  Precomissioning Inspection.PPT
Switchgear Installation Precomissioning Inspection.PPT
 

Similar to Remediation of Old Substations for Arc Flash hazard

Converting Solidly to HRG
Converting Solidly to HRGConverting Solidly to HRG
Converting Solidly to HRGEdmundo Perich
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerIRJET Journal
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_webLaurence Michael, PE
 
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...IRJET Journal
 
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1Abu Hashim
 
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...IRJET Journal
 
IRJET- Auto Earth System for HV Test Set Up for Transformer in Applicatio...
IRJET-  	  Auto Earth System for HV Test Set Up for Transformer in Applicatio...IRJET-  	  Auto Earth System for HV Test Set Up for Transformer in Applicatio...
IRJET- Auto Earth System for HV Test Set Up for Transformer in Applicatio...IRJET Journal
 
WM Siemens IEC 61850 Flyer 081914
WM Siemens IEC 61850 Flyer 081914WM Siemens IEC 61850 Flyer 081914
WM Siemens IEC 61850 Flyer 081914Ryan Bolduc, PE
 
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service Systems
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service SystemsLessons Learned of AC Arc Flash Studies for Station Auxiliary Service Systems
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service SystemsPower System Operation
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...iosrjce
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorIRJET Journal
 
Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...eSAT Publishing House
 
EHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesEHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesYashwant Chaudhari
 
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET Journal
 
Photo Voltaic Cell Integrated DVR for Power Quality Improvement
Photo Voltaic Cell Integrated DVR for Power Quality ImprovementPhoto Voltaic Cell Integrated DVR for Power Quality Improvement
Photo Voltaic Cell Integrated DVR for Power Quality ImprovementIJMTST Journal
 
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...IRJET Journal
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guidePrasad RVS
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET Journal
 

Similar to Remediation of Old Substations for Arc Flash hazard (20)

Converting Solidly to HRG
Converting Solidly to HRGConverting Solidly to HRG
Converting Solidly to HRG
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power Transformer
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web
 
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...
 
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
Electrical engineering-portal.com-mv circuit-breaker_or_vacuum_contactor_part_1
 
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...
IRJET- Different Techniques for Reducing Swag & Swell in Distribution Transfo...
 
IRJET- Auto Earth System for HV Test Set Up for Transformer in Applicatio...
IRJET-  	  Auto Earth System for HV Test Set Up for Transformer in Applicatio...IRJET-  	  Auto Earth System for HV Test Set Up for Transformer in Applicatio...
IRJET- Auto Earth System for HV Test Set Up for Transformer in Applicatio...
 
WM Siemens IEC 61850 Flyer 081914
WM Siemens IEC 61850 Flyer 081914WM Siemens IEC 61850 Flyer 081914
WM Siemens IEC 61850 Flyer 081914
 
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service Systems
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service SystemsLessons Learned of AC Arc Flash Studies for Station Auxiliary Service Systems
Lessons Learned of AC Arc Flash Studies for Station Auxiliary Service Systems
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
 
Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...
 
EHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniquesEHVAC transmission line maintenance techniques
EHVAC transmission line maintenance techniques
 
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
 
Photo Voltaic Cell Integrated DVR for Power Quality Improvement
Photo Voltaic Cell Integrated DVR for Power Quality ImprovementPhoto Voltaic Cell Integrated DVR for Power Quality Improvement
Photo Voltaic Cell Integrated DVR for Power Quality Improvement
 
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...
Simulation of DVR by using Ultra Capacitor to Analysis of THD with and withou...
 
Transformer guide
Transformer guideTransformer guide
Transformer guide
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
 

More from IJAPEJOURNAL

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...IJAPEJOURNAL
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterIJAPEJOURNAL
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointIJAPEJOURNAL
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineIJAPEJOURNAL
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceIJAPEJOURNAL
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingIJAPEJOURNAL
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...IJAPEJOURNAL
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...IJAPEJOURNAL
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...IJAPEJOURNAL
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...IJAPEJOURNAL
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsIJAPEJOURNAL
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanIJAPEJOURNAL
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationIJAPEJOURNAL
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...IJAPEJOURNAL
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...IJAPEJOURNAL
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...IJAPEJOURNAL
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...IJAPEJOURNAL
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsIJAPEJOURNAL
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeIJAPEJOURNAL
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsIJAPEJOURNAL
 

More from IJAPEJOURNAL (20)

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman Filter
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation Point
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC Motors
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in Pakistan
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based Application
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic Applications
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation Scheme
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 

Recently uploaded

Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 

Recently uploaded (20)

Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 

Remediation of Old Substations for Arc Flash hazard

  • 1. International Journal of Applied Power Engineering (IJAPE) Vol. 3, No. 1, April 2014, pp. 23~32 ISSN: 2252-8792  23 Journal homepage: http://iaesjournal.com/online/index.php/IJAPE Remediation of Old Substations for Arc Flash Hazard Zakir Husain, Deepak Kumar, Khushbu Thakur Departement of Electrical Engineering, National Institute of Technology, Hamirpur, HP, India Article Info ABSTRACT Article history: Received Jan 11, 2014 Revised Feb 21, 2014 Accepted Mar 8, 2014 Arc Flash is much different from the conventional shock hazard in the sense that it doesn’t involve direct contact of human beings with the live or energized part. The arcing energy involves high temperature of up to or beyond 20000K. This paper presents a case study of arc flash hazard analysis carried out in older industrial plant and the technological and work procedure changes that can be incorporated to reduce the incident energy level and thus provide a safer environment for the working personnels in plant. Keyword: Flash Protection Boundary Incident Energy PCC Relay coordination Copyright © 2014 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: 1. INTRODUCTION Arc Flash Hazard even after extensive study remains an unexplored area in most of the substations in India as the switchgears used are almost 30 years old with protection system designed to address short- circuit fault isolation. Thus arc flash hazard levels for these existing substations is quite high allowing almost no work to be done in live panels even with PPEs of 20cal/cm2. However for maintenance activities in the vicinity of live areas and for online condition monitoring techniques like thermography the Switchgear Panels are to be opened and their thermal imaging is to be taken in their live condition thus making it unsafe for the operators. In order to mitigate this problem, certain changes can be made in these existing switchgears as well as in Protection settings to make them safer for human operations and also the cost involved can be justified with the savings in cost by avoiding failure and consequent damage. There are several methods suggested till now to carry out the arc flash calculation [1]-[4]. However, IEEE method based on experimental results and empirical formulas derived therein are found to be most accurate First step is to carry out arc flash hazard analysis of the existing switchgear so that the problem areas can be identified and improvements or changes can then be suggested as per feasibility. 2. ARC FLASH HAZARD ANALYSIS In order to carry out the arc flash hazard analysis, first of all data collection is the single most important and cumbersome task which takes a lot of time and if maintained properly can lead to easy incorporation for future changes. In an old Industrial substation/plant, the arc flash analysis can be carried out in the following stepwise manner so as not to miss anything: The whole plant/substation should be divided into sections or areas. Individual working personnel most familiar should be given areas to gather data for all equipments in that particular area so that no equipment is missed out. While carrying out this survey, the equipments should also be labeled by their
  • 2.  ISSN: 2252-8792 IJAPE Vol. 3, No. 1, April 2014 : 23 – 32 24 voltage and source feed, if not already done. A spreadsheet should be made and following data should be captured in that. a. Generator i. Rating (MVA) ii. Sub-transient reactance iii. Bus to which connected b. Transformer i. Rating (MVA) ii. Voltage Ratio iii. Percentage impedance iv. Bus to and from c. Transmission Line i. Length (km) ii. Type of Conductor iii. Impedance (Ω/km) iv. Number of lines in parallel d. Motor i. Rating (kW) ii. Type of motor iii. Ratio of starting current to rated current e. Cable i. Size of cable ii. Material iii. Make iv. Rating (A) v. Length of cable vi. Number of runs vii. Bus to and from f. Relay i. Type (Electromechanical/Solid state/Numerical) ii. Setting range iii. Setting (PSM, TMS/Set current, time) g. CT i. Ratio ii. Secondary rating h. Breaker i. Breaking capacity ii. Trip units, if any i. Bus i. Names ii. kV Level iii. Design Fault withstand levels iv. Conductor gaps v. Switchgear type (Box or Open) The data captured above can be used to prepare an updated single line diagram incorporating the ratings of equipment and the relay settings. Also, various configurations of operation of Power system should be mentioned on the SLD (Single Line Diagram) indicating the status of breakers, transformers etc. during these configurations. Separate SLDs can be made for this purpose. There should be a listing of jobs being carried out in plant at various times including any switching operations, maintenance jobs, testing etc. The listing should also include the nature of job i.e. whether it is to be done online/offline. Most of the jobs to be carried out in a substation can be done in de-energized state thus making the job safe for the workers. For further insurance of safety for such kind of jobs, prior to carrying out the job, the de-energized state should be confirmed by a tested voltage detector. This will avoid human errors like working on the neighboring compartment, any breaker accidentally remaining closed etc. Also the voltage detector should be tested near any live equipment every time it is being used to ensure it does not give erroneous indication. Proper grounding should be provided not by insulation stick but by fixed clips to ensure the system is grounded while carrying out the job. The removal of grounding should be ensured before restoration of supply (to be incorporated in check sheet).
  • 3. IJAPE ISSN: 2252-8792  Remediation of Old Substations for Arc Flash Hazard (Zakir Husain) 25 Thus, Jobs to be done in live state are very limited. Out of these, the remote operation and remote racking of breakers can further reduce the exposure level of workers. The remote operation can be implemented by making simple changes in the control circuit of the equipment while it is taken out for maintenance. Remote racking, while not always physically possible in existing plants, can always be considered a possibility and retrofitting feasibility should be checked. Such Jobs require bare minimum change to the existing equipment and are most economical. They should be identified from the list of jobs and changes should be planned in a phase wise manner during their scheduled outage. Fig. 1. Remote Power Racking Unit Only those jobs should be highlighted which cannot be done in de-energized condition. The fault levels at these job locations should be calculated by carrying out Short circuit study. It should be ascertained that the Buses/cables/Breakers/CT secondary are designed for withstanding these fault levels as in any old substation many loads are added later on or the buses are extended without paying much attention to the design withstand fault levels. Relay coordination for the existing relay settings should be confirmed before carrying arc flash analysis. Any adjustments in relay settings, if required, should be made at this point. The arc fault current levels should be calculated at the identified job locations as per IEEE 1584. The time of operation as per the relay settings for the arc fault current should be determined. The incident energy and flash protection boundary can then be calculated by the empirical equations given by IEEE 1584 and the areas with energy levels > 1.2 cal/cm2 are to be identified. At this point, the identified locations with incident energy levels > 1.2 cal/cm2 should be checked for these points, if applicable, to bring down the energy levels: 1. While carrying out any switching actions there should be well documented procedures/ checksheets marking even the switch and compartment number to avoid human mistakes. 2. During maintenance of a breaker if any check on live bus bar is to be made to check pitting, it should be made by two-pronged shutter lifter made of insulator. 3. Only Trained Personnels should be allowed for such jobs in presence of a standby person to avoid errors. Personnels should be given live demo on spare on decommissioned equipment. 4. Provision of viewing window with better emissivity for jobs like thermography so that the panel compartment is not required to be opened 5. Provision of Maintenance bypass switch to incorporate an alternate set of relay settings for instantaneous operation of relay in the event of fault while working on the system. These settings should be normalized after the job is finished. 6. Retrofitting to arc resistant switchgears in specific problematic areas. 7. Use of Category III or IV multimeter. 8. If there is a load mixup of areas in MCCs, this should be rectified in any scheduled outage so that it does not cause heartburn. 9. Provision of fused incoming and change fuses of normal type with current limiting type (class RK1). 10. In earlier designs the LV motors are provided with only short-circuit (cleared by fuses) and thermal protection (cleared by contactor). While for faults involving two phases and single-phase ground, the fuse will take a lot of time for clearing the fault. Thus the cost vs benefit for providing additional relay protection on high rating motors for fast isolation should be carefully considered. For this, the LV
  • 4.  ISSN: 2252-8792 IJAPE Vol. 3, No. 1, April 2014 : 23 – 32 26 contactors breaking capacity in case of faults should be checked. Other Solutions - Temporary Reduced Settings, Arc Sensing Relays, Zone Selective Interlocking, Arc Containment Device and PPEs. The temporary reduced settings of relay requires specific capable trip systems and does not provide protection if the event does not occur during the planned activity. The provision of light sensors along with current input from CT and Zone selective interlocking can also be used for instantaneous tripping purpose for the arc fault. However for higher hazard risk category jobs even the 3-cycle time to be taken by breaker to clear the fault will not be acceptable. Thus in such cases, arc containment device can be used. The last line of defense can be PPE to be used while working. In market as of now even 40cal/cm2 suits are available. But these suits are very bulky and may lead to difficulty in carrying out the job. Thus, after reducing the energy levels as much as possible by other means as described above, the PPE should be chosen. After this, as per The National Electrical Code (NEC), Section 110.16, a Arc Flash Hazard Warning label should be placed on the equipment to warn the qualified persons of potential electric arc hazards. It should be placed so as to be clearly visible, should include the Hazard risk category, flash protection boundary and recommended PPEs required if work is to be done in normal working distance. Here for study a sample single line diagram is taken where the bolted fault levels and protective device ratings are calculated for different possible configurations for operating the Power System. Other Solutions - Temporary Reduced Settings, Arc Sensing Relays, Zone Selective Interlocking, Arc Containment Device and PPEs. The temporary reduced settings of relay requires specific capable trip systems and does not provide protection if the event does not occur during the planned activity. The provision of light sensors along with current input from CT and Zone selective interlocking can also be used for instantaneous tripping purpose for the arc fault. However for higher hazard risk category jobs even the 3-cycle time to be taken by breaker to clear the fault will not be acceptable. Thus in such cases, arc containment device can be used. The last line of defense can be PPE to be used while working. In market as of now even 40cal/cm2 suits are available. But these suits are very bulky and may lead to difficulty in carrying out the job. Thus, after reducing the energy levels as much as possible by other means as described above, the PPE should be chosen. After this, as per The National Electrical Code (NEC), Section 110.16, a Arc Flash Hazard Warning label should be placed on the equipment to warn the qualified persons of potential electric arc hazards. It should be placed so as to be clearly visible, should include the Hazard risk category, flash protection boundary and recommended PPEs required if work is to be done in normal working distance. Here for study a sample single line diagram is taken where the bolted fault levels and protective device ratings are calculated for different possible configurations for operating the Power System. 3. SAMPLE SYSTEM FAULT CALCULATION The Single Line diagram for the sample system is as shown below: Fig. 2. ingle Line Diagram of a Sample system
  • 5. IJAPE ISSN: 2252-8792  Remediation of Old Substations for Arc Flash Hazard (Zakir Husain) 27 The Sample system consists of a plant having Captive Power Generation of 31.5MVA in order to self-sustain the plant along with running it in parallel with the grid for improved reliability. The Power from grid is being received by the plant at 33kV level and then is being step down to 11kV, 6.6kV and 415V for subsequent distribution to loads. At each distribution level there are 2 transformers each individually capable of feeding the load. The extra capacity is provided for future usage. Now short circuit study is carried out on the given system to calculate bolted fault current levels. Here, Different operating configurations and their impact on Bolted fault current and arc flash levels is considered. The different cases considered are: Case 1: T1, T3, T5 in line Case 2: T1, T3, T4, T5, T6 in line Case 3: T1, T2, T3, T5 in line Case 4: All Transformers in line Thus bolted fault current levels of the buses are as given in Table I. Here Bus 1 is not considered as it is directly connected to the grid and any work on it will be done after disconnecting from the grid. TABLE I. FAULT CURRENT WHEN SYSTEM RUNNING IN PARALLEL WITH GRID Bus Name Voltage level (kV) Bolted Fault Current (kA) Case 1 Case 2 Case 3 Case 4 Bus 2 11 16.87 22.47 Bus 3 6.6 10.93 15.2 11.42 16.5 PCC 0.415 28.9 54.32 29.39 56.02 As can be seen the fault levels vary widely with different operating configurations and also with the rating of different equipment like transformer, generator chosen during system design. The least fault level of system is there when only one transformer is operated. But this will decrease the reliability of the system as this transformer failure can lead to complete loss of power. Further even with one transformer operation the fault current levels will change with system operation in parallel with grid or in isolated condition (as shown in Table II). Case 5: Isolated + T3, T5 in line Case 6: Isolated + All Transformers in line TABLE II. FAULT CURRENT WHEN SYSTEM RUNNING IN ISOLATED CONDITION Bus Name Voltage level (kV) Bolted Fault Current (kA) Case 5 Case 6 Bus 2 11 11.25 Bus 3 6.6 6.4 9.55 PCC 0.415 28.012 51.19 Thus, a compromise has to be reached between reliability and fault level of system. The design of the system as well as the configuration in which it is operated has a major impact on the arc flash levels. The study should be carried out for arc flash current levels and energies keeping all the scenarios of system operation in mind so as to ascertain the best operating scenario. 4. PROTECTIVE DEVICE COORDINATION Relays provided at different levels, their settings and characteristics data for the SLD given is determined based on the load data, fault levels, relay coordination [6] etc. The coordination curves are as given below. As of now, arc flash protection is not taken into consideration and calculations are done only for bolted fault current levels.
  • 6.  ISSN: 2252-8792 IJAPE Vol. 3, No. 1, April 2014 : 23 – 32 28 Fig. 1. Relay Coordination of 415V system before arc flash calculations are taken into consideration Fig. 2. Relay Coordination of 6.6kV system before arc flash calculations are taken into consideration During the relay selection and coordination when arc flash current is not taken into account, the two most important features to be kept in mind are that the selective coordination should be strictly followed i.e. the breaker closest to the fault should operate first and if it fails to operate, only then the upstream breaker should operate and in the event of starting of highest rating motor while other connected loads are running, the relay should have a time delay greater than the starting time of the machine so as to avoid erroneous operation of the protection system when there is no fault.
  • 7. IJAPE ISSN: 2252-8792  Remediation of Old Substations for Arc Flash Hazard (Zakir Husain) 29 5. ARC FLASH CALCULATION Many methods for Arc fault Hazard level calculation have been given till now. Ralph Lee’s method is one of the first methods but it gives conservative results and is only referred for voltage levels beyond 15kV for which the tests by IEEE were not carried out. The IEEE 1584 method till now is the most accurate method as it has been found out on the basis of regression analysis of the experimental data obtained by carrying out the test. As per IEEE 1584 [1], the empirical equations for arc flash levels are as given below: a. Arc Fault Current and Clearing time For PCC (< 1kV system), Arc Fault Current, Ia = 10 (K + 0.662 log (I bf ) + 0.0966V + 0.000526G + 0.5588V log (I bf ) – 0.00304G log (I bf )) Where, K = -0.153 for open configuration and -0.097 for box configuration V = system voltage in kV, G = conductor gap in mm I bf = Bolted Fault Current I a = Arc fault Current For Voltages >1kV and < 15kV, Ia = 10 (0.00402 + 0.983 log (I bf )) The fault clearing time for Ia and 85% of Ia can be checked from the relay operation curve. From this calculated arc fault current and the fault clearing time, the incident energy at a distance of 610mm from the source of arc is ca lculated as given below: b. Normalized Incident Energy and Incident energy at working distance Normalized Energy, En = 10 (K1 + K2 + 1.081 log Ia + 0.0011G) Where, K1 = -0.792 for open configuration and -0.555 for box configuration, K2 = 0 for ungrounded and high resistance grounding and -0.113, grounded system En is in J/cm2 (5 J/cm2 = 1.2 cal/cm2 ) Incident energy, E = 4.184CfEn (t/0.2) (610x /Dx ) Where, Cf = calculation factor = 1, > 1kV = 1.5, <= 1kV x = 1.473, switchgear (<1kV) = 0.973, switchgear (>5 – 15 kV) D = working distance in mm En = normalized incident energy For V> 15kV, Ralph Lee’s method [2] is used for Incident energy calculation E = 2.142 X 106 V Ibf (t/D2 ) The arc flash current, its clearing time, incident energy released at working distance are provided in the Table III, IV and V for different buses at various bolted fault current levels for configurations considered above.
  • 8.  ISSN: 2252-8792 IJAPE Vol. 3, No. 1, April 2014 : 23 – 32 30 TABLE III. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (BUS 2) Bus No. Voltage (kV) Case Bolted Fault Current (kA) Arc Fault Current (kA) 100% and 85% Time of clearing arc fault current (sec) Incident Energy released at working distance (cal/cm2) Bus 2 11 1 16.87 16.23 0.1 2.184 13.79 0.1 1.832 2 16.87 16.23 0.1 2.184 13.79 0.1 1.832 3 22.47 21.51 0.1 2.962 18.28 0.1 2.484 4 22.47 21.51 0.1 2.962 18.28 0.1 2.484 5 11.25 10.9 0.1 1.42 9.26 0.1 1.191 6 11.25 10.9 0.1 1.42 9.26 0.1 1.191 TABLE IV. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (BUS 3) Bus No. Voltage (kV) Case Bolted Fault Current (kA) Arc Fault Current (kA) 100% and 85% Time of clearing arc fault current (sec) Incident Energy released at working distance (cal/cm2) Bus 3 6.6 1 10.93 10.59 0.2232 2.72178 9 0.2382 2.4367 2 15.2 14.65 0.1982 3.4312 12.45 0.21 3.0498 3 11.42 11.06 0.2196 2.8056 9.4 0.234 2.5079 4 16.5 15.88 0.1928 3.6419 13.5 0.204 3.2326 5 6.4 6.26 0.2801 1.9341 5.32 0.3038 1.7597 6 9.55 9.28 0.2353 2.4859 7.88 0.252 2.2334 TABLE V. INITIAL ARC FLASH LEVELS AS PER IEEE 1584 (PCC) Bus No. Voltage (kV) Case Bolted Fault Current (kA) Arc Fault Current (kA) 100% and 85% Time of clearing arc fault current (sec) Incident Energy released at working distance (cal/cm2) PCC 0.415 1 28.9 14.16 0.6608 19.9886 12.04 0.7137 18.1105 2 54.32 23.73 0.5345 28.2471 20.17 0.5689 25.2211 3 29.39 14.36 0.6567 20.1637 12.2 0.7088 18.2563 4 56.02 24.33 0.5295 28.7558 20.68 0.5633 25.6626 5 28.012 13.8 0.6686 19.6742 11.73 0.7226 17.8383 6 51.19 22.604 0.5444 27.3 19.21 0.58 24.3988 From the above tables, it can be clearly seen that the most favorable scheme of operation under normal condition is Case 1 with one transformer only in operation. When work is to be done on energized equipment, the best mode of operation is Case 5 i.e. in isolated condition with only one transformer in operation to feed each bus. Any changes in the setting of the relay to bring down the clearing time so as to lower the incident energy in older plants with limited range of settings in the existing electromechanical relays results in Relay coordination disturbance and may lead to operation of the relay even under through fault conditions and isolation of even normal areas. Under these limitations two possible actions that can be taken are:
  • 9. IJAPE ISSN: 2252-8792  Remediation of Old Substations for Arc Flash Hazard (Zakir Husain) 31 Zone Selective Interlocking Zone Selective Interlocking (ZSI) can be incorporated in such a case so that if the breaker nearest to the fault senses it will give locking command to the upstream breaker and will clear the fault without any intentional time delay irrespective of the setting of the relay. Temporary Reduced Setting Another feasible solution for this is by providing maintenance bypass switch which will provide a different set of relay settings during any maintenance activity thus giving instantaneous clearance of arc fault or by providing unit differential protection on the bus, the fault current levels and thus the incident energy can be reduced substantially. The levels thus reduced are given in Table VI. TABLE VI. FINAL ARC FLASH LEVELS AS PER IEEE 1584 BY LOWERING CLEARING TIME Bus No. Voltage (kV) Bolted Fault Current (kA) Arc Fault Current (kA) Time of clearing arc fault current (sec) Incident Energy released at working distance (cal/cm2) Bus 2 11 16.87 16.2283 0.1 2.184 Bus 3 6.6 10.93 10.5921 0.1 1.22 PCC 0.415 28.9 14.1615 0.1 3.025 The Flash Protection Boundary is defined as an approach limit at a distance from live parts that are uninsulated or exposed within which a person could receive a second degree burn (IEEE 1584[1]). It can be calculates as. c. Flash Protection Boundary DB = [4.184Cf En (t/0.2) (610x /EB)] 1/x Or by Lee’s method, DB = [2.142 X 106 V Ibf (t/EB)]1/2 Where, EB = 5 J/cm2 for bare skin (second degree burns, curable) = 33.33 J/cm2 for PPE of 8 cal/cm2 Thus, flash protection boundary i.e. safe working distance for bare skin and with PPE of 8 cal/cm2 [5] before and after remediation is shown in Table VII and VIII. TABLE VII. FLASH PROTECTION BOUNDARY BEFORE REMEDIATION Bus No. Voltage (kV) Flash Protection Boundary (m) IEEE 1584 1.2 cal/cm2 (bare skin) 8 cal/cm2 (PPE) Bus 2 11 1.68 0.24 Bus 3 6.6 2.1 0.3 PCC 0.415 3.4 1.065 TABLE VIII. FLASH PROTECTION BOUNDARY AFTER REMEDIATION Bus No. Voltage (kV) Flash Protection Boundary (m) IEEE 1584 1.2 cal/cm2 (bare skin) 8 cal/cm2 (PPE) Bus 2 11 1.68 0.24 Bus 3 6.6 0.925 0.132 PCC 0.415 1.071 0.337 As can be seen from above the approach distances and incident energies reduced considerably for the 415V PCC system and 6.6kV Bus. With PPEs of 8 cal/cm2, the work can be safely done without any harm to the operators.
  • 10.  ISSN: 2252-8792 IJAPE Vol. 3, No. 1, April 2014 : 23 – 32 32 Arc Containment Device [6] Another solution that can be used is the arc containment device [6] which is essentially an enclosure containing electrodes. With the help of trigerring through light sensors and CT input the plasma gun can be used to divert the arc from the switchgear to this device with impedance lower than the arcing impedance. Thus arc current starts passing through this chamber and the interruption of arc takes place in 7-8ms as compared to almost 100ms taken by the breaker. This leads to drastic reduction of the arc energy and safety of workers. The calculations are shown in Table IX with a clearing time of 10ms. TABLE IX. FLASH PROTECTION BOUNDARY AFTER REMEDIATION WITH THE HELP OF ARC CONTAINMENT DEVICE Bus No. Voltage (kV) Flash Protection Boundary (m) IEEE 1584 1.2 cal/cm2 (bare skin) Bus 2 11 0.158 Bus 3 6.6 0.087 PCC 0.415 0.263 But prior to using the arc containment device, its effect on the BIL of the system or any other harmful effects during normal operation of the Power system should be considered. Care should be taken so that this unit does not operate under normal switching operations. For this test should be carried out after commissioning and before taking into line. Also, there should be provision of checking the condition of electrodes and replacement if required during routine maintenance or after failure. 7. CONCLUSION Safety of working personnel is paramount while carrying out any job on electrical equipment and any mistake could lead to damage to both personnel working in the vicinity and equipment. To avoid such occurrences, As much as possible, the maintenance work on any electrical system should be carried out after de-energizing the equipment to be taken for maintenance and proper work procedures and checks should be put into practice prior to starting the job. However, if it is impossible to avoid working on live panels like in case of Thermography etc., It has been found from the above calculations that by minor changes in the Protection logic of the existing system the safety of the working personnel can be ensured. REFERENCES [1] IEEE Guide for Performing Arc Flash Hazard Calculations, IEEE Std 1584-2002. [2] R. H. Lee. “The Other Electrical Hazard: Electric Arc Burns”, IEEE Power Systems Protection Committee Annual Conf. and Record, Philadelphia, PA, Oct. 5-9,1981. [3] Doughty,R.L.,Neal,T.E.,and Floyd,H.L. “Predicting incident energy to better manage the electric arc hazard on 600-V power distribution systems”, IEEE Transactions on Industry Applications, Vol/Issue: 36(1). Pp. 257-269, 2000. [4] NFPA 70E, Electrical Safety in Workplace, 2009. [5] J.C. Das. “Protection planning and system design to reduce arc flash incident energy in a multivoltage level distribution system to 8 cal/cm2 (HRC2) or less-Part 1. Methodology”, In conf. record, IEEE Pulp and Paper Industry Conference, San Antonio, 2010. [6] Roscoe, G. Papallo T. and Marcelo Valdes P.E. Arc Flash Energy Mitigation by Fast Energy Capture.