CONVERTING SOLIDILY GROUNDED TRANSFORMERS TO HIGH
RESISTANCE GROUNED SYSTEMS; PRACTICAL APPLICATIONS STUDY
Sergio Panetta,
P. Eng.
Senior Member, IEEE
I-Gard Corp
Mississauga, ON
L4T 1L2
Canada
Aaron McPhee,
CMRPe
Member, IEEE
International Paper
Augusta, GA
30906
USA
Todd Legette
Senior Member, IEEE
International Paper
Loveland, OH
45150
USA
Edmundo Perich
Member, IEEE
I-Gard Corp
Mississauga, ON
L4T 1L2
Canada
Abstract - This paper is a summary of a case study of a
pulp and paper mill that had greater than 100 solidly
grounded substations. In order to reduce the likelihood of
an arc flash, they were changes to a high resistance
grounded system. This change increased the safety and
reliability of the facility as well as reduce arc flash
incidences in the low-voltage substations.
Index Terms – High resistance grounding, arc flash
mitigation, system grounding.
I. INTRODUCTION
There are many ways to mitigate arc flash energy and
incidences. NFPA 70E states: [1].
“O.2.1 Employers, facility owners, and managers who have
responsibility for facilities and installations having electrical
energy as a potential hazard to employees and other
personnel should ensure that electrical hazards risk
assessments are performed during the design of electrical
systems and installations.”
From the onset of any power distribution project, arc flash
design discussions should first focus on how to best protect
the employees while limiting the fault currents to reduce arc
flash incident energy. To maximize the advantages of
mitigation techniques, one should employ a combination of
techniques concurrently while also limiting the probability of
occurrence utilizing High Resistance Grounding.
The following well-recognized methods should be considered
to facilitate the reduction of arch flash hazards:
(1) Achieve an electrically safe work condition.
(2) Reduce the likelihood of exposure through the use of High
Resistance Grounding
(3) Reduce the magnitude of the arc flash through several
well-recognized mitigation techniques such as relay
coordination changes and equipment changes,
(4) Reduce the severity of exposure through the use of the
proper personnel protective equipment.
This paper will discuss what strategies were employed as
well as what can be done in the future to mitigate hazards
further. This paper will be limited to the low-voltage system
only.
Per IEEE 1584[2] it is necessary to evaluate the arc flash
mitigation utilizing the following two equations:
Equation (1) shows the calculations required to solve for the
arcing current
)(lg00304.0)(lg5588.0
000526.00966.0lg662.0lg
bfbf
bfa
IGIV
GVIKI
−+
+++=
Where
lg is the log10
Ia is the arcing current (kA)
K is -0.153 for open configurations
is -0.097 for box configurations
Ibf is bolted fault current for three-phase faults (kA)
V is the system voltage (kV)
G is the gap between conductors, (mm)
Equation (2) is used to determine the normalized incident
energy.
GIKKE an 0011.0lg081.1lg 21 +++=
Where
En is Incident Energy (J/cm
2
) normalized for time and
distance
K1 is -0.792 for open configuration
Is -0.555 for box configuration
K2 is 0 for ungrounded and high resistance grounded
Is -0.113 for solidly grounded
Finally equation (3) is used to determine the incident energy
at a distance and set time.












= x
x
nf
D
t
ECE
610
2.0
184.4
978-1-5090-0416-4/16/$31.00 ©2016 IEEE 41
Where
E is Incident Energy (J/cm
2
)
Cf is calculation factor (1.5 for Low-voltage)
t is arcing time (s)
D distance from the possible arc point to the person
(mm)
x is the distance exponent.
II. REDUCING THE PROBABILITY OF EXPOSURE
The first step in addressing arc flash is to reduce the
probability of exposure at the inception of the arc fault. This
can be accomplished utilizing high resistance grounding
(HRG) systems
A. High Resistance Grounding
It is well known that up to 70% of all electrical faults begin as
single-phase-to-ground faults. [3] Therefore, reducing the
energy produced by this type of fault will reduce the likelihood
of a single phase to ground fault to propagate to a phase to
phase or 3 phase fault, thus reducing the likelihood.
Annex O of NFPA 70E clearly specifies high resistance
grounding as an arc flash mitigation technique. Yet, in looking
at equations1, 2, and 3, it is easy to determine that the act of
employing a high resistance grounded system will not lower
incident energy, but increase it, so why would NFPA 70E
reference HRG installations as a method to mitigate arc flash
hazards? The reason is that installing HRG systems reduces
the probability of the most common type of fault (Phase to
ground) being limited in energy to propagate to a phase to
phase or three phase fault.
High resistance grounding is the only method to date that will
reduce the probability of exposure before a significant phase
to ground fault arc flash occurs. The methods that will be
briefly discussed will not reduce the probability of an arc flash
occurring, and begin mitigating the arc flash only after the fault
has occurred.
In the studied facility, a significant decision-making process
was conducted to determine the best approach which gave
the facility the most protection for their employees. To do this,
the owners chose to implement arc flash reduction in a two-
pronged attack; first limit the probability of arc flash occurring
and second reduce the arc flash incident energy if more than
a phase to ground occurs. Arc flash mitigation was
accomplished through a number of strategies;
Reduce probability of Arc Flash:
1) High Resistance Grounds Systems were
installed on all low-voltage transformers
Reduce Arc Flash Incident energy:
1) Installation of low-voltage power circuit breakers
(LVPCB) digital relays on most (low-voltage (LV)
breakers for tighter tripping control.
2) Installation of electronic protection relays on low-
voltage substations which incorporated
Maintenance Mode switches programmed into
the relays
3) Installation of C200 class CTs to serve the new
digital relays
4) Installation of 15kv primary fuses which have
faster trip curves.
Many substations were converted from solidly grounded to
high resistance grounded. With disadvantages and
advantages as follows:
HRG Disadvantages:
Per their study, the installation of these HRG systems did in
fact increase the arc flash incident energy somewhat. They
found that several substations went from Category 4 to
Category Dangerous. This necessitated more remote trip
installations and equipment.
The facility also recognized another disadvantage; the
unavailability of the neutrals to service line-to-neutral loads.
This necessitated the installation of isolation transformers to
service these loads. This also made the system safer by
exposing the single phase loads to much lower bolted fault
current.
HRG Advantages:
Even with the added cost to the project, there where
overwhelming advantages observed by utilizing a high
resistance ground system and the facility felt it was well worth
it since they wanted to not only reduce the probability of an
arc flash occurrence but also reduce the incident energy to
protect their employees.
1) With the HRG systems installed, the facility saw
continuity of power even during the presence of
a phase to ground fault. This kept the
operations running and gave them the time
needed to swap to a backup motor / system and
not disrupt the operation.
2) An unexpected advantage observed was the
decrease in motor failures as represented Fig. 1
which directly correlated to the reduction of
operational LV electrical downtime and in
increase in the facility reliability. This was
significant cost avoidance for the operation.
42
Figure 1 Motor Repair costs. [4]
Shown in Figure 1 are the repair costs of the motors. It can be
seen that the trend prior to the installation of the HRG is
increasing in cost. After installation of the HRG systems both
the frequency of motor repair and the costs of motor repair
have decreased.
III. CONCLUSION
The initial state of the facility substations were solidly
grounded with some of them having an incident energy of 36
cal/cm
2
. NFPA 70 E states that high resistance grounding is
an arc flash mitigation technique, but, after its implementation
the incident energy increased to 47 cal/cm
2
which was further
mitigated using zone-selective interlocking and other
methods.
Although the incident energy increased on the substations
where HRG’s were installed, when combined with other well
accepted technical arc flash mitigation strategies the facility
considered the combination much safer and less risk to the
operational continuity than implementing a single arc flash
mitigation element.
By integrating HRG’s as suggested in NFPA 70E, we have an
arc flash mitigation technique that reduces the likelihood of an
arc flash occurring.
NFPA suggests many techniques to mitigate arc flash
hazards. By far one of the most effective and the only method
that works before the fault occurs is high resistance
grounding. This method combined with other mitigation
strategies will increase operational uptime as well as reduce
arc flash incident energy levels.
IV. REFRENCES
[1] NFPA 70E, 1996 National Electrical Code, Quincy, MA:
NFPA.
[2] IEEE Std 1584, 2002, “IEEE Guide for Performing Arc-
Flash Hazard Calculations” Piscataway, NJ, IEEE
[3] J.R. Dunki –Jacobs, F.J. Shields, Conrad St. Pierre,
Industrial Power System Grounding Design Handbook,
2007.
[4] International Paper; Augusta Mill Reliability Incident
database.
[5] International Paper; Augusta Mill AMEC Arc Flash
Study.
V. VITA
Sergio A. R. Panetta received a B.Eng. degree from
McMaster University, Hamilton, ON, in 1983, M. Eng.
Degree from McMaster University, Hamilton, ON, in 1996,
all in electrical/electronic engineering. Extensive expertise in
Automation, Control, switchgear design, and protection
relay design provides excellent resources for his position as
Vice President of Engineering at I-Gard Corporation
Mr. Panetta is registered professional engineer in the
provinces of Ontario, a designated consulting engineer,
Senior Member of the Institute of Electrical and Electronics
Engineers, a member of the Institution of Engineering and
Technology (MIET), UK. spanetta@i-gard.com
Aaron McPhee is currently Sr. Electrical Reliability
Engineer, International Paper Corporation, Augusta,
Georgia. He is responsible for all aspects of EPD (Electrical
Power Distribution) throughout the Augusta Mill. He serves
as the bleach board division electrical engineer assigned to
International Paper’s Enterprize wide EPD Steering
Committee, as well as on numerous company electrical and
reliability committees. He is also responsible for conducting
EPD courses within the company and has also received
several awards and recognitions for his practical approach
to EPD.
Mr. McPhee attended the Georgia Institute of
Technology’ Atlanta Ga, Augusta Technical College;
Augusta Ga. and Brenau University, Gainesville Ga,
receiving both an ASEE and BS degrees.
Aaron.McPhee@ipaper.com
Todd Legette is a Corporate Staff Engineer and Group
Leader for International Paper. He is responsible for
electrical power distribution, electrical reliability, turbine
controls, and instrument/electrical precision maintenance.
Mr. Legette received a B.S. in Electrical Engineering from
the University of Tennessee in Knoxville in 1987. He is a
Senior Member of the Institute of Electrical and Electronics
Engineers and serves as the Secretary/Treasurer for the
IEEE Pulp, Paper, and Forest Products Industry
Committee. Todd.Legette@ipaper.com
43
Edmundo A. Perich received the B.Sc. EE. Degree
from Simon Bolivar University in 1980 and a MBA degree
from Indiana University, IN, USA in 1991. Mr. Perich is
currently Regional Manager with I-Gard Corporation in
Ontario, Canada. Provides sales and technical support on
power system grounding products for electrical power
systems for industrial and utility applications. His research
interest include new products in grounding systems,
ground fault relaying and arc-flash mitigation
systems.eperich@i-gard.com
44

More Related Content

What's hot

PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAYPROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAYijiert bestjournal
 
FAMILIRIZATION OF THERMAL POWER PLANT
FAMILIRIZATION OF THERMAL POWER PLANTFAMILIRIZATION OF THERMAL POWER PLANT
FAMILIRIZATION OF THERMAL POWER PLANTRavindra Kumar
 
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...IRJET Journal
 
Power System Operation with Reduced System Strength for Inverter-connected Ge...
Power System Operation with Reduced System Strength for Inverter-connected Ge...Power System Operation with Reduced System Strength for Inverter-connected Ge...
Power System Operation with Reduced System Strength for Inverter-connected Ge...Power System Operation
 
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...IJERA Editor
 
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Frequency Scanning Techniques for Subsynchronous Resonance Screening AnalysisFrequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Frequency Scanning Techniques for Subsynchronous Resonance Screening AnalysisHardik Parikh, E.I.T.
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and groundingmichaeljmack
 
Westinghouse
WestinghouseWestinghouse
WestinghouseKHKJM
 
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...IRJET Journal
 
Impact of high level penetration of photovoltaics on Power system
Impact of high level penetration of photovoltaics on Power systemImpact of high level penetration of photovoltaics on Power system
Impact of high level penetration of photovoltaics on Power systemMuwaf_5
 
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities IJECEIAES
 
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...IRJET Journal
 

What's hot (19)

Islands in power systems
Islands in power systemsIslands in power systems
Islands in power systems
 
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAYPROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
PROTECTION OF MICROGRID FROM HIGH IMPEDANCE FAULT USING DIFFERENTIAL RELAY
 
FAMILIRIZATION OF THERMAL POWER PLANT
FAMILIRIZATION OF THERMAL POWER PLANTFAMILIRIZATION OF THERMAL POWER PLANT
FAMILIRIZATION OF THERMAL POWER PLANT
 
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...
Optimal Overcurrent Relay Coordination using GA, FFA, CSA Techniques and Comp...
 
Power System Operation with Reduced System Strength for Inverter-connected Ge...
Power System Operation with Reduced System Strength for Inverter-connected Ge...Power System Operation with Reduced System Strength for Inverter-connected Ge...
Power System Operation with Reduced System Strength for Inverter-connected Ge...
 
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
Active Anti-Islanding Protection For Grid Connected Solar Photovoltaic Power ...
 
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Frequency Scanning Techniques for Subsynchronous Resonance Screening AnalysisFrequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
Frequency Scanning Techniques for Subsynchronous Resonance Screening Analysis
 
Microgrid Protection
Microgrid ProtectionMicrogrid Protection
Microgrid Protection
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and grounding
 
H011117484
H011117484H011117484
H011117484
 
Westinghouse
WestinghouseWestinghouse
Westinghouse
 
10.3_Practical Implementation of Microgrid Control, Protection, and Communica...
10.3_Practical Implementation of Microgrid Control, Protection, and Communica...10.3_Practical Implementation of Microgrid Control, Protection, and Communica...
10.3_Practical Implementation of Microgrid Control, Protection, and Communica...
 
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...
IRJET- Reliability Enhancement of Low-Power Sequential Circuits using Power G...
 
Impact of high level penetration of photovoltaics on Power system
Impact of high level penetration of photovoltaics on Power systemImpact of high level penetration of photovoltaics on Power system
Impact of high level penetration of photovoltaics on Power system
 
Islanding
IslandingIslanding
Islanding
 
Managing High PV Deployment on the EPS: Overview of Key Challenges and Mitiga...
Managing High PV Deployment on the EPS: Overview of Key Challenges and Mitiga...Managing High PV Deployment on the EPS: Overview of Key Challenges and Mitiga...
Managing High PV Deployment on the EPS: Overview of Key Challenges and Mitiga...
 
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities
Wide Area Oscillation Damping using Utility-Scale PV Power Plants Capabilities
 
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 

Viewers also liked

A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEME
A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEMEA PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEME
A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEMEIbrahim Yusuf Salihu
 
Linea del tiempo line.do
Linea del tiempo line.do Linea del tiempo line.do
Linea del tiempo line.do mariagv23
 
Behind the net curtains
Behind the net curtainsBehind the net curtains
Behind the net curtainsBecky Marsh
 
Maneras de comunicar información
Maneras de comunicar informaciónManeras de comunicar información
Maneras de comunicar informaciónJOSUEELIAN
 
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...Muhammad Ihsan
 
Smith, Simon- Resume - Master
Smith, Simon- Resume - MasterSmith, Simon- Resume - Master
Smith, Simon- Resume - Mastersimon smith
 
Robert Williams Work Experience
Robert Williams Work ExperienceRobert Williams Work Experience
Robert Williams Work ExperienceRobert Williams
 
Past student work 4
Past student work 4 Past student work 4
Past student work 4 Becky Marsh
 
Ecopreneur Una empresa que vale la pena como modelo a imitar
Ecopreneur Una empresa que vale la pena como modelo a imitarEcopreneur Una empresa que vale la pena como modelo a imitar
Ecopreneur Una empresa que vale la pena como modelo a imitarAlberto Levy
 
nitalistari resume
nitalistari resumenitalistari resume
nitalistari resumenita listari
 

Viewers also liked (15)

A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEME
A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEMEA PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEME
A PRESENTATION ON STUDENT INDUSTRIAL WORK EXPERIENCE SCHEME
 
Linea del tiempo line.do
Linea del tiempo line.do Linea del tiempo line.do
Linea del tiempo line.do
 
Phillip.Gilbert.CLU
Phillip.Gilbert.CLUPhillip.Gilbert.CLU
Phillip.Gilbert.CLU
 
TUMIOFreeWifi
TUMIOFreeWifiTUMIOFreeWifi
TUMIOFreeWifi
 
Behind the net curtains
Behind the net curtainsBehind the net curtains
Behind the net curtains
 
Maneras de comunicar información
Maneras de comunicar informaciónManeras de comunicar información
Maneras de comunicar información
 
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...
Surya Grand Cisoka Tangerang, Gudang + Rumah Tinggal Murah & Strategis 0822-9...
 
Aps bomba d'água
Aps   bomba d'águaAps   bomba d'água
Aps bomba d'água
 
CURRICULUM VITA ANTH
CURRICULUM VITA ANTHCURRICULUM VITA ANTH
CURRICULUM VITA ANTH
 
Smith, Simon- Resume - Master
Smith, Simon- Resume - MasterSmith, Simon- Resume - Master
Smith, Simon- Resume - Master
 
Robert Williams Work Experience
Robert Williams Work ExperienceRobert Williams Work Experience
Robert Williams Work Experience
 
Introduction_APPC
Introduction_APPCIntroduction_APPC
Introduction_APPC
 
Past student work 4
Past student work 4 Past student work 4
Past student work 4
 
Ecopreneur Una empresa que vale la pena como modelo a imitar
Ecopreneur Una empresa que vale la pena como modelo a imitarEcopreneur Una empresa que vale la pena como modelo a imitar
Ecopreneur Una empresa que vale la pena como modelo a imitar
 
nitalistari resume
nitalistari resumenitalistari resume
nitalistari resume
 

Similar to Converting Solidly to HRG

Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardIJAPEJOURNAL
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_webLaurence Michael, PE
 
Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2IAEME Publication
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorIRJET Journal
 
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...IRJET Journal
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET Journal
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionMike Nager
 
Defense In Depth Of Electrical Systems Preliminary Findings And Recommendat...
Defense In Depth Of Electrical Systems   Preliminary Findings And Recommendat...Defense In Depth Of Electrical Systems   Preliminary Findings And Recommendat...
Defense In Depth Of Electrical Systems Preliminary Findings And Recommendat...John Bickel
 
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...IRJET Journal
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...IRJET Journal
 
DG interconnection protection ieee 1547
DG interconnection protection ieee 1547DG interconnection protection ieee 1547
DG interconnection protection ieee 1547michaeljmack
 
Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Aditya Kumar Tripathy
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guidePrasad RVS
 
Overview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesOverview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesIAEME Publication
 

Similar to Converting Solidly to HRG (20)

Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazard
 
6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web6250 application existing_jb-kz_20070214_web
6250 application existing_jb-kz_20070214_web
 
D010622334
D010622334D010622334
D010622334
 
Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2Optimal dg placement using multiobjective index and its effect on stability 2
Optimal dg placement using multiobjective index and its effect on stability 2
 
RAMS Tech Paper
RAMS Tech PaperRAMS Tech Paper
RAMS Tech Paper
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
 
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...
IRJET- Power Quality Improvement by using Three Phase Adaptive Filter Control...
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
IRJET- Embedded System based Multi-Source Leakage Current Protection for Low ...
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage Protection
 
Defense In Depth Of Electrical Systems Preliminary Findings And Recommendat...
Defense In Depth Of Electrical Systems   Preliminary Findings And Recommendat...Defense In Depth Of Electrical Systems   Preliminary Findings And Recommendat...
Defense In Depth Of Electrical Systems Preliminary Findings And Recommendat...
 
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...
IRJET- Comparative Analysis of Different Converter Topologies Employed for Tr...
 
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...Design of Low-Voltage Distributed Photovoltaic Systems Oriented to   Improve ...
Design of Low-Voltage Distributed Photovoltaic Systems Oriented to Improve ...
 
DG interconnection protection ieee 1547
DG interconnection protection ieee 1547DG interconnection protection ieee 1547
DG interconnection protection ieee 1547
 
Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems Protection of Converter Dense Power Systems
Protection of Converter Dense Power Systems
 
A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...A modified bridge-type nonsuperconducting fault current limiter for distribut...
A modified bridge-type nonsuperconducting fault current limiter for distribut...
 
Transformer guide
Transformer guideTransformer guide
Transformer guide
 
Transfguide transformer protection application guide
Transfguide transformer protection application guideTransfguide transformer protection application guide
Transfguide transformer protection application guide
 
Pe3426652670
Pe3426652670Pe3426652670
Pe3426652670
 
Overview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniquesOverview lvrt capability of dfig techniques
Overview lvrt capability of dfig techniques
 

Converting Solidly to HRG

  • 1. CONVERTING SOLIDILY GROUNDED TRANSFORMERS TO HIGH RESISTANCE GROUNED SYSTEMS; PRACTICAL APPLICATIONS STUDY Sergio Panetta, P. Eng. Senior Member, IEEE I-Gard Corp Mississauga, ON L4T 1L2 Canada Aaron McPhee, CMRPe Member, IEEE International Paper Augusta, GA 30906 USA Todd Legette Senior Member, IEEE International Paper Loveland, OH 45150 USA Edmundo Perich Member, IEEE I-Gard Corp Mississauga, ON L4T 1L2 Canada Abstract - This paper is a summary of a case study of a pulp and paper mill that had greater than 100 solidly grounded substations. In order to reduce the likelihood of an arc flash, they were changes to a high resistance grounded system. This change increased the safety and reliability of the facility as well as reduce arc flash incidences in the low-voltage substations. Index Terms – High resistance grounding, arc flash mitigation, system grounding. I. INTRODUCTION There are many ways to mitigate arc flash energy and incidences. NFPA 70E states: [1]. “O.2.1 Employers, facility owners, and managers who have responsibility for facilities and installations having electrical energy as a potential hazard to employees and other personnel should ensure that electrical hazards risk assessments are performed during the design of electrical systems and installations.” From the onset of any power distribution project, arc flash design discussions should first focus on how to best protect the employees while limiting the fault currents to reduce arc flash incident energy. To maximize the advantages of mitigation techniques, one should employ a combination of techniques concurrently while also limiting the probability of occurrence utilizing High Resistance Grounding. The following well-recognized methods should be considered to facilitate the reduction of arch flash hazards: (1) Achieve an electrically safe work condition. (2) Reduce the likelihood of exposure through the use of High Resistance Grounding (3) Reduce the magnitude of the arc flash through several well-recognized mitigation techniques such as relay coordination changes and equipment changes, (4) Reduce the severity of exposure through the use of the proper personnel protective equipment. This paper will discuss what strategies were employed as well as what can be done in the future to mitigate hazards further. This paper will be limited to the low-voltage system only. Per IEEE 1584[2] it is necessary to evaluate the arc flash mitigation utilizing the following two equations: Equation (1) shows the calculations required to solve for the arcing current )(lg00304.0)(lg5588.0 000526.00966.0lg662.0lg bfbf bfa IGIV GVIKI −+ +++= Where lg is the log10 Ia is the arcing current (kA) K is -0.153 for open configurations is -0.097 for box configurations Ibf is bolted fault current for three-phase faults (kA) V is the system voltage (kV) G is the gap between conductors, (mm) Equation (2) is used to determine the normalized incident energy. GIKKE an 0011.0lg081.1lg 21 +++= Where En is Incident Energy (J/cm 2 ) normalized for time and distance K1 is -0.792 for open configuration Is -0.555 for box configuration K2 is 0 for ungrounded and high resistance grounded Is -0.113 for solidly grounded Finally equation (3) is used to determine the incident energy at a distance and set time.             = x x nf D t ECE 610 2.0 184.4 978-1-5090-0416-4/16/$31.00 ©2016 IEEE 41
  • 2. Where E is Incident Energy (J/cm 2 ) Cf is calculation factor (1.5 for Low-voltage) t is arcing time (s) D distance from the possible arc point to the person (mm) x is the distance exponent. II. REDUCING THE PROBABILITY OF EXPOSURE The first step in addressing arc flash is to reduce the probability of exposure at the inception of the arc fault. This can be accomplished utilizing high resistance grounding (HRG) systems A. High Resistance Grounding It is well known that up to 70% of all electrical faults begin as single-phase-to-ground faults. [3] Therefore, reducing the energy produced by this type of fault will reduce the likelihood of a single phase to ground fault to propagate to a phase to phase or 3 phase fault, thus reducing the likelihood. Annex O of NFPA 70E clearly specifies high resistance grounding as an arc flash mitigation technique. Yet, in looking at equations1, 2, and 3, it is easy to determine that the act of employing a high resistance grounded system will not lower incident energy, but increase it, so why would NFPA 70E reference HRG installations as a method to mitigate arc flash hazards? The reason is that installing HRG systems reduces the probability of the most common type of fault (Phase to ground) being limited in energy to propagate to a phase to phase or three phase fault. High resistance grounding is the only method to date that will reduce the probability of exposure before a significant phase to ground fault arc flash occurs. The methods that will be briefly discussed will not reduce the probability of an arc flash occurring, and begin mitigating the arc flash only after the fault has occurred. In the studied facility, a significant decision-making process was conducted to determine the best approach which gave the facility the most protection for their employees. To do this, the owners chose to implement arc flash reduction in a two- pronged attack; first limit the probability of arc flash occurring and second reduce the arc flash incident energy if more than a phase to ground occurs. Arc flash mitigation was accomplished through a number of strategies; Reduce probability of Arc Flash: 1) High Resistance Grounds Systems were installed on all low-voltage transformers Reduce Arc Flash Incident energy: 1) Installation of low-voltage power circuit breakers (LVPCB) digital relays on most (low-voltage (LV) breakers for tighter tripping control. 2) Installation of electronic protection relays on low- voltage substations which incorporated Maintenance Mode switches programmed into the relays 3) Installation of C200 class CTs to serve the new digital relays 4) Installation of 15kv primary fuses which have faster trip curves. Many substations were converted from solidly grounded to high resistance grounded. With disadvantages and advantages as follows: HRG Disadvantages: Per their study, the installation of these HRG systems did in fact increase the arc flash incident energy somewhat. They found that several substations went from Category 4 to Category Dangerous. This necessitated more remote trip installations and equipment. The facility also recognized another disadvantage; the unavailability of the neutrals to service line-to-neutral loads. This necessitated the installation of isolation transformers to service these loads. This also made the system safer by exposing the single phase loads to much lower bolted fault current. HRG Advantages: Even with the added cost to the project, there where overwhelming advantages observed by utilizing a high resistance ground system and the facility felt it was well worth it since they wanted to not only reduce the probability of an arc flash occurrence but also reduce the incident energy to protect their employees. 1) With the HRG systems installed, the facility saw continuity of power even during the presence of a phase to ground fault. This kept the operations running and gave them the time needed to swap to a backup motor / system and not disrupt the operation. 2) An unexpected advantage observed was the decrease in motor failures as represented Fig. 1 which directly correlated to the reduction of operational LV electrical downtime and in increase in the facility reliability. This was significant cost avoidance for the operation. 42
  • 3. Figure 1 Motor Repair costs. [4] Shown in Figure 1 are the repair costs of the motors. It can be seen that the trend prior to the installation of the HRG is increasing in cost. After installation of the HRG systems both the frequency of motor repair and the costs of motor repair have decreased. III. CONCLUSION The initial state of the facility substations were solidly grounded with some of them having an incident energy of 36 cal/cm 2 . NFPA 70 E states that high resistance grounding is an arc flash mitigation technique, but, after its implementation the incident energy increased to 47 cal/cm 2 which was further mitigated using zone-selective interlocking and other methods. Although the incident energy increased on the substations where HRG’s were installed, when combined with other well accepted technical arc flash mitigation strategies the facility considered the combination much safer and less risk to the operational continuity than implementing a single arc flash mitigation element. By integrating HRG’s as suggested in NFPA 70E, we have an arc flash mitigation technique that reduces the likelihood of an arc flash occurring. NFPA suggests many techniques to mitigate arc flash hazards. By far one of the most effective and the only method that works before the fault occurs is high resistance grounding. This method combined with other mitigation strategies will increase operational uptime as well as reduce arc flash incident energy levels. IV. REFRENCES [1] NFPA 70E, 1996 National Electrical Code, Quincy, MA: NFPA. [2] IEEE Std 1584, 2002, “IEEE Guide for Performing Arc- Flash Hazard Calculations” Piscataway, NJ, IEEE [3] J.R. Dunki –Jacobs, F.J. Shields, Conrad St. Pierre, Industrial Power System Grounding Design Handbook, 2007. [4] International Paper; Augusta Mill Reliability Incident database. [5] International Paper; Augusta Mill AMEC Arc Flash Study. V. VITA Sergio A. R. Panetta received a B.Eng. degree from McMaster University, Hamilton, ON, in 1983, M. Eng. Degree from McMaster University, Hamilton, ON, in 1996, all in electrical/electronic engineering. Extensive expertise in Automation, Control, switchgear design, and protection relay design provides excellent resources for his position as Vice President of Engineering at I-Gard Corporation Mr. Panetta is registered professional engineer in the provinces of Ontario, a designated consulting engineer, Senior Member of the Institute of Electrical and Electronics Engineers, a member of the Institution of Engineering and Technology (MIET), UK. spanetta@i-gard.com Aaron McPhee is currently Sr. Electrical Reliability Engineer, International Paper Corporation, Augusta, Georgia. He is responsible for all aspects of EPD (Electrical Power Distribution) throughout the Augusta Mill. He serves as the bleach board division electrical engineer assigned to International Paper’s Enterprize wide EPD Steering Committee, as well as on numerous company electrical and reliability committees. He is also responsible for conducting EPD courses within the company and has also received several awards and recognitions for his practical approach to EPD. Mr. McPhee attended the Georgia Institute of Technology’ Atlanta Ga, Augusta Technical College; Augusta Ga. and Brenau University, Gainesville Ga, receiving both an ASEE and BS degrees. Aaron.McPhee@ipaper.com Todd Legette is a Corporate Staff Engineer and Group Leader for International Paper. He is responsible for electrical power distribution, electrical reliability, turbine controls, and instrument/electrical precision maintenance. Mr. Legette received a B.S. in Electrical Engineering from the University of Tennessee in Knoxville in 1987. He is a Senior Member of the Institute of Electrical and Electronics Engineers and serves as the Secretary/Treasurer for the IEEE Pulp, Paper, and Forest Products Industry Committee. Todd.Legette@ipaper.com 43
  • 4. Edmundo A. Perich received the B.Sc. EE. Degree from Simon Bolivar University in 1980 and a MBA degree from Indiana University, IN, USA in 1991. Mr. Perich is currently Regional Manager with I-Gard Corporation in Ontario, Canada. Provides sales and technical support on power system grounding products for electrical power systems for industrial and utility applications. His research interest include new products in grounding systems, ground fault relaying and arc-flash mitigation systems.eperich@i-gard.com 44