International Journal of Applied Power Engineering (IJAPE)
Vol. 3, No. 2, August 2014, pp. 90~104
ISSN: 2252-8792  90
Journal homepage: http://iaesjournal.com/online/index.php/IJAPE
Towards an Accurate Modeling of Frequency-Dependent Wind
Farm Components under Transient Conditions
M. A. Abd-Allah, Mahmoud N. Ali, A. Said
Faculty of Engineering at Shoubra, Benha University, Egypt
Article Info ABSTRACT
Article history:
Received Mar 2, 2014
Revised Jul 10, 2014
Accepted Jul 23, 2014
Frequency dependence complete model is set up for describing the lightning
transient behavior of the wind turbines (WTs).To get an appropriate wind
turbine model, a high frequency models of surge arrester protecting the boost
transformer, transformer and ground electrode soil ionization are
implemented. The transient responses and Ground Potential Rise (GPR) can
be obtained at different locations in the WTs and connected grid in the time
domain as well as in the frequency domain using Fast Fourier Transform
(FFT). To check the validity of the model, Surge arresters protection level at
different locations, at i.e. LV, MV and HV, is compared with ABB
manufacture data sheet, Also a comparison has been made between simple
and frequency dependence model of overall wind farm components using
ATP/EMTP. This paper provides an accurate simulation of wind farm
components under transient condition.
Keyword:
ATP/EMTP
FFT
GPR
Surge arrester model
Transient response
WTs Copyright © 2014 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
M. A. Abd-Allah,
Faculty of Engineering at Shoubra, Benha University, Egypt.
Email: abdelrahman.ghoniem@feng.bu.edu.eg
1. INTRODUCTION
With a rapid growth in wind power generation, lightning hazard to wind turbines (WTs) has come to
be regarded with more attention. Due to their great height, distinctive shape, and exposed location, WTs are
extremely vulnerable to lightning stroke. After a WT is struck by lightning, high lightning current flows
through the WT and causes considerable damage to electrical equipment inside the WT structure and wind
turbine nacelle results stop of the generator operation and probably expensive repairs [1].
In order to decrease downtime, repairs and blade damaged. Protecting the blade is very important
and well-designed lightning protection is a necessity for this equipment so Modern wind turbine blades are
made of insulating materials such as glass fibre reinforced plastic (GFRP) as a common material or wood
epoxy. The lightning protection of wind turbine blades can be classified as receptor, metallic cap, mesh wire,
and metallic conductor as reported in IEC-61400-24 standards.
In general, the problem of lightning protection of wind turbine blades is to conduct the lightning
current safely from the attachment point on the blade to the hub and then to the ground.
However another serious problem known as "back-flow surge" which not only causes damages to
the wind turbine that has been struck but also the other turbines that have not. The back-flow surge
phenomenon has been defined as the surge flowing from a customer’s structure such as a communication
tower into the distribution line. High resistivity soil often makes Surge Arresters (SAs) at tower earthing
systems operate in reverse and allow backflow of surge current to the grid. The phenomenon of surge
invasion from a wind turbine that is struck by lightning to the distribution line in a wind farm is quite similar
to the case of ―back-flow surge‖ [2].
Due to significant influence on the wind farm behavior under lightning, the transient response must
be either accurately measured which very expensive and time consuming or reliably predicated by
simulations which allowing for parametric studies and optimization. Up till now the predominant approach
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
91
for simulating transient due to lightning is based on the representation of the wind farm components by their
equivalent circuits. Performance of wind farm under lightning requires accurate modeling of its components.
So in this paper wind farm is implemented using high frequency models components as SA, Transformer and
ground electrode to integrally describe this lightning current path. Validation of these models and
computation, characteristics and hazards of back-flow surge in wind farm are analyzed using onshore wind
farm as an example.
2. DESCRIPTION OF THE INVESTIGATED ONSHORE WIND FARM:
Figure1. Shows layout of onshore wind farm composed of two identical wind power generators.
Boost transformers for the generators are installed in vicinity of the wind turbine towers. All boost
transformers are connected to the grid via grid-interactive transformer by overhead distribution line. Surge
arresters are inserted to the primary and secondary sides of the boost and grid-interactive transformers.
Figure 1.Wind farm model [2]
3. MODELING OF THE ELECTRIC COMPONENTS OF THE ONSHORE WIND FARM USING
ATP/EMTP:
In this section, the detailed high frequency modeling of the electric components of the onshore wind
farm using the ATP/EMTP is demonstrated. These components include Transmission line (TL), transformers,
power system grid and surge arresters.
3.1. Lightning Model:
In order to simulate the impact of lightning current on power system or its components with
convenience, the lightning current in the mode of mathematical function is usually represented. After the
long-term speculation and research by many researchers, the approximate mathematical function was
proposed. A current function model called Heidler is now used widely [3, 4, 5]. A 400 Ω lightning path
resistance was parallelly connected to simulate natural lightning. Equation (1) represent the lightning current,
waveform of 51kA-2/631μs is used in this study as shown in Figure 2. The waveform of Heidler lightning
current is simulated by ATP/EMTP software.
2/
2
1
2
1
]1)/[(
)/(
)( 

 t
o e
t
t
Iti 

 (1)
Where
I0: the peak of current
τ1, τ2: time constants of current rising and dropping
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
92
Figure 2. The Waveform of 51ka - 2/631μs Lightning Current
3.2. Wind Turbine Generator:
Table 1 gives the required data for modeling the generators of the wind turbines, transmission line
and transformers.
Table 1 a, b, c. Wind Turbines, Transformers Data and connected line data [2]
Wind Turbine Model(Synchronous Generator- Y connected)
Voltage (line rms) 0.660 [kV]
Rated power 1.0 [MVA]
Leakage reactance 0.1 [H]
Frequency 60.0 [Hz]
Transformer Model (Boost, Grid-Interactive)
Connection method Y / Δ , Y / Δ
Voltage (line rms) 0.660/6.6 [kV], 66.0/6.6 [kV]
Rated power 1.0 [MVA], 10.0 [MVA]
Leakage reactance 0.15 [p.u]
Copper losses 0.005 [p.u]
No-load losses neglected
Line Model (values at 60 Hz)
positive / zero phase resistance [Ω/Km] 0.00105/0.021
Positive / zero phase inductance [mH/Km] 0.83556/2.50067
Positive / zero phase capacitance [nF/Km] 12.9445/6.4723
3.3. Wind Turbine Blades and Towers:
The down conductor in the blade and the wind turbine tower have been considered as a lossless
transmission line and they were estimated according to following experimental equation [4, 5, 6, 7], where
the down conductor and the tower often were treated as a cylindrical conductor. Equation (2) represents the
characteristic impedance of tower and the blade.
(f ile modelwind11.pl4; x-v ar t) c:XX0007-X0081A
0.0 0.2 0.4 0.6 0.8 1.0 1.2[ms]
0
10
20
30
40
50
60
[kA]
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
93
)2
22
(ln60  h
r
Z (2)
Where, Z is the surge impedance, r and h are the cylinder radius and height, respectively. The wind
tower is taken as an iron vertical conductor of 60 m height and 3.0 m radius.
3.4. Transmission Lines and cables:
The overhead lines are considered and represented by single-phase positive wave impedance (i.e.
Surge impedance) with the light velocity.
 CL/Z0 (3)
sm
LC
v /
1
 (4)
Where, C and L are the capacitance and inductance of line, respectively, Z0 is the surge impedance and
v is the propagation velocity [3, 8].
3.5. Transformer:
In order to study the transient involving frequencies up to a few kHz, stray capacitance of
transformer coils must be added to the transformer model. Capacitances are actually distributed, but lumped
parameters at the winding terminals for the total capacitance can be used with reasonable accuracy in this
case [3, 8, 9]. However, the transformer capacitances are often difficult to be determined. Transformer
capacitance is represented by CH, CL and CHL as shown in Figure 3 Where, CH is the capacitance of high
winding to ground, CL is the capacitance of low winding to ground and CHL is the capacitance between high
and low windings. Normally the CL and CHL are greater than CH. This is because the fact that the high voltage
calls for more separation between windings and between windings and core. The present work considers
these capacitances as in a table 2 [3].
Figure 3. High Frequency Transformer Model.
Table 2. Typical Capacitance of Transformers (Capacitance in nF) [3]
Transformer Core Type
MVA CH CHL CL
1 1.2-14 1.2-17 3.1-16
2 1.4-16 1-18 3-16
5 1.2-14 1.1-20 5.5-17
7 2.7-11 3.5-17 8-16
10 4-7 4-11 8-18
25 2.8-4.2 2.5-18 5.2-20
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
94
3.6. Surge Arrester:
Surge arrester devices play an important role for mitigating the overvoltage due to lightning,
switching. Under both normal and abnormal conditions, the arrester handles its operation based on its
nonlinearity, i.e. V-I characteristics [9].
A simplified model was derived from IEEE model [10, 11]. The model circuit is shown in Figure 4.
This model is composed by two sections of nonlinear resistances usually designated by A0 and A1 which are
separated by inductance L1 and L0. A parallel resistance Rp (about 1 MΩ) is added to avoid the numerical
instability of the combination of the current source and nonlinear elements. This model has the same
operating principles as the IEEE model. The main advantage of this model is that the parameters were
determined using only the electrical data and did not take into consideration any physical characteristics of
the surge arrester [12].
Figure 4. Pinceti and Giannettoni model
In case medium and high voltage levels the inductances L1 and L0 in the model are in μH and
calculated using:
Un
Ur
UrTUr
L
20/8
20/82/1
4
1
1

 (5)
(6)
In case low voltage levels the inductances L1 and L0 in the model are in μH and calculated using:
L1=0.03 Un (7)
L0=0.01 Un (8)
Where UN is the arrester rated voltage in kV, Ur1/T2 is the residual voltage at 10 kA fast front
current surge (1/T2 μs). Ur8/20 is the residual voltage at 10 kA current surge with 8/20 μs time parameters.
The nonlinear characteristics of the two elements A0 and A1 are based on the pu data published in
[13] and the corresponding nonlinear characteristics of A0 and A1 are shown in Figure 6.
a. A0 non-linear characteristics. b. A1 non-linear characteristic.
Figure 6. Surge Arrester Elements Nonlinear Characteristics.
0.0 5.0 10.0 15.0 20.0
I [kA]0.9
1.0
1.1
1.3
1.4 U [kV]
0.0 5.0 10.0 15.0 20.0
I [kA]0.7
0.8
0.9
1.1
1.2 U [kV]
Un
Ur
UrTUr
L
20/8
20/82/1
12
1
0


IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
95
The surge arrester model is simulated and tested using ATP/EMTP circuit shown in Figure 7.
Figure 7. ATP/EMTP Circuit for Surge Arrester.
The arrester model is tested to match the manufacture's data sheet [14] under switching and
lightning characteristics. 440kV SA with L1 and L0 are equal 0.07μH [6] used in low voltage side boast
transformer. A discharge current 8/20 μs, 5 kA and 25 kA for nominal and maximum conditions respectively
are injected to the surge arrester. The error of residual voltage rather than the manufactured data is found
0.22% at the nominal discharge current and -1.7% at the maximum discharge current. This error is computed
as (Ups-Up)/Up, where Ups is simulated residual voltage (the simulated voltage protection level). The
injected current, the residual voltage and the absorbed energy are as shown in Figures 8 and 9 for nominal
and maximum discharge currents, respectively.
a. Injected current (nominal discharge current). b. Residual voltage.
Figure 8. Injected nominal and maximum discharge current and resuidual voltage.
Figure 9. Absorbed Energy under Injected Nominal and Maximum Discharge Current.
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
x 10
-4
0
0.5
1
1.5
2
2.5
x 10
4
Time (sec)
Current(A)
Nominal discharge current
Maxmum discharge current
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
x 10
-4
0
500
1000
1500
2000
2500
Time (sec)
Voltage(V)
Residual voltage (nominal current)
Residual voltage (Maxmum current)
ABB
manufacture
data sheet
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
x 10
-4
0
200
400
600
800
1000
1200
1400
Time (sec)
SAconsumptionenergy(J)
SA energy (maxmum current)
SA energy (nominal current)
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
96
The MV surge arrester protecting boost transformer with L1 and L0 are 0.0952 μH and 0.286 μH
respectively [6].from test as shown in Figure 10 find errors within acceptable limits
0
2
4
6
8
10
12
14
16
18
20
22
500A
30/60us
125A
30/60us
20kA
8/20us
10kA
8/20us
5kA
8/20us
2.5kA
8/20us
1kA
8/20us
10kA
1/2us
5kA
1/2us
Residual voltage(data sheet)
Residual voltage (simulation)
Error%
Impulse current
Protectionlevel(kV)
0
10
20
30
40
Error%
Figure 10. MVSA Validation
The HV surge arrester protecting grid transformer with L1 and L0 are 1.62μH and 0.54μH
respectively. From test as shown in Figure 11 find errors within acceptable limits
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
2000A
30/60us
100A
30/60us
500A
30/60us
20kA
8/20us
10kA
8/20us
5kA
8/20us
manufactur data
simulated
Error%
Impulse current
Protectionlevel(kV)
0
5
10
15
20
25
30
35
40 Error%
Figure 11. HVSA Validation
3.7. Vertical ground rod modeling:
Grounding systems behavior is well understood at power frequency. However, during lightning
strokes the grounding systems performance might be different. The waveform of the lightning current has a
major influence on the dynamic performance of ground electrodes. While high lightning current intensity
improves the dynamic grounding performance due to ionization of the soil. In case of high lightning currents
the electric field at the ground electrodes might become larger than the electric strength of the soil. Which
can cause breakdown and sparks discharge in the soil. This phenomenon improves the grounding system
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
97
performance so its ignoring always gives inaccurate results. On the other hand, due to the frequency
dependent phenomena, the grounding performance might be much worse during fast front lightning current
pulses. This can deteriorate the efficiency of the protection. Grounding system of a wind turbine plays a
critical role, since overvoltages caused by lightning strikes and other faults has to be successfully dispersed
into the ground. So, it is important to get an accurate model of the wind turbine grounding system. In this
paper the behavior of the wind turbine under lightning strikes has been studied using two different models for
the grounding resistance [15]. The first model is the linear model of grounding resistance which is based on a
constant value for the grounding resistance i.e. low voltage, low frequency [16]. The constant resistance Ro
of the model is estimated in ohm based on the rod dimensions and the soil parameters [15]:
}1
4
{ln
20 
a
l
l
R


(9)
Where, ρ is the soil resistivity (Ω.m), L is the electrode length (m) and a is the electrode radius (m).
The other model is based on the nonlinear performance of the grounding resistance with high
currents i.e. high voltage, high frequency [16]. The nonlinearity nature of the ground resistance can be
represented by a nonlinear resistance, RT, whose value is given as [15];











)(
1
)(
0
0
IgiFor
Ig
i
R
Rt
IgiForRRt 
(10)
Where, i is the current through the rod (kA), and Ig is the critical current for soil ionization (kA)
which is given by:
2
0
0
2 R
E
Ig



(11)
Where, E0 is the critical soil ionization gradient.
4. MODEL VALIDATION:
In this study, the wind power generator modeled as a synchronous machine for simplicity. The
grounding model at each wind tower is simulated as three separated ground electrodes, where each electrode
simulated as 10 Ω resistance. There is no connection between the grounding systems for wind turbines. The
distribution line is assumed as overhead line and simulated as transposed distributed line parameters. The
lightning stroke is taken as striking wind turbine (WT#1) as shown in Figure 12.
Figure 12. Lightning hit WT#1 [3]
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
98
4.1. Effect Of Frequency Dependant Surge Arrester and Transformers Model on Back Flow Current
Overvoltages:
In this work, The backflow current-overvoltages is evaluated using different transformer and surge
arrester models in the time domain as well as frequency domain using Fast Fourier Transform (FFT)
considering onshore wind farm. Case#1 Simple model of SA consists of only one non linear element with
characteristics and Power frequency transformer model as shown in figure 13.
Figure 13. Atpdraw Circuit of Two Wind Turbines with Simple Model
Case#2 frequency dependent transformer model and frequency dependent model of SA is a
combination of non linear elements and linear inductances which provides dynamic behavior during
lightning. The SAs are used at low, medium and high voltage levels in the wind farm as shown in figure 14.
Figure 14: Atpdraw Circuit of Two Wind Turbines with Freq. Dependant Model
Figures 15 to 18 show the voltage waveforms, peak value, and frequency spectrum oscillation
comparison at different locations of the wind farm. In different two cases, i.e. Simple and frequency
dependent model, It is observed that the peak magnitude of the generated overvoltage at WT#1 generator
terminal reach to 200kV, at (WT#1) boost transformer secondary side reach to 186kV, at (WT#2) boost
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
99
transformer secondary side reach to 25kV and at grid reach to 28kV in different models. It is clear that small
change in peak value of overvoltages under simple and frequency dependant model. But from frequency
content point of view, it can be seen that the amplitude voltage at different frequencies when using simple
model is higher than that when using frequency dependant model. This can be attributed to the fact that the
reflecting traveling waves at junction of the boost transformer of WT#2 and at the junction of the grid-
interactive transformer are decreased due to the presence of the capacitors in the frequency dependant model.
On the other hand, the frequency dependent model considers very high impedance at high frequencies.
Therefore, for a better surge analysis of wind farm, the capacitance between winding of transformer model
must be taken to get accurate transient results.
A. Waveforms Comparison @Wt#1 In Case Simple
and Frequency Dependant Model
B. Frequency Spectrum Comparison
Figure 15. Overvoltages and Frequency Spectrum @WT#1
c. Waveforms Comparison @WT#2 In Case Simple
And Frequency Dependant Model
d. Frequency Spectrum Comparison
Figure 16. Overvoltage and Frequency Spectrum @WT#2
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
100
c. Waveforms Comparison at Grid In Case Simple
and Frequency Dependant Model
d. Frequency Spectrum Comparison
Figure 17. Overvoltage And Frequency Spectrum At Grid
@WT#1 @WT#2 @Grid
0
20
40
60
80
100
120
140
160
180
200
Frequancy dependant model
Simple model
28.3kV28.5kV25.6kV25.7kV
186.3kV186.3kV
Voltage(kV)
Node
Figure 18. Overvoltage Peak Comparisons At Each Node Under Different Cases
4.2. Effect of Vertical Ground Rod Modeling:
In this work, each wind turbine is grounded using three vertical rods each rod has a length of (3 m)
with diameter of (2.54 cm). Assuming that the spacing between these rods is large and enough to neglect the
interaction between them. The soil parameters are taken as ρ=100 Ω.m, εr=8 and μr =1 [14]. Figures 19 to 27
show comparison of voltage wave forms and GPR with varying grounding model (constant resistance and
non linear resistance). The results show that the ground model is significant effect on the maximum GPR and
overvoltage peak value. The GPR and overvoltage peak value is low when the soil ionization effect is
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
101
considered (nonlinear resistance model). This can be attributed that when the lightning current through the
grounding rods exceeds the critical value, i.e. Ig=5.5KA, the grounding resistance is decreased where the
current in the grounding rods is high. On the other hand, the maximum value of the GPR is high when using
the constant resistance. This is because that the soil ionization is not considered in this model. Therefore, the
soil ionization effect is an important factor and should be considered for transient studies especially in
lightning study.
a. Waveforms Comparison @WT#1 Under
Different Ground Model
b. Frequency Spectrum Comparison @WT#1 Under
Different Ground Model
Figure 19. Overvoltage and Frequency Spectrum @WT#1
a. Waveforms Comparison @Wt#2 Under Different
Ground Model
b. Frequency Spectrum Comparison @Wt#2 Under
Different Ground Model
Figure 20. Overvoltage and frequency spectrum @WT#2
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
102
a. Waveforms Comparison at Grid Under Different
Ground Model
b. Frequency Spectrum Comparison at Grid Under
Different Ground Model
Figure 21. Overvoltage and Frequency Spectrum At Grid
a. GPR Waveform Comparison @WT#1 under
Different Ground Model
b.Frequency Spectrum Comparison @WT#1 under
Different Ground Model
Figure 22. GPR Waveform and Frequency Spectrum @WT#1
a. Gpr Waveform Comparison @Wt#2 Under
Different Ground Model
b.Frequency spectrum comparison @WT#2 under
different ground model
Figure 23. GPR Waveform and Frequency Spectrum @WT#2
IJAPE ISSN: 2252-8792 
Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah)
103
a. GPR Waveform Comparison At Grid Under
Different Ground Model
b.Frequency Spectrum Comparison At Grid Under
Different Ground Model
Figure 24. GPR Waveform and Frequency Spectrum at Grid
@WT#1 @WT#2 @Grid
0
100
200
300
400
500
Soil ionization
fixed resistance
Voltage(kV)
Node
@WT#1 @WT#2 @Grid
0
100
200
300
400
500
Soil ionization
Fixed resistance
Voltage(kV)
Node
Figure 25. Overvoltage Peak Comparison at Each
Node Under Different Cases
Figure 26. GPR Peak Comparison at Each Node
Under Different Cases
5. CONCLUSION
Validation of surge arrester in LV, MV and HV ABB data sheet using ATP/EMTP has been
investigated. The impact of the Pinceti and Giannettoni surge arrester and winding stray capacitance
transformer model has been carried out. The impact of the soil ionization model has been presented.
Performance of wind farm consisting of two wind turbines has been evaluated under lightning strokes.This
investigation has been carried out in time domain as well as frequency domain using FFT. All components of
the system, under study, are simulated by using ATP/EMTP. The main conclusions obtained from the results
are;
In case of the lightning stroke strikes the blade, cause GPR. The increase of the GPR can conduct
backflow current to the distribution system. It generates overvoltage on the thunderstruck and neighbor
turbines. This can cause damage to the wind farm electrical components.
It is clear that small change in peak value of overvoltages under simple and frequency dependant
model. But from frequency content point of view, it can be seen that the amplitude voltage at different
frequencies when using simple model is higher than that when using frequency dependant model, due to the
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 90 – 104
104
presence of the capacitors in the frequency dependant model. On the other hand, the frequency dependent
model considers very high impedance at high frequencies. Therefore, for a better surge analysis of wind
farm, the capacitance between winding of transformer model must be taken to get accurate transient results.
The nonlinearity behavior of the grounding resistance can be attributed to the decrease in the
grounding resistance within the increase in surge current through it. Therefore, the soil ionization effect is
important and should be considered for transient studies especially lightning study.
REFERENCES
[1] IEC TR 61400-24, "Wind Turbine Generator Systems-Part 24: Lightning Protection", 2002.
[2] Yasuda Y and Funabashi T,‖ Analysis on Back-Flow Surge in Wind Farms.‖ IPST’07, Lyon, France, June 4-7,
2007.
[3] J. C. Das, ―Transients in Electrical Systems, Analysis, Recognition and mitigation", 2nd Edition, John Wiley and
Sons, Inc. 2010.
[4] Jheng-Lun Jiang, Hong-Chan Chang and Cheng-Chien Kuo,‖ Analysis of transient energy affection for wind farm
under lightning,‖ Energy 48 (2012) 292e297. www.elsevier.com/locate/energy
[5] Jheng-Lun Jiang , Hong-Chan Chang , Cheng-Chien Kuo and Cheng-Kai Huang,‖ Transient overvoltage
phenomena on the control system of wind turbines due to lightning strike‖, Renewable Energy 57 (2013) 181-189
[6] Amr M. Abd_Elhady, Nehmdoh A. Sabiha and Mohamed A. Izzularab,‖ Overvoltage Investigation Of Wind Farm
Under Lightning Strokes‖, IET Conference on Renewable Power Generation (RPG, 2011).
[7] T. Hara, and O. Yamamoto, "Modeling of a Transmission Tower for Lightning-surge Analysis", IEE Generation,
Transmission and Distribution, Vol. 143, No. 3, pp. 283-289, 1996.
[8] J. Marti, "Accurate Modeling of Frequency Dependent Transmission Lines in Electromagnetic Transients
Simulation", IEEE Transactions on Power Apparatus and Systems, PAS-101, No.1, pp. 147–157, 1982.
[9] A. Greenwood, "Electrical Transients in Power Systems", 2nd Edition, John Wiley and Sons, Inc. 1991.
[10] IEEE working Group 3.4.11, Application of Surge Protective Devices Subcommittee Surge Protective Devices
Committee, "Modeling of Metal Oxide Surge Arresters", IEEE Transactions on Power Delivery, Vol. 7, No. 1, pp.
302-309, January 1992.
[11] P. Pinceti and M. Giannettoni, "A Simplified Model for Zinc Oxide Surge Arresters", IEEE Transactions on Power
Delivery, Vol. 14, No. 2, PP. 393-398, April 1999.
[12] M. agro, M. Giannettoni and P. Pinceti, "Validation of ZnO Surge Arresters Model for Overvoltage Studies", IEEE
Transactions Power Delivery, Vol. 19, No. 4, PP. 1692-1695, October 2004.
[13] Nehmdoh A. Sabiha and Matti Lehtonen, ―Lightning-Induced Overvoltages Transmitted Over Distribution
Transformer With MV Spark-Gap Operation—Part II: Mitigation Using LV Surge Arrester‖ IEEE
TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010
[14] Surge Arresters, Datasheet, www.abb.com/arrestersonline.
[15] Amr M. Abd-Elhady, Nehmdoh A. Sabiha and Mohamed A. Izzularab” Evaluation of Different Grounding
Models for Studying Backflow Current-Overvoltages in Wind Farm” International Middle East Power Systems
Conference (MEPCON’12) 23-25 December 2012, Cairo, Egypt.
[16] ANSI/IEEE Std 80-1986‖ AC SUBSTATION GROUNDING‖

More Related Content

What's hot

MATLAB Simulink for single phase PWM inverter in an uninterrupted power supply
MATLAB Simulink for single phase PWM inverter in an  uninterrupted power supplyMATLAB Simulink for single phase PWM inverter in an  uninterrupted power supply
MATLAB Simulink for single phase PWM inverter in an uninterrupted power supplyIJMER
 
Lecture 04 transformers
Lecture 04   transformersLecture 04   transformers
Lecture 04 transformersBibek Chouhan
 
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student ManualPower Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student Manualphase3-120A
 
Pocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsPocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsSuresh Kumar
 
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student ManualPower Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student Manualphase3-120A
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distributionrmkceteee
 
Power Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student ManualPower Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student Manualphase3-120A
 
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly Areas
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly AreasSag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly Areas
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly AreasIJCSIS Research Publications
 
Transformers
TransformersTransformers
Transformersrsamurti
 
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student ManualPower Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student Manualphase3-120A
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Gilberto Mejía
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manualphase3-120A
 
153010010 mohammad babor
153010010  mohammad  babor153010010  mohammad  babor
153010010 mohammad baborBabor10
 
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student ManualPower Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student Manualphase3-120A
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manualphase3-120A
 
Mc caster symposium on iron mills scribd
Mc caster symposium on iron mills   scribdMc caster symposium on iron mills   scribd
Mc caster symposium on iron mills scribdAMI GE International
 
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...IJERA Editor
 

What's hot (20)

Transformers
TransformersTransformers
Transformers
 
MATLAB Simulink for single phase PWM inverter in an uninterrupted power supply
MATLAB Simulink for single phase PWM inverter in an  uninterrupted power supplyMATLAB Simulink for single phase PWM inverter in an  uninterrupted power supply
MATLAB Simulink for single phase PWM inverter in an uninterrupted power supply
 
Lecture 04 transformers
Lecture 04   transformersLecture 04   transformers
Lecture 04 transformers
 
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student ManualPower Circuits and Transforers-Unit 3 Labvolt Student Manual
Power Circuits and Transforers-Unit 3 Labvolt Student Manual
 
Pocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systemsPocket book on energy efficiency in elec systems
Pocket book on energy efficiency in elec systems
 
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student ManualPower Circuits and Transformers-Unit 2 Labvolt Student Manual
Power Circuits and Transformers-Unit 2 Labvolt Student Manual
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
 
Power Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student ManualPower Circuits and Transformers-Unit 4 Labvolt Student Manual
Power Circuits and Transformers-Unit 4 Labvolt Student Manual
 
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly Areas
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly AreasSag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly Areas
Sag-Tension Analysis of AAAC Overhead Transmission Lines for Hilly Areas
 
Transformers
TransformersTransformers
Transformers
 
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student ManualPower Circuits and Transforers-Unit 7 Labvolt Student Manual
Power Circuits and Transforers-Unit 7 Labvolt Student Manual
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
 
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student ManualPower Circuits and Transforers-Unit 5 Labvolt Student Manual
Power Circuits and Transforers-Unit 5 Labvolt Student Manual
 
153010010 mohammad babor
153010010  mohammad  babor153010010  mohammad  babor
153010010 mohammad babor
 
M045037985
M045037985M045037985
M045037985
 
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student ManualPower Circuits and Transforers-Unit 8 Labvolt Student Manual
Power Circuits and Transforers-Unit 8 Labvolt Student Manual
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
 
Mc caster symposium on iron mills scribd
Mc caster symposium on iron mills   scribdMc caster symposium on iron mills   scribd
Mc caster symposium on iron mills scribd
 
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
Reactive Power Compensation and Control via Shunt Reactors and Under Ground P...
 
RGPV BE 104 Unit II
RGPV BE 104 Unit IIRGPV BE 104 Unit II
RGPV BE 104 Unit II
 

Similar to Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Under Transient Conditions

journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...IJERD Editor
 
Modeling of Wind Energy on Isolated Area
Modeling of Wind Energy on Isolated AreaModeling of Wind Energy on Isolated Area
Modeling of Wind Energy on Isolated AreaIJPEDS-IAES
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Bérengère VIGNAUX
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...IJPEDS-IAES
 
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsAnalysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsIJMER
 
Wind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyWind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyCSCJournals
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...eeiej_journal
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadIAEME Publication
 
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET Journal
 
Renewable Energy Harvesting Using SuperCapacitor
Renewable Energy Harvesting Using SuperCapacitorRenewable Energy Harvesting Using SuperCapacitor
Renewable Energy Harvesting Using SuperCapacitorIRJET Journal
 
Analysis characteristics of power PV cells and wind turbine from power genera...
Analysis characteristics of power PV cells and wind turbine from power genera...Analysis characteristics of power PV cells and wind turbine from power genera...
Analysis characteristics of power PV cells and wind turbine from power genera...IOSR Journals
 
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...IRJET Journal
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?Fang Sam
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...ecij
 
Wind turbine doubly-fed induction generator defects diagnosis under voltage dips
Wind turbine doubly-fed induction generator defects diagnosis under voltage dipsWind turbine doubly-fed induction generator defects diagnosis under voltage dips
Wind turbine doubly-fed induction generator defects diagnosis under voltage dipsTELKOMNIKA JOURNAL
 
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...IRJET Journal
 
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET Journal
 
Wind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaWind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaIAEME Publication
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Projectsagnikchoudhury
 
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...IJPEDS-IAES
 

Similar to Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Under Transient Conditions (20)

journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...journal publishing, how to publish research paper, Call For research paper, i...
journal publishing, how to publish research paper, Call For research paper, i...
 
Modeling of Wind Energy on Isolated Area
Modeling of Wind Energy on Isolated AreaModeling of Wind Energy on Isolated Area
Modeling of Wind Energy on Isolated Area
 
Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks Ferroresonance Conditions in Wind Parks
Ferroresonance Conditions in Wind Parks
 
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
Proposed PV Transformer-Less Inverter Topology Technique for Leakage Current ...
 
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsAnalysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
 
Wind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison StudyWind-Driven SEIG Systems: A Comparison Study
Wind-Driven SEIG Systems: A Comparison Study
 
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
TCSC AND SVC OPTIMAL LOCATION TO IMPROVE THE PERFORMANCE OF POWER SYSTEM WITH...
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable load
 
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
 
Renewable Energy Harvesting Using SuperCapacitor
Renewable Energy Harvesting Using SuperCapacitorRenewable Energy Harvesting Using SuperCapacitor
Renewable Energy Harvesting Using SuperCapacitor
 
Analysis characteristics of power PV cells and wind turbine from power genera...
Analysis characteristics of power PV cells and wind turbine from power genera...Analysis characteristics of power PV cells and wind turbine from power genera...
Analysis characteristics of power PV cells and wind turbine from power genera...
 
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...
IRJET- Transmission of Ac Power from Offshore to Onshore by using Low Frequen...
 
How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?How to conduct the lightning impulse withstand test on 550kv GIS?
How to conduct the lightning impulse withstand test on 550kv GIS?
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
 
Wind turbine doubly-fed induction generator defects diagnosis under voltage dips
Wind turbine doubly-fed induction generator defects diagnosis under voltage dipsWind turbine doubly-fed induction generator defects diagnosis under voltage dips
Wind turbine doubly-fed induction generator defects diagnosis under voltage dips
 
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...
Power factor and Quality improvement of Wind based system with Fuzzy Logic Co...
 
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOMIRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
IRJET- Improved IUPQC Controller to Provide Grid Voltage as a STATCOM
 
Wind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaWind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power qua
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Project
 
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
Power Quality Improvement Using Custom Power Devices in Squirrel Cage Inducti...
 

More from IJAPEJOURNAL

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...IJAPEJOURNAL
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterIJAPEJOURNAL
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointIJAPEJOURNAL
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineIJAPEJOURNAL
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceIJAPEJOURNAL
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingIJAPEJOURNAL
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...IJAPEJOURNAL
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...IJAPEJOURNAL
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...IJAPEJOURNAL
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...IJAPEJOURNAL
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsIJAPEJOURNAL
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanIJAPEJOURNAL
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationIJAPEJOURNAL
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...IJAPEJOURNAL
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...IJAPEJOURNAL
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...IJAPEJOURNAL
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsIJAPEJOURNAL
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeIJAPEJOURNAL
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsIJAPEJOURNAL
 
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...IJAPEJOURNAL
 

More from IJAPEJOURNAL (20)

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman Filter
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation Point
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC Motors
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in Pakistan
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based Application
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic Applications
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation Scheme
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
 

Recently uploaded

Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 

Recently uploaded (20)

Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 

Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Under Transient Conditions

  • 1. International Journal of Applied Power Engineering (IJAPE) Vol. 3, No. 2, August 2014, pp. 90~104 ISSN: 2252-8792  90 Journal homepage: http://iaesjournal.com/online/index.php/IJAPE Towards an Accurate Modeling of Frequency-Dependent Wind Farm Components under Transient Conditions M. A. Abd-Allah, Mahmoud N. Ali, A. Said Faculty of Engineering at Shoubra, Benha University, Egypt Article Info ABSTRACT Article history: Received Mar 2, 2014 Revised Jul 10, 2014 Accepted Jul 23, 2014 Frequency dependence complete model is set up for describing the lightning transient behavior of the wind turbines (WTs).To get an appropriate wind turbine model, a high frequency models of surge arrester protecting the boost transformer, transformer and ground electrode soil ionization are implemented. The transient responses and Ground Potential Rise (GPR) can be obtained at different locations in the WTs and connected grid in the time domain as well as in the frequency domain using Fast Fourier Transform (FFT). To check the validity of the model, Surge arresters protection level at different locations, at i.e. LV, MV and HV, is compared with ABB manufacture data sheet, Also a comparison has been made between simple and frequency dependence model of overall wind farm components using ATP/EMTP. This paper provides an accurate simulation of wind farm components under transient condition. Keyword: ATP/EMTP FFT GPR Surge arrester model Transient response WTs Copyright © 2014 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: M. A. Abd-Allah, Faculty of Engineering at Shoubra, Benha University, Egypt. Email: abdelrahman.ghoniem@feng.bu.edu.eg 1. INTRODUCTION With a rapid growth in wind power generation, lightning hazard to wind turbines (WTs) has come to be regarded with more attention. Due to their great height, distinctive shape, and exposed location, WTs are extremely vulnerable to lightning stroke. After a WT is struck by lightning, high lightning current flows through the WT and causes considerable damage to electrical equipment inside the WT structure and wind turbine nacelle results stop of the generator operation and probably expensive repairs [1]. In order to decrease downtime, repairs and blade damaged. Protecting the blade is very important and well-designed lightning protection is a necessity for this equipment so Modern wind turbine blades are made of insulating materials such as glass fibre reinforced plastic (GFRP) as a common material or wood epoxy. The lightning protection of wind turbine blades can be classified as receptor, metallic cap, mesh wire, and metallic conductor as reported in IEC-61400-24 standards. In general, the problem of lightning protection of wind turbine blades is to conduct the lightning current safely from the attachment point on the blade to the hub and then to the ground. However another serious problem known as "back-flow surge" which not only causes damages to the wind turbine that has been struck but also the other turbines that have not. The back-flow surge phenomenon has been defined as the surge flowing from a customer’s structure such as a communication tower into the distribution line. High resistivity soil often makes Surge Arresters (SAs) at tower earthing systems operate in reverse and allow backflow of surge current to the grid. The phenomenon of surge invasion from a wind turbine that is struck by lightning to the distribution line in a wind farm is quite similar to the case of ―back-flow surge‖ [2]. Due to significant influence on the wind farm behavior under lightning, the transient response must be either accurately measured which very expensive and time consuming or reliably predicated by simulations which allowing for parametric studies and optimization. Up till now the predominant approach
  • 2. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 91 for simulating transient due to lightning is based on the representation of the wind farm components by their equivalent circuits. Performance of wind farm under lightning requires accurate modeling of its components. So in this paper wind farm is implemented using high frequency models components as SA, Transformer and ground electrode to integrally describe this lightning current path. Validation of these models and computation, characteristics and hazards of back-flow surge in wind farm are analyzed using onshore wind farm as an example. 2. DESCRIPTION OF THE INVESTIGATED ONSHORE WIND FARM: Figure1. Shows layout of onshore wind farm composed of two identical wind power generators. Boost transformers for the generators are installed in vicinity of the wind turbine towers. All boost transformers are connected to the grid via grid-interactive transformer by overhead distribution line. Surge arresters are inserted to the primary and secondary sides of the boost and grid-interactive transformers. Figure 1.Wind farm model [2] 3. MODELING OF THE ELECTRIC COMPONENTS OF THE ONSHORE WIND FARM USING ATP/EMTP: In this section, the detailed high frequency modeling of the electric components of the onshore wind farm using the ATP/EMTP is demonstrated. These components include Transmission line (TL), transformers, power system grid and surge arresters. 3.1. Lightning Model: In order to simulate the impact of lightning current on power system or its components with convenience, the lightning current in the mode of mathematical function is usually represented. After the long-term speculation and research by many researchers, the approximate mathematical function was proposed. A current function model called Heidler is now used widely [3, 4, 5]. A 400 Ω lightning path resistance was parallelly connected to simulate natural lightning. Equation (1) represent the lightning current, waveform of 51kA-2/631μs is used in this study as shown in Figure 2. The waveform of Heidler lightning current is simulated by ATP/EMTP software. 2/ 2 1 2 1 ]1)/[( )/( )(    t o e t t Iti    (1) Where I0: the peak of current τ1, τ2: time constants of current rising and dropping
  • 3.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 92 Figure 2. The Waveform of 51ka - 2/631μs Lightning Current 3.2. Wind Turbine Generator: Table 1 gives the required data for modeling the generators of the wind turbines, transmission line and transformers. Table 1 a, b, c. Wind Turbines, Transformers Data and connected line data [2] Wind Turbine Model(Synchronous Generator- Y connected) Voltage (line rms) 0.660 [kV] Rated power 1.0 [MVA] Leakage reactance 0.1 [H] Frequency 60.0 [Hz] Transformer Model (Boost, Grid-Interactive) Connection method Y / Δ , Y / Δ Voltage (line rms) 0.660/6.6 [kV], 66.0/6.6 [kV] Rated power 1.0 [MVA], 10.0 [MVA] Leakage reactance 0.15 [p.u] Copper losses 0.005 [p.u] No-load losses neglected Line Model (values at 60 Hz) positive / zero phase resistance [Ω/Km] 0.00105/0.021 Positive / zero phase inductance [mH/Km] 0.83556/2.50067 Positive / zero phase capacitance [nF/Km] 12.9445/6.4723 3.3. Wind Turbine Blades and Towers: The down conductor in the blade and the wind turbine tower have been considered as a lossless transmission line and they were estimated according to following experimental equation [4, 5, 6, 7], where the down conductor and the tower often were treated as a cylindrical conductor. Equation (2) represents the characteristic impedance of tower and the blade. (f ile modelwind11.pl4; x-v ar t) c:XX0007-X0081A 0.0 0.2 0.4 0.6 0.8 1.0 1.2[ms] 0 10 20 30 40 50 60 [kA]
  • 4. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 93 )2 22 (ln60  h r Z (2) Where, Z is the surge impedance, r and h are the cylinder radius and height, respectively. The wind tower is taken as an iron vertical conductor of 60 m height and 3.0 m radius. 3.4. Transmission Lines and cables: The overhead lines are considered and represented by single-phase positive wave impedance (i.e. Surge impedance) with the light velocity.  CL/Z0 (3) sm LC v / 1  (4) Where, C and L are the capacitance and inductance of line, respectively, Z0 is the surge impedance and v is the propagation velocity [3, 8]. 3.5. Transformer: In order to study the transient involving frequencies up to a few kHz, stray capacitance of transformer coils must be added to the transformer model. Capacitances are actually distributed, but lumped parameters at the winding terminals for the total capacitance can be used with reasonable accuracy in this case [3, 8, 9]. However, the transformer capacitances are often difficult to be determined. Transformer capacitance is represented by CH, CL and CHL as shown in Figure 3 Where, CH is the capacitance of high winding to ground, CL is the capacitance of low winding to ground and CHL is the capacitance between high and low windings. Normally the CL and CHL are greater than CH. This is because the fact that the high voltage calls for more separation between windings and between windings and core. The present work considers these capacitances as in a table 2 [3]. Figure 3. High Frequency Transformer Model. Table 2. Typical Capacitance of Transformers (Capacitance in nF) [3] Transformer Core Type MVA CH CHL CL 1 1.2-14 1.2-17 3.1-16 2 1.4-16 1-18 3-16 5 1.2-14 1.1-20 5.5-17 7 2.7-11 3.5-17 8-16 10 4-7 4-11 8-18 25 2.8-4.2 2.5-18 5.2-20
  • 5.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 94 3.6. Surge Arrester: Surge arrester devices play an important role for mitigating the overvoltage due to lightning, switching. Under both normal and abnormal conditions, the arrester handles its operation based on its nonlinearity, i.e. V-I characteristics [9]. A simplified model was derived from IEEE model [10, 11]. The model circuit is shown in Figure 4. This model is composed by two sections of nonlinear resistances usually designated by A0 and A1 which are separated by inductance L1 and L0. A parallel resistance Rp (about 1 MΩ) is added to avoid the numerical instability of the combination of the current source and nonlinear elements. This model has the same operating principles as the IEEE model. The main advantage of this model is that the parameters were determined using only the electrical data and did not take into consideration any physical characteristics of the surge arrester [12]. Figure 4. Pinceti and Giannettoni model In case medium and high voltage levels the inductances L1 and L0 in the model are in μH and calculated using: Un Ur UrTUr L 20/8 20/82/1 4 1 1   (5) (6) In case low voltage levels the inductances L1 and L0 in the model are in μH and calculated using: L1=0.03 Un (7) L0=0.01 Un (8) Where UN is the arrester rated voltage in kV, Ur1/T2 is the residual voltage at 10 kA fast front current surge (1/T2 μs). Ur8/20 is the residual voltage at 10 kA current surge with 8/20 μs time parameters. The nonlinear characteristics of the two elements A0 and A1 are based on the pu data published in [13] and the corresponding nonlinear characteristics of A0 and A1 are shown in Figure 6. a. A0 non-linear characteristics. b. A1 non-linear characteristic. Figure 6. Surge Arrester Elements Nonlinear Characteristics. 0.0 5.0 10.0 15.0 20.0 I [kA]0.9 1.0 1.1 1.3 1.4 U [kV] 0.0 5.0 10.0 15.0 20.0 I [kA]0.7 0.8 0.9 1.1 1.2 U [kV] Un Ur UrTUr L 20/8 20/82/1 12 1 0  
  • 6. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 95 The surge arrester model is simulated and tested using ATP/EMTP circuit shown in Figure 7. Figure 7. ATP/EMTP Circuit for Surge Arrester. The arrester model is tested to match the manufacture's data sheet [14] under switching and lightning characteristics. 440kV SA with L1 and L0 are equal 0.07μH [6] used in low voltage side boast transformer. A discharge current 8/20 μs, 5 kA and 25 kA for nominal and maximum conditions respectively are injected to the surge arrester. The error of residual voltage rather than the manufactured data is found 0.22% at the nominal discharge current and -1.7% at the maximum discharge current. This error is computed as (Ups-Up)/Up, where Ups is simulated residual voltage (the simulated voltage protection level). The injected current, the residual voltage and the absorbed energy are as shown in Figures 8 and 9 for nominal and maximum discharge currents, respectively. a. Injected current (nominal discharge current). b. Residual voltage. Figure 8. Injected nominal and maximum discharge current and resuidual voltage. Figure 9. Absorbed Energy under Injected Nominal and Maximum Discharge Current. 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 x 10 -4 0 0.5 1 1.5 2 2.5 x 10 4 Time (sec) Current(A) Nominal discharge current Maxmum discharge current 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 x 10 -4 0 500 1000 1500 2000 2500 Time (sec) Voltage(V) Residual voltage (nominal current) Residual voltage (Maxmum current) ABB manufacture data sheet 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 x 10 -4 0 200 400 600 800 1000 1200 1400 Time (sec) SAconsumptionenergy(J) SA energy (maxmum current) SA energy (nominal current)
  • 7.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 96 The MV surge arrester protecting boost transformer with L1 and L0 are 0.0952 μH and 0.286 μH respectively [6].from test as shown in Figure 10 find errors within acceptable limits 0 2 4 6 8 10 12 14 16 18 20 22 500A 30/60us 125A 30/60us 20kA 8/20us 10kA 8/20us 5kA 8/20us 2.5kA 8/20us 1kA 8/20us 10kA 1/2us 5kA 1/2us Residual voltage(data sheet) Residual voltage (simulation) Error% Impulse current Protectionlevel(kV) 0 10 20 30 40 Error% Figure 10. MVSA Validation The HV surge arrester protecting grid transformer with L1 and L0 are 1.62μH and 0.54μH respectively. From test as shown in Figure 11 find errors within acceptable limits 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 2000A 30/60us 100A 30/60us 500A 30/60us 20kA 8/20us 10kA 8/20us 5kA 8/20us manufactur data simulated Error% Impulse current Protectionlevel(kV) 0 5 10 15 20 25 30 35 40 Error% Figure 11. HVSA Validation 3.7. Vertical ground rod modeling: Grounding systems behavior is well understood at power frequency. However, during lightning strokes the grounding systems performance might be different. The waveform of the lightning current has a major influence on the dynamic performance of ground electrodes. While high lightning current intensity improves the dynamic grounding performance due to ionization of the soil. In case of high lightning currents the electric field at the ground electrodes might become larger than the electric strength of the soil. Which can cause breakdown and sparks discharge in the soil. This phenomenon improves the grounding system
  • 8. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 97 performance so its ignoring always gives inaccurate results. On the other hand, due to the frequency dependent phenomena, the grounding performance might be much worse during fast front lightning current pulses. This can deteriorate the efficiency of the protection. Grounding system of a wind turbine plays a critical role, since overvoltages caused by lightning strikes and other faults has to be successfully dispersed into the ground. So, it is important to get an accurate model of the wind turbine grounding system. In this paper the behavior of the wind turbine under lightning strikes has been studied using two different models for the grounding resistance [15]. The first model is the linear model of grounding resistance which is based on a constant value for the grounding resistance i.e. low voltage, low frequency [16]. The constant resistance Ro of the model is estimated in ohm based on the rod dimensions and the soil parameters [15]: }1 4 {ln 20  a l l R   (9) Where, ρ is the soil resistivity (Ω.m), L is the electrode length (m) and a is the electrode radius (m). The other model is based on the nonlinear performance of the grounding resistance with high currents i.e. high voltage, high frequency [16]. The nonlinearity nature of the ground resistance can be represented by a nonlinear resistance, RT, whose value is given as [15];            )( 1 )( 0 0 IgiFor Ig i R Rt IgiForRRt  (10) Where, i is the current through the rod (kA), and Ig is the critical current for soil ionization (kA) which is given by: 2 0 0 2 R E Ig    (11) Where, E0 is the critical soil ionization gradient. 4. MODEL VALIDATION: In this study, the wind power generator modeled as a synchronous machine for simplicity. The grounding model at each wind tower is simulated as three separated ground electrodes, where each electrode simulated as 10 Ω resistance. There is no connection between the grounding systems for wind turbines. The distribution line is assumed as overhead line and simulated as transposed distributed line parameters. The lightning stroke is taken as striking wind turbine (WT#1) as shown in Figure 12. Figure 12. Lightning hit WT#1 [3]
  • 9.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 98 4.1. Effect Of Frequency Dependant Surge Arrester and Transformers Model on Back Flow Current Overvoltages: In this work, The backflow current-overvoltages is evaluated using different transformer and surge arrester models in the time domain as well as frequency domain using Fast Fourier Transform (FFT) considering onshore wind farm. Case#1 Simple model of SA consists of only one non linear element with characteristics and Power frequency transformer model as shown in figure 13. Figure 13. Atpdraw Circuit of Two Wind Turbines with Simple Model Case#2 frequency dependent transformer model and frequency dependent model of SA is a combination of non linear elements and linear inductances which provides dynamic behavior during lightning. The SAs are used at low, medium and high voltage levels in the wind farm as shown in figure 14. Figure 14: Atpdraw Circuit of Two Wind Turbines with Freq. Dependant Model Figures 15 to 18 show the voltage waveforms, peak value, and frequency spectrum oscillation comparison at different locations of the wind farm. In different two cases, i.e. Simple and frequency dependent model, It is observed that the peak magnitude of the generated overvoltage at WT#1 generator terminal reach to 200kV, at (WT#1) boost transformer secondary side reach to 186kV, at (WT#2) boost
  • 10. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 99 transformer secondary side reach to 25kV and at grid reach to 28kV in different models. It is clear that small change in peak value of overvoltages under simple and frequency dependant model. But from frequency content point of view, it can be seen that the amplitude voltage at different frequencies when using simple model is higher than that when using frequency dependant model. This can be attributed to the fact that the reflecting traveling waves at junction of the boost transformer of WT#2 and at the junction of the grid- interactive transformer are decreased due to the presence of the capacitors in the frequency dependant model. On the other hand, the frequency dependent model considers very high impedance at high frequencies. Therefore, for a better surge analysis of wind farm, the capacitance between winding of transformer model must be taken to get accurate transient results. A. Waveforms Comparison @Wt#1 In Case Simple and Frequency Dependant Model B. Frequency Spectrum Comparison Figure 15. Overvoltages and Frequency Spectrum @WT#1 c. Waveforms Comparison @WT#2 In Case Simple And Frequency Dependant Model d. Frequency Spectrum Comparison Figure 16. Overvoltage and Frequency Spectrum @WT#2
  • 11.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 100 c. Waveforms Comparison at Grid In Case Simple and Frequency Dependant Model d. Frequency Spectrum Comparison Figure 17. Overvoltage And Frequency Spectrum At Grid @WT#1 @WT#2 @Grid 0 20 40 60 80 100 120 140 160 180 200 Frequancy dependant model Simple model 28.3kV28.5kV25.6kV25.7kV 186.3kV186.3kV Voltage(kV) Node Figure 18. Overvoltage Peak Comparisons At Each Node Under Different Cases 4.2. Effect of Vertical Ground Rod Modeling: In this work, each wind turbine is grounded using three vertical rods each rod has a length of (3 m) with diameter of (2.54 cm). Assuming that the spacing between these rods is large and enough to neglect the interaction between them. The soil parameters are taken as ρ=100 Ω.m, εr=8 and μr =1 [14]. Figures 19 to 27 show comparison of voltage wave forms and GPR with varying grounding model (constant resistance and non linear resistance). The results show that the ground model is significant effect on the maximum GPR and overvoltage peak value. The GPR and overvoltage peak value is low when the soil ionization effect is
  • 12. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 101 considered (nonlinear resistance model). This can be attributed that when the lightning current through the grounding rods exceeds the critical value, i.e. Ig=5.5KA, the grounding resistance is decreased where the current in the grounding rods is high. On the other hand, the maximum value of the GPR is high when using the constant resistance. This is because that the soil ionization is not considered in this model. Therefore, the soil ionization effect is an important factor and should be considered for transient studies especially in lightning study. a. Waveforms Comparison @WT#1 Under Different Ground Model b. Frequency Spectrum Comparison @WT#1 Under Different Ground Model Figure 19. Overvoltage and Frequency Spectrum @WT#1 a. Waveforms Comparison @Wt#2 Under Different Ground Model b. Frequency Spectrum Comparison @Wt#2 Under Different Ground Model Figure 20. Overvoltage and frequency spectrum @WT#2
  • 13.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 102 a. Waveforms Comparison at Grid Under Different Ground Model b. Frequency Spectrum Comparison at Grid Under Different Ground Model Figure 21. Overvoltage and Frequency Spectrum At Grid a. GPR Waveform Comparison @WT#1 under Different Ground Model b.Frequency Spectrum Comparison @WT#1 under Different Ground Model Figure 22. GPR Waveform and Frequency Spectrum @WT#1 a. Gpr Waveform Comparison @Wt#2 Under Different Ground Model b.Frequency spectrum comparison @WT#2 under different ground model Figure 23. GPR Waveform and Frequency Spectrum @WT#2
  • 14. IJAPE ISSN: 2252-8792  Towards an Accurate Modeling of Frequecy-Dependent Wind Farm Components Under… (M. A. Abd-Allah) 103 a. GPR Waveform Comparison At Grid Under Different Ground Model b.Frequency Spectrum Comparison At Grid Under Different Ground Model Figure 24. GPR Waveform and Frequency Spectrum at Grid @WT#1 @WT#2 @Grid 0 100 200 300 400 500 Soil ionization fixed resistance Voltage(kV) Node @WT#1 @WT#2 @Grid 0 100 200 300 400 500 Soil ionization Fixed resistance Voltage(kV) Node Figure 25. Overvoltage Peak Comparison at Each Node Under Different Cases Figure 26. GPR Peak Comparison at Each Node Under Different Cases 5. CONCLUSION Validation of surge arrester in LV, MV and HV ABB data sheet using ATP/EMTP has been investigated. The impact of the Pinceti and Giannettoni surge arrester and winding stray capacitance transformer model has been carried out. The impact of the soil ionization model has been presented. Performance of wind farm consisting of two wind turbines has been evaluated under lightning strokes.This investigation has been carried out in time domain as well as frequency domain using FFT. All components of the system, under study, are simulated by using ATP/EMTP. The main conclusions obtained from the results are; In case of the lightning stroke strikes the blade, cause GPR. The increase of the GPR can conduct backflow current to the distribution system. It generates overvoltage on the thunderstruck and neighbor turbines. This can cause damage to the wind farm electrical components. It is clear that small change in peak value of overvoltages under simple and frequency dependant model. But from frequency content point of view, it can be seen that the amplitude voltage at different frequencies when using simple model is higher than that when using frequency dependant model, due to the
  • 15.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 90 – 104 104 presence of the capacitors in the frequency dependant model. On the other hand, the frequency dependent model considers very high impedance at high frequencies. Therefore, for a better surge analysis of wind farm, the capacitance between winding of transformer model must be taken to get accurate transient results. The nonlinearity behavior of the grounding resistance can be attributed to the decrease in the grounding resistance within the increase in surge current through it. Therefore, the soil ionization effect is important and should be considered for transient studies especially lightning study. REFERENCES [1] IEC TR 61400-24, "Wind Turbine Generator Systems-Part 24: Lightning Protection", 2002. [2] Yasuda Y and Funabashi T,‖ Analysis on Back-Flow Surge in Wind Farms.‖ IPST’07, Lyon, France, June 4-7, 2007. [3] J. C. Das, ―Transients in Electrical Systems, Analysis, Recognition and mitigation", 2nd Edition, John Wiley and Sons, Inc. 2010. [4] Jheng-Lun Jiang, Hong-Chan Chang and Cheng-Chien Kuo,‖ Analysis of transient energy affection for wind farm under lightning,‖ Energy 48 (2012) 292e297. www.elsevier.com/locate/energy [5] Jheng-Lun Jiang , Hong-Chan Chang , Cheng-Chien Kuo and Cheng-Kai Huang,‖ Transient overvoltage phenomena on the control system of wind turbines due to lightning strike‖, Renewable Energy 57 (2013) 181-189 [6] Amr M. Abd_Elhady, Nehmdoh A. Sabiha and Mohamed A. Izzularab,‖ Overvoltage Investigation Of Wind Farm Under Lightning Strokes‖, IET Conference on Renewable Power Generation (RPG, 2011). [7] T. Hara, and O. Yamamoto, "Modeling of a Transmission Tower for Lightning-surge Analysis", IEE Generation, Transmission and Distribution, Vol. 143, No. 3, pp. 283-289, 1996. [8] J. Marti, "Accurate Modeling of Frequency Dependent Transmission Lines in Electromagnetic Transients Simulation", IEEE Transactions on Power Apparatus and Systems, PAS-101, No.1, pp. 147–157, 1982. [9] A. Greenwood, "Electrical Transients in Power Systems", 2nd Edition, John Wiley and Sons, Inc. 1991. [10] IEEE working Group 3.4.11, Application of Surge Protective Devices Subcommittee Surge Protective Devices Committee, "Modeling of Metal Oxide Surge Arresters", IEEE Transactions on Power Delivery, Vol. 7, No. 1, pp. 302-309, January 1992. [11] P. Pinceti and M. Giannettoni, "A Simplified Model for Zinc Oxide Surge Arresters", IEEE Transactions on Power Delivery, Vol. 14, No. 2, PP. 393-398, April 1999. [12] M. agro, M. Giannettoni and P. Pinceti, "Validation of ZnO Surge Arresters Model for Overvoltage Studies", IEEE Transactions Power Delivery, Vol. 19, No. 4, PP. 1692-1695, October 2004. [13] Nehmdoh A. Sabiha and Matti Lehtonen, ―Lightning-Induced Overvoltages Transmitted Over Distribution Transformer With MV Spark-Gap Operation—Part II: Mitigation Using LV Surge Arrester‖ IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 4, OCTOBER 2010 [14] Surge Arresters, Datasheet, www.abb.com/arrestersonline. [15] Amr M. Abd-Elhady, Nehmdoh A. Sabiha and Mohamed A. Izzularab” Evaluation of Different Grounding Models for Studying Backflow Current-Overvoltages in Wind Farm” International Middle East Power Systems Conference (MEPCON’12) 23-25 December 2012, Cairo, Egypt. [16] ANSI/IEEE Std 80-1986‖ AC SUBSTATION GROUNDING‖