Understanding
Overcurrent Circuit
Protectors
Carl E.Lindquist
VP New Product Development
San-O Industrial Corporation
SOCÂŽ
Introduction to Overcurrent
Circuit Protectors
Overcurrent (Series)
vs.
Overvoltage (Shunt)
Type Protectors
We will be limiting our discussion to
Overcurrent (Series) Type Protectors
Current Cutoffs
vs.
Current Limiters
• Current Cutoff Protectors reduce current in
the circuit to zero.
• Current Limiting Protectors reduce current in
the circuit to some “acceptable” safe level.
Types of Overcurrent Protectors
• Current Cutoffs
Fuses
Circuit Breakers
• Current Limiters
Polymer Positive Temperature Coefficient (PPTC’s)
Ceramic Positive Temperature Coefficient (CPTC’s)
Line Feed Resistors (LFR’s)
Electronic Current Limiters (ECL’s)
Current Cutoffs
• Circuit Breakers
Fully resettable
Thermal vs. Magnetic vs. Thermal-Magnetic
Interrupting current at rated voltage is not the same as for a
fuse.
Never intended for use as a switch unless specifically noted
• Fuses
“Weak Links” and are not resettable.
Element vs. Thin/Thick Film
Provide the highest current and voltage ratings in smallest
space
Thermal Circuit Breaker
• Low cost
• Poor Precision
• Slow Acting
• Trip current is
significantly affected by
ambient temperature
• Complex mechanism
• Relatively large package
Outline of thermal circuit breaker.
(Courtesy Square D Co.)
Magnetic Breaker Operation
Small magnetic circuit breaker.
(Courtesy Airpax)
Magnetic Breaker Detail
• Magnetic breakers without
slowing mechanism will operate
in a few milliseconds.
Very precise
Very fast
Very sensitive to low overcurrent
Not greatly affected by ambient temperature
Relatively expensive
• The standard method of slowing
the operation at low overload
currents is use of a viscous fluid
in a dashpot.
Some loss of precision
Slow acting at low level overloads
Viscosity of fluid will be affected by temperature
• Heavy overload currents will
cause instantaneous operation.
(Hence, “instantaneous trip”
rating)
Thermal-Magnetic Breaker
• Thermal-Magnetic breakers are hybrids of the
two previously discussed devices.
• These breakers act as a thermal breaker for
low level overloads and act as magnetic
breaker for instantaneous trip at high level
current faults
• Most standard house service entrance
breakers are thermal-magnetic.
Current Limiters
• PTC’s
Resettable Passive Devices
Both Polymer and Ceramic are somewhat ambient temperature
sensitive for tripping point.
Some “drift” in nominal limiting after first reset
• LFR’s
Resettable Passive Devices
Usually limited to telecommunications
These devices can completely open the circuit if fault is heavy enough
or long term low level overload.
• ECL’s
Resettable Active Devices
Speed of operation can be adjusted
Can be made very precise
Some limitations on maximum voltage levels
Protector Selection
• Agency Approvals
• Physical Area Available
• Required Nominal Continuous Current Level
• Clearing Time
• Surge Withstand Requirements (Inrush, Lightning, etc.)
• Maximum Interrupting Current at Rated Voltage
• Open Circuit Voltage (AC, DC or Both)
• Single Event vs. Resettable
Ease of Replacement
Effect of Nuisance Operation
Long Term Availability of Replacements
• Environmental Parameters
Temperature Range (Room Temperature vs. Microclimate)
Humidity
Mechanical shock
Hazardous Environments (Corrosive, Explosive, etc.)
• High Reliability Applications
Medical
Military
Aerospace
Telecommunications
Agency Approvals
• North America
UL / CSA
Listing / Certified vs. Recognition
• European (IEC 60127)
SEMKO
DEMKO
BSI
• Japanese
<PS>E JET
IEC vs. North American
Fuses
• IEC Fuses are typically employed in 250 Vac applications.
• UL/CSA Fuses are typically employed in125 Vac applications.
• Delivering a similar amount of energy at twice the voltage will
require half the current.
• IEC Fuses have current ratings based on 100% rated current being
continuously carried.
• UL/CSA Fuses have current ratings based on 70% to 75% rated
current being continuously carried.
• Because of the current rating differences, IEC and UL/CSA Fuses
are mutually exclusive.
• Be extremely cautious when using a UL Recognized IEC fuse for a
North American application.
Component Qualification
• Industry Standards (Non-Safety)
EIA/ECA 962 “Low Voltage Supplemental Fuse Qualification
Specification”
EIA/ECA 932 “Surge Withstand Telecommunications Fuse
Qualification Specification”
• Purchasing Standards (Non-Safety)
Each user may generate minimum operational parameters for
products to be purchased. Even if these are simply replicating
tests and limits taken from the suppliers’ data sheets, they
become binding for future orders.
Details of Fuse Design
• Now we can begin to discuss
construction, parameters, and operation
of element Type fuses.
Element Type Fuses
• Single Centered Element
• Single Diagonal Element
• Twisted Pair Element
• Dual Element
• Spiral Wound Element
(On Ceramic Core)
Element #1
Element #2
Materials
• Bodies can be glass, ceramic or plastic
• End caps are typically tin plated copper or brass
• Fuse clips are not high reliability connections
Base materials can be brass, phosphor bronze or beryllium copper
Brass must have a nickel or equivalent barrier between base metal and final plating
Plating of fuse should match plating of clip
• Element materials vary greatly – Pure silver to stainless steel
• Extremely small amounts of an alloy metal can significantly
change element operating characteristics.
• Elements are typically bonded to the end caps by soldering or
welding.
• Leads, if provided, should be tin plated copper and of
appropriate cross section to easily carry fault current.
• Fillers are often employed for higher current and/or voltage
devices
Added variables
Fuse Package
• Fuse body / end cap assemblies are normally
“vented” to accommodate for the expanding solid
element as it heats and vaporizes with heavy fault
currents. Without such venting, pressure related to
the vaporization can result in rupture of the fuse
enclosure.
• For applications where the fuse will be encapsulated
or otherwise sealed, it is important to discuss the
application with the fuse company engineers.
• Always insure that leaded fuses have adequate
diameter copper leads to withstand the worst case
fault condition rating.
Element Loading Properties
• At heavy short circuit currents and full rated voltage, the element
material vaporizes – goes from a solid to a gas – during the
arcing phase and is plated out on the relatively cool inside
surface of the fuse body. If there is excessive volume of metal
in the element, the plated out metal can potentially bridge the
fuse, providing a new current path.
• Elements can be subjected to mechanical fatigue with repeated
surges or off/on cycling.
• The unique metal alloys employed for elements are extremely
difficult to assess directly due to the very small quantities of
different material needed to significantly change the element
characteristics.
• Every unique metal alloy will have a specific slope for voltage
drop (hot resistance) vs. current.
Important Fuse Electrical
Parameters
• Current Rating – Maximum level of continuous current
North American and European ratings differ significantly; they are “Mutually Exclusive”.
• Voltage Rating – Maximum level of open circuit voltage
AC and DC ratings are not necessarily the same
• Interrupting Rating (Short Circuit Current) – Maximum level of current
that can be safely interrupted at the rated voltage
European agencies refer to “Breaking Current” and there are Low and High Breaking
Current ratings.
• Low Phase Angle Faults – Faults that occur within 10 degrees of zero
crossover on the sine curve as the current is increasing.
• DC Resistance (Cold Resistance) – Nominal DC Resistance of a given
fuse type and value at agreed upon room temperature
• Voltage Drop (Hot Resistance) – Nominal voltage measured across
the fuse while carrying 75% to 100% rated current.
• I-t Curve – Log-Log plot of current vs. time.
There is a difference between “Melting Time” curve vs. “Clearing Time” curve.
• I²t Rating – “Let-Through” energy value.
Fault Position on Sine Curve
Fault Scope Trace
Fault at 4Âş on Sine Curve
600 Vac, 60 A
Important Fuse Mechanical
Parameters
• Fuse physical size is important when selecting “equivalents” for
second – or alternate – sourcing.
• Soldered connections are preferred over mechanical
connections for reliability purposes.
• Fuse lead diameters vary considerably for “equivalent” products.
• All mechanical contacts must be studied carefully for plating
compatibility.
• Soldered connections are never intended to provide mechanical
support.
• Reflow solder process is typically required for surface mount
fuses. Wave solder process is normally never recommended for
surface mount fuses.
• Fuses are not normally sealed. If a sealed device is required,
speak with the manufacturer’s engineering staff.
Element Selection
• Elements are selected to provide a given clearing current at a specific
rated voltage, and limit the possibility of bridging the fuse electrical
contacts after clearing.
• Elements are usually formed from conductive pure metals or unique
metal alloys.
• Applications requiring high tensile strength (spring loaded) elements
will typically use higher resistance and higher melting temperature
metals.
• There are both low temperature elements and high temperature
elements. Low temperature element fuses (e.g. Pb, Sn, Bi) will be
more affected by ambient temperature.
Fuse Element Voltage Drop
CURRENT
VOLTAGEDROP
Elem
ent Type
1
Element Type 2
Element Precision
Very Precision Diameter Element
Less Than Very Precision Diameter Element
Current Cutoff I-t Curve
25CF 15 A I-tCurve
Clearing Tim e (Seconds)
0.001 0.01 0.1 1 10
Current(Amperes)
10
100
1000
135% RATED CURRENT
110% RATED CURRENT
(MUST OPEN WITHIN 60 MINS.)
(MUST HOLD FOR 4 HRS.)
MAXIMUM CONTINUOUS CURRENT
(TYP. 75% RATED CURRENT)
(MUST OPEN WITHIN 2 MINS.)
t
I
200% RATED CURRENT
Current Cutoff I-t Curve – 3D
Low Overcurrent – Primarily Melting
Heavy Overcurrent – Significant Arcing
Current Cutoff I-t Curve
25CF 15 A I-tCurve
Clearing Tim e (Seconds)
0.001 0.01 0.1 1 10
Current(Amperes)
10
100
1000
I-t Curve Parameters
• Melting Time
Time at a given current for a fuse element to melt
• Arcing Time
Time after element melts open to total current cutoff
• Clearing Time
Total time required to cut current
• Clearing Time = Melting Time + Arcing
Time
Current Cutoff I-t Curve
25CF 15 A I-tCurve
Clearing Tim e (Seconds)
0.001 0.01 0.1 1 10
Current(Amperes)
10
100
1000
Temperature Distribution Along A
Precision Diameter Element Length
Conducted Heat
Radiated Heat Radiated Heat
Radiated Heat
Radiated Heat Radiated Heat
Temperature Distribution Along A Less
Than Precision Diameter Element Length
Normal / Quick Acting Fuse
• Normal, or Quick Acting,
fuses are typically a single
wire element.
• Elements can be made of
a variety of pure metals or
alloys.
• Parallel (centered on the
fuse axis) elements are
preferred over diagonal
elements.
Normal / Quick Acting Fuse
Conducted Heat
Radiated Heat Radiated Heat
Radiated Heat
Radiated Heat Radiated Heat
Normal / Quick Acting Fuse
Characteristics
• Fuse elements are typically very low
resistance – but never zero ohms.
• Because of the quick clearing time,
these fuses will be associated with I²t
ratings.
• With the faster operation, these fuses
will typically have a higher interrupting
current rating and voltage rating for a
given fuse package size.
Twisted Pair Surge Withstand Fuse
• These are compound elements that
have been tightly wrapped, or one
element is wound around another.
• The two elements are typically two
different conductive materials.
• Each conductor has a given voltage
drop at elevated current. As current
level increases, the initially primary
conductor can become the secondary
conductor, changing the elements
operating characteristics.
• The twisted elements also provide
more element surface area than a
single element, resulting in more
cooling effect.
Element #1
Element #2
Fuse Element Voltage Drop
CURRENT
VOLTAGEDROP
El ementType1
El ementType2
CURRENT
VOLTAGEDROP
Elem
ent Type
1
Element Type 2
Twisted Pair Surge Withstand
Fuse Characteristics
• Twisted pair Surge Withstand fuses are slower than Quick
Acting or Normal fuses, but faster acting than Time Delay fuses.
• This category is often referred to as a Medium Time Delay fuse.
However, it should be understood that no such official category
exists with North American Safety Agencies.
• A compound twisted element is similar to an “M” Effect fuse, in
that it requires additional energy as the two different metals alloy
during the melting process.
• Dual Element Time Delay
fuses will have two nearly
identical, parallel, elements
that share current.
• Elements can be made of a
variety of pure metals or
alloys.
• The slight difference
between element effective
diameters will make these
types of fuses less precise.
Dual Element Time Delay Fuse
Dual Element Fuse
Conducted Heat
Radiated Heat Radiated Heat
Radiated Heat Radiated Heat
Element #1
Element #2
Dual Element Characteristics
• Fuse elements may be spring loaded
• Fuse elements are seldom near perfect
electrical balance, resulting in less
precision than other designs.
• Lower precision precludes effective use
of I²t ratings.
• This type fuse usually has the greatest
time delay available.
Spiral Wound Time Delay Fuse
• Element is wrapped tightly around
high alumina ceramic core which
acts as a heat sink.
• Element is significantly longer than
comparable fast acting or dual
element fuse.
• Ends of element are bonded to fuse
contacts with solder or weld.
• Ceramic core may be either solid
rod or flexible yarn.
• As element temperature rises with
current increase, heat is absorbed
by ceramic core. Transfer of heat
will continue until core saturation
occurs.
Spiral Wound Fuse
Radiated Heat Radiated Heat
Absorbed Heat
Absorbed Heat
Ceramic Core
Fuse Element
Spiral Wound Element Characteristics
• More precise method than Dual Element type to create a Time
Delay fuse
• Typically will not have as much delay as Dual Element type fuse
• DC Resistance and Voltage Drop will typically be higher for
similar current rating of Dual Element type fuse
• Mechanical flexing of element is limited by ceramic core.
Therefore, there is less chance of incurring an element fracture.
• I²t ratings may be employed, but care must be taken to avoid
misinterpretation.
Low Overload Current
Fuse Operation
• Low level current overloads are very dangerous because of the
large amount of heat generated over extended time periods.
• Typical source for such overload condition is a “sneak current”
caused by gradual breakdown of insulation.
• Any arcing during the fuse operation will be a function of the
open circuit voltage level – arcing time is usually minimal.
• Surface mounted fuses may reflow the solder, leaving them free
to move on the circuit board.
• Mechanical contacts suffer during low level overloads due to
high temperature annealing of spring clips and chemical /
metallurgical changes.
Thin/Thick Film Fuses
• Less Expensive
• Less Precise
• Good for heavy Mechanical
Shock & Vibration
• Typically lower voltage rating
than element type fuse for a
given physical size
• Typically lower interrupting
current rating than element
type fuse for a given physical
size
• Most surface mount fuses of
length less than 6 mm are of
this type.
Element
Element
End View
(Cross Section)
End View
(Cross Section)
Side View
(Cross Section)
Side View
(Cross Section)
Manufacturing Techniques
• Stocking and Warehousing
Usually safe to stock in unheated facilities
Shelf Life is typically 1 year – Longer Shelf Life can be confirmed with
some measurements
• Assembly Alternatives
Wave Solder vs. Reflow Solder
Use of Fuse Clips and Holders – AVOID IF POSSIBLE
• Production Variables
Hand assembly vs. Automatic assembly
• Final Testing
Test results of component vs. Test results of component in circuit
• Product Shipping
With or Without Fuse
Finished Product
• Second Sourcing of Protectors
Not all “equivalent” fuses are the same
Demand Electrical and Mechanical Data Sheets.
Surface Mount fuses are generally sold by length and width (e.g. 1206).
Height may be just as important!
Try to use component Data Sheets to generate a User Specification
• Customer Support
Your customers expect support; You should expect support from your
vendors
• Maintenance Manuals
Include specifics in any equipment maintenance manuals to permit
replacement with tested equivalent fuses
Thank You

More Related Content

What's hot

Circuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingCircuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingfairautomation
 
Grounding and bonding testing
Grounding and bonding testingGrounding and bonding testing
Grounding and bonding testingmichaeljmack
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...Keren Meers
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingAsif Eqbal
 
20120504 LISAT slides Dube
20120504 LISAT slides Dube20120504 LISAT slides Dube
20120504 LISAT slides Dubemosesnbklyn
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
Overvoltages 1
Overvoltages 1Overvoltages 1
Overvoltages 1ahmedasdasd
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protectionmichaeljmack
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerRenuka Verma
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalNihal Shiroya
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices Pratik Rasam
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordinationsarunkutti
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relaysmichaeljmack
 

What's hot (20)

Circuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controlingCircuits breakers for industrial automation and process controling
Circuits breakers for industrial automation and process controling
 
Grounding and bonding testing
Grounding and bonding testingGrounding and bonding testing
Grounding and bonding testing
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
High voltage fuse test techniques
High voltage fuse test techniquesHigh voltage fuse test techniques
High voltage fuse test techniques
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...ABB switchgear safety hazards passive & active arc fault protection by David ...
ABB switchgear safety hazards passive & active arc fault protection by David ...
 
Lv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizingLv switchgear &amp; lv cable sizing
Lv switchgear &amp; lv cable sizing
 
20120504 LISAT slides Dube
20120504 LISAT slides Dube20120504 LISAT slides Dube
20120504 LISAT slides Dube
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
Overvoltages 1
Overvoltages 1Overvoltages 1
Overvoltages 1
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Overcurrent coordination
Overcurrent coordinationOvercurrent coordination
Overcurrent coordination
 
Surge supressor
Surge supressorSurge supressor
Surge supressor
 
digital testing of high voltage circuit breaker
digital testing of high voltage circuit breakerdigital testing of high voltage circuit breaker
digital testing of high voltage circuit breaker
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihal
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Fundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based RelaysFundamentals of Microprocessor Based Relays
Fundamentals of Microprocessor Based Relays
 

Viewers also liked

2015 x472 class 06- special building types
2015 x472 class 06- special building types2015 x472 class 06- special building types
2015 x472 class 06- special building typesmichaeljmack
 
X472 class 09 2 of 2 title 24 and leed
X472 class 09 2 of 2 title 24 and leedX472 class 09 2 of 2 title 24 and leed
X472 class 09 2 of 2 title 24 and leedmichaeljmack
 
2015 x472 class 07 - system selection ii - pre-class
2015 x472 class 07 - system selection ii - pre-class2015 x472 class 07 - system selection ii - pre-class
2015 x472 class 07 - system selection ii - pre-classmichaeljmack
 
Nfpa 110 review
Nfpa 110 reviewNfpa 110 review
Nfpa 110 reviewmichaeljmack
 
X472 class 09 1 of 2 title 24 and leed
X472 class 09 1 of 2 title 24 and leedX472 class 09 1 of 2 title 24 and leed
X472 class 09 1 of 2 title 24 and leedmichaeljmack
 
Ge generator and ups problems
Ge generator and ups problemsGe generator and ups problems
Ge generator and ups problemsmichaeljmack
 
Code questions
Code questionsCode questions
Code questionsmichaeljmack
 
Service cabinetandtransformerbreakersizing1082004
Service cabinetandtransformerbreakersizing1082004Service cabinetandtransformerbreakersizing1082004
Service cabinetandtransformerbreakersizing1082004michaeljmack
 
Pullbox sizing
Pullbox sizingPullbox sizing
Pullbox sizingmichaeljmack
 
2015 x472 class 8 - codes, construction documentation and coordination
2015 x472 class 8 - codes, construction documentation and coordination2015 x472 class 8 - codes, construction documentation and coordination
2015 x472 class 8 - codes, construction documentation and coordinationmichaeljmack
 
Substation design guideliness
Substation design guidelinessSubstation design guideliness
Substation design guidelinessmichaeljmack
 
2015 x472 class 05 - system selection
2015 x472 class 05 - system selection2015 x472 class 05 - system selection
2015 x472 class 05 - system selectionmichaeljmack
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidlmichaeljmack
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirementsmichaeljmack
 
2015 x472 class 01 - intro and system overview
2015 x472 class 01 - intro and system overview2015 x472 class 01 - intro and system overview
2015 x472 class 01 - intro and system overviewmichaeljmack
 
2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialtymichaeljmack
 
Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systemsmichaeljmack
 
2015 x472 class 03 - distribution systems
2015 x472 class 03 - distribution systems2015 x472 class 03 - distribution systems
2015 x472 class 03 - distribution systemsmichaeljmack
 
Power system slide notes
Power system slide notesPower system slide notes
Power system slide notesmichaeljmack
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systemsmichaeljmack
 

Viewers also liked (20)

2015 x472 class 06- special building types
2015 x472 class 06- special building types2015 x472 class 06- special building types
2015 x472 class 06- special building types
 
X472 class 09 2 of 2 title 24 and leed
X472 class 09 2 of 2 title 24 and leedX472 class 09 2 of 2 title 24 and leed
X472 class 09 2 of 2 title 24 and leed
 
2015 x472 class 07 - system selection ii - pre-class
2015 x472 class 07 - system selection ii - pre-class2015 x472 class 07 - system selection ii - pre-class
2015 x472 class 07 - system selection ii - pre-class
 
Nfpa 110 review
Nfpa 110 reviewNfpa 110 review
Nfpa 110 review
 
X472 class 09 1 of 2 title 24 and leed
X472 class 09 1 of 2 title 24 and leedX472 class 09 1 of 2 title 24 and leed
X472 class 09 1 of 2 title 24 and leed
 
Ge generator and ups problems
Ge generator and ups problemsGe generator and ups problems
Ge generator and ups problems
 
Code questions
Code questionsCode questions
Code questions
 
Service cabinetandtransformerbreakersizing1082004
Service cabinetandtransformerbreakersizing1082004Service cabinetandtransformerbreakersizing1082004
Service cabinetandtransformerbreakersizing1082004
 
Pullbox sizing
Pullbox sizingPullbox sizing
Pullbox sizing
 
2015 x472 class 8 - codes, construction documentation and coordination
2015 x472 class 8 - codes, construction documentation and coordination2015 x472 class 8 - codes, construction documentation and coordination
2015 x472 class 8 - codes, construction documentation and coordination
 
Substation design guideliness
Substation design guidelinessSubstation design guideliness
Substation design guideliness
 
2015 x472 class 05 - system selection
2015 x472 class 05 - system selection2015 x472 class 05 - system selection
2015 x472 class 05 - system selection
 
2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl2006 01-16 evap techniques r seidl
2006 01-16 evap techniques r seidl
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirements
 
2015 x472 class 01 - intro and system overview
2015 x472 class 01 - intro and system overview2015 x472 class 01 - intro and system overview
2015 x472 class 01 - intro and system overview
 
2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty2015 x472 class 04 - central and specialty
2015 x472 class 04 - central and specialty
 
Introduction to hvac systems
Introduction to hvac systemsIntroduction to hvac systems
Introduction to hvac systems
 
2015 x472 class 03 - distribution systems
2015 x472 class 03 - distribution systems2015 x472 class 03 - distribution systems
2015 x472 class 03 - distribution systems
 
Power system slide notes
Power system slide notesPower system slide notes
Power system slide notes
 
2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems2015 x472 class 02 - generation systems
2015 x472 class 02 - generation systems
 

Similar to Understanding overcurrent protection

Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020nacetwincities
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizationsMichael O'Dell
 
An introduction to FUSES
An introduction to FUSESAn introduction to FUSES
An introduction to FUSESPraveen Kumar
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptSameeraShaman
 
Elec01 electrical elements
Elec01 electrical elementsElec01 electrical elements
Elec01 electrical elementsMark Anthony Cabilo
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor GeneralizationsMichael O'Dell
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor GeneralizationsMichael O'Dell
 
ELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptxELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptxrajalakshmi769433
 
Fuse- Power system Protection
Fuse- Power system Protection  Fuse- Power system Protection
Fuse- Power system Protection Md. Nahid Sarker
 
Welding equipments
Welding equipmentsWelding equipments
Welding equipmentsPeeyush Chauhan
 
Basic Electrical Parameters ( Basic Electrical Engineering)
Basic Electrical Parameters ( Basic Electrical Engineering)Basic Electrical Parameters ( Basic Electrical Engineering)
Basic Electrical Parameters ( Basic Electrical Engineering)Chetan Patil
 
Joining processes (welding)
Joining processes (welding)Joining processes (welding)
Joining processes (welding)9665930613
 
Indicating, recording &amp; controlling devices used in dairy plants principl...
Indicating, recording &amp; controlling devices used in dairy plants principl...Indicating, recording &amp; controlling devices used in dairy plants principl...
Indicating, recording &amp; controlling devices used in dairy plants principl...Dhruv Patel
 
Protection presentation
Protection presentationProtection presentation
Protection presentationUsama Umer
 
1.Resistors_new NOTE.pdf
1.Resistors_new NOTE.pdf1.Resistors_new NOTE.pdf
1.Resistors_new NOTE.pdfanushafi1
 
Lab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxLab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxTALHA RIAZ PERSOTA
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices pptZuhairQadri
 

Similar to Understanding overcurrent protection (20)

Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
 
Contactor generalizations
Contactor generalizationsContactor generalizations
Contactor generalizations
 
An introduction to FUSES
An introduction to FUSESAn introduction to FUSES
An introduction to FUSES
 
Design of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.pptDesign of Electrical Installation of Buildings.ppt
Design of Electrical Installation of Buildings.ppt
 
Elec01 electrical elements
Elec01 electrical elementsElec01 electrical elements
Elec01 electrical elements
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor Generalizations
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor Generalizations
 
ELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptxELECTRICAL INSTALLATIONS PPT (1).pptx
ELECTRICAL INSTALLATIONS PPT (1).pptx
 
Fuse- Power system Protection
Fuse- Power system Protection  Fuse- Power system Protection
Fuse- Power system Protection
 
Welding equipments
Welding equipmentsWelding equipments
Welding equipments
 
Basic Electrical Parameters ( Basic Electrical Engineering)
Basic Electrical Parameters ( Basic Electrical Engineering)Basic Electrical Parameters ( Basic Electrical Engineering)
Basic Electrical Parameters ( Basic Electrical Engineering)
 
Joining processes (welding)
Joining processes (welding)Joining processes (welding)
Joining processes (welding)
 
Indicating, recording &amp; controlling devices used in dairy plants principl...
Indicating, recording &amp; controlling devices used in dairy plants principl...Indicating, recording &amp; controlling devices used in dairy plants principl...
Indicating, recording &amp; controlling devices used in dairy plants principl...
 
Protection presentation
Protection presentationProtection presentation
Protection presentation
 
4 fuses
4 fuses4 fuses
4 fuses
 
1.Resistors_new NOTE.pdf
1.Resistors_new NOTE.pdf1.Resistors_new NOTE.pdf
1.Resistors_new NOTE.pdf
 
Lab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptxLab # 03 Workshop Practice.pptx
Lab # 03 Workshop Practice.pptx
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices ppt
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodinationmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodination
 

Recently uploaded

Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxRaymartEstabillo3
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPCeline George
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
Quarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayQuarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayMakMakNepo
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Celine George
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentInMediaRes1
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceSamikshaHamane
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Jisc
 
Earth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatEarth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatYousafMalik24
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomnelietumpap1
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designMIPLM
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...Nguyen Thanh Tu Collection
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Celine George
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17Celine George
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........LeaCamillePacle
 

Recently uploaded (20)

Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptxEPANDING THE CONTENT OF AN OUTLINE using notes.pptx
EPANDING THE CONTENT OF AN OUTLINE using notes.pptx
 
OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERP
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
Quarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up FridayQuarter 4 Peace-education.pptx Catch Up Friday
Quarter 4 Peace-education.pptx Catch Up Friday
 
Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17Computed Fields and api Depends in the Odoo 17
Computed Fields and api Depends in the Odoo 17
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media Component
 
Roles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in PharmacovigilanceRoles & Responsibilities in Pharmacovigilance
Roles & Responsibilities in Pharmacovigilance
 
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
 
Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...Procuring digital preservation CAN be quick and painless with our new dynamic...
Procuring digital preservation CAN be quick and painless with our new dynamic...
 
Earth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice greatEarth Day Presentation wow hello nice great
Earth Day Presentation wow hello nice great
 
ENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choomENGLISH6-Q4-W3.pptxqurter our high choom
ENGLISH6-Q4-W3.pptxqurter our high choom
 
Keynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-designKeynote by Prof. Wurzer at Nordex about IP-design
Keynote by Prof. Wurzer at Nordex about IP-design
 
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
HỌC TỐT TIẾNG ANH 11 THEO CHƯƠNG TRÌNH GLOBAL SUCCESS ĐÁP ÁN CHI TIẾT - CẢ NĂ...
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17
 
How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17How to Configure Email Server in Odoo 17
How to Configure Email Server in Odoo 17
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........Atmosphere science 7 quarter 4 .........
Atmosphere science 7 quarter 4 .........
 

Understanding overcurrent protection

  • 1. Understanding Overcurrent Circuit Protectors Carl E.Lindquist VP New Product Development San-O Industrial Corporation SOCÂŽ
  • 2. Introduction to Overcurrent Circuit Protectors Overcurrent (Series) vs. Overvoltage (Shunt) Type Protectors We will be limiting our discussion to Overcurrent (Series) Type Protectors
  • 3. Current Cutoffs vs. Current Limiters • Current Cutoff Protectors reduce current in the circuit to zero. • Current Limiting Protectors reduce current in the circuit to some “acceptable” safe level.
  • 4. Types of Overcurrent Protectors • Current Cutoffs Fuses Circuit Breakers • Current Limiters Polymer Positive Temperature Coefficient (PPTC’s) Ceramic Positive Temperature Coefficient (CPTC’s) Line Feed Resistors (LFR’s) Electronic Current Limiters (ECL’s)
  • 5. Current Cutoffs • Circuit Breakers Fully resettable Thermal vs. Magnetic vs. Thermal-Magnetic Interrupting current at rated voltage is not the same as for a fuse. Never intended for use as a switch unless specifically noted • Fuses “Weak Links” and are not resettable. Element vs. Thin/Thick Film Provide the highest current and voltage ratings in smallest space
  • 6. Thermal Circuit Breaker • Low cost • Poor Precision • Slow Acting • Trip current is significantly affected by ambient temperature • Complex mechanism • Relatively large package Outline of thermal circuit breaker. (Courtesy Square D Co.)
  • 7. Magnetic Breaker Operation Small magnetic circuit breaker. (Courtesy Airpax)
  • 8. Magnetic Breaker Detail • Magnetic breakers without slowing mechanism will operate in a few milliseconds. Very precise Very fast Very sensitive to low overcurrent Not greatly affected by ambient temperature Relatively expensive • The standard method of slowing the operation at low overload currents is use of a viscous fluid in a dashpot. Some loss of precision Slow acting at low level overloads Viscosity of fluid will be affected by temperature • Heavy overload currents will cause instantaneous operation. (Hence, “instantaneous trip” rating)
  • 9. Thermal-Magnetic Breaker • Thermal-Magnetic breakers are hybrids of the two previously discussed devices. • These breakers act as a thermal breaker for low level overloads and act as magnetic breaker for instantaneous trip at high level current faults • Most standard house service entrance breakers are thermal-magnetic.
  • 10. Current Limiters • PTC’s Resettable Passive Devices Both Polymer and Ceramic are somewhat ambient temperature sensitive for tripping point. Some “drift” in nominal limiting after first reset • LFR’s Resettable Passive Devices Usually limited to telecommunications These devices can completely open the circuit if fault is heavy enough or long term low level overload. • ECL’s Resettable Active Devices Speed of operation can be adjusted Can be made very precise Some limitations on maximum voltage levels
  • 11. Protector Selection • Agency Approvals • Physical Area Available • Required Nominal Continuous Current Level • Clearing Time • Surge Withstand Requirements (Inrush, Lightning, etc.) • Maximum Interrupting Current at Rated Voltage • Open Circuit Voltage (AC, DC or Both) • Single Event vs. Resettable Ease of Replacement Effect of Nuisance Operation Long Term Availability of Replacements • Environmental Parameters Temperature Range (Room Temperature vs. Microclimate) Humidity Mechanical shock Hazardous Environments (Corrosive, Explosive, etc.) • High Reliability Applications Medical Military Aerospace Telecommunications
  • 12. Agency Approvals • North America UL / CSA Listing / Certified vs. Recognition • European (IEC 60127) SEMKO DEMKO BSI • Japanese <PS>E JET
  • 13. IEC vs. North American Fuses • IEC Fuses are typically employed in 250 Vac applications. • UL/CSA Fuses are typically employed in125 Vac applications. • Delivering a similar amount of energy at twice the voltage will require half the current. • IEC Fuses have current ratings based on 100% rated current being continuously carried. • UL/CSA Fuses have current ratings based on 70% to 75% rated current being continuously carried. • Because of the current rating differences, IEC and UL/CSA Fuses are mutually exclusive. • Be extremely cautious when using a UL Recognized IEC fuse for a North American application.
  • 14. Component Qualification • Industry Standards (Non-Safety) EIA/ECA 962 “Low Voltage Supplemental Fuse Qualification Specification” EIA/ECA 932 “Surge Withstand Telecommunications Fuse Qualification Specification” • Purchasing Standards (Non-Safety) Each user may generate minimum operational parameters for products to be purchased. Even if these are simply replicating tests and limits taken from the suppliers’ data sheets, they become binding for future orders.
  • 15. Details of Fuse Design • Now we can begin to discuss construction, parameters, and operation of element Type fuses.
  • 16. Element Type Fuses • Single Centered Element • Single Diagonal Element • Twisted Pair Element • Dual Element • Spiral Wound Element (On Ceramic Core) Element #1 Element #2
  • 17. Materials • Bodies can be glass, ceramic or plastic • End caps are typically tin plated copper or brass • Fuse clips are not high reliability connections Base materials can be brass, phosphor bronze or beryllium copper Brass must have a nickel or equivalent barrier between base metal and final plating Plating of fuse should match plating of clip • Element materials vary greatly – Pure silver to stainless steel • Extremely small amounts of an alloy metal can significantly change element operating characteristics. • Elements are typically bonded to the end caps by soldering or welding. • Leads, if provided, should be tin plated copper and of appropriate cross section to easily carry fault current. • Fillers are often employed for higher current and/or voltage devices Added variables
  • 18. Fuse Package • Fuse body / end cap assemblies are normally “vented” to accommodate for the expanding solid element as it heats and vaporizes with heavy fault currents. Without such venting, pressure related to the vaporization can result in rupture of the fuse enclosure. • For applications where the fuse will be encapsulated or otherwise sealed, it is important to discuss the application with the fuse company engineers. • Always insure that leaded fuses have adequate diameter copper leads to withstand the worst case fault condition rating.
  • 19. Element Loading Properties • At heavy short circuit currents and full rated voltage, the element material vaporizes – goes from a solid to a gas – during the arcing phase and is plated out on the relatively cool inside surface of the fuse body. If there is excessive volume of metal in the element, the plated out metal can potentially bridge the fuse, providing a new current path. • Elements can be subjected to mechanical fatigue with repeated surges or off/on cycling. • The unique metal alloys employed for elements are extremely difficult to assess directly due to the very small quantities of different material needed to significantly change the element characteristics. • Every unique metal alloy will have a specific slope for voltage drop (hot resistance) vs. current.
  • 20. Important Fuse Electrical Parameters • Current Rating – Maximum level of continuous current North American and European ratings differ significantly; they are “Mutually Exclusive”. • Voltage Rating – Maximum level of open circuit voltage AC and DC ratings are not necessarily the same • Interrupting Rating (Short Circuit Current) – Maximum level of current that can be safely interrupted at the rated voltage European agencies refer to “Breaking Current” and there are Low and High Breaking Current ratings. • Low Phase Angle Faults – Faults that occur within 10 degrees of zero crossover on the sine curve as the current is increasing. • DC Resistance (Cold Resistance) – Nominal DC Resistance of a given fuse type and value at agreed upon room temperature • Voltage Drop (Hot Resistance) – Nominal voltage measured across the fuse while carrying 75% to 100% rated current. • I-t Curve – Log-Log plot of current vs. time. There is a difference between “Melting Time” curve vs. “Clearing Time” curve. • I²t Rating – “Let-Through” energy value.
  • 21. Fault Position on Sine Curve
  • 23. Fault at 4Âş on Sine Curve 600 Vac, 60 A
  • 24. Important Fuse Mechanical Parameters • Fuse physical size is important when selecting “equivalents” for second – or alternate – sourcing. • Soldered connections are preferred over mechanical connections for reliability purposes. • Fuse lead diameters vary considerably for “equivalent” products. • All mechanical contacts must be studied carefully for plating compatibility. • Soldered connections are never intended to provide mechanical support. • Reflow solder process is typically required for surface mount fuses. Wave solder process is normally never recommended for surface mount fuses. • Fuses are not normally sealed. If a sealed device is required, speak with the manufacturer’s engineering staff.
  • 25. Element Selection • Elements are selected to provide a given clearing current at a specific rated voltage, and limit the possibility of bridging the fuse electrical contacts after clearing. • Elements are usually formed from conductive pure metals or unique metal alloys. • Applications requiring high tensile strength (spring loaded) elements will typically use higher resistance and higher melting temperature metals. • There are both low temperature elements and high temperature elements. Low temperature element fuses (e.g. Pb, Sn, Bi) will be more affected by ambient temperature.
  • 26. Fuse Element Voltage Drop CURRENT VOLTAGEDROP Elem ent Type 1 Element Type 2
  • 27. Element Precision Very Precision Diameter Element Less Than Very Precision Diameter Element
  • 28. Current Cutoff I-t Curve 25CF 15 A I-tCurve Clearing Tim e (Seconds) 0.001 0.01 0.1 1 10 Current(Amperes) 10 100 1000
  • 29. 135% RATED CURRENT 110% RATED CURRENT (MUST OPEN WITHIN 60 MINS.) (MUST HOLD FOR 4 HRS.) MAXIMUM CONTINUOUS CURRENT (TYP. 75% RATED CURRENT) (MUST OPEN WITHIN 2 MINS.) t I 200% RATED CURRENT Current Cutoff I-t Curve – 3D
  • 30. Low Overcurrent – Primarily Melting Heavy Overcurrent – Significant Arcing
  • 31. Current Cutoff I-t Curve 25CF 15 A I-tCurve Clearing Tim e (Seconds) 0.001 0.01 0.1 1 10 Current(Amperes) 10 100 1000
  • 32. I-t Curve Parameters • Melting Time Time at a given current for a fuse element to melt • Arcing Time Time after element melts open to total current cutoff • Clearing Time Total time required to cut current • Clearing Time = Melting Time + Arcing Time
  • 33. Current Cutoff I-t Curve 25CF 15 A I-tCurve Clearing Tim e (Seconds) 0.001 0.01 0.1 1 10 Current(Amperes) 10 100 1000
  • 34. Temperature Distribution Along A Precision Diameter Element Length Conducted Heat Radiated Heat Radiated Heat Radiated Heat Radiated Heat Radiated Heat
  • 35. Temperature Distribution Along A Less Than Precision Diameter Element Length
  • 36. Normal / Quick Acting Fuse • Normal, or Quick Acting, fuses are typically a single wire element. • Elements can be made of a variety of pure metals or alloys. • Parallel (centered on the fuse axis) elements are preferred over diagonal elements.
  • 37. Normal / Quick Acting Fuse Conducted Heat Radiated Heat Radiated Heat Radiated Heat Radiated Heat Radiated Heat
  • 38. Normal / Quick Acting Fuse Characteristics • Fuse elements are typically very low resistance – but never zero ohms. • Because of the quick clearing time, these fuses will be associated with I²t ratings. • With the faster operation, these fuses will typically have a higher interrupting current rating and voltage rating for a given fuse package size.
  • 39. Twisted Pair Surge Withstand Fuse • These are compound elements that have been tightly wrapped, or one element is wound around another. • The two elements are typically two different conductive materials. • Each conductor has a given voltage drop at elevated current. As current level increases, the initially primary conductor can become the secondary conductor, changing the elements operating characteristics. • The twisted elements also provide more element surface area than a single element, resulting in more cooling effect. Element #1 Element #2
  • 40. Fuse Element Voltage Drop CURRENT VOLTAGEDROP El ementType1 El ementType2 CURRENT VOLTAGEDROP Elem ent Type 1 Element Type 2
  • 41. Twisted Pair Surge Withstand Fuse Characteristics • Twisted pair Surge Withstand fuses are slower than Quick Acting or Normal fuses, but faster acting than Time Delay fuses. • This category is often referred to as a Medium Time Delay fuse. However, it should be understood that no such official category exists with North American Safety Agencies. • A compound twisted element is similar to an “M” Effect fuse, in that it requires additional energy as the two different metals alloy during the melting process.
  • 42. • Dual Element Time Delay fuses will have two nearly identical, parallel, elements that share current. • Elements can be made of a variety of pure metals or alloys. • The slight difference between element effective diameters will make these types of fuses less precise. Dual Element Time Delay Fuse
  • 43. Dual Element Fuse Conducted Heat Radiated Heat Radiated Heat Radiated Heat Radiated Heat Element #1 Element #2
  • 44. Dual Element Characteristics • Fuse elements may be spring loaded • Fuse elements are seldom near perfect electrical balance, resulting in less precision than other designs. • Lower precision precludes effective use of I²t ratings. • This type fuse usually has the greatest time delay available.
  • 45. Spiral Wound Time Delay Fuse • Element is wrapped tightly around high alumina ceramic core which acts as a heat sink. • Element is significantly longer than comparable fast acting or dual element fuse. • Ends of element are bonded to fuse contacts with solder or weld. • Ceramic core may be either solid rod or flexible yarn. • As element temperature rises with current increase, heat is absorbed by ceramic core. Transfer of heat will continue until core saturation occurs.
  • 46. Spiral Wound Fuse Radiated Heat Radiated Heat Absorbed Heat Absorbed Heat Ceramic Core Fuse Element
  • 47. Spiral Wound Element Characteristics • More precise method than Dual Element type to create a Time Delay fuse • Typically will not have as much delay as Dual Element type fuse • DC Resistance and Voltage Drop will typically be higher for similar current rating of Dual Element type fuse • Mechanical flexing of element is limited by ceramic core. Therefore, there is less chance of incurring an element fracture. • I²t ratings may be employed, but care must be taken to avoid misinterpretation.
  • 48. Low Overload Current Fuse Operation • Low level current overloads are very dangerous because of the large amount of heat generated over extended time periods. • Typical source for such overload condition is a “sneak current” caused by gradual breakdown of insulation. • Any arcing during the fuse operation will be a function of the open circuit voltage level – arcing time is usually minimal. • Surface mounted fuses may reflow the solder, leaving them free to move on the circuit board. • Mechanical contacts suffer during low level overloads due to high temperature annealing of spring clips and chemical / metallurgical changes.
  • 49. Thin/Thick Film Fuses • Less Expensive • Less Precise • Good for heavy Mechanical Shock & Vibration • Typically lower voltage rating than element type fuse for a given physical size • Typically lower interrupting current rating than element type fuse for a given physical size • Most surface mount fuses of length less than 6 mm are of this type. Element Element End View (Cross Section) End View (Cross Section) Side View (Cross Section) Side View (Cross Section)
  • 50. Manufacturing Techniques • Stocking and Warehousing Usually safe to stock in unheated facilities Shelf Life is typically 1 year – Longer Shelf Life can be confirmed with some measurements • Assembly Alternatives Wave Solder vs. Reflow Solder Use of Fuse Clips and Holders – AVOID IF POSSIBLE • Production Variables Hand assembly vs. Automatic assembly • Final Testing Test results of component vs. Test results of component in circuit • Product Shipping With or Without Fuse
  • 51. Finished Product • Second Sourcing of Protectors Not all “equivalent” fuses are the same Demand Electrical and Mechanical Data Sheets. Surface Mount fuses are generally sold by length and width (e.g. 1206). Height may be just as important! Try to use component Data Sheets to generate a User Specification • Customer Support Your customers expect support; You should expect support from your vendors • Maintenance Manuals Include specifics in any equipment maintenance manuals to permit replacement with tested equivalent fuses