The document discusses the grounding design of the Kano Hydro Power Station in Nigeria. It provides background on the authors and Skipper Electrical. It then summarizes the key aspects of designing the grounding system, including measuring soil resistivity, calculating touch and step potentials, and following relevant safety standards and codes. The results of the initial grounding design are presented, but the final design had to be re-evaluated after excavation revealed much higher soil resistivity in some areas than initially measured. The final design ensures touch and step potentials are within safe limits across the power house and switchyard.
This document discusses earthing systems and the hazards of a broken neutral connection for a power transformer. It defines system earthing and equipment earthing, and explains that a broken neutral connection can cause overvoltage issues for the transformer and prevent protective relays from operating during a fault. The document also discusses the objectives and importance of proper earthing, including providing an alternative path for fault currents, ensuring safety from electric shocks, and maintaining system voltages. It provides examples of what can occur when a transformer's neutral connection to earth is broken.
- Electrical earthing provides a safe path for lightning and fault currents to protect humans and equipment.
- There are different types of earthing for different applications like LV systems, lighting, telecoms, and computers.
- Earthing can provide either Class I or Class II protection against electric shock.
- Factors that affect earth impedance include soil type and moisture, weather, electrode type and size, nearby utilities, and distance between electrodes.
- Common earthing arrangements include TN, TT, and IT systems. Measurement methods like Wenner and Schlumberger are used to determine soil resistivity which impacts earth impedance.
Earthing in a substation is important for safety. It involves connecting electrical equipment to earth at a uniform low potential to limit dangerous voltages under fault conditions. Key aspects of substation earthing design include soil resistivity testing, sizing the earth mat conductor based on fault current and duration, and ensuring step and touch potentials remain below safety limits. Proper earthing aims to provide protection to life and property against faults.
The document discusses the key elements of distribution systems including feeders, distributors, service mains, and classifications based on current, construction, and connection schemes. It describes the functions of distribution substations and provides examples of radial, ring main, and interconnected systems. The document also covers voltage drop considerations for feeders and distributors, as well as objectives of distribution automation including improved reliability, power quality, and deferred capital expenses.
This document provides guidelines for designing an earth mat for a metro station. It discusses standards for earth mat design, the design procedure, and provides an example of a design for the Joka Station. The key steps in design include determining the fault current, selecting conductor size, and using software to model symmetrical or asymmetrical mat layouts based on space availability and soil properties. The example shows the proposed mat layout for Joka Station, simulation results verifying safe touch and step voltages, and low equipment grounding resistance and ground potential rise.
This document provides guidelines for properly installing an earthing system. It describes the working process which includes 1) checking materials and tools, 2) excavating for cable installation, 3) fitting earth rods and connecting them with cables using appropriate joining methods, 4) checking connections and resistance values, and 5) backfilling. Key points emphasized are using the correct accessories sizes, placing earth points at least 10 feet apart, and creating new points if resistance is more than 10% of requirements. Following the outlined process helps ensure a high quality, code-compliant earthing system installation.
This document discusses earthing and grounding in electrical systems. It defines earthing as connecting electrical equipment or systems to earth, usually soil, to prevent accidents and damage. There are two types: equipment earthing, which connects non-current metal parts; and system earthing, which connects parts of the electrical system. Neutral earthing connects the neutral point in a star system to earth. The document outlines the advantages of neutral earthing, such as keeping voltages stable and eliminating high voltages from arcing grounds, allowing for better protection and safety. Methods of neutral earthing include direct earthing or earthing through a resistor or reactor.
This document discusses earthing systems and the hazards of a broken neutral connection for a power transformer. It defines system earthing and equipment earthing, and explains that a broken neutral connection can cause overvoltage issues for the transformer and prevent protective relays from operating during a fault. The document also discusses the objectives and importance of proper earthing, including providing an alternative path for fault currents, ensuring safety from electric shocks, and maintaining system voltages. It provides examples of what can occur when a transformer's neutral connection to earth is broken.
- Electrical earthing provides a safe path for lightning and fault currents to protect humans and equipment.
- There are different types of earthing for different applications like LV systems, lighting, telecoms, and computers.
- Earthing can provide either Class I or Class II protection against electric shock.
- Factors that affect earth impedance include soil type and moisture, weather, electrode type and size, nearby utilities, and distance between electrodes.
- Common earthing arrangements include TN, TT, and IT systems. Measurement methods like Wenner and Schlumberger are used to determine soil resistivity which impacts earth impedance.
Earthing in a substation is important for safety. It involves connecting electrical equipment to earth at a uniform low potential to limit dangerous voltages under fault conditions. Key aspects of substation earthing design include soil resistivity testing, sizing the earth mat conductor based on fault current and duration, and ensuring step and touch potentials remain below safety limits. Proper earthing aims to provide protection to life and property against faults.
The document discusses the key elements of distribution systems including feeders, distributors, service mains, and classifications based on current, construction, and connection schemes. It describes the functions of distribution substations and provides examples of radial, ring main, and interconnected systems. The document also covers voltage drop considerations for feeders and distributors, as well as objectives of distribution automation including improved reliability, power quality, and deferred capital expenses.
This document provides guidelines for designing an earth mat for a metro station. It discusses standards for earth mat design, the design procedure, and provides an example of a design for the Joka Station. The key steps in design include determining the fault current, selecting conductor size, and using software to model symmetrical or asymmetrical mat layouts based on space availability and soil properties. The example shows the proposed mat layout for Joka Station, simulation results verifying safe touch and step voltages, and low equipment grounding resistance and ground potential rise.
This document provides guidelines for properly installing an earthing system. It describes the working process which includes 1) checking materials and tools, 2) excavating for cable installation, 3) fitting earth rods and connecting them with cables using appropriate joining methods, 4) checking connections and resistance values, and 5) backfilling. Key points emphasized are using the correct accessories sizes, placing earth points at least 10 feet apart, and creating new points if resistance is more than 10% of requirements. Following the outlined process helps ensure a high quality, code-compliant earthing system installation.
This document discusses earthing and grounding in electrical systems. It defines earthing as connecting electrical equipment or systems to earth, usually soil, to prevent accidents and damage. There are two types: equipment earthing, which connects non-current metal parts; and system earthing, which connects parts of the electrical system. Neutral earthing connects the neutral point in a star system to earth. The document outlines the advantages of neutral earthing, such as keeping voltages stable and eliminating high voltages from arcing grounds, allowing for better protection and safety. Methods of neutral earthing include direct earthing or earthing through a resistor or reactor.
This document discusses restricted earth fault (REF) protection schemes for transformers and generators. It explains that a REF scheme is needed to detect internal earth faults since they may not cause current to flow through the external overcurrent protection. A REF scheme works by summing the currents entering and exiting a protected zone using two sets of current transformers, and tripping if the sums are unequal, indicating an internal fault. Key elements of a REF scheme include the REF relay, stabilizing resistor to avoid spurious trips from CT mismatches, and specifying a high knee point voltage for the CTs. Examples of REF schemes for generators and transformer configurations are also provided.
The document discusses generator protection systems. It introduces the basic electrical quantities used for protection like current, voltage, phase angle and frequency. Protective relays use one or more of these quantities to detect faults. The document then discusses different types of relays and circuit breakers used for protection. It describes various protection zones like generator, transformer, bus, line and utilization equipment zones. The rest of the document elaborates on different protection schemes for generators including stator protection, rotor protection, loss of excitation protection and reverse power protection.
This document discusses different methods of grounding electrical systems, including solid grounding, resistance grounding, reactance grounding, and resonant groundings using a Peterson coil. Solid grounding directly connects the neutral point to earth, holding it at earth potential but allowing high fault currents. Resistance grounding limits fault current by connecting through a resistor. Reactance grounding uses an inductor instead of resistor. Resonant grounding with a Peterson coil adjusts the inductance to balance capacitive currents and prevent arcing faults.
Practical handbook-for-relay-protection-engineersSARAVANAN A
The ‘Hand Book’ covers the Code of Practice in Protection Circuitry including standard lead and device numbers, mode of connections at terminal strips, colour codes in multicore cables, Dos and Donts in execution. Also, principles of various protective relays and schemes including special protection schemes like differential,
restricted, directional and distance relays are explained with sketches. The norms of protection of generators, transformers, lines & Capacitor Banks are also given.
Substation grounding systems provide protection from electric shock hazards by dissipating electric currents into the earth during fault conditions. Safe grounding requires both an intentional grounding system buried below the earth's surface and an accidental ground temporarily established through contact between a person and the substation. Electric shock accidents can occur when high fault currents meet conditions that allow current to pass through a person, such as through soil with high potential gradients or direct contact between the body and two points of different potential. The risks of electric shock increase with current magnitude and duration, so high-speed fault clearing is important to reduce exposure time and injury risks.
PLCC: A promising futuristic technology!!!.. still in India we do not use it due to many reasons.... because PLCC, Power Line Carrier Communication, is an approach to utilize the existing power lines for the transmission of information.
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)Mayank Velani
This document provides information on earthing practices as outlined in the Indian Standard Code of Practice for Earthing from 1987. It discusses different earthing methods including reactance grounding and arc suppression coil grounding. Reactance grounding works by inserting a reactance between the neutral and ground to limit earth fault current. Arc suppression coil grounding uses an iron-cored coil connected between neutral and earth to balance out capacitive currents and limit fault current. The document explains how to determine the capacitance of a system and design an appropriately sized arc suppression coil to achieve resonant grounding conditions.
This document describes various protection schemes for transformers, including differential, restricted earth fault, overcurrent, and thermal protection.
1) Differential protection compares currents entering and leaving the transformer zone to detect internal faults. It provides the best protection for internal faults.
2) Restricted earth fault protection is used to detect high-resistance winding-to-core faults not detectable by differential relays. It uses a neutral current transformer and is sensitive to internal earth faults.
3) Overcurrent protection uses relays with current coils to detect overloads and faults above a pickup threshold. It also includes ground-fault protection.
The document discusses protection schemes for transformers. It describes faults that can occur in transformers such as open circuits, overheating, and winding short circuits. It then discusses different protection systems for transformers including Buchholz relays, earth fault relays, overcurrent relays, and differential protection systems. Differential protection systems operate by comparing currents from current transformers on both sides of the transformer and tripping the circuit breaker if a difference is detected, indicating an internal fault. The combination of protection schemes provides comprehensive protection for transformers.
Grounding in Power System Presentation
The presentation discusses the importance of grounding in power systems for safety, equipment protection, and building protection from lightning strikes. It covers types of grounding including solid grounding, resistance grounding, reactance grounding, and resonant grounding. Measurement instruments and calculation procedures for proper grounding are also reviewed. Lack of proper grounding can cause electric shocks, fires, and equipment damage. IEEE standards provide guidelines for industrial and commercial grounding systems.
The document discusses types of substations. There are several types including transmission substations, distribution substations, collector substations, converter substations, and switching stations. Substations can also be classified based on their voltage levels, whether they are indoor or outdoor, and their configuration. The key functions of substations include transforming voltage from high to low levels or vice versa, and isolating faulted portions of the electrical system. Substations contain important equipment like transformers, circuit breakers, and busbars.
HVDC (high-voltage direct current) is a highly efficient alternative for transmitting large amounts of electricity over long distances and for special purpose applications.
1) Over current occurs when electric current exceeds intended levels, potentially causing equipment damage from excess heat. It can be caused by short circuits, overloading, design flaws, or ground faults.
2) Over current relays contain a current coil. During normal operation, the magnetic effect is insufficient to trigger the relay. During over currents, the increased magnetic effect overcomes the restraint, moving the contact to isolate the circuit.
3) Over current relays come in instantaneous, definite time, and inverse time variations depending on their time of operation. Inverse time relays isolate faults faster for more severe over currents.
This document summarizes various protection schemes for power transformers, including:
1. Differential protection compares currents entering and leaving the transformer to detect internal faults.
2. Buchholz relay detects incipient faults by sensing gases produced from insulation breakdown, and can indicate the fault type.
3. Restricted earth fault protection detects high-resistance winding-to-core faults not seen by differential relays.
4. Overcurrent protection trips for overloads or external faults not isolated by other schemes.
5. Overfluxing protection monitors the voltage-to-frequency ratio to prevent damage from sustained overvoltages.
The United Arab Emirates has a power production capacity of 18.74 GW but lacks capacity during peak seasonal times due to increasing demand. It also lacks natural gas resources. The Gulf Cooperation Council began developing a regional power grid to help meet demand. Phase 3 of this grid will connect the southern system of the UAE. The UAE also plans to build 4 nuclear reactors to generate additional power. Electric power is transmitted through overhead transmission lines suspended by steel lattice towers for long distances. The document discusses the anatomy of transmission towers and the different types, configurations, and design considerations for efficient power transmission.
The document discusses different types of grounding systems used in electrical installations. It describes six common grounding systems: equipment grounds, static grounds, system grounds, maintenance grounds, electronic grounds, and lightning grounds. It provides details on each type, including their objectives and how they are implemented. The document also discusses factors to consider when designing grounding systems and recommendations for proper grounding practices.
The document discusses protection of alternators from various faults. It describes 7 types of faults that alternators require protection from: (1) failure of prime mover, (2) failure of field, (3) overcurrent, (4) overspeed, (5) overvoltage, (6) stator winding faults, and (7) unbalanced loading. It then provides details on differential protection and the Merz-Price circulating current scheme, which is commonly used to protect against stator winding faults. It also discusses limitations of this scheme and modified schemes for protection in other situations.
This paper presents 230 66 kV, substation grounding system and calculation results of required parameters. The grounding system is essential to protect people working or walking in the vicinity of earthed facilities and equipments against the danger of electric shock. This paper provides the floor surface either assures an effective insulation from earth potential or effectively equipment to a close mesh grid. Calculations of grounding grid system in the substation area which the top soil layer resistivity is less than the bottom layer resistivity, can lessen the number of ground rod used in the grid because the value of Ground Potential Rise GPR is insignificantly different. Essential equations are used in the design of grounding system to get desired parameters such as touch and step voltage criteria for safety, earth resistance, grid resistance, maximum grid current, minimum conductor size and electrode size, maximum fault current level and resistivity of soil. Calculations of three separate earthing body earth, neutral earth and main earthing are described. Zin Wah Aung | Aung Thike "Design of Grounding System for Substation" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-5 , August 2019, URL: https://www.ijtsrd.com/papers/ijtsrd26641.pdfPaper URL: https://www.ijtsrd.com/engineering/electrical-engineering/26641/design-of-grounding-system-for-substation/zin-wah-aung
This document proposes a model for an electric arc furnace used in steelmaking. It summarizes the typical electric arc furnace process in 5 stages and models key parameters like arc voltage, current, and power as nonlinear functions of arc length. The document presents measurements taken from an electric arc furnace over 9 transformer taps and 32 measurements per tap. It uses these measurements to develop empirical functions for modeling the electric arc furnace's resistance, reactance, and the resistance and reactance of the electric arc. These models are important for improving electric arc furnace productivity and efficiency by optimizing energy consumption and electrode wear.
This document discusses restricted earth fault (REF) protection schemes for transformers and generators. It explains that a REF scheme is needed to detect internal earth faults since they may not cause current to flow through the external overcurrent protection. A REF scheme works by summing the currents entering and exiting a protected zone using two sets of current transformers, and tripping if the sums are unequal, indicating an internal fault. Key elements of a REF scheme include the REF relay, stabilizing resistor to avoid spurious trips from CT mismatches, and specifying a high knee point voltage for the CTs. Examples of REF schemes for generators and transformer configurations are also provided.
The document discusses generator protection systems. It introduces the basic electrical quantities used for protection like current, voltage, phase angle and frequency. Protective relays use one or more of these quantities to detect faults. The document then discusses different types of relays and circuit breakers used for protection. It describes various protection zones like generator, transformer, bus, line and utilization equipment zones. The rest of the document elaborates on different protection schemes for generators including stator protection, rotor protection, loss of excitation protection and reverse power protection.
This document discusses different methods of grounding electrical systems, including solid grounding, resistance grounding, reactance grounding, and resonant groundings using a Peterson coil. Solid grounding directly connects the neutral point to earth, holding it at earth potential but allowing high fault currents. Resistance grounding limits fault current by connecting through a resistor. Reactance grounding uses an inductor instead of resistor. Resonant grounding with a Peterson coil adjusts the inductance to balance capacitive currents and prevent arcing faults.
Practical handbook-for-relay-protection-engineersSARAVANAN A
The ‘Hand Book’ covers the Code of Practice in Protection Circuitry including standard lead and device numbers, mode of connections at terminal strips, colour codes in multicore cables, Dos and Donts in execution. Also, principles of various protective relays and schemes including special protection schemes like differential,
restricted, directional and distance relays are explained with sketches. The norms of protection of generators, transformers, lines & Capacitor Banks are also given.
Substation grounding systems provide protection from electric shock hazards by dissipating electric currents into the earth during fault conditions. Safe grounding requires both an intentional grounding system buried below the earth's surface and an accidental ground temporarily established through contact between a person and the substation. Electric shock accidents can occur when high fault currents meet conditions that allow current to pass through a person, such as through soil with high potential gradients or direct contact between the body and two points of different potential. The risks of electric shock increase with current magnitude and duration, so high-speed fault clearing is important to reduce exposure time and injury risks.
PLCC: A promising futuristic technology!!!.. still in India we do not use it due to many reasons.... because PLCC, Power Line Carrier Communication, is an approach to utilize the existing power lines for the transmission of information.
IS : 3043 -1987 CODE OF PRACTICE FOR EARTHING(REACTANCE GROUNDING)Mayank Velani
This document provides information on earthing practices as outlined in the Indian Standard Code of Practice for Earthing from 1987. It discusses different earthing methods including reactance grounding and arc suppression coil grounding. Reactance grounding works by inserting a reactance between the neutral and ground to limit earth fault current. Arc suppression coil grounding uses an iron-cored coil connected between neutral and earth to balance out capacitive currents and limit fault current. The document explains how to determine the capacitance of a system and design an appropriately sized arc suppression coil to achieve resonant grounding conditions.
This document describes various protection schemes for transformers, including differential, restricted earth fault, overcurrent, and thermal protection.
1) Differential protection compares currents entering and leaving the transformer zone to detect internal faults. It provides the best protection for internal faults.
2) Restricted earth fault protection is used to detect high-resistance winding-to-core faults not detectable by differential relays. It uses a neutral current transformer and is sensitive to internal earth faults.
3) Overcurrent protection uses relays with current coils to detect overloads and faults above a pickup threshold. It also includes ground-fault protection.
The document discusses protection schemes for transformers. It describes faults that can occur in transformers such as open circuits, overheating, and winding short circuits. It then discusses different protection systems for transformers including Buchholz relays, earth fault relays, overcurrent relays, and differential protection systems. Differential protection systems operate by comparing currents from current transformers on both sides of the transformer and tripping the circuit breaker if a difference is detected, indicating an internal fault. The combination of protection schemes provides comprehensive protection for transformers.
Grounding in Power System Presentation
The presentation discusses the importance of grounding in power systems for safety, equipment protection, and building protection from lightning strikes. It covers types of grounding including solid grounding, resistance grounding, reactance grounding, and resonant grounding. Measurement instruments and calculation procedures for proper grounding are also reviewed. Lack of proper grounding can cause electric shocks, fires, and equipment damage. IEEE standards provide guidelines for industrial and commercial grounding systems.
The document discusses types of substations. There are several types including transmission substations, distribution substations, collector substations, converter substations, and switching stations. Substations can also be classified based on their voltage levels, whether they are indoor or outdoor, and their configuration. The key functions of substations include transforming voltage from high to low levels or vice versa, and isolating faulted portions of the electrical system. Substations contain important equipment like transformers, circuit breakers, and busbars.
HVDC (high-voltage direct current) is a highly efficient alternative for transmitting large amounts of electricity over long distances and for special purpose applications.
1) Over current occurs when electric current exceeds intended levels, potentially causing equipment damage from excess heat. It can be caused by short circuits, overloading, design flaws, or ground faults.
2) Over current relays contain a current coil. During normal operation, the magnetic effect is insufficient to trigger the relay. During over currents, the increased magnetic effect overcomes the restraint, moving the contact to isolate the circuit.
3) Over current relays come in instantaneous, definite time, and inverse time variations depending on their time of operation. Inverse time relays isolate faults faster for more severe over currents.
This document summarizes various protection schemes for power transformers, including:
1. Differential protection compares currents entering and leaving the transformer to detect internal faults.
2. Buchholz relay detects incipient faults by sensing gases produced from insulation breakdown, and can indicate the fault type.
3. Restricted earth fault protection detects high-resistance winding-to-core faults not seen by differential relays.
4. Overcurrent protection trips for overloads or external faults not isolated by other schemes.
5. Overfluxing protection monitors the voltage-to-frequency ratio to prevent damage from sustained overvoltages.
The United Arab Emirates has a power production capacity of 18.74 GW but lacks capacity during peak seasonal times due to increasing demand. It also lacks natural gas resources. The Gulf Cooperation Council began developing a regional power grid to help meet demand. Phase 3 of this grid will connect the southern system of the UAE. The UAE also plans to build 4 nuclear reactors to generate additional power. Electric power is transmitted through overhead transmission lines suspended by steel lattice towers for long distances. The document discusses the anatomy of transmission towers and the different types, configurations, and design considerations for efficient power transmission.
The document discusses different types of grounding systems used in electrical installations. It describes six common grounding systems: equipment grounds, static grounds, system grounds, maintenance grounds, electronic grounds, and lightning grounds. It provides details on each type, including their objectives and how they are implemented. The document also discusses factors to consider when designing grounding systems and recommendations for proper grounding practices.
The document discusses protection of alternators from various faults. It describes 7 types of faults that alternators require protection from: (1) failure of prime mover, (2) failure of field, (3) overcurrent, (4) overspeed, (5) overvoltage, (6) stator winding faults, and (7) unbalanced loading. It then provides details on differential protection and the Merz-Price circulating current scheme, which is commonly used to protect against stator winding faults. It also discusses limitations of this scheme and modified schemes for protection in other situations.
This paper presents 230 66 kV, substation grounding system and calculation results of required parameters. The grounding system is essential to protect people working or walking in the vicinity of earthed facilities and equipments against the danger of electric shock. This paper provides the floor surface either assures an effective insulation from earth potential or effectively equipment to a close mesh grid. Calculations of grounding grid system in the substation area which the top soil layer resistivity is less than the bottom layer resistivity, can lessen the number of ground rod used in the grid because the value of Ground Potential Rise GPR is insignificantly different. Essential equations are used in the design of grounding system to get desired parameters such as touch and step voltage criteria for safety, earth resistance, grid resistance, maximum grid current, minimum conductor size and electrode size, maximum fault current level and resistivity of soil. Calculations of three separate earthing body earth, neutral earth and main earthing are described. Zin Wah Aung | Aung Thike "Design of Grounding System for Substation" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-5 , August 2019, URL: https://www.ijtsrd.com/papers/ijtsrd26641.pdfPaper URL: https://www.ijtsrd.com/engineering/electrical-engineering/26641/design-of-grounding-system-for-substation/zin-wah-aung
This document proposes a model for an electric arc furnace used in steelmaking. It summarizes the typical electric arc furnace process in 5 stages and models key parameters like arc voltage, current, and power as nonlinear functions of arc length. The document presents measurements taken from an electric arc furnace over 9 transformer taps and 32 measurements per tap. It uses these measurements to develop empirical functions for modeling the electric arc furnace's resistance, reactance, and the resistance and reactance of the electric arc. These models are important for improving electric arc furnace productivity and efficiency by optimizing energy consumption and electrode wear.
This document analyzes grounding considerations for large kVA pad-mount transformers. It summarizes the assumptions made in analyzing different transformer voltages and kVA sizes up to 5,000 kVA. Calculations of ground potential rise, touch potential and step potential are performed and compared to safety limits. Results show the standard two ground rod system may not provide adequate protection for transformers over 750 kVA or higher secondary voltages. Larger or engineered grounding systems are recommended for safety.
The document discusses grounding considerations for large kVA pad-mount transformers. It analyzes grounding systems for pad-mounts up to 5,000 kVA to ensure step and touch potentials are limited to safe levels. Calculations were performed using IEEE standards to determine the maximum allowable touch and step voltages. Results showed the standard two ground rod system may not limit surface potentials for all sizes, while the Canadian four rod standard provided better but still insufficient results for some larger transformers. Recommendations are made to properly design grounding to render pad-mounts safe for the public and workers.
The document mentions the following with tentative quantities:
1. List of 17 nos. of main equipment
2. List of 15 nos. of miscellaneous equipment
3. List of 16 nos. of civil works required
4. List of 8 nos. of lattice type equipment
5. List of 11 nos. of foundations required
Copper Clad Steel and Copper Clad Aluminium Conductor is best Solution to Replace GI Flat Strip or Copper Flat Strip for Earthing Purpose Offering by JMV LPS LTD India Internationa Standard Follow IEC/IEEE and ASTM B228-4
The document discusses challenges in designing grounding systems for wind and solar power plants for personal safety. It compares using copper conductors versus copper clad steel conductors. While copper provides better electrical performance, the differences when using copper clad steel are manageable within engineering design. The document also examines requirements for bare ground removal from cable trenches in electrical codes and alternatives to a bare ground conductor such as unjacketed or semi-conductive jacketed cable. Grounding impedance and ground potential rise calculations were performed both with and without a bare ground conductor in the trench.
The document discusses shunt reactors used in power systems. Shunt reactors are installed to reduce grid voltage during off-peak periods when excess reactive power leads to high voltages. They absorb reactive power through magnetizing currents, thereby reducing voltage. The document recommends installing 25 additional shunt reactors of 63 MVAR each in the southern grid to maintain voltages between 416-420 kV during off-peak hours. It provides background on why reactors are needed and describes the basic operating principles and components of shunt reactors.
Principles of Cable Sizing; current carrying capacity, voltage drop, short circuit.
Cables are often the last component considered during system design even if in many situations cables are the true system’s lifeline: if a cable fails, the entire system may stop. Cable reliability is therefore extremely important, then a cable system should be engineered to last the life of the system in the installation environment for the required application. Environments in which cable systems are being used are often challenging, as extreme temperatures, chemicals, abrasion, and extensive flexing. These variables have a direct impact on the materials used for cable insulation and jacketing as well as the construction of the cable. Using a systematic approach will help ensure that designer select the best cable for the required application in the installation environment. This lessons will provide students main guidelines for perform this approach.
The document outlines the supply, erection, testing and commissioning of various electrical equipment items at BHEL Haridwar for a 2.8 MW resistance furnace. The items include:
1. Outgoing VCB panels and power transformers from major manufacturers.
2. An LT distribution panel with incomers, feeders and a bus coupler.
3. Copper bus duct sets and HT and LT cables to be supplied.
4. Additional works like earthing pits are also specified. The scope of work, terms, project schedule and responsibilities of both parties are defined.
The document provides instructions for determining the soil resistivity and installing an earthing system for a chlorine contact tank. It specifies that:
1) The surveyor should connect the earthing cable to rebar at the same level as the finished ground level around the tank, which is at elevation +578.15m or deeper according to the drawings.
2) A good connection should be made between the rebar and bare copper conductor using a clamp. Vertical rebar should be used for the connection.
3) Schwarz's method should be used to calculate the soil resistivity and design the earthing system, taking into account factors like soil type, moisture content, conductor size, rod length, and number
The document discusses insulation coordination studies for selecting insulation strength consistent with expected overvoltages. It defines insulation coordination and describes understanding insulation stresses and strength. Methods for controlling stresses include surge arresters, pre-insertion resistors, and synchronous closing control. Insulation coordination studies evaluate overvoltages from very fast transients, lightning, switching, and temporary conditions to verify protection of electrical equipment. An example application performs a lightning surge analysis of a 550kV gas-insulated substation to evaluate protective margins of equipment.
At the outset we wish to thank you for the curtsey and excellent response from you and active interest in taking a comprehensive view of modern safe Lightning Protection / Earthing and the underlying scientific principles as we posted in our Linkedin Profile, which is for your ready reference.
This document provides an overview of electrical power transmission in India. It discusses the components of transmission lines including conductors, spacers, and supports. It also covers transmission line design considerations such as voltage levels, ground clearances, conductor spacing, and tower heights. The document outlines India's existing transmission system and some issues in further developing the system such as right of way, regulation of power flows, and integration of new technologies like HVDC transmission and gas insulated substations.
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWSyamsirAbduh2
To be able to secure and safety the equipment and the workers who work in the power plant area Berau 2 x 7 MW, of course, required the earthing system design quality, reliable and efficient whereby the grounding grid resistance, voltage step and touch voltage according to the calculations contained in IEEE Std 80 -2000. This research will discuss the evaluation of system design with respect to the value of earthing resistance grounding grid, mesh voltage and step voltage. Evaluation parameters - parameters according to calculations published in IEEE Std 80-2000. Results from this study is the need for improvements to the design value of the voltage step and touch voltage is actually one - each 219.03 V and 383.29 V, which is greater than the voltage step and touch voltages are allowed each - amounting to 164.86 V for weight 50 kg; 223.13 V for weights 70 kg and 128.21 V to weight 50 kg; 173.53 V to 70 kg weight.
This document discusses the analysis of grounding systems for substations. It analyzes the grounding system design for a 220/132/33 kV substation in India as a case study. The key factors considered in grounding system design are discussed, including fault current magnitude, transient overvoltage protection, and safety. Calculations are shown for sizing conductors, determining grid resistance and step/touch voltages based on soil resistivity and other input parameters. The results found that the designed grounding system met safety requirements, with attainable step and touch voltages below tolerable limits and a grid resistance under 1 ohm. Proper grounding system analysis and design is important for safety during faults.
CHAPTER 2 Design of Building Electrical Systems (2).pptx.pptxLiewChiaPing
The document provides information on designing electrical systems for buildings and industry. It discusses:
- Design methodology including calculating panelboard ampere ratings from load data.
- Electrical wiring specifications and options for supply voltage in residential and commercial buildings.
- Examples of schematics for lighting circuits, socket outlets, and single and three-phase consumer wiring.
- Considerations for designing domestic and industrial electrical systems including load calculations and protection devices.
The document describes a project report on three phase fault analysis with auto reset. It includes a block diagram of the project, descriptions of the hardware components used including transformers, voltage regulators, 555 timers, and relays. It also includes schematic and layout diagrams and details on testing the hardware. The system is designed to automatically disconnect the three phase power supply in the event of a fault, with the supply automatically resetting for temporary faults but remaining tripped for permanent faults.
A LOW POWER, LOW PHASE NOISE CMOS LC OSCILLATORIJEEE
The document describes a low power, low phase noise CMOS LC oscillator designed and simulated using a 180nm CMOS technology. Key results include:
1) The oscillator achieves a phase noise of -96 dBc/Hz at 1MHz with a tuning range of 4.8-8.3 GHz by varying the control voltage from 0-2V.
2) It consumes 3.8mW of power at an output power of -8.92dBm.
3) Simulation results show the tuning range, output waveform, and phase noise performance meet design goals for a low power VCO for wireless applications like 5G.
A LOW POWER, LOW PHASE NOISE CMOS LC OSCILLATORIJEEE
In this paper a Double Cross Coupled Inductor capacitor based Voltage Control Oscillator (LC-VCO) is designed. In the proposed circuit the phase noise, tuning range with respect to control voltage, output power and the power dissipation of the circuit is analysed. Phase noise of approximate -96 dBc/Hz at frequency of 1MHz, frequency tuning range of 4.8 to 8.3 GHz (corresponding to 53.0% tuning range) obtained by varying the control voltage from 0 to 2.0 V, Output power of circuit -8.92 dBm at 50 Ohm resistance terminal and the power consumption of Circuit is 3.8 mW. This VCO are designed for 5.5 GHz. The circuit is designed on the UMC 180nm CMOS technology and all the simulation results are obtained using cadence SPECTRE Simulator.
1. Grounding Design of Kano Hydro Power
Station(1x8MW+1x2MW) in Kano State of
Nigeria
AUTHOR
PANKAJ SACHDEVA,JOINT GROUP PRESIDENT,SKIPPER ELECTRICAL(I) LIMITED.
M.L.SACHDEVA,FORMER CE,CEA AND SR. CONSULTANT,SKIPPER ELECTRICAL(I) LIMITED
S.L.NARASIMHAN,FORMER EE,K.P.C,BANGALORE AND DIRECTOR(ELECTRICAL),BHEC PVT. LTD
PRESENTED BY
SOURAV GHOSH,ENGINEER AT SKIPPER ELECTRICAL(I) LIMITED
2. ABOUT M/S SKIPPER.
PRESENCE IN 50 COUNTRIES,MOSTLY EXPORT ORIENTD
MANUFACTURING PLANT :
IN INDIA -3 NOS. BHIWADI
IN NIGERIA – 2NOS LOGAS
IN DUBAI - 1No
RANGE OF PRODUCT PRESNTLY UPTO 220KV SYSTEM & UPGRADING TO 400KV.
POWER TRANSFORMER- UPTO 65MVA,220KV S/S
CT,PT,ISOLATORS,CBs
C&R PANELS, CAPACITOR,LT PANELS ETC.
PACKAGED S/S AND MOBILE SUBSTATION
PLANNING, DESIGN, ERECTION, TESTING & COMMISSIONING OF AIS and GIS
SCADA AND COMMUNICATION
NEW TRANSFORMER PLANT - UPTO 800KV TR.( Under Building)
Railway Electrification
3. SYNOPSIS
THIS PAPER DEALS WITH GROUND MAT DESIGN OF POWER
HOUSE AND SWITCHYARD WITH DIFFERENT SOIL RESISTIVITY
VALUES AND DIFFERENT CALCULATED TOUCH AND STEP
POTENTIALS WHICH IN SOME CASES EXCEED THE LIMIT
VALUES
SUGGESTIONS ON REVIEWING OF PROVISIONS OF THE
GROUND MAT DESIGN OF SMALL HYDRO POWER HOUSES.
4. INTRODUCTION
GENERATING STATIONS AND SWITCHYARDS HAVE TO BE
EFFECTIVELY EARTHED FROM SAFETY CONSIDERATION
COVERED UNDER LEGAL PROVISIONS OF ELECTRICITY
REGULATIONS, ACTS, COMMISSIONS, ETC.
GUIDANCE PROVIDED UNDER SAFETY CODES AND STANDARDS.
EACH COUNTRY HAS HIS OWN GOVERNING REGULATIONS AND
STANDARDS / CODES FOR GROUNDING OF ELECTRICAL
INSTALLATIONS.
5. DESIGN CONCEPT
THE DESIGN OF GROUND MAT IS TAKEN UP CONSIDERING THE
FOLLOWING:
PLOT LAY OUT OF S/S / LAYOUT OF A POWER HOUSE(L X B )
SOIL RESISTIVITY (OHM-M)
SURFACE RESISTIVITY -RIVER STONE/CRUSHED STONE/WASHED
GRANITE/ CONCRETE ( OHM-M)
MAXIMUM PERMISSIBLE GROUND RESISTANCE OF SUBSTATION
/POWER HOUSE (OHM)
SHORT CIRCUIT CURRENT (KA) AND ITS DURATION (SEC)
DURATION OF SHOCK (SEC)
DEPTH OF BURIAL OF GROUND MAT MEMBER (MM)
MATERIAL OF GROUND MAT ( STEEL/COPPER)
STEP POTENTIAL ( VOLTS)
TOUCH POTENTIAL ( VOLTS)
6. MEASUREMENT OF SOIL RESISTIVITY
A TYPICAL EARTH TESTER HAS FOUR (4)
TERMINALS.C1, P1, C2, P2 AND FOUR (4) ELECTRODES
SUPPLIED WITH THE INSTRUMENT ARE DRIVEN IN THE
GROUND AT SPECIFIED EQUAL DISTANCES THRU CABLE AND
CONNECTED TO THE INSTRUMENT IN THE ORDER OF C1, P1
AND P2, C2.
SPECIFIC RESISTIVITY =2 Π.A. R
8. Notes
(i)DEPTH OF BURIED ELECTRODES ASSUMED
NEGLIGIBLE AS COMPARED TO SPACING BETWEEN
ELECTRODES.
ii)MORE THE DISTANCE BETWEEN ELECTRODES
MORE THE DEPTH AT WHICH SOIL RESISTIVITY IS
MEASURED.
iii) IF SOIL OF HIGH RESISTIVITY IS AT TOP
SURFACE AND SOIL RESISTIVITY AT DEEP LEVEL IS
TO BE MEASURED, TWO OR MORE RESONANCE
MODEL OF SOIL RESISTIVITY MEASUREMENT IS
ADOPTED.
9. STANDARDS AND CODES
IS: 3043(4th Reprint June 2007 including Amendment No 1/
Jan 2007 and Amendment 2 / Jan 2010): Code of Practice for
Earthing Electrical Installations.
CBI&P Publication No 223: Design of Earthing Mat of High
Voltage Substations
IEEE 80-2000: Guide for Safety in AC Substation Grounding
IEEE 665-1995: Guide for Generating Station Grounding.
BS: 7430 -1998: Code of Practice for Earthing
10. Estimation OF EARTHHING MATERIAL
PRELIMINARY SOIL RESISTIVITY ( INITIAL ESTIMATION)
AS THE SWITCHYARD PLANNED TO BE ERECTED FIRST, THE SOIL RESISTIVITY WAS
MEASURED OVER A LEVEL PORTION OF LAND EARMARKED FOR POWER HOUSE.
THE SOIL RESISTIVITY MEASSUREMENT MEASUREMENT= 80 OHM-M
EARTHING MATERIAL ( COPPER ) ESTIMATED
PROCUREMENT ACTION INITIATED
FINAL SOIL RESISTIVITY (FINAL MEASUREMENT & ESTIMATION)
THE EXCAVATION OF POWER HOUSE COMPLETED AND SWITCHYARD APPROX LEVELLED
SOIL RESISTIVITY LEVELS MEASURED AS UNDER
MAIN POWER HOUSE ( 8MW RBU) - 670 OHM-M
CANAL BAY UNIT ( 2MW) - 120 OHM-M
SWITCHGEAR ROOM & SERVICE BAY - 120 OHM-M
OUT DOOR SWITCHYARD (ODY) - 120 OHM-M
11. POWER HOUSE
THE SITE OF POWER HOUSE IS EXCAVATED FIRST TO THE DESIRED
GRADES AND SITE IS LEVELED.
THE GROUND MAT MEMBERS ARE LAID ON THE SURFACE OF CLEANED
ROCK IN CASE OF ROCKY SURFACE OR BORROWS MADE AT SPECIFIED
DEPTH (650MM) IN FISSURED ROCK OR HARD SOIL.
THE GROUND MEMBERS AND RISERS (WHERE REQUIRED) ARE JOINTED
AT CROSSING POINTS BY WELDING/ BRAZING/ EXOTHERMIC MOLD.
THE CONCRETE FLOOR IS LAID DOWN. THE END MEMBERS (X AND Y
AXIS) OF GROUND MAT EXTENDED BEYOND CONCRETE LAYER ARE
LEFT FOR EXTENDING TO NEXT FLOOR ELEVATION FOR LAYING
ANOTHER RING OF MAT AT THAT FLOOR FOR MAKING CONNECTIONS
TO EQUIPMENT AND SO ON.
12. DESIGN STEPS
AREA OF CONDUCTOR,
𝐼 𝑆𝐶
𝐴
=
𝐾
𝑡 𝑐
𝐴 =
𝐼 𝑆𝐶× 𝑡 𝑐
𝐾
(AS PER IS: 3043 CL. NO 12.2.2.1)
SPACING FACTOR FOR MESH VOLTAGE = Km
𝐾𝑚 =
1
2𝜋
ln
𝐷2
16ℎ𝑑
+
𝐷 + 2ℎ 2
8𝐷𝑑
−
ℎ
4𝑑
+
𝐾||
𝐾ℎ
ln
8
𝜋 2𝑛 − 1
CHECK FOR ADEQUACY OF (L) FOR E STEP AND E MESH
ESTEP (TOLERABLE) = ( RK +6CS X PS)… (AS PER EQ -30 OF
IEEE-80)
13. DESIGN STEPS
IK = CURRENT RMS FLOWING THRU BODY
WEIGHT 70KG= 0.157 / √ TS
RK IS THE RESISTANCE OF BODY IN OHMS = 1000 OHMS
𝐸𝑆𝑡𝑒𝑝𝑐𝑎𝑙𝑐𝑢𝑙𝑎𝑡𝑒𝑑 =
𝐾𝑠 𝐾 𝐼 𝐼 𝑆𝐶 𝜌
𝐿
(As per Eq -33 of IEEE-80)
𝐸 𝑇𝑜𝑢𝑐ℎ(𝑡𝑜𝑙𝑒𝑟𝑎𝑏𝑙𝑒) =
𝑅 𝐾+1.5𝐶𝑠 𝜌𝑠 0.157
𝑡𝑠
(As per Eq -80 of IEEE-80)
CALCULATION OF GRID RESISTANCE (As per IS 3043 Cl No
9.2.3 )
𝑹 𝑮 =
𝟏𝟎𝟎𝝆
𝟐𝝅𝑳
𝒍𝒏 𝟒𝑳
𝒕
𝛀
14. S,No Details of Earthing System Resistance Symbols
1 Single Earth Electrode
𝑅 =
100𝜌
2𝜋
𝑙𝑛
4𝑙
𝑑
𝜌=Soil Res()
l=Length of strip(cm)
d= Dia of rod (cm)
2 Multiple Earth Electrode 𝑎 =
𝜌
2𝜋𝑅𝑖 𝑆
𝑅 = 𝑅𝑖
1 + 𝜆𝑎
𝑛
Ri=Resis of one rod in isol
𝜌=Soil Res()
n= Nos of rods
S=Dist between rods (m)
= Factor as per Table
3 Strip Conductor Earthing
𝑅 =
100𝜌
2𝜋
ln
2𝑙2
𝑤𝑡
𝜌=Soil Res()
l=Length of strip(cm)
W= depth of burial of
electrode (cm)
t=width (cm)
4 Earthing Plate
𝑅 =
𝜌
4
𝜋
𝐴
𝜌=Soil Res()
A= Area of both side of
Plate(m2)
15. Factor for Parallel Electrodes
No of Electrodes Factor
2 1.00
3 1.65
4 2.15
5 2.54
6 2.87
7 3.15
8 3.39
9 3.61
10 3.81
16. GROUND MAT IN POWER HOUSE
THE GROUNDING SYSTEM IN A POWER HOUSE
COMPRISES OF:
GROUNDING SYSTEM FOR POWER HOUSE (PH)
GROUNDING SYSTEM FOR SWITCHYARD (SY)
17. DESIGN ASPECT OF GROUND MAT
LIMIT THE OVERALL POTENTIAL RISE.
PROTECT PERSONNEL & DEVICES FROM OVER VOLTAGES.
LOW IMPEDANCE PATH TO FAULT CURRENT FOR RELIABLE &
PROMPT OPERATION OF PROTECTIVE DEVICES DURING
GROUND FAULT.
STEP POTENTIAL WITHIN THE PERMISSIBLE LIMIT.
TOUCH POTENTIAL WITHIN THE PERMISSBLE LIMIT.
18. SECURITY AND SAFETY FENCE AROUND SWITCHYARD.
MANDATORY CONNECTING ALL THE METALLIC PARTS
OR STATIC PARTS OF ELECTRICAL EQUIPMENT
MINIMUM AT TWO POINTS.
EARTHING OF LIGHTNING PROTECTIVE DEVICES.
19. DESIGN ASPECT OF GROUND MAT
SOIL AND SURFACE RESISTIVITY
SIZE( DEPENDING ON AREA) AND TYPE OF EARTH SYSTEM
DEPTH OF BURIAL OF ELECTRODE
MATERIAL OF GROUND MAT
MOISTURE CONTENT OF THE SOIL.
SHORT CIRCUIT RATING AND DURATION OF SHORT CIRCUIT
DURATION OF SHOCK
PERMISSIBLE GROUNDING RESISTANCE
PERMISSIBLE TOUCH AND STEP POTENTIALS
20. DATA AND DESIGN
THE FAULT LEVEL AT 33KV LEVEL (STEP UP VOLTAGE) HAS
BEEN CONSIDERED AS 31.5KA
THE DESIGN OF EARTH MAT 60% OF 31.5 KA HAS BEEN
CONSIDERED IN ACCORDANCE WITH BS-7354-CLAUSE NO
7.3.2
THE MATERIAL OF EARTH MAT HAS BEEN CONSIDERED AS
“COPPER FLAT” AND COPPER CLAD STEEL RODS
21. BASED ON THE AVAILABLE INPUTS,THE FOLLOWING PARAMETERS
HAVE BEEN CONSIDERED FOR PRELIMINARY DESIGN IN
ACCORDANCE WITH IEEE-80
INPUT DATA (Tiga Power House)
Sl. no Symbol Descriptions Values PH Values ODY Units
1 Isc Fault current (60% of 31.5kA) 18900 18900 Amps
2 ρ
Soil resistivity (average of P1 & P2
is 75.45Ω & 81.02Ω) 80 80 Ω-m
3 ρs Surface layer resistivity 3000 3000 Ω-m
4 D
Spacing between parallel
conductor 4 1.6 Metre
5 LPH Length of PH and ODY 36 41.6 Metre
6 BPH Breadth of PH and ODY 28 22.4 Metre
22. SUMMARY OF THE RESULT
Tolerable Calculated
Power House Step voltage
(ESTEP)
3938.839 V > 653.24 V
Touch
voltage(ETOUCH)
1151.23 V EMESH
calculated >
801.17 V
Switch Yard Step voltage
(ESTEP)
3938.83 V > 2204.41 V
Touch voltage
(ETOUCH)
1151.23 V EMESH
calculated >
685.02V
Grid resistance 0.117Ω
23. DESIGN AND ITS RESULTS OF GROUND MAT OF POWER HOUSE AFTER
EXCAVATION COMPLETED
INPUT DATA
Sl. no
Symbol Descriptions
Values PH
8MW & TRL
Values
PH-2MW
Values
ODY
Values SB &
SG room
Units
1 Isc Fault current (60% of 31.5kA) 18900 18900 18900 18900 Amps
2 Ρ Soil resistivity 670.5 112 112 112 Ω-m
3 ρs Surface layer resistivity 5000 5000 5000 5000 Ω-m
4 D
Equivalent Diameter of the grid
conductor 0.020 0.020 0.020 0.020 Metre
5 D
Spacing between parallel
conductor
1.5 3 4 4 Metre
6
L Length of PH, ODY & Service bay
including switch gear room
16.7 12 53.5
28
Metre
7
B Breadth of PH, ODY & Service bay
including switch gear room
23.4 23.4 38.75
23.4
Metre
24. SUMMARY OF THE RESULT
Location Particulars Tolerable Calculated Limits
Power House 8MW Step voltage (ESTEP ) 6483.32 V < 12590.27 V Unsafe
Touch voltage (ETOUCH ) 1787.35V < EMESH calculated 1952.42 V Unsafe
Grid resistance RG 0.364 Ω Safe
Power House 2MW Step voltage (ESTEP ) 6416.71V > 492.07 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated 396.784 V Safe
Grid resistance RG 0.061Ω Safe
Switch yard Step voltage (ESTEP ) 6416.71V > 715.70 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated 579.43 V Safe
Grid resistance RG 0.061 Ω Safe
Service bay & Switch
gear room
Step voltage (ESTEP ) 6416.71 V > 774.68 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated 540.62 V Safe
Grid resistance RG 0.061 Ω Safe
25. TO LIMIT THE STEP AND TOUCH POTENTIAL
WITH IN POWER HOUSE
IN CASE OF HIGH RESISTIVITY SOIL, IT HAS BEEN REVEALED THAT IT
IS DIFFICULT TO MEET THE SAFETY CRITERIA OF TOUCH AND STEP
POTENTIALS.
IT HAS BEEN FOUND THAT LARGE LAND AREA IS REQUIRED FOR
MEETING THE REQUIREMENT.
FOR CONSIDERING THE COST EFFECTIVE SOLUTION, IT HAS BEEN
NECESSARY TO RE-EXAMINE THE REQUIREMENT
26. IEEE-665,GUIDE FOR GENERATING STATION
GROUNDING
CL NO 5.1: GROUNDING PRINCIPLE STIPULATES THAT
TOUCH AND STEP POTENTIAL SHALL MEET THE
PERMISSIBLE LIMITS
CL NO 5.2.7 STIPULATES THAT “THE MAXIMUM
ALLOWABLE TOUCH AND STEP VOLTAGES ARE THE
CRITERIA THAT SHOULD BE MET TO ENSURE A SAFE
DESIGN. IF THE TOUCH AND STEP VOLTAGES OF THE
GRID DESIGN ARE BELOW THE MAXIMUM VALUES, THEN
THE DESIGN IS CONSIDERED ADEQUATE.”
27. IEEE-665,GUIDE FOR GENERATING
STATION GROUNDING
CL NO 5.2.2 STATES THAT GENERATING STATIONS DIFFER FROM
SUBSTATIONS IN THAT THE PERSONNEL TO BE PROTECTED ARE
GENERALLY WORKING INDOORS. BECAUSE THEY ARE NOT IN DIRECT
CONTACT WITH THE EARTH OR WITH A LAYER OF CRUSHED ROCK
COVERING THE EARTH, THEY ARE NOT EXPOSED TO MANY OF THE
STEP AND TOUCH VOLTAGE CONDITIONS THAT PERSONNEL IN
SUBSTATIONS ARE EXPOSED.
THE CEA NOTIFICATION NO-211 DATED 20TH AUG 2010 ALSO STATES
THAT TOUCH AND STEP POTENTIAL SHALL BE MAINTAINED WITHIN
ACCEPTABLE LIMITS.
28. DELIBERATION
ACCORDINGLY, TAKING COGNIZANCE OF
PRACTICES IN VOGUE IN VARIOUS HYDRO POWER
STATIONS, THE CRITERIA FOR STEP AND TOUCH
POTENTIAL HAS NOT BEEN IGNORED AND
ADOPTED AS CRITERIA FOR SAFE DESIGN BUT
THIS NEEDS TO BE DELIBERATED IN THE
CONFERENCE.
29. SURFACE LAYER RESISTIVITY
IN THE PRELIMINARY DESIGN CALCULATIONS, THE SURFACE LAYER
RESISTIVITY WAS CONSIDERED AS 5000 Ω- M.
THE VALUES INDICATED FOR DRY AND WET CONDITIONS FOR THE
VARIOUS SURFACE MATERIALS ARE WIDELY VARYING VIZ: FOR
CONCRETE UNDER DRY CONDITION IT IS 1X106 TO 1X109OHM-M AND
21 TO 100 OHM-M FOR WET CONDITIONS.
IT IS ALSO INDICATES THAT 1X109 IS USED FOR OVEN DRIED
CONCRETE.
THE VALUE OF 10,000 Ω M WAS CONSIDERED AS CONCRETE MAY NOT
BE FULLY DRIED AT MIV FLOOR LEVEL.
30. FINAL DESIGN OF GROUND MAT OF POWER HOUSE
MAIN PURPOSE OF THIS REWORK HAS BEEN TO UNDERTAKE SAFE
DESIGNING AND COST EFFECTIVE GROUNDING SYSTEMS FOR TIGA HEP.
TO ADOPT SAFE LIMITS OF TOUCH AND STEP POTENTIAL INSIDE THE
POWER HOUSE WITHOUT SATELLITE GRID STATION AND SAVE COST.
TO CONSIDER SURFACE RESISTIVITY VALUE OF CONCRETE AS 10,000 Ω
INSIDE THE POWER HOUSE AND THAT OF WASHED QUARTZ AS 5,000 Ω IN
SWITCH YARD. WITH THE CHANGE IN THE SURFACE RESISTIVITY VALUES,
THE SAFE LIMITS OF E TOUCH AND E STEP OF EARTH MAT WERE ALSO
ACHIEVED IN 8MW PORTION OF POWER HOUSE AND THIS ALSO
RESULTED IN REDUCTION IN THE MATERIAL REQUIRED FOR EARTH MAT.
31. FINAL DESIGN OF GROUND MAT
INPUT DATA
Sl. no Symbol Descriptions Values
PH 8MW
& TRP
Values
PH-
2MW
Values
ODY
Values SB &
SG room
Units
1 Isc
Fault current (60% of
31.5kA) 18900 18900 18900 18900 Amps
2 ρ Soil resistiviy 670.5 112 112 112 Ω-m
3 ρs Surface layer resistivity 10000 10000 5000 10000 Ω-m
4 D
Spacing between parallel
conductor
1.5 3 4 4 Metre
5
L
Length of PH, ODY &
Service bay including
switch gear room as per
excavated profile
82.3 12.8 53.5 28.5 Metre
6
B
Breadth of PH, ODY &
Service bay including
switch gear room
22.5 22.5 38.75
22.5
Metre
32. SUMMARY OF THE RESULT
Location Particulars Tolerable Calculated Limits
Power house 8MW Step voltage (ESTEP ) 12619.39
V
> 7886.36 Safe
Touch voltage (ETOUCH ) 3319.37 > EMESH
calculated
1692.44 Safe
Grid resistance RG 0.42 Ω Safe
Power house 2MW Step voltage (ESTEP ) 12611.39V > 351.90 Safe
Touch voltage (ETOUCH ) 3319.37 > EMESH
calculated
340.97 V Safe
Grid resistance RG 0.053Ω Safe
Switch yard Step voltage (ESTEP ) 6466.71 > 488.51V Safe
Touch voltage (ETOUCH ) 1170.78V > EMESH
calculated
501.60 V Safe
Grid resistance RG 0.053 Ω Safe
Service bay & Switch
gear room
Step voltage (ESTEP ) 12611.39
V
> 346.56 V Safe
Touch voltage (ETOUCH ) 3319.37 > EMESH
calculated
414.18 Safe
33. ISSUES FOR DELIBERATION OF CONFERENCE
THE DESIGN OF GROUNDING MAT OF POWER HOUSES AND EHV
SUBSTATIONS IS CARRIED OUT LARGELY BASED ON IEEE80-2000
INCLUDING POWER HOUSE PROVISIONS OF IEEE 665-1997. THE
DESIGN OF GROUND MAT ATTAINS CRITICALITY WHEN SOIL
RESISTIVITY IS HIGH AND INHERITED SMALL GROUND AREA IN
CASE OF SMALL POWER HOUSES (SPH). THE FOLLOWING TOPICS
ARE LISTED FOR CONSIDERATION OF THE INTERNATIONAL
CONFERENCE
34. SOIL RESISTIVITY
UNIFORM SURFACE RESISTIVITY MEASURED AT THE SURFACE OF
POWER HOUSE AND SWITCH YARD WITH CONVENTIONAL METHOD OF
MEASUREMENT (80 OHM-M)]
AS THE EXCAVATION AT HIGHER LEVEL FOR 2MW GEN UNIT AND 8MW
GEN UNIT WAS COMPLETED AND SOIL RESISTIVITY WAS MEASURED AT
BOTH THE GEN UNITS LEVELS, SWITCHGEAR CONTROL & SERVICE
BAY AND ODY
THE SOIL RESISTIVITY AT ALL LOCATIONS EXCEPT 8MW UNIT WAS
MEASURED AS 120 OHM-M WHEREAS SOIL RESISTIVITY AT 8MW UNIT
WAS MEASURED AS 670 OHM-M.
THIS WAS COMPARATIVELY HIGH SOIL RESISTIVITY AND SMALL POWER
HOUSE SURROUNDED AREA
35. DESIGN OF GROUND MAT
IN IEEE 665, THE SAID STANDARD DOES NOT INSIST FOR
MEETING TOUCH AND STEP POTENTIAL REQUIREMENT INSIDE
POWER HOUSE.
OPERATORS DURING WORKING IN THE POWER HOUSE DONOT
STEP OUT OF POWER HOUSE AND DANGER OF DIFFERENT
VOLTAGE GRADIENT CAN BE AVOIDED BY PROVIDING SOME
ROUNDS OF GROUNDING MATERIAL (COPPER) AROUND THE
POWER HOUSE.
THIS IS SIMILAR TO EXTENDING THE GROUND MAT OF S/S
OUTSIDE THE FENCE TO PROTECT FROM DANGEROUS VOLTAGES
WHEN UN-AUTHORIZED PERSONNEL TOUCH THE FENCE FROM
OUTSIDE.
36. IT WAS CONSIDER TO USE SURFACE RESISTIVITY OF CONCRETE AS
10,000 OHM-M INSTEAD OF 5000 OHM-M. ON REVISION OF
CALCULATION IT HAS BEEN OBSERVED THAT TOUCH AND STEP
POTENTIAL AT ALL THE LOCATIONS MEET THE SAFE REQUIREMENT.
IT IS CONVENIENT FOR DESIGNER TO ADOPT 5000, 10,000OHM-M OR
MORE AS THE SURFACE RESISTIVITY OF CONCRETE TO ACHIEVE TOUCH
AND STEP POTENTIAL LIMITS THOUGH CONCRETE IS PROVIDED IN
EVERY POWER HOUSE
GROUND RESISTANCE VALUE WHEN CALCULATED FOR EACH PORTION
OF POWER HOUSE AND SWITCHYARD ARE WITHIN PERMISSIBLE LEVEL.
WHEN CONNECTED TOGETHER AND RESISTANCE MEASURED, THE
AVERAGE VALUE MAY BE FURTHER LESS.
37. REFERENCE
IEEE 80-2000: GUIDE FOR SAFETY IN AC SUBSTATIONS GROUNDING
IEEE 665-1995 : GIDE FOR GENERATING STATIONS GROUNDING
BS 7430-1998 : CODE OF PRACTICE FOR EARTHING
IS 3043 AS AMENDED : CODE OF PRACTICE FOR EARTHING COVERING
ELECTRICAL INSTALLATIONS
CBI&P PUBLICATION NO 223 : DESIGN OF EARTHING MAT OF HIGH VOLTAGE
SUBSTATIONS
NATIONAL ELECTRICAL SAFETY CODE ( NESC) -1990, 1997,2002 AND 2012
IE RULES 1956 AND ELECTRICITY ACT 2003
IACSIT International Journal of Engg Techn. Vol 4 No.3, June 2012,
Earthing System Design of Small Hydro Power (SHP) Stn – A Rewiew
By M.K.Singhal, S.N Singh