Results from HVAC Audit of Sutherland’s Padi Facility Presentation to Mr. K.P. Nair & Mr. Ramunni Nair Version 2 November 5, 2007
About This Presentation Choice Solutions is submitting this  final  report of findings and insights based on our HVAC audit of Sutherland’s Padi facility in Chennai. We are submitting this report after getting the feedback from Mr. Manohaur on the previous draft version. We make recommendations for optimization of the entire HVAC infrastructure. We also make strong recommendations for changes in the HVAC distribution system for better coefficient of performance.  As the next step, we recommend implementing the suggested changes followed by maintenance of the HVAC infrastructures.
Audit Scope of Work Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline  Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
 
Chiller Plant and AHU Audit Activities Check for normal working function of the chiller Check for water gauges function Check for thermometer function Check for butterfly valves at chiller, condenser inlet and outlet Check for periodical cleaning of cooling tower with chemical Check painting on supports for cooling tower, fan and motors Check pressure gauge and thermometer of AHU also Check pre filter Check cooling coils Check three way mixing valves Check drain liner Check fresh air damper Check for air balancing Check for cooling damper
Chiller (Technical Information) Compressor oil pressure  6 77PSI 215PSI Refrigerant pressure suction discharge  5 31.92 ˚c Condenser inlet temperature  3 39.20 ˚c Condenser outlet temperature  4 Compressor oil level  7 167Amp 8.4 ˚c 10.0 ˚c Plant No - 2 10.0°C  Plant No - 1   Compressor motor current 8 Chiller outlet temperature  2 Chiller inlet temperature  1 Particulars   #
AHU Air Flow Standard 40TR AHU air volume 16000 CFM Standard 25TR AHU air volume 10000 CFM 16.0 ˚C 15.0 ˚C 14.5 ˚C 14.0 ˚C 13.5 ˚C 15.5 ˚C 12.0 ˚C 12.0 ˚C Canvas  Temperature 6992 22.0 ˚C 8 th  Floor 25TR 6 10778 23.0 ˚C 8 th  Floor 40TR 5 12253 22.5 ˚C 7 th  Floor 40TR 3 1520 23.0 ˚C 7 th  Floor 25TR 4 10778 24.0 ˚C 9 th  Floor 40TR 7 6547 6230 12140 Air Volume (CFM) 23.0 ˚C 21.5 ˚C 21.5 ˚C Return Air  Temperature   9 th  Floor 25TR 8 6 th   Floor 25TR 2 6 th   Floor 40TR 1 Particulars   #
Audit Scope of Work Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline  Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
Maximum Consumption of Cooling System Cooling System COP/EER Chiller Plant   2x140TR Cooling Towers 2x140TR Chiller Plant Water Motor 3x12.5 HP AHU (292 TR) 4x40TR, 4x25TR,10TR Current: 178TR Current: 140TR Current: 2x140TR Current: 2x12.5HP Current: 38.5TR 3   Split A/C 2x8TR, 1x7.5TR, 2x5.5TR Cooling Tower  Pump Motors 3x12.5 HP Current: 2x12.5 HP
Capacity vs. Utilization Chiller Plant (Electrical) Chiller Plant Utilization = 90.8/101 = 90% There are 2x140TR chiller plants, with only one at a time operating Considering 1TR = 0.65kW for water-cooled chiller, 90.8 TOTAL 095 0.92 0.87 PF 130.75 155.96 183.47 Current (A) 29.22 234 B 33.83 235 Y 37.75 236 R kW Voltage (V) 140TR
Capacity  Vs Utilization 140 TR   Chiller Chiller TR  = Factor x Water Flow Rate x (Tin – Tout)/12000 = 500 x 840 x (50 - 47)/12000 = 105 TR Installed capacity is 140 TR and consumption is 105 TR Utilization = 105/140 = 75% Chilled Water Flow Rate: 840 US GPM   47.0°F  50.0°F  Water Temperature 8.4°C  10.0°C  Water Temperature Chiller outlet temperature  2 Chiller inlet temperature  1 Particulars   140TR
Capacity vs. Utilization AHU (6 th  Floor A and B wing) 6 th  Floor South AHU   Utilization = 2.60/7.24 = 35.9% 6 th  Floor North AHU Utilization = 1.6/4.5 = 35.6% Considering (COP) 1TR =0.181 kW for AHU, 2.60 TOTAL 0.57 0.60 0.55 PF 5.65 5.65 5.73 Current (A) 1.01 236.1 B 0.86 234.3 Y 0.73 235.0 R kW Voltage (V) A-wing 1.61 TOTAL 0.36 0.39 0.38 PF 6.10 6.13 6.04 Current (A) 0.52 232.2 B 0.56 232.7 Y 0.53 232.0 R kW Voltage (V) B-wing
Capacity vs. Utilization AHU - CFM (6 th  Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 12140 X(29-22)/12000,  = 31.5 TR Installed capacity is 40TR and consumption is 31.5TR,% of utilization = 31.5/40 = 78.5% TR for AHU  = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6230X(36.5-28)/12000 = 19.63 TR Installed capacity is 25TR and consumption is 20TR, % of utilization = 19.63/25 = 78.5% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 17.5 ˚C DBT 17.0 ˚C WBT 12.0 ˚C DBT 11.5 ˚C WBT Leaving Air  Temperature 6230 12140 Air Volume (CFM) 26.5 ˚C DBT 22.0 ˚C WBT 21.5 ˚C DBT 16.0 ˚C WBT Enter Air  Temperature   6 th   Floor 25TR 2 6 th   Floor 40TR 1 Particulars   #
Capacity vs. Utilization AHU (7 th  Floor A and B wing) 7 th  Floor South AHU   Utilization = 1.95/4.5 = 43% 7 th  Floor North AHU Utilization = 2.08/7.24 =29% Considering ( COP) 1TR = 0.181 kW for AHU, 1.95 TOTAL 0.46 0.52 0.50 PF 5.76 5.59 5.39 Current (A) 0.63 234.6 B 0.68 233.2 Y 0.64 231.2 R kW Voltage (V) B-wing 2.08 TOTAL 0.45 0.47 0.45 PF 6.67 6.43 6.38 Current (A) 0.71 234.6 B 0.71 232.9 Y 0.66 230.2 R kW Voltage (V) A-wing
Capacity vs. Utilization AHU - CFM (7 th  Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 12253 X(31.5-25.5)/12000,  = 27.3 TR Installed capacity is 40TR and consumption   is 27.3TR ,% of utilization = 27.3/40 = 68.25% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 1520 X(31.0-24.0)/12000,  = 5.7 TR Installed capacity is 25TR and consumption is 5.7TR ,% of utilization = 5.7/25 = 22.8% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 13.5 ˚C DBT 13.0 ˚C WBT 15.5 ˚C DBT 15.0 ˚C WBT Leaving Air  Temperature 1520 12253 Air Volume (CFM) 23.0 ˚C DBT 17.5 ˚C WBT 22.5 ˚C DBT 18.0 ˚C WBT Enter Air  Temperature   7 th   Floor 25TR 2 7 th   Floor 40TR 1 Particulars   #
Capacity vs. Utilization AHU (8 th  Floor A and B wing) 8 th  Floor South AHU   Utilization = 1.29/4.5 = 29% 8 th  Floor North AHU Utilization = 1.66/7.24 = 23% Considering (COP) 1TR = 0.181 kW for AHU, 1.29 TOTAL 0.40 0.44 0.37 PF 4.62 4.63 4.45 Current (A) 0.44 234.4 B 0.48 234.5 Y 0.37 232.7 R kW Voltage (V) B-wing 1.66 TOTAL 0.36 0.36 0.40 PF 6.10 6.47 6.40 Current (A) 0.52 233.2 B 0.54 234.1 Y 0.60 233.1 R kW Voltage (V) A-wing
Capacity vs. Utilization AHU - CFM (8 th  Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 10778 X(31.5.0-24.5)/12000,  = 26TR Installed capacity is 40TR and consumption is 26TR ,% of utilization = 26/40 = 65% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6992 X(30-24.0)/12000,  = 15.56 TR Installed capacity is 25TR and consumption is 16TR ,% of utilization = 15.56/25 =62.3% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 14.5 ˚C DBT 13.0 ˚C WBT 14.0 ˚C DBT 14.0 ˚C WBT Leaving Air  Temperature 6992 10778 Air Volume (CFM) 22.0 ˚C DBT 17.0 ˚C WBT 23.0 ˚C DBT 17.5 ˚C WBT Enter Air  Temperature   8 th   Floor 25TR 2 8 th   Floor 40TR 1 Particulars   #
Capacity vs. Utilization AHU (9 th  Floor A and B wing) 9th Floor South AHU   Utilization = 2.98/7.24 = 41% 9th Floor North AHU Utilization = 1.74/4.5 = 39% Considering (COP) 1TR = 0.181 kW for AHU, 2.98 TOTAL 0.54 0.60 0.53 PF 7.74 7.79 7.59 Current (A) 0.98 234.7 B 1.10 233.6 Y 0.90 232.7 R kW Voltage (V) A-wing 1.74 TOTAL 0.18 0.50 0.69 PF 5.14 7.21 5.00 Current (A) 0.21 228.9 B 0.84 229.2 Y 0.79 226.8 R kW Voltage (V) B-wing
Capacity vs. Utilization AHU - CFM (9 th  Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 10778 X(31.5-25.5)/12000,  = 40 TR Installed capacity is 40TR and consumption   is 39.96TR ,% of utilization = 40/40 = 99.9% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6547 X(31.5-25.0)/12000,  = 15.8 TR Installed capacity is 25TR and consumption is 16TR ,% of utilization = 16/25 = 64% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 16.0 ˚C DBT 14.0 ˚C WBT 15.0 ˚C DBT 14.0 ˚C WBT Leaving Air  Temperature 6547 10778 Air Volume (CFM) 23.0 ˚C DBT 18.0 ˚C WBT 24.0 ˚C DBT 22.5 ˚C WBT Enter Air  Temperature   9 th   Floor 25TR 2 9 th   Floor 40TR   1 Particulars   #
Audit Scope of Work Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline  Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
AHU (6 th  Floor) Observations A/C mounted on top of battery rack
AHU (6 th  Floor) Observations and Recommendations Observations A/Cs mounted on top of UPS and battery racks; drain water from A/C may enter the UPS  Recommendations Shift the A/Cs to different locations in the room to avoid disaster caused by drain water and shock from the body
3TR AHU (6 th  Floor)   Observations Permanent wires disconnected  Temporary wires connected
3TR AHU (6 th  Floor)   Observations No air filter
3TR AHU (6 th  Floor)   Observations Unprofessional way of routing No earth connection
3TR AHU (6 th  Floor)   Observations Filter not removable
AHU (6 th  Floor) Observations and Recommendations Observations Split is powered with temporary wires Working without filters No earth connection to split Unable to remove the filter  Recommendations Remove Temporary cables Install filters Ensure the earth connection Ensure filter is removable
25 TR AHU (6 th  Floor, B-wing)  Observations AHU with no filter
No air filter  25 TR AHU (6 th  Floor, B-wing)  Observations Fins  damaged
25 TR AHU (6 th  Floor, B-wing) Observations and Recommendations Observations No air filter for AHU; dust particles will enter facility Recommendations Install air filter
AHU Condensing Grills (6 th  Floor)   Observations Condensing grill got damaged  Fins damaged
AHU Condensing Grills (6 th  Floor)   Observations and Recommendations Observations AHU condensing grills are damaged  Recommendations Replace condensing grills
AHU Room (6 th  Floor, B-wing) Observations All unwanted materials exist in room
AHU Room (6 th  Floor, B-wing) Observations Unwanted materials near pipeline Rusted meter tube  Dust and dirt deposited on meter
AHU Room (6 th  Floor, B-wing) Observations Unnecessary cables at AHU
Drying pipe blocked AHU Room (6 th  Floor, B-wing) Observations
AHU Room – 6 th  Floor (B-wing) Observations and Recommendations Observations Unwanted materials exist Meter tube is rusted and inaccessible Unused cables exist Drying pipe is blocked, leading to water inside the AHU Recommendations Remove the unwanted materials Clean and paint the meter tube Provide sufficient space to access the meter tube Remove unused cables Clear the drying pipe
Thermo Control Valve (6 th  Floor, B-wing)  Observations Damaged thermo control valve Missing 3 way mixing valve motor
Thermo Control Valve (6 th  Floor, B-wing)  Observations and Recommendations Observations Thermo control valve is damaged  Recommendations Replace the damaged thermo control valve
Cafeteria (6 th  Floor) Observations No partition between cafeteria and wash room Exhaust fan sucking cool air
Cafeteria (6 th  Floor) Observations Open windows with A/C running
Cafeteria (6 th  Floor) Observations and Recommendations Observations Wash room exhaust fan sucking cool air out from the cafeteria No partition between wash room and cafeteria Window is opened Recommendations Provide partition between cafeteria and wash room Close the window
Chilled Water Line (8 th  Floor)   Observations Gap on chilled water line
Chilled Water Line (8 th  Floor)   Observations and Recommendations Observations Gaps along the chilled water line Recommendations Fill the gaps
Chiller Plant Motor Starters (Terrace) Observations Seepage Starter enclosures in poor condition  Pipeline too close to starters
Chiller Plant Motor Starters (Terrace)  Observations and Recommendations Observations Seepage on walls No proper enclosures for motor starters Pipeline adjacent to starters  Recommendations Avoid seepage Install proper enclosure Shift the pipeline or take necessary precautions
Chiller Plant Pumps (Terrace)  Observations Pump rusted No proper enclosure on motor  Seepages
Chiller Plant Pumps (Terrace)  Observations Pumps rusted No enclosure at termination Seepages
Chiller Plant Pumps (Terrace)  Observations Dust and dirt on the floor Termination box open  Leakage
Chiller Plant Pumps (Terrace) Observations and Recommendations Observations No general maintenance to pumps; led to rust No proper enclosure on motors and pumps; motor electrical terminators are open  Seepage on floor Floor not clean Recommendations Clean and paint rusted areas and implement maintenance Ensure proper enclosures Avoid seepage  Keep the floor clean
Chilled Water Pipes (Terrace) Observations Pipes rusted
Chilled Water Pipes (Terrace) Observations and Recommendations Observations Condensation  pipes got rusted  Insulation on pipe line is damaged Recommendations Clean and paint the rusted areas Do proper insulation wherever it is damaged
Chiller Plant Panel (Terrace) Observations Panel got rusted
Chiller Plant Panel (Terrace) Observations and Recommendations Observations Panel rusted  No proper routing and dressing inside the panel Recommendations Clean panel and paint it to protect from rust Do proper dressing
Chiller (Terrace) Observations and Recommendations Observations All the water flow measuring gauges are not working All thermometer not working Buttery fly valves are jammed  Recommendations Preventive maintenance is required for all water gauges Preventive maintenance is required for thermometers; replace, if necessary Preventive maintenance is required for Butterfly valves, replace, if necessary
FRP Cooling Towers (Terrace) Observations and Recommendations Observations Water basin is getting rusted Butterfly and gate valves are not functioning properly Motor and fan supports are got rusted Recommendations Periodic cleaning required with chemical and water basin need to be paint with chemical protective Butterfly and gate valves needs  servicing All supports needs painting
Condenser  and Chilled Water Pumps (Terrace) Observations and Recommendations Observations All gauges and thermometers are rusted Butterfly and gate valves are rusted Pump sets and base frames are rusted Recommendations Replace all rusted gauges and thermometers Replace all rusted butterfly and gate valves  Clean and paint rusted pump sets and base frames
AHU Observations Observations Siphon valve with punch cock is not working All pressure gauge meters for water flow measurement are rusted All thermometers are of 2” stem Pre filters are damaged Three way mixing valves are not functioning at AHU Missing of 3 way mixing valve motors and control cable Sedimentation inside the tube may obstruct the water flow Drain line jammed in 6 th  floor 25TR AHU Fresh air damper not properly set to a have sufficient opening Air balancing is not their Cooling dampers not fitted properly Motor installed is 0f 12.5HP is over sized Butterfly valves are not functioning properly All the AHU are being  under utilization AHU and AHU room covered with dust and dirt Fins are covered with pre filter hence it needs cleaning
AHU Recommendations Recommendations Siphon with  punch cock to be replaced with stain less steel Replace rusted pressure gauges and thermometers All thermometer are to be replace with 4” stem for proper measurement Replace damaged pre filters Replace all three way mixing valves at AHU in lets Install 3 way mixing valve wherever it is missed Clean the cooling coils Clear the drain line Provide sufficient space for fresh air dampers at least 50% Balancing is required for uniform air distribution  Fix the cooler damper properly Motor replace with proper size (10HP)  Butter fly valves are to serviced and replace wherever it is necessary Recalibrate  AHU sizing Clean AHU and AHU   room
Pipelines Observations and Recommendations Observations Insulation on chilled water pipeline got damaged Water pipeline got rusted Recommendations Insulation need to carried out wherever it damaged  All water pipelines needs painting
Audit Scope of Work Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline  Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
Chiller Plant Bus Bar   Temperature Reading Forced air cooling is required inside the panel
Audit Scope of Work Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline  Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
Conclusions and Next Steps Chiller plant is under provisioned Actual chiller required for heat load is 178 TR whereas available capacity is 140TR; in summer, both chiller plants must be operated at the same time to get sufficient cooling Increase chiller TR; as the PSI is high, compressor is getting overstrained and the compressor motor is taking more current than necessary; this reduces the life of the compressor Cooling tower usage is not appropriate Only one chilled water pump, cooling tower and cooling tower water motors have to be used per one chiller plant; there are two cooling towers and water motors being used  with one chiller plant currently; this leads to greater electrical consumption, it does not help with cooling either Running of both the cooling towers 24/7 is also a problem
Conclusions and Next Steps AHU is over provisioned Total AHU required for existing load is178TR; installed capacity is 292TR; only 9th floor AHU running at100%; others under-utilized 40TR AHU blower motor capacity is 12.5HP; required is 10HP  All 3-way mixing valves are not functioning; no control on chilled water plant leads to greater electrical consumption and reduces cooling effect With the 3-way mixing valves not functioning, we cannot bring the chilled water outlet temperature down to 6 degrees Do not change to air cooling The advantage of water cooled HVAC is that it consumes less electrical power and has no environmental pollution as against an air cooled one.  Implement a maintenance regime to lower the running costs and total cost of ownership of the HVAC system
Choice Solutions Contacts Ramesh R. Senior Solutions Architect, NCPI Choice Solutions, Chennai [email_address]   Cell: +91 98410 05183 Tel:  +91 44 2436 3391/92/93 http://www.choice-solutions.com Srinivas Chowdary Senior Solutions Architect, NCPI Choice Solutions, Hyderabad [email_address] Cell: +91 98660 79498 Tel:  +91 40 2354 7600 http://www.choice-solutions.com

Sutherland.Padi Audit Results Hvac.Final.05 Nov 07

  • 1.
    Results from HVACAudit of Sutherland’s Padi Facility Presentation to Mr. K.P. Nair & Mr. Ramunni Nair Version 2 November 5, 2007
  • 2.
    About This PresentationChoice Solutions is submitting this final report of findings and insights based on our HVAC audit of Sutherland’s Padi facility in Chennai. We are submitting this report after getting the feedback from Mr. Manohaur on the previous draft version. We make recommendations for optimization of the entire HVAC infrastructure. We also make strong recommendations for changes in the HVAC distribution system for better coefficient of performance. As the next step, we recommend implementing the suggested changes followed by maintenance of the HVAC infrastructures.
  • 3.
    Audit Scope ofWork Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
  • 4.
  • 5.
    Chiller Plant andAHU Audit Activities Check for normal working function of the chiller Check for water gauges function Check for thermometer function Check for butterfly valves at chiller, condenser inlet and outlet Check for periodical cleaning of cooling tower with chemical Check painting on supports for cooling tower, fan and motors Check pressure gauge and thermometer of AHU also Check pre filter Check cooling coils Check three way mixing valves Check drain liner Check fresh air damper Check for air balancing Check for cooling damper
  • 6.
    Chiller (Technical Information)Compressor oil pressure 6 77PSI 215PSI Refrigerant pressure suction discharge 5 31.92 ˚c Condenser inlet temperature 3 39.20 ˚c Condenser outlet temperature 4 Compressor oil level 7 167Amp 8.4 ˚c 10.0 ˚c Plant No - 2 10.0°C Plant No - 1 Compressor motor current 8 Chiller outlet temperature 2 Chiller inlet temperature 1 Particulars #
  • 7.
    AHU Air FlowStandard 40TR AHU air volume 16000 CFM Standard 25TR AHU air volume 10000 CFM 16.0 ˚C 15.0 ˚C 14.5 ˚C 14.0 ˚C 13.5 ˚C 15.5 ˚C 12.0 ˚C 12.0 ˚C Canvas Temperature 6992 22.0 ˚C 8 th Floor 25TR 6 10778 23.0 ˚C 8 th Floor 40TR 5 12253 22.5 ˚C 7 th Floor 40TR 3 1520 23.0 ˚C 7 th Floor 25TR 4 10778 24.0 ˚C 9 th Floor 40TR 7 6547 6230 12140 Air Volume (CFM) 23.0 ˚C 21.5 ˚C 21.5 ˚C Return Air Temperature 9 th Floor 25TR 8 6 th Floor 25TR 2 6 th Floor 40TR 1 Particulars #
  • 8.
    Audit Scope ofWork Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
  • 9.
    Maximum Consumption ofCooling System Cooling System COP/EER Chiller Plant 2x140TR Cooling Towers 2x140TR Chiller Plant Water Motor 3x12.5 HP AHU (292 TR) 4x40TR, 4x25TR,10TR Current: 178TR Current: 140TR Current: 2x140TR Current: 2x12.5HP Current: 38.5TR 3  Split A/C 2x8TR, 1x7.5TR, 2x5.5TR Cooling Tower Pump Motors 3x12.5 HP Current: 2x12.5 HP
  • 10.
    Capacity vs. UtilizationChiller Plant (Electrical) Chiller Plant Utilization = 90.8/101 = 90% There are 2x140TR chiller plants, with only one at a time operating Considering 1TR = 0.65kW for water-cooled chiller, 90.8 TOTAL 095 0.92 0.87 PF 130.75 155.96 183.47 Current (A) 29.22 234 B 33.83 235 Y 37.75 236 R kW Voltage (V) 140TR
  • 11.
    Capacity VsUtilization 140 TR Chiller Chiller TR = Factor x Water Flow Rate x (Tin – Tout)/12000 = 500 x 840 x (50 - 47)/12000 = 105 TR Installed capacity is 140 TR and consumption is 105 TR Utilization = 105/140 = 75% Chilled Water Flow Rate: 840 US GPM 47.0°F 50.0°F Water Temperature 8.4°C 10.0°C Water Temperature Chiller outlet temperature 2 Chiller inlet temperature 1 Particulars 140TR
  • 12.
    Capacity vs. UtilizationAHU (6 th Floor A and B wing) 6 th Floor South AHU Utilization = 2.60/7.24 = 35.9% 6 th Floor North AHU Utilization = 1.6/4.5 = 35.6% Considering (COP) 1TR =0.181 kW for AHU, 2.60 TOTAL 0.57 0.60 0.55 PF 5.65 5.65 5.73 Current (A) 1.01 236.1 B 0.86 234.3 Y 0.73 235.0 R kW Voltage (V) A-wing 1.61 TOTAL 0.36 0.39 0.38 PF 6.10 6.13 6.04 Current (A) 0.52 232.2 B 0.56 232.7 Y 0.53 232.0 R kW Voltage (V) B-wing
  • 13.
    Capacity vs. UtilizationAHU - CFM (6 th Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 12140 X(29-22)/12000, = 31.5 TR Installed capacity is 40TR and consumption is 31.5TR,% of utilization = 31.5/40 = 78.5% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6230X(36.5-28)/12000 = 19.63 TR Installed capacity is 25TR and consumption is 20TR, % of utilization = 19.63/25 = 78.5% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 17.5 ˚C DBT 17.0 ˚C WBT 12.0 ˚C DBT 11.5 ˚C WBT Leaving Air Temperature 6230 12140 Air Volume (CFM) 26.5 ˚C DBT 22.0 ˚C WBT 21.5 ˚C DBT 16.0 ˚C WBT Enter Air Temperature 6 th Floor 25TR 2 6 th Floor 40TR 1 Particulars #
  • 14.
    Capacity vs. UtilizationAHU (7 th Floor A and B wing) 7 th Floor South AHU Utilization = 1.95/4.5 = 43% 7 th Floor North AHU Utilization = 2.08/7.24 =29% Considering ( COP) 1TR = 0.181 kW for AHU, 1.95 TOTAL 0.46 0.52 0.50 PF 5.76 5.59 5.39 Current (A) 0.63 234.6 B 0.68 233.2 Y 0.64 231.2 R kW Voltage (V) B-wing 2.08 TOTAL 0.45 0.47 0.45 PF 6.67 6.43 6.38 Current (A) 0.71 234.6 B 0.71 232.9 Y 0.66 230.2 R kW Voltage (V) A-wing
  • 15.
    Capacity vs. UtilizationAHU - CFM (7 th Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 12253 X(31.5-25.5)/12000, = 27.3 TR Installed capacity is 40TR and consumption is 27.3TR ,% of utilization = 27.3/40 = 68.25% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 1520 X(31.0-24.0)/12000, = 5.7 TR Installed capacity is 25TR and consumption is 5.7TR ,% of utilization = 5.7/25 = 22.8% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 13.5 ˚C DBT 13.0 ˚C WBT 15.5 ˚C DBT 15.0 ˚C WBT Leaving Air Temperature 1520 12253 Air Volume (CFM) 23.0 ˚C DBT 17.5 ˚C WBT 22.5 ˚C DBT 18.0 ˚C WBT Enter Air Temperature 7 th Floor 25TR 2 7 th Floor 40TR 1 Particulars #
  • 16.
    Capacity vs. UtilizationAHU (8 th Floor A and B wing) 8 th Floor South AHU Utilization = 1.29/4.5 = 29% 8 th Floor North AHU Utilization = 1.66/7.24 = 23% Considering (COP) 1TR = 0.181 kW for AHU, 1.29 TOTAL 0.40 0.44 0.37 PF 4.62 4.63 4.45 Current (A) 0.44 234.4 B 0.48 234.5 Y 0.37 232.7 R kW Voltage (V) B-wing 1.66 TOTAL 0.36 0.36 0.40 PF 6.10 6.47 6.40 Current (A) 0.52 233.2 B 0.54 234.1 Y 0.60 233.1 R kW Voltage (V) A-wing
  • 17.
    Capacity vs. UtilizationAHU - CFM (8 th Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 10778 X(31.5.0-24.5)/12000, = 26TR Installed capacity is 40TR and consumption is 26TR ,% of utilization = 26/40 = 65% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6992 X(30-24.0)/12000, = 15.56 TR Installed capacity is 25TR and consumption is 16TR ,% of utilization = 15.56/25 =62.3% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 14.5 ˚C DBT 13.0 ˚C WBT 14.0 ˚C DBT 14.0 ˚C WBT Leaving Air Temperature 6992 10778 Air Volume (CFM) 22.0 ˚C DBT 17.0 ˚C WBT 23.0 ˚C DBT 17.5 ˚C WBT Enter Air Temperature 8 th Floor 25TR 2 8 th Floor 40TR 1 Particulars #
  • 18.
    Capacity vs. UtilizationAHU (9 th Floor A and B wing) 9th Floor South AHU Utilization = 2.98/7.24 = 41% 9th Floor North AHU Utilization = 1.74/4.5 = 39% Considering (COP) 1TR = 0.181 kW for AHU, 2.98 TOTAL 0.54 0.60 0.53 PF 7.74 7.79 7.59 Current (A) 0.98 234.7 B 1.10 233.6 Y 0.90 232.7 R kW Voltage (V) A-wing 1.74 TOTAL 0.18 0.50 0.69 PF 5.14 7.21 5.00 Current (A) 0.21 228.9 B 0.84 229.2 Y 0.79 226.8 R kW Voltage (V) B-wing
  • 19.
    Capacity vs. UtilizationAHU - CFM (9 th Floor A and B wing) TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 10778 X(31.5-25.5)/12000, = 40 TR Installed capacity is 40TR and consumption is 39.96TR ,% of utilization = 40/40 = 99.9% TR for AHU = Factor X Air flow X (Hin – Hout) Enthalpy difference/12000 = 4.45 X 6547 X(31.5-25.0)/12000, = 15.8 TR Installed capacity is 25TR and consumption is 16TR ,% of utilization = 16/25 = 64% Enthalpy difference (Hin and Hout ) is obtained from psychrometric chart 16.0 ˚C DBT 14.0 ˚C WBT 15.0 ˚C DBT 14.0 ˚C WBT Leaving Air Temperature 6547 10778 Air Volume (CFM) 23.0 ˚C DBT 18.0 ˚C WBT 24.0 ˚C DBT 22.5 ˚C WBT Enter Air Temperature 9 th Floor 25TR 2 9 th Floor 40TR 1 Particulars #
  • 20.
    Audit Scope ofWork Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
  • 21.
    AHU (6 th Floor) Observations A/C mounted on top of battery rack
  • 22.
    AHU (6 th Floor) Observations and Recommendations Observations A/Cs mounted on top of UPS and battery racks; drain water from A/C may enter the UPS Recommendations Shift the A/Cs to different locations in the room to avoid disaster caused by drain water and shock from the body
  • 23.
    3TR AHU (6th Floor) Observations Permanent wires disconnected Temporary wires connected
  • 24.
    3TR AHU (6th Floor) Observations No air filter
  • 25.
    3TR AHU (6th Floor) Observations Unprofessional way of routing No earth connection
  • 26.
    3TR AHU (6th Floor) Observations Filter not removable
  • 27.
    AHU (6 th Floor) Observations and Recommendations Observations Split is powered with temporary wires Working without filters No earth connection to split Unable to remove the filter Recommendations Remove Temporary cables Install filters Ensure the earth connection Ensure filter is removable
  • 28.
    25 TR AHU(6 th Floor, B-wing) Observations AHU with no filter
  • 29.
    No air filter 25 TR AHU (6 th Floor, B-wing) Observations Fins damaged
  • 30.
    25 TR AHU(6 th Floor, B-wing) Observations and Recommendations Observations No air filter for AHU; dust particles will enter facility Recommendations Install air filter
  • 31.
    AHU Condensing Grills(6 th Floor) Observations Condensing grill got damaged Fins damaged
  • 32.
    AHU Condensing Grills(6 th Floor) Observations and Recommendations Observations AHU condensing grills are damaged Recommendations Replace condensing grills
  • 33.
    AHU Room (6th Floor, B-wing) Observations All unwanted materials exist in room
  • 34.
    AHU Room (6th Floor, B-wing) Observations Unwanted materials near pipeline Rusted meter tube Dust and dirt deposited on meter
  • 35.
    AHU Room (6th Floor, B-wing) Observations Unnecessary cables at AHU
  • 36.
    Drying pipe blockedAHU Room (6 th Floor, B-wing) Observations
  • 37.
    AHU Room –6 th Floor (B-wing) Observations and Recommendations Observations Unwanted materials exist Meter tube is rusted and inaccessible Unused cables exist Drying pipe is blocked, leading to water inside the AHU Recommendations Remove the unwanted materials Clean and paint the meter tube Provide sufficient space to access the meter tube Remove unused cables Clear the drying pipe
  • 38.
    Thermo Control Valve(6 th Floor, B-wing) Observations Damaged thermo control valve Missing 3 way mixing valve motor
  • 39.
    Thermo Control Valve(6 th Floor, B-wing) Observations and Recommendations Observations Thermo control valve is damaged Recommendations Replace the damaged thermo control valve
  • 40.
    Cafeteria (6 th Floor) Observations No partition between cafeteria and wash room Exhaust fan sucking cool air
  • 41.
    Cafeteria (6 th Floor) Observations Open windows with A/C running
  • 42.
    Cafeteria (6 th Floor) Observations and Recommendations Observations Wash room exhaust fan sucking cool air out from the cafeteria No partition between wash room and cafeteria Window is opened Recommendations Provide partition between cafeteria and wash room Close the window
  • 43.
    Chilled Water Line(8 th Floor) Observations Gap on chilled water line
  • 44.
    Chilled Water Line(8 th Floor) Observations and Recommendations Observations Gaps along the chilled water line Recommendations Fill the gaps
  • 45.
    Chiller Plant MotorStarters (Terrace) Observations Seepage Starter enclosures in poor condition Pipeline too close to starters
  • 46.
    Chiller Plant MotorStarters (Terrace) Observations and Recommendations Observations Seepage on walls No proper enclosures for motor starters Pipeline adjacent to starters Recommendations Avoid seepage Install proper enclosure Shift the pipeline or take necessary precautions
  • 47.
    Chiller Plant Pumps(Terrace) Observations Pump rusted No proper enclosure on motor Seepages
  • 48.
    Chiller Plant Pumps(Terrace) Observations Pumps rusted No enclosure at termination Seepages
  • 49.
    Chiller Plant Pumps(Terrace) Observations Dust and dirt on the floor Termination box open Leakage
  • 50.
    Chiller Plant Pumps(Terrace) Observations and Recommendations Observations No general maintenance to pumps; led to rust No proper enclosure on motors and pumps; motor electrical terminators are open Seepage on floor Floor not clean Recommendations Clean and paint rusted areas and implement maintenance Ensure proper enclosures Avoid seepage Keep the floor clean
  • 51.
    Chilled Water Pipes(Terrace) Observations Pipes rusted
  • 52.
    Chilled Water Pipes(Terrace) Observations and Recommendations Observations Condensation pipes got rusted Insulation on pipe line is damaged Recommendations Clean and paint the rusted areas Do proper insulation wherever it is damaged
  • 53.
    Chiller Plant Panel(Terrace) Observations Panel got rusted
  • 54.
    Chiller Plant Panel(Terrace) Observations and Recommendations Observations Panel rusted No proper routing and dressing inside the panel Recommendations Clean panel and paint it to protect from rust Do proper dressing
  • 55.
    Chiller (Terrace) Observationsand Recommendations Observations All the water flow measuring gauges are not working All thermometer not working Buttery fly valves are jammed Recommendations Preventive maintenance is required for all water gauges Preventive maintenance is required for thermometers; replace, if necessary Preventive maintenance is required for Butterfly valves, replace, if necessary
  • 56.
    FRP Cooling Towers(Terrace) Observations and Recommendations Observations Water basin is getting rusted Butterfly and gate valves are not functioning properly Motor and fan supports are got rusted Recommendations Periodic cleaning required with chemical and water basin need to be paint with chemical protective Butterfly and gate valves needs servicing All supports needs painting
  • 57.
    Condenser andChilled Water Pumps (Terrace) Observations and Recommendations Observations All gauges and thermometers are rusted Butterfly and gate valves are rusted Pump sets and base frames are rusted Recommendations Replace all rusted gauges and thermometers Replace all rusted butterfly and gate valves Clean and paint rusted pump sets and base frames
  • 58.
    AHU Observations ObservationsSiphon valve with punch cock is not working All pressure gauge meters for water flow measurement are rusted All thermometers are of 2” stem Pre filters are damaged Three way mixing valves are not functioning at AHU Missing of 3 way mixing valve motors and control cable Sedimentation inside the tube may obstruct the water flow Drain line jammed in 6 th floor 25TR AHU Fresh air damper not properly set to a have sufficient opening Air balancing is not their Cooling dampers not fitted properly Motor installed is 0f 12.5HP is over sized Butterfly valves are not functioning properly All the AHU are being under utilization AHU and AHU room covered with dust and dirt Fins are covered with pre filter hence it needs cleaning
  • 59.
    AHU Recommendations RecommendationsSiphon with punch cock to be replaced with stain less steel Replace rusted pressure gauges and thermometers All thermometer are to be replace with 4” stem for proper measurement Replace damaged pre filters Replace all three way mixing valves at AHU in lets Install 3 way mixing valve wherever it is missed Clean the cooling coils Clear the drain line Provide sufficient space for fresh air dampers at least 50% Balancing is required for uniform air distribution Fix the cooler damper properly Motor replace with proper size (10HP) Butter fly valves are to serviced and replace wherever it is necessary Recalibrate AHU sizing Clean AHU and AHU room
  • 60.
    Pipelines Observations andRecommendations Observations Insulation on chilled water pipeline got damaged Water pipeline got rusted Recommendations Insulation need to carried out wherever it damaged All water pipelines needs painting
  • 61.
    Audit Scope ofWork Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
  • 62.
    Chiller Plant BusBar Temperature Reading Forced air cooling is required inside the panel
  • 63.
    Audit Scope ofWork Capacity vs. Utilization Chiller Plant AHU Chiller Water Pump Motor Cooling Tower Cooling Water Pump Motor Pipeline Facility Observations and Recommendations Temperature Readings and Analysis Conclusions and Next Steps Agenda
  • 64.
    Conclusions and NextSteps Chiller plant is under provisioned Actual chiller required for heat load is 178 TR whereas available capacity is 140TR; in summer, both chiller plants must be operated at the same time to get sufficient cooling Increase chiller TR; as the PSI is high, compressor is getting overstrained and the compressor motor is taking more current than necessary; this reduces the life of the compressor Cooling tower usage is not appropriate Only one chilled water pump, cooling tower and cooling tower water motors have to be used per one chiller plant; there are two cooling towers and water motors being used with one chiller plant currently; this leads to greater electrical consumption, it does not help with cooling either Running of both the cooling towers 24/7 is also a problem
  • 65.
    Conclusions and NextSteps AHU is over provisioned Total AHU required for existing load is178TR; installed capacity is 292TR; only 9th floor AHU running at100%; others under-utilized 40TR AHU blower motor capacity is 12.5HP; required is 10HP All 3-way mixing valves are not functioning; no control on chilled water plant leads to greater electrical consumption and reduces cooling effect With the 3-way mixing valves not functioning, we cannot bring the chilled water outlet temperature down to 6 degrees Do not change to air cooling The advantage of water cooled HVAC is that it consumes less electrical power and has no environmental pollution as against an air cooled one. Implement a maintenance regime to lower the running costs and total cost of ownership of the HVAC system
  • 66.
    Choice Solutions ContactsRamesh R. Senior Solutions Architect, NCPI Choice Solutions, Chennai [email_address] Cell: +91 98410 05183 Tel: +91 44 2436 3391/92/93 http://www.choice-solutions.com Srinivas Chowdary Senior Solutions Architect, NCPI Choice Solutions, Hyderabad [email_address] Cell: +91 98660 79498 Tel: +91 40 2354 7600 http://www.choice-solutions.com