The document discusses the design and components of electrical power grids. It begins with an introduction to power grids, noting their three main components: power stations, transmission lines, and transformers. It then covers various topics related to designing a power grid substation including selecting the site, layout designs, busbar schemes, safety clearances, earth mat design, and control rooms. Key equipment for grids are also discussed such as lighting arrestors, current and potential transformers, circuit breakers, and isolators. The presentation concludes that grids are important for supplying reliable and economic power from sources to loads and maintaining efficiency, though their design and components make them costly.
Distributed Generation generally refers to power generation at the point of end user or
customer. Distributed Generation is gaining worldwide acceptance due to itโs a number of benefits.
Distributed Generation eliminates the cost and complexity and reduces the chances of inefficiency
which occur in the transmission and distributed network [1]. Basically electricity produced is
generated at large generating stations which is then send at high voltages through the transmission
lines to the load centers and then through local distribution network distributed to the customers at
distribution level voltage. In present scenario there is an increase in demand which is creating gap
between demand and supply to fulfill this gap distributed generation can plays the significant role.
The main reason for the need of distributed generation is it is clean and continuous. Distributed
generation means generating power on site not centrally. Distributed generation is the best way for
rural electrification. This paper will discuss the importance and benefits of Distributed Generation in
near future
Functions and Performance Requirements
Elements of an Excitation System
Types of Excitation Systems
Control and Protection Functions
Modeling of Excitation Systems
The functions of an excitation system are
to provide direct current to the synchronous generator field winding, and
to perform control and protective functions essential to the satisfactory operation of the power system
The performance requirements of the excitation system are determined by
Generator considerations:
supply and adjust field current as the generator output varies within its continuous capability
respond to transient disturbances with field forcing consistent with the generator short term capabilities:
rotor insulation failure due to high field voltage
rotor heating due to high field current
stator heating due to high VAR loading
heating due to excess flux (volts/Hz)
Power system considerations:
contribute to effective control of system voltage and improvement of system stability
It is type of hybrid energy system consist of a photovoltaic array coupled with a wind turbine.This would create more output from the wind turbine during the winter, whereas during the summer, the solar panels would produce their peak output.Solar Photovoltaic (PV) โ Wind Turbine (WT) Hybrid System is the best way to utilize not just one local available RE resource but multiple renewable RE resources.
Distributed Generation generally refers to power generation at the point of end user or
customer. Distributed Generation is gaining worldwide acceptance due to itโs a number of benefits.
Distributed Generation eliminates the cost and complexity and reduces the chances of inefficiency
which occur in the transmission and distributed network [1]. Basically electricity produced is
generated at large generating stations which is then send at high voltages through the transmission
lines to the load centers and then through local distribution network distributed to the customers at
distribution level voltage. In present scenario there is an increase in demand which is creating gap
between demand and supply to fulfill this gap distributed generation can plays the significant role.
The main reason for the need of distributed generation is it is clean and continuous. Distributed
generation means generating power on site not centrally. Distributed generation is the best way for
rural electrification. This paper will discuss the importance and benefits of Distributed Generation in
near future
Functions and Performance Requirements
Elements of an Excitation System
Types of Excitation Systems
Control and Protection Functions
Modeling of Excitation Systems
The functions of an excitation system are
to provide direct current to the synchronous generator field winding, and
to perform control and protective functions essential to the satisfactory operation of the power system
The performance requirements of the excitation system are determined by
Generator considerations:
supply and adjust field current as the generator output varies within its continuous capability
respond to transient disturbances with field forcing consistent with the generator short term capabilities:
rotor insulation failure due to high field voltage
rotor heating due to high field current
stator heating due to high VAR loading
heating due to excess flux (volts/Hz)
Power system considerations:
contribute to effective control of system voltage and improvement of system stability
It is type of hybrid energy system consist of a photovoltaic array coupled with a wind turbine.This would create more output from the wind turbine during the winter, whereas during the summer, the solar panels would produce their peak output.Solar Photovoltaic (PV) โ Wind Turbine (WT) Hybrid System is the best way to utilize not just one local available RE resource but multiple renewable RE resources.
Distribution System Voltage Drop and Power Loss CalculationAmeen San
ย
Distribution System Voltage Drop and Power Loss
Calculation
Comparison of Overhead Versus Underground System
Power Loss Calculation,Voltage Drop Calculation
The electricity supply industry is undergoing a profound transformation worldwide. Market forces, scarcer natural resources, and an ever-increasing demand for electricity are some of the drivers responsible for such unprecedented change. Against this background of rapid evolution, the expansion programs of many utilities are being thwarted by a variety of well-founded, environment, land-use, and regulatory pressures that prevent the licensing and building of new transmission lines and electricity generating plants.
Wide area monitoring systems (WAMS) are essentially based on the new data acquisition technology of phasor measurement and allow monitoring transmission system conditions over large areas in view of detecting and further counteracting grid instabilities.
Distribution System Voltage Drop and Power Loss CalculationAmeen San
ย
Distribution System Voltage Drop and Power Loss
Calculation
Comparison of Overhead Versus Underground System
Power Loss Calculation,Voltage Drop Calculation
The electricity supply industry is undergoing a profound transformation worldwide. Market forces, scarcer natural resources, and an ever-increasing demand for electricity are some of the drivers responsible for such unprecedented change. Against this background of rapid evolution, the expansion programs of many utilities are being thwarted by a variety of well-founded, environment, land-use, and regulatory pressures that prevent the licensing and building of new transmission lines and electricity generating plants.
Wide area monitoring systems (WAMS) are essentially based on the new data acquisition technology of phasor measurement and allow monitoring transmission system conditions over large areas in view of detecting and further counteracting grid instabilities.
Abstract- This paper presents a major revision of the Universal Four Leg โDC Grid Laboratory Experimental Setupโ. This revision includes the reduction of current loops, the increase of efficiency in the power stage, the expansion of measurement possibilities and the re-specification of the input/output range.
To deal with an ever present complication in the world of measurements, simple fuse holders are converted into dedicated probe measurement connectors. These connectors reduce large ground loops to a minimum.
Key features include a clear board layout and silkscreen, a tremendous reduction of semiconductor losses resulting in a heatsink-less power stage and easy, reliable probe and power connections. Provisions are made for a Single Board Computer (SBC) to read and control the Universal Four Leg V4. The SBC can also be used to communicate with external devices to allow for remote control of the Universal Four Leg and the presentation of measurements performed.
The Universal Four Leg is a power management device with a wide range of applications in both higher educational laboratory courses, as well as a dedicated grid manager in low voltage DC-grids.
International Journal of Engineering Research and Development (IJERD)IJERD Editor
ย
journal publishing, how to publish research paper, Call For research paper, international journal, publishing a paper, IJERD, journal of science and technology, how to get a research paper published, publishing a paper, publishing of journal, publishing of research paper, reserach and review articles, IJERD Journal, How to publish your research paper, publish research paper, open access engineering journal, Engineering journal, Mathemetics journal, Physics journal, Chemistry journal, Computer Engineering, Computer Science journal, how to submit your paper, peer reviw journal, indexed journal, reserach and review articles, engineering journal, www.ijerd.com, research journals,
yahoo journals, bing journals, International Journal of Engineering Research and Development, google journals, hard copy of journal
Design of a generating substation with the description of designing a transformer. Here we show some basic components of a substation. and we also show the parameters and calculation to design a transformer of a specific ratings.
"๐ฉ๐ฌ๐ฎ๐ผ๐ต ๐พ๐ฐ๐ป๐ฏ ๐ป๐ฑ ๐ฐ๐บ ๐ฏ๐จ๐ณ๐ญ ๐ซ๐ถ๐ต๐ฌ"
๐๐ ๐๐จ๐ฆ๐ฌ (๐๐ ๐๐จ๐ฆ๐ฆ๐ฎ๐ง๐ข๐๐๐ญ๐ข๐จ๐ง๐ฌ) is a professional event agency that includes experts in the event-organizing market in Vietnam, Korea, and ASEAN countries. We provide unlimited types of events from Music concerts, Fan meetings, and Culture festivals to Corporate events, Internal company events, Golf tournaments, MICE events, and Exhibitions.
๐๐ ๐๐จ๐ฆ๐ฌ provides unlimited package services including such as Event organizing, Event planning, Event production, Manpower, PR marketing, Design 2D/3D, VIP protocols, Interpreter agency, etc.
Sports events - Golf competitions/billiards competitions/company sports events: dynamic and challenging
โญ ๐ ๐๐๐ญ๐ฎ๐ซ๐๐ ๐ฉ๐ซ๐จ๐ฃ๐๐๐ญ๐ฌ:
โข 2024 BAEKHYUN [Lonsdaleite] IN HO CHI MINH
โข SUPER JUNIOR-L.S.S. THE SHOW : Th3ee Guys in HO CHI MINH
โขFreenBecky 1st Fan Meeting in Vietnam
โขCHILDREN ART EXHIBITION 2024: BEYOND BARRIERS
โข WOW K-Music Festival 2023
โข Winner [CROSS] Tour in HCM
โข Super Show 9 in HCM with Super Junior
โข HCMC - Gyeongsangbuk-do Culture and Tourism Festival
โข Korean Vietnam Partnership - Fair with LG
โข Korean President visits Samsung Electronics R&D Center
โข Vietnam Food Expo with Lotte Wellfood
"๐๐ฏ๐๐ซ๐ฒ ๐๐ฏ๐๐ง๐ญ ๐ข๐ฌ ๐ ๐ฌ๐ญ๐จ๐ซ๐ฒ, ๐ ๐ฌ๐ฉ๐๐๐ข๐๐ฅ ๐ฃ๐จ๐ฎ๐ซ๐ง๐๐ฒ. ๐๐ ๐๐ฅ๐ฐ๐๐ฒ๐ฌ ๐๐๐ฅ๐ข๐๐ฏ๐ ๐ญ๐ก๐๐ญ ๐ฌ๐ก๐จ๐ซ๐ญ๐ฅ๐ฒ ๐ฒ๐จ๐ฎ ๐ฐ๐ข๐ฅ๐ฅ ๐๐ ๐ ๐ฉ๐๐ซ๐ญ ๐จ๐ ๐จ๐ฎ๐ซ ๐ฌ๐ญ๐จ๐ซ๐ข๐๐ฌ."
[Note: This is a partial preview. To download this presentation, visit:
https://www.oeconsulting.com.sg/training-presentations]
Sustainability has become an increasingly critical topic as the world recognizes the need to protect our planet and its resources for future generations. Sustainability means meeting our current needs without compromising the ability of future generations to meet theirs. It involves long-term planning and consideration of the consequences of our actions. The goal is to create strategies that ensure the long-term viability of People, Planet, and Profit.
Leading companies such as Nike, Toyota, and Siemens are prioritizing sustainable innovation in their business models, setting an example for others to follow. In this Sustainability training presentation, you will learn key concepts, principles, and practices of sustainability applicable across industries. This training aims to create awareness and educate employees, senior executives, consultants, and other key stakeholders, including investors, policymakers, and supply chain partners, on the importance and implementation of sustainability.
LEARNING OBJECTIVES
1. Develop a comprehensive understanding of the fundamental principles and concepts that form the foundation of sustainability within corporate environments.
2. Explore the sustainability implementation model, focusing on effective measures and reporting strategies to track and communicate sustainability efforts.
3. Identify and define best practices and critical success factors essential for achieving sustainability goals within organizations.
CONTENTS
1. Introduction and Key Concepts of Sustainability
2. Principles and Practices of Sustainability
3. Measures and Reporting in Sustainability
4. Sustainability Implementation & Best Practices
To download the complete presentation, visit: https://www.oeconsulting.com.sg/training-presentations
Implicitly or explicitly all competing businesses employ a strategy to select a mix
of marketing resources. Formulating such competitive strategies fundamentally
involves recognizing relationships between elements of the marketing mix (e.g.,
price and product quality), as well as assessing competitive and market conditions
(i.e., industry structure in the language of economics).
At Techbox Square, in Singapore, we're not just creative web designers and developers, we're the driving force behind your brand identity. Contact us today.
Cracking the Workplace Discipline Code Main.pptxWorkforce Group
ย
Cultivating and maintaining discipline within teams is a critical differentiator for successful organisations.
Forward-thinking leaders and business managers understand the impact that discipline has on organisational success. A disciplined workforce operates with clarity, focus, and a shared understanding of expectations, ultimately driving better results, optimising productivity, and facilitating seamless collaboration.
Although discipline is not a one-size-fits-all approach, it can help create a work environment that encourages personal growth and accountability rather than solely relying on punitive measures.
In this deck, you will learn the significance of workplace discipline for organisational success. Youโll also learn
โข Four (4) workplace discipline methods you should consider
โข The best and most practical approach to implementing workplace discipline.
โข Three (3) key tips to maintain a disciplined workplace.
What is the TDS Return Filing Due Date for FY 2024-25.pdfseoforlegalpillers
ย
It is crucial for the taxpayers to understand about the TDS Return Filing Due Date, so that they can fulfill your TDS obligations efficiently. Taxpayers can avoid penalties by sticking to the deadlines and by accurate filing of TDS. Timely filing of TDS will make sure about the availability of tax credits. You can also seek the professional guidance of experts like Legal Pillers for timely filing of the TDS Return.
Kseniya Leshchenko: Shared development support service model as the way to ma...Lviv Startup Club
ย
Kseniya Leshchenko: Shared development support service model as the way to make small projects with small budgets profitable for the company (UA)
Kyiv PMDay 2024 Summer
Website โ www.pmday.org
Youtube โ https://www.youtube.com/startuplviv
FB โ https://www.facebook.com/pmdayconference
Business Valuation Principles for EntrepreneursBen Wann
ย
This insightful presentation is designed to equip entrepreneurs with the essential knowledge and tools needed to accurately value their businesses. Understanding business valuation is crucial for making informed decisions, whether you're seeking investment, planning to sell, or simply want to gauge your company's worth.
B2B payments are rapidly changing. Find out the 5 key questions you need to be asking yourself to be sure you are mastering B2B payments today. Learn more at www.BlueSnap.com.
2. Synergy Institute of Engineering &
Technology,Dhenkanal
Seminar on
Power Grid Design
Submitted by
Susanta Das
7th Semester B.Tech
Reg.No-0901230234
Seminar Guide Mr. A. Panda
Department of Electrical
Engg.SIET,Dhenkanal. 2
3. Outline of Presentation
๏ Introduction
๏ Need of Power Grids
๏ Selection Site
๏ Layout Design
1.Busbar Schemes
2.Electrical Layout Drawing
3.Bill of Material
๏ Safety Clearance in Grid
๏ Design of Earth Mat
๏ Control Room
๏ Switch/Relay Room
๏ Grid Equipments
๏ Conclusion
๏ Reference
Department of Electrical Engg.SIET,Dhenkanal.
4. INTRODUCTION
๏ An electrical grid is an
interconnected network for
delivering electricity from
suppliers to consumers. It
consists of three main
components; 1) power
station that produce
electricity from combustible
fuels or non-combustible
fuels; 2) transmission
lines that carry electricity
from power plants to
demand centers; and
3) transformers that reduce
voltage so distribution lines
carry power for final
delivery.
Department of Electrical Engg.SIET,Dhenkanal.
5. WHY WE NEED GRID?
๏ Improvement of
Reliability
๏ Improvement of
economics
๏ Improvement of
efficiency
๏ Imrovement of power
quality
๏ Improvement of security
& safety
๏ Controller of entire power
system
Department of Electrical Engg.SIET,Dhenkanal.
6. SELECTION OF SITE
๏ Selection of site for construction of a Grid Sub Station is the first
and important activity. This needs meticulous planning, fore-sight,
skillful observation and handling so that the selected site is
technically, environmentally, economically and socially optimal
and is the best suited to the requirements
The site should be:-
๏ As near the load centre as possible.
๏ Easily accessible to the public road to facilitate transport of
material
๏ Above highest flood level (HFL) so that there is no water logging.
๏ Sufficiently away from areas where police and military rifle
practices are held.
๏ Free from master plans / layouts or future development activities
to have free line
๏ The should be far away from Airport
Department of Electrical Engg.SIET,Dhenkanal.
7. REQUIREMENT OF LAND / AREA:-
๏ The site should have sufficient area to properly accommodate
the Sub Station buildings, structures, equipments, etc. and
should have the sufficient area for future extension of the
buildings and / or switchyard.
๏ The requirement of land for construction of Sub Station including
staff colony is as under:
S.No. Voltage Class of GSS Required Area
1 400 20.0 Hectare
2 220 6.0 Hectare
3 132 3.5 Hectare
Department of Electrical Engg.SIET,Dhenkanal.
8. Layout Design-Bus bar Schemes
The commonly used
bus bar schemes at
Sub Stations are:
๏ Single bus bar.
๏ Main and Auxiliary
bus bar.
๏ Double bus bar.
๏ Double Main and
Auxiliary bus bar
๏ One and a half
breaker scheme.
Department of Electrical Engg.SIET,Dhenkanal.
9. Single bus bar:-
๏ This is the simplest switching scheme
in which each circuit is provided with
one circuit breaker.
๏ This arrangement offers little security
against bus bar faults .
๏ The entire Sub Station is lost in case
of a fault on the bus bar.
๏ In case of maintenance of circuit
breaker, the associated feeder has
also to be shutdown.
Main and Auxiliary bus
Bar:-
๏ This is technically a single bus bar
arrangement with an additional
bus bar called โAuxiliary busโ.
๏ As in the case of single bus
arrangement, due to the fault the
entire substation is lost.
๏ This bus arrangement has been
extensively used in 132 kV Sub
Stations.
Department of Electrical Engg.SIET,Dhenkanal.
10. Double Bus Bar
๏ In this scheme, a double bus bar
arrangement is provided. Each circuit
can be connected to either one of these
bus bars through respective bus bar
isolator.
๏ Bus coupler breaker is also provided so
that the circuits can be switched on from
one bus to the other on load.
๏ This scheme suffers from the
disadvantage that when any circuit
breaker is taken out for maintenance, the
associated feeder has to be shutdown
๏ This Bus bar arrangement was generally
used in earlier 220 kV sub stations.
DOUBLE MAIN AND
AUXILIARY BUS BAR
ARRANGEMENT
๏ The limitation of double bus bar
scheme can be overcome by using
additional Auxiliary bus,.
๏ The feeder is transferred to the
Auxiliary bus during maintenance of its
controlling circuit breaker without
affecting the other ckt.
Department of Electrical Engg.SIET,Dhenkanal.
11. One & A Half Breaker Arrangement
๏ In this scheme, three circuit breakers
are used for controlling two circuits
which are connected between two bus
bars. Normally, both the bus bars are
in service.
๏ A fault on any one of the bus bars is
cleared by opening of the associated
circuit breakers connected to the faulty
bus bar without affecting continuity of
supply. Similarly any circuit breaker
can be taken out for maintenance
without causing interruption.
๏ Load transfer is achieved through the
breakers and, therefore, the operation
is simple.
๏ The breaker and a half scheme is best
for those substations which handle
large quantities of power and where
the orientation of out going.
๏ This scheme has been used in the
400 kV substations.
Department of Electrical Engg.SIET,Dhenkanal.
14. List of Material๏ The lists of material are only typical and cover the general requirement. Any
other
๏ equipment / structure / material which may be required for construction of
Sub Station as
๏ per layout and other requirements and not included in the above typical lists
of
Department of Electrical Engg.SIET,Dhenkanal.
17. Safety Clearance๏ The various equipments and associated / required facilities have to be so arranged within the substation that
specified minimum clearances are always available from the point of view of the system reliability and safety
of operating personnel. These include the minimum clearances from live parts to earth, between live parts of
adjacent phases and sectional clearance between live parts of adjacent circuits / bays. It must be ensured
that sufficient clearance to ground is also available within the Sub Station so as to ensure safety of the
personnel moving about within the switchyard.
๏ As per Rule 64 (2) of the Indian Electricity Rules, 1956, the following safety working
๏ clearances shall be maintained for the bare conductors and live parts of any apparatus in any
๏ Sub Stations, excluding over head lines of HV and EHV installations:
Nominal
system
Voltage
in (kv)
Highes
t
Syste
m
Voltag
e in(kv)
Lightin
g
impulse
Level(K
Vp)
Switching
Implulse
Voltage in
(KVp)
Minm
Clearance
Betn Phase
&Earth(mm)
Minm
clearanc
e Betn
Phases
(in mm)
Safety
Clearan
ce(mm)
Grou
nd
Clear
ance(
mm)
11 12 70 ---- 178 229 2600 3700
33 36 170 ---- 320 320 2800 3700
132 145 550
650
---- 1100
1300
1100
1300
3700
3800
4600
4600
220 245 950
1050
---- 1900
2100
1900
2100
4300
4600
5500
5500
400 420 1425 1050(Ph-
E)
3400
----
----
4200
6400 8000
18. Earth Mat Design
๏ Provision of adequate earthing system
in a Sub Station is extremely important
for the safety of the operating
personnel as well as for proper system
operation and performance of the
protective devices.
๏ The primary requirements of a good
earthing system in a Sub Station are
a):-The impedance to ground should
be as low as possible but it should not
exceed 1.0 (ONE) Ohm.
b):- The Step Potential, which is the
maximum value of the potential
difference possible of being shunted by
a human body between two accessible
points on the ground separated by the
distance of one pace (which may be
assumed to be one metre), should be
within safe limits.
c):- Touch Potential, which is the
maximum value of potential difference
between a point on the ground and a
point on an object likely to carry fault
current such that the points can be
touched by a person, should also be
within safe limits.
Department of Electrical Engg.SIET,Dhenkanal.
19. Cont.
The details of the earthing material generally used in a
sub station are given below:
20. Design of Control Room
๏ The control room is the
main command centre of
the substation. The entire
operation of the site is
monitored and controlled
from this central location.
๏ A control room may range
from a small, seldom
manned, non-ventilated
room to a large, air
conditioned area containing
numerous staff members
and electronic equipment
(PCs, control
panels/consoles, electrical
and electronic switching
devices, under floor
cabling, etc.).
Department of Electrical Engg.SIET,Dhenkanal.
21. Design of battery Room
๏ The Battery Room houses lead acid or
nickel cadmium batteries for uninterrupted
power supply (UPS) to the substation.
๏ In power grid normally 110 no. of batteries
are present, having each capacity of 2.1V
to maintain 220V output & the specific
gravity of liquid is 1.835.
๏ Power House FCBC are designed to
supply continuous power to the DC load
and simultaneously charge the batteries
connected. Input supply form 415V. AC 3
Phase or 220V. AC 1 Ph. is converted to
regulated DC. The charger has two
independent systems.
๏ Normally the DC Power is supplied to he
load by the Float Charger. It also supplies
trickle current to the battery to keep it
healthy. If the charging current under Float
Mode exceeds a set level.Boost charger is
switched ON. It supplies Quick charging
current to the battery. On battery reaching
the set value the Boost Charger is switched
OFF.
Department of Electrical Engg.SIET,Dhenkanal.
22. Design of Switch/Relay Room
๏ The Switch Room
accommodates high density of
electronic equipment housed
in cabinets and automated
switch-gear. In-cabinet
equipment maintain the
primary functions of the facility
and form the switching
interface between the Control
Room and the field
equipment. The area may also
accommodate a significant
amount of metering and
logging equipment. Due to the
high volume of critical
electronic equipment, it is
essential that a fire event be
detected before the operation
of the plant is compromised.Department of Electrical Engg.SIET,Dhenkanal.
23. Grid Equipments
Lighting Arrestor
๏ It is an instrument that protect
vital equipments in the grid
๏ when a lightning strikes a
power transmission line, the
induced high voltage travels
along the line towards both
ends; this arrester will bypass
this high voltage to the ground
so that the nearby transformer
will not be damaged.
Line Volt.(KV) L.A.Rating(KV)
400 327
220 180
132 108
33 27
24. CVT:-
๏ It is that type tfr which is used to
measure potential
๏ It is the major advantage of PT, &
also used for carrier
communication, which replace the
coupling capacitor.
๏ At first for carrier communication a
coupling capacitor is used with a
PT, which is costlier than CVT.
๏ It act as a high pass filter.
Connection diagram of CVT
25. Potential
transformer:-
๏ Potential Transformer or Voltage
Transformer are used in electrical
power system for stepping down
the system voltage to a safe value
which can be fed to low ratings
meters and relays. Commercially
available relays and meters used
for protection and metering, are
designed for low voltage.
26. Current Transformer:-
๏ A current transformer is
used in high voltage
circuits where it is not
possible to measure
current directly.
๏ A CT is a step up
transformer with only one
turn in primary. There will
be as many cores based
on the purposes like
metering, protection etc.
๏ The secondary of a CT
should never be kept open
circuited because very high
flux will be developed in the
secondary and hence it
may be damaged.
27. Power TRANSFORMER
๏ It is a static device which
transforms electrical energy from
one ckt to another ckt without
change of frequency, but changing
voltage with the principle mutual
induction.
๏ Most of the power transformer are
in MVA ratings.
๏ It is the most costlier equipments
in the grid.
28. ๏ INSULATOR:-
๏ Insulators are used to prevent
flow of current from
conducting material to non
conducting material.
๏ It should be mechanically
strong & high dielectric
strength.
๏ Each insulator rating is of
11kv to 16kv.
Wave Trap:-
๏It is the combination of inductance &
capacitance, which act as a low pass filter,
which passes low frequencies in to the
grid, & this frequency is used in the grid.
๏The Line trap offers high impedance to
the high frequency communication signals
thus obstructs the flow of these signals in
to the substation bus bars. If there were
not to be there, then signal loss is more
and communication will be
ineffective/probably impossible.
29. Circuit breaker:-
๏ It is protective equipments in the
grid.
๏ It is the automatic on load switch.
๏ There are of 5 medium type of
circuit breaker., but SF6 ckt
breaker is used for best.
Isolators:-
๏ This is an off load switching
device to used open or close for
flow of current or not to flow
respectively in the grid.
30. Conclusion:-
๏ Grid is the nodal point of the
entire power system.
๏ It has two objectives i.e.1: Supply
Quality Power, 2:Supply the power
from source to load with an
economic reasons.
๏ AS Grids are interconnected so,
there is an improvement of
reliability of can achieved.
๏ As grid is the nodal point, if it fails
to work, then entire power system
will fails.
๏ Grid efficiency is lower i.e. 50-
70%.
๏ As Grid has too many equipments
so, design of grid is too costlier.
31. Reference:-
๏ Construction Manual for substations by Shreemat Pandey Chairman &
Managing Director Jaipur Rajasthan Rajya Vidyut Prasaran Nigam Ltd.
๏ Albert, R., Albert, I., and Nakarado, G. L. (2004). Structural Vulnerability of
the North American Power Grid. Physical Review E 69 025103(R). 1-4 pgs.