This project involves the theoretical study of Protection Devices, Protection Schemes, Analysis of Control and Logical Blocks of relays being used in the project and practical implementation of both schemes in DigSilent PowerFactory.
The document discusses transformer protection. It describes different types of faults that can occur in transformers, both internal and external. It then discusses various protection methods for transformers, including differential protection, sudden pressure relays, overcurrent protection, and thermal protection. It also provides details on magnetizing inrush current and how it is influenced by factors like transformer size, system resistance, and residual flux levels.
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
This document provides guidance on setting calculations for transformer differential protection. It discusses examining CT performance, calculating winding "tap" values, and determining pickup points for the 87T, 87H, and 87GD elements. Key steps include checking CT and relay ratings, selecting tap settings, setting the 87T minimum pickup and slope settings, setting harmonic restraint values, and setting the 87H unrestrained high set differential pickup and delay. The goal is to provide high-speed protection while avoiding misoperation during conditions like inrush current.
1. A three-phase fault occurred at Bus 5 in the power system. The fault current (IF) was calculated to be 5 pu based on the total fault impedance of 16.0j ohms as seen from Bus 5.
2. The fault current supplied by Generator 1 (IG1F) was calculated to be 2.1 pu, and by Generator 2 (IG2F) was calculated to be 8.0 pu.
3. The voltages during fault condition were calculated to be 0.68 pu at Bus 5 and 0.24 pu at Bus 3, indicating a voltage drop from the pre-fault voltage of 1.0 pu at all buses.
Transmission lines require protective schemes due to their long lengths and exposure to the open atmosphere, making faults more common. The key methods for protecting transmission lines are:
1. Unit and non-unit type protections, with the main types being differential, overcurrent, distance, and carrier current protections.
2. Distance relays operate based on the impedance seen from the relay location, tripping if the impedance indicates a fault within the reach of the relay. Directional distance relays can discriminate between faults in different directions.
3. A three-step distance protection scheme uses underreach, definite reach, and overreach zones to isolate faults along the transmission line while coordinating protection across multiple line sections
Busbar protection uses differential protection to isolate faults on the busbar. It works by comparing the current entering and leaving the busbar using CTs - any difference indicates an internal fault. Proper CT ratios and a stabilizing resistance are needed to restrain operation for external faults. PS class CTs are preferred over other classes due to more consistent accuracy. While busbar protection is important, it is currently not implemented in line at MRSS due to some unspecified reason.
The document discusses transformer protection. It describes different types of faults that can occur in transformers, both internal and external. It then discusses various protection methods for transformers, including differential protection, sudden pressure relays, overcurrent protection, and thermal protection. It also provides details on magnetizing inrush current and how it is influenced by factors like transformer size, system resistance, and residual flux levels.
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
This document provides guidance on setting calculations for transformer differential protection. It discusses examining CT performance, calculating winding "tap" values, and determining pickup points for the 87T, 87H, and 87GD elements. Key steps include checking CT and relay ratings, selecting tap settings, setting the 87T minimum pickup and slope settings, setting harmonic restraint values, and setting the 87H unrestrained high set differential pickup and delay. The goal is to provide high-speed protection while avoiding misoperation during conditions like inrush current.
1. A three-phase fault occurred at Bus 5 in the power system. The fault current (IF) was calculated to be 5 pu based on the total fault impedance of 16.0j ohms as seen from Bus 5.
2. The fault current supplied by Generator 1 (IG1F) was calculated to be 2.1 pu, and by Generator 2 (IG2F) was calculated to be 8.0 pu.
3. The voltages during fault condition were calculated to be 0.68 pu at Bus 5 and 0.24 pu at Bus 3, indicating a voltage drop from the pre-fault voltage of 1.0 pu at all buses.
Transmission lines require protective schemes due to their long lengths and exposure to the open atmosphere, making faults more common. The key methods for protecting transmission lines are:
1. Unit and non-unit type protections, with the main types being differential, overcurrent, distance, and carrier current protections.
2. Distance relays operate based on the impedance seen from the relay location, tripping if the impedance indicates a fault within the reach of the relay. Directional distance relays can discriminate between faults in different directions.
3. A three-step distance protection scheme uses underreach, definite reach, and overreach zones to isolate faults along the transmission line while coordinating protection across multiple line sections
Busbar protection uses differential protection to isolate faults on the busbar. It works by comparing the current entering and leaving the busbar using CTs - any difference indicates an internal fault. Proper CT ratios and a stabilizing resistance are needed to restrain operation for external faults. PS class CTs are preferred over other classes due to more consistent accuracy. While busbar protection is important, it is currently not implemented in line at MRSS due to some unspecified reason.
This Presentation is about l.v switch gear design, presented during the graduation project final discussion 15/7/2018.
It presented a good summary of switch gear components and types and practicing on AL.HAMOOL W.T.P M.D.B design using SIEMENS SIVACON S8
This document provides an introduction to power system fault analysis. It discusses the importance of accurately analyzing fault conditions and their effects on the power system. Various types of faults are described, including short circuits, open circuits, simultaneous faults, and winding faults. Factors that affect fault severity are also outlined. The document then discusses methods for calculating faults, including using symmetrical components and sequence networks. An example fault calculation is provided to illustrate the process. Fault analysis is necessary for proper power system design, operation, and protection.
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
This presentation discusses the key protection devices used in electrical substations. It introduces current transformers and potential transformers, which reduce current and voltage levels for protection relays. Relays detect faults by measuring currents and voltages. When a fault is detected, relays signal circuit breakers to isolate the faulty component. Other protection devices discussed include lightning arresters, isolators, and surge diverters. The objective of the substation protection system is to isolate only faulty parts of the network while keeping the rest operational.
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
Power Transformer Differential protectionRishi Tandon
This document discusses power transformer protection. It begins by explaining that transformers are static devices that transform electrical energy between circuits without changing frequency. Power transformers are vital but expensive components that are difficult to repair if damaged. Transformer protection is needed to prevent severe damage from faults and ensure continuous network operation. Common fault types and causes are then outlined, including insulation breakdown, overheating, contamination, and phase/turn faults. The document proceeds to describe the general scheme of differential protection and specific protection functions like bias differential, overfluxing, over/under voltage, and restricted earth fault protection. It provides an example calculation for setting a transformer differential relay and diagrams demonstrating differential relay operation. Finally, it reviews models from various manufacturers and presents a case study
Transmission lines have four parameters that characterize them: resistance, inductance, capacitance, and conductance. These distributed parameters determine the power carrying capacity and voltage drop across the line. Short lines only consider the series resistance and inductance, while medium and long lines must also account for the distributed shunt capacitance. The resistance of overhead transmission lines is affected by factors like skin effect, temperature, bundling of conductors, and proximity effect between phases.
This document provides an introduction to Flexible AC Transmission Systems (FACTS). It discusses why transmission interconnections are needed, including to minimize generation and fuel costs and supply electricity at minimum cost. It also explores if the full potential of interconnections can be used and describes opportunities for FACTS technology to control power flow and enhance transmission line usage. Some key limitations on transmission line loading capability like thermal, dielectric, and stability limits are also summarized.
This document provides information on a Power System Protection course taught at Vivekanandha College of Engineering for Women. The syllabus covers 5 units: introduction to protection schemes, relay operating principles and characteristics, apparatus protection, theory of circuit interruption, and circuit breakers. It lists textbooks and presents details on each unit, including topics like relay types, transformer/generator/motor protection, arc phenomena, and different circuit breaker types. The last section provides references for textbooks, websites, and presentations on related topics.
This document discusses out-of-step (OOS) protection fundamentals. It explains that power swings can cause undesired relay operation and lead to cascading outages. It discusses relay elements prone to operate during power swings like distance and overcurrent relays. It describes stable and unstable power swings and the need for OOS protection to separate asynchronous areas. The document outlines various OOS protection functions like power swing blocking and out-of-step tripping and discusses their benefits. It analyzes relay and generator performance during OOS conditions using system examples. Finally, it recommends protection system and other grid improvements to preserve stability.
Relays are electromagnetic switches that are designed to detect faults on electrical circuits and trip circuit breakers. They use a low amperage control circuit to operate a high amperage tripping circuit. Relays can be classified based on their construction, applications, or time of operation. Common types include impedance, reactance, mho, and digital protective relays. Impedance relays have an overcurrent operative torque and a voltage-restraining torque. Reactance relays have a current operative torque and a directional restraining torque. Mho relays induce operative torque from both voltage and current and have a voltage-restraining torque. Digital protective relays use microprocessors to analyze voltages, currents, and
The document discusses short-circuit analysis based on ANSI standards. It describes the different types of short-circuit faults, how fault current is calculated, and the components that contribute current. The ANSI method models sources using an internal voltage behind an impedance and represents them in multiple networks to calculate fault currents at different time periods. It also explains how fault currents are used to verify protective device ratings and settings.
The power system is protected through a zone protection scheme where the system is divided into sections, with each zone having one or more protective relays coordinated with the overall protection system. The zones are arranged to overlap so that no part of the system remains unprotected, and circuit breakers are located in the overlapped regions. Protective relaying schemes must be reliable, selective, and fast acting. Reliability ensures the relay will operate correctly, selectivity allows the relay to distinguish faults inside and outside its zone, and speed minimizes fault duration and equipment damage. Modern high-speed relays have operating times of 1-2 cycles while circuit breakers have interrupting times of 2.5-3 cycles, resulting in total clearing
Power System Analysis was a core subject for Electrical & Electronics Engineering, Based On Anna University Syllabus. The Whole Subject was there in this document.
Share with it ur friends & Follow me for more updates.!
This document is a major project report submitted by Sandiip Guptaa in partial fulfillment of their B.Tech degree in Electrical and Electronics Engineering at Sikkim Manipal Institute of Technology. The project involved modelling the integration of renewable energy sources like solar and wind in PSCAD. It describes the modelling of PV and wind systems, provides an overview of PSCAD simulation tool, discusses microgrid components, operation and control techniques. It also includes the objectives, methodology, models developed and output results of the project on modelling renewable energy integration in a microgrid using PSCAD software.
MULTIPLE TESTS ON TRANSFORMER WITH THE HELP OF MATLAB SIMULINKIRJET Journal
The document describes using MATLAB Simulink to model and simulate transformer tests, including open circuit, short circuit, and load tests. This allows performing the tests in a simpler, more efficient manner compared to traditional methods that require extensive manual measurements. The MATLAB model calculates key parameters like resistance, inductance, and efficiency. It reduces errors and human effort compared to conventional test equipment. The model is verified by comparing results to manual calculations and can be a useful educational and analysis tool.
This Presentation is about l.v switch gear design, presented during the graduation project final discussion 15/7/2018.
It presented a good summary of switch gear components and types and practicing on AL.HAMOOL W.T.P M.D.B design using SIEMENS SIVACON S8
This document provides an introduction to power system fault analysis. It discusses the importance of accurately analyzing fault conditions and their effects on the power system. Various types of faults are described, including short circuits, open circuits, simultaneous faults, and winding faults. Factors that affect fault severity are also outlined. The document then discusses methods for calculating faults, including using symmetrical components and sequence networks. An example fault calculation is provided to illustrate the process. Fault analysis is necessary for proper power system design, operation, and protection.
The document discusses busbar protection, including the need for busbar protection, types of busbar protections like high impedance, medium impedance and low impedance protections. It describes the requirements of busbar protection like short tripping time and stable operation during external faults. The document discusses different busbar arrangements and applications of numerical busbar protection systems like RADSS. It provides examples of busbar protection schemes for different bus configurations. The document also includes excerpts from technical manuals providing recommendations on busbar protection in substations.
Tutorial on Distance and Over Current ProtectionSARAVANAN A
Contents
• Protection Philosophy of ERPC
• Computation of Distance Relay Setting
• System Study to Understand Distance Relay
Behaviour
• DOC and DEF for EHV system
This presentation discusses the key protection devices used in electrical substations. It introduces current transformers and potential transformers, which reduce current and voltage levels for protection relays. Relays detect faults by measuring currents and voltages. When a fault is detected, relays signal circuit breakers to isolate the faulty component. Other protection devices discussed include lightning arresters, isolators, and surge diverters. The objective of the substation protection system is to isolate only faulty parts of the network while keeping the rest operational.
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
Power Transformer Differential protectionRishi Tandon
This document discusses power transformer protection. It begins by explaining that transformers are static devices that transform electrical energy between circuits without changing frequency. Power transformers are vital but expensive components that are difficult to repair if damaged. Transformer protection is needed to prevent severe damage from faults and ensure continuous network operation. Common fault types and causes are then outlined, including insulation breakdown, overheating, contamination, and phase/turn faults. The document proceeds to describe the general scheme of differential protection and specific protection functions like bias differential, overfluxing, over/under voltage, and restricted earth fault protection. It provides an example calculation for setting a transformer differential relay and diagrams demonstrating differential relay operation. Finally, it reviews models from various manufacturers and presents a case study
Transmission lines have four parameters that characterize them: resistance, inductance, capacitance, and conductance. These distributed parameters determine the power carrying capacity and voltage drop across the line. Short lines only consider the series resistance and inductance, while medium and long lines must also account for the distributed shunt capacitance. The resistance of overhead transmission lines is affected by factors like skin effect, temperature, bundling of conductors, and proximity effect between phases.
This document provides an introduction to Flexible AC Transmission Systems (FACTS). It discusses why transmission interconnections are needed, including to minimize generation and fuel costs and supply electricity at minimum cost. It also explores if the full potential of interconnections can be used and describes opportunities for FACTS technology to control power flow and enhance transmission line usage. Some key limitations on transmission line loading capability like thermal, dielectric, and stability limits are also summarized.
This document provides information on a Power System Protection course taught at Vivekanandha College of Engineering for Women. The syllabus covers 5 units: introduction to protection schemes, relay operating principles and characteristics, apparatus protection, theory of circuit interruption, and circuit breakers. It lists textbooks and presents details on each unit, including topics like relay types, transformer/generator/motor protection, arc phenomena, and different circuit breaker types. The last section provides references for textbooks, websites, and presentations on related topics.
This document discusses out-of-step (OOS) protection fundamentals. It explains that power swings can cause undesired relay operation and lead to cascading outages. It discusses relay elements prone to operate during power swings like distance and overcurrent relays. It describes stable and unstable power swings and the need for OOS protection to separate asynchronous areas. The document outlines various OOS protection functions like power swing blocking and out-of-step tripping and discusses their benefits. It analyzes relay and generator performance during OOS conditions using system examples. Finally, it recommends protection system and other grid improvements to preserve stability.
Relays are electromagnetic switches that are designed to detect faults on electrical circuits and trip circuit breakers. They use a low amperage control circuit to operate a high amperage tripping circuit. Relays can be classified based on their construction, applications, or time of operation. Common types include impedance, reactance, mho, and digital protective relays. Impedance relays have an overcurrent operative torque and a voltage-restraining torque. Reactance relays have a current operative torque and a directional restraining torque. Mho relays induce operative torque from both voltage and current and have a voltage-restraining torque. Digital protective relays use microprocessors to analyze voltages, currents, and
The document discusses short-circuit analysis based on ANSI standards. It describes the different types of short-circuit faults, how fault current is calculated, and the components that contribute current. The ANSI method models sources using an internal voltage behind an impedance and represents them in multiple networks to calculate fault currents at different time periods. It also explains how fault currents are used to verify protective device ratings and settings.
The power system is protected through a zone protection scheme where the system is divided into sections, with each zone having one or more protective relays coordinated with the overall protection system. The zones are arranged to overlap so that no part of the system remains unprotected, and circuit breakers are located in the overlapped regions. Protective relaying schemes must be reliable, selective, and fast acting. Reliability ensures the relay will operate correctly, selectivity allows the relay to distinguish faults inside and outside its zone, and speed minimizes fault duration and equipment damage. Modern high-speed relays have operating times of 1-2 cycles while circuit breakers have interrupting times of 2.5-3 cycles, resulting in total clearing
Power System Analysis was a core subject for Electrical & Electronics Engineering, Based On Anna University Syllabus. The Whole Subject was there in this document.
Share with it ur friends & Follow me for more updates.!
This document is a major project report submitted by Sandiip Guptaa in partial fulfillment of their B.Tech degree in Electrical and Electronics Engineering at Sikkim Manipal Institute of Technology. The project involved modelling the integration of renewable energy sources like solar and wind in PSCAD. It describes the modelling of PV and wind systems, provides an overview of PSCAD simulation tool, discusses microgrid components, operation and control techniques. It also includes the objectives, methodology, models developed and output results of the project on modelling renewable energy integration in a microgrid using PSCAD software.
MULTIPLE TESTS ON TRANSFORMER WITH THE HELP OF MATLAB SIMULINKIRJET Journal
The document describes using MATLAB Simulink to model and simulate transformer tests, including open circuit, short circuit, and load tests. This allows performing the tests in a simpler, more efficient manner compared to traditional methods that require extensive manual measurements. The MATLAB model calculates key parameters like resistance, inductance, and efficiency. It reduces errors and human effort compared to conventional test equipment. The model is verified by comparing results to manual calculations and can be a useful educational and analysis tool.
Analysis of distance protection relay in presence of static synchronous compe...IAEME Publication
This document analyzes the impact of a Static Synchronous Compensator (STATCOM) on distance protection relays for transmission lines. It presents a simulation of a 400kV, 300km transmission line with a 100MVA STATCOM at the midpoint and distance relays at each end. The simulation shows that the STATCOM affects the impedance seen by the relays during faults, as it injects current and alters line parameters. Traditional relay settings based solely on line impedance may not operate correctly with a STATCOM present. The document discusses modeling of the transmission line, STATCOM, and distance relays in MATLAB/Simulink to study their performance under normal and fault conditions with the STATCOM.
STUDY AND ANALYSIS OF PROTECTION SCHEME OF DIGITAL SUBSTATION USING IEC61850-...IAEME Publication
Substations are a fundamental part in electrical energy transmission and
distribution. The role of a substation is to transfer and transform electrical energy by
stepping up or down the voltage. To do this, high voltage switching equipment and
power transformers are used, in addition to instrument transformers that supply the
status of the primary system to the secondary equipment. Substation Automation
Systems are then used to control, protect and monitor the substations. The IEC 61850
standard developed digital substation with most advanced techniques. The IEC 61850
standard define in its sub- clauses IEC 600448 and IEC 61850-9-2 about digital
interface, digital communication and Sampled Values transmission over an Ethernet
link called Process Bus. Process Bus technology mainly developed in order to reduce
the usage of copper wiring at substation control by introducing IEC 61850-9-2 digital
interface.
Six-port Interferometer for W-band Transceivers: Design and CharacterizationIJECEIAES
The study has presented an extensive analysis of an integrated millimeter wave six-port interferometer, operating over a 10 GHz band, from 80 to 90 GHz. It has covered both semi-unlicensed point-to-point links (81-86 GHz), and imaging sensor system frequencies (above 85 GHz). An in-house process is used to fabricate miniaturized hybrid millimeter wave integrated circuits on a very thin ceramic substrate. Two-port S-parameter measurements are performed on a minimum number of circuits integrated on the same die, exploiting the circuit’s physical symmetry and chosen to collect enough data for full-port characterization. Based on these measurements on an integrated prototype, a six-port circuit computer model implemented and advanced system simulations performed for circuit analysis. Interferometer performances evaluated using several methods: analysis of harmonic balance, qi points’, homodyne quadrature demodulation, and error vector modulation (EVM). The analysis showed that this circuit can directly perform, without any calibration, the demodulation of various PSK and QAM signals over the 10 GHz band, with very good results.
IRJET- Multi-Level Inverter for Solar On-Grid System DesignIRJET Journal
1) The document discusses the design of a multi-level inverter for a solar on-grid system to provide clean and sustainable energy from photovoltaic systems.
2) A key component of grid-connected photovoltaic systems is the inverter, and multi-level inverters offer benefits like lower total harmonic distortion.
3) The proposed system includes maximum power point tracking to optimize solar panel output, a boost converter, and a three-level cascaded H-bridge inverter to integrate solar energy into the grid in a efficient manner.
Arc Fault and Flash Signal Analysis and Detection in DC Distribution Systems ...IRJET Journal
This document summarizes a research paper that proposes a new approach for detecting arc faults and flashes in DC distribution systems using wavelet transform and fuzzy logic. The researchers designed a model of an arc condition and analyzed the arc voltage using wavelet transform. Wavelet analysis was able to extract features of the signal that were then used to design a fuzzy rule base. This approach allows for arc fault detection by analyzing features in the PV output voltage. The full system was implemented and tested in MATLAB. The proposed method uses wavelet transform for spectral energy calibration of arc faults, which provides a more detectable signal signature compared to other techniques. This allows for accurate arc fault analysis and classification in DC systems.
TRANSFORMER FAULT DETECTION AND MONITORINGIRJET Journal
This document describes a project to detect and monitor faults in power transformers using sensors and GSM technology. The system measures four parameters - oil level, temperature, open circuit, and short circuit. Sensors detect faults and send SMS alerts to responsible personnel. The aim is to reduce response time for faults to protect transformers and maintain power stability. When faults are detected, the controlling unit can automatically shut down power.
Improved Nine-Level Transformerless Inverter with Reduced Part CountIRJET Journal
The document discusses improved transformerless inverter topologies for connecting photovoltaic (PV) panels to the electric grid. It describes various single-phase transformerless inverter configurations including H-bridge, HERIC, and a proposed seven-switch topology. The proposed topology aims to reduce leakage currents by maintaining a constant common mode voltage. Simulation results show the proposed topology produces a nine-level output voltage waveform and maintains leakage currents below permissible limits.
Fault analysis in power system using power systems computer aided designIJAAS Team
This work presents a fault analysis simulation model of an IEEE 30 bus system in a distribution network. This work annalysed the effect of fault current and fault voltage in a distribution system. A circuit breaker was introduced into the system to neutralize the effect of the fault. The system was run on a PSCAD software and results were obtained. The system was monitored based on the start time and the end time of the fault and how well the circuit breaker reacts with those times. Fault occurred from 0.100 to 0.300 seconds before it was removed. At the time fault was not applied (i.e. from 0.00 to 0.100 and from 0.300 to 0.72), the circuit breaker was close and became open when fault was applied so as to cut off current flow through the line.The result obtained gave the disruption caused by the fault and the quick response of the circuit breaker in neutralizing it. Results gotten are based on when the circuit breaker is close and no fault is applied and when the circuit breaker is open due to fault. From this work, it was obtained that circuit breakers are very essential in system protection and reliability.
The most important components of the distributed generation frameworks is the GTIs which is an interface amidst the utility and the source of energy. The recent years have seen an increased interest in the design and usage of GTIs due to its smaller weight and size, low cost and higher efficiency. But the problem of leakage currents in the transformerless inverter that is dependant on its topology and control scheme needs to be looked into carefully. Also, the high performance of the GTI requires a stringent control and various control systems are being developed and applied to the GTIs. This paper reviews the various topologies that are classified based on the attributes of the leakage current and the method of decoupling. Further it reviews and compares the different control techniques applied to the GTIs with respect to the frame of reference, controller, modulation technique and the control parameters considered.
It is actively developed by the Institute for Automation of Complex Power Systems.
Presented by Marija Stevic during ERIGrid - VILLAS workshop on 13th September 2018 at OFFIS, Oldenburg.
https://www.acs.eonerc.rwth-aachen.de
https://www.fein-aachen.org/projects/villas-framework/
The document discusses current limiting transformers. Current limiting transformers limit secondary current under short circuit conditions by using core gaps in the magnetic shunt paths. This prevents damage to secondary windings or loads from infinite current in short circuits. They work by bypassing increased flux from a short circuit through an iron core placed between transformer limbs. Current limiting transformers have distributed primary and secondary windings and increased leakage inductance from an extra flux path between core limbs. This limits current without dissipating power. The transformer discussed has three functions - voltage transformation, fault current limitation, and voltage regulation as a substitute for other equipment.
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET Journal
This document compares carrier-based PWM techniques for controlling a double-star modular multilevel converter (M2C) using half-bridge cells. It analyzes the total harmonic distortion of the output voltage and current for different PWM techniques. It also examines the influence of arm inductances on current and voltage THD and the allowable range of the modulation index for different techniques. The goal is to determine the most effective technique for capacitor balancing and lowest output distortion. Simulations in Matlab/Simulink will be used to compare the performance of different carrier-based PWM control methods for the M2C converter.
Design Development and Simulation of Mobile Substation for Distribution NetworkIJSRD
This document discusses the design, development and simulation of a mobile substation for distribution networks. It aims to evaluate design parameters for mobile substations and identify situations where they are needed. Mobile substations are presented as an alternative to costly construction of permanent substations, as they can be moved to different locations as needed. The document outlines the key components of a mobile substation, describes engineering calculations for system parameters, and presents simulation results showing the mobile substation operating under normal and fault conditions. The simulation validated the selection of equipment and showed the system response met expectations. Mobile substations were concluded to offer flexibility for temporary power needs like large events or construction projects.
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural ElectrificationIRJET Journal
This document summarizes a research paper that analyzes and designs a DC microgrid system for rural electrification in India. Key points:
1) The microgrid uses distributed solar PV generation, with maximum power point tracking converters connecting the solar panels. Fanout nodes distribute power to local clusters of homes, and power management units at each home regulate usage and integrate battery storage.
2) Experimental results from a 400W prototype demonstrate the steady-state operation and stability of the system when power from the solar source is varied. The microgrid is able to maintain a stable distributed voltage while enabling power sharing between components.
3) Calculations estimate the levelized cost of electricity for the microgrid design would be lower
Underground Cable Fault Detection Using IOTIRJET Journal
This document discusses a system to detect faults in underground cable lines using IoT. It proposes using a microprocessor, LCD display, fault sensing circuit module, LoRa module, and power supply to detect the location and type of fault (single line to ground, double line to ground, or three phase faults). The system measures voltage changes across series resistors when a short circuit occurs to determine the fault location. It can display the fault location and phase on the LCD and transmit the data over WiFi. The document reviews literature on condition monitoring of underground cables, current transformer saturation effects, and comparing optical and magnetic current transformers.
IRJET- Review on Performance of OTA StructureIRJET Journal
This document reviews several studies on operational transconductance amplifier (OTA) based analog filter circuits. It discusses OTA based single input single output, multi input single output, and single input multi output filter circuit topologies. It also summarizes key contributions from several papers that proposed new OTA based filter circuits, including biquad filters, oscillators, and rectifiers. The proposed circuits aim to achieve features like independently tunable frequency and quality factor responses, low component counts, and suitability for integrated circuit implementation. PSPICE simulation results confirming the theoretical analyses are also mentioned.
Analysis of Fault Detection and its Location using Microcontroller for Underg...IRJET Journal
1. The document proposes a system to detect faults in underground cables using IoT technology to identify the exact location of faults.
2. The system uses a potential divider network laid across underground cables to detect changes in voltage when faults occur. These voltage changes are sensed by a microcontroller which updates the fault information online.
3. Detecting faults in underground cables is challenging, as the entire cable line may need to be dug up to locate issues. The proposed system aims to simplify fault detection and location, saving time and money in the repair process.
Similar to Overcurrent and Distance Protection in DigSilent PowerFactory (20)
Applications of artificial Intelligence in Mechanical Engineering.pdfAtif Razi
Historically, mechanical engineering has relied heavily on human expertise and empirical methods to solve complex problems. With the introduction of computer-aided design (CAD) and finite element analysis (FEA), the field took its first steps towards digitization. These tools allowed engineers to simulate and analyze mechanical systems with greater accuracy and efficiency. However, the sheer volume of data generated by modern engineering systems and the increasing complexity of these systems have necessitated more advanced analytical tools, paving the way for AI.
AI offers the capability to process vast amounts of data, identify patterns, and make predictions with a level of speed and accuracy unattainable by traditional methods. This has profound implications for mechanical engineering, enabling more efficient design processes, predictive maintenance strategies, and optimized manufacturing operations. AI-driven tools can learn from historical data, adapt to new information, and continuously improve their performance, making them invaluable in tackling the multifaceted challenges of modern mechanical engineering.
Software Engineering and Project Management - Software Testing + Agile Method...Prakhyath Rai
Software Testing: A Strategic Approach to Software Testing, Strategic Issues, Test Strategies for Conventional Software, Test Strategies for Object -Oriented Software, Validation Testing, System Testing, The Art of Debugging.
Agile Methodology: Before Agile – Waterfall, Agile Development.
Discover the latest insights on Data Driven Maintenance with our comprehensive webinar presentation. Learn about traditional maintenance challenges, the right approach to utilizing data, and the benefits of adopting a Data Driven Maintenance strategy. Explore real-world examples, industry best practices, and innovative solutions like FMECA and the D3M model. This presentation, led by expert Jules Oudmans, is essential for asset owners looking to optimize their maintenance processes and leverage digital technologies for improved efficiency and performance. Download now to stay ahead in the evolving maintenance landscape.
Software Engineering and Project Management - Introduction, Modeling Concepts...Prakhyath Rai
Introduction, Modeling Concepts and Class Modeling: What is Object orientation? What is OO development? OO Themes; Evidence for usefulness of OO development; OO modeling history. Modeling
as Design technique: Modeling, abstraction, The Three models. Class Modeling: Object and Class Concept, Link and associations concepts, Generalization and Inheritance, A sample class model, Navigation of class models, and UML diagrams
Building the Analysis Models: Requirement Analysis, Analysis Model Approaches, Data modeling Concepts, Object Oriented Analysis, Scenario-Based Modeling, Flow-Oriented Modeling, class Based Modeling, Creating a Behavioral Model.
Rainfall intensity duration frequency curve statistical analysis and modeling...bijceesjournal
Using data from 41 years in Patna’ India’ the study’s goal is to analyze the trends of how often it rains on a weekly, seasonal, and annual basis (1981−2020). First, utilizing the intensity-duration-frequency (IDF) curve and the relationship by statistically analyzing rainfall’ the historical rainfall data set for Patna’ India’ during a 41 year period (1981−2020), was evaluated for its quality. Changes in the hydrologic cycle as a result of increased greenhouse gas emissions are expected to induce variations in the intensity, length, and frequency of precipitation events. One strategy to lessen vulnerability is to quantify probable changes and adapt to them. Techniques such as log-normal, normal, and Gumbel are used (EV-I). Distributions were created with durations of 1, 2, 3, 6, and 24 h and return times of 2, 5, 10, 25, and 100 years. There were also mathematical correlations discovered between rainfall and recurrence interval.
Findings: Based on findings, the Gumbel approach produced the highest intensity values, whereas the other approaches produced values that were close to each other. The data indicates that 461.9 mm of rain fell during the monsoon season’s 301st week. However, it was found that the 29th week had the greatest average rainfall, 92.6 mm. With 952.6 mm on average, the monsoon season saw the highest rainfall. Calculations revealed that the yearly rainfall averaged 1171.1 mm. Using Weibull’s method, the study was subsequently expanded to examine rainfall distribution at different recurrence intervals of 2, 5, 10, and 25 years. Rainfall and recurrence interval mathematical correlations were also developed. Further regression analysis revealed that short wave irrigation, wind direction, wind speed, pressure, relative humidity, and temperature all had a substantial influence on rainfall.
Originality and value: The results of the rainfall IDF curves can provide useful information to policymakers in making appropriate decisions in managing and minimizing floods in the study area.