This document establishes approval standards for automatic drip valves. It outlines 4 key requirements: [1] the valve must close between 4-10 gpm of water flow and allow 1-2 gpm leakage when closed at 100 psi; [2] the valve must have sufficient strength and durability to withstand normal stresses over many years of use; [3] the valve must pass tests for strength, closure flow, leakage, and reliability in opening; [4] the valve must be permanently marked with the manufacturer's name. Automatic drip valves drain piping to keep it dry and are commonly used on fire department connections.