Approval Standard
        for
Backflow Preventers



                                                           om
(Reduced Pressure Principle and



                                               .c
  Double Check Valve Types)
                                   a         se
                                gb
                         in
             in
          tra




         Class Number 1221
      re
     .fi
   w
  w
w




                       February 1987




       ©2002 FM Global Technologies LLC. All rights reserved.
TABLE OF CONTENTS

I. INTRODUCTION ...................................................................................................................................................................... 1
     1.1 Purpose ................................................................................................................................................................................ 1
     1.2 Scope ................................................................................................................................................................................. 1
     1.3 Basis for FM Approval ....................................................................................................................................................... 1
     1.4 Continued Approval is Based Upon ................................................................................................................................. 2
     1.5 Requirements ...................................................................................................................................................................... 2
     1.6 Effective Date ..................................................................................................................................................................... 2
     1.7 Units of Measurement ........................................................................................................................................................ 2
II. GENERAL INFORMATON ................................................................................................................................................... 3
     2.1 Product Information ............................................................................................................................................................ 3
     2.2 Sizes .................................................................................................................................................................................... 3




                                                                                                                            om
III GENERAL REQUIREMENTS
    (Other than performance Requirements) .............................................................................................................................. 4
     3.1 Preliminary Information ..................................................................................................................................................... 4




                                                                                                           .c
     3.2 End Connections ................................................................................................................................................................. 4




                                                                                                         se
     3.3 Clearances ........................................................................................................................................................................... 4
     3.4 Friction Loss ....................................................................................................................................................................... 5
     3.5 Materials ............................................................................................................................................................................. 5
                                                                                           a
     3.6 Markings ............................................................................................................................................................................. 5
                                                                                        gb
IV PERFORMANCE REQUIREMENTS .................................................................................................................................... 6
    4.1 Clapper Strength ................................................................................................................................................................. 6
                                                                                in

    4.2 Body Strength ..................................................................................................................................................................... 6
    4.3 Diaphragm Strength ............................................................................................................................................................ 6
                                                               in


    4.4 Friction Loss ...................................................................................................................................................................... 6
                                                            tra



    4.5 Other Tests .......................................................................................................................................................................... 6
V MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS ........................................................................ 7
                                                   re




   5.1 Demonstrated QC Program ................................................................................................................................................ 7
   5.2 Facilities and Procedures Audit (F&PA) ........................................................................................................................... 7
                                           .fi




APPENDIX A: UNITS OF MEASUREMENT ........................................................................................................................... 8
                             w




APPENDIX B: APPROVAL MARKS ........................................................................................................................................ 9
                            w
                     w
February 1987                                                                                              1221


I. INTRODUCTION

1.1 Purpose

   This standard states FM Approval requirements for backflow preventers of the reduced pressure principle or
   double check valve types.


1.2 Scope

   1.2.1 This standard sets performance requirements for backflow preventers which can be used in connections
         between public water supplies and fire protection systems to prevent reverse flow. Local health authorities
         usually recommend these devices to prevent contaminated water from entering public water supplies.




                                                                        om
   1.2.2 There are two varieties of backflow preventers, the reduced pressure principle type and the double check
         valve type. From a fire protection viewpoint, both have the same performance requirements as the standard
         check valves they would replace.




                                                                 .c
                                                               se
   1.2.3 This standard does not attempt to prescribe performance requirements which will ensure the public health.
         This is best handled by recognized national agencies established for this purpose.

                                                         a
   1.2.4 FM Approvals will consider for Approval only those backflow preventers which have been accepted by
                                                      gb
         one of the following agencies:
            • ASSE (American Society of Sanitary Engineering)
                                                 in

            • AWWA (American Water Works Association)
                                        in


            • USCF-MCCC (University of Southern California Foundation – Manual of Cross Connection Control)
                                     tra




1.3 Basis for FM Approval
                                re
                           .fi




   FM Approval is based upon satisfactory evaluation of the product and the manufacturer in the following major
   areas:
                   w




   1.3.1 Examination and tests on production samples shall be performed to evaluate
                  w




            • the suitability of the product;
             w




            • the proper operation and performance of the product as specified by the manufacturer and required by
              FM Approvals and, as far as practical;
            • the durability and reliability of the product.

   1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made to
         evaluate the manufacturer’s ability to produce the product which is examined and tested, and the marking
         procedures used to identify the product. These examinations are repeated as part of FM Approvals’ product
         follow-up program.




                                                                                          FM APPROVALS            1
1221                                                                                              February 1987



1.4 Continued Approval is Based Upon
          • production or availability of the product as currently Approved;
          • the continued use of acceptable quality control procedures;
          • satisfactory field experience;
          • compliance with the terms stipulated in the Approval Agreement; and
          • re-examination of production samples for continued conformity to requirements.


1.5 Requirements

    1.5.1 The requirements of this standard are based on experience, research and testing and/or the standards of
          other national and international organizations. The advice of manufacturers, users, trade associations and
          loss control specialists was also considered.




                                                                                      om
    1.5.2 The requirements of this standard reflect tests and practices used to examine characteristics of backflow
          preventers for the purpose of obtaining FM Approval. These requirements are intended primarily as




                                                                             .c
          guides, and strict conformity is not always mandatory. Backflow preventers having characteristics not




                                                                           se
          anticipated by this standard may be Approved if performance equal or superior to that required by this
          standard is demonstrated, or if the intent of the standard is met. Alternatively, backflow preventors which
          do meet all the requirements identified in this standard may not be Approved if other conditions which
                                                                   a
          adversely affect performance exist or if the intent of this standard is not met.
                                                                gb
                                                            in

1.6 Effective Date
                                                   in


    The effective date of an Approval standard mandates that all products tested for Approval after the effective date
    shall satisfy the requirements of that standard. Products Approved under a previous edition shall comply with the
                                                tra



    new version by the effective date or else forfeit Approval. The effective date shall apply to the entire Approval
    standard, or, where so indicated, only to specific paragraphs of the standard.
                                             re
                                     .fi




1.7 System of Units
                             w




          Units of measurement are English System standard units. These are followed by their arithmetic equiva-
          lents in International System (SI) units, enclosed in parentheses. Appendix A lists the selected units for
                            w




          quantities dealt with in testing these products; conversions to SI units are included. Conversion of U.S.
                        w




          Customary units is in accordance with ASTM E 380.




2     FM APPROVALS
February 1987                                                                                                1221


II. GENERAL INFORMATON

2.1 Product Information

    2.1.1 Components
            Backflow preventers of the reduced pressure principle type consist of two independently acting check
            valves which are internally loaded to a normally closed position. The check valves are separated by an
            intermediate chamber or zone with an automatic relief valve for venting to atmosphere. To facilitate field
            testing, two tightly closing valves are provided as standard equipment.
            The double check valve assembly does not have a relief valve in the intermediate chamber.

    2.1.2 Operation




                                                                           om
            a) Reduced Pressure Principle Type
            Under Normal Conditions – The first check valve is internally loaded to create the required pressure
            differential across the first check and intermediate chamber. Hydraulic force from this differential keeps




                                                                 .c
            the relief valve closed. The second check valve functions as a standard check valve.




                                                               se
            Under Backflow Conditions – A backflow condition exists when outlet pressure exceeds inlet pressure.
            The second check outlet closes to prevent backflow through the device. However, if the second check
            should become fouled or damaged, backflowing water will enter the intermediate chamber and decrease
                                                            a
            the pressure differential across the first check. When the differential pressure reaches a minimum prede-
                                                         gb
            termined value, the relief valve opens and vents the intermediate chamber to atmosphere.
            b) Double Check Type
                                                 in

            The prevention of backflow depends solely on the proper operation of at least one of the independently
                                        in


            acting check valves.
                                     tra




2.2 Sizes
                               re




    The following table lists standard check valve sizes recognized for fire protection service:
                          .fi
                   w




                                                Inches         (mm)
                                                  2             (51)
                  w




                                                 21⁄2           (64)
             w




                                                  3             (76)
                                                 31⁄2           (89)
                                                  4            (102)
                                                  5            (127)
                                                  6            (152)
                                                  8            (203)
                                                 10            (254)
                                                 12            (305)
                                                 14            (356)
                                                 16            (406)
                                                 18            (457)
                                                 20            (508)
                                                 24            (610)




                                                                                            FM APPROVALS            3
1221                                                                                               February 1987




III GENERAL REQUIREMENTS
    (Other than Performance Requirements)

3.1 Preliminary Information

    Prior to testing, the manufacturer shall provide the following information for review:

    – One copy of the ASSE, AWWA and/or USCF-MCCC Test Report(s) and a letter from the certifying agency.

    – Detail and assembly drawings

    – Performance characteristics, if available




                                                                                       om
    – Material specifications (ASTM designations, when applicable)

    – Maintenance, operation and installation instructions.




                                                                             .c
                                                                           se
3.2 End Connections


                                                                    a
    Backflow preventers shall be provided with nationally recognized end connections.
                                                                 gb
3.3 Clearances
                                                            in
                                                     in


    3.3.1 To reduce the possibility of foreign material from lodging between the periphery of the clapper, or
          equivalent component, and the inside of the valve body, a clearance of 3⁄8 in. (9.5 mm) and 3⁄4 in.
                                                  tra



          (19.0 mm) shall be maintained in every position from open to closed for bronze and cast iron bodied
          valves, respectively.
                                          re




    3.3.2 If a clapper design is incorporated, the following minimum clearances shall be provided:
                                     .fi




          – 1⁄2 in. (12.7 mm) between the hub of the clapper arm and the inside of iron bodied valves. If the materials
            of the body and clapper are corrosion resistant, the clearance may be reduced to 1⁄4 in. (6.5 mm).
                             w




          – The clearances between the clapper bearing and the body bearing faces shall not adversely affect the
                            w




            performance of the device. Past experience indicates that a 1⁄8 in. (3.2 mm) clearance has shown
                        w




            satisfactory long term performance.




4     FM APPROVALS
February 1987                                                                                                             1221


3.4 Friction Loss

    Although requirements are not specified, the friction loss of Approved devices, at the following flows, shall be
    determined and listed in the Approval Guide:
                                        Valve Size                                         Flow
                                      in.      (mm)                              gal/min          (dm3/min)
                                2                     (51)                          200                (757)
                               21⁄2                   (64)                          300              (1136)
                                3                     (76)                          400              (1514)
                               31⁄2                   (89)                          550              (2082)
                                4                 (102)                             750              (2839)
                                5                 (127)                            1000              (3785)
                                6                 (152)                            1500              (5678)
                                8                 (203)                            3000             (11,356)




                                                                                       om
                                10                (254)                            4900             (18,570)
                                12                (305)                            7000             (26,500)
                                14                (356)                            9500             (35,900)




                                                                           .c
                                16                (406)                          12,500             (47,300)




                                                                         se
                                18                (457)                          16,000             (60,500)
                                20                (508)                          19,500             (73,700)
                                24                (610)                          28,000            (105,800)
                                                                a
                                                             gb
          Note: For valves larger than 8 in. (203.2 mm) it shall be the responsibility of the manufacturer to
                submit friction loss data points.
                                                             in

3.5 Materials
                                             in
                                          tra



    Materials used in the construction of the device shall be suitable for the intended application.
                                    re




3.6 Markings
                            .fi




    The device shall be permanently marked with the following information which may be cast into the valve body
                  w




    or inscribed on a securely attached nameplate:
                 w




          – Manufacturer’s name and address
            w




          – Model or type designation
          – Maximum rated working pressure
          – Date of manufacture
          – Serial number
          – Size of inlet and outlet connections
          – Direction of water flow
          – FM Approval Mark (see Appendix B).

          See Appendix B for acceptable Approval Mark formats.




                                                                                                               FM APPROVALS   5
1221                                                                                             February 1987




IV PERFORMANCE REQUIREMENTS

4.1 Clapper Strength

    4.1.1 Requirement
          The valve clapper shall withstand exposure to hydrostatic pressure in excess of its rated working pressure.

    4.1.2 Test/Verification
          A hydrostatic pressure of two times the rated working pressure shall be applied to the outlet side of each
          check with the inlet exposed to atmosphere. During and at the conclusion of the test, no leakage, fracture,
          permanent distortion of functional impairment shall occur.




                                                                                     om
4.2 Body Strength

    4.2.1 Requirement




                                                                            .c
          The valve body shall withstand exposure to hydrostatic pressure in excess of its rated working pressure.




                                                                          se
    4.2.2 Test/Verification
                                                                   a
          The valve body shall be subjected to four times the rated working pressure for a period of 5 minutes
                                                                gb
          without evidence of physical damage.
                                                           in

4.3 Diaphragm Strength
                                                  in
                                               tra



    4.3.1 Requirement
          Diaphragms shall withstand exposure to hydrostatic pressure in excess of the rated working pressure.
                                          re




    4.3.2 Test/Verification
                                     .fi




          Diaphragms shall be subjected to twice the rated working pressure for 5 minutes. At the conclusion of the
          test there shall be no evidence of leakage or functional impairment.
                               w
                              w




4.4 Friction Loss
                        w




    4.4.1 Requirement
          Friction loss shall be determined for various flows and sizes of valve. See Paragraph 3.4.

    4.4.2 Test/Verification
          If friction loss curves have already been generated, sample valves shall be used to check submitted data
          for compliance.


4.5 Other Tests

    Other tests may be conducted at the discretion of FM Approvals to further evaluate the adequacy and reliability
    of valve performance.




6     FM APPROVALS
February 1987                                                                                           1221


V MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS

5.1 Demonstrated QC Program

   5.1.1 A Quality Control Program is required to assure that each subsequent backflow preventer produced by the
         manufacturer shall present the same quality and reliability as the specific samples examined. Design
         quality, conformance to design, and performance are the areas of primary concern.
         Design quality is determined during the examination and tests.
         Conformance to design is verified by control of quality in the following areas:
             • Existence of corporate quality control guidelines
             • Incoming inspection and test
             • In-Process inspection and test




                                                                      om
             • Final inspection and test
             • Equipment calibration




                                                             .c
             • Drawing and change control




                                                           se
             • Packaging and shipping

                                                    a
         Quality of performance is determined by field performance and by re-examination and test.
                                                 gb
   5.1.2 The manufacturer shall establish a system of product configuration control to prevent unauthorized
                                              in

         changes, including, as appropriate:
             • Engineering drawings
                                     in


             • Engineering change requests
                                  tra




             • Engineering orders
             • Change notices
                            re




         These shall be executed in conformance with a written policy and detailed procedures. Records of all
                       .fi




         revisions to all Approved products shall be kept.
                w




   5.1.3 The manufacturer shall assign an appropriate person or group to be responsible for keeping FM Approvals
               w




         informed of all pending changes applicable to Approved products. FM Approval Form 797, Approved
         Product Revision Report or Address/Contact Change Notice, is provided to notify FM Approvals of
           w




         pending changes.


5.2 Facilities and Procedures Audit (F&PA)

   5.2.1 At Manufacturing Plant
         a) An inspection of the product manufacturing facility shall be part of the Approval investigation. Its
         purpose shall be to determine that equipment, procedures, and the manufacturer’s controls are properly
         maintained to produce a product of the same quality as initially tested.
         b) Unannounced follow-up inspections shall be conducted to assure continued quality control and product
         uniformity.




                                                                                       FM APPROVALS           7
1221                                                                          February 1987




                               APPENDIX A

                       UNITS OF MEASUREMENT


                   LENGTH:      in. – ‘‘inches’’
                                (mm – ‘‘millimeters’’)

                                mm = in. × 25.4 in.


                   PRESSURE:    psi – ‘‘pounds per square inch’’




                                                                   om
                                (kPa – ‘‘kilopascals’’)

                                kPa = psi × 6.8948




                                                           .c
                                                         se
                   FLOW:        gal/min – ‘‘gallons per minute’’
                                                 a
                                (dm3/min – ‘‘cubic decimeters per minute’’)
                                              gb
                                dm3/min = gal/min × 3.7854
                                          in
                                  in
                               tra
                               re
                           .fi
                    w
                   w
               w




8   FM APPROVALS
February 1987                                                                                                  1221


                                                     APPENDIX B

                                                   APPROVAL MARKS


                             REPRODUCTION ART: FM Approval Marks


                                                    For use on nameplates, in literature, advertisements,
                                                    packaging and other graphics.

                                                                   1) The FM Approvals diamond mark is acceptable




                                                                           om
                                                                      to FM Approvals as an Approval mark when
                                                                      used with the word ‘‘Approved.’’




                                                                   .c
                                                                   2) The FM Approval logomark has no minimum




                                                                 se
                                                                      size requirement, but should always be large
                                                                      enough to be readily identifiable.

                                                            a
                                                         gb
                                                                   3) Color should be black on a light background or a
                                                                      reverse may be used on a dark background.
                                                      in
                                            in


                                                               For Cast-On Marks
                                         tra




                                                                   4) Where reproduction of the mark described
                                                                      above is impossible because of production
                                   re




                                                                      restrictions, a modified version of the diamond is
                                                                      suggested. Minimum size specifications are the
                             .fi




                                                                      same as for printed marks. Use of the word
                                                                      ‘‘Approved’’ with this mark is optional.
                    w
                   w
              w




NOTE: These Approval marks are to be used only in conjunction with products or services that have been
FM Approved. The FM Approval marks should never be used in any manner (including advertising, sales or promotional
purposes) that could suggest or imply FM Approval or endorsement of a specific manufacturer or distributor. Nor should
it be implied that Approval extends to a product or service not covered by written agreement with FM Approvals. The
Approval marks signify that products or services have met certain requirements as reported by FM Approvals.



Additional reproduction art is available through
FM Approvals
P.O. Box 9102,
Norwood, Massachusetts 02062
U.S.A.




                                                                                             FM APPROVALS             9

More Related Content

What's hot

Water treatment Dow guide
Water treatment Dow guideWater treatment Dow guide
Water treatment Dow guideAhmed Adel
 
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and up
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and upLiebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and up
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and upufhsjeskekmdm
 
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and up
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and upLiebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and up
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and upjkmsmem ejksmmd
 
Krupp hydraulic hammers hm 1000 1000 marathon service repair manual
Krupp hydraulic hammers hm 1000  1000 marathon service repair manualKrupp hydraulic hammers hm 1000  1000 marathon service repair manual
Krupp hydraulic hammers hm 1000 1000 marathon service repair manualfjkskmmdmme
 
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...hsemmd sehkdmm
 
Tma inst service_manual
Tma inst service_manualTma inst service_manual
Tma inst service_manualMuhammad Saqib
 
Daewoo doosan dx140 w wheel excavator operator and maintenance manual
Daewoo doosan dx140 w wheel excavator operator and maintenance manualDaewoo doosan dx140 w wheel excavator operator and maintenance manual
Daewoo doosan dx140 w wheel excavator operator and maintenance manualfjskkksmemm
 
Control engineering a guide for beginners
Control engineering   a guide for beginnersControl engineering   a guide for beginners
Control engineering a guide for beginnersthuanvq
 
Api 10.3 agua y sedimentos centrifugacion lab
Api 10.3  agua y sedimentos centrifugacion labApi 10.3  agua y sedimentos centrifugacion lab
Api 10.3 agua y sedimentos centrifugacion labPabel Imar Lema Copa
 
TALAT Lecture 2402: Design Recommendations for fatigue loaded structures
TALAT Lecture 2402: Design Recommendations for fatigue loaded structuresTALAT Lecture 2402: Design Recommendations for fatigue loaded structures
TALAT Lecture 2402: Design Recommendations for fatigue loaded structuresCORE-Materials
 
TALAT Lecture 2712: Design Example in Fatigue
TALAT Lecture 2712: Design Example in FatigueTALAT Lecture 2712: Design Example in Fatigue
TALAT Lecture 2712: Design Example in FatigueCORE-Materials
 
Clark op15 x forklift service repair manual
Clark op15 x forklift service repair manualClark op15 x forklift service repair manual
Clark op15 x forklift service repair manualfjjskekdmme
 
TALAT Lecture 2401: Fatigue Behaviour and Analysis
TALAT Lecture 2401: Fatigue Behaviour and AnalysisTALAT Lecture 2401: Fatigue Behaviour and Analysis
TALAT Lecture 2401: Fatigue Behaviour and AnalysisCORE-Materials
 
Veiligheidskleppen
VeiligheidskleppenVeiligheidskleppen
VeiligheidskleppenHaDeGo
 
As nzs 2908.2 2000 iso 8336 1993
As nzs 2908.2 2000 iso 8336 1993As nzs 2908.2 2000 iso 8336 1993
As nzs 2908.2 2000 iso 8336 1993AchintyaSamanta1
 

What's hot (20)

All pages
All pagesAll pages
All pages
 
Water treatment Dow guide
Water treatment Dow guideWater treatment Dow guide
Water treatment Dow guide
 
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and up
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and upLiebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and up
Liebherr R 916 Classic Hydraulic Excavator Service Repair Manual SN:17943 and up
 
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and up
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and upLiebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and up
Liebherr R 906 Classic Hydraulic Excavator Service Repair Manual SN:23145 and up
 
Krupp hydraulic hammers hm 1000 1000 marathon service repair manual
Krupp hydraulic hammers hm 1000  1000 marathon service repair manualKrupp hydraulic hammers hm 1000  1000 marathon service repair manual
Krupp hydraulic hammers hm 1000 1000 marathon service repair manual
 
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...
Liebherr R 906 Advanced Hydraulic Excavator Service Repair Manual SN:18002 an...
 
Tma inst service_manual
Tma inst service_manualTma inst service_manual
Tma inst service_manual
 
Daewoo doosan dx140 w wheel excavator operator and maintenance manual
Daewoo doosan dx140 w wheel excavator operator and maintenance manualDaewoo doosan dx140 w wheel excavator operator and maintenance manual
Daewoo doosan dx140 w wheel excavator operator and maintenance manual
 
Control engineering a guide for beginners
Control engineering   a guide for beginnersControl engineering   a guide for beginners
Control engineering a guide for beginners
 
Api 10.3 agua y sedimentos centrifugacion lab
Api 10.3  agua y sedimentos centrifugacion labApi 10.3  agua y sedimentos centrifugacion lab
Api 10.3 agua y sedimentos centrifugacion lab
 
Stress
StressStress
Stress
 
TALAT Lecture 2402: Design Recommendations for fatigue loaded structures
TALAT Lecture 2402: Design Recommendations for fatigue loaded structuresTALAT Lecture 2402: Design Recommendations for fatigue loaded structures
TALAT Lecture 2402: Design Recommendations for fatigue loaded structures
 
Nfpa 1042
Nfpa 1042Nfpa 1042
Nfpa 1042
 
TALAT Lecture 2712: Design Example in Fatigue
TALAT Lecture 2712: Design Example in FatigueTALAT Lecture 2712: Design Example in Fatigue
TALAT Lecture 2712: Design Example in Fatigue
 
Clark op15 x forklift service repair manual
Clark op15 x forklift service repair manualClark op15 x forklift service repair manual
Clark op15 x forklift service repair manual
 
TALAT Lecture 2401: Fatigue Behaviour and Analysis
TALAT Lecture 2401: Fatigue Behaviour and AnalysisTALAT Lecture 2401: Fatigue Behaviour and Analysis
TALAT Lecture 2401: Fatigue Behaviour and Analysis
 
Otc2
Otc2Otc2
Otc2
 
Asme v 2001 article 6
Asme v   2001 article 6Asme v   2001 article 6
Asme v 2001 article 6
 
Veiligheidskleppen
VeiligheidskleppenVeiligheidskleppen
Veiligheidskleppen
 
As nzs 2908.2 2000 iso 8336 1993
As nzs 2908.2 2000 iso 8336 1993As nzs 2908.2 2000 iso 8336 1993
As nzs 2908.2 2000 iso 8336 1993
 

Similar to Nfpa 1221

Denso hp-3 servis manual
Denso hp-3 servis manualDenso hp-3 servis manual
Denso hp-3 servis manualViktor
 
Approve standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversApprove standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversWiroj Kaewkan
 
Aws z49 safety in welding and cutting
Aws z49 safety in welding and cuttingAws z49 safety in welding and cutting
Aws z49 safety in welding and cuttingNguyen Huy Long
 
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)Gherghescu Gabriel
 

Similar to Nfpa 1221 (11)

Nfpa 1041
Nfpa 1041Nfpa 1041
Nfpa 1041
 
510 e10 PA.pdf
510 e10 PA.pdf510 e10 PA.pdf
510 e10 PA.pdf
 
Denso hp-3 servis manual
Denso hp-3 servis manualDenso hp-3 servis manual
Denso hp-3 servis manual
 
Approve standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump driversApprove standard for diesel engine fire pump drivers
Approve standard for diesel engine fire pump drivers
 
Aws z49 safety in welding and cutting
Aws z49 safety in welding and cuttingAws z49 safety in welding and cutting
Aws z49 safety in welding and cutting
 
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)
AUDI 00052506920 motronic fuel-injection_and_ignition_system_(5-cylinder)
 
Coulter manual de usos
Coulter manual de usosCoulter manual de usos
Coulter manual de usos
 
8_I_en.pdf
8_I_en.pdf8_I_en.pdf
8_I_en.pdf
 
8_I_en.pdf
8_I_en.pdf8_I_en.pdf
8_I_en.pdf
 
ASME-B16.49.pdf
ASME-B16.49.pdfASME-B16.49.pdf
ASME-B16.49.pdf
 
Oxymat 61 o2 analyzer
Oxymat 61  o2 analyzerOxymat 61  o2 analyzer
Oxymat 61 o2 analyzer
 

More from Jianping Wong

Yang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvYang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvJianping Wong
 
Ym uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonYm uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonJianping Wong
 
Schneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardSchneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardJianping Wong
 
Reuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformReuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformJianping Wong
 
Nyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformNyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformJianping Wong
 
Seamless transitions are_they_possible
Seamless transitions are_they_possibleSeamless transitions are_they_possible
Seamless transitions are_they_possibleJianping Wong
 
521 announcement 29102013 interim financial report q3 2013
521  announcement 29102013  interim financial report q3 2013521  announcement 29102013  interim financial report q3 2013
521 announcement 29102013 interim financial report q3 2013Jianping Wong
 
Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Jianping Wong
 
Estes express lines announces general rate increase
Estes express lines announces general rate increaseEstes express lines announces general rate increase
Estes express lines announces general rate increaseJianping Wong
 
Top 10 popular express companies in us
Top 10 popular express companies in usTop 10 popular express companies in us
Top 10 popular express companies in usJianping Wong
 

More from Jianping Wong (17)

Yang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcvYang ming to_launch_japan_koreachinavietnam_service_kcv
Yang ming to_launch_japan_koreachinavietnam_service_kcv
 
Ym uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_seasonYm uasc and_cscl_merge_tp_services_for_winter_season
Ym uasc and_cscl_merge_tp_services_for_winter_season
 
Schneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year awardSchneider logistics honors holland with 2013 ltl carrier of the year award
Schneider logistics honors holland with 2013 ltl carrier of the year award
 
Reuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platformReuse ny kcontainers_via_apcs_platform
Reuse ny kcontainers_via_apcs_platform
 
Nyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platformNyk and yang ming reuse containers thanks to apcs platform
Nyk and yang ming reuse containers thanks to apcs platform
 
Seamless transitions are_they_possible
Seamless transitions are_they_possibleSeamless transitions are_they_possible
Seamless transitions are_they_possible
 
521 announcement 29102013 interim financial report q3 2013
521  announcement 29102013  interim financial report q3 2013521  announcement 29102013  interim financial report q3 2013
521 announcement 29102013 interim financial report q3 2013
 
Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72Saia reports second quarter earnings per share of $0.72
Saia reports second quarter earnings per share of $0.72
 
Estes express lines announces general rate increase
Estes express lines announces general rate increaseEstes express lines announces general rate increase
Estes express lines announces general rate increase
 
Top 10 popular express companies in us
Top 10 popular express companies in usTop 10 popular express companies in us
Top 10 popular express companies in us
 
Nfpa 1055
Nfpa 1055Nfpa 1055
Nfpa 1055
 
Nfpa 1051
Nfpa 1051Nfpa 1051
Nfpa 1051
 
Nfpa 1032
Nfpa 1032Nfpa 1032
Nfpa 1032
 
Nfpa 1031
Nfpa 1031Nfpa 1031
Nfpa 1031
 
Nfpa 1021
Nfpa 1021Nfpa 1021
Nfpa 1021
 
Nfpa 1020
Nfpa 1020Nfpa 1020
Nfpa 1020
 
Nfpa 557
Nfpa 557Nfpa 557
Nfpa 557
 

Recently uploaded

Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebUiPathCommunity
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubKalema Edgar
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Wonjun Hwang
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 3652toLead Limited
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Scott Keck-Warren
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clashcharlottematthew16
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsRizwan Syed
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLScyllaDB
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsMiki Katsuragi
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentationphoebematthew05
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024The Digital Insurer
 

Recently uploaded (20)

Dev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio WebDev Dives: Streamline document processing with UiPath Studio Web
Dev Dives: Streamline document processing with UiPath Studio Web
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort ServiceHot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
Hot Sexy call girls in Panjabi Bagh 🔝 9953056974 🔝 Delhi escort Service
 
Unleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding ClubUnleash Your Potential - Namagunga Girls Coding Club
Unleash Your Potential - Namagunga Girls Coding Club
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
 
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
Tech-Forward - Achieving Business Readiness For Copilot in Microsoft 365
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food Manufacturing
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clash
 
Scanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL CertsScanning the Internet for External Cloud Exposures via SSL Certs
Scanning the Internet for External Cloud Exposures via SSL Certs
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQL
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering Tips
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
costume and set research powerpoint presentation
costume and set research powerpoint presentationcostume and set research powerpoint presentation
costume and set research powerpoint presentation
 
My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024My INSURER PTE LTD - Insurtech Innovation Award 2024
My INSURER PTE LTD - Insurtech Innovation Award 2024
 

Nfpa 1221

  • 1. Approval Standard for Backflow Preventers om (Reduced Pressure Principle and .c Double Check Valve Types) a se gb in in tra Class Number 1221 re .fi w w w February 1987 ©2002 FM Global Technologies LLC. All rights reserved.
  • 2. TABLE OF CONTENTS I. INTRODUCTION ...................................................................................................................................................................... 1 1.1 Purpose ................................................................................................................................................................................ 1 1.2 Scope ................................................................................................................................................................................. 1 1.3 Basis for FM Approval ....................................................................................................................................................... 1 1.4 Continued Approval is Based Upon ................................................................................................................................. 2 1.5 Requirements ...................................................................................................................................................................... 2 1.6 Effective Date ..................................................................................................................................................................... 2 1.7 Units of Measurement ........................................................................................................................................................ 2 II. GENERAL INFORMATON ................................................................................................................................................... 3 2.1 Product Information ............................................................................................................................................................ 3 2.2 Sizes .................................................................................................................................................................................... 3 om III GENERAL REQUIREMENTS (Other than performance Requirements) .............................................................................................................................. 4 3.1 Preliminary Information ..................................................................................................................................................... 4 .c 3.2 End Connections ................................................................................................................................................................. 4 se 3.3 Clearances ........................................................................................................................................................................... 4 3.4 Friction Loss ....................................................................................................................................................................... 5 3.5 Materials ............................................................................................................................................................................. 5 a 3.6 Markings ............................................................................................................................................................................. 5 gb IV PERFORMANCE REQUIREMENTS .................................................................................................................................... 6 4.1 Clapper Strength ................................................................................................................................................................. 6 in 4.2 Body Strength ..................................................................................................................................................................... 6 4.3 Diaphragm Strength ............................................................................................................................................................ 6 in 4.4 Friction Loss ...................................................................................................................................................................... 6 tra 4.5 Other Tests .......................................................................................................................................................................... 6 V MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS ........................................................................ 7 re 5.1 Demonstrated QC Program ................................................................................................................................................ 7 5.2 Facilities and Procedures Audit (F&PA) ........................................................................................................................... 7 .fi APPENDIX A: UNITS OF MEASUREMENT ........................................................................................................................... 8 w APPENDIX B: APPROVAL MARKS ........................................................................................................................................ 9 w w
  • 3. February 1987 1221 I. INTRODUCTION 1.1 Purpose This standard states FM Approval requirements for backflow preventers of the reduced pressure principle or double check valve types. 1.2 Scope 1.2.1 This standard sets performance requirements for backflow preventers which can be used in connections between public water supplies and fire protection systems to prevent reverse flow. Local health authorities usually recommend these devices to prevent contaminated water from entering public water supplies. om 1.2.2 There are two varieties of backflow preventers, the reduced pressure principle type and the double check valve type. From a fire protection viewpoint, both have the same performance requirements as the standard check valves they would replace. .c se 1.2.3 This standard does not attempt to prescribe performance requirements which will ensure the public health. This is best handled by recognized national agencies established for this purpose. a 1.2.4 FM Approvals will consider for Approval only those backflow preventers which have been accepted by gb one of the following agencies: • ASSE (American Society of Sanitary Engineering) in • AWWA (American Water Works Association) in • USCF-MCCC (University of Southern California Foundation – Manual of Cross Connection Control) tra 1.3 Basis for FM Approval re .fi FM Approval is based upon satisfactory evaluation of the product and the manufacturer in the following major areas: w 1.3.1 Examination and tests on production samples shall be performed to evaluate w • the suitability of the product; w • the proper operation and performance of the product as specified by the manufacturer and required by FM Approvals and, as far as practical; • the durability and reliability of the product. 1.3.2 An examination of the manufacturing facilities and audit of quality control procedures shall be made to evaluate the manufacturer’s ability to produce the product which is examined and tested, and the marking procedures used to identify the product. These examinations are repeated as part of FM Approvals’ product follow-up program. FM APPROVALS 1
  • 4. 1221 February 1987 1.4 Continued Approval is Based Upon • production or availability of the product as currently Approved; • the continued use of acceptable quality control procedures; • satisfactory field experience; • compliance with the terms stipulated in the Approval Agreement; and • re-examination of production samples for continued conformity to requirements. 1.5 Requirements 1.5.1 The requirements of this standard are based on experience, research and testing and/or the standards of other national and international organizations. The advice of manufacturers, users, trade associations and loss control specialists was also considered. om 1.5.2 The requirements of this standard reflect tests and practices used to examine characteristics of backflow preventers for the purpose of obtaining FM Approval. These requirements are intended primarily as .c guides, and strict conformity is not always mandatory. Backflow preventers having characteristics not se anticipated by this standard may be Approved if performance equal or superior to that required by this standard is demonstrated, or if the intent of the standard is met. Alternatively, backflow preventors which do meet all the requirements identified in this standard may not be Approved if other conditions which a adversely affect performance exist or if the intent of this standard is not met. gb in 1.6 Effective Date in The effective date of an Approval standard mandates that all products tested for Approval after the effective date shall satisfy the requirements of that standard. Products Approved under a previous edition shall comply with the tra new version by the effective date or else forfeit Approval. The effective date shall apply to the entire Approval standard, or, where so indicated, only to specific paragraphs of the standard. re .fi 1.7 System of Units w Units of measurement are English System standard units. These are followed by their arithmetic equiva- lents in International System (SI) units, enclosed in parentheses. Appendix A lists the selected units for w quantities dealt with in testing these products; conversions to SI units are included. Conversion of U.S. w Customary units is in accordance with ASTM E 380. 2 FM APPROVALS
  • 5. February 1987 1221 II. GENERAL INFORMATON 2.1 Product Information 2.1.1 Components Backflow preventers of the reduced pressure principle type consist of two independently acting check valves which are internally loaded to a normally closed position. The check valves are separated by an intermediate chamber or zone with an automatic relief valve for venting to atmosphere. To facilitate field testing, two tightly closing valves are provided as standard equipment. The double check valve assembly does not have a relief valve in the intermediate chamber. 2.1.2 Operation om a) Reduced Pressure Principle Type Under Normal Conditions – The first check valve is internally loaded to create the required pressure differential across the first check and intermediate chamber. Hydraulic force from this differential keeps .c the relief valve closed. The second check valve functions as a standard check valve. se Under Backflow Conditions – A backflow condition exists when outlet pressure exceeds inlet pressure. The second check outlet closes to prevent backflow through the device. However, if the second check should become fouled or damaged, backflowing water will enter the intermediate chamber and decrease a the pressure differential across the first check. When the differential pressure reaches a minimum prede- gb termined value, the relief valve opens and vents the intermediate chamber to atmosphere. b) Double Check Type in The prevention of backflow depends solely on the proper operation of at least one of the independently in acting check valves. tra 2.2 Sizes re The following table lists standard check valve sizes recognized for fire protection service: .fi w Inches (mm) 2 (51) w 21⁄2 (64) w 3 (76) 31⁄2 (89) 4 (102) 5 (127) 6 (152) 8 (203) 10 (254) 12 (305) 14 (356) 16 (406) 18 (457) 20 (508) 24 (610) FM APPROVALS 3
  • 6. 1221 February 1987 III GENERAL REQUIREMENTS (Other than Performance Requirements) 3.1 Preliminary Information Prior to testing, the manufacturer shall provide the following information for review: – One copy of the ASSE, AWWA and/or USCF-MCCC Test Report(s) and a letter from the certifying agency. – Detail and assembly drawings – Performance characteristics, if available om – Material specifications (ASTM designations, when applicable) – Maintenance, operation and installation instructions. .c se 3.2 End Connections a Backflow preventers shall be provided with nationally recognized end connections. gb 3.3 Clearances in in 3.3.1 To reduce the possibility of foreign material from lodging between the periphery of the clapper, or equivalent component, and the inside of the valve body, a clearance of 3⁄8 in. (9.5 mm) and 3⁄4 in. tra (19.0 mm) shall be maintained in every position from open to closed for bronze and cast iron bodied valves, respectively. re 3.3.2 If a clapper design is incorporated, the following minimum clearances shall be provided: .fi – 1⁄2 in. (12.7 mm) between the hub of the clapper arm and the inside of iron bodied valves. If the materials of the body and clapper are corrosion resistant, the clearance may be reduced to 1⁄4 in. (6.5 mm). w – The clearances between the clapper bearing and the body bearing faces shall not adversely affect the w performance of the device. Past experience indicates that a 1⁄8 in. (3.2 mm) clearance has shown w satisfactory long term performance. 4 FM APPROVALS
  • 7. February 1987 1221 3.4 Friction Loss Although requirements are not specified, the friction loss of Approved devices, at the following flows, shall be determined and listed in the Approval Guide: Valve Size Flow in. (mm) gal/min (dm3/min) 2 (51) 200 (757) 21⁄2 (64) 300 (1136) 3 (76) 400 (1514) 31⁄2 (89) 550 (2082) 4 (102) 750 (2839) 5 (127) 1000 (3785) 6 (152) 1500 (5678) 8 (203) 3000 (11,356) om 10 (254) 4900 (18,570) 12 (305) 7000 (26,500) 14 (356) 9500 (35,900) .c 16 (406) 12,500 (47,300) se 18 (457) 16,000 (60,500) 20 (508) 19,500 (73,700) 24 (610) 28,000 (105,800) a gb Note: For valves larger than 8 in. (203.2 mm) it shall be the responsibility of the manufacturer to submit friction loss data points. in 3.5 Materials in tra Materials used in the construction of the device shall be suitable for the intended application. re 3.6 Markings .fi The device shall be permanently marked with the following information which may be cast into the valve body w or inscribed on a securely attached nameplate: w – Manufacturer’s name and address w – Model or type designation – Maximum rated working pressure – Date of manufacture – Serial number – Size of inlet and outlet connections – Direction of water flow – FM Approval Mark (see Appendix B). See Appendix B for acceptable Approval Mark formats. FM APPROVALS 5
  • 8. 1221 February 1987 IV PERFORMANCE REQUIREMENTS 4.1 Clapper Strength 4.1.1 Requirement The valve clapper shall withstand exposure to hydrostatic pressure in excess of its rated working pressure. 4.1.2 Test/Verification A hydrostatic pressure of two times the rated working pressure shall be applied to the outlet side of each check with the inlet exposed to atmosphere. During and at the conclusion of the test, no leakage, fracture, permanent distortion of functional impairment shall occur. om 4.2 Body Strength 4.2.1 Requirement .c The valve body shall withstand exposure to hydrostatic pressure in excess of its rated working pressure. se 4.2.2 Test/Verification a The valve body shall be subjected to four times the rated working pressure for a period of 5 minutes gb without evidence of physical damage. in 4.3 Diaphragm Strength in tra 4.3.1 Requirement Diaphragms shall withstand exposure to hydrostatic pressure in excess of the rated working pressure. re 4.3.2 Test/Verification .fi Diaphragms shall be subjected to twice the rated working pressure for 5 minutes. At the conclusion of the test there shall be no evidence of leakage or functional impairment. w w 4.4 Friction Loss w 4.4.1 Requirement Friction loss shall be determined for various flows and sizes of valve. See Paragraph 3.4. 4.4.2 Test/Verification If friction loss curves have already been generated, sample valves shall be used to check submitted data for compliance. 4.5 Other Tests Other tests may be conducted at the discretion of FM Approvals to further evaluate the adequacy and reliability of valve performance. 6 FM APPROVALS
  • 9. February 1987 1221 V MANUFACTURING AND FIELD INSTALLATION REQUIREMENTS 5.1 Demonstrated QC Program 5.1.1 A Quality Control Program is required to assure that each subsequent backflow preventer produced by the manufacturer shall present the same quality and reliability as the specific samples examined. Design quality, conformance to design, and performance are the areas of primary concern. Design quality is determined during the examination and tests. Conformance to design is verified by control of quality in the following areas: • Existence of corporate quality control guidelines • Incoming inspection and test • In-Process inspection and test om • Final inspection and test • Equipment calibration .c • Drawing and change control se • Packaging and shipping a Quality of performance is determined by field performance and by re-examination and test. gb 5.1.2 The manufacturer shall establish a system of product configuration control to prevent unauthorized in changes, including, as appropriate: • Engineering drawings in • Engineering change requests tra • Engineering orders • Change notices re These shall be executed in conformance with a written policy and detailed procedures. Records of all .fi revisions to all Approved products shall be kept. w 5.1.3 The manufacturer shall assign an appropriate person or group to be responsible for keeping FM Approvals w informed of all pending changes applicable to Approved products. FM Approval Form 797, Approved Product Revision Report or Address/Contact Change Notice, is provided to notify FM Approvals of w pending changes. 5.2 Facilities and Procedures Audit (F&PA) 5.2.1 At Manufacturing Plant a) An inspection of the product manufacturing facility shall be part of the Approval investigation. Its purpose shall be to determine that equipment, procedures, and the manufacturer’s controls are properly maintained to produce a product of the same quality as initially tested. b) Unannounced follow-up inspections shall be conducted to assure continued quality control and product uniformity. FM APPROVALS 7
  • 10. 1221 February 1987 APPENDIX A UNITS OF MEASUREMENT LENGTH: in. – ‘‘inches’’ (mm – ‘‘millimeters’’) mm = in. × 25.4 in. PRESSURE: psi – ‘‘pounds per square inch’’ om (kPa – ‘‘kilopascals’’) kPa = psi × 6.8948 .c se FLOW: gal/min – ‘‘gallons per minute’’ a (dm3/min – ‘‘cubic decimeters per minute’’) gb dm3/min = gal/min × 3.7854 in in tra re .fi w w w 8 FM APPROVALS
  • 11. February 1987 1221 APPENDIX B APPROVAL MARKS REPRODUCTION ART: FM Approval Marks For use on nameplates, in literature, advertisements, packaging and other graphics. 1) The FM Approvals diamond mark is acceptable om to FM Approvals as an Approval mark when used with the word ‘‘Approved.’’ .c 2) The FM Approval logomark has no minimum se size requirement, but should always be large enough to be readily identifiable. a gb 3) Color should be black on a light background or a reverse may be used on a dark background. in in For Cast-On Marks tra 4) Where reproduction of the mark described above is impossible because of production re restrictions, a modified version of the diamond is suggested. Minimum size specifications are the .fi same as for printed marks. Use of the word ‘‘Approved’’ with this mark is optional. w w w NOTE: These Approval marks are to be used only in conjunction with products or services that have been FM Approved. The FM Approval marks should never be used in any manner (including advertising, sales or promotional purposes) that could suggest or imply FM Approval or endorsement of a specific manufacturer or distributor. Nor should it be implied that Approval extends to a product or service not covered by written agreement with FM Approvals. The Approval marks signify that products or services have met certain requirements as reported by FM Approvals. Additional reproduction art is available through FM Approvals P.O. Box 9102, Norwood, Massachusetts 02062 U.S.A. FM APPROVALS 9