Basic Concepts of Air
    Conditioning



   Prepared exclusively
           for
 COACH LEATHERWARE
Panel
Moderator:
Bob Keingstein
Boss Facilities Services
631-361-7430
bobk@bossfacilityservices.com




                                Slide 1
COIL    COOL
              AIR

                    HEAT



SOURCE OF
 COOL AIR
  • COIL •




                           Slide 3
TYPICAL ALL-AIR SYSTEM


         S.A. DUCT


COIL             COOL
                  AIR

                        HEAT
  S.A.
  FAN




                               Slide 4
TYPICAL ALL-AIR SYSTEM


                              S.A.
         S.A. DUCT          TERMINAL



COIL                 COOL
                      AIR

                              HEAT
  S.A.
  FAN




                                       Slide 5
TYPICAL ALL-AIR SYSTEM


                                    R.A. GRILL
                          S.A.
         S.A. DUCT      TERMINAL


                 COOL    WARM AIR
COIL              AIR

                          HEAT
  S.A.
  FAN




                                                 Slide 6
TYPICAL ALL-AIR SYSTEM


              R.A DUCT
                                    R.A. GRILL
                           S.A.
         S.A. DUCT       TERMINAL



COIL             COOL
                  AIR

                           HEAT
  S.A.
  FAN




                                                 Slide 7
TYPICAL ALL-AIR SYSTEM


          R.A.
          FAN         R.A DUCT
                                            R.A. GRILL
                                   S.A.
                 S.A. DUCT       TERMINAL


   COIL                 COOL
                         AIR
                                   HEAT
   S.A.
   FAN




                                                         Slide 8
TYPICAL ALL-AIR SYSTEM


                             R.A.
                             FAN         R.A DUCT
                                                               R.A. GRILL
                                                      S.A.
                                    S.A. DUCT       TERMINAL
                     R.A. DAMPER
                     COIL                  COOL
                                            AIR
 FRESH
OUTDOOR                                               HEAT
  AIR                 S.A.
                      FAN

     O.A.
   DAMPER
            FILTER




                                                                        Slide 9
TYPICAL ALL-AIR SYSTEM

               E.A.
EXHAUST       DAMPER
  AIR                          R.A.
                               FAN         R.A DUCT
                                                                 R.A. GRILL
                                                        S.A.
                                      S.A. DUCT       TERMINAL
                       R.A. DAMPER
                       COIL                  COOL
                                              AIR
 FRESH
OUTDOOR                                                 HEAT
  AIR                   S.A.
                        FAN

     O.A.
   DAMPER
            FILTER




                                                                         Slide 10
Economizer


•   Provides cooling to space when outdoor air
    temperatures are below 55 degrees
•   Switches over automatically from mechanical
    cooling
•   Adjusts R.A. and F.A. dampers to maintain space
    temp
•   May incorporate enthalpy control
•   Mandatory in some states based on unit capacity


                                                      Slide 11
TYPICAL ALL-AIR SYSTEM
                E.A.
EXHAUST        DAMPER
  AIR                           R.A.
                                FAN            R.A DUCT
                                                                     R.A. GRILL
                                                            S.A.
                                          S.A. DUCT       TERMINAL
                        R.A. DAMPER
                        COIL                     COOL
                                                  AIR
 FRESH
OUTDOOR                                                     HEAT
  AIR                    S.A.
                         FAN

     O.A.
   DAMPER               WATER PIPING
             FILTER




            CHILLED
             WATER               WATER
             PUMP               CHILLER


                                                                              Slide 12
TYPICAL ALL-AIR SYSTEM
                E.A.
EXHAUST        DAMPER
  AIR                           R.A.
                                FAN            R.A DUCT
                                                                       R.A. GRILL
                                                             S.A.
                                          S.A. DUCT        TERMINAL
                        R.A. DAMPER
                        COIL                     COOL
                                                  AIR
 FRESH
OUTDOOR                                                      HEAT
  AIR                    S.A.
                         FAN

     O.A.
   DAMPER               WATER PIPING
             FILTER


                                                                            HEAT


                                                                      COOLING
                                                                       TOWER
            CHILLED
             WATER               WATER
             PUMP               CHILLER
                                               CONDENSER
                                                 PUMP
                                                                                Slide 13
TYPICAL ALL-AIR SYSTEM
                E.A.
EXHAUST        DAMPER
  AIR                           R.A.
                                FAN            R.A DUCT
                                                                       R.A. GRILL
                                                             S.A.
                                          S.A. DUCT        TERMINAL
                        R.A. DAMPER
                        COIL                     COOL
                                                  AIR
 FRESH
OUTDOOR                                                      HEAT
  AIR                    S.A.
                         FAN

     O.A.
   DAMPER               WATER PIPING
             FILTER


                                                                            HEAT
  BOILER


                                                                      COOLING
                                                                       TOWER
            CHILLED
             WATER               WATER
             PUMP               CHILLER
                                               CONDENSER
                                                 PUMP
                                                                                Slide 14
Equipment Types

•   ROOFTOP PACKAGE UNIT
•   SPLIT SYSTEM
•   CHILLED WATER AIR HANDLER
•   VARIABLE AIR VOLUME (VAV)
•   AIR TO AIR HEAT PUMP
•   Life expectancy 10 to 12 yrs for rooftop and split systems
•   Expect increase in repair costs as equipment ages
•   Typically largest expense to operation of store, energy/repair costs
•   Repair or Replace?




                                                                           Slide 15
Single Package Roof Top Unit

•Most common
•Entire hvac system is
located on mall roof
•Most common to have
roof leaks from roof curb,
condensate overflow or
roof punctures
                                    Slide 16
Single Package Roof Top Unit
                                   HEAT

       COMP                  CONDR        ELECTRIC
               COIL                        HEATER
O.A.
                     FAN

E.A.                       S.A. DUCT


                         S.A.
         R.A. DUCT     TERMINAL




                            HEAT




                                                     Slide 17
Single Package Roof Top Unit



• Rooftop package unit
• Mounted on adaptor
    curb
•   Power exhaust and
    economizer installed


                                    Slide 18
Split System

•   HVAC system split into 2 pieces
•   Condensing unit located on roof (houses
    compressor, condenser coil, condenser fan motor)
•   Air handler located in space above ceiling (houses
    blower assembly, evap coil, air filters)
•   Connected electrically and with refrigerant piping
•   Most prone to refrigerant leaks especially if long
    distance between components
•   Many times refrigerant lines are buried in
    construction and inaccessible

                                                         Slide 19
SPLIT SYSTEM
            CONDENSING UNIT           HEAT
       REFRIGERANT                       C
          LINES                   C      O
                                  O      N
                                  M           AIR
                                  P      D
                                         R

                                             AIR HANDLING
                                                  UNIT
                      COIL
O.A.                                          POSSIBLE
                            FAN               ELECTRIC
                                                HEAT
E.A.                                          S.A. DUCT
                R.A. DUCT




                                  HEAT                         OPTIONAL
                                                            SUPPLEMENTARY
                                                               HEATING
                                                                SYSTEM



                                                                     Slide 20
SPLIT SYSTEM




               Slide 21
Split System


•   Air cooled condensing
    unit
•   Compressor, condenser
    coil and condenser fans
•   Connected to indoor air
    handler




                                  Slide 22
VAV BOX
•Consists of VAV terminal
                             Variable Air Volume

box located in the space
above ceiling
•May have supplemental
blower motor for positive
airflow to space
•May have air filtration
•Has a damper inside that
opens and closes on demand
from thermostat to allow
more or less airflow to
space
                                                   Slide 23
Major System Components


•   Compressor
•   Condenser coil
•   Evaporator coil
•   Condenser fan motor
•   Evaporator fan motor
•   Thermostatic expansion valve
•   Evaporator blower assembly
•   Economizers (Optional)



                                   Slide 24
HEAT REJECTION
                                                            95F DB
                                  (“HIGH TEMPERATURE”)      78F DB
                                                            HEAT
                                               95F
                                 105F
                     CONDENSER
       CONDITIONED
         SPACE                                 85F     COOLING
                                                        TOWER
                                          COMPRESSOR


95F                  55F
          75F
                                    35F
                                          COOLER
                      45F                       REFRIGERATION
                                                   MACHINE
         HEAT GATHERING                     (REFRIGERATION CYCLE)
      (“LOW TEMPERATURE”)



                                                                     Slide 25
Compressor


• This component is the heart of the system..
• Pumps refrigerant and oil throughout
    system
•   Separates the high pressure side of the
    system from the low pressure side
•   If compressor fails, no cooling is possible


                                                  Slide 26
Condenser

•   Condenser coil is what gets rid of the heat in the
    system
•   Can be water or air cooled, however most are air
    cooled in retail application
•   Located outdoors (air cooled)
•   Fins on coil are subject to corrosion in salt water
    environment. Special coatings can be applied.
•   Fins are subject to damage from hail
•   Traps dirt and requires periodic cleanings

                                                          Slide 27
Evaporator Coil

• Provides cold air to the space
• Located after the system air filters
• Return air is blown over the coil and chilled
• Removes moisture from air (condensate)
• Traps dirt that gets past air filters, reducing
    cooling capacity (95% is bacterial)
•   Requires periodic chemical cleaning


                                                    Slide 28
Evaporator Fan Motor


•   Located behind condenser coil
•   Draws ambient air across condenser coil
•   System may have up to 4 or more motors based on
    system capacity
•   Motors are direct drive with fan blades attached
•   Requires little if any maintenance (sealed
    bearings)


                                                       Slide 29
TXV Thermal Expansion Valve

•   Located at the evaporator coil
•   Provides the correct amount of refrigerant to the
    evaporator coil for proper cooling
•   Separates the high pressure side of the system
    from the low pressure side
•   Failure could cause compressor failure and loss of
    system cooling capacity
•   Frequently overlooked in diagnosing system
    problems
•   Requires manual setting of superheat for proper
    operation.
                                                         Slide 30
Evaporator Blower Assembly

•   Consists of:
•   Blower motor
•   Pulleys and fan belts
•   Bearings
•   Fan shaft
•   Fan wheels
•   Housings
•   Can be located indoors or outdoors



                                         Slide 31
Control Types


• CONVENTIONAL THERMOSTAT
• DIGITAL PROGRAMMABLE
    THERMOSTAT
•   PNEUMATIC
•   LCD SYSTEM
•   MALL INTERFACE


                            Slide 32
Low Ambient Controls

•   Low ambient controls
•   May be added to air cooled systems that must
    operate when outdoor temperatures are below 55
    degrees
•   Cycles condenser fan/s to maintain correct system
    pressures
•   Used when economizer is not present
•   Much less costly to install
•   Much more costly to operate


                                                        Slide 33
Conventional Thermostat

•   Completely manual operation
•   Will maintain a single heat or cool setting
•   System must be switched from heat to cool
•   No energy savings
•   Will allow system to operate all night while store
    is closed wasting energy
•   Easy to tamper with
•   Least expensive to install


                                                         Slide 34
Programmable Thermostat
•   Provides auto
    changeover from heat
    to cool
•   Provides up to 4
    heat/cool settings per
    24 hour period
•   Can provide different
    weekend settings
•   Keyboard can be
    locked out
•   Set it and forget it
                                Slide 35
Pneumatic Thermostat


• Uses air provided by mall to operate
    thermostat
•   Very commonly used with VAV systems
•   Least commonly found in malls
•   Parts are fairly expensive



                                          Slide 36
LCD Thermostat


• Used in newer stores
• Programmable type
• Can be dialed into by monitoring company
 for data




                                             Slide 37
Rules Of Thumb

1HP = 1KW = 1KVA                     1KW = 3413 BTU

1 Ton Cooling = 12,000 BTU           1 Ton = 400 CFM

Retail = 380 SQ FT/ Ton cooling

Delta T = 18 F across coil cooling    Delta T = 25 F for heating

 CFM = Building Volume in Cubic Feet
          Minute/Air Change

 Delta T = Difference between entering and leaving DB = ΔT




                                                                   Slide 39
Servpro of Great Neck /
   Port Washington
   For Further Information
      Please Contact Us:
         516-767-9600
  ServproOfGreatNeck.com
                             Slide 40

HVAC Basic Concepts of Air Conditioning

  • 1.
    Basic Concepts ofAir Conditioning Prepared exclusively for COACH LEATHERWARE
  • 2.
    Panel Moderator: Bob Keingstein Boss FacilitiesServices 631-361-7430 bobk@bossfacilityservices.com Slide 1
  • 3.
    COIL COOL AIR HEAT SOURCE OF COOL AIR • COIL • Slide 3
  • 4.
    TYPICAL ALL-AIR SYSTEM S.A. DUCT COIL COOL AIR HEAT S.A. FAN Slide 4
  • 5.
    TYPICAL ALL-AIR SYSTEM S.A. S.A. DUCT TERMINAL COIL COOL AIR HEAT S.A. FAN Slide 5
  • 6.
    TYPICAL ALL-AIR SYSTEM R.A. GRILL S.A. S.A. DUCT TERMINAL COOL WARM AIR COIL AIR HEAT S.A. FAN Slide 6
  • 7.
    TYPICAL ALL-AIR SYSTEM R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL COIL COOL AIR HEAT S.A. FAN Slide 7
  • 8.
    TYPICAL ALL-AIR SYSTEM R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL COIL COOL AIR HEAT S.A. FAN Slide 8
  • 9.
    TYPICAL ALL-AIR SYSTEM R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL R.A. DAMPER COIL COOL AIR FRESH OUTDOOR HEAT AIR S.A. FAN O.A. DAMPER FILTER Slide 9
  • 10.
    TYPICAL ALL-AIR SYSTEM E.A. EXHAUST DAMPER AIR R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL R.A. DAMPER COIL COOL AIR FRESH OUTDOOR HEAT AIR S.A. FAN O.A. DAMPER FILTER Slide 10
  • 11.
    Economizer • Provides cooling to space when outdoor air temperatures are below 55 degrees • Switches over automatically from mechanical cooling • Adjusts R.A. and F.A. dampers to maintain space temp • May incorporate enthalpy control • Mandatory in some states based on unit capacity Slide 11
  • 12.
    TYPICAL ALL-AIR SYSTEM E.A. EXHAUST DAMPER AIR R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL R.A. DAMPER COIL COOL AIR FRESH OUTDOOR HEAT AIR S.A. FAN O.A. DAMPER WATER PIPING FILTER CHILLED WATER WATER PUMP CHILLER Slide 12
  • 13.
    TYPICAL ALL-AIR SYSTEM E.A. EXHAUST DAMPER AIR R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL R.A. DAMPER COIL COOL AIR FRESH OUTDOOR HEAT AIR S.A. FAN O.A. DAMPER WATER PIPING FILTER HEAT COOLING TOWER CHILLED WATER WATER PUMP CHILLER CONDENSER PUMP Slide 13
  • 14.
    TYPICAL ALL-AIR SYSTEM E.A. EXHAUST DAMPER AIR R.A. FAN R.A DUCT R.A. GRILL S.A. S.A. DUCT TERMINAL R.A. DAMPER COIL COOL AIR FRESH OUTDOOR HEAT AIR S.A. FAN O.A. DAMPER WATER PIPING FILTER HEAT BOILER COOLING TOWER CHILLED WATER WATER PUMP CHILLER CONDENSER PUMP Slide 14
  • 15.
    Equipment Types • ROOFTOP PACKAGE UNIT • SPLIT SYSTEM • CHILLED WATER AIR HANDLER • VARIABLE AIR VOLUME (VAV) • AIR TO AIR HEAT PUMP • Life expectancy 10 to 12 yrs for rooftop and split systems • Expect increase in repair costs as equipment ages • Typically largest expense to operation of store, energy/repair costs • Repair or Replace? Slide 15
  • 16.
    Single Package RoofTop Unit •Most common •Entire hvac system is located on mall roof •Most common to have roof leaks from roof curb, condensate overflow or roof punctures Slide 16
  • 17.
    Single Package RoofTop Unit HEAT COMP CONDR ELECTRIC COIL HEATER O.A. FAN E.A. S.A. DUCT S.A. R.A. DUCT TERMINAL HEAT Slide 17
  • 18.
    Single Package RoofTop Unit • Rooftop package unit • Mounted on adaptor curb • Power exhaust and economizer installed Slide 18
  • 19.
    Split System • HVAC system split into 2 pieces • Condensing unit located on roof (houses compressor, condenser coil, condenser fan motor) • Air handler located in space above ceiling (houses blower assembly, evap coil, air filters) • Connected electrically and with refrigerant piping • Most prone to refrigerant leaks especially if long distance between components • Many times refrigerant lines are buried in construction and inaccessible Slide 19
  • 20.
    SPLIT SYSTEM CONDENSING UNIT HEAT REFRIGERANT C LINES C O O N M AIR P D R AIR HANDLING UNIT COIL O.A. POSSIBLE FAN ELECTRIC HEAT E.A. S.A. DUCT R.A. DUCT HEAT OPTIONAL SUPPLEMENTARY HEATING SYSTEM Slide 20
  • 21.
    SPLIT SYSTEM Slide 21
  • 22.
    Split System • Air cooled condensing unit • Compressor, condenser coil and condenser fans • Connected to indoor air handler Slide 22
  • 23.
    VAV BOX •Consists ofVAV terminal Variable Air Volume box located in the space above ceiling •May have supplemental blower motor for positive airflow to space •May have air filtration •Has a damper inside that opens and closes on demand from thermostat to allow more or less airflow to space Slide 23
  • 24.
    Major System Components • Compressor • Condenser coil • Evaporator coil • Condenser fan motor • Evaporator fan motor • Thermostatic expansion valve • Evaporator blower assembly • Economizers (Optional) Slide 24
  • 25.
    HEAT REJECTION 95F DB (“HIGH TEMPERATURE”) 78F DB HEAT 95F 105F CONDENSER CONDITIONED SPACE 85F COOLING TOWER COMPRESSOR 95F 55F 75F 35F COOLER 45F REFRIGERATION MACHINE HEAT GATHERING (REFRIGERATION CYCLE) (“LOW TEMPERATURE”) Slide 25
  • 26.
    Compressor • This componentis the heart of the system.. • Pumps refrigerant and oil throughout system • Separates the high pressure side of the system from the low pressure side • If compressor fails, no cooling is possible Slide 26
  • 27.
    Condenser • Condenser coil is what gets rid of the heat in the system • Can be water or air cooled, however most are air cooled in retail application • Located outdoors (air cooled) • Fins on coil are subject to corrosion in salt water environment. Special coatings can be applied. • Fins are subject to damage from hail • Traps dirt and requires periodic cleanings Slide 27
  • 28.
    Evaporator Coil • Providescold air to the space • Located after the system air filters • Return air is blown over the coil and chilled • Removes moisture from air (condensate) • Traps dirt that gets past air filters, reducing cooling capacity (95% is bacterial) • Requires periodic chemical cleaning Slide 28
  • 29.
    Evaporator Fan Motor • Located behind condenser coil • Draws ambient air across condenser coil • System may have up to 4 or more motors based on system capacity • Motors are direct drive with fan blades attached • Requires little if any maintenance (sealed bearings) Slide 29
  • 30.
    TXV Thermal ExpansionValve • Located at the evaporator coil • Provides the correct amount of refrigerant to the evaporator coil for proper cooling • Separates the high pressure side of the system from the low pressure side • Failure could cause compressor failure and loss of system cooling capacity • Frequently overlooked in diagnosing system problems • Requires manual setting of superheat for proper operation. Slide 30
  • 31.
    Evaporator Blower Assembly • Consists of: • Blower motor • Pulleys and fan belts • Bearings • Fan shaft • Fan wheels • Housings • Can be located indoors or outdoors Slide 31
  • 32.
    Control Types • CONVENTIONALTHERMOSTAT • DIGITAL PROGRAMMABLE THERMOSTAT • PNEUMATIC • LCD SYSTEM • MALL INTERFACE Slide 32
  • 33.
    Low Ambient Controls • Low ambient controls • May be added to air cooled systems that must operate when outdoor temperatures are below 55 degrees • Cycles condenser fan/s to maintain correct system pressures • Used when economizer is not present • Much less costly to install • Much more costly to operate Slide 33
  • 34.
    Conventional Thermostat • Completely manual operation • Will maintain a single heat or cool setting • System must be switched from heat to cool • No energy savings • Will allow system to operate all night while store is closed wasting energy • Easy to tamper with • Least expensive to install Slide 34
  • 35.
    Programmable Thermostat • Provides auto changeover from heat to cool • Provides up to 4 heat/cool settings per 24 hour period • Can provide different weekend settings • Keyboard can be locked out • Set it and forget it Slide 35
  • 36.
    Pneumatic Thermostat • Usesair provided by mall to operate thermostat • Very commonly used with VAV systems • Least commonly found in malls • Parts are fairly expensive Slide 36
  • 37.
    LCD Thermostat • Usedin newer stores • Programmable type • Can be dialed into by monitoring company for data Slide 37
  • 38.
    Rules Of Thumb 1HP= 1KW = 1KVA 1KW = 3413 BTU 1 Ton Cooling = 12,000 BTU 1 Ton = 400 CFM Retail = 380 SQ FT/ Ton cooling Delta T = 18 F across coil cooling Delta T = 25 F for heating CFM = Building Volume in Cubic Feet Minute/Air Change Delta T = Difference between entering and leaving DB = ΔT Slide 39
  • 39.
    Servpro of GreatNeck / Port Washington For Further Information Please Contact Us: 516-767-9600 ServproOfGreatNeck.com Slide 40