Fire guidelines by NBC
Maneesh kumar Reddy
Ps no 20092039
Hci metros
Basic Terminology-
1.Automatic fire detection and alarm system-
Fire alarm system comprising components for
Automatically detecting a fire, initiating an alarm
of fire and initiating other actions as appropriate.
2.Automatic sprinkler system-
A system of water pipes fitted with sprinkler
heads at suitable intervals and heights and
designed to actuate automatically, control
and extinguish a fire by the discharge of water.
Basic Terminology-
3. Down comer — An arrangement of fire fighting
within the building by means of down-comer pipe
connected to terrace tank through terrace pump,
gate valve and non-return valve and having mains
not less than 100 mm internal diameter with landing
valves on each floor/landing. It is also fitted with inlet
connections at ground level for charging with water
by pumping from fire service appliances and air
release valve at roof level to release trapped air inside.
Basic Terminology-
4. Emergency Lighting System — A complete but discrete emergency
lighting installation from the standby power source to the emergency
lighting lamp(s),
5. Escape Lighting — That part of emergency lighting which is provided
to ensure that the escape route is illuminated at all material times.
7.Fire load- It is the measure of the maximum heat that will be released
if all the combustibles in a fire area burn. It is expressed in kJ/kg
(one kJ is approx. equal to 1 btu).
Or..
Calorific energy, of the whole contents contained in a space, including
the facing of the walls , partition, floors and ceilings
Basic Terminology-
7. Fire Door — A fire-resistive door approved for openings in fire separation.
8. Fire Exit — Away out leading to an escape route
having panic bar hardware provided on the door.
9. Fire Lift — The lift installed to enable fire
services personnel to reach different floors with
minimum delay, having such features as required in
accordance with this Part.
Basic Terminology-
11. Stack Pressure:
“ Pressure difference caused by a temperature difference creating an air movement within a duct, chimney or enclosure ”
Explaination-Smoke moves from an area of higher
pressure to one of lower pressure. Pressure
differences may be caused by buoyancy from
the fire, stack effect, wind and forces from
building heating, ventilating and air-conditioning
systems. In tall buildings, these factors are
complicated by the stack effect, which is the
vertical natural air movement from the building
caused by the differences in temperature and
densities between the inside and outside air.
This stack effect plays a vital role in smoke movement.
Basic Terminology-
11. Dry Riser — An arrangement of fire fighting within the building by means of vertical
rising mains not less than 100 mm internal diameter with landing valves on each floor
landing which is normally dry but is capable of being charged with water usually by
pumping from fire service appliances.
12. Wet Riser-An arrangement for fire fighting within the building by means of
vertical rising mains of not less than 100 mm diameter with landing valves on each
floor/landing for fire fighting purposes and permanently charged with water from a
pressurized supply.
“Difference between wet and a dry riser, is that wet
risers are permanently charged with water by a fire
pump from a permanent water supply (which can
either be an underground water tank or an elevated
water tank at the terrace), whereas, the dry riser has
to be fed with water by fire brigade after their arrival.
Landing valves are nothing but internal hydrants
fitted with standard instantaneous female couplings
and may be of single or double outlet types”
Fire lift-
 A lift within the firefighting shaft with dual power supply and is capable of being commandeered
by the Fire Service.
 Operation of the firefighter switch (usually situated at the ground floor level) activates the
lift controls for firefighter use. The lift will only be controlled by the controls within the car and the
doors will only open by pressing the door open button within the car
 1 lift for Min area-1200 sq.m and shall be made exclusively available for firemen in an
Emergency.
 Floor area not less than 1.4 sq.m per person ,automatically sliding door of min 0.8m width
of 8 persons or 545 kg capacity
 Separate electric supply and along with normal electricity an alternate means of power
Arrangement.
 Operation of lift should be made by a simple toggle or two button switch situated in a glass
fronted box adjacent to lift at the entrance level
 Speed of the fire lift will be in such a way that it reaches top floor within a minute.
Internal stair case-
 Interior stairs should be constructed of non-combustible materials
throughout and as a self-contained unit with an external wall constituting
at least one of its sides and should be completely enclosed.
 A staircase should not be arranged round a lift shaft unless the latter is
totally enclosed by a material of fire-resistance rating as that for the type
of construction itself.
 Hollow combustible construction should not be permitted.
 No gas piping should be laid in the stairway.
 The minimum width of tread without nosing should be 25 cm for internal staircase of residential buildings. This should be 30 cm
for assembly, educational, institutional, business and other buildings. The treads should be constructed and maintained in a
manner to prevent slipping.
 The maximum height of riser should be 19 cm for residential buildings and 15 cm for other buildings and the number should be
limited to 15 per flight.
 Hand rails should be provided at a minimum height of 100 cm and not exceeding 120 cm to be measured from the base of the
middle of the treads to the top of the hand rails. Further, the gap between the two verticals should not exceed 30 cm. This gap
should be reduced to 15 cm where children are likely to use the staircase.
 The number of people in between floor landings in staircase should not be less than the population on each floor for the
purpose of design of staircase.
EXTERNAL FIRE ESCAPE STAIRCASE-
 Any door opening onto the stairway below the top floor and any door in the external wall beneath the stairway should
be self closing and should have a minimum half hour standard of fire resistance.
 If windows are below or less than 1.8 metres horizontally from the stairway, they should be fixed shut and have the
above standard of fire resistance.
 The route from the foot of the stairway to a final place of safety should be unobstructed and free from vegetation..
 Fire escapes should not be taken into account in calculating the evacuation time of a building.
 All fire escapes should be directly connected to the ground.
 Entrance to the fire escape should be separate and remote from the internal staircase.
 Care should be taken to ensure that the wall opening or window opens on to or close to a fire escape.
 The route to the fire escape should be free of obstructions at all times.
 The fire escape should be constructed of non-combustible materials, and any doorway leading to the fire escape should have the required fire
resistance.
 No staircase, used as a fire escape, should be inclined at an angle greater than 45° to the horizontal.
 Fire escape stairs should have straight flight not less than 75 cm wide with 20 cm treads and risers not more than 19 cm. The number of risers
should be limited to 15 per flight.
 Hand rails should be of a height not less than 100 cm and not exceeding 120 cm.
EXTERNAL FIRE ESCAPE STAIRCASE-
SPIRAL STAIR CASES-
 The use of spiral staircase should be limited to occupant load and
to a building not exceeding 9 m in height unless they are connected
to platforms, such as balconies and terraces to allow escapees
to pause.
 Spiral fire escape should be not less than 150 cm in diameter and
should be designed to give adequate headroom.
Fire Escape Plan-
 A fire escape plan is for use by the public and occupants in case of a fire as well as for the fire fighters.
 It should clearly show the layout of the floor in the correct building orientation and highlight the escape routes
(in relation to viewer’s location), escape corridors and exit staircases using appropriate colours , directional
signs and words
 Other information required on the plan are for fire fighting purposes and these include the following;
(1) Firemen’s lift (2) Hose reels (3) Extinguishers (4) Dry and wet risers
(5) Fire indicator board (6) Manual alarm call points
 These plans should be placed at common area locations in such buildings where the public and occupants of
the building are most likely to frequent or use.
Fire Escape Plan-
DOOR WAYS-
 Every exit doorway should open into an enclosed stairway, or horizontal exit of a corridor, or passageway providing continuous
and protected means of egress.
 No exit doorway should be less than 100 cm in width. Doorways should be
not less than 200 cm in height..
 Exit doorways should open outwards, that is, away from the room but should
not obstruct the travel along any exit. No door, when opened, should reduce
the required width of stairway or landing to less than 90 cm; overhead or sliding
door should not be installed.
 Exit door should not open immediately upon a flight of stairs, a landing equal to
at least the width of the door should be provided in the stairway at each doorway
; the level of landing should be the same as that of the floor which it serves..
 Exit doorways should be openable from the side which they serve without the
use of a key.
Revolving doors-
 Revolving doors should not be used as required exits except in residential, business
and mercantile occupancies but should not constitute more than half the total required
door width. In mercantile buildings where there is possibility of congregation of a large
number of people (more than 200), revolving doors should not be permitted.
 Where the revolving door provided are completely made of glass (plate glass),
a red circle or emblem or logo at 1·5 m level above sill should be painted on the glass.
The thickness of the glass should not be not less than 12 mm.
Corridors and Passageways-
 Exit corridors and passageways should be of width not less than the
aggregate required width of exit doorways leading from them in the
direction of travel to the exterior.
 Where stairways discharge through corridors and passageways, the
height of corridors and passageways should be not less than 2·4 m.
Fire guidelines by nbc part 1

More Related Content

What's hot

Active fire protection system
Active fire protection systemActive fire protection system
Active fire protection system
gauravashist
 
Services in High Rise Building
Services in High Rise Building  Services in High Rise Building
Services in High Rise Building
ShrushtiAhirrao1
 
Fire safety system of Building.
Fire safety system of Building.Fire safety system of Building.
Fire safety system of Building.
Integrated Design
 
Fire safety in Office building Literature, net and live case study
Fire safety in Office building Literature, net and live case studyFire safety in Office building Literature, net and live case study
Fire safety in Office building Literature, net and live case study
Irene Devakirubai
 
HOUSING LITERATURE STUDY M.ARCH CCA
HOUSING LITERATURE STUDY M.ARCH CCAHOUSING LITERATURE STUDY M.ARCH CCA
HOUSING LITERATURE STUDY M.ARCH CCA
Ar. Prerna Chouhan
 
Fire guidelines by nbc part 2
Fire guidelines by nbc part 2Fire guidelines by nbc part 2
Fire guidelines by nbc part 2
R821992
 
Case Study Of a Typical Apartment.
Case Study Of a Typical Apartment.Case Study Of a Typical Apartment.
Case Study Of a Typical Apartment.
Osama Farooquie
 
NBC NORMS FOR HVAC SYSTEMS
NBC NORMS FOR HVAC SYSTEMSNBC NORMS FOR HVAC SYSTEMS
NBC NORMS FOR HVAC SYSTEMS
asif anwar
 
Group Housing (Library Study)
Group Housing (Library Study)Group Housing (Library Study)
Group Housing (Library Study)
Mansi Pushpakar
 
National building code
National building codeNational building code
National building code
Mayank Rawat
 
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
Sevajothi Crafts
 
National building code for residential apartments in india
National building code for residential apartments in indiaNational building code for residential apartments in india
National building code for residential apartments in india
Vinod Kumar Nehta
 
Site analysis
Site analysisSite analysis
Site analysis
Kushal Jangid
 
Case study- ATS Group housing
Case study- ATS Group housingCase study- ATS Group housing
Case study- ATS Group housing
Ayushi Agrawal
 
Case study kohinoor square Mumbai
Case study kohinoor square MumbaiCase study kohinoor square Mumbai
Case study kohinoor square Mumbai
Tapu Taba
 
Fire protection system
Fire protection systemFire protection system
Fire protection system
Deepak Thapa
 
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Prateek Srivastava
 
Ar. Sanjay Puri and his works
Ar. Sanjay Puri and his worksAr. Sanjay Puri and his works
Ar. Sanjay Puri and his works
Rajat Nainwal
 

What's hot (20)

Active fire protection system
Active fire protection systemActive fire protection system
Active fire protection system
 
Services in High Rise Building
Services in High Rise Building  Services in High Rise Building
Services in High Rise Building
 
The architects act, 1972
The architects act, 1972The architects act, 1972
The architects act, 1972
 
Fire safety system of Building.
Fire safety system of Building.Fire safety system of Building.
Fire safety system of Building.
 
Fire safety in Office building Literature, net and live case study
Fire safety in Office building Literature, net and live case studyFire safety in Office building Literature, net and live case study
Fire safety in Office building Literature, net and live case study
 
HOUSING LITERATURE STUDY M.ARCH CCA
HOUSING LITERATURE STUDY M.ARCH CCAHOUSING LITERATURE STUDY M.ARCH CCA
HOUSING LITERATURE STUDY M.ARCH CCA
 
Fire guidelines by nbc part 2
Fire guidelines by nbc part 2Fire guidelines by nbc part 2
Fire guidelines by nbc part 2
 
Case Study Of a Typical Apartment.
Case Study Of a Typical Apartment.Case Study Of a Typical Apartment.
Case Study Of a Typical Apartment.
 
Building Code - Egress
Building Code - EgressBuilding Code - Egress
Building Code - Egress
 
NBC NORMS FOR HVAC SYSTEMS
NBC NORMS FOR HVAC SYSTEMSNBC NORMS FOR HVAC SYSTEMS
NBC NORMS FOR HVAC SYSTEMS
 
Group Housing (Library Study)
Group Housing (Library Study)Group Housing (Library Study)
Group Housing (Library Study)
 
National building code
National building codeNational building code
National building code
 
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
104875110 vernacular-architecture-of-hills-india-130926123709-phpapp02
 
National building code for residential apartments in india
National building code for residential apartments in indiaNational building code for residential apartments in india
National building code for residential apartments in india
 
Site analysis
Site analysisSite analysis
Site analysis
 
Case study- ATS Group housing
Case study- ATS Group housingCase study- ATS Group housing
Case study- ATS Group housing
 
Case study kohinoor square Mumbai
Case study kohinoor square MumbaiCase study kohinoor square Mumbai
Case study kohinoor square Mumbai
 
Fire protection system
Fire protection systemFire protection system
Fire protection system
 
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
 
Ar. Sanjay Puri and his works
Ar. Sanjay Puri and his worksAr. Sanjay Puri and his works
Ar. Sanjay Puri and his works
 

Similar to Fire guidelines by nbc part 1

Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016
Anil Kumar R
 
11. Smoke Proof Enclosures
11. Smoke Proof Enclosures11. Smoke Proof Enclosures
11. Smoke Proof Enclosures
Sadiq Alam
 
General Requirments Of Fire Resisting Building.pptx
General Requirments Of Fire Resisting Building.pptxGeneral Requirments Of Fire Resisting Building.pptx
General Requirments Of Fire Resisting Building.pptx
Afroz Saiyad
 
Fire safety in building
Fire safety in building Fire safety in building
Fire safety in building
wasim shaikh
 
Bs ii-assignment
Bs ii-assignmentBs ii-assignment
Bs ii-assignment
Lwj Welson
 
Means of egress
Means of egressMeans of egress
Means of egress
Tala Jazzy
 
Litreature study of group housing by rushali grp
Litreature study of group housing by rushali grpLitreature study of group housing by rushali grp
Litreature study of group housing by rushali grp
RUSHALI SRIVASTAVA
 
Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced Services
Pratibha Mohan
 
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDYBUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
Agrima Garg
 
Building services project 2 presentation slides
Building services project 2 presentation slidesBuilding services project 2 presentation slides
Building services project 2 presentation slides
Tan Jaden
 
Fire safety guide
Fire safety guideFire safety guide
Fire safety guide
sappy2shail
 
Service core
Service coreService core
Service core
aduiti
 
lecture 11 fire fighting.ppt
lecture 11 fire fighting.pptlecture 11 fire fighting.ppt
lecture 11 fire fighting.ppt
SanskritiJindal4
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using Shafts
Colt UK
 
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptxPRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
praveenphalani
 
GROUP 4 LITERATURE.pptx
GROUP 4 LITERATURE.pptxGROUP 4 LITERATURE.pptx
GROUP 4 LITERATURE.pptx
HarshChoudhary18682
 
Housing design n standards
Housing design n standardsHousing design n standards
Housing design n standards
JoshuaL3
 
S4 a.020 vivienda
S4 a.020 viviendaS4 a.020 vivienda
S4 a.020 vivienda
MIKYRoll
 
Unit 2 Min Space Requirements .pdf
Unit 2 Min Space Requirements .pdfUnit 2 Min Space Requirements .pdf
Unit 2 Min Space Requirements .pdf
SuryaTeja67437
 

Similar to Fire guidelines by nbc part 1 (20)

Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016Presentation Highlighting Implication of NBC, Part-IV 2016
Presentation Highlighting Implication of NBC, Part-IV 2016
 
11. Smoke Proof Enclosures
11. Smoke Proof Enclosures11. Smoke Proof Enclosures
11. Smoke Proof Enclosures
 
General Requirments Of Fire Resisting Building.pptx
General Requirments Of Fire Resisting Building.pptxGeneral Requirments Of Fire Resisting Building.pptx
General Requirments Of Fire Resisting Building.pptx
 
Fire safety in building
Fire safety in building Fire safety in building
Fire safety in building
 
Bs ii-assignment
Bs ii-assignmentBs ii-assignment
Bs ii-assignment
 
Means of egress
Means of egressMeans of egress
Means of egress
 
Litreature study of group housing by rushali grp
Litreature study of group housing by rushali grpLitreature study of group housing by rushali grp
Litreature study of group housing by rushali grp
 
Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced Services
 
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDYBUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
BUSINESS HOTEL CASE STUDY AND LITERATURE STUDY
 
Building services project 2 presentation slides
Building services project 2 presentation slidesBuilding services project 2 presentation slides
Building services project 2 presentation slides
 
Fire safety guide
Fire safety guideFire safety guide
Fire safety guide
 
Service core
Service coreService core
Service core
 
lecture 11 fire fighting.ppt
lecture 11 fire fighting.pptlecture 11 fire fighting.ppt
lecture 11 fire fighting.ppt
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using Shafts
 
Means Of Egress
Means Of EgressMeans Of Egress
Means Of Egress
 
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptxPRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
 
GROUP 4 LITERATURE.pptx
GROUP 4 LITERATURE.pptxGROUP 4 LITERATURE.pptx
GROUP 4 LITERATURE.pptx
 
Housing design n standards
Housing design n standardsHousing design n standards
Housing design n standards
 
S4 a.020 vivienda
S4 a.020 viviendaS4 a.020 vivienda
S4 a.020 vivienda
 
Unit 2 Min Space Requirements .pdf
Unit 2 Min Space Requirements .pdfUnit 2 Min Space Requirements .pdf
Unit 2 Min Space Requirements .pdf
 

Recently uploaded

weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
Divya Somashekar
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
Kamal Acharya
 
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERSCW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
veerababupersonal22
 
Basic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparelBasic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparel
top1002
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
gestioneergodomus
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
thanhdowork
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
Amil Baba Dawood bangali
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
SyedAbiiAzazi1
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
manasideore6
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
BrazilAccount1
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
MdTanvirMahtab2
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
ChristineTorrepenida1
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 

Recently uploaded (20)

weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
block diagram and signal flow graph representation
block diagram and signal flow graph representationblock diagram and signal flow graph representation
block diagram and signal flow graph representation
 
Student information management system project report ii.pdf
Student information management system project report ii.pdfStudent information management system project report ii.pdf
Student information management system project report ii.pdf
 
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERSCW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERS
 
Basic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparelBasic Industrial Engineering terms for apparel
Basic Industrial Engineering terms for apparel
 
DfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributionsDfMAy 2024 - key insights and contributions
DfMAy 2024 - key insights and contributions
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
RAT: Retrieval Augmented Thoughts Elicit Context-Aware Reasoning in Long-Hori...
 
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application14 Template Contractual Notice - EOT Application
14 Template Contractual Notice - EOT Application
 
Standard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - NeometrixStandard Reomte Control Interface - Neometrix
Standard Reomte Control Interface - Neometrix
 
DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
Fundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptxFundamentals of Electric Drives and its applications.pptx
Fundamentals of Electric Drives and its applications.pptx
 
English lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdfEnglish lab ppt no titlespecENG PPTt.pdf
English lab ppt no titlespecENG PPTt.pdf
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)
 
Unbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptxUnbalanced Three Phase Systems and circuits.pptx
Unbalanced Three Phase Systems and circuits.pptx
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 

Fire guidelines by nbc part 1

  • 1. Fire guidelines by NBC Maneesh kumar Reddy Ps no 20092039 Hci metros
  • 2. Basic Terminology- 1.Automatic fire detection and alarm system- Fire alarm system comprising components for Automatically detecting a fire, initiating an alarm of fire and initiating other actions as appropriate. 2.Automatic sprinkler system- A system of water pipes fitted with sprinkler heads at suitable intervals and heights and designed to actuate automatically, control and extinguish a fire by the discharge of water.
  • 3. Basic Terminology- 3. Down comer — An arrangement of fire fighting within the building by means of down-comer pipe connected to terrace tank through terrace pump, gate valve and non-return valve and having mains not less than 100 mm internal diameter with landing valves on each floor/landing. It is also fitted with inlet connections at ground level for charging with water by pumping from fire service appliances and air release valve at roof level to release trapped air inside.
  • 4. Basic Terminology- 4. Emergency Lighting System — A complete but discrete emergency lighting installation from the standby power source to the emergency lighting lamp(s), 5. Escape Lighting — That part of emergency lighting which is provided to ensure that the escape route is illuminated at all material times. 7.Fire load- It is the measure of the maximum heat that will be released if all the combustibles in a fire area burn. It is expressed in kJ/kg (one kJ is approx. equal to 1 btu). Or.. Calorific energy, of the whole contents contained in a space, including the facing of the walls , partition, floors and ceilings
  • 5. Basic Terminology- 7. Fire Door — A fire-resistive door approved for openings in fire separation. 8. Fire Exit — Away out leading to an escape route having panic bar hardware provided on the door. 9. Fire Lift — The lift installed to enable fire services personnel to reach different floors with minimum delay, having such features as required in accordance with this Part.
  • 6. Basic Terminology- 11. Stack Pressure: “ Pressure difference caused by a temperature difference creating an air movement within a duct, chimney or enclosure ” Explaination-Smoke moves from an area of higher pressure to one of lower pressure. Pressure differences may be caused by buoyancy from the fire, stack effect, wind and forces from building heating, ventilating and air-conditioning systems. In tall buildings, these factors are complicated by the stack effect, which is the vertical natural air movement from the building caused by the differences in temperature and densities between the inside and outside air. This stack effect plays a vital role in smoke movement.
  • 7. Basic Terminology- 11. Dry Riser — An arrangement of fire fighting within the building by means of vertical rising mains not less than 100 mm internal diameter with landing valves on each floor landing which is normally dry but is capable of being charged with water usually by pumping from fire service appliances. 12. Wet Riser-An arrangement for fire fighting within the building by means of vertical rising mains of not less than 100 mm diameter with landing valves on each floor/landing for fire fighting purposes and permanently charged with water from a pressurized supply. “Difference between wet and a dry riser, is that wet risers are permanently charged with water by a fire pump from a permanent water supply (which can either be an underground water tank or an elevated water tank at the terrace), whereas, the dry riser has to be fed with water by fire brigade after their arrival. Landing valves are nothing but internal hydrants fitted with standard instantaneous female couplings and may be of single or double outlet types”
  • 8. Fire lift-  A lift within the firefighting shaft with dual power supply and is capable of being commandeered by the Fire Service.  Operation of the firefighter switch (usually situated at the ground floor level) activates the lift controls for firefighter use. The lift will only be controlled by the controls within the car and the doors will only open by pressing the door open button within the car  1 lift for Min area-1200 sq.m and shall be made exclusively available for firemen in an Emergency.  Floor area not less than 1.4 sq.m per person ,automatically sliding door of min 0.8m width of 8 persons or 545 kg capacity  Separate electric supply and along with normal electricity an alternate means of power Arrangement.  Operation of lift should be made by a simple toggle or two button switch situated in a glass fronted box adjacent to lift at the entrance level  Speed of the fire lift will be in such a way that it reaches top floor within a minute.
  • 9. Internal stair case-  Interior stairs should be constructed of non-combustible materials throughout and as a self-contained unit with an external wall constituting at least one of its sides and should be completely enclosed.  A staircase should not be arranged round a lift shaft unless the latter is totally enclosed by a material of fire-resistance rating as that for the type of construction itself.  Hollow combustible construction should not be permitted.  No gas piping should be laid in the stairway.  The minimum width of tread without nosing should be 25 cm for internal staircase of residential buildings. This should be 30 cm for assembly, educational, institutional, business and other buildings. The treads should be constructed and maintained in a manner to prevent slipping.  The maximum height of riser should be 19 cm for residential buildings and 15 cm for other buildings and the number should be limited to 15 per flight.  Hand rails should be provided at a minimum height of 100 cm and not exceeding 120 cm to be measured from the base of the middle of the treads to the top of the hand rails. Further, the gap between the two verticals should not exceed 30 cm. This gap should be reduced to 15 cm where children are likely to use the staircase.  The number of people in between floor landings in staircase should not be less than the population on each floor for the purpose of design of staircase.
  • 10. EXTERNAL FIRE ESCAPE STAIRCASE-  Any door opening onto the stairway below the top floor and any door in the external wall beneath the stairway should be self closing and should have a minimum half hour standard of fire resistance.  If windows are below or less than 1.8 metres horizontally from the stairway, they should be fixed shut and have the above standard of fire resistance.  The route from the foot of the stairway to a final place of safety should be unobstructed and free from vegetation..  Fire escapes should not be taken into account in calculating the evacuation time of a building.  All fire escapes should be directly connected to the ground.  Entrance to the fire escape should be separate and remote from the internal staircase.  Care should be taken to ensure that the wall opening or window opens on to or close to a fire escape.  The route to the fire escape should be free of obstructions at all times.  The fire escape should be constructed of non-combustible materials, and any doorway leading to the fire escape should have the required fire resistance.  No staircase, used as a fire escape, should be inclined at an angle greater than 45° to the horizontal.  Fire escape stairs should have straight flight not less than 75 cm wide with 20 cm treads and risers not more than 19 cm. The number of risers should be limited to 15 per flight.  Hand rails should be of a height not less than 100 cm and not exceeding 120 cm.
  • 11. EXTERNAL FIRE ESCAPE STAIRCASE- SPIRAL STAIR CASES-  The use of spiral staircase should be limited to occupant load and to a building not exceeding 9 m in height unless they are connected to platforms, such as balconies and terraces to allow escapees to pause.  Spiral fire escape should be not less than 150 cm in diameter and should be designed to give adequate headroom.
  • 12. Fire Escape Plan-  A fire escape plan is for use by the public and occupants in case of a fire as well as for the fire fighters.  It should clearly show the layout of the floor in the correct building orientation and highlight the escape routes (in relation to viewer’s location), escape corridors and exit staircases using appropriate colours , directional signs and words  Other information required on the plan are for fire fighting purposes and these include the following; (1) Firemen’s lift (2) Hose reels (3) Extinguishers (4) Dry and wet risers (5) Fire indicator board (6) Manual alarm call points  These plans should be placed at common area locations in such buildings where the public and occupants of the building are most likely to frequent or use.
  • 14. DOOR WAYS-  Every exit doorway should open into an enclosed stairway, or horizontal exit of a corridor, or passageway providing continuous and protected means of egress.  No exit doorway should be less than 100 cm in width. Doorways should be not less than 200 cm in height..  Exit doorways should open outwards, that is, away from the room but should not obstruct the travel along any exit. No door, when opened, should reduce the required width of stairway or landing to less than 90 cm; overhead or sliding door should not be installed.  Exit door should not open immediately upon a flight of stairs, a landing equal to at least the width of the door should be provided in the stairway at each doorway ; the level of landing should be the same as that of the floor which it serves..  Exit doorways should be openable from the side which they serve without the use of a key.
  • 15. Revolving doors-  Revolving doors should not be used as required exits except in residential, business and mercantile occupancies but should not constitute more than half the total required door width. In mercantile buildings where there is possibility of congregation of a large number of people (more than 200), revolving doors should not be permitted.  Where the revolving door provided are completely made of glass (plate glass), a red circle or emblem or logo at 1·5 m level above sill should be painted on the glass. The thickness of the glass should not be not less than 12 mm. Corridors and Passageways-  Exit corridors and passageways should be of width not less than the aggregate required width of exit doorways leading from them in the direction of travel to the exterior.  Where stairways discharge through corridors and passageways, the height of corridors and passageways should be not less than 2·4 m.