SlideShare a Scribd company logo
Backup fault protection for
generators in case of a
failure at the generation
station
By Edvard | December, 4th 2019 | 0 comments | Save to PDF
Share!
Home / Technical Articles / Backup fault protection for generators in case of a failure at the generation station
The purpose of generator backup
protection
It is a common practice to use the differential relay as primary fault protection
for the generator. Backup fault protection is also highly recommended to protect
the generator from the effects of faults that are not cleared because of failures
within the normal protection scheme. The backup relaying is automatically
applied to provide protection in the event of a failure at the generation station,
on the transmission system, or both.
Backup fault protection for generators in case of a failure at the generation
station
Specific generating station failures would include the failure of the generator or
Generator Step Up (GSU) transformer differential scheme. On the transmission
system, failures would include the line protection relay scheme or the failure of
a line breaker to interrupt.
Table of contents:
1. Implementation of backup fault protection
2. Standard overcurrent relays
3. Voltage-dependent relays
4. Voltage supervised overcurrent relays
1. Voltage-controlled and voltage-restrained relays
2. Application options and fault sensitivity
5. Other distance relay applications
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">
1. Implementation of backup fault
protection
Figure 1 shows the sample system generator. Backup protection is provided by
distance relays (Device 21) or voltage supervised overcurrent relays (Device
51V). These relays can be connected to CTs at the neutral end of the generator
or they can be connected to CTs at the generator terminals.
The neutral end configuration is preferred because this connection will allow the
relaying to provide protection when the unit is off line. Terminal connected
relays will not see internal generator faults for this condition, because there is
no relay current.
If the scheme is intended to provide backup protection for both generating
station and system faults, the backup relays should initiate a unit shutdown.
This entails tripping the breaker on the high-voltage side of the GSU, the
generator field breaker, the auxiliary transformer breakers and initiating a prime
mover shutdown.
If the station configuration included a generator breaker it would be tripped
instead of the high-voltage breaker.
When relays are applied solely to backup transmission line relaying, only the
GSU transformer or generator breaker need be tripped. This would allow a
faster resynchronizing after the failure has been isolated. This assumes the unit
can withstand the effects of the full load rejection that will occur when the outlet
breaker opens.
If the unit cannot withstand this transient, a unit shutdown must be initiated.
Figure 1 – Generator online protection scheme
Go back to Contents Table ↑
2. Standard Overcurrent Relays
Standard overcurrent relays are not recommended for backup protection of a
generator. The backup relay must be capable of detecting the minimum
generator fault current. This minimum current is the sustained current
following a three-phase fault assuming no initial load on the generator and
assuming the manual voltage regulator in service.
If the automatic voltage regulator where service, it would respond to the fault-
induced low terminal voltage and boost the field current, thus increasing the
fault current. The assumption of no initial load on the generator defines the
minimum field current to drive the fault.
Typically, a generator’s synchronous reactance, which controls the value of the
sustained fault current, is greater than unity. If the generator is unloaded and
at rated terminal voltage (Et = 1.0) prior to the fault, the sustained short-circuit
current will be 1/Xd which will be less than full load current. In the case of the
sample system generator Xd = 1.48 and the resulting sustained three-phase
fault current would be 0.67 pu or 67% of full load current.
A standard overcurrent relay must be set above load and could not detect the
minimum sustained fault current. Tripping would be dependent on rapid relay
operation before the fault current decays below the relay’s pickup setting.
Figure 2 plots the decaying current for the minimum fault condition on the
sample system generator vs. an overcurrent relay set to carry full load. The
figure shows that the relay must be set with a very short time delay (Time Dial
= 1/4) to intersect the current plot to assure tripping.
This fast tripping is undesirable, because it would preclude coordination
with system relays and could cause misoperation during system
disturbances that do not require protective action.
Figure 2 – Fault clearing
with overcurrent relay
Go back to Contents Table ↑
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 250px; width: 300px; display: block;">
3. Voltage-Dependent relays
The problems associated with standard overcurrent protection can be
overcome if fault detection is based on current and voltage. At full load, the
generator terminal voltage will be near rated voltage. Under sustained three-
phase fault conditions, the internal generator impedance will increase to the
synchronous value and the terminal voltage will decrease sharply.
Both distance relays and voltage supervised overcurrent relays use the voltage
degradation to differentiate between load current and a sustained fault
current condition. Because of this design, these backup relays are supervised
by a potential failure detection element, device 60. This element blocks tripping
in the event of an open phase or blown fuse in the potential circuit.
Without this blocking feature, these instrument circuit malfunctions would trip
the fully loaded unit.
The decision to use a 21 or a 51 V function as backup protection is normally
dependent on the type of phase protection applied on the transmission or
distribution system to which the generator is connected.
Distance backup protection is chosen if phase distance relaying is applied
on the transmission system. A 51 V function is chosen if overcurrent relays
are used for phase protection on the connected system. These choices are
made to facilitate relay coordination.
Go back to Contents Table ↑
4. Voltage Supervised Overcurrent
Relays
4.1 Voltage-controlled And Voltage-
restrained Relays
There are two kinds of voltage-supervised overcurrent relays used in generator
backup applications. The voltage-restrained overcurrent relay is normally set
125–175% of full load current. The relay uses voltage input from the
generator terminals to bias the overcurrent setpoint.
At rated voltage, a current equal to the setpoint is required to actuate the relay.
As input voltage decreases, presumably
due to a short circuit, the overcurrent setpoint also decreases. Typically a
current equal to 25% of the setpoint is require to operate the relay at zero volts
input.
Figure 3 is a typical pickup characteristic for a voltage-restrained relay.
The voltage-controlled relay is set below full load with sufficient margin to
detect the minimum fault current. The relay includes an undervoltage
element that senses generator terminal voltage. If the voltage is above the
undervoltage element setting, the overcurrent unit is not functional.
When voltage is depressed by a fault, the undervoltage element drops out,
allowing the relay to operate as a standard overcurrent relay in accordance with
its pickup and time delay settings.
Figure 3 –
Voltage-restrained overcurrent relay characteristic
The voltage-restrained relay is more difficult to apply because operating time is
a function of both current and voltage.
The voltage-restrained relay has two adjustable setpoints, a voltage-dependent
minimum pickup current, and a time delay setting. The voltage-controlled relay
has a voltage-independent current pickup setting, a time delay setting, and an
undervoltage drop out setting.
Go back to Contents Table ↑
4.2 Application Options and Fault
Sensitivity
Voltage-supervised overcurrent relays allow many input options. The 51 V
function comprises three single-phase units. The current and voltage
connections are not standardized. Phase-to-neutral or phase-to-phase voltages
can be applied in conjunction with line or delta currents.
There is also the option of voltage-controlled or voltage-restrained relays.
Go back to Contents Table ↑
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 0px; width: 300px; display: block;">
5. Distance Relays
The term distance relays refers to a general class of relays that measure circuit
impedance. The relay distinguishes between fault current and load current in
a manner similar to the 51 V functions. The voltage applied to the distance
relay tends to restrain operation, while current promotes operation.
Both phase and ground distance relays are applied on the transmission system.
Unique relay designs are required for phase and ground fault protection.
There are many different algorithms used in these relays, but in all cases the
common goal is to measure the positive sequence impedance from the
relay to the fault. When full fault protection is provided by distance relaying, six
elements are required, phase elements A–B, B–C, C–A and ground elements
A–G, B–G, and C–G.
Phase distance relays are applied at generators for system backup
protection. Ground distance relays are not applied. Most generators are
grounded through impedance to limit the ground fault current. Specialized
ground fault protection schemes are required.
When a generator is solidly grounded and connected to a distribution system
directly or through a wye-wye transformer, overcurrent ground relays
provide superior fault sensitivity and economy when compared to ground
distance relays. Overcurrent ground relaying is applicable because generator
ground faults do not decay to values less than full load current and ground
overcurrent relays are not subject to setting limitations due to load current.
Likewise, when a generator is connected to a system through a delta-wye
grounded transformer, backup ground protection is usually provided by a time
overcurrent ground relay connected in the transformer neutral.
For example, SEL-700G protection relay offers three choices for system backup
protection. You can select one or more of the available elements:
 Distance (DC),
 Voltage Restraint (V), or
 Voltage Controlled (C) Overcurrent elements.
Modern protective relays provide four zones of phase step distance protection.
Functions are positive sequence voltage polarized mho characteristics. The
reach of the three forward looking zones can be compensated for a delta-wye
transformer.
Zone 4 is reversed and disregards any transformer between the relay and the
fault in the forward direction. Zones 1, 2, 3, and 4 each include independent
timers for phase step distance protection.
Out-of-step blocking monitors swing condition and blocks tripping. Out-of-step
tripping logic is provided with a choice of two or three mho type characteristics
with adjustable shapes.
Forward and reverse share a common maximum reach angle. Loss of
synchronism or a power swing between two areas of the power system is
detected by measuring the positive sequence impedance seen by the relay over
a period of time as the power swing develops.
Figure 4 – Generator
protection relay SEL-700 functionalscheme
Go back to Contents Table ↑
5.1 Other Distance Relay Applications
Other applications of the 21 function are also possible. Phase distance relaying
can be connected to CTs at the generator terminals with the 21 function
connected to look into the generator instead of the system. This relay can be
applied without a time delay to provide fast backup clearing for generator
faults when connected to the system.
Many generator protection microprocessor packages include two phase
distance relay functions. One zone can be implemented with a short reach and
a short time delay sufficient to coordinate with high-speed bus and line
relaying plus breaker failure time if applicable. The second zone is then set to
see into the transmission system with a delay sufficient to coordinate with zone
2 line relaying and applicable breaker failure time.
This scheme can provides 0.3 sec clearing for high current faults in the
vicinity of the generator as opposed to the single zone scheme that would
require a delay of about a second to coordinate with zone 2 and breaker failure
relaying.
Go back to Contents Table ↑
Sources:
1. Protective relaying for power generation systems by Donald Reimert
2. SEL-700G Generator Protection Relay by SEL
3. LPS-O System backup for generators and transmission lines by GE

More Related Content

What's hot

Overcurrent Protection
Overcurrent ProtectionOvercurrent Protection
Overcurrent Protection
Mohammad Zishan Alam
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
Power System Operation
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
siddharam kantoli
 
Over current protection
Over current protectionOver current protection
Over current protection
SHUBHAM KUMAR
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
Biswajit Pratihari
 
Functions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsFunctions and performance requirements of excitation systems
Functions and performance requirements of excitation systems
Rajshekar Naregal
 
Ge generator and ups problems
Ge generator and ups problemsGe generator and ups problems
Ge generator and ups problems
michaeljmack
 
Electrical Power Protection & Relay Coordination Engineering
Electrical Power Protection & Relay Coordination EngineeringElectrical Power Protection & Relay Coordination Engineering
Electrical Power Protection & Relay Coordination Engineering
DEVELOP
 
Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principles
Ammar Al Hakeim
 
1 transmission
1 transmission1 transmission
1 transmission
pradhuman deolia
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
Rishi Tandon
 
C0212014018
C0212014018C0212014018
C0212014018
theijes
 
See4423 chapter1 introduction[1]
See4423 chapter1 introduction[1]See4423 chapter1 introduction[1]
See4423 chapter1 introduction[1]
mdshahmajid
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
Bhushan Kumbhalkar
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
Power System Operation
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
Md Irshad Ahmad
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
kishore kish
 
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENTRADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
Himanshu Paghdal
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
PremanandDesai
 

What's hot (20)

Overcurrent Protection
Overcurrent ProtectionOvercurrent Protection
Overcurrent Protection
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Over current protection
Over current protectionOver current protection
Over current protection
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Functions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsFunctions and performance requirements of excitation systems
Functions and performance requirements of excitation systems
 
Ge generator and ups problems
Ge generator and ups problemsGe generator and ups problems
Ge generator and ups problems
 
Electrical Power Protection & Relay Coordination Engineering
Electrical Power Protection & Relay Coordination EngineeringElectrical Power Protection & Relay Coordination Engineering
Electrical Power Protection & Relay Coordination Engineering
 
Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principles
 
1 transmission
1 transmission1 transmission
1 transmission
 
Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
 
C0212014018
C0212014018C0212014018
C0212014018
 
See4423 chapter1 introduction[1]
See4423 chapter1 introduction[1]See4423 chapter1 introduction[1]
See4423 chapter1 introduction[1]
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENTRADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 

Similar to Backup fault protection for generators in case of a failure at the generation station

Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
Ronald Santos
 
Generator protection
Generator protectionGenerator protection
Generator protection
Keshar Rawal
 
Generator protection
Generator protectionGenerator protection
Generator protection
Parimal Bhagat
 
Protective relay.pptx
Protective relay.pptxProtective relay.pptx
Protective relay.pptx
BudhadityaBiswas5
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
Rahaf Waheep
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
javid iqbal sodagar
 
Relays
RelaysRelays
Relays
Ameen San
 
General electric
General electricGeneral electric
General electric
Carlos Rodriguez
 
Power system operation and control
Power system operation and controlPower system operation and control
Power system operation and control
venkata suresh kumar lagudu
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
IRJET Journal
 
Lecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 convertedLecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 converted
Fazal Ur Rehman
 
Notes1 intro
Notes1 introNotes1 intro
Notes1 intro
Dr. Chetan Kotwal
 
Iaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvrIaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvr
Iaetsd Iaetsd
 
D04522631
D04522631D04522631
D04522631
IOSR-JEN
 
Fy3610821086
Fy3610821086Fy3610821086
Fy3610821086
IJERA Editor
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
Samuel Okhuegbe
 
Presentation1.pptx power system
Presentation1.pptx power systemPresentation1.pptx power system
Presentation1.pptx power system
Arvind Nathan
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
AshaLatha456489
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
javid iqbal sodagar
 

Similar to Backup fault protection for generators in case of a failure at the generation station (20)

Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Protective relay.pptx
Protective relay.pptxProtective relay.pptx
Protective relay.pptx
 
Generator protection LEC 2
Generator protection  LEC 2Generator protection  LEC 2
Generator protection LEC 2
 
Major faults in an alternator and their protection.
Major faults in an alternator and their protection.Major faults in an alternator and their protection.
Major faults in an alternator and their protection.
 
Relays
RelaysRelays
Relays
 
General electric
General electricGeneral electric
General electric
 
Power system operation and control
Power system operation and controlPower system operation and control
Power system operation and control
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
 
Lecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 convertedLecture no 1 switchgears bt255 converted
Lecture no 1 switchgears bt255 converted
 
Notes1 intro
Notes1 introNotes1 intro
Notes1 intro
 
Iaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvrIaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvr
 
D04522631
D04522631D04522631
D04522631
 
Fy3610821086
Fy3610821086Fy3610821086
Fy3610821086
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
Presentation1.pptx power system
Presentation1.pptx power systemPresentation1.pptx power system
Presentation1.pptx power system
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 
Protection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagarProtection of alternators javid iqbal sodagar
Protection of alternators javid iqbal sodagar
 

Recently uploaded

How to Create a More Engaging and Human Online Learning Experience
How to Create a More Engaging and Human Online Learning Experience How to Create a More Engaging and Human Online Learning Experience
How to Create a More Engaging and Human Online Learning Experience
Wahiba Chair Training & Consulting
 
BBR 2024 Summer Sessions Interview Training
BBR  2024 Summer Sessions Interview TrainingBBR  2024 Summer Sessions Interview Training
BBR 2024 Summer Sessions Interview Training
Katrina Pritchard
 
South African Journal of Science: Writing with integrity workshop (2024)
South African Journal of Science: Writing with integrity workshop (2024)South African Journal of Science: Writing with integrity workshop (2024)
South African Journal of Science: Writing with integrity workshop (2024)
Academy of Science of South Africa
 
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptxNEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
iammrhaywood
 
Advanced Java[Extra Concepts, Not Difficult].docx
Advanced Java[Extra Concepts, Not Difficult].docxAdvanced Java[Extra Concepts, Not Difficult].docx
Advanced Java[Extra Concepts, Not Difficult].docx
adhitya5119
 
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
สมใจ จันสุกสี
 
clinical examination of hip joint (1).pdf
clinical examination of hip joint (1).pdfclinical examination of hip joint (1).pdf
clinical examination of hip joint (1).pdf
Priyankaranawat4
 
The Diamonds of 2023-2024 in the IGRA collection
The Diamonds of 2023-2024 in the IGRA collectionThe Diamonds of 2023-2024 in the IGRA collection
The Diamonds of 2023-2024 in the IGRA collection
Israel Genealogy Research Association
 
spot a liar (Haiqa 146).pptx Technical writhing and presentation skills
spot a liar (Haiqa 146).pptx Technical writhing and presentation skillsspot a liar (Haiqa 146).pptx Technical writhing and presentation skills
spot a liar (Haiqa 146).pptx Technical writhing and presentation skills
haiqairshad
 
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
imrankhan141184
 
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptxC1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
mulvey2
 
MARY JANE WILSON, A “BOA MÃE” .
MARY JANE WILSON, A “BOA MÃE”           .MARY JANE WILSON, A “BOA MÃE”           .
MARY JANE WILSON, A “BOA MÃE” .
Colégio Santa Teresinha
 
Cognitive Development Adolescence Psychology
Cognitive Development Adolescence PsychologyCognitive Development Adolescence Psychology
Cognitive Development Adolescence Psychology
paigestewart1632
 
writing about opinions about Australia the movie
writing about opinions about Australia the moviewriting about opinions about Australia the movie
writing about opinions about Australia the movie
Nicholas Montgomery
 
Chapter wise All Notes of First year Basic Civil Engineering.pptx
Chapter wise All Notes of First year Basic Civil Engineering.pptxChapter wise All Notes of First year Basic Civil Engineering.pptx
Chapter wise All Notes of First year Basic Civil Engineering.pptx
Denish Jangid
 
How to Fix the Import Error in the Odoo 17
How to Fix the Import Error in the Odoo 17How to Fix the Import Error in the Odoo 17
How to Fix the Import Error in the Odoo 17
Celine George
 
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdfবাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
eBook.com.bd (প্রয়োজনীয় বাংলা বই)
 
Wound healing PPT
Wound healing PPTWound healing PPT
Wound healing PPT
Jyoti Chand
 
Hindi varnamala | hindi alphabet PPT.pdf
Hindi varnamala | hindi alphabet PPT.pdfHindi varnamala | hindi alphabet PPT.pdf
Hindi varnamala | hindi alphabet PPT.pdf
Dr. Mulla Adam Ali
 
How to Make a Field Mandatory in Odoo 17
How to Make a Field Mandatory in Odoo 17How to Make a Field Mandatory in Odoo 17
How to Make a Field Mandatory in Odoo 17
Celine George
 

Recently uploaded (20)

How to Create a More Engaging and Human Online Learning Experience
How to Create a More Engaging and Human Online Learning Experience How to Create a More Engaging and Human Online Learning Experience
How to Create a More Engaging and Human Online Learning Experience
 
BBR 2024 Summer Sessions Interview Training
BBR  2024 Summer Sessions Interview TrainingBBR  2024 Summer Sessions Interview Training
BBR 2024 Summer Sessions Interview Training
 
South African Journal of Science: Writing with integrity workshop (2024)
South African Journal of Science: Writing with integrity workshop (2024)South African Journal of Science: Writing with integrity workshop (2024)
South African Journal of Science: Writing with integrity workshop (2024)
 
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptxNEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
NEWSPAPERS - QUESTION 1 - REVISION POWERPOINT.pptx
 
Advanced Java[Extra Concepts, Not Difficult].docx
Advanced Java[Extra Concepts, Not Difficult].docxAdvanced Java[Extra Concepts, Not Difficult].docx
Advanced Java[Extra Concepts, Not Difficult].docx
 
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
คำศัพท์ คำพื้นฐานการอ่าน ภาษาอังกฤษ ระดับชั้น ม.1
 
clinical examination of hip joint (1).pdf
clinical examination of hip joint (1).pdfclinical examination of hip joint (1).pdf
clinical examination of hip joint (1).pdf
 
The Diamonds of 2023-2024 in the IGRA collection
The Diamonds of 2023-2024 in the IGRA collectionThe Diamonds of 2023-2024 in the IGRA collection
The Diamonds of 2023-2024 in the IGRA collection
 
spot a liar (Haiqa 146).pptx Technical writhing and presentation skills
spot a liar (Haiqa 146).pptx Technical writhing and presentation skillsspot a liar (Haiqa 146).pptx Technical writhing and presentation skills
spot a liar (Haiqa 146).pptx Technical writhing and presentation skills
 
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
Traditional Musical Instruments of Arunachal Pradesh and Uttar Pradesh - RAYH...
 
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptxC1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
C1 Rubenstein AP HuG xxxxxxxxxxxxxx.pptx
 
MARY JANE WILSON, A “BOA MÃE” .
MARY JANE WILSON, A “BOA MÃE”           .MARY JANE WILSON, A “BOA MÃE”           .
MARY JANE WILSON, A “BOA MÃE” .
 
Cognitive Development Adolescence Psychology
Cognitive Development Adolescence PsychologyCognitive Development Adolescence Psychology
Cognitive Development Adolescence Psychology
 
writing about opinions about Australia the movie
writing about opinions about Australia the moviewriting about opinions about Australia the movie
writing about opinions about Australia the movie
 
Chapter wise All Notes of First year Basic Civil Engineering.pptx
Chapter wise All Notes of First year Basic Civil Engineering.pptxChapter wise All Notes of First year Basic Civil Engineering.pptx
Chapter wise All Notes of First year Basic Civil Engineering.pptx
 
How to Fix the Import Error in the Odoo 17
How to Fix the Import Error in the Odoo 17How to Fix the Import Error in the Odoo 17
How to Fix the Import Error in the Odoo 17
 
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdfবাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
বাংলাদেশ অর্থনৈতিক সমীক্ষা (Economic Review) ২০২৪ UJS App.pdf
 
Wound healing PPT
Wound healing PPTWound healing PPT
Wound healing PPT
 
Hindi varnamala | hindi alphabet PPT.pdf
Hindi varnamala | hindi alphabet PPT.pdfHindi varnamala | hindi alphabet PPT.pdf
Hindi varnamala | hindi alphabet PPT.pdf
 
How to Make a Field Mandatory in Odoo 17
How to Make a Field Mandatory in Odoo 17How to Make a Field Mandatory in Odoo 17
How to Make a Field Mandatory in Odoo 17
 

Backup fault protection for generators in case of a failure at the generation station

  • 1. Backup fault protection for generators in case of a failure at the generation station By Edvard | December, 4th 2019 | 0 comments | Save to PDF Share! Home / Technical Articles / Backup fault protection for generators in case of a failure at the generation station The purpose of generator backup protection It is a common practice to use the differential relay as primary fault protection for the generator. Backup fault protection is also highly recommended to protect the generator from the effects of faults that are not cleared because of failures within the normal protection scheme. The backup relaying is automatically applied to provide protection in the event of a failure at the generation station, on the transmission system, or both.
  • 2. Backup fault protection for generators in case of a failure at the generation station Specific generating station failures would include the failure of the generator or Generator Step Up (GSU) transformer differential scheme. On the transmission
  • 3. system, failures would include the line protection relay scheme or the failure of a line breaker to interrupt. Table of contents: 1. Implementation of backup fault protection 2. Standard overcurrent relays 3. Voltage-dependent relays 4. Voltage supervised overcurrent relays 1. Voltage-controlled and voltage-restrained relays 2. Application options and fault sensitivity 5. Other distance relay applications <="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box; height: 250px; width: 300px; display: block;"> 1. Implementation of backup fault protection Figure 1 shows the sample system generator. Backup protection is provided by distance relays (Device 21) or voltage supervised overcurrent relays (Device 51V). These relays can be connected to CTs at the neutral end of the generator or they can be connected to CTs at the generator terminals. The neutral end configuration is preferred because this connection will allow the relaying to provide protection when the unit is off line. Terminal connected relays will not see internal generator faults for this condition, because there is no relay current. If the scheme is intended to provide backup protection for both generating station and system faults, the backup relays should initiate a unit shutdown. This entails tripping the breaker on the high-voltage side of the GSU, the generator field breaker, the auxiliary transformer breakers and initiating a prime mover shutdown. If the station configuration included a generator breaker it would be tripped instead of the high-voltage breaker. When relays are applied solely to backup transmission line relaying, only the GSU transformer or generator breaker need be tripped. This would allow a faster resynchronizing after the failure has been isolated. This assumes the unit
  • 4. can withstand the effects of the full load rejection that will occur when the outlet breaker opens. If the unit cannot withstand this transient, a unit shutdown must be initiated. Figure 1 – Generator online protection scheme
  • 5. Go back to Contents Table ↑ 2. Standard Overcurrent Relays Standard overcurrent relays are not recommended for backup protection of a generator. The backup relay must be capable of detecting the minimum generator fault current. This minimum current is the sustained current following a three-phase fault assuming no initial load on the generator and assuming the manual voltage regulator in service. If the automatic voltage regulator where service, it would respond to the fault- induced low terminal voltage and boost the field current, thus increasing the fault current. The assumption of no initial load on the generator defines the minimum field current to drive the fault. Typically, a generator’s synchronous reactance, which controls the value of the sustained fault current, is greater than unity. If the generator is unloaded and at rated terminal voltage (Et = 1.0) prior to the fault, the sustained short-circuit current will be 1/Xd which will be less than full load current. In the case of the sample system generator Xd = 1.48 and the resulting sustained three-phase fault current would be 0.67 pu or 67% of full load current. A standard overcurrent relay must be set above load and could not detect the minimum sustained fault current. Tripping would be dependent on rapid relay operation before the fault current decays below the relay’s pickup setting. Figure 2 plots the decaying current for the minimum fault condition on the sample system generator vs. an overcurrent relay set to carry full load. The figure shows that the relay must be set with a very short time delay (Time Dial = 1/4) to intersect the current plot to assure tripping. This fast tripping is undesirable, because it would preclude coordination with system relays and could cause misoperation during system disturbances that do not require protective action.
  • 6. Figure 2 – Fault clearing with overcurrent relay Go back to Contents Table ↑ <="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box; height: 250px; width: 300px; display: block;"> 3. Voltage-Dependent relays The problems associated with standard overcurrent protection can be overcome if fault detection is based on current and voltage. At full load, the generator terminal voltage will be near rated voltage. Under sustained three- phase fault conditions, the internal generator impedance will increase to the synchronous value and the terminal voltage will decrease sharply. Both distance relays and voltage supervised overcurrent relays use the voltage degradation to differentiate between load current and a sustained fault
  • 7. current condition. Because of this design, these backup relays are supervised by a potential failure detection element, device 60. This element blocks tripping in the event of an open phase or blown fuse in the potential circuit. Without this blocking feature, these instrument circuit malfunctions would trip the fully loaded unit. The decision to use a 21 or a 51 V function as backup protection is normally dependent on the type of phase protection applied on the transmission or distribution system to which the generator is connected. Distance backup protection is chosen if phase distance relaying is applied on the transmission system. A 51 V function is chosen if overcurrent relays are used for phase protection on the connected system. These choices are made to facilitate relay coordination. Go back to Contents Table ↑ 4. Voltage Supervised Overcurrent Relays 4.1 Voltage-controlled And Voltage- restrained Relays There are two kinds of voltage-supervised overcurrent relays used in generator backup applications. The voltage-restrained overcurrent relay is normally set 125–175% of full load current. The relay uses voltage input from the generator terminals to bias the overcurrent setpoint. At rated voltage, a current equal to the setpoint is required to actuate the relay. As input voltage decreases, presumably due to a short circuit, the overcurrent setpoint also decreases. Typically a current equal to 25% of the setpoint is require to operate the relay at zero volts input. Figure 3 is a typical pickup characteristic for a voltage-restrained relay.
  • 8. The voltage-controlled relay is set below full load with sufficient margin to detect the minimum fault current. The relay includes an undervoltage element that senses generator terminal voltage. If the voltage is above the undervoltage element setting, the overcurrent unit is not functional. When voltage is depressed by a fault, the undervoltage element drops out, allowing the relay to operate as a standard overcurrent relay in accordance with its pickup and time delay settings. Figure 3 – Voltage-restrained overcurrent relay characteristic The voltage-restrained relay is more difficult to apply because operating time is a function of both current and voltage. The voltage-restrained relay has two adjustable setpoints, a voltage-dependent minimum pickup current, and a time delay setting. The voltage-controlled relay has a voltage-independent current pickup setting, a time delay setting, and an undervoltage drop out setting. Go back to Contents Table ↑
  • 9. 4.2 Application Options and Fault Sensitivity Voltage-supervised overcurrent relays allow many input options. The 51 V function comprises three single-phase units. The current and voltage connections are not standardized. Phase-to-neutral or phase-to-phase voltages can be applied in conjunction with line or delta currents. There is also the option of voltage-controlled or voltage-restrained relays. Go back to Contents Table ↑ <="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box; height: 0px; width: 300px; display: block;"> 5. Distance Relays The term distance relays refers to a general class of relays that measure circuit impedance. The relay distinguishes between fault current and load current in a manner similar to the 51 V functions. The voltage applied to the distance relay tends to restrain operation, while current promotes operation. Both phase and ground distance relays are applied on the transmission system. Unique relay designs are required for phase and ground fault protection. There are many different algorithms used in these relays, but in all cases the common goal is to measure the positive sequence impedance from the relay to the fault. When full fault protection is provided by distance relaying, six elements are required, phase elements A–B, B–C, C–A and ground elements A–G, B–G, and C–G. Phase distance relays are applied at generators for system backup protection. Ground distance relays are not applied. Most generators are grounded through impedance to limit the ground fault current. Specialized ground fault protection schemes are required. When a generator is solidly grounded and connected to a distribution system directly or through a wye-wye transformer, overcurrent ground relays provide superior fault sensitivity and economy when compared to ground
  • 10. distance relays. Overcurrent ground relaying is applicable because generator ground faults do not decay to values less than full load current and ground overcurrent relays are not subject to setting limitations due to load current. Likewise, when a generator is connected to a system through a delta-wye grounded transformer, backup ground protection is usually provided by a time overcurrent ground relay connected in the transformer neutral. For example, SEL-700G protection relay offers three choices for system backup protection. You can select one or more of the available elements:  Distance (DC),  Voltage Restraint (V), or  Voltage Controlled (C) Overcurrent elements. Modern protective relays provide four zones of phase step distance protection. Functions are positive sequence voltage polarized mho characteristics. The reach of the three forward looking zones can be compensated for a delta-wye transformer. Zone 4 is reversed and disregards any transformer between the relay and the fault in the forward direction. Zones 1, 2, 3, and 4 each include independent timers for phase step distance protection. Out-of-step blocking monitors swing condition and blocks tripping. Out-of-step tripping logic is provided with a choice of two or three mho type characteristics with adjustable shapes. Forward and reverse share a common maximum reach angle. Loss of synchronism or a power swing between two areas of the power system is detected by measuring the positive sequence impedance seen by the relay over a period of time as the power swing develops.
  • 11. Figure 4 – Generator protection relay SEL-700 functionalscheme Go back to Contents Table ↑ 5.1 Other Distance Relay Applications Other applications of the 21 function are also possible. Phase distance relaying can be connected to CTs at the generator terminals with the 21 function connected to look into the generator instead of the system. This relay can be applied without a time delay to provide fast backup clearing for generator faults when connected to the system.
  • 12. Many generator protection microprocessor packages include two phase distance relay functions. One zone can be implemented with a short reach and a short time delay sufficient to coordinate with high-speed bus and line relaying plus breaker failure time if applicable. The second zone is then set to see into the transmission system with a delay sufficient to coordinate with zone 2 line relaying and applicable breaker failure time. This scheme can provides 0.3 sec clearing for high current faults in the vicinity of the generator as opposed to the single zone scheme that would require a delay of about a second to coordinate with zone 2 and breaker failure relaying. Go back to Contents Table ↑ Sources: 1. Protective relaying for power generation systems by Donald Reimert 2. SEL-700G Generator Protection Relay by SEL 3. LPS-O System backup for generators and transmission lines by GE