Improving Your PUE While Consolidating Into
An Existing Live Data Center
Jay Owen
VP, IT Federal Solutions
Tweet Live!
#SchneiderXE
2
Objectives
Upon Completion of this course, you will be able to
● Identify the percentage of commercial data center operators that plan to
use co-location or cloud to meet future data center requirements
● Identify three reasons why a new data center is built
● Identify three reasons why an existing data center is upgraded
● Identify four consolidation options
● Identify the typical range of IT cabinets in a pod
● Identify attributes of a high-density pod
● Typical PUE
● Rack densities
● Raised floor requirements
● Options
● Benefits
3
Consolidation options
●Move IT to the cloud
●Move IT to Co-Location
●Build new larger data centers and consolidate
into them
●Upgrade selected existing data centers and
consolidate into them
What are commercial customers doing, and why?
4
Moving IT to cloud or co-location
● Only 50% of commercial data center operators plan to use co-
location or cloud to meet future data center requirements*
(remainder to be met with in-house data centers)
● Rarely is an entire data center moved to cloud or co-location
● Moves to cloud or co-location often free up capacity across
existing data centers, increasing the need to consolidate
● Uncertainty regarding use of cloud increases the risk of building
new data centers
*Survey by 451 group, presented at the Uptime Symposium, May 2012
Moves to cloud and co-location do not decrease the need to
consolidate, but actually increase this need
5
Typical concept: Build new data center
and consolidate into it
● When the goal is to consolidate a large number of data centers
into a single very large data center (~20 MW)
● A large capital project is feasible (~$400 M)
● High rate of IT growth is anticipated
● When the stock of existing data centers is considered hopelessly
ineffective (space, energy efficiency, power density)
● When there is a commonality of IT functions across the data
centers
● When the consolidation can be forced top-down in the organization
● When harmonized standards can be imposed across all of the IT
systems
6
New concept: Upgrade selected existing
data centers and consolidate into them
● Appropriate when consolidating 2-5 data centers into one
● When some of the existing IT is moving to the cloud or co-location
● Much lower capital investment
● No new real estate acquisition
● Consolidation projects are not organization-wide but are operated
within independent departments
● Can be phased to match IT refreshes
● Can be done while receiving data center is live
7
Example of a High Density Pod
Two Pod installation at US Army Fort Bliss
8
The High-Density Pod Overlay Method
● Method for upgrading existing data centers
● Self-contained “Pods” of data center infrastructure are placed in
existing data center space
● Pod size typically 10-20 cabinets
● Typically includes integrated air conditioning and power distribution
● Optionally contains integrated UPS
● Pods operate with superior performance
● Much higher energy efficiency (typical PUE less than 1.4)
● Much higher power density (up to 20 KW per cabinet)
● Pod does not need to rely on existing infrastructure
● Does not require raised floor
● Does not require air supply
9
Example of a Consolidation Project Using Pods
presented by SUN at data center dynamics, July 2008
10
Clear out a corner of the data center to
get started
11
Consolidation of a typical portfolio
Spec
Data
Center
A
Data
Center
B
Data
Center
C
Starting
Total
Rated KW 500 KW 700 KW 250 KW 1450 KW
Actual KW 260 KW 220 KW 160 KW 640 KW
% KW
Utilized
52% 31% 64% 44%
Ave KW
per
cabinet
3.0 KW 3.4 KW 3.5 KW 3.3 KW
PUE 2.2 2.2 2.1 2.2
Square
Feet
8,300 7,800 4,200 20,300
% Space
Utilized
29% 23% 31% 27%
Annual
Energy $
$600,000 $510,000 $350,000 $1,460,000
12
Assumptions
● Data Center B chosen as receiving data center
● Assume none of the current load will go to the cloud or be reduced
by virtualization
● At final condition Data Center B has been converted to Pods over
time
13
Consolidation of a typical portfolio
Spec
Data
Center
A
Data
Center
B
Data
Center
C
Starting
Total
Final
Total
Rated KW 500 KW 700 KW 250 KW 1450 KW 700 KW
Actual KW 260 KW 640 KW 160 KW 640 KW 640 KW
% KW
Utilized
52% 91% 64% 44% 91%
Ave KW
per
cabinet
3.0 KW 6.0 KW 3.5 KW 3.3 KW 6.0 KW
PUE 2.2 1.6 2.1 2.2 1.6
Square
Feet
8,300 7,800 4,200 20,300 7,800
% Space
Utilized
29% 38% 31% 27% 38%
Annual
Energy $
$600,000 $1,075,000 $350,000 $1,460,000 $1,075,000
14
Results of the example
● Energy use reduced 26%, even though the IT load stayed constant
● The receiving data center has only 38% space utilization after
consolidation! (space compaction due to increased density)
● 60% of the original data center space was freed up for other
purposes!
● The target receiving data center was NOT the one with the most
square feet or the best PUE
These are typical results we see in commercial installations
15
PUE contribution of cooling losses:
Traditional vs. superior data centre
1.9
0.1
0.03
0.08
0.03
0.04
0.17
0.07
0.06 1.32
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
16
PUE contribution of cooling losses:
Traditional vs. superior data centre
1.9
0.1
0.03
0.08
0.03
0.04
0.17
0.07
0.06 1.32
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
Traditional
raised-floor cooling is
responsible for most of
the energy inefficiency
High Density Pods eliminate most of the inefficiency of a
traditional data center
17
Capacity extension of maxed out data centers
Power and cooling facility
modules are added to
expand power capacity
Modular IT space is added
along with power and
cooling modules
1
2
Power, cooling, and space can be added to live data centers
in the future
18
Retrofitting a live data center requires
special skills
19
Conclusions
● Moving IT to the cloud or co-location increases
the need to consolidate internal data centers
● You don’t need to build new data centers to be
receiving data centers
● It is common in industry to consolidate a
number of data centers into an existing live
data center
● The High Density Pod Overlay Method is a
very effective technique for upgrading data
centers as part of a consolidation project
20
Resources
Containerized Power and Cooling Modules for Data
Centers
Schneider Electric White Paper 163
Deploying High-Density Pods in a Low Density Data Center
Schneider Electric White Paper 134
Preparing the Physical Infrastructure of Receiving Data
Centers for Consolidation
Schneider Electric White Paper 175
Determining the Power, Cooling, and Space Capacities when
Consolidating Data Centers
Schneider Electric White Paper 177
download:
Whitepapers.apc.com
ipad appstore: “Schneider electric white papers” free application

More Related Content

What's hot

Distributech 2015 - Mobile Work management
Distributech 2015 - Mobile Work managementDistributech 2015 - Mobile Work management
Distributech 2015 - Mobile Work management
Schneider Electric
 
Microgrid & renewable integration at burbank water & power
Microgrid & renewable integration at burbank water & powerMicrogrid & renewable integration at burbank water & power
Microgrid & renewable integration at burbank water & power
Schneider Electric
 
Practical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data CentersPractical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data Centers
Schneider Electric
 
Data centers on the Edge
Data centers on the EdgeData centers on the Edge
Data centers on the Edge
Schneider Electric
 
Underground Self-Healing Solution
Underground Self-Healing Solution Underground Self-Healing Solution
Underground Self-Healing Solution
Schneider Electric
 
The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBook
GE Energy Connections
 
AccuSine pfv+
AccuSine pfv+ AccuSine pfv+
AccuSine pfv+
Schneider Electric
 
Presentation on Green Data Centres
Presentation on Green Data CentresPresentation on Green Data Centres
Presentation on Green Data Centres
IGBC Green Building Congress
 
Data Center Server Rack Strategies
Data Center Server Rack StrategiesData Center Server Rack Strategies
Data Center Server Rack Strategies
42U Data Center Solutions
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul ppt
RAHUL KAUSHAL
 
How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...
Schneider Electric
 
Optimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsOptimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsSchneider Electric
 
[Webinar Slides] Advanced distribution management system integration of renew...
[Webinar Slides] Advanced distribution management system integration of renew...[Webinar Slides] Advanced distribution management system integration of renew...
[Webinar Slides] Advanced distribution management system integration of renew...
Schneider Electric
 
Implementing energy efficient data centers
Implementing energy efficient  data centersImplementing energy efficient  data centers
Implementing energy efficient data centers
Schneider Electric India
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure Presentation
Muhammad Asad Rashid
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?
Schneider Electric
 
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS OperationEco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Schneider Electric
 
Business intelligence
Business intelligence Business intelligence
Business intelligence
Schneider Electric
 
Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electric
Schneider Electric
 
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendDatacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendHPDutchWorld
 

What's hot (20)

Distributech 2015 - Mobile Work management
Distributech 2015 - Mobile Work managementDistributech 2015 - Mobile Work management
Distributech 2015 - Mobile Work management
 
Microgrid & renewable integration at burbank water & power
Microgrid & renewable integration at burbank water & powerMicrogrid & renewable integration at burbank water & power
Microgrid & renewable integration at burbank water & power
 
Practical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data CentersPractical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data Centers
 
Data centers on the Edge
Data centers on the EdgeData centers on the Edge
Data centers on the Edge
 
Underground Self-Healing Solution
Underground Self-Healing Solution Underground Self-Healing Solution
Underground Self-Healing Solution
 
The Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBookThe Future Of Data Center Critical Power - GP100 eBook
The Future Of Data Center Critical Power - GP100 eBook
 
AccuSine pfv+
AccuSine pfv+ AccuSine pfv+
AccuSine pfv+
 
Presentation on Green Data Centres
Presentation on Green Data CentresPresentation on Green Data Centres
Presentation on Green Data Centres
 
Data Center Server Rack Strategies
Data Center Server Rack StrategiesData Center Server Rack Strategies
Data Center Server Rack Strategies
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul ppt
 
How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...
 
Optimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operationsOptimizing machine, line, and process efficiency in manufacturing operations
Optimizing machine, line, and process efficiency in manufacturing operations
 
[Webinar Slides] Advanced distribution management system integration of renew...
[Webinar Slides] Advanced distribution management system integration of renew...[Webinar Slides] Advanced distribution management system integration of renew...
[Webinar Slides] Advanced distribution management system integration of renew...
 
Implementing energy efficient data centers
Implementing energy efficient  data centersImplementing energy efficient  data centers
Implementing energy efficient data centers
 
DataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure PresentationDataCenter:: Infrastructure Presentation
DataCenter:: Infrastructure Presentation
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?
 
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS OperationEco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
 
Business intelligence
Business intelligence Business intelligence
Business intelligence
 
Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electric
 
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der ArendDatacenter Transformation - Energy And Availability - Dio Van Der Arend
Datacenter Transformation - Energy And Availability - Dio Van Der Arend
 

Viewers also liked

El problema dels núvols
El  problema  dels  núvolsEl  problema  dels  núvols
El problema dels núvolsgegantdelrec
 
Xerrada informativa 2016
Xerrada informativa 2016Xerrada informativa 2016
Xerrada informativa 2016
gegantdelrec
 
USDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
USDmkt805 - Social Media Marketing Lecture 1 & 2 SlidesUSDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
USDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
agbegin
 
El dofi rosa i les seves aventures
El dofi  rosa  i  les  seves   aventuresEl dofi  rosa  i  les  seves   aventures
El dofi rosa i les seves aventuresgegantdelrec
 
Cuestionario 5
Cuestionario 5Cuestionario 5
Cuestionario 5andresatl
 
Content Curation per la scuola
Content Curation per la scuolaContent Curation per la scuola
Content Curation per la scuola
etostello
 

Viewers also liked (8)

El problema dels núvols
El  problema  dels  núvolsEl  problema  dels  núvols
El problema dels núvols
 
09 Greek Maritime Cluster Research Results Internationalisation
09  Greek Maritime Cluster Research Results Internationalisation09  Greek Maritime Cluster Research Results Internationalisation
09 Greek Maritime Cluster Research Results Internationalisation
 
Xerrada informativa 2016
Xerrada informativa 2016Xerrada informativa 2016
Xerrada informativa 2016
 
USDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
USDmkt805 - Social Media Marketing Lecture 1 & 2 SlidesUSDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
USDmkt805 - Social Media Marketing Lecture 1 & 2 Slides
 
El dofi rosa i les seves aventures
El dofi  rosa  i  les  seves   aventuresEl dofi  rosa  i  les  seves   aventures
El dofi rosa i les seves aventures
 
Cuestionario 5
Cuestionario 5Cuestionario 5
Cuestionario 5
 
11к
11к11к
11к
 
Content Curation per la scuola
Content Curation per la scuolaContent Curation per la scuola
Content Curation per la scuola
 

Similar to Improving your PUE while consolidating into an existing live data center

Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered Raritan
 
Retrofit, build, or go cloud/colo? Choosing your best direction
Retrofit, build, or go cloud/colo?  Choosing your best directionRetrofit, build, or go cloud/colo?  Choosing your best direction
Retrofit, build, or go cloud/colo? Choosing your best direction
Schneider Electric
 
Aged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptxAged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptx
Schneider Electric
 
PUE Reconsidered
PUE ReconsideredPUE Reconsidered
PUE Reconsidered
Sunbird DCIM
 
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
Bel Fuse Inc.
 
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
Commercial Overview   DC Session 4   Introduction To Energy In The Data CentreCommercial Overview   DC Session 4   Introduction To Energy In The Data Centre
Commercial Overview DC Session 4 Introduction To Energy In The Data Centrepaul_mathews
 
Airbyte @ Airflow Summit - The new modern data stack
Airbyte @ Airflow Summit - The new modern data stackAirbyte @ Airflow Summit - The new modern data stack
Airbyte @ Airflow Summit - The new modern data stack
Michel Tricot
 
Improvements in Data Center Management
Improvements in Data Center ManagementImprovements in Data Center Management
Improvements in Data Center Management
ScottMadden, Inc.
 
27546 pod overview including 240a
27546 pod overview including 240a27546 pod overview including 240a
27546 pod overview including 240agmazuel
 
Datacenter Efficiency: Building for High Density
Datacenter Efficiency: Building for High DensityDatacenter Efficiency: Building for High Density
Datacenter Efficiency: Building for High Density
Christopher Kelley
 
Virtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green gridVirtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green grid
DCC Mission Critical
 
Server room presentation 16th january 2014
Server room presentation 16th january 2014Server room presentation 16th january 2014
Server room presentation 16th january 2014
Building Sustainability Ltd
 
MIG 5th Data Centre Summit 2016 PTS Presentation v1
MIG 5th Data Centre Summit 2016 PTS Presentation v1MIG 5th Data Centre Summit 2016 PTS Presentation v1
MIG 5th Data Centre Summit 2016 PTS Presentation v1blewington
 
Going Modular? Lessons learned from 500 modular data center implementations
Going Modular?  Lessons learned from 500 modular data center implementations Going Modular?  Lessons learned from 500 modular data center implementations
Going Modular? Lessons learned from 500 modular data center implementations
John M. Kundtz ☛ Associate Partner / Sales Mgr / BDE
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
ConsultingSpecifyingEngineer
 
PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009
Henry Hsu
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdf
bui thequan
 
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPCExceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
inside-BigData.com
 

Similar to Improving your PUE while consolidating into an existing live data center (20)

Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered
 
Retrofit, build, or go cloud/colo? Choosing your best direction
Retrofit, build, or go cloud/colo?  Choosing your best directionRetrofit, build, or go cloud/colo?  Choosing your best direction
Retrofit, build, or go cloud/colo? Choosing your best direction
 
Aged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptxAged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptx
 
PUE Reconsidered
PUE ReconsideredPUE Reconsidered
PUE Reconsidered
 
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
Bel Power Solutions: Applying Open Compute Rack (OCP) & Power Specifications ...
 
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
Commercial Overview   DC Session 4   Introduction To Energy In The Data CentreCommercial Overview   DC Session 4   Introduction To Energy In The Data Centre
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
 
Airbyte @ Airflow Summit - The new modern data stack
Airbyte @ Airflow Summit - The new modern data stackAirbyte @ Airflow Summit - The new modern data stack
Airbyte @ Airflow Summit - The new modern data stack
 
Improvements in Data Center Management
Improvements in Data Center ManagementImprovements in Data Center Management
Improvements in Data Center Management
 
27546 pod overview including 240a
27546 pod overview including 240a27546 pod overview including 240a
27546 pod overview including 240a
 
Datacenter Efficiency: Building for High Density
Datacenter Efficiency: Building for High DensityDatacenter Efficiency: Building for High Density
Datacenter Efficiency: Building for High Density
 
Virtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green gridVirtualization for efficiency: by Kathrin Winkler, The green grid
Virtualization for efficiency: by Kathrin Winkler, The green grid
 
Server room presentation 16th january 2014
Server room presentation 16th january 2014Server room presentation 16th january 2014
Server room presentation 16th january 2014
 
MIG 5th Data Centre Summit 2016 PTS Presentation v1
MIG 5th Data Centre Summit 2016 PTS Presentation v1MIG 5th Data Centre Summit 2016 PTS Presentation v1
MIG 5th Data Centre Summit 2016 PTS Presentation v1
 
Going Modular? Lessons learned from 500 modular data center implementations
Going Modular?  Lessons learned from 500 modular data center implementations Going Modular?  Lessons learned from 500 modular data center implementations
Going Modular? Lessons learned from 500 modular data center implementations
 
Google ppt. mis
Google ppt. misGoogle ppt. mis
Google ppt. mis
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
Build Energy Saving into Your Datacenter
Build Energy Saving into Your DatacenterBuild Energy Saving into Your Datacenter
Build Energy Saving into Your Datacenter
 
PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009PUE Reconsidered - AFCOM (MI), July 2009
PUE Reconsidered - AFCOM (MI), July 2009
 
OCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdfOCP liquid direct to chip temperature guideline.pdf
OCP liquid direct to chip temperature guideline.pdf
 
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPCExceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
Exceeding the Limits of Air Cooling to Unlock Greater Potential in HPC
 

More from Schneider Electric

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
Schneider Electric
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
Schneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
Schneider Electric
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
Schneider Electric
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
Schneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
Schneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Schneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
Schneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
Schneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
Schneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
Schneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
Schneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
Schneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
Schneider Electric
 

More from Schneider Electric (20)

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 

Recently uploaded

The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
Adam Smith
 
Business Valuation Principles for Entrepreneurs
Business Valuation Principles for EntrepreneursBusiness Valuation Principles for Entrepreneurs
Business Valuation Principles for Entrepreneurs
Ben Wann
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
Nicola Wreford-Howard
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
HumanResourceDimensi1
 
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).pptENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
zechu97
 
LA HUG - Video Testimonials with Chynna Morgan - June 2024
LA HUG - Video Testimonials with Chynna Morgan - June 2024LA HUG - Video Testimonials with Chynna Morgan - June 2024
LA HUG - Video Testimonials with Chynna Morgan - June 2024
Lital Barkan
 
Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...
Lviv Startup Club
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Lviv Startup Club
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
BBPMedia1
 
The-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic managementThe-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic management
Bojamma2
 
20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf
tjcomstrang
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
seri bangash
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
BBPMedia1
 
VAT Registration Outlined In UAE: Benefits and Requirements
VAT Registration Outlined In UAE: Benefits and RequirementsVAT Registration Outlined In UAE: Benefits and Requirements
VAT Registration Outlined In UAE: Benefits and Requirements
uae taxgpt
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Arihant Webtech Pvt. Ltd
 
Attending a job Interview for B1 and B2 Englsih learners
Attending a job Interview for B1 and B2 Englsih learnersAttending a job Interview for B1 and B2 Englsih learners
Attending a job Interview for B1 and B2 Englsih learners
Erika906060
 
Project File Report BBA 6th semester.pdf
Project File Report BBA 6th semester.pdfProject File Report BBA 6th semester.pdf
Project File Report BBA 6th semester.pdf
RajPriye
 
Cracking the Workplace Discipline Code Main.pptx
Cracking the Workplace Discipline Code Main.pptxCracking the Workplace Discipline Code Main.pptx
Cracking the Workplace Discipline Code Main.pptx
Workforce Group
 
Sustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & EconomySustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & Economy
Operational Excellence Consulting
 
Skye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto AirportSkye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto Airport
marketingjdass
 

Recently uploaded (20)

The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
 
Business Valuation Principles for Entrepreneurs
Business Valuation Principles for EntrepreneursBusiness Valuation Principles for Entrepreneurs
Business Valuation Principles for Entrepreneurs
 
Exploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social DreamingExploring Patterns of Connection with Social Dreaming
Exploring Patterns of Connection with Social Dreaming
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
 
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).pptENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
ENTREPRENEURSHIP TRAINING.ppt for graduating class (1).ppt
 
LA HUG - Video Testimonials with Chynna Morgan - June 2024
LA HUG - Video Testimonials with Chynna Morgan - June 2024LA HUG - Video Testimonials with Chynna Morgan - June 2024
LA HUG - Video Testimonials with Chynna Morgan - June 2024
 
Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
 
The-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic managementThe-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic management
 
20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf20240425_ TJ Communications Credentials_compressed.pdf
20240425_ TJ Communications Credentials_compressed.pdf
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
 
VAT Registration Outlined In UAE: Benefits and Requirements
VAT Registration Outlined In UAE: Benefits and RequirementsVAT Registration Outlined In UAE: Benefits and Requirements
VAT Registration Outlined In UAE: Benefits and Requirements
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
 
Attending a job Interview for B1 and B2 Englsih learners
Attending a job Interview for B1 and B2 Englsih learnersAttending a job Interview for B1 and B2 Englsih learners
Attending a job Interview for B1 and B2 Englsih learners
 
Project File Report BBA 6th semester.pdf
Project File Report BBA 6th semester.pdfProject File Report BBA 6th semester.pdf
Project File Report BBA 6th semester.pdf
 
Cracking the Workplace Discipline Code Main.pptx
Cracking the Workplace Discipline Code Main.pptxCracking the Workplace Discipline Code Main.pptx
Cracking the Workplace Discipline Code Main.pptx
 
Sustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & EconomySustainability: Balancing the Environment, Equity & Economy
Sustainability: Balancing the Environment, Equity & Economy
 
Skye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto AirportSkye Residences | Extended Stay Residences Near Toronto Airport
Skye Residences | Extended Stay Residences Near Toronto Airport
 

Improving your PUE while consolidating into an existing live data center

  • 1. 1 Improving Your PUE While Consolidating Into An Existing Live Data Center Jay Owen VP, IT Federal Solutions Tweet Live! #SchneiderXE
  • 2. 2 Objectives Upon Completion of this course, you will be able to ● Identify the percentage of commercial data center operators that plan to use co-location or cloud to meet future data center requirements ● Identify three reasons why a new data center is built ● Identify three reasons why an existing data center is upgraded ● Identify four consolidation options ● Identify the typical range of IT cabinets in a pod ● Identify attributes of a high-density pod ● Typical PUE ● Rack densities ● Raised floor requirements ● Options ● Benefits
  • 3. 3 Consolidation options ●Move IT to the cloud ●Move IT to Co-Location ●Build new larger data centers and consolidate into them ●Upgrade selected existing data centers and consolidate into them What are commercial customers doing, and why?
  • 4. 4 Moving IT to cloud or co-location ● Only 50% of commercial data center operators plan to use co- location or cloud to meet future data center requirements* (remainder to be met with in-house data centers) ● Rarely is an entire data center moved to cloud or co-location ● Moves to cloud or co-location often free up capacity across existing data centers, increasing the need to consolidate ● Uncertainty regarding use of cloud increases the risk of building new data centers *Survey by 451 group, presented at the Uptime Symposium, May 2012 Moves to cloud and co-location do not decrease the need to consolidate, but actually increase this need
  • 5. 5 Typical concept: Build new data center and consolidate into it ● When the goal is to consolidate a large number of data centers into a single very large data center (~20 MW) ● A large capital project is feasible (~$400 M) ● High rate of IT growth is anticipated ● When the stock of existing data centers is considered hopelessly ineffective (space, energy efficiency, power density) ● When there is a commonality of IT functions across the data centers ● When the consolidation can be forced top-down in the organization ● When harmonized standards can be imposed across all of the IT systems
  • 6. 6 New concept: Upgrade selected existing data centers and consolidate into them ● Appropriate when consolidating 2-5 data centers into one ● When some of the existing IT is moving to the cloud or co-location ● Much lower capital investment ● No new real estate acquisition ● Consolidation projects are not organization-wide but are operated within independent departments ● Can be phased to match IT refreshes ● Can be done while receiving data center is live
  • 7. 7 Example of a High Density Pod Two Pod installation at US Army Fort Bliss
  • 8. 8 The High-Density Pod Overlay Method ● Method for upgrading existing data centers ● Self-contained “Pods” of data center infrastructure are placed in existing data center space ● Pod size typically 10-20 cabinets ● Typically includes integrated air conditioning and power distribution ● Optionally contains integrated UPS ● Pods operate with superior performance ● Much higher energy efficiency (typical PUE less than 1.4) ● Much higher power density (up to 20 KW per cabinet) ● Pod does not need to rely on existing infrastructure ● Does not require raised floor ● Does not require air supply
  • 9. 9 Example of a Consolidation Project Using Pods presented by SUN at data center dynamics, July 2008
  • 10. 10 Clear out a corner of the data center to get started
  • 11. 11 Consolidation of a typical portfolio Spec Data Center A Data Center B Data Center C Starting Total Rated KW 500 KW 700 KW 250 KW 1450 KW Actual KW 260 KW 220 KW 160 KW 640 KW % KW Utilized 52% 31% 64% 44% Ave KW per cabinet 3.0 KW 3.4 KW 3.5 KW 3.3 KW PUE 2.2 2.2 2.1 2.2 Square Feet 8,300 7,800 4,200 20,300 % Space Utilized 29% 23% 31% 27% Annual Energy $ $600,000 $510,000 $350,000 $1,460,000
  • 12. 12 Assumptions ● Data Center B chosen as receiving data center ● Assume none of the current load will go to the cloud or be reduced by virtualization ● At final condition Data Center B has been converted to Pods over time
  • 13. 13 Consolidation of a typical portfolio Spec Data Center A Data Center B Data Center C Starting Total Final Total Rated KW 500 KW 700 KW 250 KW 1450 KW 700 KW Actual KW 260 KW 640 KW 160 KW 640 KW 640 KW % KW Utilized 52% 91% 64% 44% 91% Ave KW per cabinet 3.0 KW 6.0 KW 3.5 KW 3.3 KW 6.0 KW PUE 2.2 1.6 2.1 2.2 1.6 Square Feet 8,300 7,800 4,200 20,300 7,800 % Space Utilized 29% 38% 31% 27% 38% Annual Energy $ $600,000 $1,075,000 $350,000 $1,460,000 $1,075,000
  • 14. 14 Results of the example ● Energy use reduced 26%, even though the IT load stayed constant ● The receiving data center has only 38% space utilization after consolidation! (space compaction due to increased density) ● 60% of the original data center space was freed up for other purposes! ● The target receiving data center was NOT the one with the most square feet or the best PUE These are typical results we see in commercial installations
  • 15. 15 PUE contribution of cooling losses: Traditional vs. superior data centre 1.9 0.1 0.03 0.08 0.03 0.04 0.17 0.07 0.06 1.32 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
  • 16. 16 PUE contribution of cooling losses: Traditional vs. superior data centre 1.9 0.1 0.03 0.08 0.03 0.04 0.17 0.07 0.06 1.32 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 Traditional raised-floor cooling is responsible for most of the energy inefficiency High Density Pods eliminate most of the inefficiency of a traditional data center
  • 17. 17 Capacity extension of maxed out data centers Power and cooling facility modules are added to expand power capacity Modular IT space is added along with power and cooling modules 1 2 Power, cooling, and space can be added to live data centers in the future
  • 18. 18 Retrofitting a live data center requires special skills
  • 19. 19 Conclusions ● Moving IT to the cloud or co-location increases the need to consolidate internal data centers ● You don’t need to build new data centers to be receiving data centers ● It is common in industry to consolidate a number of data centers into an existing live data center ● The High Density Pod Overlay Method is a very effective technique for upgrading data centers as part of a consolidation project
  • 20. 20 Resources Containerized Power and Cooling Modules for Data Centers Schneider Electric White Paper 163 Deploying High-Density Pods in a Low Density Data Center Schneider Electric White Paper 134 Preparing the Physical Infrastructure of Receiving Data Centers for Consolidation Schneider Electric White Paper 175 Determining the Power, Cooling, and Space Capacities when Consolidating Data Centers Schneider Electric White Paper 177 download: Whitepapers.apc.com ipad appstore: “Schneider electric white papers” free application