SlideShare a Scribd company logo
1 of 23
Jason Schafer, ATS
Director, Technology & Operations Management
Retrofit, Build, or Go Colo/Cloud:
Choosing Your Best Direction
Schneider Electric 2
Objectives
1. Review the evaluation criteria that goes into determining
whether to upgrade, build new, or outsource a data center.
2. Understand the financial metrics and scenarios that go
into determining the direction of the data center.
3. Identify the 10 strategic, non-financial factors that go into
the decision.
4. Overview of tools available to help in the decision making
process.
Schneider Electric 3
• Upgrade
• Build
• Outsource
Business
Requirements
IT
Requirements
Evaluation of
Data Center
Capacity
Options
The Tail of the Dog?
Schneider Electric 4
The Tail of the Dog?
Schneider Electric 5
Evaluation Criteria
Upgrade,
Build or
Co-locate
Cost
Cash Flow
Strategic
Factors
Process to evaluate these attributes is not always clear.
Schneider Electric 6
Challenge for Customers
● Create a financial model to evaluate
options
● Create a common financial metric to
easily compare options
● Create a structured approach to
evaluate strategic factors
Schneider Electric 7
Financial Metrics
● Normalize costs to 10 year TCO per watt
● Utilize cumulative cash outlay to
determine a break even point
● Provide insight into opex versus capex
Schneider Electric 8
Using Modeling to Evaluate Options
Benefits
Drawbacks
• Provides possibility of easy to use tools
• Provides structure to decision making
• Provides quick iterations to assist in planning
• Not every situation matches model
• Results as good as the data and assumptions
Schneider Electric 9
10 Year TCO for Co-location
We picked assumptions we view to be typical.
Baseline
• Determined to be $62 per watt
• Rate increase assumed to be 5% per year
• “Remote Hands” fee of $225 per hour,
each rack takes 1 hour per month
• 4kW per rack
• 3% discount rate for TCO calculations
Key Assumptions
• Rack - $1,000 month/rack
• Colo provides the rack at no
additional cost to customer
• Power - $800 month/rack
• Bandwidth - $2,000 month
Schneider Electric 10
Upgrade Options – 3 Basic Strategies
Approach Description Assumptions Example
Increase
utilization of
installed
equipment
Stranded capacity may
exist that can be re-
claimed
Data center has sufficient
power & cooling capacity,
but cooling system is de-
rated due to poor airflow
management practices
Blanking
panels, brush
strips, aisle
containment
Add capacity
with new high
density zones
One or more rows of
racks can be added to a
larger, low-density data
center to increase
capacity
Data center has sufficient
switchgear & heat rejection
capacity, and has available IT
space
High density
zone(s)
Add capacity
with facility
modules
For larger capacity
upgrades with available
IT space, facility modules
increase bulk capacity
Data center is out of
switchgear & heat rejection
capacity, has no space in
mechanical/electrical rooms,
but has available IT space
Power and/or
cooling facility
module(s)
White Paper 153
Implementing Hot and Cold
Air Containment in Existing
Data Centers
White Paper 134
Deploying High-Density Pods
in a Low-Density Data
Center
White Paper 163
Containerized Power and
Cooling Modules for Data
Centers
Schneider Electric 11
Upgrade Options – 3 Basic Strategies
Approach Description Assumptions Example
Increase
utilization of
installed
equipment
Stranded capacity may
exist that can be re-
claimed
Data center has sufficient
power & cooling capacity,
but cooling system is de-
rated due to poor airflow
management practices
Blanking
panels, brush
strips, aisle
containment
Add capacity
with new high
density zones
One or more rows of
racks can be added to a
larger, low-density data
center to increase
capacity
Data center has sufficient
switchgear & heat rejection
capacity, and has available IT
space
High density
zone(s)
Add capacity
with facility
modules
For larger capacity
upgrades with available
IT space, facility modules
increase bulk capacity
Data center is out of
switchgear & heat rejection
capacity, has no space in
mechanical/electrical rooms,
but has available IT space
Power and/or
cooling facility
module(s)
Consider
low- hanging fruit
Consider going to
higher density
Consider adding
facility capacity
White Paper 153
Implementing Hot and Cold
Air Containment in Existing
Data Centers
White Paper 134
Deploying High-Density Pods
in a Low-Density Data
Center
White Paper 163
Containerized Power and
Cooling Modules for Data
Centers
Schneider Electric 12
Scenario #1: Low-Hanging Fruit Model
Break even in less than 1 year.
● Tier 3 1MW design load only
utilized to 900 kW
● De-rating largely due to air mixing, etc.
● 10 year TCO - $17.00 per watt
● Blanking panels, brush strips, cold-aisle
containment gain 100kW
● First cost of $2.10 per watt
● Co-lo 10 year TCO - $62.00 per watt
Schneider Electric 13
Scenario #2: Implement Higher Density
Break even in less than 2 years.
● Key Assumptions
● Add 40kW zone @ 4 kW per rack
● Pod includes 2N UPS, 2N Inrow
cooling
● Discounted bandwidth cost due to
existing bandwidth available
● PUE for data center of 1.35
● 10 year TCO - $22.00 per watt
● First Cost to upgrade - $4.80 per watt
● Co-lo 10 year TCO - $62.00 per watt
Schneider Electric 14
Scenario #3: Add to Facility Capacity
Break even in about 2 years.
● Key Assumptions
● Add 500kW power and chilled water
modules, 450kW of IT load
● Discounted bandwidth cost due to
existing bandwidth available
● PUE of 1.35
● 10 year TCO - $27.00 per watt
● First Cost to upgrade - $8.45 per watt
● Co-lo 10 year TCO - $62.00 per watt
Schneider Electric 15
Scenario #4: Build New Facility
Break even in about 3 ½ years
● Key Assumptions
● 1 MW capacity, $12/watt*
● 4kW per rack
● Lease - $5/sq. ft./month
● One battery refresh in Year 7
● PUE of 1.33
● Opex increases 3% per year
● Bandwidth - $5,000/month
● 10 year TCO - $42.00 per watt
● Co-lo 10 year TCO - $62.00 per watt
* Schneider Electric Capitalized Cost Trade-off Tool, Tier 3, St. Louis, Air Chillers
Schneider Electric 16
But is it really about the money?
The 10 factors that may trump any financial discussion.
Schneider Electric 17
„Soft‟ Issues to Consider
Company Culture
● Sometimes the server huggers win
Comfort with IT Equipment in Shared Space
● Does one colo have better security than another?
● Will my neighbors negatively impact my equipment?
IT Accessibility to the Data Center
● Can my guys get there if they need to be there?
Comfort with Dependence on Contract Terms
● If I call with a problem will anyone answer?
Schneider Electric 18
Quantitative Issues to Consider
Critical Facilities Expertise
● If you have no staff, the decision is easy
● Confidence in ability to operate a data center
Regulatory Compliance
● HIPAA for example
Life Expectancy
● Cloud computing wins for temporary use
Deployment Timeframe
● If I need it next week, the decision is easy
Schneider Electric 19
Financial Model Preferences
Perceived size of capital investment
● Is $200k a lot or a little?
● Depends on relative size – relatively little for a company
like Schneider Electric but for a start up…
Cash flow model preference
0 1 2 3 4 5 6 7 8 9 10
Opex Capex
Year 0 1 2 3 4 5 6 7 8 9 10
Opex Capex
Year
BUILD CO-LOCATION
Lower TCO but higher
capital expense model
Higher TCO but
smoother Opex model
Schneider Electric 20
Strategic
Factors
Rating Guide Score
Company Culture
1 = Strong company culture to keep direct control & avoid outsourcing any business function
10 = Company is open to outsourcing business functions
Comfort with IT
Equipment in
Shared Space
1 = Data center must be in company owned space
10 = Data center can be in shared IT space
IT Accessibility to
the Data Center
1 = IT staff must be located in same facility as data center
10= IT staff can be remote to data center
Comfort with
Dependence on
Contract Terms
1 = Low degree of comfort with contract dependence
10 = High degree of comfort with contract dependence
Critical Facilities
Expertise
1 = Strong critical facilities expertise exists within the company
10= Little to no critical facilities expertise exists within the company
Regulatory
Requirements
1 = Business has very specific regulatory compliance issues
10 = Business has no specific regulatory compliance issues
Life Expectancy
1 = Data center will be utilized for >10 years
10 = Data center requirement is temporary
Deployment
Timeframe
1 = Business requirement for deployment in years
10 = Business requirement for deployment in weeks
Perceived Size of
Capital Investment
1 = Nominal capital expense is not viewed as significant to company
10 = Nominal capital expense is viewed as significant to company
Cash Flow Model
Preference
1 = Comfortable with spikes in capital expense
10= Prefer smooth predictable operating expenses
TOTAL SCORE *
* The total score will range from 10 to 100 based on the relative scales from 1 to 10 for each of the 10 considerations.
Evaluation Scorecard
These issues will sometimes dominate the decision.
Schneider Electric 21
Summary
Use model to evaluate financial options with a common language
● 10 year TCO is less for doing it yourself and is almost always
cheaper than co-location
● Break even time and capital preservation may be more important
than TCO
● Using the right financial metric is critical
Cultural issues sometimes can dominate the conversation – create
an objective way to discuss these
● Scorecard or weighted scorecard
● Are there Filtering Criteria?
Use tools to help facilitate the conversation and allow for rapid
evaluation of options
*
*
*
Schneider Electric 22
New TradeOff Tool™
● Simple, automated tools to
support specific planning
decisions
● Models complex interactions
of systems based on data
and science
● One-screen, standardized
user interface
● Instant output allows for rapid
creation of “what if” scenarios
Try it yourself: http://j.mp/sebvb
Schneider Electric 23
Questions?
Links for:
Considerations for Owning versus Outsourcing Data Center Physical Infrastructure
http://www.apc.com/whitepaper/?wp=171
Data Center Build vs. Colocation TCO Calculator
http://www.apc.com/tool/?tt=13 -or- http://j.mp/sebvb

More Related Content

What's hot

Containerized Power and Cooling Modules for Data Centers
Containerized Power and Cooling Modules for Data CentersContainerized Power and Cooling Modules for Data Centers
Containerized Power and Cooling Modules for Data CentersSchneider Electric
 
Schneider electric automationcom pes ppt
Schneider electric   automationcom pes pptSchneider electric   automationcom pes ppt
Schneider electric automationcom pes pptSharon Smith
 
How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...Schneider Electric
 
Schneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric
 
Essential elements of data center operations
Essential elements of data center operationsEssential elements of data center operations
Essential elements of data center operationsSchneider Electric
 
The smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsThe smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsSchneider Electric
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operationsSchneider Electric
 
Integrating efficiency into healthcare - a life cycle approach
Integrating efficiency into healthcare  - a life cycle approachIntegrating efficiency into healthcare  - a life cycle approach
Integrating efficiency into healthcare - a life cycle approachSchneider Electric
 
Energy solutions for federal facilities : How to harness sustainable savings ...
Energy solutions for federal facilities : How to harness sustainable savings ...Energy solutions for federal facilities : How to harness sustainable savings ...
Energy solutions for federal facilities : How to harness sustainable savings ...Schneider Electric
 
New trends in video analytics and surveillance systems for the mining industry
New trends in video analytics and surveillance systems for the mining industryNew trends in video analytics and surveillance systems for the mining industry
New trends in video analytics and surveillance systems for the mining industrySchneider Electric
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operationsSchneider Electric
 
Aged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptxAged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptxSchneider Electric
 
Simplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSimplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSchneider Electric
 
Practical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data CentersPractical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data CentersSchneider Electric
 
Energy efficiency for mid-size buildings
Energy efficiency for mid-size buildingsEnergy efficiency for mid-size buildings
Energy efficiency for mid-size buildingsSchneider Electric
 
Funding Infrastructure Investments with Guaranteed Performance
Funding Infrastructure  Investments with  Guaranteed PerformanceFunding Infrastructure  Investments with  Guaranteed Performance
Funding Infrastructure Investments with Guaranteed PerformanceSchneider Electric
 
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS OperationEco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS OperationSchneider Electric
 

What's hot (20)

Containerized Power and Cooling Modules for Data Centers
Containerized Power and Cooling Modules for Data CentersContainerized Power and Cooling Modules for Data Centers
Containerized Power and Cooling Modules for Data Centers
 
Data centers on the Edge
Data centers on the EdgeData centers on the Edge
Data centers on the Edge
 
Schneider electric automationcom pes ppt
Schneider electric   automationcom pes pptSchneider electric   automationcom pes ppt
Schneider electric automationcom pes ppt
 
How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...How Data Center Infrastructure Management Software Improves Planning and Cuts...
How Data Center Infrastructure Management Software Improves Planning and Cuts...
 
Schneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference Designs
 
Essential elements of data center operations
Essential elements of data center operationsEssential elements of data center operations
Essential elements of data center operations
 
Scada expert Clear Scada
Scada expert Clear ScadaScada expert Clear Scada
Scada expert Clear Scada
 
The smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsThe smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutions
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operations
 
Integrating efficiency into healthcare - a life cycle approach
Integrating efficiency into healthcare  - a life cycle approachIntegrating efficiency into healthcare  - a life cycle approach
Integrating efficiency into healthcare - a life cycle approach
 
Energy solutions for federal facilities : How to harness sustainable savings ...
Energy solutions for federal facilities : How to harness sustainable savings ...Energy solutions for federal facilities : How to harness sustainable savings ...
Energy solutions for federal facilities : How to harness sustainable savings ...
 
New trends in video analytics and surveillance systems for the mining industry
New trends in video analytics and surveillance systems for the mining industryNew trends in video analytics and surveillance systems for the mining industry
New trends in video analytics and surveillance systems for the mining industry
 
How green standards are changing data center design and operations
How green standards are changing data center design and operationsHow green standards are changing data center design and operations
How green standards are changing data center design and operations
 
Aged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptxAged Data Center Infrastructure.pptx
Aged Data Center Infrastructure.pptx
 
Simplifying Data Center Design/ Build
Simplifying Data Center Design/ BuildSimplifying Data Center Design/ Build
Simplifying Data Center Design/ Build
 
Practical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data CentersPractical Considerations for Implementing Prefabricated Data Centers
Practical Considerations for Implementing Prefabricated Data Centers
 
Ensuring your plant is secure
Ensuring your plant is secureEnsuring your plant is secure
Ensuring your plant is secure
 
Energy efficiency for mid-size buildings
Energy efficiency for mid-size buildingsEnergy efficiency for mid-size buildings
Energy efficiency for mid-size buildings
 
Funding Infrastructure Investments with Guaranteed Performance
Funding Infrastructure  Investments with  Guaranteed PerformanceFunding Infrastructure  Investments with  Guaranteed Performance
Funding Infrastructure Investments with Guaranteed Performance
 
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS OperationEco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
Eco-Mode: Benefits and Risks of Energy Saving Modes of UPS Operation
 

Similar to Retrofit, build, or go cloud/colo? Choosing your best direction

Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...IBMAsean
 
Improvements in Data Center Management
Improvements in Data Center ManagementImprovements in Data Center Management
Improvements in Data Center ManagementScottMadden, Inc.
 
Improving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerImproving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerSchneider Electric
 
Equota Pitch Deck EN 2015
Equota Pitch Deck EN 2015Equota Pitch Deck EN 2015
Equota Pitch Deck EN 2015Lucia Shen
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul pptRAHUL KAUSHAL
 
American Institute of Architects Committee on the Envrinment
American Institute of Architects Committee on the EnvrinmentAmerican Institute of Architects Committee on the Envrinment
American Institute of Architects Committee on the EnvrinmentCenter for Energy and Environment
 
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
Commercial Overview   DC Session 4   Introduction To Energy In The Data CentreCommercial Overview   DC Session 4   Introduction To Energy In The Data Centre
Commercial Overview DC Session 4 Introduction To Energy In The Data Centrepaul_mathews
 
How To Achieve a Green Energy Workspace
How To Achieve a Green Energy WorkspaceHow To Achieve a Green Energy Workspace
How To Achieve a Green Energy WorkspaceOakland Air
 
Building a Sustainable Data Center
Building a Sustainable Data CenterBuilding a Sustainable Data Center
Building a Sustainable Data CenterAngela Miller
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingGraybar
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered Raritan
 
Achieving more with less - Infrastructure
Achieving more with less - InfrastructureAchieving more with less - Infrastructure
Achieving more with less - InfrastructureGethNichols
 
Datacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildDatacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildChristopher Kelley
 
Unlock Your Buildings Hidden Energy Data - Corenet Seattle
Unlock Your Buildings Hidden Energy Data - Corenet SeattleUnlock Your Buildings Hidden Energy Data - Corenet Seattle
Unlock Your Buildings Hidden Energy Data - Corenet SeattleJason Burt
 
Derek Schwartz Fed Lessons Learned.Final
Derek Schwartz Fed Lessons Learned.FinalDerek Schwartz Fed Lessons Learned.Final
Derek Schwartz Fed Lessons Learned.Finalwlambert_2001
 

Similar to Retrofit, build, or go cloud/colo? Choosing your best direction (20)

Going Modular? Lessons learned from 500 modular data center implementations
Going Modular?  Lessons learned from 500 modular data center implementations Going Modular?  Lessons learned from 500 modular data center implementations
Going Modular? Lessons learned from 500 modular data center implementations
 
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
 
Improvements in Data Center Management
Improvements in Data Center ManagementImprovements in Data Center Management
Improvements in Data Center Management
 
The next wave of GreenIT
The next wave of GreenITThe next wave of GreenIT
The next wave of GreenIT
 
Google ppt. mis
Google ppt. misGoogle ppt. mis
Google ppt. mis
 
Improving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerImproving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data center
 
Emerson Energy Logic
Emerson Energy LogicEmerson Energy Logic
Emerson Energy Logic
 
O2ne draft white
O2ne draft whiteO2ne draft white
O2ne draft white
 
Equota Pitch Deck EN 2015
Equota Pitch Deck EN 2015Equota Pitch Deck EN 2015
Equota Pitch Deck EN 2015
 
Green data center_rahul ppt
Green data center_rahul pptGreen data center_rahul ppt
Green data center_rahul ppt
 
American Institute of Architects Committee on the Envrinment
American Institute of Architects Committee on the EnvrinmentAmerican Institute of Architects Committee on the Envrinment
American Institute of Architects Committee on the Envrinment
 
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
Commercial Overview   DC Session 4   Introduction To Energy In The Data CentreCommercial Overview   DC Session 4   Introduction To Energy In The Data Centre
Commercial Overview DC Session 4 Introduction To Energy In The Data Centre
 
How To Achieve a Green Energy Workspace
How To Achieve a Green Energy WorkspaceHow To Achieve a Green Energy Workspace
How To Achieve a Green Energy Workspace
 
Building a Sustainable Data Center
Building a Sustainable Data CenterBuilding a Sustainable Data Center
Building a Sustainable Data Center
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
Data Center PUE Reconsidered
Data Center PUE Reconsidered Data Center PUE Reconsidered
Data Center PUE Reconsidered
 
Achieving more with less - Infrastructure
Achieving more with less - InfrastructureAchieving more with less - Infrastructure
Achieving more with less - Infrastructure
 
Datacenter Strategy, Design, and Build
Datacenter Strategy, Design, and BuildDatacenter Strategy, Design, and Build
Datacenter Strategy, Design, and Build
 
Unlock Your Buildings Hidden Energy Data - Corenet Seattle
Unlock Your Buildings Hidden Energy Data - Corenet SeattleUnlock Your Buildings Hidden Energy Data - Corenet Seattle
Unlock Your Buildings Hidden Energy Data - Corenet Seattle
 
Derek Schwartz Fed Lessons Learned.Final
Derek Schwartz Fed Lessons Learned.FinalDerek Schwartz Fed Lessons Learned.Final
Derek Schwartz Fed Lessons Learned.Final
 

More from Schneider Electric

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsSchneider Electric
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing Schneider Electric
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsSchneider Electric
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service ProvidersSchneider Electric
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingSchneider Electric
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSchneider Electric
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingSchneider Electric
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingSchneider Electric
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Schneider Electric
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesSchneider Electric
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Schneider Electric
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.Schneider Electric
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580Schneider Electric
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...Schneider Electric
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTSchneider Electric
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingSchneider Electric
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingSchneider Electric
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingSchneider Electric
 

More from Schneider Electric (20)

Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
Digital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting InvestorsDigital International Colo Club: Attracting Investors
Digital International Colo Club: Attracting Investors
 
32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing 32 phaseo power supplies and transformers briefing
32 phaseo power supplies and transformers briefing
 
Key Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation TrendsKey Industry Trends, M&A Valuation Trends
Key Industry Trends, M&A Valuation Trends
 
EcoStruxure™ for Cloud & Service Providers
 EcoStruxure™ for Cloud & Service Providers EcoStruxure™ for Cloud & Service Providers
EcoStruxure™ for Cloud & Service Providers
 
Magelis Basic HMI Briefing
Magelis Basic HMI Briefing Magelis Basic HMI Briefing
Magelis Basic HMI Briefing
 
Zelio Time Electronic Relay Briefing
Zelio Time Electronic Relay BriefingZelio Time Electronic Relay Briefing
Zelio Time Electronic Relay Briefing
 
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures BriefingSpacial, Thalassa, ClimaSys Universal enclosures Briefing
Spacial, Thalassa, ClimaSys Universal enclosures Briefing
 
Relay Control Zelio SSR Briefing
Relay Control Zelio SSR BriefingRelay Control Zelio SSR Briefing
Relay Control Zelio SSR Briefing
 
Magelis HMI, iPC and software Briefing
Magelis HMI, iPC and software BriefingMagelis HMI, iPC and software Briefing
Magelis HMI, iPC and software Briefing
 
Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?Where will the next 80% improvement in data center performance come from?
Where will the next 80% improvement in data center performance come from?
 
EcoStruxure for Intuitive Industries
EcoStruxure for Intuitive IndustriesEcoStruxure for Intuitive Industries
EcoStruxure for Intuitive Industries
 
Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017Systems Integrator Alliance Program 2017
Systems Integrator Alliance Program 2017
 
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
EcoStruxure, IIoT-enabled architecture, delivering value in key segments.
 
It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580It's time to modernize your industrial controls with Modicon M580
It's time to modernize your industrial controls with Modicon M580
 
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
A Practical Guide to Ensuring Business Continuity and High Performance in Hea...
 
Connected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoTConnected Services Study – Facility Managers Respond to IoT
Connected Services Study – Facility Managers Respond to IoT
 
Telemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories BriefingTelemecanqiue Cabling and Accessories Briefing
Telemecanqiue Cabling and Accessories Briefing
 
Telemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors BriefingTelemecanique Photoelectric Sensors Briefing
Telemecanique Photoelectric Sensors Briefing
 
Telemecanique Limit Switches Briefing
Telemecanique Limit Switches BriefingTelemecanique Limit Switches Briefing
Telemecanique Limit Switches Briefing
 

Recently uploaded

原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证
原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证
原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证jdkhjh
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Naveed Bangali
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachiamil baba kala jadu
 
black magic specialist amil baba pakistan no 1 Black magic contact number rea...
black magic specialist amil baba pakistan no 1 Black magic contact number rea...black magic specialist amil baba pakistan no 1 Black magic contact number rea...
black magic specialist amil baba pakistan no 1 Black magic contact number rea...Amil Baba Mangal Maseeh
 
A Costly Interruption: The Sermon On the Mount, pt. 2 - Blessed
A Costly Interruption: The Sermon On the Mount, pt. 2 - BlessedA Costly Interruption: The Sermon On the Mount, pt. 2 - Blessed
A Costly Interruption: The Sermon On the Mount, pt. 2 - BlessedVintage Church
 
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdf
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdfUnity is Strength 2024 Peace Haggadah_For Digital Viewing.pdf
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdfRebeccaSealfon
 
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝soniya singh
 
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptx
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptxThe Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptx
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptxNetwork Bible Fellowship
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Mangal Maseeh
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Naveed Bangali
 
Do You Think it is a Small Matter- David’s Men.pptx
Do You Think it is a Small Matter- David’s Men.pptxDo You Think it is a Small Matter- David’s Men.pptx
Do You Think it is a Small Matter- David’s Men.pptxRick Peterson
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Mangal Maseeh
 
Unity is Strength 2024 Peace Haggadah + Song List.pdf
Unity is Strength 2024 Peace Haggadah + Song List.pdfUnity is Strength 2024 Peace Haggadah + Song List.pdf
Unity is Strength 2024 Peace Haggadah + Song List.pdfRebeccaSealfon
 
Study of the Psalms Chapter 1 verse 1 - wanderean
Study of the Psalms Chapter 1 verse 1 - wandereanStudy of the Psalms Chapter 1 verse 1 - wanderean
Study of the Psalms Chapter 1 verse 1 - wandereanmaricelcanoynuay
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Naveed Bangali
 
Tremble song lyrics Powerpoint church music
Tremble song lyrics Powerpoint church musicTremble song lyrics Powerpoint church music
Tremble song lyrics Powerpoint church musicmaynjc
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Mangal Maseeh
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiAmil Baba Mangal Maseeh
 

Recently uploaded (20)

原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证
原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证
原版1:1复刻莫纳什大学毕业证Monash毕业证留信学历认证
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
black magic specialist amil baba pakistan no 1 Black magic contact number rea...
black magic specialist amil baba pakistan no 1 Black magic contact number rea...black magic specialist amil baba pakistan no 1 Black magic contact number rea...
black magic specialist amil baba pakistan no 1 Black magic contact number rea...
 
A Costly Interruption: The Sermon On the Mount, pt. 2 - Blessed
A Costly Interruption: The Sermon On the Mount, pt. 2 - BlessedA Costly Interruption: The Sermon On the Mount, pt. 2 - Blessed
A Costly Interruption: The Sermon On the Mount, pt. 2 - Blessed
 
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdf
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdfUnity is Strength 2024 Peace Haggadah_For Digital Viewing.pdf
Unity is Strength 2024 Peace Haggadah_For Digital Viewing.pdf
 
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Greater Kailash Delhi 💯Call Us 🔝8264348440🔝
 
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptx
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptxThe Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptx
The Chronological Life of Christ part 097 (Reality Check Luke 13 1-9).pptx
 
St. Louise de Marillac: Animator of the Confraternities of Charity
St. Louise de Marillac: Animator of the Confraternities of CharitySt. Louise de Marillac: Animator of the Confraternities of Charity
St. Louise de Marillac: Animator of the Confraternities of Charity
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
young Whatsapp Call Girls in Adarsh Nagar🔝 9953056974 🔝 escort service
young Whatsapp Call Girls in Adarsh Nagar🔝 9953056974 🔝 escort serviceyoung Whatsapp Call Girls in Adarsh Nagar🔝 9953056974 🔝 escort service
young Whatsapp Call Girls in Adarsh Nagar🔝 9953056974 🔝 escort service
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
Do You Think it is a Small Matter- David’s Men.pptx
Do You Think it is a Small Matter- David’s Men.pptxDo You Think it is a Small Matter- David’s Men.pptx
Do You Think it is a Small Matter- David’s Men.pptx
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
Unity is Strength 2024 Peace Haggadah + Song List.pdf
Unity is Strength 2024 Peace Haggadah + Song List.pdfUnity is Strength 2024 Peace Haggadah + Song List.pdf
Unity is Strength 2024 Peace Haggadah + Song List.pdf
 
Study of the Psalms Chapter 1 verse 1 - wanderean
Study of the Psalms Chapter 1 verse 1 - wandereanStudy of the Psalms Chapter 1 verse 1 - wanderean
Study of the Psalms Chapter 1 verse 1 - wanderean
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
Tremble song lyrics Powerpoint church music
Tremble song lyrics Powerpoint church musicTremble song lyrics Powerpoint church music
Tremble song lyrics Powerpoint church music
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in KarachiNo.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
No.1 Amil baba in Pakistan amil baba in Lahore amil baba in Karachi
 

Retrofit, build, or go cloud/colo? Choosing your best direction

  • 1. Jason Schafer, ATS Director, Technology & Operations Management Retrofit, Build, or Go Colo/Cloud: Choosing Your Best Direction
  • 2. Schneider Electric 2 Objectives 1. Review the evaluation criteria that goes into determining whether to upgrade, build new, or outsource a data center. 2. Understand the financial metrics and scenarios that go into determining the direction of the data center. 3. Identify the 10 strategic, non-financial factors that go into the decision. 4. Overview of tools available to help in the decision making process.
  • 3. Schneider Electric 3 • Upgrade • Build • Outsource Business Requirements IT Requirements Evaluation of Data Center Capacity Options The Tail of the Dog?
  • 4. Schneider Electric 4 The Tail of the Dog?
  • 5. Schneider Electric 5 Evaluation Criteria Upgrade, Build or Co-locate Cost Cash Flow Strategic Factors Process to evaluate these attributes is not always clear.
  • 6. Schneider Electric 6 Challenge for Customers ● Create a financial model to evaluate options ● Create a common financial metric to easily compare options ● Create a structured approach to evaluate strategic factors
  • 7. Schneider Electric 7 Financial Metrics ● Normalize costs to 10 year TCO per watt ● Utilize cumulative cash outlay to determine a break even point ● Provide insight into opex versus capex
  • 8. Schneider Electric 8 Using Modeling to Evaluate Options Benefits Drawbacks • Provides possibility of easy to use tools • Provides structure to decision making • Provides quick iterations to assist in planning • Not every situation matches model • Results as good as the data and assumptions
  • 9. Schneider Electric 9 10 Year TCO for Co-location We picked assumptions we view to be typical. Baseline • Determined to be $62 per watt • Rate increase assumed to be 5% per year • “Remote Hands” fee of $225 per hour, each rack takes 1 hour per month • 4kW per rack • 3% discount rate for TCO calculations Key Assumptions • Rack - $1,000 month/rack • Colo provides the rack at no additional cost to customer • Power - $800 month/rack • Bandwidth - $2,000 month
  • 10. Schneider Electric 10 Upgrade Options – 3 Basic Strategies Approach Description Assumptions Example Increase utilization of installed equipment Stranded capacity may exist that can be re- claimed Data center has sufficient power & cooling capacity, but cooling system is de- rated due to poor airflow management practices Blanking panels, brush strips, aisle containment Add capacity with new high density zones One or more rows of racks can be added to a larger, low-density data center to increase capacity Data center has sufficient switchgear & heat rejection capacity, and has available IT space High density zone(s) Add capacity with facility modules For larger capacity upgrades with available IT space, facility modules increase bulk capacity Data center is out of switchgear & heat rejection capacity, has no space in mechanical/electrical rooms, but has available IT space Power and/or cooling facility module(s) White Paper 153 Implementing Hot and Cold Air Containment in Existing Data Centers White Paper 134 Deploying High-Density Pods in a Low-Density Data Center White Paper 163 Containerized Power and Cooling Modules for Data Centers
  • 11. Schneider Electric 11 Upgrade Options – 3 Basic Strategies Approach Description Assumptions Example Increase utilization of installed equipment Stranded capacity may exist that can be re- claimed Data center has sufficient power & cooling capacity, but cooling system is de- rated due to poor airflow management practices Blanking panels, brush strips, aisle containment Add capacity with new high density zones One or more rows of racks can be added to a larger, low-density data center to increase capacity Data center has sufficient switchgear & heat rejection capacity, and has available IT space High density zone(s) Add capacity with facility modules For larger capacity upgrades with available IT space, facility modules increase bulk capacity Data center is out of switchgear & heat rejection capacity, has no space in mechanical/electrical rooms, but has available IT space Power and/or cooling facility module(s) Consider low- hanging fruit Consider going to higher density Consider adding facility capacity White Paper 153 Implementing Hot and Cold Air Containment in Existing Data Centers White Paper 134 Deploying High-Density Pods in a Low-Density Data Center White Paper 163 Containerized Power and Cooling Modules for Data Centers
  • 12. Schneider Electric 12 Scenario #1: Low-Hanging Fruit Model Break even in less than 1 year. ● Tier 3 1MW design load only utilized to 900 kW ● De-rating largely due to air mixing, etc. ● 10 year TCO - $17.00 per watt ● Blanking panels, brush strips, cold-aisle containment gain 100kW ● First cost of $2.10 per watt ● Co-lo 10 year TCO - $62.00 per watt
  • 13. Schneider Electric 13 Scenario #2: Implement Higher Density Break even in less than 2 years. ● Key Assumptions ● Add 40kW zone @ 4 kW per rack ● Pod includes 2N UPS, 2N Inrow cooling ● Discounted bandwidth cost due to existing bandwidth available ● PUE for data center of 1.35 ● 10 year TCO - $22.00 per watt ● First Cost to upgrade - $4.80 per watt ● Co-lo 10 year TCO - $62.00 per watt
  • 14. Schneider Electric 14 Scenario #3: Add to Facility Capacity Break even in about 2 years. ● Key Assumptions ● Add 500kW power and chilled water modules, 450kW of IT load ● Discounted bandwidth cost due to existing bandwidth available ● PUE of 1.35 ● 10 year TCO - $27.00 per watt ● First Cost to upgrade - $8.45 per watt ● Co-lo 10 year TCO - $62.00 per watt
  • 15. Schneider Electric 15 Scenario #4: Build New Facility Break even in about 3 ½ years ● Key Assumptions ● 1 MW capacity, $12/watt* ● 4kW per rack ● Lease - $5/sq. ft./month ● One battery refresh in Year 7 ● PUE of 1.33 ● Opex increases 3% per year ● Bandwidth - $5,000/month ● 10 year TCO - $42.00 per watt ● Co-lo 10 year TCO - $62.00 per watt * Schneider Electric Capitalized Cost Trade-off Tool, Tier 3, St. Louis, Air Chillers
  • 16. Schneider Electric 16 But is it really about the money? The 10 factors that may trump any financial discussion.
  • 17. Schneider Electric 17 „Soft‟ Issues to Consider Company Culture ● Sometimes the server huggers win Comfort with IT Equipment in Shared Space ● Does one colo have better security than another? ● Will my neighbors negatively impact my equipment? IT Accessibility to the Data Center ● Can my guys get there if they need to be there? Comfort with Dependence on Contract Terms ● If I call with a problem will anyone answer?
  • 18. Schneider Electric 18 Quantitative Issues to Consider Critical Facilities Expertise ● If you have no staff, the decision is easy ● Confidence in ability to operate a data center Regulatory Compliance ● HIPAA for example Life Expectancy ● Cloud computing wins for temporary use Deployment Timeframe ● If I need it next week, the decision is easy
  • 19. Schneider Electric 19 Financial Model Preferences Perceived size of capital investment ● Is $200k a lot or a little? ● Depends on relative size – relatively little for a company like Schneider Electric but for a start up… Cash flow model preference 0 1 2 3 4 5 6 7 8 9 10 Opex Capex Year 0 1 2 3 4 5 6 7 8 9 10 Opex Capex Year BUILD CO-LOCATION Lower TCO but higher capital expense model Higher TCO but smoother Opex model
  • 20. Schneider Electric 20 Strategic Factors Rating Guide Score Company Culture 1 = Strong company culture to keep direct control & avoid outsourcing any business function 10 = Company is open to outsourcing business functions Comfort with IT Equipment in Shared Space 1 = Data center must be in company owned space 10 = Data center can be in shared IT space IT Accessibility to the Data Center 1 = IT staff must be located in same facility as data center 10= IT staff can be remote to data center Comfort with Dependence on Contract Terms 1 = Low degree of comfort with contract dependence 10 = High degree of comfort with contract dependence Critical Facilities Expertise 1 = Strong critical facilities expertise exists within the company 10= Little to no critical facilities expertise exists within the company Regulatory Requirements 1 = Business has very specific regulatory compliance issues 10 = Business has no specific regulatory compliance issues Life Expectancy 1 = Data center will be utilized for >10 years 10 = Data center requirement is temporary Deployment Timeframe 1 = Business requirement for deployment in years 10 = Business requirement for deployment in weeks Perceived Size of Capital Investment 1 = Nominal capital expense is not viewed as significant to company 10 = Nominal capital expense is viewed as significant to company Cash Flow Model Preference 1 = Comfortable with spikes in capital expense 10= Prefer smooth predictable operating expenses TOTAL SCORE * * The total score will range from 10 to 100 based on the relative scales from 1 to 10 for each of the 10 considerations. Evaluation Scorecard These issues will sometimes dominate the decision.
  • 21. Schneider Electric 21 Summary Use model to evaluate financial options with a common language ● 10 year TCO is less for doing it yourself and is almost always cheaper than co-location ● Break even time and capital preservation may be more important than TCO ● Using the right financial metric is critical Cultural issues sometimes can dominate the conversation – create an objective way to discuss these ● Scorecard or weighted scorecard ● Are there Filtering Criteria? Use tools to help facilitate the conversation and allow for rapid evaluation of options * * *
  • 22. Schneider Electric 22 New TradeOff Tool™ ● Simple, automated tools to support specific planning decisions ● Models complex interactions of systems based on data and science ● One-screen, standardized user interface ● Instant output allows for rapid creation of “what if” scenarios Try it yourself: http://j.mp/sebvb
  • 23. Schneider Electric 23 Questions? Links for: Considerations for Owning versus Outsourcing Data Center Physical Infrastructure http://www.apc.com/whitepaper/?wp=171 Data Center Build vs. Colocation TCO Calculator http://www.apc.com/tool/?tt=13 -or- http://j.mp/sebvb